Forwards Applicant Final Deficiency Rept Re Butt Splices in Electrical Conductors.Subj Deficiency Was Addressed at May 1984 Prehearing Conference.Related Correspondence
ML20097E415
Person / Time
Site: Byron  
Issue date: 09/14/1984
From: Gibbs M
COMMONWEALTH EDISON CO., ISHAM, LINCOLN & BEALE
To: Callihan A, Cole R, Smith I
Atomic Safety and Licensing Board Panel
References
OL, NUDOCS 8409180187
Download: ML20097E415 (69)


Text

-

RQu ~

3%

s.,

ISHAM, LINCOLN & BEALE COUNSELORS AT LAW THREE FIRST NATIONAL PLAZA

,84 SEP 17 P2:54 cacAso.ituNo$.0 02 TELEPHONE 312 558-7500 EDVuARD 5 ISHAM. 1872 1902 1120 NE AVENU.N W G EA 1

'A u -gty sunt:40 000Xi. T M & $EPv M *^8"'"gsy'" '

3 RANCH September 14, 1984 Ivan W. Smith, Chairman Dr. A. Dixon Callihan Administrative Judge Administrative Judge Atomic Safety and Licensing Board Union Carbide Corporation U.S. Nuclear Regulatory Com-P.O. Box Y mission' Oak Ridge, Tennessee 37830 Washington, D.C.

20555 Dr. Richard F. Cole Administrative Judge Atomic Safety and Licensing Board U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Re:

In the matter of Commonwealth Edison Company (Byron Nuclear Power Station, Units 1 and 2) Docket Nos. 50-454 O L_.

and 50-455 O L

Dear Administrative Judges:

Enclosed is Commonwealth Edison Company's final report of a deficiency considered reportable pursuant to 10 C.F.R.

S 50.55 (e) regarding butt splices in electrical conductors at Byron Station.

This subject was addressed at ti e prehearing conference last May.

h Very truly yours, f lOAlm bp Martha E. Gibbs MEG:mg l

Encl.

l cc:

Service List l

~

ho O

\\.O a

4

N Commonw cith Edison

/

) one First Nation 21 Clara Chicago. Ilhno's I

~;

k T J Address Reply to Post Office Box 767

\\

/ Chicago, Illinois 60690 August 28, 1984 Mr. James G. Keppler Regional Administrator U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137

Subject:

Byron Generating Station Units 1 and 2 Electrical Conductor Butt Splices NRC Docket Nos. 50-454 and 50-455 References (a):

May 17, 1984 letter from D. L. Farrar to J. G. Keppler.

(b): June 12, 1984 letter from T. R. Tramm to J. G. Keppler.

(c): July 2, 1984 letter from T. R. Tramm to J. G. Keppler.

Dear Mr. Keppler:

This letter provides the final report of a deficiency considered reportable pursuant to 10 CFR 50.55(e) regarding butt splices in electrical conductors at Byron station. For tracking purposes, this deficiency is numbered 84-03.

In reference (c), we provided the results of the electrical butt splice reinpection program which was described in reference (a). At that point in time the inspections had been completed but the safety significance of the minor splice installation discrepancies had not been established through engineering analysis. Those analyses are now complete.

i A total of 82 butt splices were reviewed. In reference (c) we indicated that only 65 discrepant splices were found. In several cases, however, the cut-out section of the deficient butt splice did not contain enough of the conductor to positively identify the color code. Wherever this occurred, all of the conductors in the cable were analyzed.

i Attachment A to this letter contains the documentation on the engineering review of each conductor.

i

F

,; g J. G. Keppler August 28, 1984 i

1

)

In 73 cases it was found that an open circuit at the splice would not result in a loss of control that would defeat the safety function of the associated equipment. In nine cases it was determined that the butt splice failure would defeat the safety function of the associated equipment. In each of those nine cases, however, indication regarding the status of the equipment is available and the operator can take manual actions to accomplish the safety function through manipulation of switches or valves.

Please address any further questions you may have regarding this matter to this office.

Very truly yours, 3gfgw- - - _ -

T. R. Tramm Nuclear Licensing Administrator 1m 9120N l

,w

,m,

~

-e-

.r---,------

-r,-.

-m--

v--

O ATTACHNENT A Safety Impact of Butt Splice Failure Cables Reviewed:

1APO47 ISI142 1RH110 1RH029 ISX286 IVA228 1RH034 1RH010 1RH062 2SX013 ISI495 1MS543 IVA073 1MS286 10G157 1MS276 ISIO63 IFW441 1SX474 1FW122 ISX280 1FP039 1RC241 ISX172 IVQ097 1RC239 IVQ087 1AP137 1RC091 10G158 1S1152 ISIl06 1SX204 1EF038 IVA003 1CCO26 IVC 387 1CC008 IVQ136 2AP052 2AP137 1MS528 2DC014 1MS276 ISI149 15I143 1AP137 1RH062 1CC008 ISI143 9120N

n SARGENTOLUNDY g

E N GIN E E R@

CMsCAGO Byron Butt Splice Inspection Report Disposition Cable Number:

lAPO47 Conductor:

  1. 4 Green Function:

.The' green wire of cable 1APO47 is in the circuit for the' System Auxiliary Transformer (SAT) feed to 4kV bus 142 overcurrent alarm which annunciates in the main control room.

Safety Impact:

None, alarm only.

The feed breaker will still perform its protective function of tripping on overcurrent.

Information breaker Etatus (open, closed, tripped) is provided in the control room via position indicating lights above the breaker control switch.

References:

Schematic 6/20E-1-4030AP32, Rev. N Drawings:

W/D 6/20E-1-4613S, Rev. S

4 SARGENTOLUNDY ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

2AP052

. Conductor:

Red Function:

The red conductor of cable 2AP052 is in the circuit for the SAT feed to 4kV Bus 241 overcurrent alarm in the main control room.

A failure of the butt splice i

would disable the alarm.

l Safety Impcct:

None.

The breaker will still perform its pro-tective function of tripping on overcurrent.

Information on breaker status will be provided in the main control room by the position indicating lights (open, tripped, close) above the breaker control switch.

References:

6/20E-2-4611, Rev. P 6/20E-2-4030AP23, Rev. M

l c

SARGENT & LUNDY ENGINEERS CMICACC j

Byron Butt Splice Inspection Report Disposition Cable Number:

1AP137 Conductor:

White Function:

The white conductor of. cable 1AP137 is in the auto-trip alarm circuit for the manually operated feed breaker in 480V ESF unit substation 1322 to 460V essential service water cooling tower motor control center 132Zl.

This auto-trip alarm is activated by an overcurrent trip switch in the feed breaker assembly.

The alarm is in the main control room.

Safety Impact:

None.

The breaker will perform its protective function of tripping on overcurrent.

Loss of the motor control center can be determined by other indication in the control room (i.e., loss of position indication and alarms associated with services fed from the motor control center).

In addition, close/ trip indication for the feed breaker is provided locally at the 480V unit substation.

References:

6/20E-1-4156A, Rev. M 6/20E-1-4156C, Rev. T 6E-1-4030AP76, Rev. B

@ARGENTa LUNDY ENGINEERS C HIC ASO Byron Butt Splice Inspection Report Disposition Cable Number:

2AP137 Conductor:

Green Function:

The green conductor of cable 2AP137 is a connection in the auto trip alarm circuit of ACB #2425X (4kV feed to 480V ESF auxiliary transformer 232X).

A failure of the butt splice will prevent an initiation of this alarm, s

Safety Impact:

None.

Loss of alarm function only.

The breaker

(#2425X) will still perform its protective function.

The breaker trip position is indicated in the main control room by indicating lights above the breaker control switch.

In addition, if a loss of power to the 480V unit substation should occur, equipment fed from this substation will cause other alarms to annunciate in the main control room.

References:

Equipment No. 2PA32J 6/20E-2-4156A, Rev. H 6/20E-2-4030AP36, Rev. D Wire code - (CB9)

'\\

~

SARGENTQ LUNDY E N GIN E E R S C H lC A G3 Byron Butt Splice Inspection Report Disposition Cable Number:

ICC008

. Conductor:

White-Black' Function:

The white-black conductor of cable ICC008 is in the auto-start alarm of the component cooling pump 1A (lCC0lPA).

A failure of the butt splice will prevent the initiation of the auto-start alarm.

Saf ety. Impact:

None.

Control circuit performing safety-related function is. unaffected, Operator can find the position of the breaker from indicating lights above the control switch.

