Text
_-
l ALOD ENGINEERING EVALVATION L; NIT:
Multiple EE REPORT NO.: AE00/[90 01
)
DOCKET NO.: Multiple DAlt:
February 7,1990 LICENSEE:
Multiple EVALL!ATOR/ CONTACT:
M. Wegner NS$$/AE:
Multiple / Multiple
SUBJECT:
TAILURES OF ELECm! CAL SUPPLY AND POWER GENERATION EQUIPMENT WHICH DISRUPTED PLANT FUNCTION AT NUCLEAR POWER PLANTS i
SUMMARY
This study war *nitiated because of the occurrence of several events in early l
1989 involvin;, major electrical equipment or offsite power problems. A search for similar events identified 79 events in the past 18 montis.
Twenty-two of l
those events were considered to be of major interest and are described in this i
report.
The issues addressed in this report concern disruptions of normal station auxiliary alternating current (AC) power supply caused by grid, switchyard, and non-1E electrical system problems and major electrical equipment failures.
failures in electrical supply or power generation equipment can impact safety equipment in that they often cause scrams or require unit shutdown, they may j
cause engineertd safety features systems to operate, they frequently cause interruptions of offsite power supply to station auxiliaries, they occasionally cause fires, and they complicate post-scram operations by rendering equipment unavailable or unreliable.
1 Interruptions of offsite power to 1E busses, while they are contributors to the risk of a station blackout, generally cause transfer of the busses to the i
emergency diesel-generators (EDGs); while interruptions of offsite power to non-1E busses cause scrams loss of forced circulation, loss of preferred heat sink, and loss of service / Instrument air.
/.n AEOD Eng weering Evaluation, AEOD/E905,
- Electrical Bus Bar failures," and an NRC information notice, IN 89-064; and an ongoing AEOD study on main trans-former failures address the major equipment failures. Fast bus transfer AEOD study. The operating failure is also being adessed in an on-going'iance, and)rocedural problems, o perience, particular 9 naintenance, surveil should be utilized by hKR in developing procedures for t1e upcoming team inspections.
DISCUS $10N From January 1 to February 7,1989, there were reports of a breaker and a trans-former explosion and fire, a partial loss of off site power, another breaker fire, another partial loss of offsite power, a fire in the main generator, a bus bar short, loss of offsite power, a second partial loss of offsite )ower at a startup plant, a loss of offsite power involving two units, turbine ligh vibration, another breaker fire, and a fire in the turbine area. The quantity of the reports was large enough to warrant a look at the report data bases to determine the scope of the problem and an analysis of the safety impact.
$$$ $?$M y Q s PDC
-2 At that tio+, a preliminary search was perforred. All events involving electrical supply couipment up to (but not including) the startup transformer were included as well as events involving power generation equipment. The main turbine and gererator were included but not their control systems, instruments, valves, or otler attendant systems. Additionally the initiator must also have i
caused or contributed to a complicated transient In which there was a turbine trip, reactor scram, engineered safety features (EST) actuation, and/or other s.ejor complications.
Several events of signif tunce were found and this study was undertaken.
The NRC's document control system (DCS) was searched for licensee event reports (LERs) which involved a turbine tri) or loss of the main generator in the 12 month period from February 7,194, to February 7,1989. Twelve significant events were found which showed the im>act of electrical disruptions on plant I
function. A more thorough search of _ERS for the period using the Secuence CodingandSearchSystem(SCSS)found45LERs.
from daily reports anc 10 CFR 50.72 reports n.ede from fi! ruary 7,1989, through May 31, 1989, additional reports were selected.
From all these data bases, a total of 79 event reports involving interruptions i
ci offsite power supply to the station auxiliaries or major electric equipment problems was identified. Twenty-two of theseinterest,aredetailedinthefollowing co Events involving interruptions ofoffsitepowertotheplant(eitherpartialortotallossofoffsitepower) are shown in Table 2.
Appendix 1 is a tabulation of all the other events.
[
i Search Strategies l
The events which are discussed were selected from the LERs written from 02/07/88 l
to 05/31/89. These events involve failures in electrical supply or power generation equipment which disrupted plant function. These events were selected l
from a larger number of events found in a variety of Boolean searches of the l
DCS. The most fruitful search was DTC (docurent tT (term) yse code) TRLER (the TIJRBINE TRIP. Additional LERs) + DA (date range) 880207. 890207 +
events were found by using the sare DTC and DA and combining with T GENERATOR and by scanning 10 CFR 50.72 reports. The loss of offsite power inforr.ation for 1989 was taken from a scan of DCS listings of all LERs submitted in 1989, DTC TRLER and DA 890101. 890720 and 10 CFR 50.72 reports.
l A boolean search of the DCS for all LERs written in 1988 describing scrams found about 320 events. A Sequence Codina and Search System search of LERs written in the same period by a variety of strategies found about 141 LERs of which 45 were applicable to this study. The data bases queried were designed to have safety system information readily accessible. The keywords relevant to this study were few and non-specific; that is, a term such as ' transformer" I
would locate a tiny device on a printed circuit as well as a station transformer.
l Therefore, the strategies used were
- reactor scram" and " turbine trip'. LERs l
were then read to determine if they were pertinent.
i l.
Major Events of Inter g 1he following 22 events were of major interest because of the complexity of the event, the safety consequences of the occurrence, the failures of the equipment involved, and the effects on plant systems - safety related and r.on-safety 1
i l
-30 I
related.
In general, automatic systems functioned as they were espected to j
fur.ction for the event describa unless otherwise indicated. The events t
described in the following paragraphs are identied by plant name. LER nunter, l
date, and event descriptors as defined in Table 1.
Table _1.
Event Descriptors 10PS Interruption of offsite power XFMR Transformer failure BRKR Breaker failure FIRE Fire ESF Engineered safety features actuation, including ECCS, AFW, EDG, PCIS, SRV SCRAM Reactor shutdown, manual or automatic, while r?itical i
RPS Reactor shutdown signal while shutdown I
T-G Turbine or generator non electrical problems COMP Complications DUAL Both units at the site involved Kewaunee LER 88/001 03/02/88 SCRAM / FIRE A reactor scram and turbine trip occurred due to an undervoltage transient on t
two 4160 volt busses which supply power to a reactor coolant sump (RCP) motor and a main feedwater (MFW) pump motor. A section of the bus >ar running fres the main auxiliary transformer to the bus switchgear was badly damaged due to l
insulation failure and subsequent fault. The fault caused the voltage at the i
switchgear to decrease and the undervoltage on both busses caused a reactor scram and turbine trip. The busses were automatically isolated from the main auxiliary transformer and transferred to the reserve auxiliary transformer as l
expected preventing the trip of the RCP and the MFW pump.
l Due to to amount of smoke in the turbine ouilding, the shift supervisor activated i
the emergency sire which required all the on-site personnel to assemble for
[
accountability. The root cause of the event was a fault on the bus bar at the bus bar support.
