ML20043F647

From kanterella
Jump to navigation Jump to search
Training Material for E-111 Emergency Diesel Generator Course, South Texas Technical Specifications
ML20043F647
Person / Time
Issue date: 02/12/2020
From:
Office of the Chief Human Capital Officer, Woodard Corp
To:
Gary Callaway
Shared Package
ML20043F634 List:
References
Download: ML20043F647 (13)


Text

3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES OPERATING LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE.

a. Two physically independent circuits between the offsite transmission network and the onsite Class 1 E Distribution System(I), and
b. Three separate and independent standby diesel generators, each with a separate fuel tank containing a minimum volume of 60,500 gallons of fuel, and an automatic load sequencer.

APPLICABILITY: MODES 1,2, 3, and 4.

ACTION:

a. With one offsite circuit of the above-required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirement 4.8.1.1.1 .a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> restore the offsite circuit to OPERABLE status or apply the requirements of the CRMP, or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
b. With a standby diesel generator inoperable, demonstrate the OPERABILITY of the above-required A.C. offsite sources by performing Surveillance Requirement 4.8.1.1.1 .a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If the standby diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining OPERABLE standby diesel generators by performing Surveillance Requirement 4.8.1.1.2.a.2) for each such standby diesel generator separately within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless it can be demonstrated there is no common mode failure for the remaining diesel generator(s). Within 14 days restore the inoperable standby diesel generator to OPERABLE status or apply the requirements of the CRMP, or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. (12)
c. With one offsite circuit of the above-required A.C. electrical power sources and one standby diesel generator inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Specification 4.8.1.1.1 a. within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; and if the standby diesel generator became inoperable due to any cause other than an inoperable support system, an independently testable component, or preplanned preventive SOUTH TEXAS - UNITS 1 & 2 3/4 8-1 Unit 1 - Amendment No. 85 179 Unit 2 - Amendment No. 72, 148 166

ELECTRICAL POWER SYSTEMS LIMITING CONDITION FOR OPERATION ACTION (Continued) maintenance or testing, demonstrate the OPERABILITY of the remaining OPERABLE standby diesel generator(s) by performing Surveillance Requirement 4.8.1.1.2a.2) within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless it can be demonstrated there is no common mode failure for the remaining diesel generators; within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> restore at least one of the inoperable sources to OPERABLE status or apply the requirements of the CRMP, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. (12)

d. With one standby diesel generator inoperable in addition to ACTION b. or c. above, verify that:
1. All required systems, subsystems, trains, components, and devices that depend on the remaining OPERABLE diesel generators as a source of emergency power are also OPERABLE, and
2. When in MODE 1, 2, or 3, the steam-driven auxiliary feedwater pump is OPERABLE.

If these conditions are not satisfied within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, apply the requirements of the CRMP, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

e. With two of the above required offsite A.C. circuits inoperable, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> restore at least one of the inoperable offsite sources to OPERABLE status or apply the requirements of the CRMP, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
f. With two or three of the above required standby diesel generators inoperable, demonstrate the OPERABILITY of two offsite A.C. circuits by performing the requirements of Specification 4.8.1.1.la.

within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. With three of the above required standby diesel generators inoperable, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> restore at least one standby diesel generator to OPERABLE status or apply the requirements of the CRMP, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. (12) With two of the above required standby diesel generators inoperable, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> restore at least two standby diesel generators to OPERABLE status or apply the requirements of the CRMP, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SOUTH TEXAS - UNITS 1 & 2 3/4 8-2 Unit 1 - Amendment No. 8& 179 Unit 2- Amendment No. 72,-48 166

ELECTRICAL POWER SYSTEMS 2LIMITING CONDITION FOR OPERATION ACTION (continued)

g. With one or more diesel generator fuel oil storage tanks with stored fuel oil total particulates not within the Diesel Fuel Oil Testing Program limits, within 7 days restore the fuel oil total particulates within limits, or declare the associated standby diesel generator(s) inoperable.
h. With one or more diesel generator fuel oil storage tanks with new fuel oil properties not within the Diesel Fuel Oil Testing Program limits, within 30 days restore the fuel oil properties within limits, or declare the associated standby diesel generator(s) inoperable.
i. Specification 3.0.4.b is not applicable for standby diesel generators.

I SOUTH TEXAS - UNITS 1 & 2 3/4 8-2a Unit 1 -Amendment No. 454 170 Unit 2 - Amendment No. 439,'158

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS 4.8.1.1.1 Each of the above required independent circuits between the offsite transmission network and the Onsite Class 'I E Distribution System shall be:

a. Determined OPERABLE at a frequency in accordance with the Surveillance Frequency Control Program by verifying correct breaker alignments, indicated power availability, and
b. Demonstrated OPERABLE at a frequency in accordance with the Surveillance Frequency Control Program during shutdown by transferring the unit power supply from the normal circuit to each of the alternate circuits.

