ML20064E193

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violation Noted in IE Insp Rept 50-358/75-05.Corrective Actions:Two Cans of Stainless Steel Electrodes Stored in Separate Holding Ovens & Weld Rod Control Clerk Reinstructed on Proper Procedure
ML20064E193
Person / Time
Site: 05000000, Zimmer
Issue date: 10/29/1975
From: Borgmann E
CINCINNATI GAS & ELECTRIC CO.
To: Hunnicutt D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20064E073 List:
References
FOIA-82-206 NUDOCS 8301050164
Download: ML20064E193 (2)


Text

p** w 1, - -

[s

  1. d i

,Jp>">

~

THE CINCINNATI GAS & ELECTRIC COMPANY EC f CIN CIN N AT1.QMIO 4 5201 O}ctober 29, 1975

.5 ^i.P.f.7.$.".^."."

U.S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region III 799 Roosevelt Road Glen Ellyn, Illinois 60137 Attention:

Mr. D. M. Hunnicutt, Chief Construction and Engineering Support Branch RE:

WM. H.

ZIMMER NUCLEAR POWER STATION -

UNIT 1 - IE INSPECTION REPORT NO.

050-358/75-05, W.O.

57300-957, JOB E-5590 Gentlemen:

This letter constitutes our formal reply to your Inspection Report Letter dated October 16, 1975.

It is our opinion that nothing in your report or in this reply involves any information of a proprietary nature.

The NRC routine unannounced inspection was conducted by Messrs. T. E. Vandel and W. J. Key on September 23-24, 1975.

j The Inspection Report lists one activity shown as a " deficiency",

involving the storage of welding electrodes in a manner not in compliance with the Constructor's procedures for safety related pipe welding electrodes'.

The deficiency identified by the inspector was a holding oven containing cans of both stainless steel and low hydrogen carbon steel electrodes.

The applicable Special Process Procedure No. 3.3, Revision 4, requires that these classes of electrodes be stored in holding ovens contain-i ing only one single classification of electrode.

The immediate corrective action, performed in the presence of the inspector, was the removal of the two cans of ptainless steel electrodes from the oven and placing them in h separate holding oven.

e-The steps taken to prevent recurrence of this defi-l ciency were verbal instructions to the weld rod control clerk, I

reminding him of the necessity to comply with the pr6cedure; l

and a written memorandum by the Chief Welding Engineer directing the rod shack clerk at the construction site to maintain the required segregation.

l 8301050164 821116 PDR FOIA

.. 7 l

DEVINE82-206 PDR e '

u To:

U.S. Nuclear Regulatory Commission October 29, 1975 Re:

Wm. H. Zimmer Nuclear Power Station -

- Page #2 Unit 1 - IE Inspection Report No.

5 050-358/75-05, W.O. 57300-957, Job E-5590

.I Subsequently this matter has been the subject of QC inspection and informal QA auditing on practically a daily basis.

Such surveillance will be continued.

We are of the opinion that the condition described above had no safety significance on the construction project, and that the corrective actions and future surveillance will serve to prevent recurrence.

We trust that this letter will serve as an acceptable response to your inspection report.

Very truly yours, THE CINCINNATI GAS & ELECTRIC COMPANY By 7'* "

E. A. BORGMANN EAB: dew cc:

W. H. Dickhoner E. C. Pandorf i

i 4

-