ML20062L708
ML20062L708 | |
Person / Time | |
---|---|
Site: | Salem |
Issue date: | 09/19/1980 |
From: | Bailey J, Connor G Public Service Enterprise Group |
To: | |
Shared Package | |
ML18085A819 | List: |
References | |
I-4.9-01, I-4.9-1, NUDOCS 8102170406 | |
Download: ML20062L708 (19) | |
Text
-
- .- . 1-4.9 l E?IRGENCY INSTRUCTION P B KbuT 1.0 Pm:0?E ,
- 1 IHIS INSTRUCTION PROVIDES THE STEFS REQUIRED TO RECOVER THE STATION FOLLOWING A "3LACKOUT".
' 1.1 A '3LACKOUT", l.0SS OF POWER TD THE 4KV GROUP 3USSES, WILL RESULT IN A REACTOR TRIP, TURBINE TRIP, AND A LOSS OF STATION POWER TO BOTH UNIT 1 AND UNIT 2. THE 4KV VITAL 3USSES WILL BE AUTOMATICALLY ENERGlZED FRCM THE EMERGENCY DIESEL GENERATORS. THE
~ 4KV GROUP EUSSES CAN BE MANU/LLY ENERGlZED FROM THE GAS IURBINE GENERATOR.
1.2 SINCE A 3LACKOUT WILL RESULT IN A LOSS OF FORCED FLOW THROUGH THE REACTOR, DECAY HEAT WILL BE REMOVED BY NATURAL C:RUCLATION. IHIS INSTRUCTION PROVIDES THE GUIDELINES TO ;
BE FOLLOWED TO VERIFY NATURAL CIRCULATION.
2.0 INI~Ial CONDITIONS 2.1 GENERAL LOSS OF ELECTRICAL PCwER.
F 3.0 1**E! ATE acT10E 5.1 S UWm t W
3.1.1 REACTOR IRIP - IdRBINE IRIP 3.1.2 4KV VI- t BUS LOADS STRIPPED.
3.1.3 DIESEL 6ENERATOR STAR ~ AND LOAD IN THE BLACKOUT MODE.
3.1.4 THE 13(23) TURBINE DR:VEN AuxrLIARY FEED PUMP STARTS 3.1.5 IHE EQUIPMENT LISTED :*: IABLE I WILL SEQUENCE ON THE BUS.
3.1.6 IHE FOLLOWING DC Ott FUMPS WILL START AS HEADER OIL PRESSURE DECREASES:
- 1) 11 1.12 (21 & 22) STEAM GENERAla FEED PUMP IURBINE EMERGENCY Ott PUMPS.
- 2) 1 & 2 TURBINE GENERATOR EMERG(NCY BEARING 0!L PUMPS
- 3) 1 & 2 EMERGENCY SEAL OIL pumas.
3.2 MMUAL 3.2.1 VERIFY THAT A REACTOR TRIP HAS TAKEN PLACE:
I" 1) CHECK THAT ALL FU' . LENGTH RCDS ARE FULLY INSERTED BY CHECKING INDIVI: UAL RCD POSITION INDICATORS AND RCD BOTTCM LIGHTS.
81 02170gcg ,
SALEM us:T 1/ UNIT 2 1 0F 19 REv.10
I-4.9
- 2) IF ALL FULL LENGTH CONTROL RODS ARE NOT FULLY INSERTED, RAPID BORATE BY 150 PPM FOR EACH RCD NOT FULLY INSERTED AS FOLLOW:
W .
A. 3HIFT ONE OR BCTH 30RIC ACID TRANSFER PUMPS TO FAST SPEED.
~
B. OPEN 1(2)CV75, RAPID 30 RATION STOP VALVE. -
C. 30 RAT'E FOR AT LEAST 8 MINUTES FOR EACH RCD NOT FULLY INSERTED (4 MINUTES WITH BOTH PUMPS IN FAST).
3.2.2 VERIFY TURBINE TRIP BY CHECKING THE FOLLOWING:
- 1) UNIT TRIP LIGHT ON E/H CONSOLE ILLUMINATED.
- 2) TURBINE STOP VALVES, GOVERNOR VALVES, INTERCEPTOR VALVES AND REHEAT STOP VALVES CLOSED.
- 3) TURBINE $ PEED DECREASING.
IF THE TURBINE HAS NOT TRIPPED, PROCEED AS FOLLOWS UNTIL STEAM FLOW FF..M THE STEAM 6ENERATORS IS TEFMINATED.
- 4) INITIATE A MANUAL TRIP WITH THE HANDLE ON THE CONSOLE
- 5) TRIP CLOSED THE MA*N $ TEAM ISCLATION VALVES, 11-14(21-24)MS167 FROM EITHER
'HE SAFEGUARDS BEZE S OR MAIN STEAM BEZELS.
W IF THE UNCONTROLLED STE AM FLOW HAS CAUSED REACTOR COOLANT SYSTEM PRESSURE TO DECREASE To <1755#, INSJRE $AFETY INJECTION IS ACTUATED. IF SAFETY INJECTION IS NOT ACTUATED, INITI ATE IT MANUALLY BY INSERTING THE 3AFEGUARDS KEY INTO EITHER IRAIN "A" OR "3" SAFETY INJECTION OPERATE BEIEL AND TURN THE KEY.
PROCEED TO El I-4.0, "D FETY INJECTION INITIATION".
3.2.3 VERIFY THAT RCS WIDE Rana; TC IS DECREASING TOWARD OR IS BEING MAINTAINED AT 547'F BY ATMOSPHERIC STEAM RELIEF.
3.2.4 ANNOUNCE OVER THE PLANT PA $YSTEM TWICE: " UNIT NO.1(2) REACTOR TRIP".
4.0 SimSEQtTNT ACTIONS COPENTS 4.1 VERIFY ALL IMMEDIATE ACTIONS ARE COMPLETED.
ACCOMPLISH ANY WHICH HAVE NOT.
