GENuclear Energy l
- ee sin a comr.a 1.',5 (UT
- 1 AvT%E $1 kht. Ch !!b I2b l
April 7,1993 Docket No. STN 52-001 Chet Poslusny, Senior Project Manager Standardization Project Directorate Associate Directorate for Advanced Reactors and License Renewal Office of the Nuclear Reactor Regulation
Subject:
Submittal Supporting Accelerated ABWR Review Schedule - Iluman Factors Engineering
Dear Chet:
Enclosed are clean markups of the HFE Tier 1 information and SSAR Appendix 18E, ABWR Human-Machine Interface Design Implementation Process.
Please provide a copy of this transmittal to Clare Goodman for her review and concurrence.
Sincerely, O het Jack Fox Advanced Reactor Programs cc: Norman Fletcher (DOE) w/o enclosure Keith Gregorie (GE) w/o enclosure i
090020 do nm2 5
9304090313 930407 PDR ADOCK 05200001 PDR A
I
A"j'yu jas weur ABWR oesign oocument y
3,6 Human Factors Engineering Design Description The ABWR certified design's.p human-system interfaces (HSI) will be developed, designed, and evaluated based upon a human factors systems analysis Acro %.
M and shall reflect hum (an4prmciples. The ;m. ;3 HSI scope w(Log $...wd m thc wing hmfapf +c phm oper*m pe=nnelin the Niain r.unt 1 A-Control Room (NICR) and RegtgSgtdown System (RSS). Further,within the 51CR, the ymd HSI scope is de ~d a that area which provides the displays, n
controls and alarms required for normal, abnormal and emergency plant operations.
The HSI design efrort will be directed by a multi-disciplinary HFE Design Team comprised of personnel with expertise in HFE and in other technical areas relevant to the HS1 design, evaluation and operations. An HFE Program Plan shall be developed, by the HFE Design Team, which establishes the methods for implementing the HSI design through a process of human factor systems analyses as shown in Figure 3.6. Implementation of that process will be as follows:
(a) A System Functional Requirements Analysis Implementation Plan shall be developed which establishes that plant system functional requirements will be analyzed to identify those functions which must be performed to satisfy the objecthes of each functional area. System function requirements analyses will be conducted to determine the objective, performance requirements and constraints of the design; and establish the functions which must be accomplished to meet the objectives and required performance.
(b) An Allocation of Functions Implementation Plan will be developed which establishes the methodology of allocating functions to personnel.
system elements and personnel-system combinations. An analysis of the i
allocation of system functions will be carried out according to the
{
provisions of the Allocation of Functions Implementation Plan.
j f
i (c) A Task Analysis Implementation Plan will be developed which
'f f establishes the methods for the conduct of the task analysis. The task
(/
analysis will be conducted according to the provisions of the Task
- /
Analysis Implementation Plan and will be used to identify the
/
behavioral requirements of the tasks the personnel are required to 'h perform in order to achieve the functions allocated to them. The task analysis will also be used to maintain human performance requirements within human capabilities; as an input for developing personnel skill, personnel training, plant procedures and svstem communication requirements and as an input to the evaluation of established plant 3.6 10/27/92
_______________________ ________ _____ _______ __ _________ _________~
x t *!T*
~ - -
p3gs ABWR oesign 0: cum:nt f gI C 0 QIOGN7tf1 TM e*+'
, e ~~ r,.> uo c.*arnos usuru-Ma r.s m y-operations control room staffing levels e task analysis wilhform the asis for specifying the requirements for the displays, data processing and controls needed to carry out the tasks.
l (d) A Human-System Interface Design Implementation Plan will be developed which establishes the methods for applying human engineering principles in the design definition'and enluation of the human-system interface (HSI). Human engineering principles will be used, as prescribed by the HSI Design Implementation Plan, during the HSI design definition and evaluation.
(e) A Plant and Emergency Operating Procedure Development Impiementation Plan will be developed which establishes the methods for the preparation of plant and emergency operating procedures.
Plant and emergency operating procedures will be prepared to support l'
and guide human interaction with plant systems and to support and guide human interactions in the control of plant operations. Human 4
engineering principles and criteria will be applied in the procedures l
preparation.
j FAcr*5 (f) A Humanherification and Validation Implementation Plan will be developed which establishes the methods for the conduct of the evaluation of the ljSI design as an integral system using HFE evaluation p proceduresInhnnciple9 The HSI design will be evalug ts,an mtegrated system using the HFE evaluatiorfprocedures agnrmcipley
{
prescribed by the Human Factors Verification and Validauon l
Implementation Plan.
b Inspections, Tests, Analyses and Acceptance Criteria t'
Table 3.6 provides a definition of the instructions, tests, and/or analyses i
together with associated acceptance criteria which will be performed to demonstrate compliance with the HFE commitments for the certified design.
i I
i N
i i
3.6 10/27/92 1
4 9o Table 3.6: Human Factors Engineering Inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections, Tests, Analyses Design Acceptance Criteria 1.a. A multi-displinary Human Factors 1.a. The composition of the HFE Design 1.a. The HFE design team shall be comprised Engineering (HFE) Design Team shall be Team shall be reviewed.
of the following expertise:
established and be comprised of personel with expertise in HFE and in other technical (1) Technical Project Management areas relevant to the HSI design, evaluation and operation.
(2) Systems Engineering (3) Nuclear Engineering (4) Control and instrumentation Engineering 9
(5) Architect Engineering (6) Hurs.an Factors (7) Plant Operations (8) Computer Systems Engineering (9) Plant Procedure Development (10) Personnel Training 3
2
=.
J w
AL..R.
.m
_tma 4,
__,as.1 h
Lw 4
m m,-
ma L.
M ai.
,m ai._,
g Table 3.6: Human Factors Engineering (Continued) inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections Tests Analyses Design Acceptance Criteria 1.b The Human Factors Engineering (HFE[
1.b. An HFE Program Plan shall be developed 1.b. The HFE Program Plan shall be which establishes that the F.c.,7 human-reviewed.
Program Plan shall establish:
system interfaces shall be developed, designed, and evaluated beoed upon (1) Human System interface (HSI) design human factors systems analysis and shalt and evaluation methods and criteria.
,eei nor.s rox,,co. rem->c. :
reflect human factors prig'_. ^. Theg;d to the (2) The PZ "regrar "! n 05:!! -d-kees -
p'cq HSI scope shalk n
amtrehmd mca! sring EMe 4-*- of tM i
fplent-opeestions per e n 2 in ;he Main (i) The ability of the operating Control Room and Remote Shutdown personnel to accomplish assigned tasks.
System.
(ii) Operator workload levels and i
vigilance.
b (iii) Operating personnel " situation awa reness. "
(iv) The operators' information processing requirements.
(v) Operator memory requirements.
P (vi) The potential for operator error.
V J
ti (3) HSI design and evaluation scope which b
- eeeeeeee c44he+enteel end-meneteang interim nf e% pSe ;;;;;;;;n; M #"
- ;;.ne' in the Main Control Room g w4 T gp7f37^((7pgrecT (MCR) and Remote Shutdown System T
ME #d (RSS). The HSI scope shall address hg6&f^'#5 r
WE M
sd80 "ormal, abnormal and emergency ss p g c 50*',,E L.
plant operationspaeluding u
S en a-A --* e n of y e a; u pu,m.u n f 8
'w i
d"?hg p-'!Gd whenp!o..i eysioni/ --
oc upment of+fSt uquign.m..;,e - --
.undergomg ;ee;. raa;n:;nen;; er --
Jaegocinni. The HSI scope shall also
. -. -. _ =. _ _..
... =
.. -- - - -_ ~
g Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections Tests Analyses Design Acceptance Criteria 1.b. Continued 1.b. Continued address the development of operating technical procedures for normal, abnormal and emergency plant operations and the identification of personnel training needs applicable to the HSI design.
(4) The HFE Design Team as being responsible for:
(i) the development of HFE plans and procedures; (ii) the oversight and review of HFE V'
design, development, test, and evaluation activities; (iii) the initiation, recommendation, and provision of solutions through designated channels for problems identified in the implementation of the HFE activities; (iv) verification of implemention of solutions to problems; (v) assurance that HFE activities comply to the HFE plans and procedures, and (vi) phasing of activities.
9 (5) The methods for the identification, d
closure and documentation of human I
factors issues.
1.
(6) The HSI design configuration control procedures..
-+-w
.m
-r-~
.m--
--r-w---.-- - - -.
-,---er-
g Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections, Tests, Analyses f%:gn Acceptance Criteria 2.a. A System Functional Requirements 2.a. The System Functional Requirements 2.a. The System Functional Requirements Analysis implementation Plan shall be Analysis implementation Plan shall be Analysis implementation Plan shall developed which establishes that plant reviewed.
establish:
system requirements shall be analyzed to identify those functions which must be (1) Methods and criteria for con-performed to satisfy the objectives of each ducting the System Functional functional area. System function analysis Requirements Analysis.
shall determine the objective, performance requirements, and (2) That system requirements shall constraints of the design; and establish the define the system functions and functions which must be accomplished to those system functions shall pro-meet the objectives and required vide the basis for determining the performance.
associated HSl performance requirements.
,?
(3) That functions critical to safety shall I,e identified.
(4) That descriptions shall be developed for each of the identified functions and for overall system configuration design itself. Each function shall be identified and described in terms of inputs (observable parameters which will indicate system status) functional processing (control process and performance measures required to achieve the fonction), functional operations (including detecting signals, measuring information.
comparing one measurement with d
another, processing information, 8
and acting upon decisions to produce a desired condition or result such as a system or component operation actuation or trip) outputs, feedback
l l
i g
Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria j
Design Commitment inspections, Tests, Analyses Design Acceptance Criteria 2.a. Continued 2.a. Continued (how to determine correct discharge of function), and interface requirements so that subfunctions are related to larger functional elements.
2.b. An analysis of system functional 2.b. The analyses of the system functional 2.b.The system functional requirements requirements shall be conducted.
requirements shall be reviewed.
analyses,Mconducted in accordance with the requirements of the Human Factors Engineering Program Plan and the System Functional Requirements Analysis implementation Plan.
L, AS COFAGCTEP to AccoudT
~
FOR HeMCONFoAMANefs, AfE 3
8 m
w n
w
-.,.e--r
-w
-w, e--
s e
'=-w.'-- m-a
--a.-
ua
g Table 3.6: Human Factors Engineering (Continued)
Inspections. Tests, Analyses and Acceptance Criteria Design Commitment inspections. Tests, Analyses Design Acceptance Criteria 3.a. An Allocation of Function implementation 3.a. The Allocation of Function implement-3.a.The Allocation of Function implement-Plan shall be developed which establishes station Plan shall be reviewed.
ation Plan shall establish:
the methods for allocating functions to personnel, system elements, and (1) The methods and criteria for the personnel-system combinations.
execution of function allocation, (2) That aspects of system and functions definition shall be analyzed in terms of resulting human performance requirements based on the user population.
