/03L-0:on 810717,main Control Board Steam Flow Indicator of FT-474 Instrumentation Loop Failed High.Caused by Transmitter Vent Pipe Break Due to Use of Oversized Valve in Sensing Line.Lighter Valve Installed
ML20010D218
Person / Time
Site: Farley 
Issue date: 08/18/1981
From: Hairston W
ALABAMA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20010D212 List:
References
LER-81-028-03L-01, LER-81-28-3L-1, NUDOCS 8108240106
Download: ML20010D218 (1)


LER-1981-028, /03L-0:on 810717,main Control Board Steam Flow Indicator of FT-474 Instrumentation Loop Failed High.Caused by Transmitter Vent Pipe Break Due to Use of Oversized Valve in Sensing Line.Lighter Valve Installed
Event date:
Report date:
3641981028R03 - NRC Website

text

uL,umec a um nuun, ccNTRa' stoc<: l 1

I l

l I

'h (PLEASE PRINT OR TYFE ALL REQUIRED INTCRMATICN)

I

!c l i j l A l L l J I M l F l 2 l@L 01 01 -! 01 O ! 01010 l - ! 0 l 0 !@l 4 ! l l 1 11 l l@l I

l m:@

4 9 u a:,sEEcenE i4 ts uCe,sar. m ca a

s u c c.st n gE

.o 37 3y [_[@[ 0 ! 510 l 01 0 ! 3 ! 614 '@l 017 l 1 17 18 11_.'@(o0 l 8 !1 1 8 IR I 1!@

3 o

si e c c.< : T,;.. m

a n

ee.TouE RecaT ouE a

2 Event o scmPHON AND PRCEA3LE COS.SicuENcES h [3 12j l At 0610 on 7-17-81, the instrumentation loop associated with steam flow transmitter I

j c,3 ; ; FT-474 was declared inoperable when the main control board steam flow indicator failed l

, high due to breakage of a transmitter vent pipe. Tech. spec. 3.3.1 and 3.3.2, in part, j

g,,

uire FT-474 to be operable.

'ech. Spec. action statement requirements were met.

l 10 i = i.

r Health / safety of the public was not affu ted.

Ic is i !

_.J i l l

l0 t 7

12;3 i

I 1

3 ?

60 SY 3 TEM

CAUSE

CALSE COv P.

VALvt C:.,C E CCOE SUECODE COv7CNENT CODE SU3CCOE SUSCCOE laivi l Tl Al@ 18 l@ ! A l@ l Z l Z !Z IZ IZ l Z l @ l Z l @ [ L.j @

3 9

30 11 13 13 20 SE OU ENT:AL CC:.U R R E N C E RECORT REVISION

_ EVENT YE AR

E*CR T T.O.

0002 TYPE N O.

@ *=te p. q g18I11 11 1012181 1/!

l 0! 31 iL I l-!

LD_}

m ai

      • L:i 2:
4 2s 27
s
3 a

ai 22 A:T::N go UaE EF=ECT s u :c.v.

2rrAcwENT pa c-4 rRiuCCc a.

OceacNENT OL 3 *.u r-~ E O 80Rt1 M.0.

SUPPLIER YANLFACTURER T A*'. i N ACT:CN CN FLA?.T MET-*';O HOURS l A!@l Z l@

l Z l@

iZ!@

l 0101010 l

((L @

l N!@

lZ!@

lZ l 9 I 919 l(

l

.2 a

.2 2,

40

,i n

43 u

47 cAusE cercmPacN Ana ccer,... ;E Acr: ass @

!i i o i !The use of an oversized valve in a sensing line which had higher than expected vibration j

[i i ! contributed to the fatigue failure of the line. Following installation of a lighter valve & 1 g,, _ ; ; satisfactory completion of the surveillance test, the FT-474 instrumentation -loop was returnqd

! i: i Lto service at 2210 on 7-19-81. All similar instrumentatior, vent lines were also insoected I

and valves replaced. No such similar condition exists in Unit 1 since the heavier valve was [iiai l selected for use in Unit 2 because of an error on a vendor drawing.

j i

a a e3 5

  • 80ZER OT'-* E R 2T/.TUS 15 0 'hRY CISCOVEnv OE!C;1?PT;CN l 15i l E l(3) i 11. 0 1. 0 l(v l NA l

l A j6hl Operator Observation v

3 I

v 7

s 9

?O 12 11 44 45

- 4 63 AC T:Vf TY CONTENT q

h AEL ASED Oc3,ELI? E Av0gN OF CTtviTY LC0ATION CF RELEASE NA l

l NA

_ _}

U i6 I l Zl @ lZ !@l J

3 J

?O Ii 44 45 80

  1. EMO*.N E r. E UC0# E 5 p

OES mP*1CN h NLYEER TYPE l i i, j l 0 I 0 10 r@! z j@'

NA l

3 3 11

?:

1; 30 DE A SONN E L INr.;Pi:3 p

O EIC w TI O?.6 NU'i E R 1313! 10 10 10 l@l NA l

7 J

t1 12 60 LCSS OF CF Oav AC E TD ;A;;urv A T fPE

  • EC mPnCN h

_l [ITT} l Z l@l NA i

d

'J to 30

've uC: ry

',5U E Qn 3 E SC a' P TIC'J.

nnc ($5 CNLY 1.L 8109240106 810819 NA I

!IIIi!!I IIIfI; gDRADOCK05000

.rer W. G. Hairston, III Phone:

(205) 891-5156 l