ML20012G667

From kanterella
Jump to navigation Jump to search
Semiannual Effluent Release Rept for Jul-Dec 1992
ML20012G667
Person / Time
Site: Oyster Creek
Issue date: 12/31/1992
From:
GENERAL PUBLIC UTILITIES CORP.
To:
Shared Package
ML20012G668 List:
References
NUDOCS 9303110274
Download: ML20012G667 (41)


Text

,

EXECUTIVE

SUMMARY

.1992-2 SEMI-ANNUAL RELEASE REPORT i

The Semiannual Effluent Release Report is submitted to the United States Nuclear i

Regulatory Commission (NRC) every six months in accordance with the Oyster Cmek f

Nuclear Generating Station (OCNGS) Technical Specifications (Tech Specs). It Summarizes the radioactive gaseous and liquid effluents released and solid radioactive wastes shipped from the OCNGS. In addition, meteorological data are presented in joint frequency tables per atmospheric stability class.

Attached Tables show that doses based on quantities of radioactive material released were all less than 1 % of the limits allowed by the OCNGS Tech Specs. Limits for the release of radioactive effluents at OCNGS are based upon offsite exposure to members of the general-public. These limits were compared to dose projections calculated using the methodology in the Offsite Dose Calculation Manual (ODCM). There were no liquid releases from OCNGS

.l during the period. Solid waste shipments were similar to those of nuclear plants of comparable type, age and size. Concrete was used for solidiGeation material during the reponing period. The report summarizes the fact that all effluents mleased were within j

federal regulatory requirements of the OCNGS Technical Speci6 cations.

l t

i A summary of Oyster Creek's meteorological data is provided in tabular fonn. Also included is a description of changes made t the Offsite Dose Calculation Manual (ODCM) and the Pmeess Control Plan (PCP) during the reporting period. Ef0uent monitoring instruments that were inoperative as per Technical Specification 3.15 for the reporting period i

a e also discussed.

j i

aanw c.oug 9303110274 930226

{DR ADOCK 05000219 PDR

4 4

i e

i Maximum Offsite Dose Due to Radionuclides in Eff tuents July-Dec.1992 Tech. Spec.

3.6.J.1 3.6.J.1 3.6.L.1 3.6.L.1 3.6.K.1 3.6.M.1 3.6.K.1 i

Liquid Dose Air Dose (Gas)

Whole (Thyroid)

WB Organ Beta Garmaa Body Organ Skin mrem mrem mree mrem arem mrom arem JULY-DEC. Total 0.00E+00 0.00E+00 1.45E-03 2.74E-03 2.21E 03 2.13E-02 2.36E-03 Tech. Spec. Limit 3

10 20 10 500 15 3000 f raction of Limit 0.00E+00 0.00E+00 7.25E-05 2.74E-04 4.42E-061.42E-03 7.85E 07 Tech. Spec. Ref.

3.6.N.1 3.6.N.1 Whole (thyroid)

Body Organ mrem arem 1992 total 6.32E-03 2.47E-01 Tech. Spec. Limit 25 75 Fraction of 2.53E-04 3.30E-03 Annual Limit f

k

+

1 7

{

i

o Effluent and Waste Disposal Supplemental Information FACILITY:

Oyster Creek Nuclear Generating Station i

L.lCENSEE: Owner - Jersey Central Power and Light Company Operator - GPU Nuclear Corporation 1.) Regulatory Limits a.) Fission and Activation Gases Technical Specification 3.6.E.1 llic gross radioactivity in noble gases discharged from the main condenser air ejector shan not exceed a 0.21/E Ci/sec after the holdup line,where E is the average ganuna energy (Meu per atomic transfonnation).

i Technical Specification 3.6.K.1 i

The dose equivalent rate outside of the EXCLUSION AREA due to radioactive l

noble gas in gaseous effluent shall not exceed 500 mrem / year to the total body or 3000 mrem / year to the skin.

i Technical Specification 3.6.L1 The air dose outside of the EXCLUSION AREA due to noble gas released in gaseous effluent shall not etcced:

l 5 mrad / calendar quaner due to ganuna radiation, i

10 mrad / calendar quarter due to beta radiation, i

10 mrad /calendaryear due to ganuna radiation, or.

f 20 mrad /calendaryear due to beta radiation i

Technical Specification 3.6.N.1 i

The annual dose to a MEMBER OF THE PUBLIC due to radiation ' and radioactive material in effluents from thc OCNGS outside of the EXCl.U510N AREA shah not exceed 75 nuem to his thyroid or 25 mrem to his total body or to miy ather organ.

f

P e

i

b. Iodines and Particulates Technical Specification 3.6.K.2 77:e dose equivalent rate outside of the EXCLUSION AREA due to 11-3, 1 131, 1-133, and to radioactive materialin particulates havhtg half-lives of S days or more in gaseous effluents shall not etceed 1500 miem/ year to any body organ when the dose rate due to 11-3, Sr-89, Sr-90, and alpha-emitting radionuclides is averaged over no i

more than 3 months and the dose rate due to other radionuclides is averaged over no more than 31 days.

t Technical Specification 3.6.M.1 The dose to a MEMBER OF THE PUBLICfrom iodine-131, iodine-133, andfrom radionuclides in particulate fonn having half-lives of S days or more in gaseous effluents, outside of the EXCLUSION AREA shall not exceed 7.5 mrem to any body organ per calendar quarter or 15 mrem to any body organ per calendaryear.

c. Liquid Effluents h

Technical Specification 3.6.I.1 The concentration ofradioactive material, other than noble gases, in liquid effluent l

in the discharge canal at the Route 9 bridge shall not crceed the concentrations Specified in 10 CFR Part 20, Appendit B, Table H, Column 2.

Technical Specification 3.6.I.2 l

The concentration of noble gases dissolved or entrained in liquid effluent in the discharge canal at the Route 9 bridge shall not crceed 2X10-4 microcuries/ milliliter.