A

References:

6/20E-1-4155B, Rev. T 6/20E-1-4030CC01, Rev. L

SARGENT & LUNDY ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1CCO26 Conductor:

Red Function:

The red conductor of cable ICC026 is in the circuit for the trip alarm for the common component cooling (OCC0lP) in the main control roor.

A failure of pump the butt splice would disable this alarm.

Safety Impact:

None.

Pump breaker position status is a,lso provided in the main control room by the indicating lights (open, tripped, close) above the pump control switch.

References:

6/20E-1-4054G, Rev. S 6/20E-0-4030CC01, Rev. K

1 o

SARGENT OLUNDY ENGINEERO CHICt.C3 Byron Butt Splice Inspection Report Disposition Cable Number: 2DC014 Conductor: Orange-Black, Blue-Black Function:

The orange-black conductor of cable 2DC014 is connected in the under voltage alarm circuit of DC bus 212.

The failure of the butt splice will prevent actuation of this alarm.

The blue-black conductor of cable 2DC01A is connected in the alarm circuit for battery charger breaker to bus 212 tripped.

The failure of the butt splice will prevent the actuation of this alarm.

Safety Impact: None.

Failure in these circuits will only impact alarm functions.

If the undervoltage alarm does fail, a bus voltmeter is provided in the control room to allow monitoring of the bus voltage.

If the battery charger feed breaker trip alarm fails,

'the tripping of this breaker will also initiate a charger fail alarm in the control room.

References:

6/20E-2-4156A, Rev. H, 4251A, Rev. N, 4251B, Rev. J 6/20E-2-4030DC02, Rev. E 6/20E-2-4030DC08, Rev. F

SARGENT & LUNDY E N GlN E E RS CHIC AGO Byron Butt Splice Inspection Report Disposition Cable Number: lEF038 Conductor:

Black Function:

The black conductor of cable 1EF038 is in the reset leg of the test lockout relay in the ESF sequencing and actuation cabinet Train A.

This conductor is specifically in a circuit that resets the test lockout relay if the SAT feed breaker to 4kV ESF Bus 141 trips.

A failure of the butt splice will prevent this resetting of the test lockout relay.

Safety Impact:

Minimal.

For a loss of offsite power concurrent with periodic testing of the sequencing panel, failure to reset the test lockout relay will prevent sequencing of the associated safety-related loads.

Before beginning testing of the sequencing cabinet surveillance procedures require that the shift engineer be notified and that authorization to proceed be obthined.

Performance of this testing also requires that the cabinet door be opened which is alarmed in the Main Control Room.

Should a loss of offsite power occur during the testing, each of the ESF loads could be manually started from the Control Room.

Operating procedures require the operator to verify that all ESF loads have auto-started following a loss of offsite power, and if not manually start the load.

This circuit was also tested and found functional during pre-op testing.

Due to the renote possibility of a loss of offsite power occuring concurrently with testing of the ESF sequencing cabinet, administrative controls with regard to the testing, and the ability to manually start the loads from the Control Room, failure of this butt splice was determined to have a minimal safety impact.

References:

6/20E-1-4122C, Rev. G 6/20E-1-4030EF01, Rev. J

CARGENTOLUNDY E N GINE ERO C H 6C ASO Byron Butt Splice Inspection Report Disposition Cable Number:

1FP039 Ccnductor:

White Function:

The white conductor of cable 1FP039 is the negative return path for containment isolation contact monitoring lights.

A failure of the butt splice will disable both white and green lights that monitor contacts K607 and K818 used in control of the fire protection containment isolation valve.

Safety Impact:

None.

Loss of indication only.

References:

6/20E-1-4120B, Rev. F 6/20E-1-4030FP03, Rev. E

@ARGENTQ LUNDY ENGINEER 0 C MICASO Byron Butt Splice Inspection Report Disposition Cable Number:

1FW122 Conductor:

  1. 1 - Black Function:

The black wire of 1FW122 is used to connect isolation signals from the Protection System Cabinet Train A (IPA 093) to auxiliary feedwater isolation relays.

Contacts of these " isolation" relays are used to auto-matically close various Division 11 feedwater isolation valves.

The affected valves are 1FWO43A, B, C, D,

1FW540, 1FW510A, 1FW520, 1FW520A, 1FW530, 1FW530A, 1FW540A,
1FWO35A, B,

C, D,

1FWO34A, B,

C, D,

1FWOO9A, B,

C, D

and 1FWO39A, B, C, D.

Valve's 1FM510, 1FW510A, 1FW520, 1FW520A, 1FW530, 1FW530A, 1FW540, 1FW540A, and

1FWO34A, B, C, D do not perform a safety function.

Valves 1FWOO9A, B,

C, D,

1FWO35A, B,

C, D,

1FWO39A, B,

C, D and 1FWO43A, B, C, and D do perform a safety function The operator for each of these valves is provided with redundant solenoids (Solenoids "A"

& "B")

interlocked with ESF actuation signals from redundant trains.

For each valve which performs a safety function, the control circuit has a control switch on the main control board with position station indicating lights.

Safety Impact:

Minimal.

Butt splice failure will only cause loss of one train's ESF actuation signal to the valve operator.

The manual closing circuit,in this control train is unaffected by this failure.

Position indicating lights and control switches are provided in the control room to allow the operator to manually close these valves.

In addition, pre-op testing and periodic testing of the ESF actuation signals would detect any failure of the butt splice.

The redundant ESF actuation signal to the redundant solenoid is unaffected by this failure.

References:

6/20E-1-4030FW46, Rev. D 6/20E-1-4256C, Rev. R 6/20E-1-4114J, Rev. H M-36, Sheet 1

SARGENT Q LUNDY ENGlNEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1FW441 Conductor: #1 - Black Function: -The black wire of 1FU441 is used tc connect an ESF actuation signal into the circuitry for Solenoid A of steam generator feedwater isolation bypass isolation valve (lFWO43A).

Solenoid A is normally energized.

Upon receipt of an actuation signal the solenoid de-energizes which closes the valve.

Failure of this wire will de-energize the solenoid and cause valve to close (i.e.,

go to its safe position).

In addition, there is a Solenoid B interlocked with the ESF actuation signal from the redundant train which will also close the valve.

Safety Impact:

None.

Valve 1FWO43A is normally closed and the ESF actuation signal is merely a confirmatory signal.

Failure of the butt splice (i.e., circuit opening) will also simulate the actuation signal and place the valve in its safe position.

In addition, a redundant solenoid interlocked with'an ESF actuation signal from the redundant train is provided in the valve circuit.

References:

6/20E-1-4030FW50 6/20E-1-4256C 6/20E-1-4148D

l SARGENT & LUNDY ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1FW441 Conductor: #2 - White Function:

The white wire of 1FW441 is used to connect an ESF actuation signal into the circuitry for Solenoid A of steam generator feedwater isolation bypass isolation valve (lFWO43A).

Solenoid A is normally energized.

Upon an actuation signal the valve will close.

Failure

~

of this wire will de-energize circuit and cause valve to close (go in its safety direction).

In addition, there is a Solenoid B powered from opposite divisional train, which is provided for redundancy, to close valve.

Safety Impact:

None.

Valve 1FWO43A is normally closed and the ESF actuation signal is merely a confirmatory

/

signal.

Failure of the butt splice (i.e., circuit opening) will also simulate the actuation signal and place the valve in its safe position.

In addition, a redundant solenoid interlocked with'an ESF actuation signal from the redundant train is provided in the valve circuit.

References:

6/20E-1-4030FW50 6/20E-1-4256C 6/20E-1-4148D

y 4

SARGENT G LUNDY E N GIN E E R S CHIC AGO Byron Butt Splice Inspection Report Disposition Cable Number:

1FW441 Conductor: #6 - Blue Function:

The blue wire of 1FW441 is used to connect an ESF actuation signal into'the circuicry for Solenoid A of steam generator feedwater isciation bypass isolation valve '(lFWO43C).

Solenoid A is normally energized.

Upon an actuation signal the valve will close.

Failure of this wire will de-energize circuit and cause valve to close (go in its safety direction).

In addition, there is a Solenoid B powered from opposite divisional train, which is provided for redundancy, to close valve.

Safety Impact:.

None.

Valve 1FWO43C is normally closed and the s

ESF actuation signal is merely a' confirmatory signal.

Failure of the butt splice (i.e., circuit opening) will also simulate the actuation signal and

~

place the valve in its safe position.