Poor housekeeping in the area of the bus bar lead to water l
and dirt accumulation which hestened the deterioration of the insulation and i
i provided a path to ground, f
Palo Verde 1 LER 88/010 07/06/88 10PS/XFMR/ FIRE /ESF/ SCRAM / COMP l
A B-phase ground fault occurred on a non-1E 13.8KY bus, ionizing the air in the vicinity, precipitating a three-phase fault to ground. The feeder breakers to l
this and another bus did not immediately trip because they had a 0.7 second l
time delay (42 cycles).
In that tine period, the unit aux 111ery transformer i
i which was connected to the faulted bus experienced a greater than 24,000 amp fault, exploded, and caught fire. The busses' supply breakers and the generator output breakers opened. The unpowered RCPs coasted down causing the the reactor to scram as expected.
Fast bus transfer of the safety busses failed to occur 4
which compares the voltage of one of the safety because the sync check nlay,found them both in sync, but at zero potential due l
busses with the faulted bus i
due to the failed unit auxiliary transformer and the faulted bus.
(They must be in sync and have the required voltage for the fast transfer to occur.)
i
E Severt i electrical equipment problems complicated the post-scram transient. The nucle 4r cooling water system (non safety related) was lost when the non-1E power was lost.
The essential cooling water (ECW) system was cross tied to the nuclear cooling water system. One of the cross-tie valves was found to be shut when the ir.struments read both open and closed.
When the control room was notified that a fire was in progress, the fire area auxiliary operator proceeded to the area to check the equipment. Deluge flow to the failed transformer could not be verified because the panel was located inside a well damaged by the transformer explosion.
The operator activated the deluge valves to all the transformers and exited the area. Since electrical power to remotely operate the deluge valves had been lost, the manual actuation was necessary.
{
Emergency ventilation to the control room was initiated when nonnal ventilation was lost due to loss of power. The normal source of instrument air was not I
available due to the loss of power and the nitrogen system provided pneuw.atic i
backup according to design.
EDGs were started and the safety busses were loaded onto the EDGs in order to isolate the safety busses from the wet transformers and non-safety busses. The t
I supply breaker to one of the safety busses could not be opened remotely but was opened manually. To determine if the faulted but could be re-energized.
operations personnel proceeded to the switchgear room and noted that the only targets on the bus were undervoltage relays (the bus was de-energized) and the trip flags were recorded and reset prior to re-energiring. The room was dark l
and smoke was present. The smoke was thought to be coming from the transfonner fire. An attempt was made to re-energize the bus, but the breaker tripped and the bus was reported afire.
I Upon restarting RCps A and B, the pumps tripped on an actuation of the lock-out i
relay in the speed sensor. The cause of the relay actuation was low direct l
current (DC) voltage due to a discharged non 1E station battery.
l Although all types of errors contributed to complicate the event, the initiator
- f ailed bus bar - was caused in a large part by poor house-keeping in the area of the bus bar. The dirt accumulation contributed directly to the evolution of a single phase fault into a three phase fault. The second fire was caused by l
personnel error, with the failure to maintein the emergency lighting as a strong l
contributor.
r Ginna LER 88/006 07/16/88 10PS/BRKR/SCP.AM/ COMP An electrical fault in the plent's main electrical substation caused five main l
breakers in the substation to open.
This caused loss of about one-half of the transmission capability of the substation and loss of all normal off site power to the plant. The four safety busses deenergized and were reenergized with the l
EDGs in about 30 seconds, in that period, an instrument bus was lost momentarily l
causing a turbine runback. The plant was stabilized at 75 percent power.
l The security department reported hearing an explosion at the substation. Upon investigation, it was discovered that a bushing on a 115KV oil-filled circuit i
breaker had failed and the breaker exploded. A plant shutdown was commenced at the request of the power control dispatcher because of the damage to the t
~
t
-5 off-site power trentmission equipment. The turbine was taken off-line and the reactor trip brealers were opened. After the turbine was off-line, in operator l
attemptingtoresetthefeedwaterisolationontheB-steamger.erator($/G),
pressed the S/G isolation reset button instead and the MSIY closed, j
Other problems reported were a rod which f ailed to insert manus 11y but did insert when the trip breaker was opened, and an oil leak at the substation in l
the 115KY underground line from the plant to the substation.
Peach Bottom 243 LER 88/020 07/29/88 XfMR/f!RE/ESF/RPS/ DUAL l
The capacitors which connect the 500KY f1 bus tie line with the A-phase potential transformer failed and the transformer caught on fire. The potential i
transformer steps line voltage down to that used by equipment in the substation, i
A voltage disturbance ensued which ultiutely resulted in several expected ESF actuations on Units 2 and 3 and a partial loss of telephone services at the site.
The power susply which was established was permissible for the conditions which i
i existed at tie site. Both units were shutdown and defueled with equipment out i
of service for maintenance, These events occurred as expected while the plants were in off-norinal configura-tions for maintenance outages.
River Bend LER F8/018 08/25/88 SCRAM /ESF/10PS/ COMP The generator tripped from loss of field excitation, resulting in a turbine trip which caused a reactor scram.
prior to the scram, one of the main generator brushes had been sparking and maintenance procedures were being readied to address the problem. During the post scram transient, the recirculation pumps transferred to the slow speed motor / generator set on an end of-cycle recircula-tion pump tri Reactor pressure peaked high causing five safety / relief valves ($RVs)psignal.
to 1ift. Turbine )ypass valves opened. The pressure spike collapsed the voids causing reactor water level to decrease. All actuations were expected in an event of this type. An hydraulic perturbetion on the wide range level instruments showed a low level spike greater than -29 inches.
High pressure core spray (HPCS) and reactor core isolation cooling (RCIC) l initiated and injected for about 30 seconds. Subsequently the HPCS injection line u > stream of the injection valve was found to be hot, due to backleakage from tie reactor.