(3) That the allocation of functions to personnel, system elements, and
,?
personnel system combinations shall reflect:
(i) sensitivity, precision, time, and safety requirements, (ii) reliability of system perfor-mance, and (iii) the number and the necessary skills of the personnel required to operate and maintain the system.
(4) That allocation criteria, rationale, analyses, and procedures shall be i
documented.
i$
S (5) That analyses shall confirm that the j
personnelcan perform tasks l
allocated to them while maintaining operator situation awareness, acceptable personnel i' -.
r--, n couccrw to Accovar foo koocowow'cU, g
Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections, Tests, Analyses Design Acceptance Criteria
~
3.a. Continued 3.a. Continued workload, and personnel vigilance.
3.b. A/2-+,-i e' % allocation e(functionM 3.b. The m'9 i e' %c allocationstdunctionA 3.b.The function allocation analyses #
/
shall be conducted.
shall be reviewed.
conducted in accordance with the requirements of the Human Factors Engineering Program Plan and the Allocation of Functions Implementation Plan.
4.
A Task Analysis implementation Plan shall 4.a. The Task Analysis implementation Plan 4.a. The Task Analysis implementation Plan be developed which establishes that task shall be reviewed.
shall establish:
analysis shall be conducted and used to identify the behavioral requirements of the (1) The methods and criteria for conduct of tasks the personnel are required to perform the task analyses.
g in order to achieve the functions allocated to them. The task analysis shall be used to (2) The scope of the task analysis which maintain human performance shall include operations performed at requirements within human capabilities; be the operator interface in the Main used as an input for developing personnel Comrol Room and at the Remote skill, personnel training, and system Shutdown System. The analyses shall communication requirements and as an be directed to the range of plant input to the evaluation of established plant operating modes, including start-up, operations control room staffing levels; normal operations, abnormal and form the basis for specifying the operations, transient conditions, low requirements for the displays, data power and shutdown conditions. The processing and controls needed to carry analyses shall also address operator out tasks.
interface operations during periods of maintenance test and inspection of plant systems and equipment and of i
the HS! equipment.
i l
(3) That the analysis shall be used to l
8 identify which tasks are critical to 5
safety.
~
e s
m. m
~
g Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections, Tests Analyses Design Acceptance Criteria 4.a. Continued 4.a. Co ntinued (4) That task analysis shall develop narrative descriptions of the personnel activities required for successful
/ n S <o# AEc re o ro completion of the task.
Acc oaa T W jvcw coarornas cES, M4 (5) That task analysis shall identify requirements for alarms, displays, data processing, and controls.
(6) That task analysis results shall be made available as input to the personnel training programs.
4.b. An analysis of tasks shall be conducted.
4.b. The task analyses shall be reviewed.
4.b. The task analyses
" S8 conducted in p
accordance with the requirements of the Human Factors Engineering Program Plan and the Task Analysis implementation Plan.
5.a. HS! Design implementation Plan shall be 5.a. The HSI Design implementation Plan shall 5.a. The HSI Design implementation Plan shall developed which establishes that human be reviewed.
establish:
engineering principles and criteria shall be applied in the design definition and (1) The methods and criteria for HSI evaluation of the HSI.
equipment design.
- 2) That the HSl design shall implement the information and control require-ments dev6foped through the task analyses, including the displays, controls and alarms necessary for the execution of those tasks identified in the task analyses as being critical tasks.
Oy (3) The methods for comparing the consistency of the HSI human performance, equipment design and associated workplace factors with that modeled and evaluated in the comple-
- - ~ -
g Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections Tests, Analyses Design Acceptance Criteria 5.a. Continued 5.a. Continued ted task analysis.
Osma (4) The HSI saign criteria and guidance for control room operations during e s cog g r erte ro g.
periods of maintenance, test and j
inspection.
r o.a c e a poivwets, a
W (5) The test and evaluation methods for resolving HFE/HSI design issues.These test and evaluation methods shall include the criteria to be used in selecting HFE/HSI design and 66 evaluation tools.
pt LO 5.b. The HSI designaimplementateq,shdbe 5.b. The HSI design implementation shall be 5.b. The HS_I design implementation and
" "' a nd reviewed.
analyses'ehe%e conducted in accordance with the requirements of the Human Factors Engineering Program Plan and the HSI Design implementation Plan, 6.a. A Plant and Emergency Operating 6.a. The Plant and Emergency Operating 6.a. The Plant and Emergency Operating Procedure Development implementation Procedure Development Implementation Procedure Development implement-Plan shall be developed which establishes Plan shall be reviewed.
ation Plan shall establish:
that plant and emergency operating procedures shall be developed to support (1) That operator actions identified in and guide human interaction with plant the task analysis shall be used as systems and to support and guide human the basis for specifying the interactions in the control of plant procedures for operations, operations. Human engineering priciples and criteria shall be applied in the (2) That the procedures to be procedures development.
developed shall address normal, 8
abnormal, and emergency plant 5
operations including consideration of plant operations during periods when plant systems / equipment and primary operator interface (i.e.,
g Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Commitment Inspections, Tests, Analyses Design Acceptance Criteria 6.a. Continued 6.a Continued main control room) equipment is i
undergoing test, maintenance or inspection.
gg,cygp r oA (3) Methods and criteria for development
[>g of the operating technical procedures.
A "!
f p a c a pow A * '.o (4) That a Writer's Guide shall be developed which establishes the process for developing the technical procedures for normal plant and system operation, abnormal plant operations, emergency plant operations and for responding to plant g
alarm conditions.
~-
6.b.The Plant and Emergency Operating 6.b. The Plant and Emergency Operating 6.b. The development of the Plant an]s.92" S d
Procedures shall be developed.
procedure development results shall be Emergency Operating Procedure.
reviewed.
conducted in accordance with the requ' aments of the Human Factors Engineering Program Plan and the Plant and Emergency Operating Procedure Development implementation Plan.
7.a. A Human Factors Verification and 7.a. The Human Factors V&V Plan shall be 7.a. The Human Factors V&V Implement-Validation (V&V) Implementation Plan shall reviewed.
ation Plan shall establish:
be developed which establishes that the HSI design shall be evaluated as an (1) Human factors V&V methods and integrate _d system _using HFE evaluation criteria.
C procedures an @rincipleD n
(2) That scope of the evaluations of the N
" 'T'#'d integrated HSI shall include:
8
g Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections, Tests, Analyses Design Acceptance Criteria 7.a. Continued 7.a. Continued (i) The HSI(including both the interface of the operator with the HSI equipment hardware and the interface of the operator with the HSI equipment's software driven functions).
(ii) The Plant and Emergency Operating Procedures, and (iii) the HS! work environment.
(3) That evaluations of the HSI equipment shall be conducted to confirm that the
,y controls, displays, and data processing functions identified in the task analyses are pre vided.
(4) That integration of HSi equipment with each other, with the operating personnel and with the Plant and Emergency Operating Procedures shall be evaluated through the conduct of dynamic task performance testing.
The dynamic task performance tests and evaluations shall have as their objectives:
(i) Confirmation that the identified critical functions can be achieved using the integrated HSI design, O
d (ii) Confirmation that the HSl design 3
and configuration can be operated using the established Main Control Room staffing levels,
g Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Cornmitment inspections Tests, Analyses Design Acceptance Criteria 7.a. Continued 7.a. Continued (iii) Confirmation that the Plant and Emergency Operating Procedures provide direction for completing the identified tasks associated with normal, abnormal and emergency operations, and i
(iv) Confirmation that the time dependent aspects of the HSI equipment performance allow for task accomplishment.
(5) That dynamic task performance test evaluations shall be conducted over f
the range of operational conditions and l
upsets.
(6) The HFE performance measures to be used as the basis for evaluating the dynamic task performance test results.
These performance measures shall l
address:
(i) Operating crew primary task performance characteristics, such as task times and procedure compliance, I
(ii) operating crew errors and error
- rates, g
(iii) operating crew situation l
s awareness, 8
(iv) operating crew workload, (v) operating crew communications and coordination.
.~.
g Table 3.6: Human Factors Engineering (Continued)
Inspections, Tests, Analyses and Acceptance Criteria Design Commitment inspections, Tests, Analyses Design Acceptance Criteria 7.a. Continued 7.a. Continued (vi) anthropometry evaluations, and (vii) HSl equipment performance measures.
(7) The methods to confirm that HFE issues identified and documented have been resolved, and n
(8) the methc 'a and criteria to be used to V'
confirm tha. critical human actions, as defined by the task analysis, have been addressed in the integrated HSl design.
7.b. A human factors engineering analysis of 7.b. The analyses of the integrated HSt design 7.b.The human factors engineering analysis of the integrated HSI design shall be rhall be reviewed.
Si desighb" be conducted in conducted.
y accordance with the requirements of the Human Factors Engineering Program Plan y
and the Human Factors V&V implementation Plan.
f53 CcKMECTEO f6<
/YCr!cer4fo/ft M et3, M E O
6
.e--
..m._--------.-4.-
+ -.. - - -
w
.w---
.,-_-e.
m SYSTEM FUNCTIONAL REQUIREMENTS ANALYSIS I
l I
4-
- - - - - - - J ALLOCATION OF FUNCTIONS (b) l i
I (c)
TASK ANALYSIS q
I 5
l 1
- - - H
(,) PROCEDURE DEVELOPMENT (d)
IN FACE N
I n
yI
_ _ _ _ __q l
HUMAN FACTORS
- - - - - ~~
j VERIFICATION AND VALIDATION IO (FEEDBACK) l f
IMPLEMENTED DESIGN l
g g
l l
i j
Figure 3.6 Human System Interface Design implementation Process.
... - ~...
.w._
+
+
,.s.3 u.
u--
A3 g
4 e
i i
4 APPENDIX 18E
- i ABWR HUMAN-MACHINE INTERFACE DESIGN IMPLEMENTATION PROCESS l
t i
4 1
4 I
T
APPENDIX 18E TABLE OF CONTENTS Section Tit!R Eage 18E Human System Interface Design implementation Process 18E.0 Introduction 18E.1 HSI Design Implementation Process 18E.2 HSI Design implementation Requirements ILLUSTRATIONS t
Flaure Ilt!!g Eggg 18E.1 -1 ABWR Human-System Interface Design implementation Process TABLES Table lille P_ggg 18E.2-1 HFE Design Team and Plans 18E.2-2 HFE Analyses l
18E.2-3 HSI Design and Procedures Development 18E.2-4 Human Factors Verification and Validation 6
I
i8E.0
. INTRODUCTION Section 18.3 discusses the program of human factors related activities conducted throughout the development of the ABWR plant system designs, including the development of the Main Control Room (MCR) and Remote Shutdown System (RSS) designs. Appendix 18E describes the process through which the MCR and RSS human system interface (HSI) design implementations will be conducted and evaluated through the application of accepted human factors engineering (HFE) practices and principles. Section 18E.1 discusses the basic elements of this HFE design implementation process and includes identification of where in the process the results are planned to be made available for NRC review. The criteria to be used by the NRC in their review of the design implementation, (i.e., the Design Acceptance Criteria - DAC),
are presented in Section 18E.2 18E.1 HSI DESIGN IMPLEMENTATION PROCESS The designs of the MCR and RSS areas of.p operator interface, for the execution of normal plant operation and emergency operation, will be implemented and evaluated in accordance with the process illustrated in Figure 18E.1-1. As shown in Figure 18E.1-1, the implementation process begins with the establishment of the Human Factors Engineering (HFE)'
Design Team which prepares the HFE Program and Implementation Plans and guides the process through the remaining steps to the final validation of the implemented design. Figure 18E.1-1 also identifies the relative timing of the planned NRC conformance reviews along with the corresponding table in Section 18E.2 that defines the accepance criteria applicable to the, individual reviews.