In addition, a redundant solenoid interlocked with an ESF actuation s#gnal from the redundant train is provided in the valve circuit.

References:

6/20E-1-4030FW50 6/20E-1-4256C 6/20E-1-4148D

~

t'

.I SARGENT & LUNDY ENGINEERS CHicAco Byron Butt Splice Inspection Report Disposition Cable Number:

1FW441 Conductor: #7 - White-Black Function:

The white-black wire of 1FW441 is used to connect an ESF actuation signal into the circuitry for Solenoid A of steam generator feedwater isolation bypass isolation valve (1FWO43D).

Solenoid ~A is normally energized.

Upon an actuation signal the valve will close.

Failure of this wire will de-energize circuit and cause valve to close (go in its safety direction).

In addition, there is a Solenoid B powered from opposite divisional train, which is provided for redundancy, to close valve.

Safety Impact:

None.

Valve 1FWO43D is normally closed and the ESF actuation signal is merely a confirmatory signal.

Failure of the butt splice (i.e.,

circuit opening) will also simulate the actuation signal and place the valve in its safe position.

In addition, a redundant solenoid interlocked with an ESF actuation signal from the redundant train is provided in the valve circuit.

References:

6/20E-1-4030FWSO 6/20E-1-4256C 6/20E-1-4]48D i

-y,--y,,

-,.,,,,____,..m-

.,-,,-_.-y,,,,--%

,,m_____

,___,m,._,-,,n,...-.--~-

1 CARGENTQLUNDY E N GIN E EQO CMIC ASO Byron Butt Splice Inspection Report Disposition Cable Number:

.lMS276 Conductor:

Blue & White-Black Function:

The blue and white-black conductors of cable 1MS276 connect the test control switch in Main Control Board 1PM06J to Panel'lPLO5J, for testing of the main steam isolation valve 1A.

Failure of one or both of the butt splices will disable the test function.

Safety Impact:.

None.

Control circuits permitting manual or a~tomatic closing (i.e. safety functi'on) of the valve are unaffected.

In addition, there is a redundant test circuit in the second control train actuated simultaneously from the same control switch, therefore, valve can be tested through second train

References:

6/20E-1-4089K, Rev. R 6/20E-1-4030MS01, Rev. J

I

@ARGENTOLUNDY ENGINEERS CHICAGO 1

Byron Butt Splice Inspection Report Disposition Cable Number:

1MS286 Conductor:

Red Function:

The red conductor of cable 1MS286 is in the auto closing circuit of main steam' isolation valve 1B (IMS001B).

A failure of the butt splice will prevent energi ation of solenoid "A" to close the valve on a safety actuation signal from Relay K616.

The test circuit for K616 will not operate also.

Safety Impact: Minimal.

Position indicating lights and a control switch are provided in the control room.

Upon failure to auto-close, the operator could manually close the valve.

In addition, the valve operator is furnished with redundant controls.

Failure of this butt splice does not affect the redundant auto-close circuit.

This butt splice was also tested and found to be functional during system pre-op testing.

The periodic testing of the ESP actuation signals would also detect failure of this butt splice.

References:

6/20E-1-4089K, Rev. R 6/20E-1-4030MS02, Rev. J A

SARGENTuLUND

+ - -

E N c I N E E R 15 CHICAGO lV I

Byron Butt Splice 1

Inspection Report Discositi,on J:3., /[

N 9

f!,siCd,ble Number

1MS$28

_ '2:

/Cbductor:

Red-Black,.

('

e, i

punction:

The redLblac8' conductor of cable IMS528 is in the manual clo'siSg' circuit,of the main steam isolation valve IMS001D:from Main Control Board. LPM 06J.

A failu o of the butt splice will prevent energization of solenoid "Al".in'the Division 12 circuit to close the' valve.j

,c j

W 4

i 3.L '

\\

0-S i

s

.i 3

Safety Impact: None.

The valvelihas two redundant control circuits.

The control switch "CS2" at 1PM06J simultaneously actuates the closing solenoids ~in both control

{

trains.

Failure of this butt' splice only affects

< ), /

the Division 12 manual closing circuit.

The

'y Division 11 closing circuit is unaffected by this t

.' -i failure.

The automatic closure of this valve on

' ifl[

a low steamline pressure or hi-hi containment pressure g

signal (i.e., the valve's safety function) is also unaffected by thic failure.

> i.

p.

t, th 4<

.c

References:

6/20E-1-4d54L, Rev. S 6/20E-1-4Gb0hSO4, Rev. J

~

  • g h

s

i'

+

SARGENTG LUNDY ENGINEERS C HIC AGO Byron Butt Splice Inspection Report Disposition Cable Number:

1MS543 Conductor:

Red & Green Function:

The red and green conductors of cable IMS543 are in an auxiliary relay circuit which energizes on a contain-ment phase A isolation signal.

Contacts from this relay close the letdown orifice isolation valves ICV 8149A, B& C.

Safety Impact:

None.

These valves are non-safety related and do not perform a containment isolation function.

The isolation function is performed by valves 1CV8152 &

1CV8160.

The containment phase A isolation signal interlock with these valves was added to prevent the letdown orifice common outlet header isolation relief valve 1CV8117 from operating.

References:

6/20E-1-4150C, Rev. M 6/20E-1-4030EF100, Rev. B

't SARGENTGLUNDY ENGINEEMS CMICA10 Byron Butt Splice Inspection Report Disposition Cable Number:

lyG157 Conductor:

  1. 4 Green Function:

The green wire of cable lpg 157 is used to connect a limit switch of valve 1%G079 (H2 Recombiner Discharge Containment Isolation valve) into the valve control circuit to light a green (valve closed) status lamp.

A failure of the butt splice would prevent the " closed" indication light from illuminating on the main control panel.

Safety Impact:

No safety impact, indication only.

References:

Schematic 6/20E-1-40300G09, Rev. F Drawings:

W/D 6/20E-1-4683C, Rev. J e

i CARGENTQ LUNDY E N G1N E E R S cwicaco Byron Butt Splice Inspection Report Disposition Cable Number:

10G158 Conductor:

Red & Green Function:

The red and green conductors of cable lpg 158 are in the indication circuit of hydrogen recombiner containment isolation valve lpg 079 A failure of the butt splice for the red conductor will disable the "open" indicating light.

A failure of the butt splice for the green conductor will disable the "close" indicating light.

-Safety Impact:

None.

Loss of indication only.

The valve's opening and closing circuits, including automatic operation on containment isolation signal, are unaffected.

References:

6/20E-1-4683C, Rev. J l

6/20E-1-4330%G09, Rev. F

{

l i

l SARGENTG LUNDY E N GIN E E RS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1RC091 Conductor:. Black, White, Red, Orange, Blue, Red-Black, Green-Black, Orange-Black-and Blue-Black Two of the splices passed reinspection but color codes

.could not be identified; therefore all splices were analyzed.

I 4

Function:

Control, indication and limit switch interlocks of reactor coolant loop 1A - hot leg stop value 1RC8001A.

The function of the circuit containing each butt splice is discussed below:

1.

The orange-black and red-black conductors interlock a close limit switch contact of valve IRC8001A with a loop isolation /b3ock safety injection signal input to the reactor projection system, a loop 1A bypass relief line low flow alarm, and an indicating light (relay K104) and one of the permissives in a reactor coolant pump trip circuit.

2.

The white and black conductors interlock an open limit switch contact of valve IRC8001A with a permissive in the cold leg.stop valve open circuit and a reactor coolant pump permissive light.

3.

The red conductor energizes the open indicating light on the main control board.

~

4.

The black conductor energizes the control circuit for valve IRC8001A.

5.

The blue-black and green-black conductors energize the heater in the valve's motor operator.

6.

The orange conductor energizes the opening circuit for valve'lRC8001A.

Safety Impact:

None.

The hot leg loop stop valve IRC8001A is normally open with power to the motor operator " locked out".

Closure of the stop valve is only allowed with the unit in a shutdown mode.

The valve therefore has no safety function and failure of the butt splices has no safety impact.

SARGENT & LUNDY

-e-E N GlN E E RO c..

CHlCAGO Byron Butt Splice Inspection Report Disposition Cable Number:~

1RC091 (Cont'd)

References:

Equipment No. ISIO3E 6/20E-1-4326B, Rev, M 6/20E-1-4030RC07,.Rev. J 6/20E-1-4030RC22, Rev. J Uire codes:

Black (8001AX1), k'hite (105A)

Red - ( 8 001 AR), Orange (8001A01)

Blue (004A), Red-Black (106A)

Green-Black (HTRY),

Blue-Black (HTRX)-

Oranga-Black (004A)

Technical Specification 3/4.4.1 NRC Safety Evaluation Report - Byron Station Section 7.6.2.6

+

4 j-

?

e

--*.,,....w ys-w..,,.+..

