05000321/LER-1980-092-03, /03L-0:on 800731,while at Steady State Power, Cooling Water to LPCI Inverter Room Cooler Was Isolated Resulting in High Ambient Temp in Inverter Room.Caused by High Ambient Temp Causing B Loop of RHR to Be Inoperable

From kanterella
(Redirected from ML19344E655)
Jump to navigation Jump to search
/03L-0:on 800731,while at Steady State Power, Cooling Water to LPCI Inverter Room Cooler Was Isolated Resulting in High Ambient Temp in Inverter Room.Caused by High Ambient Temp Causing B Loop of RHR to Be Inoperable
ML19344E655
Person / Time
Site: Hatch 
Issue date: 08/29/1980
From: Coggin C
GEORGIA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19344E651 List:
References
LER-80-092-03L-01, LER-80-92-3L-1, NUDOCS 8009020414
Download: ML19344E655 (2)


LER-1980-092, /03L-0:on 800731,while at Steady State Power, Cooling Water to LPCI Inverter Room Cooler Was Isolated Resulting in High Ambient Temp in Inverter Room.Caused by High Ambient Temp Causing B Loop of RHR to Be Inoperable
Event date:
Report date:
3211980092R03 - NRC Website

text

~

Nuc ronta acs

' u.s. nuCtrAn occutAToRY COf.1MISSloN (7 77)

LICENSEE EVENT REPORT V cornnc'.otock: I I

l l

l l

l@

(PLEASE PRINT OH TYPE ALL REQUIDED INrOHMATION) s b

Io l1l LG l A l E l I l H l 1 l@l 0 l 0 l-l 0 l0 l 0 l 0 l 0 l-1010 l@l4 l1 l1 l1 l1 j@l I _] @

7 8 W LICENSt[ CODE 14 lb LICLN'.L NUMutH

/b 2b LICLNSL TYPE JG bi L Al bd con'T I l'1 Si% LLJ@l 0151010_10131211_J@l 0171311 I n 10_]@l 01 a l 2191 a l o l@

i 8

00 61 DOCKET NUMBE H

(.B b)

LVENT oATL 74 iS HL POf 4 T ()A I E lid EVEfJT DESCHIPTiou AND PROD ADLE CONSEcuCNCES h 10171IWhile_at steady state power the coo _ ling water to the LPCI inverter room i lcooler was isolated resulting in a high ambient temperature in the in-1 O 3 l0l4lIverter room.

The B LPCI inverter tripped making B loop of RHR inop; I

Isince the inverter supplies power to LPCI injection valve E11-F015B and 1 o s IRilR pump min flow bypass valve E11-F007B.

There was no effect on the 1

0 c l0 l71 l remaining Unit 1 & 2 inverters despite their being in the same room.

I i o ir71 IThere ~were no ef fects upon public heal th and safety.

I

~

'$E"

  • ^TE SO^CiSE Su'aiEoc SEE'oE C

CO CorsONtNTCOo:

I E l Oj @ l Lj @ I A l @ l G l E l N IE l R l A l@ LF_J @ [ Zl @

o o 7

8 9

la 18 12 13 13 l'>

20 SE QUEN TI AL OCCURRENCE REFORT fiEVISION LE R EVENT YE AR REPORT NO.

CODE TYPE NO.

O ago/RO 18 10 I l-l 10 l<; 12 I l/l 1013 l lL l

[-j [0_J g

N 21 22 23 24 26 21 28

'9 30 31 31 4

T KL 0

'ONPLANT ET O HOUHS S B iT O FO F bub.

SU PLIE mat t r CTUHrft LLJ@l 21@

IZl@

LzJ@

I01010101 l Yl@

l N l@

l Al@

l El 3l 5l 5l@

3J 34

)

30 3/

40 41 42 43 44 47 CAUSE oESCRIPTioN AND CORRECTIVE ACTIONS h li101IThe LPCI inverter tripped due to high amb. temp. causina B loop of RHR I

.lililIto'be inop.

Tech Specs 3.9.A.6/3.9.B.6 was performed, cooling water wasl Irestored to the inverter room cooler, and inverter was reenergized.

I i 2 i a IThis is a' recurring event - R0 80-82.

Inverter rm. chillers are being l

li i4 i l instal 1ed to al1eviate this prob 1em. Investigation should be complete by 12-1-801 7

8 9 80 STA S

% POWE R OTHERSTATUS IS O IY DISCOVERY DESCFtIPTION L'_.l.sJ LcJ@ l 01 9I al@l NA l

[JJ@l Operator Observation

}

COkTENT A TlVITY RE LE ASE OF HELEASE AMOUNT OF ACTIVITY LOCATION OF RELEASE LIJ l.z.J@l NA l

1 NA l.

1 6 PEnsONNEt expos 5I<ES oESCniPnO~ @ -

~UuoEn im i 01010 l@LIJ@l NA I

i 7

' PtnSONNa'imVi?iES oESCniPuO~@

i NuvoEn l01010!@l NA l

l t n l 3 8 9.

11 12 80 l

'mo' 'afST,^, YON '^c'""'@

[Z_J@l NA l

1 9 l7 8 9 10 80 ihsSUEt@DESCniPTION l

NA l

llIl11llllll12 2 o l'

8 0 090 2 04/f

" 'I t

{iE or PI tE PAR EH E-'!.Coggin. Supt. Plt. Eno. Serv.

pngg.912-367-7781 1

NA

LER #:

50-321/1980-092 Licenrce:

Georgia Power Company Facility Name:

Edwin 1.

llatch Docket #:

50-321

Narrative

Report for LER 50-321/1980-092 On 7-31-80, the cooling water to the LPCI inverter room cooler was i s o l a t. e d resulting in a high ambient temperature in the inverter room.

The "B"

LPCI inverLer R44-S003 tripped due to this high tempercture causing "B"

loop of RlIR to become inop since this inverter supplies power to the LPCI injection valve E11-F015B and the RilR pump

' minimum flow bypass valve Ell-F007B.

The LPCI inverters for both Units 1

and 2 are located in the same room;

however, the cooling water was restored to the inverter room cooler before any of the other inverters were affected by the high temperature in the inverter room.

This is a

recurring prob 1cm with the same event occurring on 7-11-80, and reported by.RO

  1. 80-82.

Inverter room chillers are presently being installed and are expected to be operational by 12-1-80.

The unit is now in full compliance with the requirements, and no further r e p o r t i~ug is required.