4.2 VERIFY AUXILIARY FEEDWATER FLO4 IS ESTABLISHED TO AT LEAST TWO STEAM GENERATCRS BY CHECKING THE AUXILIARY FEEDWATER FLOW INDICATORS CN THE CONTROL CONSOLE.
i 4.2.1. IF FLCW HAS NOT EEEN ESTABLISHED, ?ROCEED AS FOLLOWS:
$gg hae llois ? I /lleef
- 7 ** 10 0 "'
- iO
- . . [_4,9
, . 1) CHECK THE DISCHARGE PRESSURE ON THE I MOTOR DRIVEN AUxlLIARY FEEDWATER PUMPS fil 8 12, 21 & 22) WHICH ARE RUNNING s
11 SHouto INDICATE 11350#.
t .
- 2) IF PRESSURE IS LOW 9 1350#) DEPRESS 2) THIS WILL REMOVE THE PUMP t THE PRESS OVERRIDE TEFEAT PUSHBUTTON RUN0UT PROTECTION.
ON THE CONSOLE BEZE'. FOR EACH Aux. THE DISCHARGE PRESSURE TRANS-FEEDWATER PUMP WITH A LOW PRESSURE. MITTER MAY BE FAILED LOW PREVENTING THE DISCHARGE VALVES FROM OPENING.
- 3) IF PRESSURE IS 11350# CHECK THE 3) A FAILURE IN THE PUMP RUNOUT VALVE DEMAND SET AT $95: FOR PROTECTION CIRCUlTRY MAY 11-14(21-24)AF21 ON THE CONSOLE PREVENT THE DISCHARGE VALVES BEZEL. ALSO, DEPRESS THE PRESS FROM CPENING.
4 OVERRIDE DEFEAT PUShBUTTON ON NO. 1](23) FEEDS NO. 13 E THE CONSOLE BEZEL F"R kACH 14(21824) STEAM GENERATOR 3.
i AUXILIARY FEEDWATER PUMP FOR No. 12(22) FEEDS No. 11 &
WHICH THERE IS NO F_0W. 12(21 & 22) STEAM 6ENERATORS.
! 4) IF EXCESSIVE FLOW IS INDICATED TO ONE OR MORE STEA*4 GENERATORS, RE-ESTABLISH THE PU:'P RUNOUT PROTECTION BY DEPRE'; SING THE
{v -
PRESS OVERRIDE NORFAL PUSH-i BUTTON CN THE CONSC.E FOR THE ,
AFFECTED Aux!LIARY FEEDWATER
! PUMP (S). PROCEED T' El i l-4.6, "l0SS OF SEC'NDARY COOLANT".
.l ,
- 5) START, IF No ALREADV RUNNING, NO.
13(23) aux!LIARY FEEDWATER PUMP AND VERIFY 11-14(21-24)AF11 ARE OPEN.
- 6) IF THE MAIN STdAM ISOLATION VALVES, 6) RUNNING NO. 13(23) Aux FEED 11-14(21-24)MS167, 4RE CLOSED, STOP PUMP WITH 11-14(21-24)MS167 NO. 13(23) aux FEED PUMP WHEN CLOSED MAY RESULT IN A STEAMLINE i NO. 11112(21122) Au<. FEED PUMPS aP SAFETY INJECil0N.
ARE RUNNING.
4.3 VERIFY DECAY HEAT REMOVAL BY NATURAL CIRCULATION 4.3 IT MAY TAKE SEVERAL MINUTES
. BY CBSERVING THE FOLLOWING: TO ESTABL!$H NATURAL CIRCULA-TION INDICATIONS DUE TO IN-CREASED LOOP TRANSIT TIMES.
- c. ... . t m... 9 1r .,- u Dev 10
i l-4.9 1
. 4.3.1 INCORE THERM 0 COUPLES A'JD LOOP WIDE RANGE THARE STABLE OR SLOWLY DECREASING. >
4.3.2 STEAM GENERATOR PRESSURE IS $1000 PSIG FOR ALL STE M GENERATORS FOR WHICH LOOP aT IS <62*F.
4.3.3 REACTOR COOLANT l.00P AI 162*F CN ONE OR MORE LOOPS.
4.4 ESTABLISH OR MAINTAIN THE FOLLOWING CONDITIONS TO ENSURE MAXIMUM NATURAL CIRCULATION IS MAIN- 7 TAINED IN THE REACTOR COOLANT SYSTEM FOR DECAY HEAT REMOVAL.
4.4.1 REACTOR COOLANT PRESSU:E 1 2000 PSIG.
4.4.2 PRESSURIZER LEVEL 1 50%.
4.4.3 STEAM GENERATOR LEVEL i 10% IN THE NARROW RANGE CN AT LEA!T ONE STEAM GENERATOR, AND IF POSS:3LE, ALL FOUR.
4.3 VER!FY BOTH MAIN FEED PUMPS ACE TRIPPED. 4.5 TURBINE EXHAUST TO No. 11(21) v IF EITHER 13 NOT TRIPPED, THE IRIP PUSH- CONOENSER MAY' OVERPRESSURE THE BUTTON ON THE APPROPRIATE CON 90L CONSOLE CONDENSER SHELL.
BE::EL.
4.6 MAINTAIN THE UNIT IN A HOT STMOBY. 4.6 IT IS PREFERRED TO MAINTAIN CONDITION AS FOLLOWS UNTIL OFF-SITE POWER THE UNIT IN HOT STANDBY.
IS RESTORED. IF NECESSARY, PLACE THE PLANT IN COLD SWuTDOWN AS DIRECTED LY APPENDIX 1.
4.6.1 MAINTAIN STEAM GENERATOR PRESSURE BY 4.6.1 FOR CONDITIONS WHERE A HIGH ADJUSTING THE SETPolNT FOR THE ATMOS- DEGREE OF DECAY HEAT IS PRE-PHERE STEAM RELIEF VALSES, MS-10's SENT, THE AI INDICATED WILL TO MAINTAIN THE LQEEE CF FOLLOWING APPROACH THE FULL LOAD AI.
CONDITIONS; SINCE THE STEAM GENERATCR PRESSURE IS INDICATIVE OF IC
, 2) INCORE THERMCCOUPLE IEMPERATURES AS $610*F FOR A STEAM GENERATOR
<600*F. PRESSURE OF 1000 PSIG. IHERE-FORE A REDUCTION IN STEAM 6ENERATOR PRESSURE MAY BE REQUIRED.
l 4.6.2 IF ADJUSTMENTS IN STEAR GENERATOR 4.6.2 RESPONSES IN TEMPERATURE ARE l t l PRESSURE ARE REQUIRED, MAKE THE SEEN SLOWLY DUE TO LONG LOOP ADJUSTMENTS SLOWLY. TRANS!ENT TIMES.