18 E.1.1 The HFE Design Team: The HFE Design Team will be composed of experienced individuals whose collective expertise cover a broad range of disciplines relevant to the design and implementation process. These disciplines willinclude technical project management, control and engineering, plant operations and architect engineering, as well as human factors engineering.
The duties of the HFE Design Team will be to establish the HFE Program and Implementation Plans, to guide and oversee the design implementation process and to assure that the execution and documentation of each step in the process is carried out in accordance with the established program and procedures. The team will have the authority to insure that allits areas of responsibility are accomplished and to identify problems in the implementation of the HSI design The team will have the authonty to determine where its input is required and to access work areas and design documentation. The team will also have the authority to control further processing, delivery, installation or use of HFE/HSI products until the disposition of a non-conformance, deficiency or unsatisfactory condition has been achieved.
18E.1.2 The HFE Program and implementation Plans: The HFE Design Team will establish the HFE Program and implementation Plans that provide overall direction and integration of the includes the RSS and MCR areas of p*=pa u tion activities for the specific HFE related design implementation and ev identify the individuals who comprise the HFE Design Team and establish the processes through which the HFE Design Team will perform its functions. Included in the HFE Program Plan will be a system for documenting human factors issues, that may be identified throughout the implementation of the designs, and the actions taken to resolve those issues. The HFE
Design Team will also establish the implementation Plans for conducting each of the following HFE related activities:
a) System functional requirements analysis r
b) Allocation of functions c) Task analysis d) Human-system interface design e) Procedure development f) Human factors verification and validation The implementation Plans will establish methods and criteria, for the conduct of each of these HFE related activities, which are consistent with accepted HFE practices and principles. (For additional detailed information regarding the scope and content of the HFE Program and Implementation Plans, refer to the acceptance criteria presented in Table 18E.2-1) 18E.1.3 System Functional Requirements Analysis: Analyses of the system functional requirements will be conducted through application of the methods and criteria established by the HFE Design Team in the System Functional Requirements Analysis implementation Plan.
The system functional analysis will determine the performance requirements and constraints of the HSI design and establish the functions which must be accomplished to meet these requirements. Safety functions will be specifically identified along with any functional interrelationship that those safety functions may have with non-safety systems. In addition, critical functions (i.e., functions required to achieve major system performance requirements or functions which,if failed, could degrade system performance or pose a safety hazard to plant personnel or the general public) will be identified. Detailed narrative descriptions will be developed for each of the identified functions.
18E.1.4 Allocation of Functions: The functions defined through the function analysis will then be allocated (i.e., defined as a function to be performed by the human, the system equipment or by a combination of the human and system equipment) per the methods and enteria established by the HFE Design Team in the Allocation of Functions implementation Plan.
The allocation of functions will be done to take advantage of areas of human strengths and avoid allocating functions to personnel which would be impacted by human limitations. The allocation of functions to personnel, systems or p6rsonnel-system combinations will be made to reflect: sensitivy, precision, time and safety requirements, required reliability of system performance and the number and level of skills of personnel required to operate and maintain the system.
As alternative allocation concepts are developed, analyses and trade-off studies shall be conducted to determine adequate configurations of personnel and system performed functions.
Analyses will be done to confirm that the personnel elements can properly perform tasks that are allocated to them while maintaining proper operator situational awareness, workload and vigilance.
18E.1.5 Task Analyses:
Following completion of the function allocation step, task analyses will be performed on those functions which have been allocated to personnel. These task analyses will be performed per the methods and criteria established by the HFE Design Team Task Analysis implementation Plan. The task analyses willidentify the behavioral requirements of the tasks associated with individual functions. Tasks are defined as groups of activities that have a common purpose, often occurring in temporal proximity, and which utilize the same displays and controls. The task analyses will: provide one of the bases for making design
decisions; e.g., determining before hardware fabrication, to the extent practicable, whether system performance requirements can be met by combinations of anticipated equipment, software and personnel; assure that human performance requirements do not exceed human capabilities; be used as basic information for developing manning, skill, training and communications requirements of the system; and form the basis for specifying the requirements for the displays, data processing and controls needed to carry out the tasks.
The scope of the task analyses shallinclude all operations performed at the operator interface in the main control room and at the Remote Shutdown System. The analysis shall be directed to the full range of plant operating modes, including startup, normal operations, abnormal operations, transient conditions, low power and shutdown conditions. The analysis shall also address operator interface operations during periods of maintenance test and inspection of plant systems and equipment and of the HSI equipment.
18 E.1.6 Human-System lnterface Design: As established by the HFE Design Team in their development of the HSI Design impismentation Plan, human engineering criteria will be applied along with all other design requirements to select and design the particular equipment for application to the MCR and RSS HSI. The HSI design willimplement the information and control requirements that have been developed in the task analysis, including the displays, control and alarms necessary for the execution of those tasks identified in the task analyses as i
being critical tasks. The equipment design configuration will satisfy the functional and technical design requirements and insure that the HSI is consistent with applicable HFE principles.
18 E.1.7 Procedure Development:
Plant and emergency operating procedures will be developed to support and guide human interactions with plant systems and to control plant-related events and activities. Following the methods and criteria established by the HFE Design Team in the Plant and Emergency Operating Procedures Development implementation Plan, the operator actions identified in the task analyses will be used as the basis for specifying the procedures for operation. The procedures developed will address normal, abnormal and emergency plant operations includinyonsideration of plant operations during periods when plant systems / equipment and pMc., operator interface (i.e., main control room) equipment is undergoing test, maintenance or inspection.
18E.1.8 Human Factors Verification and Validation: Following the methods and criteria established by the HFE Design Team in the Human Factors Verification and Validation Plan,
the successfulincorporation of human factors engineering into the implemented HSI design and the acceptability of the resulting HSI will be thoroughly evaluated as an integrated system.
The evaluations willinclude consideration of the HSI, the plant and emergency operating technical procedures and the overall work environment (e.g., lighting, ventilation, etc.).
Individual HSI elements will be evaluated in a static mode to assure that all controls, displays and data processing that vere identified in thegh al ses are availat,le and that they are designed according to acepted HFErpractices an - ncdieD in addition,theintegration of HSI elements with each other and with pet 5onnel will be evaluated and validated through dynamic task performance evaluation using evaluation tools such as a dynamic HSI prototype driven by real-time plant simulation models. The dynamic task performance evaluation will be conducted over the full range of operational conditions and plant maintenance activities including: normal plant operation; plant system and equipment failures: HSI equipment failures; plant transients and postulated plant emergency conditions
I HFE DESIGN TEAM V
HFE PROGRAM AND IMPLEMENTATION PLANS h (C CONFORMANCE REhlEW NR SEE TABLE 18E.2-1 FOR ACCEPTANCtiCRiTER:A)
SYSTEM FUNCTIONAL REQUIREMENTS ANALYSIS U
ALLOCATION OF FUNCTIONS
+
TASK ANALYSIS A
NRC CONFORMANCE REVIEW 4
(SEE TABLE 18E.2-2 FOR ACCEPTANCE CRITERIA) l I HUMAN-SYSTEM PROCEDURE DEVELOPMENT INTERFACE DESIGN I
m NRC CONFORMANCE REVIEW F (SEE TABLE 18E.2 3 FOR ACCEPTANCE CRITERIA)
HUMAN FACTORS VERIFICATION AND VALIDATION j g NRC CONFORMANCE REVIEW (SEE TABLE 18E.2-4 FOR ACCEPTANCE CRITERIA)
IMPLEMENTED DESIGN Figure 18E.1-1 1
ABWR Human System Interface Design implementation Process i
18E.2 HS1 IMPLEMENTATION REQUIREhENTS Section 18E.1 describes the process through which the ABWR Main Control Room (MCR) and remote shutdown system (RSS) areas of pdr7 operator interface will be implemented and evaluated. Figure 18E.1-1 presents the relative timing of the NRC conformance reviews which are planned throughout the MCR and RSS Human-System Interface (HSI) design implementation.
Tables 18E.2.1 through 18E.2.4 of this section define the requirements that are to be met by the HSI design implementation activities that are to be made available for review by the NRC. The HS1 design implementation-related Design Acceptance Criteria (DAC) which are established through Rule Making, (refer to Section 3.6 of the Tier 1 Design Certification material for the GE ABWR design), are defined such that there exists a direct correspondence between the DAC entries and requirements imposed herein on those design activities whose results are to be made available foi the NRC conformance reviews, as identified in Figure 18E.1-1. Those requirements presented in Table 18E.2.1 through 18E.2.4 which correspond to individual Tier 1 DAC acceptance criteria are specifically identified. Therefort, satisfaction of those specific requirements shall result in full compliance with the Certified Desip. Commitment and the corresponding Acceptance Criteria presented in the Tier 1 (Rule Making) DAC ctshlished for the HS1 design implementation.
i 1
1 REV. 4 102392
4 TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS 1.
HFE DESIGN'IEAM COMPOSITION (Satisfaction of the requirements presented herein shall result in the creation of an HFE Design Team which is in full compliance with the Item la Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification Material for the GE ABWR design).
1.
The composition of the Human Factor Engineering (HFE) Design Team shall include, as a minimum, the technical skills presented in Article (4), below.
2.
The education and related pmfessional experience of the HFE Design Team personnel shall satisfy the muumum personal qualification requirements specified in Article (4), below, for each of the areas of required skills. In those skill areas where related professional experi-ence is specified, qualifying experience of the individual HFE Design Team personnel shall include experience in the ABWR main contml room and remote shutdown system Human System Interface (HSI) designs and design implementation activities. The required pro-fessional expedence presented in those personal qualifications of Article (4) are to be sat-isfied by the HFE Design Team as a collective whole. Therefore, satisfaction of the pro-fessional experience requirements associated with a particular skill area may be realized through the combination of the professional experience of two or more members of the HFE Design Team who each, individually, satisfy the other defined credendals of the particular skill area but who do not possess all of the specified professional experience. Similarly, an individual member of the HFE Design Team may possess all of the credentials sufficient to satisfy the HFE Design Team qualification requirements for two or more of the defined skill areas.