.,-,..e-y.m w w-

,n.<n.-,-

,--r,

.r_..e e--,.--,-w

-y w ww.

+,.---.

-_,w+--e e,-----ry

U e

CARGENTQ LUNDY E N GlN E E R9 CMICAco Byron Butt Splice Inspection Report Disposition Cable Number:

1RC241 Conductor:

Red & Green Function:

The red and green conductors of cable IRC241 are connections in an alarm circuit for " Loop 1C Bypass Relief Line Flow Low".

A break in this circuit will prevent initiation of this alarm.

The alarm is initiated by flow indicating switch IFIS-0438A in series with permissive interlocks from valves 1RC8001C and IRC8002C, Safety Impact:

None.

The valve permissives in this alarm circuit are such that valve IRC001C must be open and valve IRC002C must be closed to initiate the alarm.

These valves are the loop hot and cold leg stop valves.

Closure of the stop valves is only allowed with the unit in a shutdown mode.

Both these valves are normally in the "open" position with power " locked-out" to the motor actuator.

The bypass line is only opened when a reactor coolant loop is isolated.

Therefore, this alarm is normally disabled.

In addition, a redundant instrument (lFIS-0438B) provides a low flow input to the same annunciator window in the main control room.

References:

Equipment No. IPA 15J 6/20E-1-4126D, Re. E C/20E-1-4030RC24, Rev. J Mire code - Red (CAS), Green (0074A)

Technical Specification 3/4.4.1

SARGENT & LUNDY ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1RC329 Conductor:

White Function:

The white conductor of cable IRC329 is in the circuit for the loop 1A bypass relief line low flow alarm in the main control room.

This conductor is in the circuit initiated by flow indicating switch 1FIS-418A in series with permissive interlocks from valves 1RC8001A and 1RC8002A.

Safety Impact:

None.

Loss of alarm only.

The valve permissives in the alarm circuit are such that valve IRC8001A must be open and valve IRC8002A must be closed.

Both valves are normally in the open position with power " locked-out" to the motor actuator; therefore, disabling the alarm.

The bypass line is only opened (i.e., valve IRC8002A closed) when a reactor coolant loop is isolated.

In addition, a redundant instrument (1FIS-418B) provides a low flow input to the same annunciator window in the main control room.

References:

6/20E-1-4155B, Rev. T 6/20E-1-4030RC22, Rev. J M-2060, Sheet 4, Rev. K

@ARGENTOLUNDY EN G IN E E RS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1RH010 Conductor:

Blue Function:

The blue conductor of the cable IRH010 is in the auto-start alarm circuit of the residual heat removal pump 1B (1RE0lPB).

A failure of the butt splice will prevent initiation of the auto-start alarm.

Safety Impact:

Mone.

Control circuit performing safety-related function is unaffected.

Operator can find the position of the breaker from indicating lights above the control switch in the control room.

References:

6/20E-1-4054S, Rev. V 6/20E-1-4030RH02, Rev. J

't I

SARGENT & LUNDY ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition

' Cable Number:

1RH110 Conductor:

  1. 3 Red Function:

The red wire of cabl6 1RH110 is used to connect a limit switch of valve IRH611 (RHR pump 1B minimum flow valve) to the Equipment Status Display (ESD).

Failure of the butt splice could provide erroneous information on the position of this valve.

Position status of the valve is also available in the main control room from the indicating. lights above the valve control switch.

s

?

r Safety Impact:

None.

Loss of indication only.

References:

6/20E-1-4030RH03, Rev. E 6/20E-1-4681C, Rev. F 4

>-+-M

CARGENT Q LUNDY E N GIN E EQO CHIC AGO Byron Butt Splice i

Inspection Report Disposition Cable Number: 1RH029 Conductor: Green Function: The green wire of cable 1RH029 is used to connect a close limit switch permissive of valve 1SI8811A (containment sump isolation valve) in'to the open control circuit of valve 1RH8701A (reactor coolant loop to RHR pump isolation valve).

Failure of this butt splice would prevent the manual opening of this valve.

This valve is normally closed and is opened when the RHR system is to be put in operation.

Safety Impact: None.

The RHR system is aligned to take suction from two reactor coolant hot legs and discharge to two reactor coolant cold legs to bring the unit to a cold shutdown mode.

As part of this alignment valve IRH8701A must be manually opened.

This align-ment is not utilized following a LOCA.

Position indicating lights in the control room will provide valve position status information to the operator.

The valve can be opened locally utilizing a hand-wheel at the valve operator.

The portion of the RHR system utilized with the emergency core cooling system during the injection and recirculation phases of a loss of coolant accident are unaffected by this failure.

References:

6/20E-1-4030RH04, Rev. K 6/20E-1-4661M, Rev. L FSAR Sections 5.4.7 and 6.3.2

l CARGENTO LUNDY EN GIN E E RS CMICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1RH029 Conductor: #1 - Black Function:

The black wire of 1RH029 is used to connect a limit switch, of valve IRH8701A into the opening control circuit of valve ISI8811A (containment sump isolation valve).

This limit switch contact (LS/C) is used as a permissive in the manual (control switch) opening circuitry.

Failure of this butt splice would prevent the valve from being opened via the control switch, but the automatic function for the opening (safety injection concurrent with RWST lo-lo level) is unaffected.

Safety Impact:

None.

Automatic function is unaffected.

References:

6/20E-1-4030SIl4, Rev. F 6/20E-1-4661M, Rev. L

I SARGENT & LUNDY ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1RH029 Conductor: #2 - White Function:

The white wire of 1RH029 is used to connect a limit switch of valve 1RH8701A into the opening control circuit of valve ISI8811A (containment sump isolation valve).

This limit switch contact (LS/C) is used as a permissive in the manual (control switch) opening circuitry.

Failure of this butt splice would prevent the valve from opening via the control switch, but the automatic function for the opening (safety injection concurrent with RWST lo-lo level) is unaffected.

a Safety Impact:

None.

Automatic function is unaffected.

I

References:

6/20E-1-4030SI14, Rev. F 6/20E-1-4661M, Rev. L l

CARGENTOLUNDY ENGINEERO CMic A GO Byron Butt Splice Inspection Report Disposition Cable Number:

1RH034 Conductor:

  1. 4 Green Function:

The green wire of cable IRH034 is used to connect a limit switch contact (LS/IC) of valve IRH8701B to a " closed" indication light in the valve control circuitry.

Failure of the butt splice would prevent the " closed" indicator light for valve IRH8701B from illuminating on main control panel 1PM06J.

This valve is normally closed.

Safety Impact:

No safety impact, indication only.

References:

6/20E-1-4030RH04, Rev. K 6/20E-1-4683B, Rev. ?!

emcTes " -

Byron Butt Splice Inspection Report Disposition Cable Number:.lRH062 Conductor: Green Function:

The green wire of cable 1RH062 is used to connect a close limit switch permissive of valve 1SI8811B (containment sump isola' tion valve) into the open control circuit of valve IRH8702B (reactor coolant loop to RHR pump isolation valve).

Failure of this butt splice would prvent the manual opening of this valve.

This valve is normally closed and is opened when the RHR system is to be put in operation.

Safety Impact:

None.

The RHR system is aligned to take suction from two reactor coolant hot legs and discharge to two reactor coolant cold legs to bring the unit to a cold shutdown mode.

As part of this alignment valve IRH8702B must be normally opened.

This alignment is not utilized following a LOCA.

Position indicating lights in the control room will provide valve position status information to the operator.

The valve can be opened locally utilizing a handwheel at the valve operator.

The portion of the RHR system utilized with the emer-gency core cooling system during the injection and recirculation phases of a loss of coolant accident are unaffected by this failure.

References:

Drawings - Schematic 6/20E-1-4030RH05, Rev. K Wiring 6/20E-1-4683B, Rev. M

r CARGENT & LUNDY E N GIN E EQO cmcaea l

l Byron Butt Splice Inspection Report Disposition Cable Number: 1SIO63 Conductor:

  1. 12 Black-White Function: The black-white wire cf cable ISIO63 is part of the opening control circuit for valve 1SI8804B (RHR heat exchanger to safety injection pumps isolation valve).