.)
Sr.!? " " 1/t.N:.T 2 D ,;r 19 REv.10
9 l-4.9 ,
4.6.3 REFER TO THE PRESSURE-IEMPERATURE 4.6.3 SAMPLE CALCULATION:
CURVE TO CALCULATE THE STEAM PRESSURE AI IS 67'F, STEAM PRESSURE '
REQUIRED TO MAIN 1AIN TFE DES! RED 1000#, TC IS 547; SO Tg tS REACTOR COOLANT TEMPERATURE. 609'F.
TO REDUCE I BY 10'F, TC MuST .
' H BE REDUCED BY 10*F SINCE AI IS CONSTANT.
REDUCE STEAM GENERATOR PRES-SURE To s950 PSIG.
4.6.4 MAINTAIN STEAM GENERATCR LEVELS AT
$33: BY CONTROLLING THE AF-11 AND AF-21 FOR EACH STEAM 6E'lERATOR.
CAUTION: IF THE LEVEL IN ANY STEAM IME FEED RING DRAINS SLOWLY GENERATOR HAS 3EEN <10% IN THROUGH THE LOOSE FIT CONN-THE NARROW RA.*1GE,FOR MORE ECTION TO THE FEED INLET THAN 5 MINUTES AND ALL FEED- PIPING.
WATER FLOW HAS BEEN ISOLATED IF CONDITIONS REQUIRE MAXIMUM FORMORETHAN3 MINUTES,Fp0W FLOW FOR DECAY HEAT REMOVAL MUST BE LIMITED TO < 10x10 CONSIDERATIONS, THIS TAKES LBM/HR. TO TFAT STEAM GEN- PRECEDENCE OVER THE WATER ERATOR UNTIL THE LEVEL IS HAMMER CONSIDERATION.
RETURNED TO >10% IN THE lv NARROW RANGE.
4.7 DETERMINE WHETHER THE BLACKoui IS DUE 4.7 CALL THE LOAD D!$PATCNER.
TO A LOCAL MALFUNCTION OR A FAILURE OF THE NEw FREEDCM AND XEENEY LINES. :sRCD TO MA;-
o... . . . .
4.8 OPEN OR VERIFY OPEN THE FOLLOV!NG:
3REAKERS AND DISCONNECTS.
4.8.1 500 KV BREAKERS, 1-5, 5-6, 2-6 1-8, 2-8, 2-10, 9-10, 1-9.
4.8.2 500 KV DISCONNECTS - 1760, 2T60.
4.8.3 13 KV BREAKERS 2, 2-3, 3-4, 4-5, 5-6, 1-6.
~
CAUTION: DO NOT QPEN 13 KV DISCONNECTS INTERLOCKS REQUIRE 6AS IUR3!NE IT50 AND 2T50. BREAKER AND 13KV 3REAKERS OPEN TO CLOSE THESE.
4.9 STRIP ALL LOADS FROM THE 4KV 690UP 3HSES 4.9 IO.!NSURE LOADS CO NOT IN-FOR UN!7 1 AND UNIT 2. OPEN CR CHECK ADVERTENTLY START WHEN BUS g
OPEN THE FCLLONING INFEED BREA<ERS TO FEED IS SUBSEQUENTLY CLOSED.
THE GROUP BUSSES.
4 P " t1 )/ UNIT 2 f. ; y 8.Ev. 10
I-4.9 1H - 11HSD 21AHGD 2H - 21H:D 1 2AHGD IE - 11ESD 8 1AEGD 2F - 2]EID & 2AEGD N IF'- 12FSD 1 1BFGD .2F - 21F;D 1 2BFGD 1G - 12GSD & 2BGGD 2G - 22G D 1 2BGGD 4.10 START THE GAS TURBINE LAW 01 V-13.3.3,
" DEAD BUS OPERATION 300TSTRAP CTARTUP".
4.10.1 WHEN THE GAS TURBINE l'; !N OPERATION RETURN TO THIS INSTRUCTION AND COMPLETE THE APPROPRIATE SUBSEQUENT ACTIONS.
4.10.2 IF THE 6AS IURBINE FA!.S TO START, PROCEED TO STEP 4.17.
4.11 COORDINATE THE CLOSURE OF THE COLLOWING 4.11 TO ENERGIZE NO. 11, 17, 23 13KV BREAKERS WITH THE LCAD D1iPATCHER: 1 22 STATION POWER IRANS-3-4, 4-5, 2-3, 5-G. PROCEED A0 FOLLOWS FORMERS.
FCR EACH BREAKER.
~
4.1].1 DEPRESS THE LOCAL PUSH 3UTTON ON THE APPROPRIATE BEZEL.
p 4.11.2 SELECT THE DESIRED BREAKER ON THE M MIC bus.
4.1].3 DEPRESS SYNC POT ON FC . THE DESIRED BREAKER.
4.11.4 CLOSE THE BREAKER.
4.11.5 DEPRESS SYNC POT OFF.
4.12 CLOSE THE FOLLOWING BREAKERS TO ENERGlZE 4.12 RECOVERY MAY PROCEED WHILE THE 4KV GROUP BUSES. AS EACH ::US IS ANY INVESTIGATICNS ARE CON-ENERGIZED CHECK THE BUS VOLTAGE s4160 DUCTED.
IF BUS VOLTAGE IS NOT AS EXPEC ED, REOPEN THE FEEDER AND INVESTIGATE THE CAUSE.
~
1H - 11HSD 2H - 21HSD 1E - 1]ESD 2E - 21ESD 1F - 12FSD 2E - 22FSD IG - 12GSD 2G - 22GSD
\
c .c ~ * ' %:- 2 : . so PEv. 10
I-4.9 4.13 START THE FOLLOWING EQUIPMENT ON THE 4.13 THE EXACT COMPONENT DEPENDS GROUP BUSES. MONITOR THE GAS IURBINE ON PLANT COND*TIONS AND h LOAD, VOLTAGE, FREQUENCY, ETC. FOR EQUIPMENT AVAILABILITY.
