ML20078H161

From kanterella
Jump to navigation Jump to search
Application for Amends to Licenses NPF-10 & NPF-15 Re Changes to TS 3/4.3.2, ESFAS, to Provide for Installation of Enhanced Degraded Voltage Protection Sys
ML20078H161
Person / Time
Site: San Onofre  Southern California Edison icon.png
Issue date: 02/02/1995
From: Rosenblum R
SOUTHERN CALIFORNIA EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20078H163 List:
References
NUDOCS 9502060089
Download: ML20078H161 (21)


Text

,

l f~5A b Southem Calibmia Edison Company j 23 "'ARME R STREET 1RVIN E, C ALWORNIA 92788 I

"'*"^*",,"f',"*""

, February 2, 1995 ,l.7((fll.

U.S. Nuclear Regulatory Commission Attention: Documeat Control Desk Washington, D.C. 20555 Gentlemen:

Subject:

Docket Nos. 50-361 and 50-362 Supplement 1 to Amendment Application Nos. 136 and 120 Change to Technical Specifications 3/4.3.2,

" Engineered Safety Features Actuation Systems," j San Onofre Nuclear Generating Station, Units 2 and 3  ;

References:

See Enclosure 1 f By letter dated September 30, 1993, (Reference 1) Southern California Edison  !

(Edison) submitted Amendment Application Nos. 136 and 120 to Facility Operating Licenses NPF-10 and NPF-15, respectively, for the San Onofre Nuclear Generating Station, Units 2 and 3. These Amendment Applications consisted of Proposed Change Number (PCN) 429. PCN 429 requests changes to Technical i Specification (TS) 3/4.3.2, " Engineered Safety Features Actuation Systems  !

(ESFAS)." These changes provide for installation of an enhanced degraded voltage protection system.

Provided as Enclosure 2 is Supplement I to Amendment Application Nos. 136 and 120. Supplement 1 is being submitted to expand the response time testing i requirements for the new degraded voltage protection signals, Sustained -

Degraded Voltage Signal (SDVS) and Degraded Grid Voltage with Safety Injection Actuation Signal (SIAS) Signal (DGVSS).

PCN 429 provided overall response times for these two signals. These overall j response times were based on the summation of the time delays for the  !

individual sensing relays. The time delays for the individual sensing relays j were to be verified according to procedures. Such verification, however, would not have been specifically required by the TSs proposed by PCN 429. 1 This was because the overall response time requirement was sufficient to assure that the safety function of the enhanced degraded voltage protection I system would be met. J It was realized during discussions with the NRC in support of the Technical Specification Improvement Project (TSIP) that additional TS response time requirements should be provided. This is to provide assurance that the sensing window for the DGVSS would not oper before 4.3 seconds following a Safety Injection Actuation Signal (SIAS). Opening this sensing window too early could lead to a spurious DGVSS trip because the degraded voltage sensors 9502060089 950202 PDR P

ADOCK 05000361 pf p

PDR

/l

f[5 Document Control Desk would be activated during a voltage dip caused by load sequencing, thus creating an apparent degraded voltage on the grid. '

Suppitment I to PCN 429 provides allowable response time values for each degraded voltage relay. The relays for SDVS are given individual response times to maintain consistency within the TS. i Since PCN 429 was submitted, the response time for relay 162T has been i reanalyzed. The allowable ran  :

0.85 seconds to 1.65 seconds1.25 (geseconds for the response time ofPreviously i 0.4 seconds). relay 162Tthis is now allowable response time had been reported as 1.5 seconds i 0.15 seconds.

Because the longest allowabl. response time for this relay (1.65 seconds) has not changed, this change has no effect on the overall proposed response time for the DGVSS of 6.14 seconds. This change is discussed in Reference 6 and is reflected in Supplement 1.

Similarly, for the Sustained Degraded Voltage Signal (SDVS), the response time for relay 162D has teen reanalyzed from 120 seconds i 12 seconds to 110 seconds i 22 seconds. A this relay (132 seconds) has gain,not because changed,thethere longest allowable is no effect onresponse time for the overall response time of 134.2 seconds for SDVS. This change is discussed in l Reference 6 and is reflected in Supplement 1.

PCN 429 proposed Note 10 to Table 3.3-5 to clarify that the DGVSS response j times were measured from initiation of SIAS. The format of the proposed response time requirements in Supplement I show this explicitly. Therefore, proposed Note 10 is no longer necessary and is withdrawn by Supplement 1.

The additions to PCN 429 are shown highlighted and the deletions are shown as  !

lined out.

PCNs 401, 405, and 431, (References 2, 3, and 4) also requested changes to portions of TS 3/4.3.2. Both the proposed changes from PCNs 401, 405, and 431 i which affect the pages of PCN-429 and the proposed changes of this Supplement to PCN-429 are marked in Enclosure 3. PCN 401 has been approved since the submittal of PCN 429. Therefore, in the proposed pages of Supplement 1 ,

(Enclosure 2) and the pages of Enclosure 3, the changes from PCN 401 appear as existing TSs.

By Reference 5, Edison submitted PCN 299, " Technical Specification Improvement  ;

Project (TSIP)." Harkups of the proposed TSIP pages, including the proposed l changes resulting from this supplement to PCN 429, are shown in Enclosure 4.  !

