05000311/LER-1981-079, Forwards LER 81-079/03L-0.Detailed Event Analysis Encl

From kanterella
(Redirected from ML20010E675)
Jump to navigation Jump to search
Forwards LER 81-079/03L-0.Detailed Event Analysis Encl
ML20010E675
Person / Time
Site: Salem 
Issue date: 08/26/1981
From: Midura H
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20010E676 List:
References
NUDOCS 8109080135
Download: ML20010E675 (3)


LER-1981-079, Forwards LER 81-079/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
3111981079R00 - NRC Website

text

I O PSEG Public Service Electric and Gas Company P.O. Box 168 Hancocks Bridge, New Jersey 08038 Salem Generating Station August 26, 1981 Mr. Boyce H.

Grier Y,\\g' / a Director of USNRC

/

Office of Inspection and Enforcement gs

'/

Region 1 Q

"q 631 Park Avenue g#

King of Prussia, Pennsylvania 19406 Z_ @

gN

};

Dear Mr. Grier:

. N 9,5-("

LICENSE NO. DPR-75 s

00CKET NO. 50-311

' "l y",

REPORTABLE OCCURRENCE 81-79/03L Pursuant to the requirements of Salem Generating Station Unit No. 2 Technical Specifications, Section 6.9.1.9.b, we are submitting Licensee Event Report for Reportable Occurrence 81-79/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, dh H.

J. Midura Manager -

Salem Generating Station CC:

R. A.

Uderitz General Manager - Nuclear Production Director, Office of Inspection yhN and Enforcement (30 copies)

I Director, Office of Management Information and Program Control (3 copies)

/ ['

8109080135 810826 PDR ADOCK 05000311 95 2t89 (12.59311 eo S

PDR i

N _.

Report Number:

81-79/03L Report Date:

8-26-81 Occurrence Date:

8-3-81 Facility:

Salem Generating Station, Unit 2 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Electrical Distribution System -- No. 22 CSD Breaker - Unidentified Trip.

This report was initiated by Incident Report 81-301.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - Rx Power 75% - Unit Load 760 MWe DESCRIPTION OF OCCURRENCE:

On August 3, 1981, No. 22 CSD breaker tripped from an unidentified

cause

There were no indicating flags showing on the relays.

No. 21 CSD breaker was closed. manually.

Action statement 3.8.2.1.a was entered at 1533 hours0.0177 days <br />0.426 hours <br />0.00253 weeks <br />5.833065e-4 months <br />, August 3, 1981.

This occurrence constituted operation in a degraded mode in accord-ance with technical specification 6.9.1.9.b.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

The cause of this breaker trip, and previously reported ones, is still uadetermin;d.

It is suspected that the cause of this is in the safe-guards equipment cabinet (SEC).

As was previously stated, all possible trouble areas are being thoroughly investigated.

ANALYSIS OF OCCURRENCE:

Technical specificati - 1 8.2.1.a requires:

With less than the stated complement of A.C. busses operable or energized, restore the inoperable busses to operable and energized status within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or be in at least hot standby within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in cold shutdown within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

_]

LER 81-79/03L *

CORRECTIVE ACTION

The cause of the breaker trip is still under investigation.

The immediate corrective action was to manually close the No. 21 CSD breaker.

At 1542 hours0.0178 days <br />0.428 hours <br />0.00255 weeks <br />5.86731e-4 months <br />, August 3, 1981, action statement 3.8,2.1.a was terminated.

A supplemental report will be issued when the investigation is completed.

FAILURE DATA:

Not Applicable Prepared By F.

Dickey

/

'y Ews Manager - S61emiGenerating Station SORC Meeting No.

81-82

_)