.i TechnicalSpecification 3.6J.2 l

The dose to a MEMBER OF THE PUBLIC due to radioactive niaterial in liquid effluents l>cyond the outside of the EXCLUSION AREA shall not esteed:

l.5 nuem to the total body during any calendar quarter, 5 miem to any body organ during any calendar quarter, 3 nuem to the total body dming any calendaryear, or 10 mrem to any body organ during any calendaryear.

I 2.) Maxiinum Perrnissible Concentrations (MI'C) f i

I

y a.

Fission and Activation Gases:

Appendix B, Table II, Column 2 of 10 CFR 20 b.

Iodines and Particulates:

Appendix B, Table II, Column 2 of 10 CFR 20 c.

Liquid Effluents:

Appendix B, Table II, Column 2 of 10 CFR 20, except for dissolved or entrained noble gases where the limit is 2 x 104 uCi/mi 3.) Measurements and Approximation of Total Radioactivity f

a.

Fission and Activation Gases:

l

1. Stack l

The continuous recording of gross activity and the incorporation of isetopic data obtained from a weekly grab sample analyzed using gamma l

spectroscopy.

1

2. Augmented Offgas (AOG) Vent j
I The continuous recording of gross activity and the incorporation of isotopic data obtained from a weekly grab sample analyzed' using gamma spectroscopy.

-]

3. Turbine Building Stack and Feedpump Room Vent The continuous recording of gross activity and the mcorporation of isotopic. ~

1 s

data obtained from a monthly grab sample analyzed using gamma l

spectroscopy.

b.

Iodines

'!q

1. Stack 1

Filters are changed twice weekly and analyzed using gamma spect roscopy.

2.~AOG Vent i

Filters are changed twice weekly and analyzed using gamma spectroscopy.

q

6 r

t

3. Turbine lluilding Stack and Feedpump Room Vent j

i I

Filters are changed twice weekly and analyzed using gamma spectroscopy.

l c.

Particulates I

i

1. Stack l

f Filters are changed twice weekly and analyzed using a low background beta counter and gamma spectroscopy.

j

2. AOG Vent I

.i Filters are changed twice weekly and analyzed using gamma spectroscopy.

3. Turbine lluilding Stack and Feedpump Room Vent j

i Filters are changed twice weekly and analyzed using ganuna spectroscopy.

l 1

1 d.

Liquid Effluents j

Analysis per batch release using gamma spectrometry with a germanium l

detector, a low background beta counter, and a liquid scintillation counter.'

'l l

e i

f i

i

.i 1

i t

f l

I I

h

OYSTER CREEK NUCLEAR GENERATING STATION GASEOUS EFFLUENT ELEVATED RELEASES l

Third Quarter 1992 l

FISSION GASES QUANTITY (ci )

l KR85M 9.81E+00 KR87 7.21E+00 KR88 1.02E+01 XE133 5.35E+01 XE135 1.66E+01 Total Fission Gases Released: 9.73E+01 ci j

Gamma EBar:

0.347 Mev Average Rate of Release:

1.22E+01 uCi/sec IODINES QUANTITY (ci )

I131 4.34E-03 1132 8.22E-03 I133 1.54E-02 I134 7.72E-03 I135 1.48E-02 Total Iodines Released:

5.04E-02 ci Average Rate of Release:

6.35E-03 uCi/sec PARTICULATES glr.NTITY(ci )

NA24 2.44E-03 CR51 9.98E-05 MN54 1.69E-05 l

C058 5.34E-06 CO60 1.11E-04 RB89 4.51E-01 SR89 6.73E-04 SR90 3.66E-06 SR91 2.76E-03 SR92 4.60E-04 Y91M 1.74E-01 Y92 1.76E-04 i

TC99M 2.58E-03 RU106 8.58E-05 TE132 1.06E-05 CS137 3.91E-06 CS138 1.92E+00 BA139 7.93E-01 j

BA140 4.58E-04 LA140 5.20E-04 GROSSA 1.15E-05 Total Particulates Released:

3.35E+00 ci Average Rate of Release:

4.22E-01 uCi/ sec RADIONUCLIDE QUANTITY (ci )

H3 2.80E+00 Avg. Rate of Release for H3:

3.52E-01 uCi/sec Quantity of noble gases derived from gross activity.

i OYSTER CREEK NUCLEAR GENERATING STATION GASEOUS EFFLUENT GROUND-LEVEL RELEASES Third Quarter 1992 FISSION GASES QUANTITY (ci )

KR85M 5.64E-04 KR87 5.64E-04 KR88 5.64E-04 XE133 1.22E-02 XE135M 8.32E-03 XE135 6.24E-03 XE138 1.28E-03 Total Fission Gases Released: 2.97E-02 ci Average Rate of Release:

3.74E-03 uCi/sec IODINES QUANTITY (ci-)

I131 4.16E-05 I133 3.77E-04 Total Iodines Released:

4.18E-04 ci Average Rate of Release:

5.26E-05 uCi/sec PARTICULATES QUANTITY (ci )

NA24 6.88E-06 CR51 3.19E-06 I

SR89 8.67E-06 Y91M-1.08E-03 TC99M 2.81E-05 CS138 9.00E-03 BA139 7.27E-03 CE141 6.94E-07 CE143 2.21E-06 Total Particulates Released:

1.74E-02 ci Average Rate of Release:

2.19E-03 uCi/sec RADIONUCLIDE QUANTITY (ci )

H3 0.00E+00 i

Avg. Rate of Release for H3:

0.00E+00 uCi/sec i

  • Quantity of noble gases derived from gross activity.

l t

OYSTER CREEK NUCLEAR GENERATING STATION GASEOUS EFFLUENT ELEVATED RELEASES Fourth Quarter 1992 FISSION GASES QUANTITY (ci )

XE133 4.51E+01 XE135 6.18E+01 Total Fission Gases Released: 1.07E+02 ci Gamma EBar:

0.162 MeV Average Rate of Release:

1.34E+01 uCi/sec IODINES QUANTITY (ci )