The enhanced degraded voltage protection system for Unit 2 is planned for installation during the Unit 2 Cycle 8 refueling outage. The enhanced .

degraded voltage protection system is already installed, although not I currently in use, at San Onofre Unit 3. Edison has currently scheduled replacement of some defective relays on the Unit 3 system. This will require testing of the system before it is declared OPERABLE for use in the plant.

Therefore, to avoid the necessity of on-line channel functional testing, Edison requests allowance that implementation of this TS change for Unit 3 be I

/* ""

Document Control Desk delayed until Unit 3 Cycle 8 refueling outage ulose breakers (currently scheduled for September 11,1995), or with,in 30 days of issuance of the amendments, whichever is later.

If you would like additional information regarding this Technical l Specification change request, please let me know. l l

Sincerely,

. 1

'M l Enclosures cc: L. J. Callan, Regional Administrator, NRC Region IV A. B. Beach, Director, Division of Reactor Projects, NRC Region IV K. E. Perkins, Jr., Director, Walnut Creek Field Office, NRC Region IV J. A. Sloan, NRC Senior Resident Inspector, San Onofre Units 2 and 3 M. B. Fields, NRC Project Manager, San Onofre Units 2 and 3 H. Kocol, California Department of Health Services ,

e 4

i l

f ENCLOSURE 1 References 1

I

(

l l

l

_ I

l REFERENCES

1) September 30, 1993, letter from R. M. Rosenblum (Edison) to Document Control Desk (NRC),

Subject:

Amendment Application Nos. 136 and 120, Change to Technical Specifications 3/4.3.2, " Engineered Safety Features Actuation Systems," San Onofre Nuclear Generating Station, Units 2 and 3

2) April 7, 1992, letter from Harold B. Ray (Edison) to Document Control Desk (NRC),

Subject:

Amendment Applications 115 and 99, Change to Technical Specifications Tables 3.3-3, 3.3-4, 3.3-5, and 4.3-2, " Engineered Safety Features Actuation Systems," San Onofre Nuclear Generating Station, Units 2 and 3 3)

December Desk (NRC), 30,,

Subject:

1992, letter Amendment from Harold Applications B. Ray 129 and 113, (Edison) to Document Cont Changes to Technical Specifications 3/4.3.2 and 3/4.3.3, San Onofre Nuclear Generating Station, Units 2 & 3

4) September 16, 1993, letter from Richard M. Rosenblum (Edison) to Document l Control Desk (NRC),

Subject:

Amendment Applications 134 and 118, Automatic Removal of Low Pressurizer Pressure Trip Bypass, San Onofre Nuclear Generating Station, Units 2 and 3

5) December 30, 1993, letter from R. M. Rosenblum (Edison) to Document Control Desk (NRC),

Subject:

Proposed Change Number 299, Technical Specification Improvement Project, San Onofre Nuclear Generating station, Units 2 and 3

6) January 18, 1995, letter from W. C. Marsh (Edison) to Document Control Desk (NRC),

Subject:

Additional Information for Amendment Application Nos.136 and 120, " Degraded Grid Voltage" San Onofre Nuclear Generating Station Units 2 and 3 '

I i

i ENCLOSURE 2  !

SUPPLEMENT 1 TO PCN 429 DEGRADED GRID VOLTAGE  !

l l

l J

5 i

UNITED STATES OF AMERICA

@ CLEAR REGULATORY COMMISSION I Application of SOUTHERN CALIFORNIA ) Docket No. 50-361 EDIS0N COMPANY, ET AL. for a Class 103 )

License to Acquire, Possess, and Use )

a Utilization facility as Part of ) Amendment Application Unit 2 of the San Onofre Nuclear ) No.136R~Ssppliiiiiht?1.

Generating Station )

" ^~~~~~

SOUTHERN CALIFORNIA EDIS0N COMPANY, ET AL. pursuant to 10 CFR 50.90, hereby submit Amendment Application No.136]Qup@emejg.

f This amendment application consists of proposed Technical Specification '

Change No. NPF-10-429, $sgniQtl[1] to Facility Operating License No. NPF-10.  !

Proposed Technical Specification Change NPF-10-429, [s@jMijt]R will revise  :

Technical Specification 3/4.3.2, " Engineered Safety Features Actuation Systems." '

This proposed change reflects the planned enhancement to the degraded voltage protection scheme to protect against the recently racognized possibility of i 1

sustained degraded. grid voltage conditions.

Subscribed on this c2nd day of FERuM/ , 1995.

Respectfully submitted, SOUTHERN CALIFORNIA EDIS0N COMPANY

?

By:

b, j // .) /

KulwJH/_ ~

Richard M. Rosenblum Vice President i

State of California County of Orange /, pu du c.,

On _ 2 /.2 / 0 5 before me,3& BRA A N'CM/, ggy personally appeared &k N N D M. 2c.s m hud, personally known to me to be the person whose name is subscribed to the within instrument and acknowledged to me that he executed the same in his authorized capacity, and that by his signature on the instrument the person, or the entity upon behalf of which the person acted, executed the instrument. i WITNESS my hand and official seal.

omen un l itAAJ & .