A non-safety related bus failed to transfer from the normal station service i
transformer and a second bus f ailed the fast transfer but did slow transfer.
l The first failure caused a loss of power to to the HPCS bus. The HPCS diesel-generator started and loaded the bus. The turbine building closed cooling l
water pumps tripped and the instrument air compressors subsequently tripped on i
high temperature. Power to the RPS bus A was lost resulting in an initiation of the standby gas treatunt end annulus mixing systems and the trip of the annulus pressure control system. A spurious high drywell alarm also actuated.
l T
i l
.< j i
Catawba 2 LER 88/028 09/28/88 T.G/ COMP / SCRAM The generator stator water cooling system circulates high purity water through the stator coil hollow conductors, tither of two AC motor-driven centrifugal l
pumps will produce the required flow. Pressure actuated switches cause the I
automatic startup of the reserve pump in the event that the pressure decreases.
If the stator cooling water is lost, the turbine runback circuitry will autora.
l tically reduce the generator output to the rated capability without stator i
coolingwatercirculation(about23%turbineload).
In this event, maintenance personnel bumped the pump switch while removing masking tape af ter painting the j
switch panel. The switch was put in the OFF position. The running pump j
tripped and the reserve pump was prevented from starting by the switch position.
r The loss of stator cooling caused a turbine runback as designed and reactor
{
power was reduced from 951 to 35% in 3 minutes.
l The turbine runback failed to stop at the rated capability without stator cooling water circulation but terminated when the operator restored the stator l
cooling water pump.
Following the runback, the steam dumps erratic operation caused an increase in the reactor coolant system (RCS) average temperatere (Tave) which caused a S/6 level swell when the steam dum>s failed to open f
pro >erly. Then a steam dump fully opened aggravating tie level swell.
The tur>ine tripped on an indication of $/G hIgh level} to autostart by design.
isolating MFW and causing the MfW pumps to trip and auxiliary feedwater (AFW l
The reactor was then manually scrammed because of the loss of main feedwater with the reactor above 10% power.
j Braidwood 1 LER 88/022 10/16/88 10PS/ COMP /ESF/ SCRAM / DUAL A loss of all off site power to the unit occurred when the A-phase potential transformer for a 138KV line failed causing a current surge on the low side of a transfonner at an off-site substation, causing its sudden pressure relay to actuate. A transfer trip signal was sent to the 345KV breakers associated with both the substation and the plant. The 345KV oil circuit breaker and the 345KV r
air circuit breakers opened, but the air circuit breaker took longer to open causing a pole disagreenent actuation (all three phases not in the same state).
This caused another air circuit breaker to open, which resulted in the being removed from the high side of the station auxiliary transformers. power Auto l
transfer of two 6.9KY busses occurred and EDGs started and loaded two 4KV busses.
An RCP supply breaker tripped on instantaneous overcurrent because of a piece of cardboard in the relay that bypassed the time delay of the relay. The i
l licensee speculates that the card >oard was inserted during the last maintenance i
j on the relay and not removed. This caused a reactor scram on low RCP flow with the reactor above 30% power. The turbine and generator tripped as expected.
Voltage on the unit auxiliary transformers decayed, causing a loss of power on edditional busses.
Station air compressors tripped and instrument air pressure began to decrease to both units. Several attempts to restore equipment were i
thwarted by the pole disagreement. The pole disagreement was found to have been caused by an out-of-calibration circuit breaker.
r.
r a
r t
7 4
Hope Creek LER 68/029 11/01/88 SCRAM /ESF/ COMP A main generator lockout occurred on the loss of excitation which was caused by r
the failure of the exciter brush-collector ring assently from undetermined I
causes followed by fast closure of the turbine control valves, main turbine trip, and reactor scram. The recirculation pumps tripped on end-of-cycle logic.
Reactor pressure increased and the H-SRV lifted. Recctor feedwater i
pumps tripped on high level.
High pressure coolant injection (HPCI) and RCIC actuated and injected for about 10 minutes. Automatic actuations were as l
expected for this type of event. During the subsequent transient, the P SRV l
(low set) failed to lif t because of a faulty pressure transmitter, j
Although the licensee could not determine the root cause of the exciter brush l
failure due to the extent of damage to the equipment, it was speculated that a l
more rigorous inspection may have prevented the failure.
To tits end, the l
utility is developing a new procedare.
Clinton LER 88/028 11/11/88 XFMR/ SCRAM / FIRE i
The C-phase main power transformer experienced a phase to ground overturrent fault causing a generator-to-transformer differential relay trip of the main generator and a consequential turbine trip. The reactor scrammed on turbine stop valve fast closure as designed. A fire had started from oil which had i
erupted from the transformer bushing. Thefireprotectiondelug'einitiatedin the transformer area and the fire brigade was dispatched. The ire was above the deluge, since the deluge was designed to preclude spraying of the high
?
voltage bushini. The fire brigade extinguished the fire in about 30 minutes.
The cause of tle event was an internal fault on the high voltage side of the j
transformer.
Sequoyah 1 LER 88/045 11/18/88 SCRAN/ESF/ COMP A reactor scram occurred as a result of the main turbine being tripped by the j
main generator neutral overvoltage relay, which had detected a ground fault.
Steam dump valves opened, MFW isolated, and AFW actuated. All automatic j
actuations were as designed. Both motor driven and the turbine-driven AFW pumps injected. The flow indicator for the turbine-driven AFW pump indicated off-scale,high(greaterthan1000gpm). The overspeed protection should have i
limited the flow to 880 gpm to prevent pump runout. Consequently the RCS cooled down below the no-load Tave. Also the volume control tank level decreased below 7 percent. Maints; nance personnel determined that the cause of the event l
I l
was a ground fault internal to the main generator. There was an insulation breakdown on a C-phase stator bar.
j i
Oconee 1 LER 89/002 01/03/89 FIRE / SCRAM / COMP A fire began in the non-1E switchgear while escalating in power. Two RCPs tripped. Af ter 30 minutes, the reactor was manually scrammed and the remaining 2 RCPs were tripped so that water could be safely ustd to fight the fire after carbon dioxide and dry chemicals had proven unsuccessful.
Afailureoftheintegratedcontrolsystem(105)tocontrolsteamgenerator I
level using the AFW nor:1es (main feedwater is required to change injection
}
l from MFW norrles to AFW uorrles) ceused an RCS pressure transient and technical I
0 g.