I131 1.91E-03 1132 5.57E-03 1133 9.36E-03 1134 7.65E-03 I135 1.03E-02 Total Iodines Released:

3.48E-02 ci Average Rate of Release:

4.38E-03 uCi/sec l

1 PARTICULATES QUANTITY (ci )

NA24 8.63E-04 CRS1 8.47E-04 i

MN54 1.01E-05 j

CO60 1.32E-04 RB89 1.99E-01 SRB 9 4.09E-04 SR90 3.79E-06 SR91 2.99E-03 SR92 1.12E-03 Y91M 1.29E-01 TC99M 4.46E-03 TE132 4.72E-06 CS138 1.57E+00 BA139 5.73E-01 BA140 3.09E-04 LA140 1.34E-04 GROSSA 3.50E-05 Total Particulates Released:

2.48E+00 ci Average Rate of Release:

3.12E-01 uCi/sec RADIONUCLIDE QUANTITY (ci )

H3 3.01E+00 Avg. Rate of Release for H3:

3.79E-01 uCi/sec

  • Quantity of noble gases derived from gross activity.

OYSTER CREEK NUCLEAR GENERATING STATION GASEOUS EFFLUENT GROUND-LEVEL RELEASES Fourth-Quarter 1992 FISSION GASES QUANTITY (ci )

KR85M 4.71E-03 KR87 4.71E-03 KR88 4.71E-03 XE133 1.02E-01 e

XE135M 6.94E-02 XE135 1.20E-01 XE138 1.07E-02 Total Fission Gases Released: 3.16E-01 ci j

Average Rate of Release:

3.97E-02 uCi/sec r

IODINES QUANTITY (ci )

i 1131 6.44E-05 I133 1.12E-04 Total Iodines Released:

1.76E-04 ci I

Average Rate of Release:

2.21E-05 uCi/sec PARTICULATES QUANTITY (ci )

CR51 4.99E-04 MN54 5.85E-06 CO60 5.35E-05 SR89 1.10E-05 SR90 1.16E-05 Y91M 9.44E-03 i

TC99M 8.81E-06 RU103 2.90E-06 CS138 5.69E-03 l'

BA139 4.77E-03 CE141 4.32E-07 Total Particulates Released:

2.05E-02 ci Average Rate of Release:

2.58E-03 uC1/sec RADIONUCLIDE QUANTITY (ci )

H3 0.00E+00 Avg. Rate of Release for H3:

0.00E+00 uC1/sec l

  • Quantity of noble gases derived from gross activity.

r t

4

OYSTER CREEK NUCLEAR GENERATING STATION LIQUID EFFLUENT RELEASES Third and Fourth Quarters 1992 Oyster Creek Nuclear Generating Station policy is to strive for zero liquid discharge of radioactive material.

As a result, there were no liquid continuous or batch releases from OCNGS in the second half of 1992.

4 Solid Waste Shipped Offsite for Disposal t

During Period from 07/1/92 to 12/31/92 Report Date 2/1/93 WASTE STREAM: DRY ACTIVE WASTE WASTE VOLUME CURIES

% ERROR (C1)

CLASS SHIPPED 3

3 Ft M

1 A

180.1 5.1 8.80 25%

E-01 B

0 0

0 25%

j C

0 0

0 25%

All 180.1 5.1 8.80 25%

E-01 r

L 2551.WAC

Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM: DRY ACTIVE WASTE With 1% Cutoff Waste Nuclide Percent Class Name Abundance Curies A

Fe-55 50.673%

4.46 E-1 Co-60 34.426%

3.03 E-1 Cs-137 9.123%

8.03 E-2 Mn-54 2.500%

2.20 E-2 Cs-134 1.852%

1.63 E-2 Cr-51 1.318%

1.16 E-2 H-3

.105%

9.28 E-4 C-14

.002%

1.79 E-5 Cm-242 0

0 Pu-241 0

0 I-129 0

0 Tc-99 0

0 Sr 00 0

0 Nb '

0 0

Ni-oo 0

0 Ni-59 0

0 l

1 I

l l

l l

l 2551.WAC

--J

i Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM: DRY ACTIVE WASTE With 1% Cutoff Waste.

Nuclide Percent Class Name Abundance Curies All Fe-55 50.673%

4.46 E-1 Co-60 34.426%

3.03 E-1 Cs-137 9.123%

8.03 E-2 Mn-54 2.500%

2.20 E-2

^

Cs-134 1.852%

1.63 E-2 Cr-51 1.318%

1.16 E-2 H-3 0.105%

9.28 E-4 C-14 0.002%

1.79 E-5 Cm-242 0

0 Pu-241 0

0 1-129 0

0 Tc-99 0

0 Sr-90 0

0 Hb-94 0

0 Hi-63 0

0 Ni-59 0

0 h

1 I

2551.WAC i

l 1

Solid Waste Shipped Offsite for Disposal During Period From 07/1/92 to 12/31/92 1

Report Date 2/1/93 l

1 l

l i

l WASTE STREAM: OTHER WASTE l

WASTE VOLUME CURIES

% ERROR (Ci)

CLASS SHIPPED l

3 3

Ft M

1 A

0 0

0 25%

l B

0 0

0 25%

C 0

0 0

25%

All 0

0 0

25%

l l

l l

l l

l 2551.WAC 1

s Solid Waste Shipped Offsite for Disposal During Period 07/01/92 to 12/31/92 i

Report Date 2/1/93 WASTE STREAM: RESINS. FILTERS. & EVAP. BOTTOMS Waste Volume Curies

% Error (Ci)

Class Shipped 3

3 Ft M

A 3812.1 107.9 3.28 E+2 25%

B 788.2 22.3 1.21 E+2 25%

C 0

0 0

25%

All 4600.3 130.2 4.49 E+2 25%

i i

(

l l

2551.WAC i

l Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM: RESINS. FILTERS. & EVAP. BOTTOMS i

