ML20073R997
| ML20073R997 | |
| Person / Time | |
|---|---|
| Site: | Wolf Creek |
| Issue date: | 02/09/1994 |
| From: | Maynard O WOLF CREEK NUCLEAR OPERATING CORP. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| TAC-M85625, WO-94-0013, WO-94-13, NUDOCS 9402160243 | |
| Download: ML20073R997 (21) | |
Text
9 4
0 6
WOLF CREEK
~
~
I
' NUCLEAR OPERATING CORPORATION Otto L. Maynard Vice President Plant operations February 9, 1994
U. S. Nuclear Regulatory Commission ATTN:
Document Control Desk Mail Station F1-137 Washington, D.C.
20555
Reference:
1)
NRC letter dated December 17, 1992, "Thermo-l Lag 330-1 Fire Barriers (Generic Letter 92-08) 2)
NRC letter dated December 22, 1993, " Request For Additional Information Regarding Generic Letter 92-08 (TAC No. M85625)"
Subject:
Docket No. 50-482: Response To NRC Request For Additional Information Regarding Thermo-Lag 330-1 Fire Barriers (Generic Letter 92-08) f Gentlemen:
This letter provides Wolf Creek Nuclear Operating Corporation's (WCNOC)
~
response to Reference 2, pursuant to the requirements of 10 CFR 50.54 (f). The NRC issued a Request for Additional Information (RAI) regarding Generic Letter 92-08, "Thermo-Lag 330-1 Fire Barriers," on December 22, 1993.
The RAI requires each addressee to provide additional information on the configurations and amounts of Thermo-Lag fire barriers installed in the plant and the cable loading within particular Thermo-Lag configurations.
The RAI i
also requires additional information be provided concerning: each addressee's plans for addressing barriers not bounded by the NUMARC test program; each addressee's plans for addressing ampacity derating concerns; alternatives available to each addressee to installing Thermo-Lag upgrades; and.an integrated schedule addressing the overall corrective action schedule for the plant to resolve Thermo-Lag fire barrier concerns.
Attached is WCNOC's response to the RAI.
The attached response provides as complete a response as is possible at this time.
Following completion of the NUMARC test program, WCNOC will re-examine this response and provide an updated response, if necessary,
[t[
b15
\\
\\
9402160243 940209 io. Box 411/ Burkngton. KS 66839 / Phone: (316) 364-8831 DR ADOCK 0500 82 An cauai opportunity Ernployer WF/HCNET
WO 94-0013 Page 2 of 2 If you have any questions concerning this matter,.please contact me at (316) 364-8831 Ext. 4002 or Mr. Kevin J. ' Moles of my staff 'at Ext. 4565.
Very truly yours, J
c'7T. /
/
l ) b l l
{ 8 l/ J W
. Otto L. Maynard: '
Vice President
.)
Plant Operations' I
OLM/jra I
Attachment
)
cc:
L. J. Callan (NRC), w/a G. A.
Pick (NRC), w/a
{
W. D. Reckley (NRC), w/a l
L. A. Yandell (NRC), w/a i
1 l
l 1
i
- - -, _ ~. _.... _ -
4 1
1 i
STATE OF KANSAS
)
)
SS COUNTY OF COFFEY
)
Otto L. Maynard, of lawful age, being first duly sworn upon oath says that he is Vice President Plant Operations of Wolf Creek Nuclear Operating l
Corporation; that he has read the foregoing document and knows the content thereof; that he has executed that same for and on behalf of said Corporation
+
g with full power and authority to do so; and that the facts therein stated are true and correct to the best of his knowledge, information and belief.
=
4(
]),,
~
b By_
'ffyffua, j
Otto L. Maydard
/
., f U 6 O g u Vice President Plant Operations i
<., 47. "
Cc 1
1 SUBSCRIBED and sworn to before me this b
day of1ktttcuy,1994.
fg
(
26A?al?
Ektt
/
.' Notary Public C
t Expiration Date 5 /[/ /fbf a
i j
2
-[
E a
i 4
e e+.e+-e r
m-r--
w g-+e-w
l Attachment to WO 94-0013 Pag,e 1 of 18 I
RESPONSE TO THERMO-LAG REQUEST FOR ADDITIONAL INFORMATION RAI Section I.
Thermo-Lag Fire Barrier Configurations and Amounts NRC Item I.B.1-Describe the Thermo-Lag 330-1 barriers installed in the plant 3
to:
1 1
a.
meet 10 CFR 50.48 or Appendix R to 10 CFR Part 50, b.
support an exemption from Appendix R, l
c.
achieve physical independence of electrical systems, d.
meet a condition of the plant cperating license, e.
satisfy licensing commitments The descriptions should include the following information:
the intended purpose and fire rating of the barrier (for example, 3-hour fire barrier, 1-i hour fire barrier, radiant energy heat shield), and the type and dimension of the barrier (for example, 8-ft by 10-ft wall, 4-ft by 3-ft by 2-ft equipment enclosure, 36-inch-wide cable tray, or 3-inch-diameter conduit).
WCNOC Response Wolf Creek Generating Station (WCGS) relies upon Thermo-Lag 330-1 fire i
d barriers to meet 10 CFR 50.48 (e), which is implemented at WCGS by NRC guidance l
provided in Branch Technical Position CMEB 9.5-1.
A listing of these WCGS i
applicaticns is provided in Table 1 (attached), which identifies the purpose, fire rating, type, and dimension of each barrier.
WCGS also utilizes Thermo-Lag 330-1 barriers to meet Regulatory Guide 1.75 j
physical independence of electrical system criteria.
These barriers are not intended to meet the 1-hour or 3-hour fire rated configurations.
Table 2 (attached) provides a listing of these WCGS applications and identifies the type and dimension of each barrier.
1 NRC Item I.B.2.-For the total population of Thermo-Lag fire barriers described under Item I.B.1, submit an approximation of:
a.
For cable tray barriers:
the total linear feet and square feet of 1-hour barriers and the total linear feet and square feet of 1
3-hour barriers, b.
For conduit barriers: the total linear feet of 1-hour barriers i
j and the total linear feet of 3-hour barriers.
j c.
For all other fire barriers: the total square feet of 1-hour barriers and the total square feet of 3-hour barriers.
d.
For all other barriers and radiant energy heat shields:
the total linear or square feet of 1-hour barriers and the total linear or square feet of 3-hour barriers, as appropriate for the barrier configuration or type.
d
Attachment to WO 94-0013 Page 2 of 18 WCNOC Response BRANCH TECHNICAL POSITION CMEB 9.5-1 APPLICATIONS:
The following table provides un approximation of the installed amounts of Thermo-Lag 330-1 material used in WCGS Branch Technical Position CMEB 9.5-1 applications.
Table 3 1-hour Barrier 1-hour Barrier 3-hour Barrier 3-hour Barrier Total Linear Total Square Total Linear Total Square Feet Feet Feet Feet CABLE TRAY 0
0 23 107 CONDUIT 53 Not Requested 600 Not Requested OTHER" Not Requested 5.5 Not Requested _
525
- Includes hatches, an encapsulation box, junction boxes and fire stops.
REGULATORY GUIDE 1.75 APPLICATIONS:
The following table provides an approximation of installed amounts of Thermo-Lag 330-1 material used in WCGS Regulatory Guide 1.75 applications.
These applications for Regulatory Guide 1.75 requirements ' utilize 1-hour rated material, 1/2" thick.
Table 4 Fire Barrier Fire Barrier Total Linear Feet Total Square Feet 1
CABLE TRAY 2
11 CONDUIT 805 Not Requested JUNCTION BOXES Not Requested 80 RAI Section II.
Important Barrier Parameters II.B.1 State whether or not you have obtained and verified each of the aforementioned parameters for each Thermo-Lag barrier installed;in the plant.
If not, discuss the parameters you have not obtained or verified. Retain detailed information on site for NRC audit where the aforementioned parameters are known.
1 II.B.2 For any parameter that is not known or has not been verified, describe how you will evaluate the in-plant barrier fc.r acceptability.