The failure of the butt' splice would prevent the opening of this valve.

This valve is required to be manually opened as part of the realignment of the ECCS from the injection mode to the recirculation mode.

As a result, a portion of the train B RHR pump flow provides suction to the safety injection pumps.

Safety Impact:

Failure of the butt splice would prevent manual opening of valve ISI8804B as part of the realign-ment of the ECCS from the injection of the recirc-ulation mode.

The operator can determine the valve position from position indicating lights in the control room.

The valve can be opened locally utilizing a handwheel at the valve operator.

In addition, during pre-op tests, the butt splices were found to be functional.

The redundant RHR system can also be aligned to supply suction to the safety injection pump utilizing a flow path through valves ICV 8801A and 1SI8807A.

References:

Drawings - Schematic 6/20E-1-4030SIO9, Rev. H Wiring 6/20E-1-4687E, Rev. F

CARGENTOLUNDY E N GlN E E R S

'A.

cHicAco s

Byron Butt Splice Inspection Report Disposision (Cable Number:

1SIl06 Conductor: Red Function:

The red conductor of cable ISIl06 is in the indication circuit of the accumula' tor 1B discharge isolation valve 1SI8808B.

This conductor energizes the "open" isdicating light at Main Control Board 1PM06J.

A s

failure of the butt splice will disable this position indicating light.

Safety Impact:

None.

Loss of indication.only.

The valve opening and closing circuits, including automatic operation on safety injection signal, are unaffected.

References:

6/20E-1-4683A, Rev. M 6/20E-1-4030 Sill, Rev. G C

1 SARGENTO LUNDY ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1SI142 Conductor: #4 - Green Function:

The green wire of 1SI142 is used to connect a limit switch of valve 1SI8811A (containment sump 1A isolation-valve) into the valve control circuit to light a green (valve closed) status lamp.

A failure of this butt splice would prevent the " closed"' indication light from lighting on the control room panel.

Safety Impact:

No safety impact, indication only.

References:

6/20E-1-4 030SI14, Rev. F 6/20E-1-4574A, Rev. E t

1

CARGENTQLUNDY ENGINEERO C H SC LC3 Byron Butt Splice Inspection Report Disposition Cable Number:

ISI142 Conductor:

  1. 7 White-Black Function: The white-black wire of 1SI142 connects a limit switch contact (9-9C) of valve ISI8811A (containment sump isolation valve) into the opening circuitry of valve 1CV8804A (RHR heat exchanger 1A to charaing pumps isolation valve).

A failure of this butt splice would prever.:

both automatic and manual opening of ICV 8804A.

This valve is manually opened as psrt of the realignment of the ECCS from the injection mode to the recirculation mode.

As a result a portion of the Train A RHR pump flow provides suction to the charging pumps.

Safety Impact:

Failure of the butt splice would prevent manual opening of valve 1CV8804A as part of the realignment of the ECCS from the injection to the recirculation mode.

The operator can determine the valve position from position indicating lights in the control room.

The valve can be opened locally utilizing a hand-wheel a t the operator.

In addition, during pre-op tests, the butt splices were found to be functional.

The redundant RHR system can also be aligned to supply suction to the charging pump utilizing a flow path through valves ISIS 804B and ISI8807B.

Reference:

Drawings - Schematic 6/20E-1-4030CV14, nov. G Wiring 6/20E-1-4574A, Rev. E FSAR - Section 6.3.2.8

CARr-ENT Q LUNDY LNGINEERO CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number: 1SI143 Conductor:

  1. 1 - Black Function: The black wire of cable ISIl43 is used to connect the common side of all the limit switches used in the MOV 1SI8811A-120V contrbl circuitry.

Failure of this wire would cause loss of indication, and the inability to open or close the containment sump 1A isolation valve ISI8811A.

This valve is normally closed and is automatically opened on a safety injection signal con-current with a RWST lo-lo level signal to re-align the emergency core cooling system (ECCS) from the injection mode to the recirculation mode.

Safety Impact:

Failure of this butt splice defeats the auto opening of the containment sump isolation valve which is the' initial step in the realignment of the ECCS from the injection mode to the recircu-lation mode.

The operator can determine the valve position from position indicating lights in the control room.

The valve can be, opened locally by a hand wheel on the valve operator.

In addition, this butt splice was tested during pre-op test and found to be functional.

The ECCS also includes a redundant containment recirculation sump and isolation valve.

Reference:

Drawings Schematic 6/20E-1-4030SIl4, Rev. F Wiring 6/20E-1-4661M, Rev. L 6/20E-1-4574A, Rev. E 4

1 CARGENTQLUNDY ENGINEERS CHIC AGO I

Byron Butt Splice Inspection Report Disposition Cable Number:

ISI149 Conductor:

  1. 1 - Black Function:

The black wire of ISI149 is used to connect a limit switch contact (LS/C) o'f valve 1RH8701B into the opening control circuitry of valve ISI8811A (containment sump isolation valve).

This contact is provided as a permissive in the manual opening circuitry.

Failure of the butt splice could disable the manual (handswitch) opening of this valve.

But the automatic function for the opening (safety injection concurrent with RWST lo-lo level) is unaffected.

Safety Impact:

None.

Automatic function is unaffected.

References:

6/20E-1-4030SIl4 6/20E-1-4030RH04 6/20E-1-4232A

l CARGENT O LUNDY ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1SI152 Conductor:

Black Function:

This is a spare conductor not used in wiring.

4 Safety Impact:

No impact.

References:

Equipment No. LAP 21E 6/20E-1-4661M, Rev. L (2-24-84)

CARGENT OLUNDY L'

ENGlNEEDS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number: 1SI495 Conductor:

  1. 9 Green-Black Function:

The green-black wiere of cable ISI495 is used to connect a limit switch of valve 1SI8802B (safety

. injection pump discharge isolation valve) to the Equipment Status Display (ESD).

Failure of the butt splice could provide erroneous information on the position of this valve.

Valve position status can be determined from position indicating lights in the control room.

Safety Impact:

None.

The Equipment Status Display is not essential.

~

References:

6/20E-1-4030SIO7, Rev. F 6/20E-1-4687L, Rev. D O

t

=

!g o

SARGENT & LUNDY ENGINEERS CHICAGO s

Byron Butt Splice Inspection Report Disposition Cable Number:

ISI495 Conductor: 412 Black-White Function:

The black-white wire of cable 1S1495 is used to connect a limit switch of valve ISI8802B (safety injection pump discharge isolation valve) to the Equipment Status Display (ESD).

Failure of the butt splice could pro-vide erroneous information on the position of this valve.

Position status of the' valve is also available in the main control room from the indicating lights above the valve control switch.

I None.

Loss of indication only.

Safety Impact:

1

References:

6/20E-1-4030SIO7, Rev. F 6/205-1-4687L, Rev. D L

I I

i

CARGENT O LUNDY ENGlNEERO CHICAGO Byron Butt Splice Inspection Report Disposition v

Cable Number:

2SX013 Conductor:

  1. 2 - White Function:

The white wire of 2SX013 is used to connect the ESW Pump 2B mtor space heater to a 120V supply s

from 480V Auxiliary Bui'lding MCC 232-X3 (2AP24E).

A break in this wire will prevent the operation of the space heater.

The control circuit is designed to energize the motor heater when the y

ESW pump is not operating.

The heater is not required but is provided (as an extra precaution) to minimize the possibility of moisture condensation on the motor windings.

Saf ety Impact:

None.

The ESU pump and motor is located in a cubicle,in the auxiliary building for which the maximum relative humidity is 70% by design.

The space heater does not perform a direct safety function.

The service water pump motor performs the safety function.

As noted above, the space heater is provided to keep moisture ou,t of motor insulation.

Moisture alone, doesn't damage the insulation; the insulation wears away or cracks for other reasons.

Moisture plays a secondary role (in the failure) in that it provides an electrical path between the conductor (via damaged insulation) and ground.

References:

FSAR Table 3.11 - Environmental Zone A9 6/20E-2-4030SX02, Rev. D 6/20E-2-4613J, Rev. H 6/20E-2-4685B, Rev. q

i CARGENT & LUNDY ENGINEERS CMcC AGO Byron Butt Splice Inspection Report Disposition Cable Number:

1SX172 Conductor:

Blue Function:

The blue conductor of, cable 1SX172 inputs to the diesel driven essential service water make-up pump start-up panel trouble alarm in the main control room.