4.8.1.1.2 Each standby diesel generator shall be demonstrated OPERABLE: (2)(11)

a. At a frequency in accordance with the Surveillance Frequency Control Program by:
1) Verifying the fuel level in its associated fuel tank,
2) Verifying the diesel starts from standby condition and accelerates to 600 rpm (nominal) in less than or equal to 10 seconds. (3) The generator voltage and frequency shall be 4160 +/- 416 volts and 60 +/- 1.2 Hz within 10 seconds(3) after the start signal. The diesel generator shall be started for this test by using one of the following signals:

a) Manual, or b) Simulated loss-of-off site power by itself, or c) Simulated loss-of-offsite power in conjunction with a Safety Injection test signal, or d) A Safety Injection test signal by itself.

3) Verifying the generator is synchronized, loaded to 5000 to 5500 kW, and operates with a load of 5000 to 5500 kW for at least 60 minutes, (4)(6) and
4) Verifying the standby diesel generator is aligned to provide standby power to the associated emergency busses.
b. At a frequency in accordance with the Surveillance Frequency Control Program and after each operation of the diesel where the period of operation was greater than or equal to 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> by checking for and removing accumulated water from its associated fuel tank;
c. Maintain properties of new and stored fuel oil in accordance with the Fuel Oil Monitoring Program.

SOUTH TEXAS - UNITS 1 & 2 3/4 8-3 Unit 1 - Amendment No. sa, ~ 188 Unit 2 - Amendment No. +2, ++G 175

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)

d. Deleted
e. At a frequency in accordance with the Surveillance Frequency Control Program, during shutdown, by:
1) Deleted
2) Verifying the generator capability to reject a load of greater than or equal to 785.3 kW while maintaining voltage at 4160 +/- 416 volts and frequency at 60 +/-

4.5 Hz; (4)(5)

3) Verifying the generator capability to reject a load of 5500 kW without tripping.

The generator voltage shall not exceed 5262 volts during and following the load rejection; '4)(5)

4) Simulating a loss-of-offsite power by itself, and:

a) Verifying deenergization of the ESF busses and load shedding from the ESF busses, and b) Verifying the diesel starts on the auto-start signal within 10 seconds, energizes the auto-connected shutdown loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the shutdown loads. After energization, the steady-state voltage and frequency of the ESF busses shall be maintained at 4160 +/-

416 volts and 60 +/- 1.2 Hz during this test.

5) Verifying that on a Safety Injection test signal, without loss-of-offsite power, the diesel generator starts on the auto-start signal and operates on standby for greater than or equal to 5 minutes. The generator voltage and frequency shall be 4160 +/- 416 volts and 60 +/- 1.2 Hz within 10 seconds after the autostart signal; the steady-state generator voltage and frequency shall be maintained within these limits during this test;
6) Simulating a loss-of-offsite power in conjunction with a Safety Injection test signal, and:

a) Verifying deenergization of the ESF busses and load shedding from the ESF busses; b) Verifying the diesel starts on the auto-start signal within 10 seconds, energizes the auto-connected ESF (accident) loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator SOUTH TEXAS - UNITS 1 & 2 3/4 8-4 Unit 1 -Amendment No. 8a,42-i 188 Unit 2 -Amendment No. 72,4W 175

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) is loaded with the ESF loads. After energization, the steady-state voltage and frequency of the ESF busses shall be maintained at 4160 i 416 volts and 60 I1.2'Hz during this test; and c) Verifying that all automatic diesel generator trips, except engine overspeed, generator differential, and low lube oil pressure are automatically bypassed upon loss of voltage on the ESF bus concurrent with a Safety Injection Actuation signal.

7)'°Verifying the standby diesel generator operates for at least I 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. During the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this Jest the diesel generator shall be loaded to 5700 to 6050 kW ")c)) and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of thif test, the diesel generator shall be loaded to 5000 to 5500 kW. " The steady-state generator voltage and frequency shall be 4160 i 416 volts and 60 i 1.2 Hz during this test. Within 5 minutes after completing this 24-hour test, pefform a fast start per Specification

8) Verifying that the auto-connected loads to each standby diesel generator do not exceed the 2000-hour rating of 5935 kW;
9) Verifying the standby diesel generator's capability to:

a) Synchronize with the offsite power source while the generator is loaded with its ESF loads upon a simulated restoration of offsite power, b) Transfer its loads to the offsite power source, and c) Be restored to its standby status.