,,gnature j

@ BARBAllA ORANGE gm%

44sch 31,1996 l

1 i

I l

1 l

l

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION Application of SOUTHERN CALIFORNIA ) Docket No. 50-362 EDISON COMPANY, ET AL. for a class 103 )

License to Acqu',re, Possess, and Use )

a Utilization Facility as Part of ) Amendment Application Unit 3 of the San Onofre Nuclear ) No.120.jlS6@lbinehB1.

Generating Station )

"""*"~"~^

SOUTHERN CALIFORNIA EDISON COMPANY, EI.AL. pursuant to 10 CFR 50.90, hereby submitAmendmentApplicationNo.120,)ppgembjQJ.

e This amendment application consists of proposed Technical Specification j

Change No. NPF-15-429, Sppp]jmEh{lQ*;,) to Facility Operating License No. NPF-15.

Proposed Technical Specification Change NPF-15-429, $6pp]jge{t}{Q] will revise Technical Specification 3/4.3.2, " Engineered Safety Features Actuation Systems." l This proposed change reflects the planned enhancement to the degraded voltage  ;

l protection scheme to protect against the recently recognized possibility of sustained degraded grid voltage conditions.

f f

[

l l

I

Subscribed on this c2nd day of F66#a M Y , 1995.

Respectfully submitted, SOUTHERN CALIFORNIA EDISON COMPANY b

By:

a

<4<

/

Richard M. Rosenblulii Vice President i

State of California ,

of Orange paduG County On 3 /2/95 before me, BARMLA A N'UL7NY,g7pf

/

y 11y I persona appeared FicNAAD M. ~4'e.sr4hn, personally known to me to be the person whose name is subscribed to the within instrument and acknowledged to me that he executed the same in his authorized capacity, and that by his signature on the instrument the person, or the entity upon behalf of which the person acted, executed the instrument.

WITNESS my hand and official seal.

P-~- --~

OFFICIAL SEAL

' BARIRRA A MC CARTHY ]

Signature , h O- '

=-%

S'" " 5 31, 1996 1

l 1

1

I DESCRIPTION AND SAFETY ANALYSIS  !

0F PROPOSED CHANGE NPF-10/15-429pl{Su@jssrig1;

'This is a request'to revise Technical Specification (TS) 3/4.3.2, " Engineered Safety Feature Actuation Systems (ESFAS) Instrumentation," Figure 3.3-1 and i Tables 3.3-3, 3.3-4, 3.3-5, and 4.3-2 to reflect implementation of the enhanced degraded voltage protection scheme. i Existina Soecifications Unit 2: Attachment "A" i Unit 3: Attachment "B" Proposed Specifications i l Unit 2: Attachment "C" l Unit 3: Attachment "D" l

Descriotion The following changes are proposed for the San Onofre Units 2 and 3 Technical Specifications (TSs):

1. Revise heading of item 7 of Tables 3.3-3, 3.3-4, and 4.3-2, to read

" Loss of Power (LOVS, SDVS, or DGVSS)" to reflect that undervoltage protection is now provided through more than one signal.

l l

2. Delete the-phrase "and degraded voltage" from item 7a of Tables j 3.3-3, 3.3-4, 3.3-5, and 4.3-2 to reflect that degraded voltage  ;

protection will be separate from loss of voltage protection. ,

3. Replace the reference to Figure 3.3-1 with definite voltage and time I i

characteristics in item 7a of Tables 3.3-4 and 3.3-5. l l

4. Add item 7b, "4.16 kV Emergency Bus Undervoltage (Degraded Voltage),  !

to Tables 3.3-3, 3.3-4, and 4.3-2.

5. Add footnote "d" to Table 3.3-3. This footnote will read,

" Applicability for SDVS is Modes 1, 2, 3, and 4 when the diesel generator circuit breaker is open."

6. Add item 7b, " Degraded Voltage," to Table 3.3-5, to provide response times for the Sustained Degraded Voltage Signal and the Degraded Grid Voltage with SIAS Signal.
7. Add Notes 9 :nd 10 to Table 3.3-5. Note 9 clarifies that the 1.05 l second response time for a Loss of Voltage Signal is for a step  !

voltage change from nominal bus voltage to 0.0 volts. ht: 10 1

-1: rift:0 th:t th: r::p:n:: tim: for th: Degr:d:d Crid " lt:g: With SIAS Signal i: ::::ured frc: initi: tion Of : SIAS.

l l

8. Delete item 4 of Table 3.3-4, " Table Notation," to reflect that Figure 3.3-1 is being deleted. 1
9. Delete Figure 3.3-1, " Degraded Bus Voltage Trip Setting."

Backaround With the shutdown of Unit 1, Southern California Edison (SCE) performed a new grid stability study to confirm that 218 kV will be maintained at the San Onofre Nuclear Generating Station (SONGS) 230 kV switchyard under all required postulated scenarios. SCE has determined that 218 kV will be maintained under all conditions with the following exception:

1) only one SONGS unit is on line, and
2) a major transmission line or tower is lost, and
3) SCE system load exceeds specified thresholds (typical of system loading on a weekday summer afternoon)

Should a subsequent trip of the operating cnit occur, the voltage at the switchyard could drop below the minimum analyzed value of 218 kV. SCE has implemented procedure changes as a short term compensatory action to mitigate the consequences of low switchyard voltage. These procedures require the SCE Energy Control Center Operator to notify the San Onofre Control Room whenever the three conditions stated above exist. The San Onofre Control Room Operator would then declare the offsite source INOPERABLE and enter the appropriate action statement. The Class lE buses in the operating unit will then ne manually transferred from their Reserve Auxiliary Transformer to the Unit Auxiliary Transformer. Because the Unit Auxiliary Transformer will be tripped on a Unit trip, a Loss of Voltage Signai (LOVS) will be generated and the Class IE buses will shed their loads and automatically transfer to their respective Emergency Diesel Generators (EDGs).