With 1% Cutoff Waste Nuclide Percent Class Name Abundance Curies f

5 A

Co-60 43.360%

1.42 E+2 Fe-55 32.508%

1.07 E+2-Mn-54 8.807%

2.89 E+1 Cr 5.600%

1.84 E0 Cs-137 4.016%

1.32 E+1 00-58 2.313%

7.58 EO Cs-134 1.124%

3.69 E0 i

Ni-63 0.335%

1.10 EO I

Pu-241 0.032%

1.04 E-1

(

Sr-90 0.027%

8.86 E-2 5

Ni-59 0.016%

5.33 E-2 C-14 0.009%

2.85 E-2 H-3 0.002%

7.94 E-3 e

Cm-242 0

5.14 E-4 I-129 0

0 Tc-99 0

0 Nb-94 0

0 j

I 2551.WAC

4 4

Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM: RESINS. FILTERS. & EVAP. BOTTOMS v

With 1% Cutoff Waste Nuclide Percent Class Name Abundance Curies-B Cs-137 38.251%

4.63 E+1 Fe-55 26.096%

3.16 E+1 Co-60 24.175%

2.92 E+1 Cs-134 3.469%

4.19 EO Mn-54 2.723%

3.29 E0 Sr-90 1.939%

2.34 E0 Sr-89 1.499%

1.81 EO Ni-63 0.248%

3.00 E-1 Pu-241 0.160%

1.93 E-2 C-14 0.046%

5.61 E-2 Ni-59 0.016%

1.90 E-2 H-3 0.003%

3.97 E-3 Cm-242 0.001%

6.11 E-4 1-129 0

0 Tc-99 0

0 Nb-94 0

0 i

e I

i

}

i 2551.WAC I

i

^

O Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM: RESINS. FILTERS. & EVAP. BOTTOMS With 1% Cutoff Waste Nuclide Percent Class Name Abundance Curies All Co-60 38.192%

1.71 E+2 Fe-55 30.781%

1.38 E+2

'I Cs-137 13.239%

5.94 E+1 Mn-54 7.168%

3.22 E+1 Cr-51 4.260%

1.91 E+1 C0-58 1.770%

7.95 E0 Cs-134 1.756%

7.88 E0 Sr-90 0.542%

2.43 E0 Ni-63 0.312%

1.40 E0 i

l Pu-241 0.066%

2.97 E-1 l

C-14 0.019%

8.'46 E-2 Ni-59 0.016%

7.23 E-2 H-3 0.003%

1.19 E-2 Cm-242 0

1.13 E-3 I-129.

0 0

Tc-99 0

0 Nb-94 0

0 2551.WAC

Solid Waste Shipped Offsite for Disposal During Period from 07/1/92 to 12/31/92 Report Date 2/1/93 WASTE STREAM:

IRRADIATED HARDWARE WASTE VOLUME CURIES

% ERROR (Ci)

CLASS SHIPPED 3

3 Ft M

A 728.4 20.61 7.53 25%

B 0

0 0

25%

C 78.6 2.22 23990 25%

All 807 22.83 23997.53 25%

8 2

i Estimates of Major Nuclides by. Waste Class and Stream WASTE STREAM:

IRRADIATED HAR0 WARE Waste Nuclide Percent Ran Name Abundance Curies A

Co-60 45.2 3.40 Fe-55 43.5 3.28 Co-58 5.4

.41 Mn-54 3.5

.26 Ni-63 1.3

.10 Fe-59

.9

.07 Cr-51

.1

.008 Cs-137

.1

.008 Pu-241

.1

.008 H-3 0

0 C-14 0

0 Tc-99 0

0 I-129 0

0 Sr-90 0

0 Ce-144 0

0 Pu-238 0

0 Pu-239/40 0

0 Am-241 0

0 Cm-242 0

0 Cm-243/44 0

0

J Estimates-of Major Nuclides by Waste Class and Stream i

WASTE STREAM:

IRRADIATED HARDWARE-Waste Nuclide Percent Class Hame Abundance Curies C

Fe-55 47.7%

1.17 E4 Co-60 43.9%

1.05 E4 i

Ni-63 5.2%

1.20 E3 Mn-54 2.9%

6.35 E2 Cr-51 0.1%

1.13 El Ni-59 0

7.75 E0 Nb-94 0

2.05 E-2 i

H-3 0

2.24 E-2 C-14 0

1.96 E0 Tc-99 0

1.13 E-2 1-129 N.P.

N.P.

Np-237 0

1.20 E-7 Pu-238 0

7.81 E-4 Pu-239/40 0

1.71 E-6 Pu-241 0

-2.14 E-4 Pu-242 0

1.38 E-9 Am-241 0

4.50 E-7 Am-243 0

1.41 E-8 i

Cm-242 0

4.00 E-5 Cm-243/44 0

4.60 E-6 i

I Solid Waste Shipped Offsite for Disposal During Period 07/01/92 to 12/31/92 Report Date 2/1/93 WASTE STREAM:

FILTERS (FROM SPENT FUEL POOL PROJECT)

Waste Volume Curies

% Error (Ci)

Class Shipped 3

3 Ft M

A 0

0 0

25%

B 361 10.21 2.94 E2 25%

C 0

0 0

25%

All 361 10.21 2.94 E2 25%

fl0TE: One shipment also contained Irradiated Hardware (Velocity Limiters from Control Rod Blades).

I

i Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM:

FILTERS (FROM SPENT FUEL POOL PROJECT)

Waste Nuclide Percent Class Name Abundance Curies B

Co-60 44.60 1.31 E2 Fe-55 46.94 1.38 E2 Mn-54 4.10 1.20 El Cs-137 1.57 4.62 E0 Cs-134

.60 1.77 E0 C0-58

.40 1.15 E0 Ni-63 1.62 4.75 E0 C-14 0

4.35 E-2 Sr-90 0

1.51 E-2 Ce-144 0

8.85 E-3 Sr-89 0

1.47 E-2 Pu-238 0

1.50 E-4 Pu-239/40 0

9.67 E-5 Pu-241 0

6.98 E-3 Am-241 0

1.34 E-4 Cm-242 0

1.70 E-4 i

Cm-243/44 0

1,67 E-4 H-3 0

4.02 E-5

.i i

"l i

Solid Waste Shipped Offsite for Disposal During Period From 07/1/92 to 12/31/92 t

Report Date 2/1/93 l

l WASTE STREAM: SUM OF ALL CATEGORIES t

i WASTE VOLUME Cud!ES

% ERROR (Ci)

CLASS SHIPT'ED 3

3 Ft M

i A

4720.6 133.61 336.53 25%

f B

1149.2 32.51 415.00 25%

C 78.6 2.22 23990.00 25%

All 5948.4 168.34 24741.53 25%

t NOTE:

Does'not include waste shipped to S.E.G.

t t

a b

f L

s

t Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM:

SUM OF ALL EXCEPT D.A.W. TO S.E.G.