NORMAL RESPONSE. IF ABNORMAL COND!-
TIONS ARE OBSERVED, ,STOP THE PIECE OF EQUIPMENT AND INVESTIGATE.
CAUTION: Qq !(QI ATTEMPT TO START A REACTOR COOLANT PUMP.
4.13.1 4KV LOADS
- 1) ONE STATION AIR C:MPRESSOR
- 2) ONE CONDENSATE Pur=
- 3) ONE IllRBINE AUXILI ARY COOLING PUMP.
4.13.2 ENERGIZE THE 460V BUSES BY CLOSING 4.13.2 THE 460V AND 230V 3REAKERS THE INDICATED 4KV FEE ER. STOP DO NOT HAVE UNDERVOLTAGE ANY EQUIPMENT WHICH S* ARTS AND IS TRIPS AND WILL REMAIN CLOSED.
NOT DESIRED.
ENERGIZE ONE AT A TIME AND
- 1) 1H3D To LIGHTING EUS 1HL AND STABILIZE LOAD.
No. 1 500KV SwtTCrvARD 280V/
v 120V Bus.
- 2) 1F3D To LIGHTING EUS lfl.
. 3) 1E6D To IE 450V BUS AND PRES-SURIZER HEATER 3U~ 1EP.
- 4) 1G6D To 1G 460V BL.S AND PRES-SURIZER HEATER ButES 1GP (CON-TROL AND 3ACKUP HEATERS)
- 5) 1H5D To 1H 460V BUS AND 1H 230V 3us.
- 6) 1F5D To 1F 460V 3'.'S AND 1F 230V bus.
- 7) 2H3D To LIGHTING PUS 2HL AND No. 2 500KV SWITCrYARD 280V/ 120V bus.
- 8) 2F3D To LIGHTING sus 2Fl.
- 9) 2E6D To 2E 460V 3C3 AND PRES-g SURIZER HEATER 3UE 2EP.
er rw " l 'ti.;r ? ., y C v. 10
I-4.9
- 10) 2G6D TO 2G 460V EUS AND PRES-SURIZER HEATER 3CSES 2GP, (CON-TROL AND 3ACKUP FEATERS)
- 11) 2H5D 70,2H 450V EUS AND 2H 230V 3us.
- 12) 2F5D TO 2F 460V EMS AND 2F 230V EuS.
4.13.3 START, IF NOT ALREADY RUNNING, THE 4.13.3 SHOULD HAVE STARTED IF IM FOLLOWING PUMPS. AUTO.
- 1) ONE LUBE OIL PUMP ON NO.11,12 21 AND.22 STEAM 6E'iERATOR FEED PUMP.
- 2) AIR $1DE SEAL OrL ' UMP.
- 3) AUXILIARY 3 EARING )!L PUMP.
- 4) 3 EARING l!FT PUMP.
- 5) HIGH PRESSURE SEAL 0. ? UMP.
v 4.14 STOP THE FOLLOWING DC LUBE OIL PUMPS:
4.14.1 11, 12, 21 AND 22 FEED PUMP EMER-GENCY LUBE Ort PUMP.
4.14.2 1 AND 2 EMERGENCY AIR 51:E SEAL Ort PUMP.
4.14.3 1 AND 2 EMERGENCY BEAR.NG Ott PUMP.
4.15 RESET THE SAFEGUARDS LOADING SEOUENCE BY DEPRESSING THE EMERGENCY LOADIT:3 RESET PUSHBUTTONS ON THE CONTROL CCN: OLE FOR 1A, 13. IC(2A, 23, 2C) DIESEL GENERATORS.
l 4.15, PLACE TURBINE GENERATOR ON TUR';!NG GEAR.
IF TURNING GEAR TRIPS, DO NOT ATTEMPT RE?!ATED STARTS. THEREAFTER, ATTEMPT TO PLACE TURNING GEAR IN CPERA~10N AT
. CNE HOUR INTERVALS.
g 4.17 IF ut.ABLE TO UTILI:E THE 6AS IM 3tNE l GENERATOR, PROCEED AS FOLLOWS:
ihrrw iter - 1 IP.;!T
- 2" 0- 10; UN/ IU3
1-4.9 4.17.1 3REAK CONDENSER VACUUM TO REDUCE TURBINE 4.17.1 THE VALVES ARE MOTOR OPERATED.
ROLL TIME BY MANUALLY OPENING 11, 12, 13 -
(21, 22, 23)AR65 VACuut 3REAKER VALVES.
4.17.2 IHE DC EMERGENCY 3 FARING OIL PUMP SHOULD SUPPLY LUBRICATING OIL DURING THE ROLL DOWN TO ZERO SPEED AND FOR 1/2 HOUR THEREAFTER.
4.17.3 SUBSEQUENT OPERATION 0: THE DC PUMP 4.17.3 THIS WILL EXTEND THE USE-SHOULD BE INTERMITTENT; 0FF FOR 45. FULLNESS OF THE 250V BATTERY.
MINUTES AND RUN FOR 15 MINUTES, TO AVotD DAMAGING BEARING BABBITT.
4.17.4 DURING CPERATION OF THE EMERGENCY Olt 4.17.4 THERE IS NO POWER TO THE PUMP, ATTEMPT TO OPERA *E TURNING GEAR TURNING GEAR.
WITH AN AIR DRIVE ON GEAR, EXTENSION SHAFT.
4.17.5 REDUCE Hg PRESSURE IN THE MAIN GENERATOR TO < 2 PSIG IAW 01 IV-2.3.2, " GENERATOR GAS SYSTEMS - NORMAL C2ERATION", AS SOCN AS POSSIBLE TO PREVENT H2 LEAKAGE.
(v 4.17.6 ENERGl:E ONE GROUP OF RESSURIZER U
3ACKUP HEATERS FROM IT3 EMERGENCY 4.17.5 ENERGl:E THE BACKUP HEATERS FROM THE DIESEL WITH THE VITAL
- SUPPLY AS DESCR!3ED BY A, i LOWEST LOAD.
ca C BELOW: IHE ARRANGEMENT FOR 1E? AND 2FP ARE DIFFERENT. THE AR-A. ENERGlZE 1EP PRESEURIZER RANGEMENT FOR 1GP AND 26P HEATERS FROM 1A 4EJV VITAL 3US. ARE THE SAME. ,
- 2) OPEN 1E6D,' 4KV INFEED TO PRESSURIZER HEATER IRANS-FORMER, FROM THE CONTROL CON-SOLE.
