TABLE 3.3-4 (Continued) 7g ENGINEERED SAFETY FEATURE ACTUATION SYSTEM INSTRUMENTATION TRav VALUES N

h,,4 ~

gul.

ALLOWABLE M

FUNCTIONAL UNIT TRIP VALUE VALUES DU go 9.

CONTROL ROOM ISOLATION (CRIS) no N.

a.

Manual CRIS (Trip Buttons)

Not Applicable Not Applicable 04 e

b.

Manual SIAS (Trip Buttons)

Not Applicable Not Applicable

,0U c.

Airborne Radiation ggM wg i.

Particulate / Iodine 5 5.7 x 104 cpm **

5 6.0 x 104 cpm **

ii. Gaseous 5 3.8 x 102 cpm **

5 4.0 x 10. cpm 2

an d.

Autsnatic Actuation Logic Not Applicable Not Applicable 10.

T0XIC GAS ISOLATION (TGIS) a.

Manual (Trip Buttons)

Not Applicable Not Applicable b.

Chlorine - High 5 14.3 ppm 5 15.0 ppm c.

Ammonia - High 5 97 ppm

$ 100 ppm d.

Butane / Propane - High

$ 193 ppm 5 200 ppm h

e.

Automatic Actuation Logic Not Applicable Not Applicable a an 6o 4=

5k

.g

- ~ _.. _

TABLE 3.3-4 (Continued) 1 TABLE NOTATION (1) Value may be decreased manually, to a minimum of greater than or equal to 300 psia, as pressurizer press.ure is reduced, provided the margin between the pressurizer and this value is maintained at less than or equal to 400 psia;* the setpoint shall be increased automatically as pressurizer pressure is increased until the trip setpoint is reached.

Trips may be bypassed when pressurizer pressure is < 400 psia. Bypass shall be automatically removed before pressurizer pressure exceeds 500 psia (the corresponding bistable allowable alue is 5 472 psia).

(2) Value may be decreased manually as steam generator pressure is reduced, provided the margin between the steam generator pressure and this value is maintained at less than or equal to 200 psi;* the setpoint shall be increased automatically as steam generator pressure is increased until the trip setpoint is reached.

(3) % of the distance between steam generator upper and lower level instrument nozzles.

(4) Deleted.

(5) Actuated equipment only; does not result in CIAS.

(6) The trip setpoint shall be set sufficiently high to prevent spurious alarms / trips yet sufficiently low to assure an alarm / trip should an inadvertent release occur.

(7)

Prior to the completion of DCP 53N, the setpoints for Containment Airborne Radiation Monitor 2RT-7804-1 shall be determined by the ODCH.

(8) The trip setpoint shall be set sufficiently high to prevent spurious alann/ trips yet sufficiently low to assure an alarm / trip should a fuel handling accident occur.

l

  • Variable setpoints are for use only during normal, controlled plant heatups and cooldowns.
    • Above normal background.

SAN ON0FRE-UNIT 2 3/4 3-26 Amendment No. 120

" ATTACHMENT "B" EXISTING SPECIFICATIONS UNIT 3 i

i

s TABLE 3.3-4 (Continued)

Y Z

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP VALUES Ea A

ALLOWABLE a

FUNCTIONAL UNIT TRIP VALUE VALUES 5

9.

CONTROL ROOM ISOLATION (CRIS) a.

Manual CRIS (Trip Buttons)

Not Applicable Not Applicable

]

b.

Manual SIAS (Trip Buttons)

Not Applicable Not Applicable

'i c.

Airborne Radiation i.

Particulate / Iodine 1 5.7 x_104 cpm **

1 6.0 x 104 cym**

ii. Gaseous 1 3.8 x 102 cpm **

$ 4.0 x 102 cpm **

d.

Automatic Actuation Logic Not Applicable Not Applicable w

E 10.

T0XIC GAS ISOLATION (TGIS) i a.

Manual (Trip Buttons)

,Not Applicable Not Applicable b.

Chlorine - High 1 14.3 ppm i 15.0 ppm c.

Ammonia - High 5 97 ppm 1,100 ppm d.