Although these scenarios will still' require operator f action, as a long term measure to ensure that adequate voltage is" maintained at'the Class lE buses at

~~

all voltage levels under the conditions stated abeve, SCE plans to enhance the j existing degraded voltage protection scheme to provide more reliable protection against a degraded grid. This enhancement will also transfer ead 4.16 kV C1,ss IE bus directly to the standby power source when a loss of voltage or degraded I voltage condition exists concurrent with a Safety injection Actuation Signal (SIAS). This eliminates the time delay inherent in the existing scheme wherein the logic first seeks the alternate preferred power source before transferring I the buses to the standby power source. This enhancement requires installation )

of new relays to perform the degraded voltage trip function. l This proposed TS change is being submitted to reflect the new undervoltage protection scheme.

I l

Existino Desian The power sources to the Train A Class IE 4.16 kV buses for SONGS Units 2 and 3 are provided in Figure 2. Train B has the same configuration.

The existing undervoltage trip channels are provided to detect a loss of voltage at the Class 1E 4.16 kV buses. In addition, this scheme also provides protection to the onsite power system during sustained degraded voltage conditions. This loss of voltage and degraded voltage protection is currently provided by a single set of induction disc-type relays with an inverse-time characteristic. The time-voltage characteristic curve of the relay is shown in TS Figure 3.3-1, " Degraded Bus Voltage Trip Setting." The relay setpoint is 3675V, (88.3% of 4.16 kV). If a complete loss of voltage occurs, t.he scheme will initiate a loss of Voltage Signal (LOVS) after 1 second. For a degraded voltage condition, the scheme initiates a delayed LOVS. The LOVS actuation time would be dependent upon the severity of the degraded voltage condition at the Class IE 4.16 kV bus. This design was approved in the NRC Safety Evaluation Report (SER) dated February 6, 1981.

For both types of undervoltage conditions, the LOVS first attempts to transfer the 4.16 kV Class IE buses to the alternate preferred power source through the cross-tie breaker to the companion Unit at the 4.16 kV level. Upon receipt of the LOVS, the auxiliary relays associated with the undervoltage protection ,

scheme will 1) trip the associated 4.16 kV Class IE bus source breaker and 2) l send a start signal to the associated diesel generator. After the residual voltage at the 4.16 kV Class IE bus has decayed to approximately 30%, the cross- i tie breakers close, switching the bus to the alternate preferred power source.

Within 4 seconds after the LOVS is initiated, if the connection to the cross-tie is unsuccessful, all loads connected to the 4.16 kV Class IE bus are shed except  ;

the 480V Class IE load center, so as to limit startup in-rush currents. The bus  !

is then connected to the diesel generator within 10 seconds following the LOVS.

10CFR50, Appendix A, General Design Criterion (GDC) 17 requires that two physically independent connections to the offsite transmission network be available. One of these two connections must be available within a few seconds following a Loss of Coolant Accident (LOCA). Because the existing design for Units 2 and 3 provides two immediate access circuits from the preferred power system to the onsite emergency buses, the requirements of Criterion 17 are exceeded. This is documented in the SER.

With the existing design, if a degraded voltage condition occurs following a Safety Injection Actuation Signal (SIAS), the unit experiencing a trip will attempt to transfer its 4.16 kV Class 1E buses through the cross-tie to the companion unit. l However, because the switchyard, which is common to both units,  ;

could be in a degraded condition, the alternate preferred power source would also be degraded. Following an additional 4 second delay, the unit would then 1 j'

transfer its 4.16 kV Class IE buses to the diesel generators, which would have started on receipt of the SIAS. Under this scenario it would be preferable to transfer the 4.16 kV Class IE buses directly to the standby power source. This direct transfer would eliminate the unnecessary delays that would exist if the buses were to first attempt to transfer to the alternate preferred power source, and then transfer to the standby power source.

4

. ._ - = . _ . - .. - -

l l

Planned Desian In order to provide more reliable protection against a degraded grid and also to allow the 4.16 kV Class lE buses of the affected unit to go directly to the standby power source in case of a SIAS with a loss of voltage or degraded voltage condition, SCE is planning to modify the existing LOVS logic and install ,

a separate degraded voltage protection scheme. The logic diagram for the new ,

configuration is shown in Figure 1.

The existing LOVS trip function without SIAS will be unaffected by this change. i Relays 127F1, 127F2, 127F3, and 127F4 will still provide the LOVS trip for a complete loss of voltage. This signal will still connect the affected unit to the alternate preferred power source if it is available, and then to the standby 1 power source if the alternate preferred power source is unavailable. However, with the new configuration, LOVS with SIAS will transfer the 4.16 kV Class IE bus directly to the standby power source.