- 3) RACK OUT 1E6D, AND REMOVE 3) ON 1E 4KV GROUP 3US IN THE KEY FROM I.S!DE THE BREAKER 64 FT. ELEVATION 3HITCHGEAR
- CUBICLE FOR THE CORREY KEY ROOM.
INTERLOCK.
( 4) ON 1E 460V GRCUP 3US IN
- 4) OPEN AND RACK OUT 1EX AND REMOVE THE KEY FOR THE 84 FT. ELEVATION S,41TCHGEAR
'CORREY KEY IN*ERLOCK. E00M.
? . i t? '.. . 6 .- .qq O e.. g
t I-4.9 ,
- 5) VERIFY 1A14X CPEN. 5) ON 1A 460V VITAL BUS IN 84 FT. ELEVATION SWITCHGEAR N
Ro0M.
- 6) 0/EN,ALL BUT THREE BREAKERS 6) IN 78 FT. ELEVATION ELECTRICAL
- L FOR INDIVIDUAL HEATERS ON THE PENETRATION AREA.
1EP HEATER Bus. EMERGENCY FEED WILL TRIP IF
>250 KW OF HEATERS ARE CON-NECTED.
THREE GROUPS IS
- 207 KW. ,
- 7) REMOVE THE PA LOCK AND CLOSE 7) ON COLUMN NEXT TO 1EP THE MANUAL Dl! CONNECT SWITCH HEATER 3US. ;
FOR THE EMERGENCY FEED TO No LOAD DISCONNECT SWITCH.
IEP HEATER 3U5.
- 8) INSERT THE KEYS FROM 1E6D AND 1EX INTO 1A14) AND CLOSE THE BREAKER.
- 9) OPERATE THE EE GROUP OF BACKUP HEATERS IN THE NORMAL MANNER.
. 10) OBSERVE THE LCAD ON 1A DfESEL 10) 2000 HR. RATING.
N GENERATING AN: VERIFY !T REMAINS <2750 <W.
- 3. ENERGlZE 2E? PRES!'JRIZER HEATERS FROM 2A 460 V VITAL 3uS.
- 1) OPEN 2E?X FR0f' THE PRESSURIZER 3ACKUP HEATER 3ROUP 22 BEZEL ON THE CONTROL CCNSOLE.
- 2) REMOVE THE KEY FROM THE BREAKER CUBICLE FOR 2EPX FOR THE CORREY KEY INTERI.0CK.
- 3) VERIFY 2A14X C=EN. 3) ON 2A 460V VITAL 3US IN 84 FT.
ELEVATION SWITCHGEAR ROOM.
- 4) OPEN ALL BUT THREE BREAKERS 4) IN 78 FT. ELEVATION ELECTRICAL FOR INDIVIDUAL HEATERS ON PENETRATION AREA. EMERGENCY THE 2E? HEATEF BUS. EEED WILL TRIP IF >250 xW ;
0F HEATERS ARE CONNECTED.
IHREE GROUPS IS s207 xW. i
\
- 5) REMOVE THE PA '.0CK AND CLOSE 5) ON COLUMN NEXT TO 2E? HEATER THE MANUAL D!!!CNNECT SWITCH 3US.
FOR THE EMERGENCY FEED TO 2E? NO LCAD DISCONNECT SWITCH.
HEATER 3uS.
- 4. .. . . -+,w a t * , c e ' t.0 'Rev "M1
~
1-4.9
- 6) INSERT THE KEY FROM 2EPX INTO BREAKER 2A14X AND CLOSE THE BREAKER.
- 7) OPERATE THE 2E3 GROUP OF BACKUP 7) IHIS SCHEME BYPASSES THE HEA1ERS FROM TWE CONTROL CONSOLE PRESSURIZER PRESSURE CONTROL BY DEPRESSING THE EMERG FEED ON SYSTEM.
ENERGlZE THE FEATERS AND THE CONTROL OF THE HEATER IS EMERG FEED OFF To DE-ENERGIZE STRICTLY MANUAL.
THE HEATERS.
- 8) OBSERVE THE LCAD ON 2A DIESEL 8) 2000 HR. RATING.
GENERATOR AND '.'ERIFY IT REMAINS
<2750 KW.
C. ENERGIZE 1GP(2GP) 2RESSURIZER HEATERS FROM IC(2C) 460V VITAL BUS.
- 1) OPEN 1GPX(2G?X} FROM THE PRESSUR:IER BACKUP HEATER ~
GROUP 11(21) ECZEL ON THE .
CONTROL CONSOLE.
- 2) VERIFY BREAKEp 1CPX(2CPX) 2) ON 1C(2C) 460V VITAL BUS IN I'" IS CLOSED TO PiOVIDE POWER 84 FT. ELEVATION SWITCHGEAR TO THE IC(2C) -60V VITAL ROCM.
3US EXTENSION.
POWER AVAILABLE LIGHT ON THE VITAL 3US EXTENSION IN 64 FT.
ELEVATICN SWITCHGEAR ROOM.
- 3) Vil!FY 1C23X(2C23X) OPEN. 3) ON 1C(2C) 460 VITAL 3US EXTENSION.
REQUIRES SDECIAL RACKING TOOL.
- 4) OPEN ALL BUT THREE BREAKERS 4) IN 78 FT. ELE,VATION ELECTRICAL FOR !NDIVIDUAL HEATERS ON PENETRATION AREA.
THE 1GP(2GP) HEATER BUS. EMERGENCY FEED WILL TRIP IF
>250 KW OF HEATERS ARE CONNECTED.
IHREE GROUPS IS s 207 xW.
. 5) RACK,0UT 1GPX(23PX) AND 3) IN 78 FT. ELEVATION ELECTRICAL REMOVE THE KEY. PENETRATION AREA.
- 6) REMOVE THE PADLOCK AND CLOSE 6) ON COLUMN NEXT TO 1GP(2GP)
THE MANUAL DISCONNECT SWITCH HEATER 305.