3.
Altemative personal credentials may be accepted as the basis for satisfying the minimum personal qualification requirements specified in Article (4), below. Acceptance of such altemative personal credentinis shall be evaluated on a case-by-case basis and approved, documented and retained in editable plant construction files by the COL Applicant. The following factors are examples of alicmative credentials which are considered acceptable.
- a. A Professional Engineer's license in the regtured skill area may be substituted for the required Bachelor's degree.
- b. Related experience may substitute for education at the rate of six semmer credit hours for each year of experience up to a maximum of 60 hours6.944444e-4 days <br />0.0167 hours <br />9.920635e-5 weeks <br />2.283e-5 months <br /> credit.
- c. Where course work is related tojob assignments, post secondary education may be substiemM for experience at the rate of two years of education for one year experience.
Total candit for post secondary education shall not exceed two years experience credit.
?
2 REV.4 102392
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS 4.
Recuired Skill An-a Personal Oualification a.
Technical Project Management a.
- Bachelor's degree, and five years experience in nuclear powerplant design operations,and
- thme years management expenence b.
Systems Engineering b.
- Bachelor's of Science degree, and
- four years cumulative experiencein atleast three of the following areas of systems engineering; design, development,integra-tion, operation, and test and evaluation c.
Nuclear Engineering c.
- Bachelor's of Science degree, and
- four years nuclear design, development, test or operations expenence d.
Control and Instrumentation d.
- Bachelor's of Science (C&I) Engineering degree, and
- four years experience in design of process control systems, and
- experience in at least one of the following amas of C&I engineering; development, power plant operations, and test and evaluation c.
Architect Engineering e.
- Bachelor's of Science degree, and
- four years power plant control mom design expenence 3
REV.4 102392
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS Recuimi Skill Area Personal Oualification f.
Human Factors f.
- Bachelor's degree in human factors engi-neenng, engmeenng psychology or related science, and
- four years cumulative experience related to the human factors aspects of human-comauterinter-faces. Quaifying experience shallinclude experience in at least two of the following human factors related activities; design, devel-opment, and test and evaluation, and
- four years cumulative experience related to the human factors field of ergonomics. Again, qualifying experience shallinclude experience in atleast two of the following areas of human factors activi-ties; design, develop-ment, and test and evaluation g.
Plant Operations g.
- Have or have held a Senior Reactor Operator license
- two years experience in BWR nuclear power plant operations h.
Cornputer System Engineering h.
- Bachelor's degree in Electrical Engineering or Computer Science, or graduate degree in other engineering discipline (e.g., Mechanical Engineering or Chemical Engineering), and
- four years experience in the design of digital computer systems and real time systems applications 4
REV.4 102392
i
)
l TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS i
Recuired Skill Area Personal Oualification i.
Plant Procedure Development i.
- Bachelor's degree, and
- four years experience in i
developing nuclear power plant operatmg procedures j.
Personnel Training j.
- Bachelor's degree, and four years experience in the development of j
personnel training pro-i grams for power plants, and
- experience in the appli-cation of systematic training development methods II HUMAN FACTORS ENGINEERING PROGRAM PLAN I
1.
(Satisfaction of the requirements presented herein shall result in the creation of a Human Factors Engineering Program Plan which is in full compliance with the Item 1.b.
Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). The Human Factors Engineering (HFE) Program Plan shall establish:
- a. Methods and criteria, for the development and evaluation of the Main Control Room (MCR) and Remote Shutdown System (RSS) HSI which are consistent with accepted HFE practices and principles. Within the defined scope and content of the HFE Program Plan, accepted HFE methods and criteria are presented in the following i
documents:
l (i) AR 602-1, Human Factors Engineering Program,1983, (Dept. of Defense)
(ii) DI-HFAC-80740, Human Engineering Program Plan,1989, (Dept. of Defense)
(iii)DOD-HDBK-763, Human Engineering Procedures Guide, Chapters 5-7 and Appendices A and B,1991,(Dept. of Defense)
(iv)EPRI NP-3659, Human Factors Guide for Nuclear Power Plant Control Room Development,1984, (Electric Power Research Institute)
(v) IEEE Std.1023-1988, IEEE Guide to the Application of Human Factors Engineering to Systems, Equipment and Facilities of Nuclear Power Generating l
Stations,1988, (IEEE)
(vi) MIL-H-46855B, Human Engineering Requirements for Military Systems, Equipment and Facilities,1979, (Dept. of Defense)
(vii)NUREG-0700, Guidelines for Control Room Design Reviews,1981, (U. S.
Nuclear Regulatory Commission) 5 REV.4 102392
1 i
TABLE 18.E.2.1 HUMAN FACIORS ENGINEEPJNG DESIGN TEAM AND PLANS (viii)NUREG-0737, Clarification of TMI Action Plan Requirements (Item I.C.5, g
" Feedback of Operating Experience to Plant Staff"),1983, (U. S. Nuclear w
Regulatory Commission) 3 (ix) NUREG-0899, Guidelines for the Preparation of Emergency Operating 45' Procedures,1982, (U. S. Nuclear Regulatory Commission)
$4 gs (x) NUREG/CR-3331, A Methodology for Allocating Nuclear Power Plant Control h7 Functions to Human and Automated Control,1983, (U. S. NRC)
,y YE (xi) TOP l-2-610, Test Operating Procedure - Part 1,1990, (Dept. of Defense)
{k w
p, fog A FAKTs cLtLa t Z.53uf, Note that withg the set of documents listed above, differences may exist regarding specific methods and criteria applicable to the HFE Program Plan. In situations that such m differences exist,pl of the methods and criteria presented within those document (are considered to be equally appropriate and valid and, therefore, any of de e ce !! :P r9031 documents may be selected as the basis for -!:=n: -fthe HFE Program.
A DDLLKSD IN nttr+003 Fox MDDLL33WG l
",*; 'Jl$n yswL sssat 42
- b. The H%m2P1m sh!! %ss:
(i) De ability of the operating personnel to accomplish assigned tasks.
(ii) Operator workload levels and vigilance.
(iii) Operating personnel " situation awareness."
(iv) The operators' information processing requirements.
(v) Operator memory requirements.
(vi) The potential for operator error.
A PPU L% T*
- c. HSI design and evaluation scope whichton:ict: cf $c conrol and moni:cring i=7
__.- -E=cfie plant opcrn:Ing pcr;canciin the Main Control Room (MCR) and Remote Shutdown System (RSS) The HSI scope shall address normal, abnormal and Cemergency plant operationslincludhg widem:ica cf plc.: cp stion: dring periods "
~
f sta plan; sy:t:-Jepr er HS! cqdptacnt is maisums u, me nw vi m
~
_SspW. The HSI scope shall also address the development of operating technical procedures for normal, abnormal and emergency plant operations and the identification of penannel traming needs applicable to the HSI design.
U AMO *rE3 r A HD MA tH TE *l A *J CE /*lTB K fAC ES THA T I!1PA of TME Q PER ATrods PEK3cNdfL.
i 6
REV.4 102192 1
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS
- d. De HFE Design Team as being responsible for.
(i) the development of HFE plans and procedures';
(ii) the oversight and review of HFE design. development, test, and evaluation activities; (iii)the initiation, recommendation, and provision of solutions thmugh designated channels for problems identified in the implementation of the HFE activities; (iv) verification of implementation of solutions to problems, (v) assurance that HFE activities comply to the HFE plans and procedures, and (vi) phasing of activities.
j
- e. He methods for identification, closure and documentation of human factors issues.
1
- f. The HSI design configuration control procedures.
2.
The HFE Pmgrarn Plan shall also establish:
I
- a. That each HFE issue / concern shall be entered on the HFE Issue Tracking System log when first identified, and each action taken to eliminate or reduce the issue / concern should be documented. The final resolution of the issue / concern, as accepted by the HFE DesignTeam, shall be documented along with information regarding HFE Design Team acceptance (e.g., person accepting, date, etc.) the individual responsibilities of the HFE Des:gn Team members when an HFE issue / concern is identified, including definition of who should log the item, who is responsible for tracking the resolution effons, who is responsible for acceptance of a resolution, and who shall enter the necessary closcout data, and
- b. That the HFE Issue Tracking System shall address human factors issues that are identified throughout the development and evaluations of the Main Control Room and Remote Shutdown System HSI Design implementation.
e HFE Pmgram Management Plan document shall include:
- a. He purpose and organization of the plan.
I
- b. The relationship between the HFE program and the overall plant equipment procurement and construction program (organization and phasing).
- c. Defmition of the HFE Design Team and their activities including:
~
_s MSCRT HEsa A f ricct s C.Ho l As f w E m o w M r m w T sJ.s a r b a
7 REV.4 102392
I
~
' aswr A l
l j
"c. That the MCR and RSS designs shall be implemented using HSI equipment technologies which are consistent win those defined 1
in Section 18.4.3 of the Standard SafetyAnalysis Report (SSAR).
Ie
- d. That in the event other HSI equipment technologies are alternatively selected for application in the MCR and RSS design implementations:
(i) a review of the industry experience with the operation of those a
selected new HSI equipment technologies shall be conducted; i
(ii) the Operating Experience Review (0ER) of those new HSI equipment technologies shallinclude both a review of literature pertaining to the human factors issues related to similar system applications of those new HSI equipment technologies and interviews with personnel experienced with the operation of those systems;and (iii) any relevant HFEissues/ concerns associated with those selected new HSI equipment technologies, identified through the conduct of the OER, shall be enteredinto the HFElssue Tracking System for closure."
O_
f TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS (i) Description of the HFE Design Team function within the bmader scope of the plant equipment procurement and construction program, including chans to show organizational and functional relationships, reporting relationships, and lines of communication; (ii) Description of the responsibility, authority and accountability of the HFE Design Team organization; (iii) Description of the process through which management decisions will be made reprding HFE; (iv) Description of the pmcess through which technical decisions will be made by the HFE Design Team (v) Description of the tools and techniques (e.g., review fonns, documentation) to be utilized by the HFE Design Team in fulfilling their responsibilities (vi) Description of the the HFE Design Team staffing, job descriptions of the individualHFE Design Team personnel and their personal qualifications, and; (vii) Definition of the procedures that will govern the intemal management of the HFE Design Team.
- d. Definition of the HFE Issue Tracking System and its implementation including:
(i) Individual HFE Design Team member responsibilities regarding HFE issue identification, logging, issue resolution, and issue closeout; (ii) Procedures and documentation requirements reganiing HFE issue identification.
Rese shall include description of the HFE issue,cffects of the issue if no design change action is taken and an assessment of the criticality and likelihood of the identified HFE issue manifesting itself into unacceptable HSI performance, and (iii) Procedures and documentation requirements regarding HFE issue resolution.
Rese procedures shall include evaluation and documentation of proposed solutions, implemented solutions, evaluated residual effects of the implemented solution and the evaluated criticality and likelihood of the implemented resolution of the HFE issue manifesting itself into unacceptable HSI performance.