10) Verifying that with the standby diesel generator operating in a test mode, connected toits bus, a simulate4dSafety Injection signal overrides'the test'mode by: (1) returnin'g'Athe diesel generator to'st'an-dby.operation, and t(2)auto tbcilly' energizing-the ESFjloads. with.offsite power;  ;
11) VerifyIng that'the.automatic lo'adsequence timer Is 0PEBLE '

' with the first sequenced'lad verified-to5 be'loaded between 1.0 second and 1.6 seconds,-.and all other load blocks wIthin +/-10%

of its design interval,

12) Verifying that the standby diesel generator emergency stop lockout feature prevents diespl generator starting; ard SOUTH TEXAS - UNITS 1 & 2 3/4 8-5 Unit 1 - Amendment No. 68,81 Unit 2 - Amendment No. P,70 FEB 21 1996

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)

13) Demonstrating the OPERABILITY of the automatic load shed bypass and the manual load shed reinstatement features of the load sequencer.
f. At a frequency in accordance with the Surveillance Frequency Control Program or after any modifications which could affect standby diesel generator interdependence by starting all standby diesel generators simultaneously, during shutdown, and verifying that all standby diesel generators accelerate to at least 600 rpm in less than or equal to 10 seconds; and
g. At a frequency in accordance with the Surveillance Frequency Control Program by draining each fuel tank, removing the accumulated sediment and cleaning the tank.

4.8.1.1.3 (Not used)

SOUTH TEXAS - UNITS 1 & 2 3/4 8-6 Unit 1 - Amendment No. -lOO, +22 188 Unit 2 - Amendment No. W, +W 175

TABLE 4.8-1 DIESEL GENERATOR TEST SCHEDULE (Not used)

SPECIFICATION NOTATIONS (1) Loss of one 13.8 kV Standby Bus to 4.16 kV ESF bus line constitutes loss of one offsite source. Loss of two 13.8 kV Standby busses to 4.16 kV ESF bus lines constitutes loss of two offsite sources.

(2) All diesel generator starts for the purpose of these surveillances may be preceded by a prelube period.

(3) A diesel generator start in less than or equal to 10 seconds (fast start) shall be at a frequency in accordance with the Surveillance Frequency Control Program. All other diesel generator starts for the purpose of this surveillance may be modified starts involving reduced fuel (load limit) and/or idling and gradual acceleration to synchronous speed.

(4) Generator loading may be accomplished in accordance with vendor recommendations, including a warmup period prior to loading.

(5) The diesel generator start for this surveillance may be a modified start (see SR 4.8.1.1.2a.2)).

(6) Momentary transients outside this load range due to changing conditions on the grid shall not invalidate the test.

(7) If Specification 4.8.1.1.2a.2) is not satisfactorily completed, it is not necessary to repeat the preceding 24-hour test. Instead, the standby diesel generator may be operated at 5000-5500 kW for a minimum of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or until operating temperature has stabilized.

(8) (Not used)

(9) (Not used)

(10) This test may be performed during power operation provided that the other two diesel generators are operable.

(11) Credit may be taken for events that satisfy any of these Surveillance Requirements.

(12) For the Unit 2 Train B standby diesel generator (SDG 22) failure of December 9, 2003, restore the inoperable standby diesel generator to OPERABLE status within 113 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the next 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

SOUTH TEXAS - UNITS 1 & 2 3/48-7 Unit 1 - Amendment No. eg, ~ 188 Unit 2 - Amendment No. 5+, 110, 148, 49 175

THIS PAGE IS INTENTIONALLY BLANK SOUTH TEXAS - UNITS 1 & 2 3/4 8-8 Unit 1 - Amendment No. $$, 122 Unit 2 - Amendment No. 7i, 110 JANS I q 206,,

ELECTRICAL POWER SYSTEMS A.C. SOURCES SHUTDOWN LIM1 T1MG COND0TION FOR QPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shall be OPERABLE:

a. One circuit between the offsite transmission network and the Onsite Class IE Distribution System, and
b. Two1 standby diesel generators each with a separate fuel tank containing a minimum volume of 60,500 gallons of fuel.

APPLICABILITY: MODE 5 and MODE 6 with water level in the refueling cavity <23 ft above the reactor pressure vessel flange.

ACTION:

With less than the above minimum required A.C. electrical power sources OPERABLE, immediately suspend all operations involving CORE ALTERATIONS, operations involving positive reactivity additions that could result in loss of required SHUTDOWN MARGIN or required boron concentration, movement of irradiated fuel, operations with a potential for draining the reactor vessel or crane operation with loads over the spent fuel pool. Immediately initiate actions to restore the inoperable A.C.

electrical power source to OPERABLE status.

SVER 4.8.1.2 The above required A.C. electrical pomver sources shall be demonstrated OPERABLE by the performance of each of the requirements of Specifications 4.8.1.1.1, 4.8.1.1.2 (except for Specification 4.8.1.1.2a.3), and 4.8.1.1.3.