Waste Nuclide Percent Class Name Abundance Curies A

Co-60 44.03%

1.45 E+2 Fe-55 33.40%

1.10 E+2 Mn-54 8.87%

2.92 E+1 Cr-51 5.62%

1.85 E+1 Cs-137 4.04%

1.33 E+1 Co-58 2.43%

7.99 Cs-134 1.12%

3.70 i

Ni-637 0.36%

1.20 Pu-241 0.03%

1.12 E-1 Sr-90 0.03%

8.86 E-2 Ni-59 0.02%

5.33 E-2 C-14 0.01%

2.85 E-2 H-3 0

8.87 E-3 Cm-242 0

5.14 E-4 1-129 0

0 Tc-99 0

0 Nb-94 0

0 fe-59 0.20%

7.00 E-2 3.293 E2 i

[

A

Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM: SUM OF ALL WASTE STREAMS i

Waste Nuclide Percent Class Name a undance Curies B

CS-137 12.30%

5.09 El Fe-55 41.20%

1.70 E2 Co-60 38.70%

1.60 E2 Cs-134 1.44%

5.96 Mn-54 3.70%

1.53 El Sr-90 0.57%

2.36 Sr-89 0.44%

1.82 Ni-63 1.22%

5.05 Pu-241 0.05%

2.00 E-1 C-14 0.02%

9.96 E-2 Ni-59 0

1.90 E-2 H-3 0

4.01 E-3 Cm-242 0

7.81 E-4 Co-58 0

1.15 Ce-144 0

8.85 E-3 Pu-238 0

1.50 E-4 Pu-239/40 0

9.67 E-5 Am-241 0

1.34 E-4 Cm-243/44 0

1.67 E-4 Tc-99 0

0 Nb-94 0

0 I-129 0

0 4

l l

t Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM:

SUM OF ALL WASTE STREAMS Waste Nuclide Percent Class Name Abundance Curies C

Fe-55 47.7%

1.17 E4 Co-60 43.9%

1.05 E4 Ni-63 5.2%

1.20 E3 Mn-54 2.9%

6.35 E2 Cr-51 0.1%

1.13 El Ni-59 0

7.75 E0 Nb-94 0

2.05 E-2 H-3 0

2.24 E-2 C-14 0

1.96 E0 Tc-99 0

1.13 E-2 I-129 0

0 Np-237 0

1.20 E-7 Pu-238 0

7.81 E-4 Pu-239/40 0

1.71 E-6 Pu-241 0

2.14 E-4 Pu-242 0

1.38 E-9 Am-241 0

4.50 E-7 Am-243 0

1.41 E-8 Cm-242 0

4.00 E-5 Cm-243/44 0

4.60 E-6 j

i i

t

)

Estimates of Major Nuclides by Waste Class and Stream WASTE STREAM: SUM OF ALL WASTE STREAMS Waste Nuclide Percent Class Name Abundance Curies All Fe-55 48.310%

1.198 E4 Co-60 43.550%

1.080 E4 Ni-63 4.880%

1.210 E3 Mn-54 2.740%

6.800 E2 Cs-137 0.260%

6.420 El Cr-51 0.120%

2.980 El Co-58 0.040%

9.140 Cs-134 0.040%

9.660 Sr-90 0.010%

2.450 C-14 0.008%

2.090 Pu-241 0.001%

3.120 E-1 Hi-59 0.030%

7.820 Nb-94 0

2.050 E-2 H-3 0

3.530 E-2 Tc-99 0

1.130 E-2 1-129 0

0 Np-237 0

1.200 E-7 Pu-238 0

9.310 E-4 Pu-239/40 0

9.840 E-5 i

Pu-242 0

0 Am-241 0

1.350 E-4 Cm-242 0

1.340 E-3 Fe-59 0

7.000 E-2 Cm-243/44 0

1.720 E-4 J

3

+

j s

-Regulatory Guide 1.21 Report Solid Waste Shipped Offsite for Disposal 7/1/92 to 12/31/92 P

Waste Type Cubic Meters Curies

% Error (Cl) l SEG 331.45 m 2.71 25% Class A-u 3

3 Volume buried by S.E.G. - 23.93 m - Beatty, NV Activity buried by S.E.G. - 1.93 Curies

~i Waste Tvoe Nuclide

% Abundance Curies Waste Shipped Fe-55 50.70%

1.37 to SEG Co-60 34.40%

.93 Cs-137 9.08%

.25 Mn-54 2.49%-

.07 Cs-134 1.84%

.05 Cr-51 1.31%

.04 H-3 0%

0 C-14 0%

0 Tc-99 0%

0 t

1-129 0%

0 Pu-241 0%

0 Cm-242 0%

0 Ni-63 0%

0 Sr-90 0%

0 t

i Number of Mode of Shipments Transportation Destination 7

Truck Oak Ridge, TN--

i l

2549WAC.

l l

b P

.l.-

Solid Waste Shipped Offsite for Disposal 7/1/92 to 12/31/92 i

-i Waste Tyne Cubic Meters Curies

% Error (CI)'

3 Metals 78 14 m 1.32 25% Class A-u.

3 Volume buried by Alaron - 9.10 m - Barnwell, SC Activity buried by Alaron = 1.143 Ci i

1 Waste Tvoe Nuclide

% Abundance Curies Metals Shipped Fe-55 50.70%

.670 to Alaron Co-60 34.40%

.450 l

Cs-137-9.08%

.120 i

Mn-54 2.49%

.033 i

Cs-134 1.84%

.024 i

Cr-51 1.31%

.017 H-3 0%

0 C-14 0%

0 Tc-99 0%-

0 I-129 0%

0-l Pu-241 0%

0 1

Cm-242 0%

0 Ni-63' 0%

0 Sr-90 0%

0 l

i Humber of Mode of j

Shioments Transportation Destination 4

Truck Wampum, PA 2549.WAC l

SOLID WASTE DISPOSITION

SUMMARY

NUMBER OF SHIPMENTS MODE OF TRANSPORTATION DESTINATION

?