II.B.3 To evaluate NUMARC's application guidance, an understanding of the types and extent of the unknown parameters is needed. ~
Describe the type and extent of the unknown parameters at your plant in this context.
I
j Attachment to WO 94-0013 Page 3 of 18 WCNOC RESPONSE i
j The response to Item II has been divided into two sections.
The first one addresses the twenty-four parameters of importance to Thermo-Lag 330-1 f
material installation.
The second addresses the eight parameters of importance concerning cable protected by fire barriers.
i j
Raceway Fire Barrier Parameters WCNOC has been actively evaluating WCGS Thermo-Lag 330-1 applications relied upon to meet BTP CMEB 9.5-1 requirements. WCNOC has obtained and verified the 24 parameters listed in the RAI for WCGS BTP CMEB 9.5-1 applications.
This j
information was obtained and/or verified through the use of general walkdowns, j
design drawing reviews, and review of QA records of the applications.
It should be noted that additional rated fire barrier parameters, including fire barrier panel rib location, raceway gauge (mass), type of cable tray side rails, cable tray rung spacing and thermal shorts penetrating the barrier but not contacting the raceway, have been identified as potentially important.
In addition, the planned NUMARC Phase 2 testing could result in identification of further fire barrier parameters of importance or demonstrate that some of the exiting fire barrier parameters are not significant.
1 It is WCNOC's intent to utilize the fire barrier performance parameters specified in the final Application Guide as issued by NUMARC and. agreed upon by the NRC when evaluating fire barriers for acceptability.
As requested in Action Item II.B.1, detailed information is available on-site for NRC audit of the known parameters.
l l
Cable Parameters Cable functionality is presently an unresolved issue, and NUMARC is not currently conducting any cable functionality. tests or evaluations as part of 4
its Phase 2 Test Program.
Conduit in the NUMARC tests use a bare copper a
4 conductor.
WCGS has very limited applications of Thermo-Lag 330-1 on cable trays.
There t
are two applications of 3-hour rated Thermo-Lag 330-1 on a 24" x 4" tray for a length of approximately eleven feet each.
j If NUMARC fire tests demonstrate temperature criteria exceedance, one optional approach to resolution, as provided in the NRC draft test and acceptance j
criteria, would be to evaluate cable functionality at the elevated temperature j
j using cable performance test data or information for specific installed cable l
types.
However, the NRC has not yet finalized requirements for cable I
functionality evaluation, and test results are not yet available that would clearly indicate the scope of such evaluations.
i Based on the above, WCNOC does not intend to obtain and verify the eight listed parameters for each of the WCGS applications for the purposes of this response.
However, if the results of the NUMARC testing does warrant cable functionality evaluations on an application specific
- basis, and NRC requirements have been finalized for that type of evaluation, WCNOC will 4
4 e
r
Attachment to WO 94-0013 Page 4 of 18 obtain and verify the necessary cable parameters on an at
. cation speci.fic basis.
The WCGS Thermo-Lag 330-1 applications installed to meet Regulatory Guide 1.75 requirements are not intended to meet 1-hour or 3-hour rated fire barrier configurations.
Therefore, the twenty-four fire barrier parameters of importance referenced in Section II A of the RAI, are not all applicable to the Regulatory Guide 1.75 applications.
Parameters such as location, material thickness, and material amounts have been obtained for WCGS Regulatory Guide 1.75 applications.
These parameters may be necessary to evaluate these applications for ampacity derating and to perform a material conbustibility screening.
Chemical testing performed by NUMARC on a wide variety of aged samples has not revealed significant variations in chemical composition.
NUMARC intends to discuss these test results with the NRC and distribute them, along with the Phase 1 test reports, to the various licensees.
Further, NUMARC has indicated
.j that Phase 2 testing will include additional chemical testing on barrier j
materials of various ages.
Unless unexpected results are encountered, plant unique chemical evaluation should not be necessary.
Therefore, WCNOC does not have any plans at this time to conduct material chemical testing.
RAI Section III THERMO-LAG FIRE BARRIERS OUTSIDE THE SCOPE OF THE NUMARC PROGRAM III.B.1.
Describe the Larriers discussed under Item I.B.1 that you have determined will not be bounded by the NUMARC test program.
III.B.2.
Describe the plant-specific corrective action program or plan you expect to use to evaluate the fire barrier configurations particular to the plant. This description should include a discussion of the evaluations and test begin considered to resolve the fire barrier issues identified in GL 92-08 and to demonst rate the adequacy of existing in-plant barriers.
III.B.3.
If a plant-specific fire endurance test program is anticipated, describe the following:
a.
Anticipated test specimens.
b.
Test methodology and acceptance criteria including cable functionality.
WCNOC RESPONSE As discussed in the April 16, 1993 WCGS response to NRC Generic Letter 92-08 (Letter ET 93-0047, F.
T.
Rhodes, WCNOC, to USNRC) the WCGS rated fire barrier applications can be classified into two categories.
The first category (typical fire barrier applications) includes conduit, with their associated junction boxes and supports, and cable tray.
The second category (WCGS unique applications) includes various hatch covers, a cable tray fire stop and a single encapsulation box.
Attachment to NO 94-0013 Page 5 of 18 1
The first category falls within the scope of the NUMARC test program in terms j
of applications, fire barrier ratings, raceway types, raceway sizes and j
configurations.
~
The second category is outside the scope of the NUMARC test program. The'WCGS unique fire barrier applications are:
i 1.
Tendon Surveillance Access Hatches in the Auxiliary Building - at Elev. 2020'-0" (2 hatches) and 2047'-6" (2 hatches).
l l
2.
Residual Heat Removal and Containment Spray Encapsulation Access f
Covers in the Auxiliary Building at Elev.
2000'-0" (2 access.
)
covers).
3.
Box type enclosure of. motor operated valve AL-HV-32 supplying Essential Service Water to the Turbine Driven Auxiliary Feedwater Pump in the Auxiliary Building at Elev. 1989'-0".
j l
4.
Radiolcgical Control Area 5 Personnel Escape Hatch in the l
Auxiliary Building at Elev. 1989'-0"-
l l
5.
Cable Tray Fire Stops in the Corridor between the Component l
Cooling Water Pumps in the Auxiliary Building at Elev. 2026'-0".
l WCNOC has completed a detailed evaluation of each of the above fire barriers.
Resulta of these evaluations are as follows:
i l
1.
Tendon Surveillance Access Hatches in the Auxiliary Building at f
Elev. 2026'-0" (2 hatches) and 2047'-6" (2 hatches).
i At each elevation identified there are two hatches which consist I
of a 2'-10" x 3'-3" x 1/4" checker steel plate with a 1" layer of Thermo-Lag 330-3 material bolted on the top side..The covers rest I
on 5" x5" x1/2" steel angle supports attached to concrete walls on i
two sides and to concrete curbs on the other two sides. The steel plate and the angle supports are covered with Albi-Duraspray l
fireproofing material on the bottom side.
The hatch covers serve to provide separation between fire areas'within the plant.
i
^
The detailed evaluation determined that the as-installed hatches represent a non-rated fire barrier which affords protection from fire based on the hazards present in the fire areas.
Therefore, l
no further work is required for this item.
l 2.
Residual Heat Removal (RHR) and Containment Spray Encapsulation I
Access Covers in the Auxiliary Building at Elev.
2000'-0" (2
access covers).
j The two access covers located in the floor of the auxiliary i
building at elevation 2000'-0" consist of openings that are approximately 10'-6" x 12'-6" with C15 steel channel frames around the perimeter of the opening on top of 18" high curbs.
The barrier is made of 4"x4" tube steel in a grid with 1" Thermo-Lag 330-1 material panels.
The channel steel is covered with I
i
t l
Attachment to WO 94-0013 Page 6 of 18 j
Albi-Duraspray fireproofing material.
The hatch covers are provided as a separation between two fire areas in the plant.
i
?
The detailed evaluation determined that, due to' the large unsupported span of Thermo-Lag 330-1 material, installation of 1/4" steel plating in lieu of the existing Thermo-Lag panels would provide a.non-rated fire barrier suitable'for the hazards present
' i in the two fire areas.