Identification and description of the following implementation plans to be developed; e.
(i) System Functional Requirements Development, (ii) Allocation of Function, (iii) Task Analysis, l
8 REV.4 102392 i
I
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS (iv) Human-system Interface Design, (v) Plant and Emergency Operating Procedure Development, and '
(vi) Human Factors Verification and Validation.
- f. Definition of the phasing of HFE pmgram activities including:
(i) The plan for completion of HFE tasks which addresses the relationships between HFE elements and activities, the development of HFE reports and the conduct of HFE reviews, and (ii) Identification of other plant equipmer/. procurement and construction activities which are related to HFE Design Team activities but outside the scope of the team (e.g., C&I equipment manufacture)
- g. Definition of HFE documentation requirements and procedures for retention and retrieval, and
- h. Description of the manner in which HFE Program requirements will be communicated to applicable personnel and organizations, including those which may be subcontracted, who are responsible for the performance of work associated with the Main Contml Room and Remote Shutdown System design implementation.
III.
SYSTEM FUNCTIONAL REQUIREhENTS ANALYSIS IMPLEMENTATION PLAN 1.
(Satisfaction of the requirements presented herein shall result in the creation of a System Functional Requirements Analysis Implementation Plan which is in full compliance with the Item 2.a acceptance criteria presented in Table 3.6 of the Tier 1 Design Cemfication material for the GE ABWR design). The System Functional Requirements Analysis Implementation Plan shall establish:
- a. Methods and criteria for conducting the System Functional Requirements Analysis which are consistent with accepted HFE practices and principles. Within the cona:xt of l
system functional requirements analysis, accepted HFE methods and criteria r.re presented in the following documents:
(i) AD/A233 168, System Engineering Management Guide 1990, (Dept. of Defense -
Defense Systems Management College, Kockler, F., et al)
(ii) AR602-1, Human Factors Engineering Pmgram,1983, (Dept. of Defense)
(iii)EPRI NP-3659. Human Factors Guide for Nuclear Power Plant Control Room Development,1984, (Electric Power Research Institute)
(iv)IEC 964, Design for Control Rooms of Nuclear Power Plants,1989, (Bureau Central de la Commission Electrotechnique Intemationale) 9 REV.4 W2392 l
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS (v) TEFE Std. 1023-1988. TEFF Guide to the Application of Human Factors Engineering to Systems, Equipment and Facilities of Nuclear Power Generating Stations,1988, (IEEE)
(vi)M'L-H 46855B, Human Engineering Requirements for Military Systems, g
Equipmes and Facilities,1979, (Dept. of Defense) g (vii)NUREG-0700, Guidelines for Control Room Design Reviews,1981, (U. S.
(
Nuclear Regulatory Commission) t>'
(viii)NUREG/CR-3331, A Methodology for Allocating Nuclear Power Plant Control (d
Functions to Human and Automated Control,1983, (U. S. NRC)
{4 jeg A enerocaw s>suG,$
2g Note that within the set of documents listed above, diffe es may exist regarding the specific methods and criteria applicable to the conduct of sy m functional
- A$
requirements analysis. In situations that such differences exis I of the methods and a
criteria presented within thgocuments considered to be equally appropriate and 2
valid and, therefore, any of- __ m SL uments may be selected as the basis for the system functional requirements analysis.
wgicn 4vogos ru4r ru7icum s.uu t
- b. that system requirements shall define the system functions and those system functions shall provide the basis for determining the associated HSI performance requirements.
c that functions critical to safety shall be defined (i.e., those functions required to achieve safety system performance requirements; or those functions which, if failed, could pose a safety hazard to plant personnel or to the general public),
- d. that descriptions shall be developed for each of the identified functions and for the overall system configuration design itself. Each function shall be identified and described in terms ofinputs (observable parameters which willindicate systems status) functional processing (control process and performance measures required to achieve the function), functional operations (including detecting signals, measuring information, comparing one measurement with another, processing information, and acting upon decisions to produce a desired condition or result such as a system or component operation actuation or trip) outputs, feedback (how to determine correct discharge of function), and interface requirements so that subfunctions are related to larger functional elements.
2.
The System Functional Requirements Analysis Implementation Plan shall include:
- a. The methods foridentification of system level functions based upon system performance requirements. The functions shall be defined as the most general, yet differentiable means whereby the system requirements are met, discharged, or satisfied.
Functions shall be arranged in a logical sequence so that any specified operational usage of the system can be traced in an end-to-end path.
- b. 'Ihe methods for developing graphic function descriptions (e.g., Functional Flow Block Diagrams and Time Line Diagrams). The functions shall be described initially in graphic form. Function diagramming shall be done starting at a " top level", where major functions are described, and continuing to decompose major functions to lower levels until a specific critical end-item requirement emerges, e.g., s piece of equipment, software, or an operator.
10 REV.4 102392
1 TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS
- c. ne method for developing detailed function narrative desedptions which encompass:
(i) observable parameters that indicate system status, (ii) contml process and data required to achieve the function, and (iii) how to determine the manner in which pmper discharge of function is to be determined.
- d. Analysis methods which define the integration of closely related subfunctions so that they can be treated as a unit.
- c. Analysis methods which divide identified subfunctions into two groups according to whether:
(i) Cnmmon achievement of the subfunction is an essential condition for the accomplishment of a higher level function, or (ii)he subfunction is an alternative supporting functions to a higher level function or the subfunction's accomplishment is not necessadly a requisite for a higher level function.
f.
Requirements to identify for each integrated subfunction:
(i) The basis for why accomplishment of the subfunction is required, 1
(ii) ne control actions necessary for accomplishment of the subfunctions, (iii)The parameters necessary for the subfunction control actions, (iv) The criteria for evaluating the resu f the subfunction control actions, (v) The parameters necessary for evaluation of the subfunction, (vi) The criteria to be used to evaluate the subfunction, and (vii)The criteria for selecting altemative function assignments if the evaluation criteria is not satisfied.
IV.
ALLOCATION OF FUNCTION IMPLEMENTATION PLAN 1.
(Satisfaction of the requirements presented herein shall result in the creation of an Allocation of Function Implementation Plan which is in full compliance with the Item 3.a Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). He Allocation of Function Implementation Plan Shall establish:
- a. The methods and criteria for the execution of function allocation which are consistent with accepted HFE practices and principles. Within the context of function allocation, accepted HFE practices and principles are presented in the following documents:
11 REV.4 102392
j 1
j TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS (i) AD/A223 168, System Engineering Management Guide 1990, (Dept. of Defense -
Defense Systems Management College, Kockler, F., et al) y (ii) AR 602-1, Human Factors Engineering Program,1983, (Dept of Defense)
)
(iii)EPRI NP-3659, Human Factors Guide for Nuclear Power Plant. Control Room v
Development,1984, (Electric Power Research Institute)
'/
{
(iv)IEC 964, Design for Control Rooms of Nuclear Power Plants,1989, (Bureau R
Central de la Commission Electrotechnique Intemationale)
[
(v) NUREG-0700, Guidelines for Control Room Design Reviews,1981, (U. S.
V Nuclear Regulatory Commission) d-(vi)NUREG/CR-3331, A Methodology for Allocating Nuclear Power Plant Control T
Functions to Human and Automated Control,1983, (U. S. NRC)
Nb
$w
,for A PAxmusn snug ygoj qR Note that within the set of documents listed abo e, differences may exist regarding the !.i l s
12 specific methods and criteria applicable to the co et and analysis of function u
d4pp allocation. In situations that such differences exist, all of the methods and criteria l
[-
presented witnm mash _gmentskare considered to be equally appropriat y
accaicig the function allocation and analysis.
- b. That aspects of system and functions defmition shall be analyzed in terms of resulting human performance requirements based on the expected user population.
- c. That the allocation of functions to personnel, system elements, and personnel system combinations shall reflect :
Q ggry or gyr<na.sn6475.snao unrrnr>w (i) sensitivity, precision, time, and safety requirements, (ii) reliability of system performance, and.
(iii)the number and the necessary skills of the personnel required to operate and maintain the system.
- d. That the allocation criteria, rationale, analyses, and procedures shall be documented.
Analyses shall confum that the personnel can perform tasks allocated c.
to thern while maintaining operator situation awareness, acceptable personnel workload, and pawel vigilance.
2.
The Allocation of Function Implementation Plan shall include
- a. Establishment of a stmetwed basis and criteria for function allocation.
- b. Definition of function allocation analyses requirements including:
12 REV.4 1o2392
)
e TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS (i) Definition of the objectives and requirements for the evaluation of function allocations (ii) Development of altemative function allocations for use in the conduct of comparative evaluations (iii) Development of criteria to be used as the basis for selecting between alternative function allocations (iv) Development of evaluation criteria weighting factors (v) Development of test and analysis methods for evaluating function allocation altematives (vi) Definition of the methods to be used in conducting assessments of the sensitivity of the comparative function allocation altematives analyses results to the individual anrdysis inputs and criteria (vii) Definition of the methods to be employed in selecting individual function allocation for incorporation into the implemented design.
V.
TASK ANALYSIS IMPLEMENTATION PLAN 1.
(Satisfaction of the requirements presented herein shall result in the creation of a Task Analysis Implementation Plan which is in full compliance with the Item 4.a Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). The Task Analysis Implementation Plan shall establish:
- a. The methods and criteria for conduct of the task analyses which are consistent with accepted HFE practices and principles. Within the context of performing task analysis, accepted HFE methods and criteria are presented in the followmg documents:
(i) AD/A223168, System Engineering Management Guide 1990, (Dept. of Defense -
Defense Systems Management College, Kockler, F., et al)
(ii) DOD-HDBK-763, Human Engineering Procedures Guide, Chapters 5-7 and Appendices A and B,1991, (Dept. of Defense)
(iii)EPRI NP-3659, Human Factors Guide for Nuclear Power Plant Control Room Development,1984, (Electric Power Research Institute)
(iv)IEC 964, Design for Control Rooms of Nuclear Power Plants,1989, (Bureau Central de la Commission Electrotechnique Internationale)
(v) IEEE Std.1023-1988,IEEE Guide to the Application of Human Factors Engineering to Systems, Equipment and Facilities of Nuclear Power Generating Stations,1988,(IEEE)
(vi) MIL-H-46855B, Human Engineering Requirements for Military Systems, Equipment and Facilities,1979, (Dept. of Defense)
(vii) MIL-STD-1478, Task Performance Analysis,1991, (Dept. of Defense) 13 REV.4 1o2192
x t
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS g
v (viii)NUREG-0700, Guidelines for Control Room Design Reviews,1981, (U. S.