- s specifications (T$)cooldownrateswereexceededwhilemitigatingthepressure I
transient as a result of overfeeding the steam generators. The failure of the 10$ was caused by fire damage to control cables in the switchgear. The result-ant operation in the therul shock operating range was not properly compen-sated. Other equiprent f ailures and personnel errors complicated the post-scram transient.
South Texas 1 LER 89/005 01/20/69 FIRE /T-G/$ CRAM / COMP l
Alarms were received which indicated that there was high vibration in the turbine and a high temperature on the #8 and #9 bearings. A fire was reported at the #9 bearing and the deluge actuated. The turbine was unvally tripped causing an automatic reactor scram. The fire brigado extinguished the fire in I
about 20 minutes and the generator was purged of hydrogen with carbon dioxide and the carbon dioxide with air in the usual manner. The problem with the i
generator began with a loss of stator cooling due to a loose wire in the temperature sensing unit which caused a temperature increase to go unnoticed i
and without compensation until the hydregen seal at the #9 bearing was damaged j
by the heat causing pressure to increase and lealage.
The source of ignition is not known. The visible flares around the bearing were probably caused by heat igniting grease or lube oil.
l The generator was disassembled and the rotor removed for inspection. No significant damage was found. The bearings' pedestals were inspected and no l
dange was found. The lutse cil was drained and flushed, j
WNP 2 LER 89/002 01/30/89 $CRIN/ESF/ COMP j
A buildup of a conductive film on the surface of an insulator on the outsut i
side of the main transforu r caused the insulator to short to ground. T ie i
resultant high currents tripped the main generator output breakers.
The load rejection tripped the generator and turbine and scroaned the reactor as expected.
l During the post scram transient, a level transient caused certain containment isolations on 'ow level and subsequent pump trips on high level (due to over-compensation).
Six SRVs lifted and resented properly as expected. The scram t
discharge volume vent and drain valves did not reopen on the scram reset.
pilgrim LER 89/010 02/21/89 RPS/ESF/10PS i
Aircircuitbrealers(ACBs)openedduetoagroundfaultintheunderground portion of one of the C-phase power feedtr cables between the secondary side of the startup transformer and a non safety related 4160 volt bus. The differen-tial ground current relay detected the cable fault and caused the startup transformer to be locked out which, in turn, tripped the ACBs. The EDGs started and leaded the safety busses as expected. An RPS actuation - scram signal PCl$ actuation, reactor building isolation, and $BGT actuation occurred asdesIgned. Offsite pcwer was restored 15 hours1.736111e-4 days <br />0.00417 hours <br />2.480159e-5 weeks <br />5.7075e-6 months <br /> later.
LaSalle 1&2 LER 89/009 03/02/89 10PS/ SCRAM /BRKR/ COMP / DUAL
{
l The C phase lightning arrestor on the station auxiliary transformer ($AT) failed resulting in a phase-to-ground fault on the line to the unit 2 distribu-tion system.
Oil circuit breakers (OCBs) and unit 2 feeder breaker from the L
I
.g.
SAT opened to isolate the fault. Automatic transfer from the SAT to the unit I
auxiliary tranformer (UAT) was accompitsbed and an EDG started and loaded a bus
(
as designed.
Because of the lightning arrestor failure, the Unit 1 main generator protective relays sensed a high differential current on phase A and locked out tse i
generator. The load rejection caused a turbine trip and a reactor scres. An DCB failed while opening, j
Pre existing conditions complicated the post-scram transient. The Unit 2 l
process computer was performing the primary data acquisition and safety i
parameter cisplay system (SPDS) functions for both units, with the Unit 1
(
nrocess computer in standby. The Unit 2 process computer was powered from the Jnit 1 SAT sy >assing the uninterruptible power system (UPS) because of a f ailed i
inverter in tie UPS.
The computer used for core monitoring and off-site dose calculations had also bypassed UPS and was powered from Unit 2 SAT. Additionally, intersediate range power monitors (IRMs) D and F werd out of service.
{
The loss of the process coruter made the job of assuring that all rods went to full-inmoredifficultintbatithadtobedonemanuallyforeachrodby selecting the rod and observing the rod sequence control system panel " full-in' lights.
Service air was lost briefly on Unit 1 making it difficult to reset the A-scram I
channel. The B-scram channel could not be reset beceuse of the inoperable l
1RMs.
Unit 2 service air was also lost briefly.
The drywell chillers in Unit 2 were lost for about 15 minutes while the unit l
was in mode 1.
Drywell temperature rose to 213 degrees F and pressure rose to 40.6 psig, j
The 2A reactor feedpump controller locked up causing a reactor level transient.
Yessel minimum was +25.0 inches and maximum was 453.0 inches. Operators took control of the pump to limit the transient. Reactor water cleanup system and i
l the rea m r building ventilation system isolated.
1 I
l palo ierde 3 l.ER 89/001 03/03/89 COMP /ESF/10PS/SCPAM l
l A fault in a California switchyard caused a grid disturbance wnich actuated the subsynchronous oscillation protection relay for the unit 3 main turbine /
l generator. The generator output breakers opened and the steam bypass control system was called upon to dump steam to the condenser while reactor power was I
f run back. Automatic actuations were as expected for this transients however, j
four of the steam dumps cycled from 105 to 100% open about nine times while the remaining valves fluttered between 80% and 100% open.
Excessive steam removal caused the pressure in steam generator 2 to go low enough to scram the reactor, and to cause the main steem isolation valves to close.
There was a safety injection on pressurizer low pressure as well as a containment isolation actuation.
Fast transfer did not occur because the house loads were connected to the generator which was isolated from the grid. (Reverse power signal from the grid would have dropped the house loads from the generator.) As the generator
w 10 -
i I
coasted down, the frequency decayed to 30 Hz. When the house loads were dropped from the generator, they could not be synchronized to offsite power because non 1E busses 3E NAN 501 and 3E-NAN 502 were deenergized.
l Two of the RCPs had been manually shutdown. Loss of power to the non 1E busses shut down the other two. Also the condenser circulating water pumps, air Compressors, nuclear cooling water, and some Control room displays Were lost.