FOR THE EMERGENCY FEED To NO LOAD DISCONNECT SWITCH. l t 1GP(2GP) HEATE: Bus.
- 7) 1.NSERT THE KEY FROM 16PX(26PX)
IN 1C23X(2C23X: AND CLOSE THE BREAKER.
. . ,. 4,9 l
- 8) OPERATE THE 6E GROUP OF BACKUP 8) IHIS SCHEME BYPASSES THE ,
I HEATERS FROM THE CONTROL CONSOLE PRESSU.1!ZER PRESSURE CONTROL h BY DEPRESSING THE EMERG FEED ON TO ENERGIZE Thi HEATERS AND THE SYSTEM. CONTROL OF THE HEATERS
!$ STRICTLY MANUAL.
l EERG FEED OFF TO DE-ENERr!ZE ,
THE 'HEATEPS.
OlESEL 6ENERATOR AND VERIFY IT REMAINS <2750 KW.
4.17.7 WHEN OFF-SITE POWER !! AVAILABLE, ESTABLISH STATION POWER IN C00RDI-NATION WITH THE LOAD [ISPATCHER AS FOLLOWS: .
- 1) VERIFY THAT 5023 4:D/OR 5024 AND/OR 5015 LINES ARE ENER-GlZED.
- 2) CLOSE THE FOLLOWli;G BREAKERS FOR THE LINES WHICi ARE ENERGlZED:
5023 8 AND 2-E w 5024 6 5015 10 PROCEED AS FOLL0k? FOR EACH BREAKER.
A) DEPRESS THE LOCAL PUSHBUTTON.
B) SELECT THE DEE! RED BREAKER ON THE mimic Bus.
c) DEPRESS SYNC EDT ON.
D) CLOSE THE'3REAKER.
E) DEPRESS THE SYNC POT OFF.
~
- 3) CLOSE CIRCUIT SWI HES IT60 AND 2T60.
. 4) CLOSE THE FOLLOWING 13<V BREAKERS TO ENERG'. E THE NO. 1), 12, 23 AN: 22 STATION IRANSFORMERS:
1-2,1-6,3-4,4-5
- c. - " - i m.:. 7 ,, ,, 30 REv. 10
I-4.9
- 5) CLOSE THE FOLLOWING BREAKERS TO ENERGIZE THE 4KV OROUP BUSSES:
1H - 11HSD 2H - 21HSD 1E - 11ESD 2E - 21ESD -
IF - 12FSD 2F - 22FSD 1G - 12GSD 2G - 22GSD COORDINATE LOADING OF THE BUSSES WITH THE LOADING [ISPATCHER.
- 6) RETURN THE 4KV VITAL 3USSES TO NORMAL OPERATION I:W 01 IV-16.3.1,
" EMERGENCY POWER - DIESEL OPERATION".
CAUTION: IN THE EVENT ONE OF THE DIESEL PAS FAILED TO ENERGlZE ITS VITA:. BUS, THAT VITAL 6 3US MUST BE RETURNED TO OFF-SITE PCWER FIRST IN ORDER TO MAINTAIN MINIMUM OPERABLE SAFEGUAFOS EQUIPMENT.
4.18 IF THE GAS IURBINE GENERATOR 4AS STARTED IN STEP 4.9, CCNTINUE OPERATION UNTIL 5023 AND/CR 5024 AND/OR 5015 - 500xV LINES ARE ENERGIZED TO
$ALEM FROM NEw FREEDOM CR KEE:iEY. _ PROCEED AS FCLLOWS 17; COORDINATION WITH ~HE LOAD DISPATCHER TO RESUME NCRMAL STATION POWE9:
4.18.1 VERIFY THAT 5023 AND/C- 5024 AND/0R '
5015 500xV LINES ARE EhERG12ED.
CAUTION: TWO OFF-SITE POWER SUPPLIES 4.18.1 IHE USE OF TWO LINES PREVENTS MUST BE AVAILABLE BEFORE SYN- THE GAS IURBINE FROM ATTEMPT-CHRON! ZING #3 GENERATOR Wi1H ING TO SUPPLY A 500xV Ll'NE THE 500xV INFEED LINES, 50 THAT IF THE INFEED AT KEENE( OR VAR RATING CF THE #3 GENERATOR NEW FREEDOM QPENS UP.
IS NOT EXCEE*.ED.
r 4.13.2 CHECK THAT lib 0 CIRCut: SWITCH !$ OPEN.
4.18.3 CLOSE 2T60 CIRCult SWITCH TO ENERGlzE 500xV BUS SECTION 1.
4.13.4 CLOSE THE FOLLOWING BREAKERS FCR THE LINES WHICH ARE ENERG1:ED TO ENERGl:E
( 500xV bus SECTicN 2. '
5023 8 5024 6
, 5015 10
. w. , ,, . . . . w .. , , . , t . ,n ni o v. 10
l 1-4.9 l 211Il0![: WHILE NO. 3 GENERATOR IS
! SYNCHRONIZED TO TWO 500KV p LINES 5023 (en 5024) (OR 5015) THE THEE BREAKERS ASSOCIATED AT NEw FREEDOM .
OR*KEENEY WITH EACH LINE MUST BE CLOSED. VERIFY.
WITH LOAD DISPATCHER.
5023 - NEW F9EEDOM 3REAKERS 20X, 21X,22X.
5024 - NEw FREEDOM 3REAKERS 30X, 31X,32X.
5015 - KEENEY 3REAKERS 503 OR 504
{
l PROCEED AS FOLLOWS FOR EACH BREAKER:
J A) DEPRESS THE LOCAL >USMBUTTON.
B) SELECT THE DESIRED BREAKER ON THE MtMtC Bus C) DEPRESS SYN POT ON D) CLOSE THE 3REAKER E) DEPRESS THE SYNC F3T OFF -
4.13.5 IF THE 5023 LINE IS NOT AVAILABLE, 4.18.5 THIS WILL ALLOW 500KV CPEN THE LINE DISCONNE:: 21X50 AND BREAKER 1-8 TO BE USED To THEN CLOSE 500KV BREAKER 2-8 AS PARALLEL BUS SECTION 1 AND 2.
DESCR,IBED IN STEP 4.17 4 4.13.6 CLOSE IT60 CIRCutT SWITCH TO ENERGlZE 13KV bus SECT: N 1.