[
g Nuclear Regulatory Commission)
{
b y
(ix)NUREG/CR-3331, A Methodology for Allocating Nuclear Power Plant Control 4
ky g
a3 Functions to Human and Automated Control,1983,(U. S. NRC)
(x) NUREG/CR-3371. Task Analysis of Nuclear Power Plant Contiul Room Crews
}w x
e {3
{
(Vol.1),1983, (U. S. NRC) g g, m et,.A u_w e,
- Q
,v o
((
Note that within the set of docume ts listed above, differences may exist regarding the 12 specific mehods and criteria applic ble to the conduct of HFE task analysis. In 7
[3s situations that such differences exis all of the methods and criteria presented within those documentMare considered to be equally appropriate and valid and, therefore, any 4 2 ofah: :ia Ed documents may be selected as the basis for the task analysis.
J y
uose
- b. The scope of the task analysis which shallinclude operations performed at the operator interface in the Main Control Room and at the Remote Shutdown System. The analyses shall be directed to the full range of plant operating modes, including startup, normal operations, abnormal operations, transient conditions, low power and shutdown conditions. The analyses shall also address operator interface operations during periods of maintenan st and inspection of plant systems and equipment and- /dct.w o*G d the HSI equipment.
- c. That the analysis shall link the identified and described tasks in operational sequence diagrams The task descriptions and operational sequence diagrams shall be used to identify which tasks are entical to safety in terms of imporemce for function achievement, potential for human error, and impact of task failure. Human actions which are identified through PRA sensitivity analyses to have significant impact on safety shall also be considered " critical" tasks. Unen carr'ed' Fu d cf'M J A f f A W7M N #>
"' 'N'E!!AANO NNr".YZfo'?le'*il? NY%!$!?cloY$5?a 'A!vY$515?* *!
i
- d. Yas[c analysis shall develop narrative descriptions of the personnel activities req ^
W A WP occurring in temporal proximity, which utilize a common set of displays for successful completion of the task. A task shall be a group of activities, often Task analyses shall define the input, process, and output required by and of personnel.
- e. The task analysis shall identify requirements for alarms, displays, data processing, and ;
controls.
- f. The task analysis results shall be made available as input to the personnel training programs.
2.
The Task Analysis Implementation Plan shallinclude:
- a. The methods and data sources to be used in the conduct of the task analysis
- b. The methods for conducting the initial (high level) task analysis including:
(i) converting functions to tasks, (ii) developing narrative task descriptions, (iii) developing the basic statement of the task functions, 14 REV.4 1a2392
l j
TABLE 18.E.2.1 HUMAN FACTORS ENOINEERING DESIGN TEAM AND PLANS (iv) decomposition of tasks to individual activities, and (v) development of operational sequence diagrams
- c. The methods for developing detailed task descriptions that address;
~
(i) information requirements (i.e., information required to execute a task, including cues for task initiation),
i (ii) decision-making requirements (i.e., d:cisions that are probable based on the '
l evaluations, description of the decisions to be made and the evaluations to be i
performed),
(iii) response requirements (i.e., actions to be taken, frequency of action, speed / time line requirements, any tolemnce/ accuracy requirements associated with the action, consideration of any operational limits of personnel performance or of equipment i
body movements required by an action taken, and any overlap of task requnements
~
such as serial vs. parallel task elements),
(iv) feedback requirements (i.e., feedback required to indicate adequacy of actions taken),
(v) personnel workload (i.e., both cognitive and physical workload and the estimation of the level of difficulty associated with a particular workload condition),
(vi) any associated task support requirements (i.e., special/ protective clothing, job aids or reference materials required. any tools and equipment required or any computer processing support aids),
(vii)workplace factors (i.e., the workspace envelope required by the ae on taken, d
workspace environmental conditions, location that the work is to be performed, the physical / mental attributes of the work),
l (viii)staffmg and communication requirements (i.e., the number of personnel, their technical specialty, and specific skills, the form and content of communications and other personnel interaction required when more than one person is involved),
and (ix) the identification of any hazards involved in execution of the task.
- d. 'Ihe methods for identification of critical tasks. The identified critical tasks shall i
includs, at the minimum, those operator actions which have significant impact on the PRA results as presented in Section 19D.7 of the SSAR.
- e. The methods for establishing information and control requirements.
- f. The methods for conducting alarm, display, processing, and control requirements analysis.
- g. The methods through which the application of task analysis results are assembled and documented to provide input to the development of personnel training programs J
15 REV.4 m2392
l TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS
- h. the methods to be used to evaluate the results of the task analysis.
t VI.
HSI DESIGN IMPLEMENTATION PLAN 1.
(Satisfaction of the requirements presented herein shall result in the creation of an HSI Design Implementation Plan which is in full compliance with the Item 5.a Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). The HSI Design Implementation Plan shall establish:
- a. The methods and criteda for HSI equipment design and evaluation of HSI human performance, equipment design and associated work place factors; which are consistent with accepted HFE practices and principles. Within the context of performmg these HSI design evaluations, accepted HFE methods and criteria are presented in the following documents:
(i) AD/A223 168, System Engineering Management Guide 1990, (Dept. of Defense -
Defense Systems Management College, Kockler, F., et al) l (ii) ANSI HFS-100, American National Standard for Human Factors Engineering of Visual Display Terminal Workstations,1988, (Am. Nat'l. Standards Institute)
(iii)EPRI NP-3659. Human Factor Guide for Nuclear Power Plant Control Room Development,1984, (Electric Power Research Institute)
(iv)EPRI NP-3701, Computer-Generated Display System Guidelines,1984, (Electric Power Research Institute)
(v) ESD-TR-86-278, Guidelines for Designing User Interface Software,1990, (Department of Defense)
(vi)IEC 964, Design for Control Rooms of Nuclear Power Plants,1989. (Bureau Central de la Commission Electrotechnique Intemationale)
(vii) MIL-H-46855B, Human Engineering Requirements for Military Systems, Equipment and Facilities,1979, (Dept. of Defense)
(viii) MIL-HDBK-759A, Human Factors Engineering Design for Army Material,1981, (Dept. of Defense)
(ix)DOD-HDBK-761 A, Human Engineering Guidelines for Management Information Symems,1990, (Dept. of Defense)
(x) MIL-STD-1472D, Human Engineering Design Criteria for Military Systems, Equipment and Facilities,1989, (Dept. of Defense) i (xi)FJke. 3-0696, Functional Criteria for Emergency Response Facilities,1980,
, R S. 4uclear Regulatory Commission) 16 REV.4 132M2 4
Gilmore, et. al. (1989). User-computer interface in process control: A humanfactors en p
- handboo an Diego,CA
- Academic Press,Inc. J '
TABl_E 18.E.2.1 HUMAN FACIORS ENGINEERING DESIGN TEAM AND PLANS (xii)NUREG-0700, Guidelines for Control Room Design Reviews,1981, (U. S.
Nuclear Regulatory Commission)
(xiii)NUREG-0800, Standart! Review Plan, Rev.1,1984, (U. S. Nuclear Regulatory Commission)
(xiv)NUREG-0899, Guidelines for the Preparation of Emergency Operating Procedures,1982, (U. S. Nuclear Regulatory Commission)
(xv)NUREG/CR-5228, Techniques for Preparing Flowchart Format Emergency 3
Operating Procedures (Vols. 1 & 2),1989, (U. S. NRC) 4 (xvi)NUREG/CR-4227,. Human Ergineering Guidelines for the Evaluation and g '5 Assessment of Video Display Er.its,1985, (U. S. Nuclear Regulatory t-3 Commission)
,gn. g rn n eu m asue, vc iM Note that within the set of dw listed above, differences may exist regarding the 2k specific methods and criteria appli le to the conduct of HSI design evaluations. In situatio h differences exi of the methods and criteria presented within thosegpn are considered to be equally appropriate and valid and, therefore, any ofE a Sd documents may be selected as the basis the HSI design evaluations.
PE F ed'a c ***' r m m = "
is.se os accawrc ~
- b. Dat the HSI design shallimplement the information and control requirements developed through the task analyses, including the displays, controls and alarms necessary for the execution of those tasks identified in the task analyses as being critical tasks.
- c. He methods for comparing the consistency of the HSI human performance equipment, design and associated workplace factors with that modeled and evaluated in the cornpleted t.uk analysis,
- d. nat the HSI design shall not incorporate equipment (i.e., hardware or softwam function) which has not been specifically evaluated in the task analysis.
- e. The HSI design criteria and guidance for control room operations during periods of maintenance, test and inspection of control room HSI equipment and of other plant equipment which has control room personnel interface.
- f. The test and evaluation methods for resolving HFE/HSI design issues. These test and evaluation methods shall include the criteria to be ured in selecting HFE/HSI design and evaluation tools which:
(i) may incorporate the use of static mockups and models for evaluating access and workspace related HFE issues, and (ii) shall require dynamic simulations and HSI prototypes for conducting evaluations of the human performance associated with the advities in the critical tasks identified in the task analysis.
17 REV. 4 102392 A
e a
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS 2.
The Human System Interface Design Implementation Plan shallinclude:
i
- a. Identification of the specific HFE standards and guidelines documents which substantiate that the selected HSI Design Evaluation Methods and Criteria are based upon accepted HFE practices and principles.
- b. Definition of standardized HFE design conventions.
- c. Definition that the standard design features, presented in Section 18.4.2 of the Standard Safety Analysis Repon (SSAR); the Standard HSI equipment technologies, presented in Section 18.4.3 of the SSAR: and the displays, controls and alarms presented in Tables 18F-1,18F-2 and 18F-3 of the SSAR Appendix 18F, shall be incorporated as requirements on the HSI design,
- d. Definition of the design / evaluation tools (e.g., pmtotypes) which are to be used in the conduct of the HSI design analyses, the specific scope of evaluations for which those tools are to be applied and the mtionale for the selection of those specific tools and their associated scope of application.
VII.
PLANT AND EhERGENCY OPERATING PROCEDURE DEVEIDPhENT IMPLEhENTATION PLAN 1.
(Satisfaction of the requirements presented herein shall result in the creation of a Plant and Emergency Operating Procedure Development Implementation Plan which is in full compliance with the item 6.a Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). The Plant and Emergency Operating Procedure Development Implementation Plan shall establish :
a.
Methods and criteria for development of the operating technical procedures which are consistent with accepted HFE practices and principles. Within the context of operating procedure development, accepted HFE methods and criteria are presented in the following documents:
(i) ANSI-N18.7-1976, Admmistrative Controls and Quality Assurance for the Operation Phase of Nuclear Power Plants,1976, (Am. Nat'l. Stds. Instit.)
(ii) EPRI NP-3659, Human Factors Guide for Nuclear Power Plant Control Room Development,1984, Electric Power Research Institute (iii)IEC 964, Design for Control Rooms of Nuclear Power Plants,1989, (Bureau Central de la Commission Electrotechnique Intemationale)
(iv) MIL H-46855B, Human Engineering Requirements for Military Systems, Equipment and Facilities,1979,(Dept. of Defense) i (v) NUREG-0899, Guidelines for the Preparation of Emergency Operating Procedures, 1982, (U. S. Nuclear Regulatory Commission)
(t9sD uo Nuns -1559 Sur!'EM I D990 (vi)NUREG-1358/ Lessons Leamed from the Special Inspection Program for Emergency Operating Procedures, #)S9; (U. S. Nucl. Regul. Commission) 18 REV.4 102392
x
.sER7 Nfd Riff / TAME.S (i2),(%d 4" Od.) A5 Qwaano w nrwo Iaurr B.