Therefore, a plant modification-has been initiated to replace the Thermo-Lag 330-1 panels on the RHR and Containment Spray Encapsulation Access Covers with 1/4" steel plate.
l l
3.
Box type enclosure of motor operated valve AL-HV-32 supplying
- I Essential Service Water to the Turbine Driven Auxiliary Feedwater f
Pump (AFWP) in the Auxiliary Building at Elev. 1989'-0".
j The 4'-9" Lx 3'-0" Wx 5'-0" H enclosure is constructed of 1"
Thermo-Lag 330-1 material on 5 sides with the sixth side against a.
ccncrete wall.
- l Both Turbine Driven AFWP suction. valves are located within the i
same fire area. This fire. barrier provides separation between the'
(
two valves to ensure that a suction source for the Turbine Driven-l AFWP is available, as required by BTP CMEB 9.5-1, for areas which do not have installed suppression systems.
The detailed evaluation determined that an equivalent method of f
compliance with BTP CMEB 9.5-1 requirements could be achieved with
[
the addition of fire detection and fire suppression to the area, since the redundant Turbine-driven AFWP suction valves have more l
than the required 20' horizontal separation.
This would ' allo'w j
removal of the box-type enclosure.
Therefore, a
plant
.}
modification has been initiated to add fire detection and fire suppression to the area, and to remove the box enclosure.
f t
4.
Radiological Control Area 5 Personnel Escape Hatch in' the) l Auxiliary Building at Elev. 1989'-0".
l
~
The 3'-0" x
3'-0" hatch installed in the floor at elevation j
i 1989'0" is covered by a 1/4" steel plate that has a hinge on one l
side. The underside of the plate is covered by 1" Thermo-Lag 330-l 1 material. Embedded steel around the perimeter of the opening is covered with the same Thermo-Lag material and a minimal amount of l
the 1 1/2" thick Albi-Duraspray on the vertical leg of the 6"
angle iron supporting the cover.
The hatch cover provides a fire barrier between two fire areas in the plant.
The detailed evaluation determined that the as-installed hatch l
cover represents a non-rated fire barrier suitable'for the hazards present in the two fire areas.
Therefore,.no further work is.
required for this item.
1
. Attachment to WO 94-0013 Page 7 of 18 I
5.
Cable Tray Fire Stops in the Corridor between the Component f
Cooling Water Pumps in the Auxiliary Building at Elev. 2026'-0".
l The cable tray fire stops extend for a total length of 3'-0" along l
cable trays-6USE, 6U5D and 6J5B.
The fire stops consist of 1/2" thick Thermo-Lag 330-1 panels which form'a 3'-0" long box around each of the 24" ladder back cable trays.
Within the Thermo-Lag box there is approximately 9" of Dow corning 3-6548 silicone foam between two 1/2" thick Thermo-Lag panels installed vertically in the tray to act as damming boards.
Trays 6U5E, 6USD and 6J5B are totally enclosed in a solid steel cover for a distance of approximately 10 feet in one direction and 25 feet in the other direction from the fire stop.
l t
The fire stop was installed adjacent to the sprinkler protected area of Room 1408 based upon an original licensing concern that the non-safety related cables in these trays were intervening combustibles between two redundant safe shutdown trains in this
- area, The fire stop is intended to'stop flame propagation along the cables in the above mentioned trays.
The detailed evaluation determined that the presence of Thermo-Lag
(
material in the fire stops on cable trays 6U5E, 6USD and 6J5B will
]
i not degrade the performance of the configuration as designed.
j Therefore, no further work is required for this item.
j As a result of the above evaluations and design changes, WCNOC currently has no plans to conduct plant-specific testing of any WCGS-specific fire barriers.
No discussion of the WCGS Thermo-Lag 330-1 applications installed to meet the requirements of Regulatory Guide 1.75 has been included in response to this item.
These applications are not intended to meet 1-hour or 3-hour rated fire i
barrier configurations.
Therefore, the NUMARC fire endurance program.is not j
applicable to them.
I RAI Section IV AMPACITY DERATING IV.B.1.
For the barriers described under Item I.B.1, describe those that you have determined will fall within the scope of the NUMARC program for ampacity derating, those that will not be bounded by the NUMARC program, and those for which ampacity derating does notapply.
IV.B.2.
For the barriers you have determined fall within the scope of the NUMARC program, describe what additional testing or evaluation you will need to perform to derive valid ampacity derating factors.
IV.B.3.
For the barrier configurations that you have determined will not be bounded by the NUMARC test program, describe your plan for evaluating whether or not the ampacity derating tests relied upon i
for the ampacity derating factors used for those electrical components protected by Thermo-Lag 330-1 (for protecting the safe-shutdown capability from fire or to achieve physical independence of electrical systems) are correct and applicable to the plant i
i l
j
.i
. Attachment to WO 94-0013 Page 8 of 18 i
design.
Describe all corrective actions needed and submit the schedule for completing such actions.
r IV.B.4.
In the event that the NUMARC fire barrier tests indicate the need 1
to upgrade existing in-plant barriers or to replace existing Thermo-Lag barriers with another fire. barrier system, describe the alternative actions you will take (and the schedule for performing j
those actions) to confirm that the ampacity derating factors were derived by valid tests and are applicable to the modified plant design.
Your response to Section IV.B may depend on unknown specifics of the NUMARC ampacity derating test program (e.g.,
the final barrier upgrades).
- However, your response should be as complete as possible.
In addition, your response i
should be updated as additional information becomes available on the NUMARC program.
WCNOC RESPONSE As discussed in the April 16, 1993 WCNOC response to NRC Generic Letter 92-08 (Letter ET 93-0047, F.
T.
Rhodes, WCNOC, to USNRC) WCGS ampacity derat.ing factors for conduit and cable trays covered with Thermo-Lag 330-1 are based on vendor supplied heat transfer coefficient values for Thermo-Lag 330-1.
During_
f original design, WCNOC performed heat transfer calculations to address the specific applications and provide the basis for ampacity derating.
The ampacity derating values are not based on ampacity derating tests.
Conservatism was used in the assumptions made to bound operating parameters.
.l The generic concern with the acceptability of ampacity derating factors is that long term life of the cable insulation may be degraded due to a potentially higher operating temperature for the cable.
WCNOC has evaluated WCGS Thermo-Lag 330-1 applications of conduits and cable trays for ampacity margin.
Ampacity margin is the percentage difference between the actual current of the cable and the acceptable current of the t
cable not including the thermal insulating effects of Thermo-Lag.
It was determined that WCGS has very conservative ampacity margins ccmpared to results of tests performed by other organizations.
The ampacity margins will be applieo to future upgrades as appropriate.
Furthermore, WCGS Class 1E electrical cables are qualified for a 40 year life and have been in service less than one-quarter of the qualified life.
WCNOC currently has no plans to evaluate instrumentation and control cable as i
they do not carry a significant current compared to the ampacity of the conductors.
Furthermore, the heat generated is not significant compared to that generated by power conductors.
i WCNOC also does not intend to evaluate ampacity deratings on fire barrier f
configurations which enclose a raceway for six (6) inches or less in length.
This is based on the assumption that this small an area will not create a significant temperature rise.
NUMARC has not yet determined an exact method to test configurations for ampacity derating associated with fire barrier material.
Although it is currently anticipated that most WCGS Thermo-Lag 330-1 applications on cable
Attachment to NO 94-0013 Page 9 of 18 tray and conduit will be bounded by the NUMARC testing, it is not possible to determine exactly which WCGS barriers will be bounded by the NUMARC testing program until the scope of the NUMARC testing has been finalized.
Therefore, the specifics of the additional testing and evaluation needed to envelop the ampacity derating configurations to the NUMARC program can not be specified at this time.
Furthermore, any schedule proposed at this time for conducting additional testing and evaluations for ampacity derating would be speculative, since the scope of the NUMARC testing has not yet been defined.
As indicated above, the need for and future scope of additional testing and evaluations by WCNOC for ampacity derating will be based on the results of the NUMARC test program.