Butane / Propane - High 5 193 ppm i 200 ppe e.

Automatic Actuation Logic Not Applicable Not Applicable D

E c_-

h

,z m

o e

m s

02

TABLE 3.3-4 (Continued)

TABLE NOTATION (1) Value may be decreased manually to a minimum of greater than or equal to 300 psia, as pressurizer pressur,e.is reduced, provided the margin between the pressurizer and this value is maintained at less than or equal to 400 psia;* the setpoint shall be increased automatically as pressurizer pressure is increased until the trip setpoint is reached. Trips may be bypassed when pressurizer pressure is < 400 psia.

Bypass shall be automatically removed before )ressurizer pressure exceeds 500 psia (the corresponding bistable allowa)le value is s 472 psia).

(2) Value may be decreased manually as steam generator pressure is reduced, provided the margin between the steam generator pressure and this value is maintained at less than or equal to 200 psi;* the setpoint shall be increased automatically as 4 steam generator pressure is increased until the trip setpoint is reached.

-(3) % of the distance between steam generator upper and lower level instrument nozzles.

(4) Deleted.

(5) Actuated equipment only; does not result in CIAS.

(6) The trip setpoint shall be set sufficiently high to prevent spurious alarms / trips yet sufficiently low to assure an alarm / trip should an inadvertent release occur.

(7)

Prior to the completion of DCP 53N, the setpoints for Containment Airbaine Radiation Monitor 3RT-7804-1 shall be determined by the ODCH.

(8) The trip setpoint shall be set sufficiently high to prevent spurious alarm / trips yet sufficiently low to assure an alarm / trip should a fuel 1

handling accident occur.

  • Variable setpoints are for use only during normal _, controlled plant heatups and cooldowns.
    • Above normal background.

j i

SAN ONOFRE - UNIT 3 3/4 3-26 Amendment No. 45,107,109

k l

" ATTACHMENT "C" PROPOSED SPECIFICATIONS UNIT 2

TABLE 3.3-4 (Continued)

ENGINEERED SAFETY FEATURE ACTUATION SYSTEM INSTRUMENTATION TRIP VALUES g

ALLOWABLE q

FUNCTIONAL UNIT TRIP VALUE VALUES 9.

CONTROL ROOM ISOLATION (CRIS) a.

Manual CRIS (Trip Buttons)

Not Applicable Not Applicable b.

Manual SIAS (Trip Buttons)

Not Applicable Not Applicable c.

Control? Room Airborne Radiation lN R

i.

Particulate / Iodine s 5.7 x 10' cpm **

s 6.0 x 10" cpm *'

l gal %L a

l

  • p ii.

Gaseous s 3.8 x 10 cpm s 4.0 x 10 cpm 2

2 g.1 l

N d.

Automatic Actuation Logic Not Applicable Not Applicable 10.

T0XIC GAS ISOLATION (TGIS)

I a.

Manual (Trip Buttons)

Not Applicable Not Applicable b.

Chlorine - High 5 14.3 ppm 5 15.0 ppm c.

Ammonia - High 5 97 ppm s 100 ppm d.

Butane / Propane - High 5 193 ppm 5 200 ppm k

e.

Automatic Actuation Logic Not Applicable Not Applicable "i

5

TABLE 3.3-4 (Continued)

TABLE NOTATIO!!

(1)

Value may be decreased manually, to a minimum of greater than or equal i

to 300 psia, as pressurizer pressure is reduced, provided the margin between the pressurizer and this value is maintained at less than or equal to 400 psia;* the setpoint shall be increased automatically as pressurizer pressure is increased until the trip setpoint is reached.

Trips may be bypassed when pressurizer pressure is < 400 psia.

Bypass shall be automatically removed before pressurizer pressure exceeds l

500 psia (the corresponding bistable allowable value is 5 472 psia).

(2)

Value may be decreased manually as steam generator pressure is reduced, provided the margin between the steam generator, pressure and this value is maintained at less than or equal to 200 psi; the setpoint shall be increased automatically as steam generator pressure is increased until the trip setpoint is reached.