~
s s
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS 9
b (vii)NUREG/CR-5228, Techniques for Preh89, (U. S. NRC)aring Flowchart Form g
y Operating Procedures (Vols.1 & 2), l h&
t 3 a3 (viii)MII M - 63035 (TM), Military Specifications Manuals, Technical: Front End
)3
{[3 1{7 Analysis,1977, (Dept. of Defense) pg 3 ggncuus s.ssus, o
s s =E Note that within the set of documents listed abov differences may e'xist regarding the v y o g4 specific methods and criteria applicable to the deve pment of operating technical 1 gE procedures. In _ situations that such differences exis all of the methods and criteria fUf A
' presented within those g!Ep= lL;d documents may be selected as the basis forntga ocur I
and, therefore, any of4 operating technical procedure develogmen(
}
~. -~n 4
,,,7 aaw.
ra-
- b. That thepprocedmes to be ve[oped shall address normar, abnormal, and emergency
(
plant operations including consideration of plant operations during pedods when plant systems / equipment and 9Toperator interface (i.e., main control room) equipment 7
is undergomg test, mamtenance or mspection. -Thc scepc of ic plant ope a'i=
technical-proceduresievelupumuila liudtcd4oihesc ymcdureneq&d for f=11mh gdanitial-plara egs6n. -
l
- c. That operator actions identified in the task analysis shall be used as the basis for-specifying the procedures for operanons.
- d. That a Writer's Guide shall be developed which establishes the process for developing the technical procedures for normal plant and system operation, abnormal plant operations, emergency plant operations and for responding to plant alarm conditions.
The Wdter's Guide shall contain objective cdteria which will require that the operations l
technical procedures developed are consistent in organization, style, content and usage i
of terms.
2.
The Plant and Emergency Operating Procedure Development Implementation Plan shall I
include:
- a. Identification of the task analyses' definition of required human actions as the data source to be used as the basis for procedure development,
- b. Requirements for the development and use of a Technical Procedure Writer's Guide,
- c. Definition of the methods through which specific operator skills and traming needs, as may be considered necessary for reliable execution of the procedures, will be identified and 6mnted as part of the technical procedures development activities, and
- d. Requirement that the documented technical procedures developed shallinclude:
(i) Title of the procedure (ii) Statement of the procedure's goal and applicability i
(iii) Identification of reference matedal necessary to support execution of the procedure i
i 19 REV.4 m2392
r w nsen 1
-I f
ANSI HFS-100 American Nadonal Standard for Human Factors Engineenng of (iD Visual Display Temunal Wodtstations,1988, (Am. Nat'l. Standards Institute)
MIL-STD-1472D, Human Engineering Design Criteria for Military Systems, g
Equipment and Facilities,1989, (Dept. of Defense) 1/)-
Gilmore, et. al. (1989). User-com,:aer interface in process control A humanfactors engineering
,i handbook. San Diego,CA: Academic Press,Inc.
s 1
4 TABLE 18.E.2.1 HUMAN FACIDRS ENGINEERING DESIGN TEAM AND PLANS (iv) Identification of prerequisite conditions which must be satisfied prior to execution of the procedure (v) Identification of precautions ( i.e., warnings, cautions, and notes) that must be considemd in the execution of the procedure (vi) Identification of operational limits (vii) Definition of the specific human actions steps required, and (viii) Identification of the specific criteria that the operator may use tojudge that the goals of the procedure have been achieved VIII. HUMAN FACTORS VERIFICATION AND VALIDATION IMPLEMENTATION PLAN 1.
(Satisfaction of the requirements presented herein shall result in the creation of a Human Factors Verification and Validation Implementation Plan which is in full compliance with the Item 7.a Acceptance Criteda presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). The Human Factors Verification and Validation (V&V) Implementation Plan shall establish:
- a. Human factors V&V methods and criteria which are consistent with accepted HFE practices and principles. Within the context of performing human factors V&V, accepted HFE methods and criteria are presented in the following documents:
(i) AD/A223 168, System Engineering Management Guide 1990, (Dept. of Defense -
Defense Systems Management College, Kockler, F., et al)
(ii) DOD-HDBK-763, Human Engineering Procedures Guide, Chapters 5-7 and Appendices A and B,1991, (Dept. of Defense)
(iii)DODI 5000.2, Defense Acquisition Management Policies and Procedures,1991, (Dept. of Defense)
(iv)EPRI NP-3701, Computer-Generated Display System Guidelines,1984, (Electric Power Research Institute)
(v) IEC 964, Design for Control Rooms of Nuclear Power Plants,1989, (Bureau Central de la Commission Electrotechnique Intemationale)
(vi)IEEE Std. 845-1988, IEEE Guide to Evaluation of Man-Machine Perfonnance in Nuclear Power Generating Station Control Rooms and Other Peripheries,1988 (IEEE)
(vii) MIL-H-46855B, Human Engincedng Requirements for Military Systems, Equipment and Facilities,1979,(Dept. of Defense)
(viii)DOD-HDBK-761 A, Human Engineering Guidelines for Management Information Systems,1990, (Dept. of Defense)
(ix)NUREG-0700, Guidelines for Control Room Design Reviews,1981, (U. S.
Nuclear Regulatory Commission) 20 REV.4 102392
i TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS i
(x) NUREG-0899, Guidelines for the Preparation of Emergency Operating Procedures, 1982, (U. S. Nuclear Regulatory Commission)
(xi) TOP 1-2-610, Test Operating Procedure - Part 1,1990, (Dept. of Defense)
]
x
}
t (xii)NSAC-39, Verification and Validation for Safety Parameter Display Systems, k
y3 1981, (Electric Power Research Institute) xy
.{
c w:
?, u (xiii)NUREG/CR-4227, Human Engineering Guidelines for the Evaluation and I${
Q$
Assessment of Video Display Units,1985, (U. S. Nuclear Regulatory 20
[
Commission)
- , ret a r e nc m 4R i554 f,
$;E 7u r.
Ew Note that within the set of documents liked above, differences may exist rega-ding
$ n e, i
s %
31 the specific methods and criteria applicable to the conduct of human factors V&V.
iEN l~
'~In situations that such differences exist /all of the methods and criteria presented Z;&
withTn~those document $ pre considered to be equally appropriate and valid and, gyg therefore, any offhe sca limd documents may be selected as the basis for human t
i factors V & V.
nc5E U
- b. That the scope of the evaluations of the integrated HSI shallinclude:
)
I (i) The Human-System Interface (including both the interface of the operator with the HSI equipment hardware and the interface of the operator with the HSI equipment's software driven functions) i (ii) The plant and emergency operating technical procedures, and i
(iii) HSI work environment.
3 i
- c. That static and/or "part-task" mode evaluations of the HSI equipment shall be 1
conducted to confirm that the controls, displays, and data processing functions identified in the task analyses are previdedF DES /GNED ffR dCef FrfD Hff G4'Ofg,a j
As'D FE wc IPLE.5.
)
- d. (The integration of HSI equipment with each other, with the operating personnel and l
l with the Plant and Emergency Operating Technical Procedures shall be evaluated g
! through the conduct of dynamic task performance testing. The dynamic task 1
/ performance testing and evaluations shall be performed over the full scope of the y mtegrated HSI design using dynamic HSI prototypes (i.e., prototypical HSI equipment which is dynamically driven by real time plant simulation computer models), other 1 -
evaluation tools and/or past dynamic task performance test and evaluation results. The methods for defining the scope and application of the dynamic HSI prototype, past test e/
results and other evaluation tools shall be documented in the implementation plan. The, iQtask performance tests and evaluations shall have as their objectives:f f
(i) Confumation that the identified critical functions can be achieved using integrated pgg C HSI design, Fror NNT (ii) Confumation that the HSI design and configuration can be operated using the Fy,c To established Main Control Room staffing levels, MfLAC! #b y E y 7 IH 113 a
g M7/ff 7Y.
21 REV.4 1G2392
A/3ELT f
g; =. C::
/w u
The integration of HSI equipment with each other, with the operating personnel and with the plant and emergency operating technical procedures shall be evaluated through the conduct of. dynamic task performance testing. The dynamic task performance testing and evaluations shall be performed over the full scope of the integrated HSI design using dynamic HSI prototypes (i.e., prototypical HSI equipment which is dynamically driven by real time plant simulation computer models). In the event that the particular HSt design implementation under consideration is referenced to a previous HSI design for which dynamic task performance test and evaluation results are available, those existing results, along with the results of limited scopo dynamic task performance tests which' l
address the areas of difference between the two subject HSI designs, may be used to l
satisfy this requirement. The methods for defining the scope and application of the dynamic HSI prototype, past test results and other evaluation tools shall be documented in the implementation plan. The dynamic task performance tests and evaluations shall have as their objectives:
e i
1 h
l 2.1 a.
4 v
- (v) Cearrauarios rnr rm suecarios er rn.scort As DE!!"eo tw ef ru scrions ASE Zu!focresr To
,Agricse301al.b cF TM YABA gau rn.sx secourcosme ir (yi) ca. pau,arros rear for serecaerso N 53 96'""
l 8. f.2, I, unneucosar** 12 coupsre.or woro accerrso MFE rpacroccs >Jo !***r"2.
TABLE 18.E.2.I HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLAN}
i (iii) Confirmation that the flant and gmergency dperating fechnical /meeduresiprovide.
dimetion for completing the identified tasks associated with normal, abnormal and emergency operations, and (iv) Confirrnation that the time dependentpspects of the HSI equipment performance L.,
,.,,,,ur,,,e G.p. msrt4y fewr seue"*".)
allow for task accomplishment.
4 i
- e. That dynamic task performance test evaluations shall be conducted over the range of l
operational conditions and upsets, including:
(i) Normal plant operations, such as plant startup, shutdown, full power operations, and plant maintenance activities, (ii) Plant system and equipment failures,Cuccaows
'"8f"'"'*"**' """
(iii)HSI equipment failures, j
(iv) Plant transients, and (v) Postulated plant accidents condinons.
- f. The HFE performance measures to be used as the basis for evaluating the dynamic task
- performance test results. These performance measures shallinclude:
l (i) Operating crew primary task performance characteristics, such as task times and i
procedure compliance, (ii) operating crew errors and ermr rates, (iii) operating crew situation awareness, (iv) operating crew workload, (v) operating crew communications and coordination, (vi)anthropometry evaluations, and (vii)HSI equipment performance measures, i
- g. The teethods to confMn that HFE issues identified and d cumented in the Human j
Factoss Issue Tracking System have been resolved in the integrated HSI design.
- h. 'Ihe methods and criteria to be used to confirm that critical human actions, as defined by the task analysis, have been addressed in the integrated HSI design.
i
- i. The methods and criteria to be used to evaluate the adequacy of the operating technical i
procedures.