Depending on those results, WCNOC intends to perform one of the following options:
If the NUMARC test results indicate that WCGS fire barriers need to be modified, WCNOC will determine an acceptable ampacity derating for the new configurations by:
- 1) following NUMARC's ampacity derating tests, or 2) analysis of the new configuration using heat transfer techniques, or 3) performing additional testing beyond the scope of the NUMARC I
tests, or 4) a combination of the above.
If the NUMARC test results indicate that WCGS fire barriers are
- adequate, and NUMARC conducts ampacity derating tests following completion of the fire barrier tests; then WCNOC will address the issue as mentioned above.
If NUMARC does not perform the ampacity derating tests, WCNOC will acquire test methods and results from other organizations which have already performed ampacity derating tests.
WCNOC will then analyze the test methods and results to determine an acceptable resolution to the issue by:
- 1) using the test results as applicable, or 2) evaluating the configurations with heat transfer techniques, or 3) perform additional testing, or 4) a combination of the above options.
This response is applicable for both Regulatory Guide 1.75 and BTP CMEB 9.5-1 i
applications.
l RAI Section V ALTERNATIVES V.B.
Describe the specific alternatives available to you for achieving compliance with NRC fire protection requirements in plant areas that contain Thermo-Lag fire barriers.
Examples of possible alternatives to Thermo-Lag based upgrades include the following:
1.
Upgrade existing in-plant barriers using other materials.
2.
Replace Thermo-Lag barriers with other fire barrier materials or systems.
l 3.
Reroute cables or relocate other protected components.
j i
4.
Qualify 3-hour barriers as 1-hour barriers and install detection and suppression systems to satisfy NRC fire protection requirements.
Attachment to WO 94-0013 Page 10 of 18 I
t i
WCNOC RESPONSE l
f In the event the NUMARC Phase 2 tests which bound the WCGS applications are not successful, or if additional WCGS evaluations using the NUMARC Application Guide indicate that some upgrades that rely on additional thicknesses of f
Thermo-Lag material (or other fire barrier materials) may not be practical due to the effects of ampacity derating or clearance problems, alternative methods exist to restore the fire barriers to operable status.
The following is a discussion of some of the alternatives available.
However, the following discussion is not meant to limit WCNOC to only those methods described.
- 1. The majority of WCGS applications involve 3-hour rated fire barriers.
If the NUMARC test results indicate that some WCGS configurations would j
not pass a 3-hour fire endurance test, evaluations, based upon the use of fire modeling in conjunction with NUMARC baseline (noa-upgraded) test j
results, may be performed to demonstrate adequate protection for the j
installed hazard.
Alternatively, or in conjunction with the above j
evaluations, probabilistic safet" analysis (PSA) could be used as an exemption basis, by demonstrating insignificant core damage frequency i
impacts, assuming barrier inoperability.
- 2. Reroute of cable, or replacement of specific cables with fire rated cable (i.e., Rockbestos Firezone R) 3.
If NUMARC Phase 2 testing is successful but evaluation using the NUMARC Application Guide indicates that the specific WCGS applications are not bounded due to differences in baseline Thermo-Lag 330-1 installation details, WCNOC can rework the WCGS baseline installations to achieve compliance with the as-tested NUMARC configurations.
- 4. In many WCGS applications it would be possible to install fire l
suppression and fire detection to the area and then qualify the existing 3-hour barriers as 1-hour rated barriers.
5.
Performing a
re-evaluation of engineering analyses used for determination of safe shutdown pathways, equipment, and actions, could provide a basis for reduction in the scope of protected circuits and their associated fire barriers.
- 6. For certain applications, WCNOC could replace the Thermo-Lag fire barrier with rated fire barriers using other qualified materials or systems.
7.
If the NUMARC tests of fire barrier upgrades using Thermo-Lag material are not successful, upgrades using other fire barrier materials may be developed.
However, test and acceptance criteria have not yet been finalized and issued by the NRC.
The final approved test methods and acceptance criteria must be evaluated to determine net effect on the l
scope and complexity of upgrades to WCGS installed barriers before this option could be chosen.
The WCGS applications of Thermo-Lag 330-1 material installed to meet the requirements of Regulatory Guide 1.75 are not intended to meet 1-hour or l
3-hour rated fire barrier configuration requirements.
Future ampacity I
Attachment to WO 94-0013 Pam 11 of 18 derating evaluations, or combustibility evaluations, for these applications may indicate Thermo-Lag 330-1 material is not suitable for use in specific applications.
In this event, the Thermo-Lag 330-1 material will be replaced with an alternate material which is suitable as a radiant energy shield.
i RAI Section VI SCHEDULES i
VI.B. Submit an integrated schedule that addresses the overall corrective j
action schedule for the plant. At a minimum, the schedule should address the following aspects for the plant:
1 l
1.
Implementation and completion of corrective actions and fire barrier upgrades for fire barrier configurations within the scope i
of the NUMARC program.
]
2.
Implementation and completion of plant-specific analyses, testing, I
or alternative actions for fire barriers outside the scope of the NUMARC program.
WCNOC RE, 'ONSE The WCGS schedule is subdivided into tnree smaller schedules, each one addressing the different application categories.
)
1)
WCGS UNIQUE APPLICATIONS l
As discussed in our response in Section III, the engineering evaluation of each of the WCGS unique Thermo-Lag 330-1 applications is complete. A Plant Modification Request (PMR) has been developed to modify several of these applications as discussed in Section III.
This PMR will be implemented by December 30, 1994 2)
WCGS REGULATORY GUIDE 1.75 APPLICATIONS WCNOC has evaluated WCGS Thermo-Lag 330-1 applications of conduits and cable trays for ampacity margin.
Ampacity margin is the percentage difference between the actual current of the cable and the acceptable current of the cable not including the thermal insulating effects of Thermo-Lag.
It was determined that WCGS has very conservative ampacity margins compared to results of tests performed by other organizations.
These ampacity margins will be applied to future upgrades as appropriate.
It is WCNOC's intent to evaluate and utilize the ampacity deratings derived by Texas Utilities Electric Company for these applications once NRC acceptance is obtained.
A schedule for completion of this activity will be provided to the NRC by July 15, 1994.
3)
WCGS PTP CMEB 9.5-1 APPLICATIONS WITHIN THE SCOPE OF THE NUMARC TEST PROGRAM.
Attachment to WO 94-0013 Page 12 of 18 i
Numerous uncertainties currently exist within the NUMARC program as l
noted in several of the above responses.
It is WCNOC's intent to begin detailed engineering evaluations for potential application upgrades as l
soon as the NUMARC Application Guide is received.
The extent of specific upgrades will be based primarily on the level.of success of j
l NUMARC's Phase 2 Test Program.
The following is a schedule provided by l
NUMARC for their Phase 2 testing and ampacity testing.
l l
Activity Schedule Issue Phase 2 test reports April 15, 1994 i
Issue Application Guide April 15, 1994 i
Ampacity program information April 29, 1994 j
Perform ampacity testing July 1994 (estimated)
Issue Ampacity test reports August 1994 (estimated)
Before any upgrades using Thermo-Lag 330-1 or other barrier materials can be approved for the WCGS 3-hour rated applications, the ampacity derating testing for the upgrade must be completed.
Because the NUMARC schedule for ampacity j
derating testing is estimated, an integrated schedule for this activity will be provided to the NRC by July 15, 1994.
It is WCNOC's intention that restoration of fire barrier operability will be complete prior to startup from the WCGS eighth refueling outage, which is scheduled for the spring of 1996.
(
RAI Section VIII SOURCES AND CORRECTNESS OF INFORMATION I
l Describe the raurces of the information provided in response to this request l
fer information (e.g.,
from plant drawings, quality assurance documentation, walsdown= or inspections) and how the accuracy and validity of the information was verified.
WCNOC RESPONSE The sources of information provided in response to this request for information included plant
- drawings, QA documentation, NUMARC-provided documentation, electrical circuit databases, plant walkdowns, and installation procedures.
The accuracy and validity of the information was verified by independent physical plant inspections.