1 (3)

% of the distance between steam generator upper and lower level instrument nozzles.

(4)

Deleted.

(5)

Actuated equipment only; does not result in CIAS.

(6)

The trip setpoint shall be set sufficiently high to prevent spurious alarms / trips yet sufficiently low to assure an alarm / trip should an i

inadvertent release occur.

(7)

Prior to the completion of DCP 53N, the setpcints for Containment FM Akborne Radiation Monitor 2RT 78041 shall be determined by the 00CM. l n6Mp Deleted.

r

.1 (8)

The trip setpoint shall be set sufficiently high to prevent spurious alarms / trips yet sufficiently low to assure an alarm / trip should a fuel handling accident occur.

  • Variable setpoints are for use only during normal, controlled plant heatups and cooldowns.
    • Above normal background.

SAN ONOFRE - UNIT 2 3/4 3-26 AMENDMENT NO.

ATTACHMENT "D" PROPOSED SPECIFICATIONS UNIT 3 l

l l

g TABLE 3.3-4 (Continued) g ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION TRIP VALUES 2m ALLOWABLE FUNCTIONAL UNIT TRIP VALUE VALUES c=

l

[

9.

CONTROL ROOM ISOLATION (CRIS) a.

Manual CRIS (Trip Buttons)

Not Applicable Not Applicable b.

Manual SIAS (Trip Buttons)

Not Applicable Not Applicable yg W%

c.

Control;; Room Airborne Radiation

-I i.

Particulate / Iodine s 5.7 x 10' cpm 5 6.0 x 10' cpm **

' Icd W w

2 2

2 ii.

Gaseous s 3.8 x 10 cpm 5 4.0 x 10 cpm

'J d.

Automatic Actuation Logic Not Applicable Not Applicable 10.

T0XIC GAS ISOLATION (TGIS) a.

Manual (Trip Buttons)

Not Applicable Not Applicable b.

Chlorine - High s 14.3 ppm 5 15.0 ppm c.

Ammonia - High 5 97 ppm s 100 ppm d.

Butane / Propane - High 5 193 ppm s 200 ppm Eg e.

Automatic Actuation Logic Not Applicable Not Applicable E9 5

1 TABLE 3.3-4 (Continued)

TABLE NOTATION (1) Value may be decreased manually, to a minimum of greater than or equal to 300 psia, as pressurizer pressure is reduced, provided the margin between the pressurizer and this value is maintained at less than or equal to 400 psia; the setpoint shall be increased automatically as pressurizer pressure is increased until the trip setpoint is reached.

Trips may be bypassed when pressurizer pressure is < 400 psia.

Bypass shall be automatically removed before pressurizer pressure exceeds 500 psia (the corresponding bistable allowable value is 5 472 psia).

(2) Value may be decreased manually as steam generator pressure is reduced, provided the margin between the steam generator, pressure and this value is maintained at less than or equal to 200 psi; the setpoint shall be increased automatically as steam generator pressure is increased until the trip setpoint is reached.

(3) % of the distance between steam generator upper and lower level instrument nozzles.

(4) Deleted.

(5) Actuated equipment only; does not result in CIAS.

(6) The trip setpoint shall be set sufficiently high to prevent spurious alarms / trips yet sufficiently low to assure an alarm / trip should an inadvertent release occur.

k l

(7)

Prior to the completion of DCP 53N, the :ctpcint: for Containment f

,m u__,, o,.m.s :..-.u...,4.+_.,.

n,

v..e n. a, i.
u.., n..

.a. - _...... a n.,,. u. - nn c u..

,a m.

..m u_

_+

(8) The trip setpoint shall be set sufficiently high to prevent spurious alarms / trips yet sufficiently low to assure an alarm / trip should a fuel handling accident occur.

  • Variable setpoints are for use only during normal, controlled plant heatups and cooldowns.
    • Above normal background.

SAN ONOFRE - UNIT 3 3/4 3-26 AMENDMENT NO.