Inputs to this trouble alarm are from the control selector switch on the start-up panel when placed in either the " manual" or "off" positions and from activation of any alarms on the start-up panel annunciator.

Safety Impact:

None.

Loss of this alarm has no direct safety impact (i.e., does not prevent auto-start of diesel) with regard to loss of the trouble alarm.

1.

The annunciation on the start-up panel is for abnormal conditions that may occur when the diesel is operating.

None of the conditions alarmed will prevent the diesel from auto-starting.

2.

Placing the modo selector switch on the start-up panel to the " manual" or "off" position inhibits the auto-start of the diesel on a low level signal in the essential service water cooling tower basin (CLS-SXO96).

Information on basin icvel is available in the control room by IcVel indicator OLI-SXO64 and a low level alarm initiated by OLSL-SXO64~

Upon acknowledgement of this alarm the operator could manually start the diesel from the control room.

In addition, a redundant diesel driven essential service water pump is provided in the design.

References:

6/20E-1-4087H, Rev. L 6E-0-4030SXO9, Rev. F 6E-0-4030SX24, Rev. C M-2042, cheet 5, Rev. E

E SAR3ENT&LUNDY E N GIN E E R s emcaso Byron Butt' Splice Inspection Report Disposition Cable Number 1SX172 Conductor:

White-Black Functions The white-black conductor of cable 1SX172 inputs to the diesel driven essential service water make-up pump start-up panel trouble alarm in the main control room.

Safety Impacts None.

Loss of this alarm has no direct safety impact (i.e., does not prevent auto-start of diesel) with regard to loss of the trouble alarm.

1.

The annunciation on the start-up panel is for abnormal conditions that may occur when the diesel is operating.

None of the conditions alarmed will prevent the diesel from auto-starting.

2.

Placing the mode selector switch on the start-up panel to the " manual" or "off" position inhibits the auto-start of the diesel on a low level signal in the essential service water cooling tower basin (OLS-SXO96).

Information on basin level is available in the control room by level indicator OLI-SX064 and a low level alarm initiated by OLSL-SX064.

Upon acknowledgement of this alarm the operator could manually start the diesel from the control room.

In addition, a redundant diesel driven essential service water pump is provided in the design.

References:

6/20E-1-4087H, Rev. L 6/20C-0-4030SXO9, Rev. F

CARGENT Q LUNDY ENolNEEDO C HlC A13 Byron Butt Splice Inspection Report DisptIsition Cable Number:

1SX204 Conductor:

White & Blue Function:

The blue conductor of the cable 1SX204 is in the alarm circuit of " diesel-driven essential service water make-up pump OB".

A failure o'f the butt splice will prevent initiation of trip and auto-start alarms.

The white conductor of the cable 1SX204 is in the control and indication circuit of diesel-driven essential service water make-up pump 08.

This conductor connects local / remote selector switch at the remote shutdown panel 1PLO5J to the Main Control Board OPM0lJ.

A failure of the butt splice will cause loss of control and indication at Main Control Board OPM01J.

Safety Impact: With regard to loss of the trip and auto-start alarms, the operator has indicating lights on the main control board indicating the pump position.

If the pump does not auto-9 tart on a low level signal in the Essential Service Water cooling tower basin, a

low level alarm and a level indicator is provided in the control room.

The pump can then be manually started.

With regard to less of control at the main control board, the pump can be controlled from the remote shutdown panel.

Ecferences:

6E-0-4044AA 6E-0-4030SM10, Rev. F

i' i i CARGENT O LUNDY ENG1NEER9 i

C MIC ASO 11 Byron Butt Splice Inspection Report Disposition Cable' Number:

ISX280 s

.i Conduqtor:

Red Function:

The red wire of ca$le 1SX280 is used in the "ESW Pump 1A Lube Oil Pressure Low-Low'? alarm circuit.

The ESW pump 1A is provided with two lube oil pumps - one shaft driven and one motor driven.

The motor driven pump is a back-up to the shaf t driven pump.

The alarm'is initiated by a low-low..isbe oil pressure signal in series with an ESW pump running signal (fl.e.,. shaf t driven.l ube oil pump should be operating) or a'imotor driven lube oil pump running signal.

Failu're ot" this butt splice will only diable the alarm throughtthe ESW pump running signal circuit.

ti

+

e Safety Impact:

None.

If the'~sNaft'dbiven lube oil pump fails, a low lube oil pressure signal will start the motor driven auxiluary lube oil pump for Essential i

Service Water pump 1A.

If a low-low lube oil pressure condition exists with motor driven lube oil pump running, the ale.'rm will be intiated.

References:

Equipment No.' LAP 05EB l

6/20E'-l 4611B, Rev.' P 6/20E-1-4030SX01, Rev.-J t

~

6/20E-1-4030SXO3, Rev. F l

Wiye Code - (0123A) 1 f

. t

h.

ic g

SARGENTO LUNDY ENGlNEERS CMacaso Byron Butt Splice Inspection Report Disposition Cable Number: 1SX286 Conductor:

  1. 3 Red Function:

The red wire of cable 1SX286 is used in the Essential Service Water Pump 1B lube oil low-low pressure alarm circuit.

The ESW pump 1B is provided with two lube oil pumps - one shaft driven and one motor driven.

The motor driven pump is a back-up to the shaft driven pump.

The alarm is initiated by a low-low lube oil pressure signal in series with an ESW pump running signal (i.e. shaft driven lube oil pump should be operating) or a motor driven lube oil pump running signal.

Failure of this butt splice will only disable the alarm through the ESW pump running signal circuit.

Safety Impact:

None.

If the shaf t driven lube oil pump f ail:3, a low lube oil pressure signal will start the motor driven auxiliary lube oil pump.

If a low-low lube oil pressure condition exists with the motor driven lube oil pump running, the alarm will be initiated.

Reference:

Drawings - Schematic 6/20E-1-4030SX03, Rev. F Wiring 6/20E-1-4681H, Rev. K l

CARGENTOLUNDY 6

ENGINEERS CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number: 1SX286 Conductor: #4 Green Function: The green wire of cable ISX286 is a wire connection in an annunciator circuit for,ESW pump 1B lube oil pressure low.

Failure of this wire would prevent an alarm on low lube oil pressure.

Scfety Impact:

None - annunciation is not an essential funct.on.

Reference:

Drawings - Schematic 6/20E-1-4030SX03, Rev. G Wiring 6/20E-1-4681H, Rev. K 4

ew.

mewww

-a,,.e-w e

-r-v-,-~~

~--

SARGENT & LUNDY E N G I N.E E R S C MIC AGO Byron Butt Splice Inspection Report Disposition Cable Number:

ISX474 Conductor:

  1. 3 Red Function:

The red wire of cable 1SX474 is part of the closing control circuit for RCFC 1B & ID service water outlet valve ISX027B.

The failure of the butt splice would prevent the closing of the outlet valve.

Safety-Impact:

None.

The valve is normally open and is required to be open for the reactor containment fan coolers to operate.

Thus the closing control circuit is not required to operate to perform a safety function.

2

References:

6/20E-1-4030SX11, Rev. C 6/20E-1-4687A, Rev. E

I SARGENT & LUNDY E N GIN E E R S CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

1SX474 Conductor:

  1. 4 Green Function:

The green wire of cable 1SX474 is part of the closing control circuit for RCFC 1B & 1D service water outlet valve ISX027B.

The failure of the butt splice would prevent the closing of the outlet valve.

I Safety Impact:

None.

The valve is normally open and is required to be open for the reactor containment fan coolers to operate.

Thus the closing control circuit is not required to operate to perform a safety function.

References:

6/20E-1-4030SX11, Rev. C 6/20E-1-4687A, Rev. E

SARGENT & LUNDY E N GIN E ERS CMacaco Byron Butt Splice Inspection Report Disposition Cable Number:

lVA003 Conductor:

Green-Black Function:

The green-black wire of cable IVA003 is a connection in the starter circuit for fuel handling building charcoal booster fan.0VA04CA.

This fan is normally not running but is automatically started on a fuel handling area high radiation signal or an ESP actuation signal from Unit 1 or Unit 2.

This fan can also be manually started in the control room.

Starting of this fan closes the normal exhaust flow and diverts it through charcoal absorbers.

Failure of this butt splice will prevent both manual and automatic starting of the fan.

Safety Impact:

Minimal.

Failure of this fan to start may result in the release of radioactive gases to the atmosphere.