The time-voltage characteristic of the new LOVS trip will be identical to the  :

existing inverse time delay. The proposed TS time-voltage setting requirements  ;

are bounding values which will replace the curve in Figure 3.3-1. i The degraded voltage condition will be detected by new definite time delay solid state relays 127DI, 127D2, 127D3, and 127D4. These relays will be connected to the same set of bus potential transformers as the existing relays 127F1,127F2, 127F3, and 127F4. The new 1270 relays are set at 4228 V, with a definite time delay setting of 2.0 seconds. This voltage setting will assure adequate voltage at the terminals of all engineered safety features equipment based on a  :

switchyard minimum allowable voltage of 218 kV. The voltage setting of 4228 V  :

is below the voltage normally expected at the 4.16 kV level (4360 V or above) '

with switchyard voltage of 230 kV. Therefore, under normal operating conditions a spurious actuation is not expected.

The new relays, in conjunction with the timing relays 162S1 and 162T1, 162S2 and 162T2, 162S3 and 162T3, and 162S4 and 162T4, will provide the Degraded Grid Voltage with SIAS Signal (DGVSS). ?The voltage and time delay settings are such that a sensing window will open with a time delay of apprcximately 4.3 4.3ft 0.19 seconds after initiation of SIAS. This window will remain open for appred mately 1.5 1125 1 0.40 seconds, during which time a DGVSS will be initiated if a degraded voltage condition is established. Upon initiation of ,

the DGVSS, the 4.16 kV Class lE buses will be transferred directly to the standby power source rather than to the alternate preferred power source, which ,

is likely to also be experiencing a degraded voltage.

The 4.3 second time delay for this signal is initiated by SIAS, and is independent of the time delay chosen for sustained degraded voltage protection.

This time delay is chosen to 1) ride through the voltage transients and 2) to ensure that adequate voltage is available on the Class 1E bus during post-accident emergency safety feature load sequencing. Following acceleration of the first load group during post-accident load sequencing, the degraded voltage scheme will have ar, approximately 1.5 1.25~i;0.40 second window in which to sense the voltage on the 4.16 kV Class'IE bus. 'If the voltage is below the

~

l l

l l

degraded voltage setpoint, the Class IE bus will separate from the preferred i power source and transfer to the standby power source. -

The same 12701, 127D2, 127D3, and 127D4 relays are also used for sustained ,

degraded voltage protection when the diesel generator is not supplying the 4.16 ,

kV Class IE bus. A Sustained Degraded Voltage Signal (SDVS) is generated with the associated timing relays 162D1, 162D2, 162D3, and 162D4 within 4M 134;2 seconds so that permanently connected class IE equipment will not be damaged.  !

If a SIAS signal is present, SDVS will transfer the 4.16 kV Class IE buses directly to the standby power source. If a SIAS signal is not present, SDVS will transfer the 4.16 kV Class lE buses to the alternate preferred power j source.

If the alternate source is not available, the buses will transfer to the standby power source.

This new configuration provides two independent connections from the offsite  ;

transmission network to the onsite emergency buses. Because only one of these ,

connections provides immediate access to the offsite transmission network, this ,

configuration no longer exceeds the requirements of GDC 17, as does the existing configuration. However, this configuration meets the requirement in that one of  :

the two offsite circuits is immediately available following a LOCA.

The 12701, 127D2, 127D3, and 127D4 relays are also used for annunciation of a  !

sustained degraded voltage condition at the 4.16 kV Class lE bus within approximately 7 seconds. The existing 127L undervoltage annunciation will be ,

deleted.  ;

A two-out-of-four actuation logic similar to that of the existing configuration  ;

protects against spurious actuation.  ;

Standard Review Plan, section 8.3, Branch Technical Position PSB-1, " Adequacy of i Station Electrical Distribution System Voltages," describes the basis for '

acceptability of an undervoltage trip function. In addition to the ability to detect a loss of offsite power at the Class IE bus, a second level of i undervoltage should have the ability to separate the Class lE distribution  !

system from the offsite power system following a SIAS, to alert the control room of a degraded condition, and to have the ability to detect a sustained degraded condition. The new undervoltage configuration meets the intent of these guidelines.

i This planned configuration ensures that adequate voltage is maintained at the  :

Class IE 4.16 kV buses for all cases except one. With heavy system loading on the offsite transmission grid and only one SONGS unit on-. 'e during an outage of the Imperial Valley-Miguel 500 kV line and the Imperia / alley-Rosita 230 kV line, followed by a trip of the operating SONGS unit, the voltage at the SONGS i 230 kV switchyard will not return to a stable level. Instead, the grid voltage, I will oscillate in such a manner that the relays may not detect an undervoltage l condition. For this condition only, pending further evaluat4en, SCE plans to continue using the procedures that are currently in place as short term compensatory actions. SCE and San Diego Cas and Electric (SDC'.E) are evaluating 9Md-improvement which may climinate this condit4en6 For. the cases Lwhich are protected by'the; planned enhancement,' Edisoniwillf,till declare the offsite power sources _ inoperable' whenever the p're-trip conditionsL exist.

