STRUCTURAL STEEL ANALYSIS for PEACH BOTTOM GENERATING STATION Calculation No. 94 Unit 2,3 Turbine Building El. 116'-O" Counting Room Fire Area 78E Prepared byt Date: _8" (Y_~_8_(_
Reviewed by:
h Revision: O kl A
7 1922 West Chester Pike
- Upper Darby, Pa.19082 e (216) 853 1700
m-A Pmfruional tan Contml Inc.
(
PEACH BOTTOM GENERATING STATION 1-eBE6_QEggBIEIlgM The area under consideration is the Counting Room on the 116'-O" elevation of the Turbine Building (Fire Area 78E).
The bounding walls are constructed of reinforced concrete with an average thickness of 1 ft.
The total surface area for heat transfer la 1,242 ft2 (see Attachment A for a sketch of the area under consideration).
2.
gggggSIlg(E_(Q6plHQ There are no combustible liquida or cable traya located in this area.
1 3.
MEHII(6IlON_E686HEIEgg
/
There is one door khich enters this area.
DeeE_
__Hise__
Leestien 119 3'-O"x7'-O" East Wall
~
4.
C6gEg_gX6HIHgg Since there are no exposed fixed combustibles in this area, no cases were examined for a general room fire.
1
s e
Pmfruionalloss ontml.Inc.
15.
Eg@ybIf No general room fire was postulated because of the lack of exposed fixed combustibles in the area.
There are no cable traya in this area to preacnt a localized heating exposure to the structural steel.
6.
EEEE9I!_9E_IBAHEIEMI_995aEDIIDLE!
This area contains no exposed fixed combustibles.
The table below lista the maximum heat release rate for transient
-combustibles for different fire durations which result in an area 0
temperature less than 1100 F.
2 Eire _gurntien 926_1hWlm 1 91hW1 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 10.5 1212 2 hourd 8.0 923 3 houra 6.5 750 The distance between the floor and the deepeat beams supporting the ceiling in 16*-8 1/2".
The heat release rates required of floor level transient combustible fires to produce plume 0
temperatures of 1100 F, 13OOO.e and 1500 F at the bottom 0
flange of the beam have been determined and tabulated below.
For the temperatures greater than 1100 F the time 2
- em_,
.s hofeesional1.aen Courel,ine.
(-
required to heat the sizes of the beams supporting the ceiling have also been determined.
Ilme_te_1199 Elmin!
~
Il 1 91BW1 W16_x_99_
'1100 7,257 1300 9,549 38 1500 12,042 26 t
4 0
i 3
/
k
//
t, Profmsonal Lane Control. Inc.
~
N c
W g
T.
C.00 NTIN G ROOM "I
3 r-(
Q..i Unit 2,3 Turbine Building, Elevation 116'-0" Counting Room Surface Area Calculation Walls 2
North wall (11' x 18')
198 ft 2 East wall 18' x 18')
324 ft2 South wall 11' x 18')
198 ft2 West wall 18' x 18')
324 ft j
2 1,044 ft 2
Ceiling (11' x 18')
198 ft 2
Total Surface Area Calculation 1,242 ft
(
)
ATTACHMENT A