Radiation monitors in both the fuel handling area end the vent stack would monitor such releases and provide alarms in the control room.

Position indicating lights in the control room would also indicate that the charcoal booster fan is not running.

The operator could isolate the exhaust path by closing the charcoal filter isolation dampers OVA 058YA, YB, YC and OVA 059YA and YB, utilizing a control switch in the control room.

This butt splice was also tested during system pre-op testing and found to be functional.

Failure of the butt splice would be detected during periodic testing l

of the ESF actuation signal. auto-starting the fan.

Failure of this butt splice also does not affect the circuits for the redundant charcoal booster fan.

References:

6/20E-0-4030VA22, Rev. F 6/20E-0-4046A, Rev. F 6/20E-0-4030VA19, Rev. J Wire code VA4CAC1 I

1

SARGENT G LUNDY ENGINEERS i

cmcAco l

Byron Butt Splice Inspection Report Disposition Cable Number:

lVA073 Conductor:

  1. 11 Blue-Black Function:

The blue-black wire of cable lVA073 is used to connect one side of 2 relay contacts into the start circuitry and seal-in circuitrp of containment spray pump cubicle cooler (lVA03SB) fans.

One relay contact auto starts the fans when the_ temperature is greater than 120*F.

The other relay contact keeps the fan running following a high temperature auto-start until the temperature drops below 108'F.

This butt splice affects controls for 2 of the 4 fans on the cooler.

The function of this cooler is to provide supplemental I

cooling to the pump room to maintain environmental conditions within the pump requirements.

The 4 fans have 3 starting modes - manually from a local control switch, automatically when the CS pump 1B is running and automatically on a second stage ( 120*F) temperature signal.

The starting signals are sealed in such that the fan will not stop until the temperature in the cubicle is less than 108*F.

The cubicle cooler is expected to operate only when the containment spray pump is running.

In addition, a third stage ( 130*F) temperature-alarm is provided in the control room.

Safety Impact:

None.

All the fans still start and run on a CS pump 1B running signal (normal mode of operation).

The above failure would also affect only 2 of the 4 fans for the cooler which would only reduce the cooling capacity.

In addition should a high temperature condition exist, at any time; an alarm will alert the operator.

References:

6/20E-1-4030VA10, Rev. H 6/20E-1-4030VAll, Rev. E 6/20E-1-4681E, Rev. M

SARGENT & LUNDY E N GlH E E RS CHicAco Byron Butt Splice Inspection Report Disposition Cable Number:

lVA228 Conductor:

  1. 1 - Black Function:

The black wire of IVA228 is used to connect one side of a temperature switch (set at 108*F) to an auxiliary relay mounted out MCCl31X1.

Contacts of this relay are used in the start (seal-in) circuitry of essential service water pump cubicle cooler (1VA0lSA) fans.

The 1A, 1B, 1C, and 1D fans are affected.

The function of these coolers is to provide supplemental cooling for the pump room to maintain environmental conditions within the pump requirements.

The fans have 3 starting modes - manually from a local control switch, automatically when the ESW pump runs and automatically on a second stage ( 120*F) high temperature signal.

The starting signals are sealed in such that the fan will not stop until the temperature in the cubicle is less than 10S*F.

The cubicle cooler is expected to operate only when the ESW pump is running.

In addition, a third stage ( 130 F) high temperature condition is alarmed in the control room.

Safety. Impact:

None.

Fans will still start on an ESW pump running signal (normal mode of starting).

Should the cooler fans fail, a high temperature alarm in the control room will alert,the operator.

References:

6/20E-1-4030 val 2, Rev. J 6/20E-1-4661H, Rev. H 6/20E-1-4661J, Rev. L 6/20E-1-4471A, Rev. H

SARGENT & LUNDY E N GIN E E R@

CHIC AGO Byron Butt Splice Inspection Report Disposition Cable Number:

IVA228 Conductor:

  1. 2 - White Function:

The white wire of IVA228 is part of the start circuitry for the auxiliary building HVAC essential service water pump cubicle cooler (lVA01SA) fans lA & IB.

Failure of the wire would prevent the auto-start of fans lA & 1B on a high temperature ( 120*F) in the cubicle.

Fans 1C &

1D for the cubicle cooler are unaffected by failure of this wire.

The function of this cooler is to provide supplemental cooling to the pump room to maintain environmental conditions within the pump requirements.

The fans have 3 starting modes - manually from a local control switch, automatically wnan the ESW pump is running, and auto-matically on a second stage ( 120*F) temperature signal.

The starting signals are sealed in such that the fan will not stop until the temperature in the cubicle is less than 108*F.

The cubicle cooler is expected to operate only when the ESW pump is running.

In addition, a third stage ( 130*F) temperature alarm is provided in the control room.

Safety Impact:

None.

Fans will still start on an ESW pump' running signal (normal mode of starting).

This failure would also affect only 2 of the 4 fans for the cooler which would only reduce the cooling capacity.

Should a high temperature condition exist, an alarm will alert the operator.

References:

6/20E-1-3040VA12, Rev. J 6/20E-1-4661H, Rev. H 6/20E-1-4661J, Rev. L 6/20E-1-4471A, Rev. H l

i i

SARGENT G LUNDY ENGlNEERo CHIC AGO Byron Butt Splice Inspection Report Disposition Cable Number:

lVA228 Conductor:

  1. 5 - Orange Function:

The orange wire of IVA228 is used to connect temperature switch (1TS-VA001), monitoring the service water pump cubicle temperature, to auxiliary relays mounted at McCl31X1.

The failure of this wire would prevent these relays from picking up on high temperature and in turn would prevent the cubicle cooler (lVA0lS A) fans lA, 1B, 1C and ID from automatically starting.

The function of this cooler is to provide supplemental cooling to the pump room to maintain environmental conditions within the pump requirements.

The fans have 3 starting modes - manually from a local control switch, automatically when the ESW pump is running and auto-matically on a second stage ( 120'F) high temperature.

The starting signals are sealed in such that the fan will not stop until the temperature in the cubicle is less than 108*F.

The cubicle cooler is expected to operate only when the ESW pump is running.

In addition, a third stage ( 130*F) high temperature alarm is provided in the control room.

Safety Impact:

None.

Fans will still start on an ESM pump running signal (normal mode of starting).

Should the cooler fans fail, a high temperature alarm in the control room will alert the operator.

References:

6/20E-1-4030 val 2, Rev. J 6/20E-1-4661H, Rev. H 6/20E-1-4661J, Rev. L 6/20E-1-4471A, Rev. H

SARGENT & LUNDY ENGINEERS cMicAco I

Byron Butt Splice Inspection Report Disposition CaDie Number:

lVA228 Conductor:

  1. 6 - Blue Function:

The blue wire of IVA228 is part of the start circuitry for the auxiliary building HVAC essential service water pump cubicle cooler (lVA0lSA) fans lA & 1B.

Failure of the wire would prevent the auto-start of fans lA &

1B on a high temperature ( 120*F) in the cubicle and prevent the circuitry from sealing-in with a temperature signal ab~ove 108"F.

Fans 1C & 1D for the cooler are unaffected by failure of this wire.

The function of this cooler is to provide supplemental cooling to the pump roon to maintain environmental conditions within the pump requirements.

The fans have, 3 starting modes - manually from a local control switch, automatically when_the ESW pump is running and automatically on a second stage ( 120*F) temperature signal.

The starting signals are sealed in such that the fan will not stop until the temperature in the cubicle is less than 108'F.

The cubicle cooler is expected to operate only when the ESW pump is running.

In addition, a third stage ( 130*F) temperature alarm is provided in the control room.

Safety Impact:

None.

Fans will still start on an ES,W pump running signal (nonnal. mode of starting).

This failure only affects 2 of the 4 fans for the cooler which would reduce the cooling capacity.

Should a 'high temperature condition exist, an alarm will alert the operator.

References:

6/20E-1-4030VA12, Rev. J 6/20E-1-4661H, Rev. H 6/20E-1-4661J, Rev. L 6/20E-1-4471A, Rev. H l_

SARGENTOLUNDY e

E N GlN E E RO CMICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

lVC387 Conductor:

Red & Green-Black Function:

The red conductor of cable IVC 387 is a connection in a detector trouble alarm, circuit at a local panel, fcr smoke detector OXY-VC065AA.

Failure of the butt splice will prevent initiation of this alarm.

The smoke detector is monitoring return air from main control board 2PM05J.