Discussion This proposed change separates the loss of voltage channel from the degraded voltage channel in item 7a of TS Tables 3.3-3, 3.3-4, 3.3-5, and 4.3-2. The new channel is added as item 7b to the Tables. These tables outline instrumentation, trip values, response time, and surveillance requirements for the Emergency Safety Features Actuation Systems (ESFAS) channels, including the loss of voltage and degraded voltage channels.

The new entry in Table 3.3-3 for the degraded voltage trip requires a total of 4 channels per bus, with a minimum of two channels per bus to trip and a minimum of 3 channels OPERABLE per bus. The new degraded voltage function is required to be OPERABLE in Modes 1 through 4. With one less than the total number of channels OPERABLE, power operation may continue provided the INOPERABLE channel is bypassed or placed in a tripped condition within I hour. With the number of channels OPERABLE one less than tha minimum required, power operation may continue provided that one of the INOPERABLE channels is bypassed and the other is placed in the tripped condition- These requirements are identical to the instrumentation requirements for the existing LOVS channel, and therefore provide the same level of assurance of operability as the existing requirements for the existing undervoltage scherie.

Footnote d is added to Table 3.3-3 to reflect that SDVS is not required to be OPERABLE when the diesel generator is in parallel with the offsite source or is supplying the 4.16 kV Class IE bus. This is because an undervoltage trip for a degraded voltage condition is not desirable when the standby power source is already in use. LOVS will remain in service when the diesel generator is in parallel with the offsite source or is supplying the 4.16 kV Class IE buses.

LOVS remains OPERABLE in order to detect more significant undervoltage conditions. DGVSS also remains OPERABLE to detect degraded voltage on the offsite sources following a LOCA.

When the diesel generator is in parallel with the offsite source for surveillance testing, a degraded voltage condition will cause control room annunciation as discussed above. After the alarm the emergency diesel generator and the offsite power would be separated. If a sustained degraded voltage condition is encountered while only the diesel generator is supplying the 4.16 kV Class IE bus, control room annunciation occurs, and action may be taken to return to the offsite sources, if available.

The proposed trip value of 3675 V for the loss of voltage signal is identical to the bounding value for the range of voltage settings in the existing figure

3.3-1. The proposed allowable value range is based on the proposed setting of 3675 V plus or minus a tolerance of 121 V (3.3%) to account for total loop uncertainty.

The proposed trip value of 4228 V for the degraded voltage signal will assure adequate voltage at the terminals of all engineered safety features equipment based on a switchyard minimum allowable voltage of 218 kV. The voltage setting of 4228 Y is below the voltage normally expected at the 4.16 kV level (4360 V or above) with switchyard voltage of 230 kV. Therefore, under normal operating conditions a spurious actuation is not expected. The allowable value range for

the degraded voltage trip is based on the proposed trip setting of 4228 V, plus or minus an allowance of 47 V.

The response time requirements for the new degraded voltage protection scheme will ensure that in a sustained degraded voltage condition, an SDVS will be generated within W 13412 seconds (based on a time delay of 2.0 +/- 0.2 seconds for the undervoltage" detection relays plus 120 :/ 12.0110T22 seconds for the when voltage at the 4.15~kV Class IE bus is less degraded than 4228 V.voltage timing relays)ll response time r:q;ir ;;nt of M134;2 seconds The peepesedovera ensures that permanently cbnnected Class IE equipment will not be ' damaged.

The peepesed iserall response time r:q;ir:::nt of 6.14 seconds for Degraded Grid Voltage with SIA51111 also ensure that if a degraded voltage condition exists with SIAS, the 4.16 kV Class IE bus will transfer directly to the standby power source within 10 seconds. The response time r:q !r :nt of 6.14 seconds is based on the requirementiforia 4.3 +/- 0.19 second delay between initiation of SIAS and initiation of thE" degraded voltage sensing window, plus the requirement

[orTa1.5;/ 0.151.25;110j4, second duration of the degraded voltage sensing ~

window.

The 1.05 second response time for the LOVS signal is based on a step change from nominal bus voltage to 0.0 volts. The 5.11 ::: nd rc: pen:: ti;; f r th OC"SS i; ::::ured fr ; initi tion Of the SIAS, n:t detecti:n of d:;;r:d:d v lt:;;.

Notes 9 :nd 10 cr:isladded to Table 3.3-5 to clarify 4Aesethis stipulat'.ons.

The Surveillance Requirements for the new degraded voltage trip require a channel check once every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, and a channel calibration and functional test every refueling interval. These requirements must be met to allow operation in Modes 1 through 4. These Surveillance Requirements are identical to those for the existing loss of voltage trip function.

Item 4 of the " Table Notation" of TS Table 3.3-4 is deleted to reflect that Figure 3.3-1 is being deleted. Figure 3.3-1 is deleted to reflect that the degraded voltage function is no longer associated with the loss of voltage relays. The degraded voltage trip will have a definite voltage setting and time delay. The loss of voltage trip will still have inverse time delay characteristics but will have a voltage setting of 3675 V, which is identical to the existing voltage setting from Figure 3.3-1, and a time delay of 1.05 seconds  !

for a step loss of voltage from nominal bus voltage to 0.0 volts. Therefore, l the curve in Figure 3.3-1 is no longer necessary.