35 Truck Barnwell, SC O

Truck Richland,-WA O

Truck Beatty, NV 7

Truck Oak Ridge, TN 4

Truck Wampum,_PA t

I k

t L

t i

f r

t 4

2549.WAC

i OYSTER CREEK 33 FOOT GROUND LEVEL RELEASE DATA JOINT FREQUENCY TABLES i

Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class:A HOURS AT WIND SPEED AND DIRECTION i

WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S O

20 19 0

0 0

39 NNE SSW 2

17 11 0

0 0

30 NE SW 0

29 44 6

0 0

79

+

ENE WSW 1

36 88 6

0 0

131 E

W O

54 75 1

0 0

130 ESE WNW 0

54 37 0

0 0

91 SE NW 1

24 78 1

0 0

104 SSE NNW 0

12 60 16 0

0 88 S

N 1

13 51 70 1

0 136 SSW NNE 1

7 22 20 0

0 50 i

SW NE 1

14 23 11 0

0 49 WSW ENE O

22 45 12 0

0 79 W

E 1

22 56 16 0

0 95 WNW ESE O

20 101 26 0

0 147 NW SE 1

16 111 45 1

0 174 NNW SSE O

24 51 11 0

0 86 TOTAL 9

384 872 241 2

0 1508 Period of Record 01/01/92 00000 TO 12/31/92 02300 l

Stability Class:B HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 1

14 5

0 0

0 20 NNE SSW 0

6 2

0 0

0 8

NE SW 0

20 13 2

0 0

35 ENE WSW 0

19 18 2

0 0

39 E

W 0

23 9

0 0

0 32 ESE WNW 0

10 8

0 0

0 18 SE NW Or 13 10 0

0 0

23 SSE NRW 1

9 24 1

0 0

35 S

N O

11 28 7

1 0

47 SSW NNE O

13 16 4

0 0

33 SW NE O

11 12 1

0 0

24 WSW ENE 1

16 12 2

0 0

31 W

E O

12 16 6

0 0

34 WNW ESE 2

10 31 12 0

0 55 NW SE 1

25 26 8

1 0

61 NNW SSE 2

28 8

1 1

0 40 TOTAL 8

240 238 46 3

0 535

+

P

[

i OYSTER CREEK 33 FOOT GROUND LEVEL RELEASE DATA JOINT FREQUENCY TABLES I

Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class:C HOURS AT WIND SPEED AND DIRECTION j

WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 15-24

>24 TOTAL i

N S

0 10 0

0 0

0 10 NNE 6SW 1

7 0

0 0

0 8

NE SW 0

12 4

0 0

0 16 ENE WSW 1

15 7

0 0

0 23 E

W 0

12 3

0 0

0 15 ESE WNW 0

9 6

0 0

0 15 h-SE NW 0

9 7

0 0

0 16 SSE NNW 1

7 6

1 0

0 15 S

N 0

7 9

4 0

0 20 SSW NNE 1

2 11 8

1 0

23 SW NE 1

6 0

2 0

0 9

WSW ENE 1

7 1

0 0

0 9

W 0

12 12 5

0 0

29 WNW JO 1

7 5

2 0

0 15 NW Sh 0

9 12 2

1 0

24 l

NNW SSE O

10 6

1 0

0 17 TOTAL 7

141 89 25 2

0 264 i

Period of Record 01/01/92-@0000 TO 12/31/92 02300 St. ability Class:D i

HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 20 62 24 5

0 0

111 NNE SSW 24 77 45 4

0 0

150 NE SW 29 125 102 17 0

0 273 ENE WSW r7 103 83 15 2

0 220 E

W 10 65 58 7

1 0

141 ESE WNW 4

62 38 10 1

0 115 SE NW 8

65 31 2

0 0

106 i

SSE NNW 10 39 39 17 2

0 107 S

N 11 66 93 21 4

2 197 SSW NNE 11 64 90 20 1

1 187 SW NE 7

37 34 4

1 0

83

~

WSW ENE 14 46 45 3

0 0

108 i

W E

10 44 25 19 1

0 99 WNW ESE 12 49 68 21 0

0 150 NW SE 18 58 62 30 1

0 169 NNW SSE 14 66 30 2

0 0

112

?

TOTAL 219 1028 867 197 14 3

2328 i

i i

--t

, e OYSTER CREEK 33 FOOT GROUND LEVEL RELEASE DATA JOINT FREQUENCY TABLES Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class:E HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 J 12 13-18 19-24

>24 TOTAL N

S 26 36 7

0 0

0 69 NNE SSW 29 30 9

0 0

0 68 NE SW 25 40 8

4 0-0 77 ENE WSW 20 32 7

4 2

0 65 E

W 22 55 9

0 6

3 95 ESE inni 15 21 14 9

0 0

59 SE NW 17 34 12 4

1 0

68 SSE NNW 20 30 18 9

1 0

78 S

N 32 56 32 5

1 1

127 SSW NNE 26 107 68 20 3

0 224 SW NE 36 144 52 2

0 0

234 WSW ENE 56 154 29 1

0 0

240 W

E 41 138 8

3 0

0 190 WNW ESE 43 135 82 6

0 0

266 NW SE 40 130 42 3

0 0

215 NNW SSE 37 100 16 0

0 0

153 TOTAL 485 1242 413 70 14 4

2228 Period of Record 01/01/92 00000 TO 12/31/92 @2300 Stability Class:P HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOT.*L r