I h
Attachment tO WO 94-0013 Page 13 of 18 TAsLe 1
(
WCGS Applications of Thermo-Lag 330-1 Material Required to Meet 10CFR50.4B(e) Requirements Cornponent; Type / Size Hours Purpose Remarks 3JJ053 J-BOX 16 x 6 x 30 1
Fire Barrier 5.5 sq. ft.
1J1LO1 TRAY /4x24 3
Fire Bamer 11 feet 3 inch / Ready Access Design / supports - WR 03329-92) 1J1 LIB CONDUIT /1 3
Fire Bamer 37 feet 1J2027 CONDUlT/1 N/A Heat Shield 65 feet /Non. Comb. Rad. Energy Shield /7 supts-19 sq. ft./(2) unscheduled J-Box 14 sq. ft.
IU1037 CONDUlT/3 3
Fire Barrier 53 feet / supports - 32 sq. ft./P-Box - 7.1 sq. ft./ unscheduled J-Box - 6.2 sq. ft.
1U1038 CONDUlT/1 1/2 3
Fire Bamer 6 feet 2 inch / enclosed w/1U1039/w/ supports 7.5 sq. ft.
l 1U1039 CONDUlT/1 1/2 3
Fue Bamer 6 feet 2 inch / enclosed w/1U1038/w/ supports 7.5 sq. ft.
(
1U1040 CONDUIT /1 1/2 3
Fire Bamer 6 feet 6 inch IU1041 CONDUlT/1 1/2 3
Rre Bemer 6 feet 6 inch l
1U1002 CONDUIT /1 1/2 3
Fire Barrier 18 inch / enters J-BOX 1UJO29/1U1044,45,43,42 enclosed 1U1043 CONDUlT/1 1/2 3
Fue Barrier 18 inch / enters J-BOX 1UJO29/1U1044,45,43,42 enclosed 1U1064 CONDUlT/1 1/2 3
Fire Barrier 18 inch / enters J-BOX 1UJO29/1L 1044,45,43,42 enclosed 1U1045 CONDUlT/1 1/2 3
Fire Bemer 18 inch / enters J-BOX 1UJO29/1U1044,45,43,42 enclosed 1U1E6N CONDUIT /3 3
Fire Bamer 6 feet
)
1U1K01 TRAYi4X24 3
Fire Bamer 11 feet 3 inches / Ready Access Design / Supports /28 sq. ft, supports 1U1K5C CONDUIT /1 1/2 3
Fire Bamer 6 inch /J-Box (1UJO29) to floor 1U1K5N CONDUIT /4 3
Fire Barrier 3 feet /PMR 01320/ trowel grade skim coat entire length IUJ029 J-BOX /24X12X8 l 3 Fire Samer 8 sq. ft./ wall mounted 2J1019 CONDUIT /1 1/2 l 3 Rre Barrier 2 feet / enclosed with 2J1052
~
l 2J1026 CONDUIT /2 l 3 Fue Bamer 6 feet / wrapped at (2) supports f/1J1L1B 2J1035 CONDUlT/3 3
Fwe Bamer l10 feet /(2) supts. 6" x 8" x 2* long 2J1036 CONDUIT /3 3
Fire Barrier 40 feet /15 sq. ft. supports 2J1037 CONDUlT/3 3
Fire Bamer 75 feet / supports - 39 sq. ft.
I 2J1040 CONDUlT/3 3
Fire Barrier 4 feet / supports - 2 sq. ft.
2J1042 CONDUIT /4 3
Fire Barrier 43 feet /4U3E9Z,4J3C9Y,2J1042 in common enclosure i
2J1063 CONDUIT /4 3
Fire Bamer 75 feet / supports - 39 sq. ft.
2J1046 CONDUlT/3 3
Fire Barrier 13 feet 2J1067 CONDUlT/3 3
Fire Bamer 24 feet 2J1052 CONDUIT /1 1/2 3
Fire Barrier 3 feet / supt 6/C-0604/ wrapped with 2J1019 l
2J181G CONDUIT /4 3
Fire Barrier 27 feet / supports - 12.5 sq. ft.
l 2J181H CONDUlT/4 3
Fue Barrier 27 feet / supports - 19 sq. ft.
l l
2JJ051 J-BOX /30X24XB 3
Fire Bamer 11 sq. ft.
j 2JJ052 J-BOX /6X6X24 3
Rre Barrier 4.5 sq. ft.
2JJ053 J BOX /6X6X30 3
Fire Barrier 5.5 sq. ft.
2JJ054 J-BOX /6X6X24 3
Fire Bamer 4.5 sq. ft.
2JJ056 J-BOX /18X18X8 3
Fire Barrier 11 sq. ft.
201021 CONDUIT /4 3
Fire Barrier 18 inch 2Ul014 CONDUIT /4 3
Fire Barrier 18 inch 3J1024 CONDUlT/1 1/2 3
Fire Bemer 8 feet / Includes unscheduled J-Boxes 3J1027 CONDUlT/3 1
Fire Bamer 22 feet 3J1029 CONDUIT /3 3
Fire Bamer 18 inch / support (4 x 8 x 24)- 4 sq. ft.
3J1031 CONDUIT /3 3
Fire Barrier 82 feet /65 sq. ft on hangers and unscheduled pull boxes 3J1034 CONDUlT/1 1/2 3
cire Barrier 23 feet 3J181D CONDUIT /4 3
Fire Barrier 20 inch / supports - 6 sq. ft.
3J181 F CONDUIT /3 3
Fire Barrier 21 feet / supports - 10 sq. ft.
3JJ052 J-BOX /30X15 X8 3
Fwe Barrier 11.25 sq. ft.
301002 CONDUIT /1 1/2 3
Fire Barrier 9 feet 4J1013 CONDUIT /3/4 3
Fire Barrier Enclosed w/4JJO46,4J3C1C,4J1014,4J1038/8" x 9" x 29" / 8 sq. ft.
GJ1014 CONDUIT /3 3
Fire Bamer Enclosed w/4J3C1C,4J1038,4J1013,4JJO46/8" x 9"x 29" / 8 sq. ft.
4J1038 CONDUIT /1 1/2 l 3 Fire Barrier Enclosed w/4JJO46,4J3C1C,4J1014,4J1013/8" x 9"x 29" / 8 sq. ft.
4J1064 CONDUlT/2 3
Fire Bamer 12 feet 6 inch 4J1066 CONDUlT/2 3
Fire Barrier 4 feet 4J3CIC CONDUlT/3 3
Fire Bamer Enclosed w/4JJO46,4J1038,4J1014. 4J1013/8" x 9" x 29" / 8 sq. ft.
i Attachment to WO 94-0013 Page 14 of 18 TABU 1 (Continued)
WCGS Applications of Thermo-Lag 330-1 Material Required to Meet 10CFR50.48(e) Requirements C:rnponent Type / Size Hours Purpose Remarks 1JJ046 ABOx/24X6X6 3
Fire Bemer Enclosed w/4J3C1C,4J1038,4J1014,4J1013/8" x 9" x 29" / 8 sq. ft.
4U3003 CONDUIT /2 1
Fire Bemer 30 feet 6 inch j
SJ1026 CONDUIT /4 3
Fire Barrier 3 feet 501Y5X CONDUIT /2 3
Fire Barrier 2 feet 6 inch / supports - 4 sq. ft.
6J1030 CONDUIT /1 1/2 3
Fire Barrier 3 feet 6J1120 CONDUIT /1 1/2 3
Fire Barrier 11 feet / Portions wrapped w/1U1037 6J5B30 TRAY /4x24 N/A Fire Stop 3 feet long/ Fire Stop/15.5 sq. ft.
6U1116 CONDUtT/3/4 3
Fire Bamer 18 inch 6USD30 TRAY /4X24 N/A Fire Stop 3 feet long/ Fire Stop/15.5 sq. ft.
6U5E30 TRAY /4X24 N/A Fire Stop 3 feet long/ Fire Stop/15.5 sq. ft.
N/A HATCH N/A Fire Barrier PMR 04585/ Area 5 Personnel Hatch /3' x 3' / 9 sq. ft.
