Concurs W/Meteorology & Effluent Treatment Branch 840821 Position Re Use of Snow & Ice Load in Design of Category I Structures.Applicant Confirmation That All Structures Can Withstand Load of 100 Psf Requested
ML20132C487
Person / Time
Site: Beaver Valley
Issue date: 11/05/1984
From: Lear G
Office of Nuclear Reactor Regulation
To: Knighton G
Office of Nuclear Reactor Regulation
Shared Package
ML19283C868 List: ... further results
References
FOIA-84-926 NUDOCS 8411160442
Download: ML20132C487 (1)


Text

._

[

\\

UNITED STATES

.a 8

NUCLEAR REGULATORY COMMISSION o

gg p

WASHINGTON, D. C. 20555 NOV 0 51984 MEMORANDUM FOR:

George W. Knighton, Chief Licensing Branch No. 3 Division of Licensing FROM:

George Lear, Chief Structural and Geotechnical Engineering Branch Division of Engineering

SUBJECT:

SNOW AND ICE LOAD - BEAVER VALLEY POWER STATION UNIT NO. 2 E. Markeetof Meteorology and Effluent Treatment Branch (METB) has expressed concerns that a snow and ice load of 100 PSF should be used in the design of Category I Structures at BV.2, whereas the applicant only used 72 PSF in the design. METB brought up this issue in the draft SER (February 24,1984),

and the applicant's response (July 30,1984) stated that 72 PSF for snow and ice was sufficient Finally, METB issued a memo to G. Kni (August 21,1984) disagreeing with the applicant's positions (ghton see enclosure for all the references). We concur with the METB's position and suggest that the applicant be requested to provide confirmation that all the Category I Structures at B.V.2 can safely withstand a snow and ice load of 100 PSF.

If requested, we will be able to discuss the re-evaluation criteria with the applicant.

In addition, we sent you our SER on July 26, 1984. To date, we have not received any responses from the applicant to the open and confirmatory items contained in the SER. However, in order to resolve these open items, we need prompt responses from the applicant. We suggest to have a meeting in Bethesda with the applicant to resolve the outstanding issues.

A=*-

George r, Chief Structural and Geotechnical Engineering Branch Division of Engineering

Enclosure:

As stated cc:

J. Knight I. Spickler E. Markee M. Ley L. Heller D. Jeng

< K. Le.u Qtf \\ \\ \\(pDL\\L l

.