N S

12 7

0 0

0 0

19 NNE SSW 16 0

0 0

0 0

16 NE SW 5

4 0

0 0

0 9

ENE WSW 2

4 0

0 0

0 6

E W

2 2

0 0

0 0

4 ESE WNW 2

3 0

0 0

0 5

SE NW 5

1 0

0 0

0 6-SSE NNW 9

4 0

0 0

0 13 S

N 13 6

2 0

0 0

21 SSW NNE 25 16 0

0 0

0 41 SW NE 18 62 5

0 0

0 85 WSW ENE 56 82 2

0 0

0 140 i

W E

52 53 0

0 0

0 105 WNW ESE 29 39 2

1 0

0 71 l

IN SE 34 29 1

0 0

0 64 NNW SSE 44 28 0

1 0

0 73 TOTAL 324 340 12 2

0-0 678 j

l 7

i

  • A t

l 4

l OYSTER CREEK 33 FOOT GROUND LEVEL RELEASE DATA JOINT FREQUENCY TABLES Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class:G HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 S-12 13-18 19-24

>24 TOTAL N

S 20 3

0 0

0 0

23 NNE SSW 7

1 0

0 0

0 8

NE SW 6

1 0

0 0

0 7

ENE WSW 5

0 0

0 0

0 5

E W

4 1

0 0

0 0

5 ESE WNW 4

1 0

0 0

0 5

SE NW 3

2 0

0 0

0 5

SSE NNW 9

4 0

0 0

0 13 S

N 15 4

0 0

0 0

19 SSW NNE 24 7

0 0

0 0

31 l

SW NE 59 28 0

0 0

0 87 WSW ENE 202 100 0

0 0

0 302 W

E 248 80 1

1 0

0 330 i

WNW ESE 109 13 0

1 0

0 123 NW SE 123 19 0

0 0

0 142 NNW SSE 57 41 0

0 0

0 98 TOTAL 895 305 1

2 0

0 1203 Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class:ALL HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS l

TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 79 152 55 5

0 0

291 NNE SSW 79 138 67 4

0 0

288 NE SW 65 231 171 29 0

0 496 i

ENE WSW 46 209 203 27 4

0 489 E

W 38 212 154 8

7 3

422 ESE WNW 25 160 103 19 1

0

-308 SE NW 34 148 138 7

1 0

328 j

SSE NNW 50 105 147 44 3

0 349 l

S N

72 163 215 107 7

3 567 i

SSW NNE 88 216 207 72 5

1

-589 SW NE 122 302 126 20 1

0 571 i

WSW ENE 330 427 134 18 0

0 909 W

E 352 361 118 50 1

0 882 WNW ESE 196 273 289 69 0

0 827 i

NW SE 217 286 254 88 4

0 849 i

NNW SSE 154 297 111 16 1

0 579' TOTAL 1947-3680 2492 583 35 7

8744 i

HOURS OF MISSING / INVALID DATA:

40 i

i

' ~

OYSTER CREEK 380 FOOT ELEVATED RELEASE DATA JOINT FREQUENCY TABLES Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class: A HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S O

1 0

0 0

0 1

NNE SSW 0

1 0

0 0

0 1

NE SW 0

1 0

5 3

0 9

ENE WSW 0

0 3

20 7

1 31 E

W 0

1 6

7 1

0 15 ESE WNW 0

1 4

0 0

0 5

SE NW O

O 4

0 0

0 4

SSE NNW 0

0 0

3 2

0 5

S M

0 0

0 5

8 1

14 SSW NNE O

O 2

1 0

0 3

SW NE O

1 0

0 0

0 1

WSW ENE O

1 1

5 2

4 13 W

E O

O 1

1 6

2 10 WNW ESE O

O 1

2 16 13 32 NW SE O

O 1

11 16 9

37 NNW SSE O

O 1

3 6

1 11 TOTAL 0

7 24 63 67 31 192 Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class: B HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 0

0 4

2 1

0 7

NNE SSW 0

0 0

1 2

0 3

NE SW 0

1 5

11 5

2 24 ENE WSW 0

0 13 11 3

1 28 E

W 0

1 17 7

0 0

25 ESE WNW 0

1 11 0

0 0

12 SE NW 0

0 14 5

0 0

19 SSE NNW 0

0 4

14 0

0 18 S

N O

1 2

11 11 2

27 SSW NNE O

1 1

2 3

3 10 SW NE O

O 4

2 1

0 7

WSW ENE O

2 2

3 9

4 20 W

E O

O 2

5 9

3 19 WNW ESE O

O 5

11 7

3 26 NW SE O

O 2

9 17 14 42 NNW SSE O

O 2

8 4

1 15 TOTAL 0

7 88 102 72 33 302

' O OYSTER CREEK 380 FOOT ELEVATED RELEASE DATA JOINT FREQUENCY TABLES Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class: C HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 0

1 2

7 1

0 11 NNE SSW 0

1 3

1 0

0 5

NE SW 0

2 12 10 3

3 30 ENE WSW 0

1 23 12 4

2 42 E

W 0

11 20 6

0 0

37 ESE WNW 0

3 23 1

0 0

27 SE NW 0

0 14 4

0 0

18 SSE NNW 0

2 11 13 0

0 26 1

S N

O O

11 34 13 2

60 SSW NNE O

2 5

14 4

1 26 SW NE O

1 4

10 5

2 22 WSW ENE O

4 14 17 7

3 45 W

E 1

2 16 13 10 4

46 WNW ESE O

1 12 21 20 13 67 NW SE O

O 14 23 19 16 72 NNW SSE O

1 12 13 4

2 32 TOTAL 1

32 196 199 90 48 566 Period of Record 01/01/92 J00 TO 12/31/92 02300 Stability Class: D HOURS AT WIND SPEED AND L' ECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 2