I The atmospheric dump valves malfunctioned for several reasons, one of which was l
directly related to the loss of IE power - no lighting in the area made the manual operation more difficult. One main steam safety valve opened lower than the TS limits. Normal pressurizer spray was unavailable because the RCps were not running. RCP IB seals were degraded when charging was secured. The MS!Y l
bypass valve could not be operated runotely.
Dresden 3 LER 89/001 03/25/89 10PS/ COMP / SCRAM / DUAL i
A 345 KV circuit breaker developed a phase-to-ground fault and tripped. Local breaker backup logic tripped additional breakers isolating busses 8 and 15 and l
de energizing the reserve auxiliary transformer (RAT) 32.
Bus 32, which was poweredfromRAT32,transferredtoRAT31in14 seconds (slowerthandesign).
I Bus 32 developed an undervoltage condition because of this and the 3B reactor r
feedpump tripped and reactor feedpum) 3A sped up to the point where runout flow control took control of the pump. Tie 3B recirculation pump also tripped and the 30 standby feedpump would not start until the 32 bus transfer was completed.
At that time, still in runout flow control mode, the 3C feedpump started and its flow increased rapidly until the high level trip setpoint was reached, whereupon the feedpump tripped and the turbine stop valves closed tripping the turbine and scramming the reactor.
Other problems were a loss of an annunciator panel - an alert level condition.
l a transfer of a low pressure coolant injection system motor control center failure of the isolation which should r.ot have occurred, spurious breaker trips, failure of a breaker to condenser supply valve to open, HPCI lube oil problems, remain closed. HPCI turning gear motor f ailure, security electronics problems, i
oxygen analyzer failure, and loss of instrunent air. Loss of instrunent air also affected unit 2.
South Texas 2 LER E9/009 04/05/89 10PS/ SCRAM / COMP /ESF j
On initial synchronization, with a jumper missing between two terminals of the generator baclup distance relay in the generator protection circuit causing an i
open circuit on the phase C current transformer of the protection circuit, the breaker pole failure relay actuated causing a generator lockout.
(Another l
wiring error in the protection circuit on the negative phase sequence relay would have also caused a generator lockout.)
Two 345 KV switchyard breakers, the generator circuit breaker, the generator i
exciter field breaker, the generator voltage regulator, the main turbine, and l
the 13.8 KV feeder breakers to auxiliary busses 2F, 2G, 2H, and 2J trisped as designed. The tie breaker to the 13.8 standby bus from the auxiliary sus 2F opened as designed deenergizing the bus and 4160 volt bus EPA.
h
- 11 The RCPs lost power on the loss of the auxiliary busses and the undervoltage coils (n their trip breakers generated a low flow signal to the solid state protection system which scramed the reactor. The digital rod position indicator sad lost power so all rods on bottom could not be verified and the RCS was borated.
The EDG for the energency bus started and loaded the emergency bus as expected.
When bus 2J was reenergized, RCP 2D restarted because its breaker failed to trip on loss of voltage. The additional flow caused a loss in S/G water level l
and an actuation of AFW, RCS teriperature was decreasing and the MSIVs were closed to prevent overcooling.
The non ESF balance-of plant diesel-generator could not be started in auto or l
manual. The Technical Support Center diesel generator was out of service for maintenance.
j hine Mile point 2 LER 89/014 04/13/89 SCRAM /10PS/ESF/ COMP A disconnected wire in the main gerierator potential transfoi w.sbicle caused a signal to be sent to the main generator )rotective circuitiy which generated a turbine trip.
The reactor scramed on tie turbine trip. Fast transfer to offsite power was only partially successful: one of the 13.8 KY busses failed i
to transfer.
This caused a loss of feedwater and subsequent reactor level reduction to level 2.
HPCS and RCIC actuated and injected. After water level reached norsel, HPCS and RCIC were shut down. Water continued to be injected into the vessel condensate booster pump could (pressure had been lowered to the point w from the feedwater lines. RCS anddid)injectwaterintothevesselthrougha failed-open valve.
Due to a series of personnel errors and equipment f ailures, the remaining 13.8 KV bus was deenergized momentarily. This tripped the operating condenser circulating water pump and the decrease in water box level prevented the immediate restart of the pump, in the face of falling condenser vacuum, the j
MSIVs were closed but auto-closure occurred before the manual closure could be accouplished.
The uninterruptible power supply to an instrument bus was interrupted causing loss of comunications in the control room and partial loss of emergency lighting. Water level was reported to have risen slightly above the lowest l
elevation of the main steam lines.
Oyster Creek LER 89/016 06/25/89 XfMR/ SCRAM /ESF s
A fault in one of the two main transformers caused the main generator to be I
tripped on a phase differential condition. Subsequently, the turbine tripped and the reactor sc*amed. Rapid closure of the turbine stop valves caused a reactor pressure spike to 1067 psig. The isolation condensers auto actuated.
two safety / relief valves lif ted, all five reactor recirculation pumps tripped, and the reactor water clean u s system tripped and isolated. All automatic 1
responses were expected for tiis transient. The cause of the transforner 1
L, failurs was sttributed to a failu m of an internal winding which caused the i
phase differential condition which cause the generator trip, f
Oyster Creek LER 89/017 L7/11/89 XFMR/ SCRAM The second of two a.ain transformers failed due to a failed internal winding which caused a phase differential condition on the main generator. The generator tripped, the turbine tripped, the reactor scramed, and all antici-l pated automatic responses occurred. Since this was the second main transforver the licensee initiated a study to determine the root cause i
failure in a month, failures.
of the transforser Surimer LER 89/012 07/11/89 10PS/ESF/ COMP Technicians working inside the generator stator cooling water cabinet shorted t
the power leads on the temperature converter causing tie AC power fuses to blow, giving a false indication of loss of stator cooling water. A turbine runback relay in the circuitry failed to operates instead, the turbine tripped and the reactor scrammed.
i Sumer was su sp1lring 860 megawatts of power to the grid at 440 megavolt-amperes, reactive (MVAO ;89.75 power factor). The McKeekin generating station and the Saluda hydro units (older units with their generator backup relays set below i
theutility'sstandard) tripped. The subsequent loss of voltage tripped the i
four fairfield Pumped Storage units whose backup relays were set at the utility's standard. The cascading failures caused a degraded voltage to be sensed by the ESF busses at Sumer.
I The ESF busses tripped on undervoltage and transferred to the EDGs as designed.
l Non.1E busses remained on the grid and equipment supplied from them experienced I
the degraded voltage.