Safety Analysis The proposed change described above shall be deemed to involve a significant  !

hazards consideration if there is a positive finding in any one of the following l areas:

1: Will operation of the facility in accordance with this proposed change involve a significant increase in the probability or consequences of an accident previously evaluated?  !

Response: No l

This proposed change reflects separation of the loss of voltage and degraded voltage function into separate Emergency Safety Features Actuation Systems (ESFAS) schemes. This configuration meets the intent of Standard Review Plan, Section 8.3, PSB-1.

Instrumentation, trip setting, response time, and surveillance requirements are added for the new schemes. The new configuration accomplishes both the existing loss of voltage and degraded voltage trip functions.

In addition, for loss of voltage and degraded voltage conditions following a Safety Injection Actuation Signal (SIAS), the affected unit is connected to the standby power source without first attempting to connect to the alternate preferred power source through the cross-tie to the companion unit, thus ensuring that power is available within 10 seconds following the SIAS. This is accomplished by the new trip functions Loss of Voltage Signal (LOVS) with SIAS and Degraded Grid Voltage with SIAS Signal (DGVSS).

While automatic transfer to the alternate preferred power source is normally desirable during undervoltage conditions, the proposed configuration is necessary because following the SIAS there is the possibility of the alternate preferred power source being in a degraded condition, resulting in a delay before power becomes available to safety-related equipment. The proposed configuration assures that this delay will not occur and power is available to safety-related equipment within the time allowed by the safety analyses. Therefore, there is no significant increase in the probability or consequences of any accident previously evaluated.

2: Will operation of the facility in accordance with this proposed l change create the possibility of a new or different type of accident '

from any previously evaluated?

Response: No This proposed change reflects separation of the loss of voltage and degraded voltage function into separate (ESFAS) relays. The proposed TSs for the new configuration maintain the same instrumentation and surveillance requirements as the existing TS with the exception of the applicability of the SDVS OPERABILITY requirements. SDVS is not required to be OPERABLE when the emergency diesel generator (EDG) is parallel to the offsite source or is supplying the 4.16 kV Class IE bus because an undervoltage trip for a degraded condition is not desirable when the standby power source is already in use. The LOVS and DGVSS will remain OPERABLE. Control room annunciation of bus low voltage is provided to cause operator action to separate the EDG and the offsite power source.

The proposed voltage setting of 3675 V for the loss of voltage trip is identical to the bounding value of the range of voltage settings l in the existing Figure 3.3-1. The proposed allowable value range of l

i l

, _ _ _ . _ __ ~_ _ _ _ . . __ __ __

l

.g.

i 3554 V to 37g6 V for the loss of voltage trip is based on the existing trip setting plus or minus a 3.3% tolerance. The proposed  :

trip value of 4228 V for the degraded voltage signal provides i assurance that adequate voltage is seen at the terminals of all ,

safety-related equipment. The allowable value range of 4181 V to j 4275 V for the degraded voltage trip is based on the 4228 V trip l value plus or ninus a 47 V tolerance. ,

The proposed response time for the loss of voltage signal is a bounding value to replace the time voltage curve of figure 3.3-1, '

which is being deleted by this proposed change. For a completa loss of voltage (0.0 V), a loss of volta e si nal will be generated ,

l within 1.05 seconds. The 1 response time coqu4 cement "

for degraded voltage of 446 I sk66ds* ensures that permanently connected Class IE equipment Ili not be damaged. The b~r~erall '

response time of 6.14 seconds for the DGVSS will also ehsLis that if  ;

a degraded voltage condition exists with SIAS, the 4.16 kV Class IE  ;

bus will transfer directly to the standby power mode within 10 l seconds. The proposed Notes g end-40 to Table 3.3-5 ace lqi' clarificatione only.

The two-out-of-four actuation logic provides protection against  !

spurious actuation. The additional functions of DGVSS, LOVS with  !

SIAS and Sustained Degraded Voltage Signal (SDVS) with SIAS provide  !

a faster transfer to standby power under SIAS conditions. The new configuration meets the requirement of General Design Criterion 17 in that one offsite circuit will be immediately available following a Loss of Coolant Accident. Therefore, there is no possibility of a new or different type of accident than any previously evaluated.

3: Will operation of the facility according to this proposed change involve a significant reduction in a margin of safety?

Response: No The DGVSS, LOVS with SIAS and SDVS with SIAS will provide a faster and more reliable transfer to standby power than the existing configuration. The proposed TS changes provide instrumentation, trip setting, response time, and surveillance requirements consistent with the existing design and the appropriate regulatory documents.

Safety and Sianificant Hazards Determination Based on the above Safety Analysis, it is concluded that: 1) the proposed change does not constitute a significant hazards consideration as defined by 10CFR50.92; 2) there is reasonable assurance that the health and safety of the public will not be endangered by the proposed change; and 3) this action will not result in a condition which significantly alters the impact of the station on the environment as described in the NRC Final Environmental Statement.

l

--* (- ,

.t s U l f .

.C'.0SS Tit AU70 Y.f R O!!A.!tto (stas)

".Y-

-s- ., .

1

  • 1 e 1277-1 h l sec 0 0 Vel t s

! .~ # -

~; .

f 1277-2 3 1 see C 0 Volte : .