ATTACHMENT "E" POST PCN-299 (TECHNICAL SPECIFICATION IMPROVEMENT PROGRAM) SPECIFICATIONS UNIT 2

CRIS 3.3.9 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.9.2 Perform a CHANNEL FUNCTIONAL TEST on 92 days required CRIS radiation monitor channel.

Verify CRIS high radiation setpoint is 5 4E2 cpm above normal background.

I i

SR 3.3.9.3


NOTE-------------------

Surveillance of Actuation Logic shall include the verification of the proper operation of each initiation relay.

4 e

a Perform a CHANNEL FUNCTIONAL TEST on 18 months required CRIS Actuation Logic channel.

l SR 3.3.9.4 Perform a CHANNEL CALIBRATION on required 18 months l

CRIS radiation monitor channel.

SR 3.3.9.5 Perform a CHANNEL FUNCTIONAL TEST on 18 months l

required CRIS Manual Trip channel.

1 j

I L

a j

i i

SAN ONOFRE--UNIT 2 3.3-41 AMENDMENT NO.

I

ATTACHMENT "F" POST PCN-299 (TECHNICAL SPECIFICATION IMPROVEMENT PROGRAM) SPECIFICATIONS UNIT 3

'CRIS 3.3.9

)

SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY 1

SR 3.3.9.2 Perform a CHANNEL FUNCTIONAL TEST on 92 days required CRIS radiation monitor channel, i

l Verify CRIS high radiation setpoint is 5 4E2 cpm above normal background, t

i 1

SR 3.3.9.3


NOTE-------------------

2 Surveillance of Actuation Logic shall include the verification of the proper operation of each initiation relay.

i Perform a CHANNEL FUNCTIONAL TEST on 18 months

{

required CRIS Actuation Logic channel.

1 j'

SR 3.3.9.4 Perform a CHANNEL CALIBRATION on required 18 months CRIS radiation monitor channel.

i SR 3.3.9.5 Perform a CHANNEL FUNCTIONAL TEST on 18 months required CRIS Manual Trip channel.

i 1

i l

4 4

j SAN ONOFRE--UNIT 3 3.3-41 AMENDMENT NO.

i I

)

l l

ATTACHMENT "G" PROPOSED SPECIFICATIONS Unit 2 4

CRIS 3.3.9 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY 4

l gc,g-Y73 SR 3.3.9.2 Perform a CHANNEL FUNCTIONAL TEST on 92 days required CRIS airborne radiation monitor channel.

Verify CRIS high radiation setpoint is N

5 4E2 cpm above normal background.

Sy A i

i SR 3.3.9.3


NOTE-------------------

Surveillance of Actuation Logic shall include the verification of the proper operation of each initiation relay.

h Perform a CHANNEL FUNCTIONAL TEST on 18 months required CRIS Actuation Logic channel.

SR 3.3.9.4 Perform a CHANNEL CALIBRATION on required 18 months Ig y$P CRIS airborne radiation monitor channel.

j SR 3.3.9.5 Perform a CHANNEL FUNCTIONAL TEST on 18 months required CRIS Manual Trip channel.

SAN ON0FRE--UNIT 2 3.3-41 AMENDMENT NO.

ATTACHMENT "H" PROPOSED SPECIFICATIONS Unit 3 l

4 a

-a~

CRIS i

3.3.9 i

SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.9.2 Perform a CHANNEL FUNCTI0ilAL TEST on 92 days lf4byp required CRIS airb~orne~ radiation monitor channel.

Verify CRIS high* radiation setpoint is N

5 4E2 cpm above normal background.

g. i SR 3.3.9.3

NOTE-------------------

Surveillance of Actuation Logic shall include the verification of the proper operation of each initiation relay.

Perform a CHANNEL FUNCTIONAL TEST on 18 months required CRIS Actuation Logic channel.

SR 3.3.9.4 Perform a CHANNEL CALIBRATION on required 18 months lfggy CRIS ' airborne radiation monitor channel.

i SR 3.3.9.5 Perform a CHANNEL FUNCTIONAL TEST on 18 months l

required CRIS Manual Trip channel.

l SAN ONOFRE--UNIT 3 3.3-41 AMENDMENT N0.

.