29 52 43 15 6

147 NNE SSW 5

40 67 61 8

5 186 4

NE SW 4

30 101 85 72 54 346 ENE WSW 5

30 83 107 65 52 342 E

W 4

31 89 86 31 9

250 ESE WNW 6

40 86 32 16 16 196 SE NW 4

28 64 26 10 3

135 SSE NNW 6

24 81 47 13 12 183 S

N 2

17 79 98 28 17 241 SSW NNE 4

23 51 149 55 33-315 SW NE 3

18 45 34 24 4

128 WSW ElH3 6

16 49 51 31 9

162 W

E' 2

25 42 51 23 39 182 WNW ESE 2

14 48 75 79 70 288 NW SE 1

28 57 91 86 93 356 NNW SSE 3

18 50 67 31 13 182 i

TOTAL 59 411 1044 1103 587 435 3639 I

i b

.]

l i

o

~

~'

OYSTER CREEK 380 FOOT ELEVATED RELEASE DATA JOINT FREQUENCY TABLES Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class: E HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 3

14 20 52 15 3

107 NNE SSW 3

11 22 20 0

0 56 NE SW 6

11 24 28 7

8 84 ENE WSW 8

6 19 23 13 20 89 E

W 2

7 18 20 15 14 76 ESE WNW 5

16 7

22 11 5

66 SE NW 5

7 19 24 15 11 81 SSE NNW 1

10 22 18 31 20 102 S

N 3

22 40 39 26 12 142 SSW NNE 5

10 45 114 74 32 280 SW NE O

2 28 73 81 24 208 WSW ENE 1

11 30 63 73 14 192 W

E 2

6 22 69 37 5

141 l

WNW ESE 2

5 27 83 92 11 220 NW SE O

8 24 98 97 11 238 NNW SSE 2

3 21 53 61 11 151 TOTAL 48 149 388 799 648 201 2233 Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class: F HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 1

9 11 38 30 1

90 NNE SSW 0

5 5

16 5

0 31 NE SW 0

11 8

13 0

0 32 ENE WSW 2

1 2

9 1

0 15 E

W 3

1 1

4 1

0 10 ESE WNW 1

6 5

2 0

0 14 SE NW 3

2 6

3 0

0 14 SSE NNW 1

5 9

7 1

0 23 S

N 2

11 14 20 2

0 49 SSW NNE O

8 15 21 6

1 51 SW NE 3

8 30 31 48 22 142 WSW ENE 2

7 14 39 53 21 136 W

E O

15 14 45 32 8

114 WNW ESE O

7 22 41 43 14 127 NW SE 2

5 18 39 52 13 129 NNW SSE 1

11 11 32 19 4

78 TOTAL 21 112 185 360 293 84 1055 l

[

L

a o

. OYSTER CREEK 380 FOOT ELEVATED RELEASE DATA JOINT FREQUENCY TABLES Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class: G HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 3

4 15 16 8

0 46 NNE SSW 1

12 20 17 3

0 53 NE SW 1

11 21 20 1

0 54 ENE WSW 0

5 9

3 0

0 17 E

W 0

6 6

1 0

0 13 ESE WNW 1

5 9

2 0

0 17 SE NW 0

3 11 3

0 0

17 SSE NNW 2

7 3

2 1

0 15 S

N 3

4 16 11 2

0 36 SSW NNE 2

15 11 18 2

1 49 SW NE 10 14 14 20 9

5 72 WSW ENE 3

5 28 26 14 5

81 W

E 6

8 19 18 9

6 66 WNW ESE 3

8 33 25 9

2 80 NW SE 3

13 17 39 8

1 81 NNW SSE 6

7 15 20 6

2 56 TOTAL 44 127 247 241 72 22 753 Period of Record 01/01/92 00000 TO 12/31/92 02300 Stability Class: ALL HOURS AT WIND SPEED AND DIRECTION WIND SPEED SECTOR WINDS TO FROM 1-3 4-7 8-12 13-18 19-24

>24 TOTAL N

S 9

58 104 158 70 10 409 NNE SSW 9

70 117 116 18 5

335 NE SW 11 67 171 172 91 67 579 ENE WSW 15 43 152 185 93 76 564 E

W 9

58 157 131 48 23 426 ESE WNW 13 72 145 SP 27 21 337 SE NW 12 40 132 65 25 14 288 SSE NNW 10 48 130 104 48 32 372 S

N 10 55 162 218 90 34 569 SSW NNE 11 59 130 319 144 71 734 SW NE 16 44 125 170 168 57 580 WSW ENE 12 46 138 204 189 60 649 7

W E

11 56 116 202 126 67 578 7

WNW ESE 7

35 148 258 266 126 840 NW SE 6

54 133 310 295 157 955 NNW SSE 12 40 112 196.

131 34 525 TOTAL 173 845 2172 2867 1829 854 8740 HOURS OF MISSING / INVALID DATA :

44

.l r

i

.+

(

Oyster Creek Nuclear Station 1992-2 Semi Annual Effluent Report Changes to the Offsite Dose Calculation Manual:

-l No changes were made to tne ODCM during this time period.

r Changes to the Process Control Plan:

The Process Control Plan procedure for Transfer, Solidification, and Dewatering of Solid Wet Waste was modified in October. Valving procedures already used per operator experience but not explicitly l

specified in the procedure are now identified and controlled by a valve check off.

i Effluent Monitors Out of Service Greater than 30 Days:

During the second half of 1992 three instruments were out of service for longer than 30. days:

1 The Overboard Discharge Monitor was long out of service and was being refurbished during July and August. The instrument was placed l

into service in August. No overboard discharges occurred during the period from July through August when the instrument was out of service.

The Service Water Rad. Monitor was not declared operable as a result of repeated failures, air binding and biological fouling.

The monitor is being evaluated for return to service.

Daily discharge samples are collected as required while the monitor is out of service.

i The AOG vent monitor was out of service from November until the end of the reporting period due to sample tubing leakage. Tubing repair is scheduled.

i h

.6 u

i

.