N/A HATCH N/A Fire Barrier PMR 04585/ Tendon Access Hatches (4)/ 39 sq. ft./40" x 35' N/A HATCH N/A Fire Bemer PMR 04585/RHR Valve Encap. Tank Hatches f 21/ 262 sq. f t./126" x 150" N/A SUPPORTS 3
Fire Barrier M-16EG01-RO14/142 / W8 x 40 x 5 feet 1 inch /17 sq. ft.
)
N/A SUPPORTS 3
Fire Bamer On same support as 3J1027/ support 5B/C-603 wrapped 36 inches l
N/A SUPPORTS 3
Fire Barrier Supports f/ 4J3C9Y & 4U3E9Z/2 supts. ceiling rnounted/26 sq. ft.
N/A SUPPORTS 3
Fire Berrier Supports f/4U3C05,4U3D05,4U3E05/24 sq. ft.
N/A SUPPORTS 3
Fire Barrier l Supports f/4U3C05,4U3D05,4U3E05/24 sq. ft.
N/A SUPPORTS 3
Fire Bamer Supports f/4U3C05,4U3005,4U3E05/24 sq. ft.
N/A VALVE ENCAP.
3 Fire Barrier 4*9"L x 3'W x 5'H/PMR 04585/ALHV032 Valve Encapsulation /
i I
l 1
l i
l I
i l
i l
l
Attachment to WO 94-0013 2
Page 15 of 18 wees Applications of Thermo-Lag 330-1 Material Required to Meet Regulatory Guide 1.75 Requirements L
Ccmpinent Type / Size Hours Purpose Remarks l
16031 CONDUIT /11/2 Fles N/A Radiant Energy Heat SNeld 6 inch l
1G181C CONDUIT /2 N/A Radiant Energy Heat SNeld 9 feet IG6004 CONDUIT /3 N/A Radiant Energy Heat SNeid 6 inch 1G6006 CONDUlT/3 N/A Radiant Energy Heat SNeld 6 inch j
IJ1019 CONDUIT /4 N/A Radiant Energy Heat Shield 36 feet i
1J1020 CONDUlT/4 N/A Radiant Energy Heat Shield 9 feet IJ1021 CONDUfT/4 N/A Radiant Energy Heat ShieH 18 inches IJ1022 CONDUIT /4 N/A Radiant Energy Heat SNeid 18 inch
['
1J1024 CONDUlT/1 N/A Radiant Energy Heat SNeid 6 inch IJ1033 CONDUIT /3/4 Flex N/A Radiant Energy Heat Shield 6 inch t
IJ1062 CONDUIT /4 N/A Radiant Energy Hest Shield 7 feet / supports 3 sq. ft.
IJ1063 CONDUlT/4 N/A Radiant Energy Heat SNeld 20 feet 1J1098 J-BOX /
N/A Radiant Energy Heat SNeld 5 sq. ft./J-Box between IJ1098 & 4U1105 1J1130 CONDUlT/4 N/A Radiant Energy Heat SNeid 5 feet w/ supports i
1J1132 CONDUIT /4 N/A Radiant Energy Heat Shield 24 feet /w/ supports IJ1J8B CONDUIT /4 N/A Radiant Energy Heat Shield 10 inch 1J2030 CONDUIT /2 N/A Radiant Energy Heat SNeid 4 feet 1J2069 CONDUIT /1 N/A Radiant Energy Heat Shield 6 inch IJ3011 CONDUIT /1 Flex N/A Radiant Energy Heat SNeld 6 inch 1J31AB CONDUIT /1 1/2 N/A Radiant Energy Heat Shield 10 feet l
IJ3A1L CONDUlT/11/2 Flex N/A Radiant Energy Heat Shield 14 inch I
IJ6004 CONDUIT /2 N/A Radiant Energy Heat SNeld 9 feet / Runs w/1U6036 (WR 03244-92)/ Trowel grade overtay 1J6CO8 CONDutT/11/2 Flex N/A Radiant Energy Heat Shield 18 inch /Runa together w/ IJ6009,1J6010/ Trowel grade overlay IJ6009 CONDUlT/1 1/2 Flex N/A Radiant Energy Heat Shield 18 inch / Runs together w/1J6010 (WR 03245 92)/ Trowel grade overlay l
1J6010 CONDUIT /11/2 Flex N/A Radiant Energy Heat SNeld 18 inch / Runs together w/1J6009 (WR 03246-92)/ Trowel grade overlay f
IJJ038 JBOX/30X6X6 N/A Radiant Energy Heat Shield 5.5 sq. ft.
1JJ039 J-BOX /30X6X6 N/A Radiant Energy Heat Shield 5.5 sq. ft.
l 1JJOS2 J-BOX /36X24X12 N/A Radiant Energy Heat SNeld 22 feet / supports 8 sq. ft.
IJJO44 J-BOX /30X8X15 N/A Radiant Energy Heat Shield 11.25 sq. ft.
IJJ077 J-Bo7J36X6X6 N/A Radiant Energy Heat SNeid 6.5 sq. ft 1U1062 CONDUIT /1 1/2 N/A Radiant Energy Heat SNeld 6 inch 1U1104 CONDUlT/4 N/A Radiant Energy Heat SNeld 6 inch 1U1116 CONDUlT/3 N/A Radiant Energy Heat SNeld 8 inch 1U1119 CONDUlT/2 N/A 4diant Energy Heat Shield 10 feet 1U1260 CONDUlT/1 1/2 N/A Radiant Energy Heat Shield 6 inch 1U1263 CONDUlT/2 Fles N/A Radiant Energy Fest SNeid 4 inch 1U1347 CONDUlT/3/4 N/A Radiant Energy Heat Sihld 4 feet 1U1E8A CONDUIT /2 N/A Radiant Energy Heat SNeld 10 inch 1U1KSC CONDUIT /4 N/A Radiant Energy Heat Shield 6 inch /
1U2063 CONDUIT /3/4 Flex N/A Radiant Energy Heat SNeld 6 inch 1U3081 CONDUlT/3/4 Flex N/A Radiant Energy Heat Shield 12 inch 1U3A2C CONDUIT /1 N/A Radiant Energy Heat Shield 3 feet / unscheduled J-Box 6 x 6 x 5 - 1.3 sq. ft.
1U3E1C CONDUIT /3 N/A Radiant Energy Heat Shield 6 inch IU3J1H CONDUIT /3/4 N/A Radiant Energy Heat SNeld 14 feet / supports 10.5 sq. ft.
1U3M1H CONDUlT/11/2 Flex N/A Radiant Energy Heat Snield 6 inch 1U3M10 CONDulT/3/4 Flex N/A Radiant Energy Heat SNeld 6 inch 1U6C08 CONDUIT /3 Flex N/A Radiant Energy Heat SNeld 6 inch IU6029 CONDUIT /3 N/A Radiant Energy Heat SNeld 6 inch 1U6036 CONDUtT/1 1/2 N/A Radiant Energy Heat Shield 12 feet / Runs together w/1J6004, WR 03248-92/ Trowel grade overlay 1UJ042 ABOX/36X12X8 N/A Radiant Energy Heat Sheeld RWST Valve House /12 sq. ft.
2J1042 CONDUIT /4 N/A Radiant Energy Heat SNeld 12 inch 2J1048 CONDUIT /3/4 N/A Radiant Energy Heat SNeld
-9 inch (at elbowl 2J1BIL CONDUIT /1 1/2 N/A Radiant Energy Heat SNeid 6 inch
( --
i Attachment to WO 94-0013 l
TABLE 2 (Continued!
Page 16 of 18 WCGS Applications of Thermo-Lag 330-1 Material Required to Meet Regulatory Guide 1.75 Requirements Ccmponent Type / Size Hours Purpose Remarks 2J2033 CONDUIT /3 N/A Radiant Energy Heat Shield 4 feet 2J3017 CONDUIT /2 Flex N/A Radiant Energy Heat Shield 24 inch 2U1014 CONDUlT/4 N/A Radiant Energy Heat SNeld 6 inch 2U1023 CONDUIT /1 1/2 Flex N/A Radiant Energy Heat Shield 6 inch 201B1G CONDUIT /1 1/2 N/A Radiant Energy Heat Shield 6 inch 2U181K CONDUIT /3 N/A Radiant Energy Heat SNeld 6 inch I
2U3005 CONDUIT /1 N/A Radiant Energy Heat Shield 6 inch 2U3016 CONDUlT/2 N/A Radiant Energy Heat Shield 9 feet 6 inch / supports - 2 so. ft.