[
i South Texas 2 LER 89/017 07/13/89 XfMR/ SCRAM /10PS/ESF/ COMP 1
An internal fault ocurred on the main transformer 2A causing the main transfor-i mer differential relay and the primary side allot wire differential relay to actuate the main transformer lockout relay wiich tripped the main generator i
breaker, the offsite power feeds from the switchyard, the auxiliary transforrer, and the main turbine. The reactor screwed on the turbine trip. Loss of the I
i auxiliary transferrer caused loss of one IE bus and the non-1E busses which L
supplied power to the RCPs. The 1E bus was loaded on its EDG. AFW initiated.
All responses to the incident were as expected, j
Events Involving Interruptions of Offsite Power; Twenty-four events in the first 6 nonths of 1989 were found involving an interruption of offsite power to the plant. These events are tabulated in i
Table 2 by plant, LER number, date, number and type of busses involved, and duration of the loss.
Note that the time begios at the loss of power and stops at its restoration.
"Available" power which is not used to energize busses is not considered in computing the duration of the incident.
4 13 -
a j
4 Table 2.
Interruptions of Offsite Power in 1989:
f Plant LER d Date Description Time Palo Verde 2 89/001 01/03/89 2 1E busses 21h8m l
South Texas 2 89/001 01/06/89 2 1E busses Not known Catawba 1 89/012 01/07/69 1 1E bus blackout
- 28m fernt 2 89/003 01/10/89 2 1E busses 20m l
ANO 1 89/002 01/20/89 1 non-1E bus Not known i
touth Texas ?
89/006 01/21/89 All non 1E, th53m train A 1E Pilgrim 89/010 02/21/89 All 15h45m Palo Verde 3 89/001 03/03/89 2 non-1E busses 30m/41m South Texas 2 89/005 03/20/89 2 1E busses 32m Dresden 3 89/001 03/25/89 All 6h35m/7h33m South Texas 2 89/009 04/05/89 4 non-1E, 1 Brief 1E busses i
Surry 1&2 89/010 04/06/89 1 1E,non-1E 4h5m i
bus es unit Surry 182 89/013 04/13/89 1 1E,non-1E 3h17e i
bus ea unit Nine Mile Pt 2 89/014 04/13/89 1 non-1E lost, Not known l
1 dropped North Anna 182 89/010 04/16/89 1 1E bus, each 40m/46m i
unit South Texas 2 89/014 04/18/89 1 1E bus 51m Millstone 1 89/012 04/22/89 All Brief WNP 2 89/016 05/14/89 2 1E busses 50m Millstone 2 89/009 05/23/89 1 1E bus Brief River Bend EN 15855 06/13/89 1 1E bus Not known
[
t l
River Bend EN 15858 06/13/89 2 non IE busses Not known
)
l Crystal River 3 EN 15886 06/16/89 All 1h6m Brunswick 2 EN 15895 06/17/89 All 9h45m Crystal River 3 EN 15986 06/29/89 All(and1E06)
Not known c
ANALYSIS l
i The issues eddressed by this study are disruptions of normal AC power as manifested by grid, switchyard, and non-1E electric systems (including the power generation system) problems and major electrical equipment failures.
The equipment whose failures caused these events (the 22 detailed in the Major I
Events of Interest, the 24 listed in Table 2, as well as the 57 in Appendix 1) were busses, circuit breakers, capacitors, potential transformers, switchgear, neutral grounding transformers, lightning arrestors stator exciterbrushes,forthemaingenerator,andmaintransformersaswellasthe cooling systems I
main turbine and the main generator.
1 Fires have been caused by the catastrophic failure of transformers and circuit breakt.rs, oil filled devices which have both fuel (oil) and ignition source (electricalfailure).
In other cases, the failure of devices such as switchgear
i 1
\\
t 14 -
and bus bars provide the ignition source with the fuel being provided by i
nearby combustible u terial sometimes the result of poor houseLeeping. The resu)ts of fire are often equipment damage and personnet hazard, j
A common factor to N ny of these events is maintenance. At Kewaunee and Palo l
Verde poor housekeeping contributed to the breakdown of the bus insulation and compilcatedtheevent. Maintenance errors at Catawba initiated and complicated the event. At Palo Verde, poor maintenance of emergency lighting complicated the recovery from the event by contributing to personnel error tiat caused a second fire. A piece of cardboard left in a relay from a previous maintenance l
st Braidwood complicated recovery from the event by tripping the RCPs and causing a scram.
Peach Bottom was vulnerable to tie problems they experienced because they were in an alignment for a maintenance outage.
i a bus i
The events at Kewaunee and Palo Verde 1 had virtually the same initiator,le; failure caused by insulation degradation complicated by dirt in the cubic j
yet consequences at Kewaunee were normal and expected, while the consequences j
at Palo Verde 1 were complicated by equipment failures, design errors, personnel errors, and >re existing plant conditions. AE00 has issued a report AEOD/E905,
- Electrical Sus Bar Failures,' based on these two events. An NRC information j
notice, IN 89-064, based on this report was also issued.
River Bend had two events on the list an exciter brush failure while prepara-tionsformaintenancewerebeingcompleted,andafaultonaneutralgrounding transformer caused by a stray cat grounding the high side of the transformer.
i The latter event led to a rather " normal" load rejection and scram while the former was complicated by a partial failure to transfer to offsite power several ESF actuations, and a coincidental, but potentially serious, backleakage i
from the reactor into the high pressure core spray lines.
i The Braidwood incident was caused by the failure of an off site potential transformer and affected both units on the site. General Design Criterion 17 (10 CFP, 50 Appendix A) calls for "two physically independent circuits...
i designed and located so as to minimize to the extent practical the likelihood l
of tieir simultaneous failure under operating and postulated accident and
- nvironmental conditions.' A common point is vulnerable to a failure that could cause simultaneous loss of more than one circuit.