The green-black conductor is a connection from smoke detector OXY-VC065AA to an alarm in the main control room for " main control room ionization high".

~

Failure of the butt splice will prevent the initiation i

of this alarm from smoke detector OXY-VC065AA.

Safety Impact:

None.

With regard to the loss of the main control room ionization alarm, this smoke detector will initiate an alarm at a local panel.

Alarms at this local panel annunciate in the main control room as part of an HVAC common trouble alarm.

With regard to the loss of the detector trouble alarm, since an independent fire detection system is provided, failure to identify the detector trouble will not jeopardize the control room.

l Rr.ferences:

Equipment No. OVC0lJC 6/20E-0-4623E, Rev. E 6/20E-0-4030VC41, Rev. E Wire Code - Red (VC65AA10), Green-black (CA14 )

i l

l

SARGENTO LUNDY ENGINEERO C HIC ACO

. Byron Butt Splice Inspection Report Disposition Cable Number:

lVQ087-

' Conductor:

White-Black, Green-Black, Blue, Orange and Red.

Re-inspection rejected only one conductor, but since conductor color could not be identified, each conductor in splice was analyzed.

Function:'

Control and indication for the normally closed primary containment purge system supply isolation valve IVQOOlA.

Valve' operator is hydraulic.

Failure of the butt splices in these conductors will res' ult in the following:

Red - Loss of open indicating light in main control room Orange - Loss of auto starting of accumulator hydraulic pump Blue - Loss of control to manually open the valve White-Black - Loss of control to manually close the valve Green-Black - Loss of control to the accumulator discharge solenoid Safety Impact:

None.

Safet'y impact of the' failure of each butt splice is discussed below:

Red - No safety impact.

Loss of indication only.

Orange - No safety impact.

Low accudulator pressure is alarmed in the control room.

Upon receipt of the alarm the operator can take corrective action to recharge the accumulator.

Maintaining the accumulator

-in a charged condition is essential for the valve to perform its isolation function.

Blue - No safety inpact.

The containment purge ventilation system is only operated during planned reactor shutdowns.

Therefore, this valve will only be opened with the unit in a shutdown mode.

. White-Black - No safet-, impact, since the valve is closed during normal operation.

Manual closure of the valve would only be required when shutting down the containment purge ventilation system.

As discussed above, this system is only' operated with the unit in a shutdown mode.

SARGENT & LUNDY ENGINEER 0 C HIC A1@

Byron Butt Splice Inspection Report Disposition Safety Impact:

(Cont'd)

Green-Black - No safety impact.

Since failure of this butt splice will de-energize the accumulator discharge solenoid.

This will open the solenoid.

and allow the accumulator to discharge and close the valve which is its safety position.

References:

Equipment No. LAP 25E FSAR Section 9.4.9.2 W/D No. 1-4663C, Rev. J S/D No. 1-VQ07, Rev. J Color Code - Red (VQlAR)

Orange (VQlASL2)

Blue (VQlASL3)

White-Black (VQlAPS4)

Green-Black (VQlASL1)

O

SARGENT Cr LUNDY cNasNceno-CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number:

lVOO97 White-Black, Red-Black, Green-Black, Red and Blue Conductor:

Re-inspection rejected only one conductor, but since conductor color could not be identified, each conductor in splice was analyzed.,

Control and indication for the normally closed primary containment purge system supply isolation valve IVQ001A.

Function:

Failure of the butt splices Valve operator is hydraulic.,

in these conductors will result'in the following:

Red - Loss of open indicating light in main control room Blue - Loss of control to manually open the valve Green-Black - Loss of control to manually close the valve White-Black - Loss of control to the accumulator discharge solenoid Red-Black - Loss of power to de control circuit for valve Safety impact of~the failure of each butt Safety Impact:

None.

splice is discussed below::

Loss of indication only.

Red - No safety impact.

The containment purge Blue - No safety impact.

ventilation system is only operated during planned reactor. shutdowns.

Therefore, this valve will only be opened with the unit in a shutdown mode.

Since failure Green-Black - No safety impact.

of this butt splice will de-energize the accumulator This will open the solenoid discharge solenoid.

and allow the accumulator to discharge and close the valve which is its safety position.

since the valve is White-Black - No safety impact, Manual closure of the closed during normal operation.

valve would only be required when shutting down the As discussed containment purge ventilation system.

this system is only operated with the unit in a

above, shutdown mode.

SARGENT G LUNDY E N GlNE E RS CMtCA?-D Byron Butt Splice Inspection Report Disposition Safety Impact:

(Cont'd)

Red-Black - No safety impact.

Loss of power will de-energize the accumulator discharge solenoid ensuring that the valve is in a closed position and de-energize a solenoid locking out the manual open circuit of the valve.

References:

Equipment No. LAP 25E FSAR Section 9.4.9.2 W/D No. 1-4663C, Rev. J S/D No. 1-VQ07, Rev. J Color Code - Red (VQlAR)

Blue (VQlAP)

White-Black (.VQl ASL1)

Red-Black (VQlAN)

Green-Black (VQlAP53) e 4

e -

SARGENT & LUNDY ENGINEERS chicago Byron Butt Splice Inspection Report Disposition Cable Number:

lVQ136 Conductor:

' Green Function:

Re-inspection report identified this splice as acceptable.

Safety Impact:

None-e

o SARGENT & LUNDY EN GIN EERs concAeo Byron Butt Splice Inspection Report Disposition Cable Number LAP 137 Conductor:

Blue Function:

The blue conductor of cable 1AP137 is in the auto-trip

~

alarm circuit for the manually operated feed breaker in 480V ESF unit substation 132Z to 480V essential

This auto-trip alarn is activated by an overcurrent trip switch in the feed breaker assembly.

The alarm is in the main control room.

Safety Impact:

None.

The breaker will perform its protective function of tripping on overcurrent.

Loss of the motor control center can be determined by other indication in the control room (i.e., loss of position indication and alarms associated with

)

services fed from the motor control center).

In addition, close/ trip indication for the feed breaker.is provided locally at the.480V unit substation.

?

References:

6/20E-1-4156A, Rev. M 6/20E-1-4156C, Rev. T 6E-1-4030AP76, Rev. B

CARGENT & LUNDY ENGINEERS CH3CAGO Byron Butt Splice Inspection Report Disposition Cable Number: ICC008 Conductor:

Black-White Function: The Black-White conductor of cable ICC008 is a spare conductor.

Safety Impact: None.

The conductor is spare.

References:

6/20E-1-4155B, Revision T 6/20E-1-4030CC01, Revision L e

i D

i J

6 6

r


,,.,-..~,_w-,,---------.r-.,.-..~--y--

cy v w,,,

-.--,,--,---,----.e-.

---vw--m-'.--

-w

- w - - - - - -

\\

4 SARGENTOLUNDY EN GIN EERS cmcaso Byron Butt Splice Inspection Report Disposition Cable Number:

1RH062 Conductor: White Function:

The white wire of cable 1RH062 is used to connect a close limit switch permissive of valve ISI8811B (containment sump isolation valve) into the open control circuit of valve 1RH8702B (reactor coolant

, loop to RHR pump isolation valve).

Failure of this butt splice would prvent the manual opening of this valve.

This valve is normally closed and is opened when the RHR system is to be put in operation.

Safety Impact:

None.

The RHR' system is aligned to take suction from two reactor coolant hot legs and discharge to two reactor coolant cold legs to bring the unit to a cold shutdown mode.

As part of this alignment valve IRH8702B must be normally opened.

This alignment is not utilized following a LOCA.

Position indicating lights in the control room 1

will provide valve position status information to the operator.

The valve can be opened locally utilizing a handwheel at the valve operator.

The portion of the RHR system utilized with the emer-gency core cooling system during the injection and l

recirculation phases of a loss of coolant accident are unaffected by this failure.

References:

' Drawings

' Schematic 6/20E-1-4030RH05, Rev. K Wiring 6/20E-1-4683B, Rev. M i

i f

1 l

t

+

CARGENTQ LUNDY EN G1N E E R S CHICAGO Byron Butt Splice Inspection Report Disposition Cable Number: ISIl43 Conductor: Blue-Black Function:

The Blue-Black conductor of cable ISIl43 is a spare conductor.

Y Safety Impact:

None.

The conductor is spare.

References:

Drawings - Schematic 6/20E-1-4030SIl4, Revision F l

Wiring 6/20E-1-4661M, Revision L 6/20E-1-4574A, Revision E l

e

(

l n-----------

,,--,- - - - - -,