Rev 0 to Structural Steel Analysis for Peach Bottom Generating Station:Calculation 96,Unit 2,3,Turbine Bldg El 116 Ft Toilet Area,Fire Area 115
ML20126J976
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 05/24/1985
From: Dewey J, Melly B
PROFESSIONAL LOSS CONTROL, INC.
To:
Shared Package
ML20126J788 List:
References
NUDOCS 8506100748
Download: ML20126J976 (5)


Text

_ _-__-______ _

f hfessiorsal Loss Control, Inc.

STRUCTURAL STEEL ANALYSIS I

l' for PEACH BOTTOM GENERATING STATION Calculation No. 96 I

Unit.2,3 ~

]

. i Turbine Building El. 116'-O" l

T911et Aree l

Fire Area 115 W

Prepared by: ____ _ _

Date: __I'k_'_E(

Reviewed by: _ M __ Revision: 0 8506100748 850606 PDR ADOCK 05000277 F PDR 7922 West Chester Pike

  • Upper Darby, Pa.19082 * (215) 853-1700

,4 d4

' Pmfruiond Ian Contml. ine.

PEACH BOTTOM GENERATING STATION 1- eBE6_DE29BIEII9N The area under consideration is the Toilet Area on the 116'-O" elevation of the Turbine Building (Fire Area 115). The bounding walls are constructed of reinforced concrete with an average thickness of 1 ft. The total surface area for heat transfer la 1661 ft2 (see Attachment A for a sketch of the area under consideration).

2. 995aHEIIHLE_L9691gG -

-- There are no combustible liquida or cable traya located in this area. ,

+

3. vggIIbaIIgy_gegeggIggg -'

1 There is one door 'which enters this area. {

9eer_ __Elas__ besatien .

l 123 3'-0"x 7'-O" West Wall l

4. gAgg@_gXAMINgg Since there are no exposed fixed combustibles in this area, no cases were examined for a general room fire.

1 l

_1

u

. .e

  • r r .ua u.. c a,a.s

(..

RgggLTg 5.

No general room fire was postulated because of the lack of

-exposed fixed combustibles in the area.

There are no cable-trays in this area to present a localized heating exposure to the structural steel.

6- EEEE9I!_9E_IBeHEIEHT_995aMEIIBLE!

~

This area contains no exposed fixed combustiblea. The table below lists the maximum heat release rate for transient

- combustibles for different fire durations which result in an area

(~ temperature less than 11000F. ,

Eirg_guratign gla_1ggtm 21 91hW1 l' hour' 10.5 1,620 2 houra -

8.0 1,235 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> 6.5 1,003 The distance between the floor and the deepeat beams supporting the ceiling is 16'-8 1/2".- The heat release rates required of floor level transient combustible fires to produce plume temperatures of-11000F, 13OOOF and 15000F at the bottom 2

, - , - .,...--e,g_ , . , .-,-_,n.,_g., ,,..n_.-..,,_e., ,. , .,, , e -v ,

v- , - - - , - - - . , , , - - . , , , . . _ . .

  • Profmionalloes Omtrol,ine.

'(T-flange of'the beam have been determined and tabulated below. For the temperatures. greater than 11000 F the time required to heat the sizes of the beams supporting the ceiling have also been determined.

Ilme_t9_1199 Elmini Il 1 91hW1 W1E_u_29 _W1E_a_2E_

1100 7,257 -

g

^

1300 9,549 14 38 1500 12,042 10 26

~

a f

A 3

_ - _ ~ _ _ _ - _ _ _ _ _ _ _ _ . _ _ _

s-Pmfensionsi Lose Castml. Inc.

~

( N W

g TotLET

.)  %.1,

(.

. ,) ,

(' .

Unit 2,3 Turbine Building Elevation 116'-0" Toilet Area Surface Area Calculation

. Walls North wall (30' x 18') 540 ft 2 East wall (9.3' x 18')

South wall (30' x 18') 167ftf 540 ft West wall (9.3' x 18') 167 ft 2 2

1,414 ft Ceiling (9.3' x 30') - (5.3' x 6) 247 ft 2 Total Area for Heat Transfer 2 1,661 ft k

ATTACHMENT A