2U3019 CONDUIT /3/4 N/A Radiant Energy Heat Shield 12 feet / supports - 1 so. ft.
203019 CONDUIT /3/4 N/A Radiant Energy Heat SNeld 15 feet 2UJ022 J-BOX /36X12X8 N/A Radiant Energy Heat Shield RWST Valve House /12 sq. ft.
3J1029 CONDUIT /3 N/A Radiant Energy Heat Shield 6 inch 3J1033 CONDUlT/1 1/2 N/A Radiant Energy Hest Shield 43 feet / supports 1 so. ftdunscheduled J-Box 3.5 sq. ft.
3J1049 CONDUIT /3/4 N/A Radiant Energy Heat SNeld 3 feet w/ supports 1.5 so. ft, j
3J1050 CONDUIT /3/4 N/A Radient Energy Heat SNeld 6 feet 6 inch 3J1050 CONDUlT/3/4 Flex N/A Radiant Energy Heat Shield 4 feet i
I 3J1051 CONDUIT /3/4 N/A Radient Energy Heat Shield 3 feet w/ supports 3U1010 CONDUlT/1 1/2 N/A Radiant Energy Heat SNeld 6 feet 6 inch i
3U183C CONDUlT/4 N/A Radiant Energy Heat Shield 6 inch 3U1BBC CONDUITi4 N/A Radiant Energy Heat Shield 19 inch SC3G3A CONDUlT/1 1/2 N/A Radiant Energy Heat Shield 12 inch l
4C8J1W CONDUIT /4 Flex N!A Radiant Energy Heat SNeld 6 inch
[
4G2A1A CONDUIT /2 N/A Radiant Energy Heat Shield 23 feet / supports - 17 so. ft.
4G2A1B CONDUlT/4 N/A Radiant Energy Heat Shield 27 feet /oupports - 17 sq. ft.
4G2A1C CONDUIT /4 N/A Radiant Energy Heat Shield 27 feet 4G2A1F CONDUIT /1 N/A Redient Energy Heat SNeld 23 feet 4J1035 CONDUlT/1 N/A Radiant Energy Heat Shield Rigid & Flex /11 inch (2 pcs),4 jh,7 inch,33 inch total 4J1039 CONDUlT/3/4 Flex N/A Radiant Erwgy Heat Shield 12 inch 4J1099 CONDUIT /1 1/2 N/A Radiant Energy Heat Shield 10 feet 4J1101 CONDUtT3/4 N/A Radiant Energy Heat Shield 20 feet 4J1103 CONDUIT 3/4 N/A Radiant Energy Heat SNeld 20 feet I
4J1106 CONDUIT /1 1/2 N/A Radiant Energy Heat SNeld 6 feet 6 inch 4J1115 CONDUIT /1 N/A Radiant Energy Heat SNeld 45 feet 4J1118 CONDUIT /1 Flex N/A Radiant Energy Heat Shield 18 inch 4J1141 CONDUIT /1 Flex N/A Radiant Energy Heat Shield 6 inch 4J1C1Z CONDUIT /1-1/2 N/A Radiant Energy Heat SNeld 6 inch 4J1J19 TRAY /6 x 12 N/A Radiant Energy Heat Shield 2 feet 4J3002 CONDUIT /3/4 N/A Radiant Energy Heat SNeld 11 inch 4J3020 CONDUIT /2 Flex N/A Radiant Energy Heat Shield 24 inch 4J6008 CONDUIT /1 1/2 N/A Radiant Energy Heat SNeld 12 feet 6 inch / Runs w/4U6054/ Trowel grade overley SU1039 CONDUlT/1 1/2 N/A Radiant Energy Heat Shield 3 feet 4U1115 CONDUIT /1 1/2 N/A Radiant Energy Heat Shield 6 inch 4U1152 CONDUIT /4 N/A Radiant Energy Heat SNeid 6 inch 4U1211 CONDUIT /1 Flex N/A Radiant Energy Heat Shield 6 inch 4U1220 CONDUIT /2 N/A Radiant Energy Host Shield 6 inch 4U1228 CONDtJIT/1 N/A Radiant Energy Heat Shield 6 inch 4U1245 CONDUlT/1 N/A Radiant Energy Heat SNeld 4 feet / support 1.5 so. ftJJ-Box 9 so. ft.
SU1246 CONDulT/1 N/A Radiant Energy Heat Shield 6 inch 4U1253 CONDUIT /1 N/A Rad %t Energy Heat Shield 6 inch 4U1254 CONDUlT/3 N/A Radiant Energy Heat SNeid 9 feet / supports SU1260 CONDUlT/l 1/2 N/A Radiant Energy Heat SNeid 12 feet i
4U1304 CONDUIT /1 1/2 Flex N/A Radiant Energy Heat SNeld 8 inch 4U1331
,CONDUlT/3/4 Flex N/A R6diant Energy Heat Shield 15 inch I
1 l
u
Attachment to WO 94-0013 Page 17 of 18 TABLE 2 (Continued)
WCGS Applications of Thermo-Lag 330-1 Material Required to Meet Regulatory Guide 1.75 Requirements
)
l C4mponent' Type / Size Hours Purpose Remarks 4U1335 CONDUfT/3/4 N/A Radiant Energy Heat Shield 9 inch 4U1340 CONDUlT/1 1/2 Flex N/A Radiant Energy Heat SNeld 6 inch 4U1348 CONDUIT /
N/A Radiant Energy Heat Shield 6 inch 4U1351 CONDUlT/3/4 Flex N/A Radiant Energy Heat Shield 6 inch 4U1C4X CONDUlT/1 N/A Radiant Energy Heat SNeld 15 inch CU2008 CONDUlT/1 Flex N/A Radiant Energy Heat Shield 8 inch 4U3033 CONDUlT/2 Flex N/A Radiant Energy Heat Shield 12 inch (U3A1J CONDUlT/3/4 N/A Radiant Energy Heat Shield 10 feet 4U3A2K CONDUlT/2 N/A Radiant Energy Heat Shield 10 feet 4U382U CONDUIT /1 N/A Radiant Energy Heat SNeld 3 feet /aupport - 1.5 sq. ft.