~

j -

t O*'I j 2/4]

, -l ,

127r-s 31 ses c e vet te

)

(,o.t 1) i 127r-4 31 s e e 0 0 Vel t s *

$, A e a

it .

i .

, '{

mS N 4.3 set a g-p1

! U 181T-1 1270-1 3 2 se 1515-1 - "

, , gf_g

) e ..

a

'~'&

I 1

1270-2 3 2 see n>-

1 2r.2 3 0% ~

A 3 M/-2 l * } ' -

a i O-*

C2 -

1 1.25 sec 2/4l n.ts h 4.3 sec 9 m 8 y1 , (toi! 1)

' 117 -3 h 2 *

  • c "

1 2t-3

. L/ i - . 3 c:, 3 m0-"

9 h 4.3 s ec 8

,_s v!

1(2T4

)

  • 127>-4 h 2 s e e 1 25-4 _a ,

Y ' ) ~,

. - r,O-- J

.EDC Etxt CPI *4  !

l hQ0 sQ l] .

v 1

. 1523-1 l g

hM v

1

'h' 1620.-2 SM I i

. m ,

2/' it  ;

v *

(rote ) 1 1s2ss -

I h

v ] .

t62D-4 5 j

j i - h s see

- t . . 2 v A 152A i

mmy mucs 3 n

s. .

..x  :

\

? .{- s

.c -

p '

y. -

4 s -

_ _ _ _ . m. .u s. < tn sat

. - . . . _ _ , . --~

m *"****~8e+ oe . ommee. , _

tc/15 CR LCVS-5! AS, C4 50VS-SfAS

  • 7 [
- . STAAT DIESEL CENIRATC4 (51A5 STA?.TS DIEtEL CI'NEAATCR).

. Trip at su.CE EAEAxtr.s To mE ArrECito CtAsS 1E 4.is xv sus.

. pO/$$ INITIATE ltutDIATE BVS LCA3 SMIC31tc.

  • e ,tCt/5-S! AE $WS-51 AS INITIATE 4-SEC CELATED LCAD IMED3!t.c. * *

.ITRuitrtt TF'I At 1E

.P>tn $7AC. ESC . 4.15W EUS.70 THE tin.0SY  !

. +

SWS CA tCJS .l

  • STAAT O!E!!L CD;EPATCA. ,

I

. TRIP ALL $3ACC E?.EAXERS TO TME .ATTECTED CLATE 1E 4.tER/ EV5.

INITI ATE BUS T7xi$rER TO TEE ALTEP.' RTE FAITC?.ACO PO.!R 53.8.CC. *

. !F 4 TERNATE FRETEAAE3 POW 4 SOACE II 20T AVAjLA!LE WiiHIN

  • 4 SEC fr.04 (CYS, Ca 5 vs, IslTI ATE Sus LCA3 sx. colic. 1/t J;'

I

  • s,_

f * '{' ..k"

r "*Er

. TF.RtSTEM TEE CtLt31E 4.1Er/ BVS TO TFE StuC5Y esta soxt (to;). [i D o FCt [.'if lO' dp ~;

CARD

! l A b u d'J. Ur..Id; (l.

g n r ;'- , ,{ l' ICTE:

1. 2 OJT C# 4 (c/3 tctst Ax3 S?vS LCCIC USE int SET CF l AUXILI AAT RELAYE TC3 COiTACT l onruis.
  • 1 l '

760120/10097+/

l N

ft SONGS 2 k 3 115 CNCf tt nCLEAR CIK11111F5 5 TAI!CM LOGIC DIAGRAM CLASS 1E 4.16XV BUS Uh0EitV01.TAGi LETEC110ll g~ 50VIHERM CAllf 0RHI A EDISO!!

_ _ _ _._%_ --, flGU.RE

-- 1 ,__

~ ~ . . . . . . ~ ~ . _ _

, , '3 '


.---.-:.., ., -r-

2MEI IUS r-1 @ '

.- .. w

[] l E3

) o - - a - E I'm iR0 M 1 m ARD

{] b]

e, _

j 230KY St SUS 230KV NW BUS i

WIT 3 WIT 2 RESERVE .

RESERVE AUXILIARY AUXILIART WW TRANSFORER W W TRANSFORMER TO WIT

  • ThWIT AUXILIARY b AUXILIARY TRANSFORTR TRANSFORER 3DI i 2WI 3A04 TIE BREAKER 2A04 2A0417 TIE BREAKER h 3A0416 , l o /\

/\ o o o 3A0419 gg 2A0419 NC)2A0418NO ) NO ) NC )3A04183g-

  • BUS 3A04 BUS 2A04 .

) o .

N0 U)n04is n

NO ,)a04i3 Y* Y-UNIT 3 WIT 2 DIESEL GENERATOR DIESEL GEERATOR .

30002 ,

2G002 .

~

' UNITS 2 & 3

@ NORMAL PREFERRED POWER SOURCE. SAN ONOFRE NUCLEAR GEERATING STATION

@ ALTERNATE h M WER SO@CE. ONE LINE DIAGRAM OF LOAD GROU POWER SOURCES q)STAN0sfPosERSouRCE. .

) . @ E lRD ? REFERRED NUER SOURCE.

f[f SOUTHERN CAL.lFORNIA ED FIGURE 2 x .

g