Text
.
July 31,1985 Docket No. 50-298 Mr. J. M. Pilant, Technical Staff Manager Nuclear Power Group Nebraska Public Power District Post Office Box 499 Columbus, Nebraska 68601
Dear Mr.- Pilant:
SUBJECT:
RECIRCULATION PIPING REPLACEMENT PROGRAM Re:
Cooper Nuclear Station On September 1, 1983, the Commission authorized restart of the Cooper Nuclear Station based upon certain Nebraska Public Power District (NPPD) connitments and approval of the recirculation piping repair activities and associated corrective actions. An Order was issued on September 1,1983 to confirm the NPPD commitments. After restart and full power operation for Cycle 9, Cooper was removed from service on September 16,1984 for a refueling and major. pipe replacement outage. As required by the above-referenced Order, plans for the Cooper pipe replacement activities were transmitted to the NRC on June 4, 1984. On July 12, 1984, a meeting between NPPD and the NRC was held at the NRC offices in Bethesda, Maryland to more fully discuss your proposed pipe replacement plans and the radiation protection program for the pipe replacement activities.
At our request, NPPD provided additional information on the pipe replacement by letter dated April 30, 1985. This additional information was sought by the staff in its. efforts to complete the review of Cooper against the guidelines of Generic Letter 84-11 " Inspections of BWR Stainless Steel l
Piping." In the June 4, 1984 and April 30, 1985 submittals, NPPD described the piping susceptible to intergranular stress corrosion cracking (IGSCC) in the recirculation system, reactor water cleanup system, residual heat removal system and core spray system that would be replaced with IGSCC-resistant material. NPPD also stated that the enhanced reactor coolant leakage limits and monitoring requirements delineated in the September 1, 1983 Order will continue to be in effect.
I 8508000420 850731 PDR ADOCK 05000298 p
Mr. J. M. Pilant Based on the NPPD'submittals cited above, we conclude that (1) NPPD has completed the actions required by the September 1,1983 Order, and (2) NPPD has complied with Generic Letter 84-11 and no augmented inspections need be performed before startup of Cycle 10 because all IGSCC-susceptible piping has been replaced.
Sincerely.
Original signed by/
Domenic B. Vassallo, Chief Operating Reactors Branch #2 Division of Licensing cc: See next page DISTRIBUTION N
NRC POR Local PDR ORB #2 Reading HThompson OELD SNorris ESylvester EJordan JPartlow BGrimes ACRS(10)
Gray File FCongel WJohnston DL:0RB#2 DL:0RB#2 DL:0RB#2 SNo8TITajs ESylvester DVassallo 07/.2/85 07/31/85 07/gl/85
4 i
Mr. J. M. Pilant Cooper Nuclear Station Nebraska Public Power District
~
CC:
Mr. G.
D'. Watson, General Counsel Nebraska Public Power District Post Office Box 499 Columbus, Nebraska 68601 Mr. Arthur C. Gehr, Attorney Snell & Wilmer 3100 Valley Center Phoenix, Arizona 85073 Cooper Nuclear Station ATTN: Mr. Paul Thomason, Division Manager of Nuclear Operations Post Office Box 98 Brownville, Nebraska 68321 Director Nebraska Dept. of Environmental Control Post Office Box 94877 State House Station tincoln, Nebraska 68509 Mr. William Siebert, Commissioner Nemaha County Board of Commissioners Nemaha County Courthouse Auburn, Nebraska 68305 Mr. Dennis DuBois U. S. Nuclear Regulatory Commission Resident Inspector Post Office Box 216 Brownville, Nebraska 68321 Robert D. Martin Regional Administrator Region IV Office U. S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 H. Ellis Simmons, Director Division of Radiological Health Department of Health 301 Centennial Mall, South Post Office Box 95007 Lincoln, Nebraska 68509
--