4U3B6E CONDUlT/2 N/A Radiant Energy Heat SNeld 4 inch i
4U3C4G CONDUlT/1 1/2 N/A Radiant Energy Heat Shield 10 feet
]
4U305R CONDUIT /4 N/A Radiant Energy Heat Shield 5 feet SU4004 CONDillT/2 N/A Radiant Energy Heat SNeld 98 feet 4U6030 CONDUlT/1-1/2 N/A Radiant Energy Heat Shield 6 inch 4U6054 CONDUlT/1 N/A Radiant Energy Heat SNeld 12 feet 6 inch / Runs w/4J6008/ Trowel grade overlay SC2004 CONDUIT /3/4 Flex N/A Radiant Energy Heat SNeld 6 inch 5C3074 CONDUlT/1 1/2 Flex N/A Radiant Energy Heat Shield 8 inch 5J1029 CONDUIT /3/4 N/A Radiant Energy Heat Shield 6 inch 5J1130 CONDUIT /3/4 Flex N/A Radiant Energy Heat Shield 6 inch 5J1150 CONDUlT/3/4 Flex N/A Radiant Energy Heat Shield 6 inch 5J1181 CONDUIT /1 1/2 N/A Radiant Energy Heat Shield 2 feet 5J1223 CONDUfT/1 1/2 N/A Radiant Energy Heat Shield 6 inch 5J1C1C CONDUIT /4 N/A Radiant Energy Heat Shield 6 inch DJ1M1F CONDUIT /3 N/A Radiant Energy Heat Shield 6 inch 5J2A1R N/A N/A Radiant Energy Heat Shield 2 feet / Air Drop Cable SJ3140 CONDUIT /3 N/A Radiant Energy Heat Shield 6 feet 5J3150 CONDUlT/1 N/A Radiant Energy Heat Shield 18 inch 5J6017 CONDUIT /1-1/2 Flex N/A Radiant Energy Heat Shield 6 inch 5SD101 AA N/A N/A Radiant Energy Hest Shield 24 inch / Monitor SD-RE-13/ Air Drop Cable l
SSDl01CA N/A N/A Radiant Energy Heat Shield 15 inch / Monitor SD-RE-23/ Air Drop Cable 5SDl01FA N/A N/A Radiant Energy Heat Shield 24 inch / Monitor SD-RE 18/ Air Drop Cable 5SDl02HA N/A N/A Radiant Energy Heat SNeld 15 inch / Monitor SD-RE-38/ Air Drop Cable 5S0103BB N/A N/A Radiant Energy Heat Shield 24 inch / Monitor SD-RE-40! Air Drop Cable SU1155 CONDUIT /3/4 l N/A Radiant Energy Heat Shield 6 inch SU1250 CONDUlT/3/4 Flex l N/A Radiant Energy Heat SNeld 13 inch SU2HIJ CONDUIT /1 Flex l N/A Radiant Energy Heat Shield 6 inch 6C3004 CONDUIT /2 l N/A Radiant Energy Heat Shield 6 inch 6C3015 CONDUlT/1 1/2 Flex N/A Radiant Energy Heat Shield 12 inch 6C3087 CONDUlT/1 1/2 N/A Radiant Energy Heat Shield 6 inch 6C8J1B CONDUlT/1 Flex N/A Radiant Energy Heat Shield 14 inch 6G3002 CONDUIT /4 N/A Radiant Energy Heat Shield 6 inch 6J1136 CONOUIT/3/4 N/A Radiant Energy Heat SNeld 6 inch j
6J1137 CONDUIT /1 Flex N/A Radiant Energy Hast Shield 8 inch 6J1140 CONDUlT/3/4 N/A Radiant Energy Heat Shield 6 inch 6J2A18 CONDUIT /1 N/A Radiant Energy Heat SNeld 6 inch j
6J3038 CONDUIT /1 N/A Radiant Energy Heat SNeld 18 inch 6J5848 CONDUIT /1 1/2 N/A Radiant Energy Heat Shield 1 foot 3 inch 6J5E1J CONDUlT/1 1/2 N/A Radient Energy Heat SNeld 6 inch
)
6J5E1J CONDUIT /3/4 N/A Radiant Energy Heat Shield 8 inch I
6J7B48 CONDUIT /1 N/A Radiant Energy Heat SNetd 16 inch (2 each) 6J8C3E CONDUIT /4 N/A Radiant Energy Heat Shield 6 inch 6J8C4F CONDUlT/4 Flex i N/A Radiant Energy Hest Shield 6 inch
Attachment to WO 94-0013 TABLE 2 (Continued)
Page 18 of 18 WCGS Applications of Thermo-Lag 330-1 Material Required to Meet Regulatory Guide 1.75 Requirements Component Type / Size Hours Purpose Remarks 6SDl02AA N/A N/A Radiant Energy Heat Shield 15 inch / Monitor SD-RE 25/ Air Drop Cable 6SD102GA N/A N/A Radiant Energy Heat SNeld 24 inch /Morutor SD-RE-12/ Air Drop Cable SU1126 CONDUlT/3/4 Flex N/A Radiant Energy Heat SNeld 6 inch 6U3112 CONDUlT/1 1/2 N/A Radiant Energy Heat SNeld 6 inch 6U3HIN CONDUIT /1/2 N/A Radiant Energy Heat SNeld 6 inch 6U5014 CONDUIT /2 N/A Radiant Energy Heat SNeld 6 inch 605D4G CONDUIT /1 N/A Radiant Energy Heat SNeld 3 feet / supports 6U5D9X CONDUIT /3/4 N/A ' Radiant Energy Heat SNeld 18 inch 6U7A1N CONDUlT/2 N/A Radiant Energy Heat Shield 2 feet ABHY18A CONDUIT /1 Flex N/A Radiant Energy Heat Shield 6 inch ABLY 7A/8B CONDUIT Flex /3/4 N/A Radiant Energy Heat Shield 6 inch ABLY 7A/8B CONDUIT F ex/3/4 N/A Radiant Energy Heat SNeld 10 feet BMHV1 CONDUIT Rex /3/4 N/A Radiant Energy Hast SNeld (2) 6 inch / unscheduled 1 Box 12 x 12 x 6 4 so. ft.
N/A CONDUlT/1 N/A Radiant Energy Heat SNeid 6 inch /Norslass Security Conduits N/A CONDUlT/1 Flex N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Flex between 1U4006/5U4562 i
N/A CONDUlT/1 Flex N/A Radiant Energy Heat Saield 6 inch / Unscheduled Flex between 404007/5U4563 N/A CONDUlT/1 Flex l N/A Radiant Energy Heat Shield 6 inch / Unscheduled Flex F/44011 l
N/A CONDUIT /1-1/2 l N/A Radiant Energy Heat SNeld 6 inch / Unmarked Comm. Con. at 481H60 N/A CONDUIT /1/2 Flex N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Flex F/1U4005 (T7.7',11*ETE)
[
N/A CONDUlT/1/2 Flex N/A Radiant Energy Heat SNeld 6 inch / unscheduled Flex between 104005/5J4085 i
N/A CONDUIT /1/2 Flex N/A Radiant Energy Heat Shield 6 inchMnscheduled Flex between 4U4007/5J4085 l
N/A CONDUIT /3/4 N/A Radiant Energy Heat Shield 6 inch /EMT LIGHTING CONDUIT f
N/A CONDUIT /3/4 N/A Radiant Energy Heat Shield 6 inch / Field routed lighting conduit N/A CONDUIT /3/4 Flex N/A Radiant Energy Heat Shield 6 inch /EJ HCV8625/Gaitronics N/A CONDUlT/3/4 Flex N/A Radiant Energy Heat Shield 6 inch / Unscheduled Flex between 1U4008/4U4010 7
N/A CONDUIT /3/4 Flex N/A Radiant Energy Heat Shield 6 inch / Unscheduled Flex between 1U4005/4U4007 I
N/A CONDUIT /3/4 Flex N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Flex for EPtW8878D N/A CONDUIT /3/4 Flex N/A Radiant Energy Heat SNeld 12 inch / Heat trace Flex et 1815302 f
N/A CONDUIT /3/4 Flex N/A Radiant Energy Heat Shield 6 inch / Unscheduled Flex F/1U4013 N/A CONDUlT/3/4 Flex N/A Radiant Energy Heat Shield 6 inch / Unscheduled Rex F/1U4011 N/A CONDUIT /3/4 Flex N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Flex between 1U4011/4U4014 N/A CONDUlT/3/4 Flex N/A Radiant Energy Heat Shield 6 inch / Unscheduled Flex between 1U4011/1U4014 N/A CONDUlT/3/4 Flex N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Flex between 1U4006/5J4086 N/A CONDUlT/3/4 Flex N/A Radiant Energy Heat Shield 6 inch / Unscheduled Flex between 1U4006/4U4008
[
N/A CONDUIT /3/4 Flex l N/A Radiant Energy Heat Shield 6 inch / Unscheduled Flex between 1U4005/5U4563 N/A CONDUIT /3/4 Flex l N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Flex F/1U4005 (T7. 6* 6*E TE)
N/A CONDUIT /3/4 Flex ! N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Flex frorn 4U4007 N/A CONDUlT/3/4 Flex l N/A Radiant Energy Heat Shield 6 inch / Unscheduled Flex between 4U4007!5J4085/See WR 00370 94 N/A CONDUlT/3/4 Flex N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Flex Fi4U4008 N/A CONDUIT /3/4 Flex N/A Radiant Energy Heat SNeld 6 inch / Unscheduled Rex F/4U4015
. - -