4.19 PARALLEL ACROSS AND CLOSE 500nv BREAKER 1-3 AS FOLLOWS:
4.19.1 SWITCH THE GAS IURR!NE FROM ISOLATED 4.19.1 THE GAS TURBINE MAY BE PRECISE TO PActLLEL CAUTION. GAS OPERATING IN EITHER LOCAL IURBlNE FREQUENCY MAY ECREASE AT A OR REMOTE. ADJUSMENTS CAN RATE OF Sl CYCLE /5 SECCNDS TO
- 57.5 BE MADE IN EITHER MODE.
HZ. [0bORRECT,SELECTMANUALONTHE 50VERNCR CONTROL AND RE-ADJUST THE FREQUENCY TO 60 HZ.
4.19.2 DEPRESS THE LOCAL PUSHSUTTON.
4.19.3 DEPRESS BREAKER 1-8 CN THE MIMIC Bus.
4.19.4 DEPRESS SYNC POT ON.
4 SALEn UNIT 1/ UNIT 2 14 0F 19 REv.10
.,. . .. .; o m
I-4.9 l 4.19.5 OBSERVE THE SYNCHROSCOPE AND THE 4.19.5 THE GAS IURBINE MAY BE RUNNING AND INCOMING VCLTAGE METERS OPERATING IN EITHER LOCAL OR (V ON THE CONTROL CONSOLE. IF THE SYNCHR0 SCOPE IS NOT ROTATING SLOWLY REMOTE. ADauSTMENTS CAN BE MADE IN EITHER MODE.
IN THE FAST DIRECTION, SELECT MANUAL .
ON THE 60VERNOR CONTRCL AND ADJUST THE 6AS IURRINE SPEED AS NECESSARY.
i 4.19.6 WHEN THE SYNCHROSCOPE :S 1-2 MINUTES BEFORE THE VERTICLE, CLOSE THE BREAKER.
4.19.7 DEPRESS THE SYNC POT OFF.
4.20 OPERATE THE GAS TURBINE AS DieECTED BY THE LOAD DISPATCHER.
4.21 RETURN THE 4KV VITAL BUSES TO NORMAL OPERATION IAW 01 IV-16.3.1, " EMERGENCY POWER - DIESEL OPERATION".
CAyTION: IN THE EVENT ONE OF THE DIESELS FAILED TO ENERG!ZE ITS VITAL BUS, "
THAT BUS MUST BE RETURNED TO OFFSITE POWER FIRST IN ORDER TO MAINTAIN MINIMUM SM E3UARDS EQUIP-MENT.
4.22 AS CONo!TIONS DICTATE, OPERATE LAW ONE OF THE FOLLOWING Ol'S:
4.22.1 01 l-3.8, " MAINTAINING HOT STANDBY" 4.22.2 01 1-3.3, " HOT STANDBY TO MINIMUM LOAD" 4.22.3 01 1-3.6, " HOT STANDBY TO COLD SHUTDOWN" PREPARED BY 1 EA f f ev /
MANAGER-SAIEMGENERATINGSTATION l REVIEWED BY G. CONNOR l
SORC MEETING NO. 74-Rn DATE !
/
k SALEM UNIT 1/ UNIT 2 15 0F 19 REV. 10
. . t
. I-4.9 TABLE I e
BLACKCUT LOADING SEQUENCE 011(21) #12(22) 13(23)
- DIESEL CENERATOR DTESEL CENERATOR DIESEL CENERATOR 1(21A 1(21B 1(21C 240/480V Breaker 240/480V Breaker 240/480V Breaker ,
11(21) Component Cooling Pump 11(21) Charging Pump 12(22) Charging Pump 11(21) Auxiliary Feed Pump 12(22) Component Cooling Pump 13(23) Component Cooling Pump 15(21) Servics water Pump 12(22) Auxiliary Feed Pump 11(25) Service Water Pump or* or*
16(22) Service Water Pump 14(24) Service Water Pump 12(26) Service Water
- Pump or*
11(21) Auxiliary Building 13(23) Service Water Pump Emergency Air Compressc '
Exhaust Fan 11(21) Reactor Shield Vent Fan 12(22) Auxiliary Building 11(21) Auxiliary Build-Supply Fan ing Supply Fan 11(21) Roseter Nozzle Suppor; 12(22) Auxiliary Building 1.3(23) Auxiliary Build-Vent Fan Exhaust Fan ing Exhaust Fan 11(2;) Ch:11er 12(22) Reactor Shield Vent 13(23) Reactor Nozzle Fan Support Vent Fan ,
(V 12(22) Reactor Nozzle Support 14(24) Reactor Nozzle Vent Fan Support Vent ran 12(22) Chiller 13(23) Chiller 11(21) Electrical Equipment Room 12(22) Electrical Equipment Rocm 13(23) Electrical Main Supply Fan Main Supply Fan Equipment Room Main Supply ran
- NCTE: Only the lead Service Water Pump will start, if the lead pump f ails to start the backup pump breaker will riose.
f i
I
\
TABLE I
, Salem Unit 1/ Salem Unit 2 16 0F 19 Rev.10 l
I-4.9 APPENDIX 1 h.0 PU:e0s; 1.1 TO PROV!DE THE INSTRUCTIONS NECESSARY TO PLACE THE PLANT IN A COLD SHUTDCWN CCNDITION WHILE ON NATURAL CIRCULATION :0LLOWING A STATION BLACKOUT.
2.0 INITIAL CONDITIONS 2.1 THE UNIT IS BEING MAINTAINED IN HOT STANDBY CONDITION ON NATURAL CIRCULATION.
2.2 NORMAL CHARGING AND LETDCWN ARE ESTABLISHED.
2.3 PRESSURIZER HEATERS ARE ENERG!!ED AND AVAILABLE TO MAINTAIN PRESSURIZER PRESSURE.
3.0 DECAUTIONS
~
3.1 LIMIT THE COOLDOWN RATE TO *D-25'F/HR.
3.2 HOLD TEMPERATURE AT $350*F rCR AT LEAST FOUR HOURS TO ALLOW STORED HEAT IN THE REACTOR VESSEL HEAD TO DISS!PATE. ,
3.3 MA:NT::N RC3 PRESSURE AS HIGF AS ALLOWED BY THE PRESSURE IEMPERATURE CURVE. .
(s 3 . 14 MAINTAIN RCS SuBCCOLING AT LEAST 50*F..