Loss of offsite power is identified as the main contributor to risk of station blackout. The staff states in NUREG 1109, " Regulatory Backfit Analysis for the Resolution of Unresolved Safety Issue A-44. Station Blackout
- that 'the estimated frequency of core damage from station blackout events is directly pr@ortional to the frequency of the initiating event." Table 2, com)iled from all LERs and 10 CTR 50.72 reports made in 1989, lists the events in t1e first l
6 months of 1989 that have met parts of the blackout criteria (turbine trip or f
off-line, loss of offsite power to IE and non-1E busses, and unavailability of i
onsite tmergency AC power).
t Of the 24 events in Table 2, only one involved a IE bus blackout (a total loss of AC power) - a short duration event caused by a loss of offsite power to the bus with its EDG unavailable. Twenty events involved the loss of one or more 1E busses and 14 events involved the loss of one or nere non-1E busses. The I
l
c 4
5
- 16 duration of the avents ranged f rom momentary to 21 hours2.430556e-4 days <br />0.00583 hours <br />3.472222e-5 weeks <br />7.9905e-6 months <br />.
Four plants rGported eere than one evtnt. Three events involved both plants on the sitt, The 24 events involved 19 plants at 15 sites. The causes of the events are nearly equally divided between human error and electrical failure with weather being a e,inor contributor.
Six of the total events reviewed involved either total or partial interruptions of offsite power to the station auriliary power system because of problems with the 'f ast bus transfer" scheme, pelo Verde 1 - 07/06/68 River Bend - 08/25/68; Palo Verde 3 - 03/03/09; Dresden 3 - 03/25/89; Nine Nile Point 2 - 04/13/891 and South Texas 2 - 07/13/89, in all cases, the M Gs provided power to the plants' safety busses.
1he fast bus transfer schene is designed to permit the station's auxiliary electricloads(bothIEandnon-1E)tobecontinuedtobesuppliedfromoffsite following a generator / turbine power sources, the preferred source per CDC 17.ly transferring power to the trip with reactor scram. This is done by cuick various auxiliary busses from the UAT (connected to the generator) to the reserve or startup transfonner (connected directly to the switchyard).
The transfer is quick enough so that the associated busses and loads see virtually uninterrupted power supply.
Improving the reliable operation of this scheme the likelihood of simul-would, per GDC 17, ' minimize to the extent aractical teneous f ailure* of electrical power from t1e transmission network to the onsite distribution system.
The results of the loss of power to the 1E busses have in all but one case been the inmediate transfer to EDGs. ThelossofnonIEbusseshaveresulted in the loss of condenser circulating water pumps, consequent loss of condenser vacuum, and unavailability of the condenser as heat sinks the loss of one or more RCPs, subsequent reactor scram, and loss of forced circulation; and the loss of cooling water to air compressors and subsequent loss of service and instrunent air.
FINDINGS 1.
The enumerated events show that failures in electrical supply or power generation equipment impact safety equipment in that they often cause scrams or necessitate unit shutdown in operating plants, they cause ESF systems to operate.
they frequently cause interruptions in offsite power, they occasionally cause fires, and they complicate post-scram transients by rendering needed equipment unavailable or unreliable.
Table 3.
,$unenary of Findings Total 10PS fire Comp.
Detailed Events 22 13 6
18 Other Reports 57 20 1
31 Total 79 33 7
49
- - ~
w vw-m u
-_-------r----__---,----,------.-____u.---,-.-------
i e
l The comparison of the number of interruptions of offsite power in 1969 in i
Apptodix 1 (4) which was c(epiled by a variety of autcested searches to the nunter in Table 2 (24) which was comp 11td fr:n reading expanded titles of each l
LER shows that the scope of the problem to be even greater than Appendix 1 would suggest. Expanding that ides, it may be said that for each f ailure in i
electrical supply systems and power generator equipment found by computer i
searches, there may be several others not found.
i 2.
Interruptions of offsite power to 1E busses generally cause transfer of i
the busses to EDGs while interruptions of offsite power to non-1E busses cause scrams, loss of forced circulation, loss of heat sink, and loss of service and j
instrument air. from Table 2, it can be seen that several plants have multiple r
tvents and several events involve multiple units.
[:
3.
Seven fires occurred which damaged equipwent and caused complicated l
transients and involved exposure of personnel to fire and smoke.
l 4.
After a scram initiated by and coupled with electrical power problems, i
there may be a failure of the fast bus transfer scheme and a resultant complica-tion of the post scram transient in which the s W 1 and training of personnel; i
operation, and maintenance of many systems and components in, construction, b the aceutacy and completeness of procedurest and the design t
the plant can i
cialienged. As with every scram, additional duty cycles on the RCS pressufe boundary due to the cool oown and reh st also occur.
i 5.
a.
Several E5F actuations occurred as a consequence of the initiator, the normal actuations (expected to occur as a result of the transient caused by the j
initiator) were - EDG autostart and load, PCl$ actuations HPCI and RCIC injection, and AFW initiation.
b.
The abnormal actuations (not an expected response to the initiator, occurred as a result of equipment failure caused by the initiator in the ensuing transient) were EDGs manually started and loaded, emergency control room ventilation actuated, nitrogen backup for instrument air actuated, all area radiation monitors alarmed standby service water actuated, standby gas i
treatnent system actuated, annulus mixing system actuated HPCS and RCIC actuated, and AFW autostart.
I c.
Coincidental r.ouipment failures (occurring in the transient but not
[
caused by the initiator) include atmospheric steam dump malfunctions, valve i
position indicator malfunction, flashing in the letdtwn line, pressurizer 1tvel l
transient, malfunctioning letdown isolation valve, operator errors, failure to remotely operate of various devices, backleakage of RCS into HPCS, and other instrument malfunctions.
7 1
4 17 CONCLUSIONS Failures in electrical supply or power generation squipment impact safety toutp-sent. They often cause scrats or require unit shutdown, they may cause engineered safety features systems to operate, they frequently cause interruptions of offsite power supply to station auxiliaries, they occasionally cause fires, and they complicate post-scram operations by rendering equipment unavailable or unreliable.
Interruptions of offsite power to IE busses, while they are potential contribu-tors to the risk of a station blackout, generally cause transfer of the busses to EDGs while interruptions of offsite >ower to non 1E busses cause major plant transients and complicate scrams. Of t9e 24 events involving interruptions of offsite power supply, six were total losses of offsite power as considered in the blackout rule, but the remaining events are equally important.
Interruptions which are not recoverable from the off site power source due to either equipment or system failures lead to the same consequences as a station blackout due to a total loss of offsite power. Therefore, improvement in the c>eration and reliability of equipment such as EDGs, transformers, busses, switcigear, fast bus transfer scheme, etc. are necessary.
Furthermore, improvement of the reliability of the non 1E power supply and equipment has the potential of lessening the impact of problers with electrical supply on the safety systems by decreasing the number of scrams, ESF actuations, and cceplicated post-scram transients.