4.8.1.2.1 The alternate onsite emergency power source shall be demonstrated functional by:

a. Within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> of taking credit for the onsite emergency power source as a standby diesel generator, verify it starts and achieves steady state voltage (.El1O%) and frequency (E2%) in 5 minutes.
b. Within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> of taking credit for the onsite emergency power source as a standby diesel generator and every 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, verify the emergency power source is capable of being aligned to the required ESF bus by performing a breaker alignment check.

'An alternate onsite emergency.power source, capable of supplying power for one train of shutdown cooling maybe substituted for one of the required diesels for 14 consecutive days (SR 4.8.1.2.1 is the only requirement applicable).

SOUTH TEXAS -UNITS 1 & 2 3/4 8-9 Unit 1- AmendmentNo. et 128 Unit 2 - Amendment No. -64 117

182 169

ELECTRICAL POWER SYSTEMS 3/4.8.2 DC SOURCES OPERATING LIMITING CONDITION FOR OPERATION 3.8.2.1 As a minimum, the following DC electrical sources shall be OPERABLE:

a. Channel I 125-volt Battery Bank ElAl 1 (Unit 1), E2A1 1 (Unit 2) and one of its two associated chargers,
b. Channel 11 125-volt Battery Bank El D11 (Unit 1), E2D1 1 (Unit 2) and one of its two associated full capacity chargers,
c. Channel III 125-volt Battery Bank ElB1 1 (Unit 1), E2B1 1 (Unit 2) and one of its two associated full capacity chargers, and
d. Channel IV 125-volt Battery Bank El Cl 1 (Unit 1), E2C1 1 (Unit 2) and one of its two associated chargers.

APPLICABILITY: MODES 1,2,3, and 4.

ACTION:

NOTE If the batteries discharge for more than 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> as the sole source of power to their DC bus while the CRMP is being applied and no alternate source of power is available, the LCO shall be considered not met.

a. With one of the required battery banks inoperable, within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> restore the inoperable battery bank to OPERABLE status or apply the requirements of the CRMP or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
b. With more than one of the required battery banks inoperable, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> restore at least three battery banks to OPERABLE status or apply the requirements of the CRMP or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
c. With one channel with no battery chargers OPERABLE,
1. Restore battery terminal voltage to greater than or equal to the minimum established float voltage within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, AND
2. Verify float current for the affected battery does not exceed 2 amps once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, AND 3., Restore one battery charger to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

If the battery terminal voltage cannot be restored in the allowed time, float current is excessive, or a battery charger is not restored to operability in the time allowed, apply the requirements of the CRMP or the affected reactor unit is to be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SOUTH TEXAS - UNITS 1 & 2 3/4 8-10 Unit 1 - Amendment No. 4,73,A-7 180 Unit 2 - Amendment No. 62-,-66 167

ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)

d. With more than one channel with no battery chargers OPERABLE, 1 Restore terminal voltage for at least three battery banks to greater than or equal to the minimum established float voltage within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, AND
2. Verify float current for the affected batteries does not exceed 2 amps once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, AND
3. Restore one battery charger to OPERABLE status on at least three channels within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

If the battery terminal voltage cannot be restored in the allowed time, float current is excessive, or a battery charger is not restored to operability in the time allowed, apply the requirements of the CRMP or the affected reactor unit is to be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

e. With one of the required channels inoperable for reasons other than (a), (b), (c), or (d) above, restore the channel to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.8.2.1 Each 125-volt battery bank and charger shall be demonstrated OPERABLE:

a. At a frequency in accordance with the Surveillance Frequency Control Program by verifying that:

The total battery terminal voltage is greater than or equal to the minimum established float voltage.

b. Not used.
c. At a frequency in accordance with the Surveillance Frequency Control Program by verifying that:
1. The battery charger can supply at least 300 amperes at greater than or equal to the minimum established float voltage for at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

OR Each battery charger can recharge the battery to the fully charged state within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> while supplying the largest combined demands of the various continuous steady-state loads followinq a battery discharqe to the boundino desion-basis event discharoe state.

NOTE: 1. The modified performance discharge test in SR 4.8.2.3.f may be

2. performed in lieu of Surveillance Requirement 4.8.2.1.c.2.
2. Credit may be taken for unplanned events that satisfy this surveillance requirement.

The battery capacity is adequate to supply and maintain in OPERABLE status all of the actual or simulated ESF loads for the design duty cycle when the battery is subjected to a battery service test.

d. Not used.
e. Not used.
f. Not used.

SOUTH TEXAS - UNITS 1 & 2 3/48-11 Unit 1 - Amendment No. 4, 179, 180, 184 188 Unit 2 - Amendment No. 66. 167, 171 175