~
4.0 0:0CEDO I COMMENTS' 4.1 SAMPLE THE RCS TO DETERM!NE !:RON CONCENTRATION. SAMPLE THE FC. LOWING POINTS:
4.1.1 RCS HOT LEGS 4.1.2 LETDOWN LINE 4.1.3 PRESSURIZER LIQU!Q SPACE 4.2 BORATE THE RCS IAW 01-11-3.3.5, 4.2 REFER TO REACTCR ENGINEERING "30RCN CCNCENTRATION CONTRCL.' INCREASE MANUAL FIGURE 20A FOR THE COLD
, THE CONCENTRATION IN THE RCS scT LEGS SHUTDCWN CONCENTRATION.
AND LETDCWN LINE TO AT LEAST 100 PPM EXCESS BORATICN OF THE ACTIVE GREATER THAN THAT RECU! RED TC ACHIEVE PORTICNS OF THE RCS IS REOUIRED COLD SsuTDCHN. $1NCE THE PRESSURIZER CANNOT BE 3 CRATED.
I SALEM UNIT 1/ UNIT 2 REv. 10 17 CF le
\ '
~ , .
-1 s, I-4.9
N 4.3 SET THE BLENDER UP FOR AUTO w TH A . .
s s BORON CONCENTRATION EQUAL TO OF 3REATER
+
, THAN THE CONCENTRATION ESTABL15HED fBOVE.
\ ,
\
4.4 COMMENCE A CONTROLLEn C00LDOWN OF THE'SCS AS FOLLOWS:
4.4.1 SLOWLY OPEN THE ATMOSPHERIC $18AM' '
4.4.I' EITHER DECREASE THE AUTO SET-RELIEF VALVES. 11-14(21-24)MS10, POINTS OR PLACE THE VALVES IN MANUAL AND OPEN THEM. .,
4.4.2 ESTABLISH A C00LDOWN RATE OF <25'F. [ 4.4.2 MONITOR THE CORE E'i2T'THERMC-CUPLES AND WIDE RANGE it /
s? '
e 4 4.3 VERIFY NATURAL CIRCULATION IS MAIN-TAINEDBYOBSERVINGWIDERANG}IH $
AN" IC. IHEY SHOULD DECREASE AT, THE SAME RATE. 4 4.4.4 MAINTAIN PRESSURIZER PRES $URE'AS ,
i HIGH AS ALLOWABLE IAW TrE PRES $UPE- .
TEMPERATURE CURVE BY OPERATION CP - ,
THE PRESSUR!IER HEATERS AND AUXI- 3 LIARY SPRAY VALVE, 1(2)C/75. -
gv CAUT!0N
^
N' s NORMAL CHARGING AND LETDOWN MUST _.
REMAIN IN CPERATION WHEN USING AUXILIARY SPRAY.
a 4.4.5 REFER TO 01 I-3.5, " HOT STANDBY TO 4.4.5 SOME SYSTEMD MAY NOT BE COLD SHUTDOWN" FOR GUIDA*10E IN AVAILABLE DUE TO LOSS OF POWER.
THE OPERATION OF SUPPORT SYSTEMS DURING THE C00LD0hN. s 4.4.6 WHEN RCS TEMPERATURE REACHES ~350*F; 5 s ', .
TERMINATE THE C00LDOWN AND STABILIZE .
.. T ,y THE PLANT. g ,,
,4.4.7 MAINTAIN THE PLANT AT si 0*F WITH 4.4.7 ALLOW ALL PORTIONS OF THE ,
PRES $URE AS HIGH AS ALLOWABLE FOR \ . RCS TO SOAK AND EOUALIZE ' c' AT LEAST FOUR HOURS. TEMPERATURES. ' '
\ '
4.4.3 AFTER THE FOUR HOUR SCAK, REDUCE Nf.S ; ',/
PRES $URE SLOWLY USING THE AU)i1CIARY 'M SPRAY VALVE, 1(2)CV75. s
(
eu r- IN*- 1/Ust- ? se . in REv. 10
=;; ;
I
. m
- l
, 1 i
.* ? ,, e s .
s I-4.9
.. .. s e 4.4.9 CLOSELY MONITOR PRESSta!ZER LEVEL.. IF 4.4.9 RAPID CHANGES IN PRESSURIZER ;
UNEXPLAINED FLUCTUATICf3 ARE EXPERIENCED LEVEL INDICATE VOIDING IN THE !
- TERMINATE THE DEPRESSLRIZATION AND RC3, PROBABLY IN THE HEAD AREA.
REPRESSURIZE THE RC3 TO THE ORIGINAL VALUE. MAIN,TAIN THAT PRESSURE FOR AT LEAST AN A".DITIONAL T'n3 HOURS \3E(0RE ~
. ATTEMPT!NG'TD DEPRES$t'RIZE AGAIN.
4.4.10 PLACE THE RESIDUAL HEer Remove.
' ~ '
SYSTEM IN OPERA 716N 1/W 01 11-6.3.2, f-. "INITI ATING RESIDUAL FEAT REMOVAL."
^
- 4. 11 CONT!' l00LDOWN TO COLD (
s 3HUR .wNUIT!dNS.
w-s' s s ,
i" ,
~
s .
j *- 7 w..., ,. t.
' t
\
g
\\
~
,. e
\, n.
4 a
\
GV
(
-s y ', ;
s ,
s .
- j %.
\
- g ,
t
- - a ,
'g g
- 4. f \
.. i 1
+
sh 3 .
I w ,
,y s , }< ,
t % ,-
- ' 3' t [g . - ' -
,a , % ,
s\ ,s.(
I
% i v. %, , .
\' V.. '), I ,
tw !, 1, ,, t 3 _
. + V! g 3 g . - ,
v ._ j '
% .a , i+%, '"
si
, *,tt vv, a t <
g- .% 's
.\ - - t i N -- e-1 -
.j \ 7,, g ,.
h e
.y <
- ,~
C a. ew 't.- 1/IN.- 9 10 se 10 t a. .a
',; , .} '