2.
The Human Factors Verification and Validation Implementation Plan shall include.
- a. Definition of Test Objectives I
22 REV.4 102392
c i
TABLE 18.E.2.1 HUMAN FACTORS ENGINEERING DESIGN TEAM AND PLANS 3
- b. Definition of Test methods and procedures.
- c. Identification of the participants in the dynamic task perfonnance testing, which shall include licensed operators as test subjects.
- d. Definition of dynamic task performance test conditions which shall. include:
(i) plant startup operations, (ii) plant power operations, (iii) plant shutdown operations, (iv) plant refueling and maintenance operations.
(v) individual plant system and equipment failures,( ra u_uo,ss issuuus.irmes Fnos uM)h (vi) individual HSI equipment failure (e.g., loss of VDU functions),
(vii) design basis transients (e.g., turbine trip, loss of feedwater),
(viii) design basis accidents (e.g., LOCAs),
(ix) execution of symptom based emergency procedures, and 4
(x) execution of task scenarios which contain critical tasks as identified in the task
[
analyses.
- e. Methods for defining scope and configuration of the prototypical HSI requued to suppon testmg
- f. Methods for defining criteria and perfonnance measures to be used in evaluating test results.
- g. Method for conducting analysis of test data.
- h. Requirement that the HSI design shall be reviewed and confirmed:
(i) to have incorporated the inventory of controls, displays and alarms presented in Tables 18F.1,2 and 3 of the ABWR Standard Safety Analysis Report (SSAR),
and (ii) that the implemented design is consistent with the standard design features and technologies as presented in Sections 18.4.2 and 18.4.3, respectively, of the 1
SSAR.
i t
- i. Requirements for the development of documented test & evaluation plans and procedures.
- j. Requirements for documenting test results.
23 REV. 4 102192
TABLE 1SE.2.2 HFE ANALYSIS I.
SYSTEMFUNCTIONALREQUIREMENTS ANALYSES 1.
(Satisfaction of the requirements presented herein shall result in the conduct of system functional requirements analyses which are in full compliance with the Item 2.b Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). The system functional requirements analyses shall be conducted in accordance with the rec uirements of the Human Factors Engineering Program Plan and the System Functional hquirements Analysis Implementation Plan.
2.
The results of the system functional requirements analyses shall be documented in a repon that includes the following:
Objectives of the system functional requirements analyses.
a.
- b. Description of the methods employed in Ice conduct of system functional requirements analyses.
- c. Identification of deviations from the System Functional Requirements Analysis Implementation Plan,
- d. Presentation and discussion of the results of the system functional requirements analysis including discussion of design change recommendations derived from these analyses and/or negative implications that the current design may have on safe plant operations.
- e. Conclusions regarding the conduct of the analyses and the analysis results.
3.
The results of the HFE Design Team's evaluation of the conduct and results of the system functional requaements analyses shall be documented in a repon that includes the following:
- a. The methods and procedures used by the HFE Design Team in their review of the system functional requirements analyses.
b. The HFE Design Team's evaluation of the completed system functional requirements analyses including evaluation of the compliance with the System Functional Require-ments Analysis Implementation Plan and the HFE Program Plan.
- c. Presentation and discussion of the HFE Design Team's Review findings.
I II.
FUNCITON ALLOCATION ANALYSES 1.
(Satisfaction of the requirements presented herein shall result in the conduct of function allocation analyses which are in full compliance with the Item 3.b Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). The function allocation analyses shall be conducted in accordance with the regturements of the Human Factors Engineering Program Plan and the Allocation of Functions Implementation Plan.
24 REV.4 102392
~.
i TABLE 18.E.2.2 HFE ANALYSIS 2.
The results of the function allocation analysis shall be docuraented in a report that includes the following:
- a. Objectives of the function allocation analyses.
.j
- b. Description of the methods employed in the conduct of the function allocation analyses.
- c. Idennfication of deviations from the Allocation of Function Implementation Plan.
- d. Presentation and discussion of the results of the function allocation analyses including discussion of design change recommendations derived from these analyses and/or negative implications that the current design may have on safe plant operations.
4
- e. Conclusions regarding the conduct of the analyses and analysis results.
i 3.
The results of the HFE Design Team's evaluation of the conduct and results of the function l
allocation analyses shall be documented in a report that includes the following:
- a. The methods and procedures used by the HFE Design Team in their review of the function allocation analyses.
- b. The HFE Design Team's evaluation of the completed function allocation analyses including an evaluation of the compliance with the Allocation of Function Implementation Plan and the HFE Program Plan,
- c. Presentation and discussion of the HFE Design Team's review findings.
III.
TASK ANALYSES l
l 1.
(Satisfaction of the requirements presented herein shall result in the conduct of task analyses which are in full compliance with the Item 4.b Acceptance Criteria presented m i
Table 3.6 of the Tier I Design Certification material for the GE ABWR Design). The task analyses shall be conducted in accordance with the requirements of the Human Factors Engmeering Program Plan and the Task Analysis Implementation Plan.
i 2.
The results of the task analyses shall be documented in a report that includes the following:
i 4
- a. Objectives of the task analyses.
- b. Descripdon of the methods employed in the conduct of the task analyses.
i
- c. Identi6 cation of deviations from the Task Analyses Implementation Plan.
- d. Presentation and discussion of the results of the task analyses, including discussion of design change recommendations derived from these analyses and/or negative implications that the current design may have on safe plant operations, and d
- e. Conclusions regarding the conduct of the analyses and the analyses results.
4 e
25 REV.4 102192
TABLE 18.E.2.2 HFE ANALYSIS -
3.
'Ihe results of the HFE Design Team's evaluation of the conduct and results of the task analyses shall be documented in a report that includes the following:
- a. The methods and pmcedures used by the HFE Design Team in their review of the completed task analyses.
- b. The HFE Design Team's evaluation of the completed task analyses including an evaluation of the compliance with the Task Analysis Implementation Plan and the HFE Program Plan.
- c. Presentation and discussion of the HFE Design Team's review findings.
I i
t t
5 b
l 26 REV.4 102192
TABLE 18.2.3 HUMAN SYSTEM INTERFACE DESIGN AND PROCEDURES DEVELOPhENT I.
HSI DESIGN ANALYSES 1.
(Satisfaction of the requirements presented herein shall result in the conduct of HSI design analyses which are in full compliance with the Item 5.b Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR. design). The Human System Interface (HSI) design implementation and analyses shall be conducted in accordance with the requirements of the Human Factors Engineering Program Plan and the HS1 Design Implementation Plan.
2.
The results of the human system interface (HSI) design analyses shall be documented in a repon thatincludes the following:
- a. Objectives of the HSI design analyses,
- b. Description of the methods employed in the conduct of the HSI design analyses,
- c. Identification of deviations from the HSI Design Implementation Plan,
- d. Presentation and discussion of the results of the HSI design analyses, including discussion of design change recommendations derived from these analyses and/or negative implications that the current design may have on safe plant operations, and
- e. Conclusions regarding the conduct of the analyses and the analysis results.
3 The results of the HFE Design Team's evaluation of the conduct and results of the HSI design analyses shall be documented in a report that includes the following:
- a. The methods and procedures used by the HFE Design Team in their review of the HSI design analyses,
- b. The HFE Design Team's evaluation of the completed HSI design analyses, including an evaluation of the compliance with the HSI Design Implementation Plan and HFE Pmgram Plan, and
- c. Presentation and discussion of the HFE Design Team's review findings.
II.
PLANT AND EMERGENCY OPERATING PROCEDURE DEVELOPMENT I
1.
(Satisfaction of the requirements presented herein shall result in the development of plant operations technical procedures which are in full compliance with the Item 6.b Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Cenification material for the GE ABWR design). The development of the plant operations technical procedures shall be conducted in accordance with the requirements of the Human Factors Engineering Pmgram Plan and the Plant and Emergency Operating Procedure Development Implementation Plan.
2.
The results of the technical procedure development activities shall be documented in a repon that includes the following:
- a. Objectives of the technical procedure development.
- b. Description of the methods employed in the development of the technical procedures.
27 REV.4 1023S2 i
.--------- ----- ----- --J
5 j
4 TABLE 18.2.3 HUMAN SYSTEM INTERFACE DESIGN AhT PROCEDURES DEVELOPhENT
- c. Identification of any deviations from the Plant and Emergency Openting Procedure Development Implementation Plan.
- d. Presentation and discussion of the results, including a list of the procedures developed, discussion of a representative sample of procedures, and a discussion of design change recommendations derived during the course of technical procedure development and/or negative implications that the current design may have on safe plant operations.
- c. Conclusions regardmg the conduct of the procedures development and regarding the resultant procedures.
3.
The results of the HFE Design Team's evaluation of the conduct and results of the technical procedures development shall be documented in a report that includes the following:
- a. The methods and procedures used by the HFE Design Team in their review of the operating technical procedures development.
- b. 'Ihe HFE Design Team's evaluation of the completed technical procedures development, including an evaluation of the compliance with the Plant and Emergency Operating Procedure Development Implementation Plan and HFE Program Plan.
- c. Presentation and discussion of the HFE Design Team's review findings.
I i
i 28 REV.4 102392
TABLE 18.E.2.4 HUMAN FACTORS VERIFICATION AND VALIDATION I.
HUMAN FACTORS VERIFICATION AND VALIDATION 1.
(Satisfaction of the requirements presented herein shall result in the conduct of human factors verification and validation activities which are in full compliance with the Item 7.b Acceptance Criteria presented in Table 3.6 of the Tier 1 Design Certification material for the GE ABWR design). The human factors verification and validation (V&V) of the human system interface (HSI) design shall be conducted in accordance with the requirements of the Human Factors Engineering Program Plan and the Human Factors V&V Implementation Plan 2.
The results of the human factor verification and validation (V&V) activities shall be documented in a report that includes the following:
~
- a. Objectives of the human factors V&V.
t
- b. Description of the methods employed in the conduct of the human factors V&V.
- c. Identification of deviations from the Human Factors V&V Implementation Plan.
- d. Presentation and discussion of the human factors V&V results, including discussion of design change recommendations derived from the human factors V&V tests and evaluations and/or significant negative implications that the current HSI design may have on safe plant operations which may have been identified.
t
- c. Conclusions regarding the conduct of the human factors V&V and the results.
3.
The results of the HFE Design Team's evaluation of the conduct and results of the human factor verification and validation (V&V) shall be documented in a report that includes the following:
i
- a. The review methodology and procedures used by the HFE Design Team in their review of the human factor V&V.
- b. The HFE Design Team's evaluation of the completed human factors V&V, including an evaluation of the compliance with the Human Factors V&V Implementation Plan and HFE Program Plan.
- c. The HFE Design Team's evaluation of the completed human factors V&V, including an evaluation of the presentation and discussion of the HFE Design Team's review i
- findings, i
29 REV.4 102192 l