Pecent examples of failure in the fast bus transfer scheme point to the need to find the root cause of the failure and to make effective corrective actions so that the simultaneous failure of offsite power sources is truly minimized.
Failure of the fast bus transfer schere is being addressed in an on going AE00 study.
Fires are easier to prevent through surveillance and maintenance than to fight.
Fires occur when an electrical f6 ult ignites a fuel source. Personnel and equipment are at risk in fires.
Preventive maintenance and good housekeeping practices can minimize both ignition sources and fuel for fires.
The bus bar failures at Palo Verde 1 and Kewaunee were addressed in AEOD/E905,
' Electrical Bus Bar failures" at,d an NRC information notice, IN 89 064.
Transformer failurss which have occurred are being investigated in an on-going AEOD study.
The electrical maintenance surveillance, and procedural problems identified in this report should be uti1Ized in the development of the instructions to be used in the upcoming electrical team inspections being formulated by NRR.
' 't pga,,wij4e g/
+
L
,-' a q wgjiq
..l 0
l 18 4
i I
i o
i s
I
{
1 i
b t
i
(.-
I P-f e
c j-t; f'
l t
u.,.
d s
3 2
i h
t i
l t
'i
- ' e t
5 l
.I rd !%Y VN
y j
I t
e y :.
APPENDIX 1 i
b i
OTHER REPORTS INITIATOR DKT LER NO. DATE SCRAM 10PS FIRE WESF COMP LOSS OF EXCITATION 029 88/008 880517 A
P N
Y Y
LOAD REJECT 155 88/002 880307 M
Y N
Y Y
- GROUND FAULT ON BUS 219 88/022 881002 (SD)
N N
Y Y
l 0
LOW VOLTAGE 220 88/015 880725 A
N N
N N
BUS DEENERGlZED 237 88/021 881113 P
N Y
N m
10PS 245 89/012 890429 P
N N
N 4+
BUS DEENERGIZED
'259 88/045 881129 P
N Y
.N GENERATOR GROUND 265 88/001 880127 A
N N
Y Y
i TURBlhE VIBRATION 271 88/008 880719 A
N N
Y N
ANTI-MOTORING RELAY 275 88/026 880930 A
N N
N N
BREAKER FAILURE 280 89/005 890303 (SD)
P N
Y Y
LOSS OF EXCITATION 287 89/002 890306 A
N N
N Y
LOSS OF EXCITATION 295 W/011 880606 A
N N
N N
DEGRADED BUS 295 88/015 880813 (SD)
Y N
N N
l BREAKER FAILURE 296 8d/005 881108 (SD)
Y N
Y N
4 ARC IN IS0 PHASE BUS 298 88/019.880715 M
N N
Y N
TRANSFORNER FAILURE 301 89/0W E90329 A
P N
Y Y
l l
GRID PERTURBATIONS 309 89/003 890505 A
N N
N N
. FAULTED MAIN XFMR 309 88/006 Ct'0819 A.
Y N
Y Y
PHASE VOLT IMBALANCE 312 88/015 8E1014 A
N N
Y Y
GENERATOR-8ND 321 88/003 880226 A
N N
N Y
LINE FAULT 322 88/016 081011 (SD)
N N
Y N
i LOAD REJECTION 323 89/005 890416 A
N N
N Y
l
'LIGHINING STRIKE 328 88/034 880815 N
D Y
Y Y
l.
TURBINE VIBRATION 331 88/008 880724 A
N N
N N
110PS 333 88/011 881031 Y
N Y
Y l
10PS 336 88/005 880304.
Y N
7 Y
LOSS OF VACUUM 338 88/002 880203 M
N N
Y Y
DUAL UNIT 10PS 338 89/010 890416 (SD)
Y N
Y Y
GROUND fat lLT ON XFMR 341 88/019 880606 M
P N
Y Y
l '
TUREINE VIBRATION 341 88/030 680912 A
N N
N Y
XfMR FAULT 358 88/021 880906 A
N N
Y N
LOSS OF EXCITATION 369 88/001 880107 A
N N
Y Y
' LOAD REJECT 387 88/006 880304 A
N N
N N
GP,00ND FAULT, L1NE 387 88/010 880618 A
N N
N N
L LOAD REJECT 410 88/012 880305 A
N N
Y Y
MAIN XFMR FAllLT 416 88/002 880110 A
N N
N Y
GEN FIELD GND 424 88/006 880215 A
N N
Y N
HIGH STATOR COOLING 424 68/008 880407 A
N N
Y Y
OVEREXCITATION 424 88/022 880808 A
N N
Y N
L, FAULT ON DISCONNECT 424 88/024 880730 A
N N
N N
LOSS OF STATOR COOLING 425 89/018 890422 N
N N
N Y
' TUP.BINE TRID H0 88/026 880623 A
N N
N N
10PS 443 88/004 880810 (SD)
Y N
Y N
GRID INSTABILITY 454 88/005 880804 A
N N
Y Y
i
P~.
e f
i C.
' l,,.
.p.
o APPENDIX 1(CONT.)
l OTHER REPORTS INITIATOR DKT LER NO. DATE SCRAM 10PS FIRE #ESF COMP 1
BUS DEF.NERG1 ZED 455 88/008 880714 A
N N
Y Y
GENERATOR LOCK 0UT 457 88/012 880620 A
N N
Y N
i LOSS STATOR COOL 458 88/003 880128 A
N N
N Y
XfMR FAULT 458 88/005 880314 M
P N
Y N
t PARTIAL 10PS 498 88/026 880330 A
P N
Y Y
STATOR COOLING LOW 498 88/049 880826 A
N N
Y Y
10PS 499 89/005 890320 N
P N
Y N
GEN PROT CIRCUIT ACT 499 89/014 890418 (SD}
N N
N N
10PS 528 88/003 880216 (SD)
Y N
Y Y
LOAD REJECT 528 88/011 880419 A
N N
N Y
LOW STATOR COOLING 528 88/021 880821 A
N N
N Y
10PS 530 88/004 880505 N
Y N
Y N
- n I
(,
b\\'
KEY:
SCRAM - A AUY0MATIC 10PS - P PARTIAL M MANUAL T TOTAL (SD) SHUTDOWN D DUAL UNIT
~
1
',,t
,J,,,',
' '