Rev 0 to Structural Steel Analysis for Peach Bottom Generating Station:Calculation 97,Unit 2,3,Turbine Bldg El 116 Ft Janitor Room,Fire Area 116
ML20126J990
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 05/24/1985
From: Dewey J, Melly B
PROFESSIONAL LOSS CONTROL, INC.
To:
Shared Package
ML20126J788 List:
References
NUDOCS 8506100751
Download: ML20126J990 (5)


Text

-

Y=

ff 1%fessional Loss Control, Inc.

STRUCTURAL STEEL ANALYSIS

for PEACH BOTTOM GENERATING STATION Calculation No. 97 Unit 2,3 Turbine Building El. 116'-O" Janitor Room Fire Area 116 9

l J

4 i

Prepared by Date: _[~_2_M' E _

Reviewed by:

_D _

Revision: 0 8506100751 850606 PDR ADOCK 05000277 F

PDR 7922 West Chester Pike

  • Upper Darby, Pa. 19082 * (215) 853 1700

(

- - - ~ - - - - - - * - - - ' " - - ' ' - ~ " ' ' " ~ ~ - - ~ " ' ' ' - ~

~ ~ ~ " " ~ " '

e o

Professiond Loss Contml, Inc.

(

PEACH BOTTOM GENERATING STATION 1.

AREA _QgggRIEIIQN The area under consideration is the Janitor Room on the 116'-O" elevation of the Turbine Building (Fire Area 116).

The bounding walls are constructed of reinforced concrete with an average thickness of 1 ft.

The total surface area for heat transfer la 426 ft2 (see Attachment A for e sketch of the area under consideration).

2.

ggggggIIgLg_LgepINg There are no combustible liquida or cable traya located in this area.

9 3.

VgNIIb6IIgN_geg6MEIggg J

There is one door,which enters this area.

9egr_

__gige__

Legstien 124 3'-O"x 7'-O" West Wall 4-g8EEE_EE8EIEEE Since there are no exposed fixed combustibles in this area, no cases were examined for a general room fire.

1 m.

u

u,, c-,.t. i.

(

5.

Eg@M61@

No general room fire was postulated because of the lack of exposed fixed combustibles in the area.

There are no cable trays in this area-to present a localized heating exposure to the structural steel.

6.

-EEEE9I!_9E_IBeHEIENT_995H95IIHLE!

This area containa no exposed fixed combustibles.

The table below lista the maximum heat release rate for transient-combustibles for different fire durations which result in an area

(

temperature less than 11000F.

2

~

Eire _Duratigg 946_1hWfs 1 91hW1 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />" 10.5 416 2 houra 8.0 317 3 houra 6.5 257 The distance between the ficor and the deepeat beams supporting the ceiling is 16'-8 1/2".

The heat release rates required of floor level transient combustible fires to produce plume temperatures of 1100'F, 13OOOF and 15000F at the bottom

(

2 e

7,

.,. ~. -.

P o-ProfessionalI.ase Control, bee.

(

flange.of the beam have been datermined and tabulated below.

For 0

the temperatures greater than 1100 F the time required to heat the sizes of the beams supporting the ceiling have also been determined.

Ilms_te_1199 Elmial II 1 91hh1 W16_u_26 1100 7,257 1300 9,549 14 1500 12,042 10 l

9 f

e 3

L_

a hofresumal Lons Contmi, Inc.

b JAutroWd RtA N

u l

{

..h N

E

(

@..i

~

Unit 2,3' Turbine Building Elevation 116'-0" Janitor's Room

. Surface Area Calculation Walls 2

North wall (6' x 18')

108 ft 2 East wall (5' x 18')

90 ft 2 South wall (6' x 18')

108 ft 2 West wall (5' x 18')

90 ft 2

396 ft 30 ft Ceiling 2

Total Area for Heat Transfer 426 ft

(

ATTACHMENT A

\\