05000254/LER-1980-022-03, /03L-0:on 800903,during Calibr Surveillance,Temp Switch TS 1-2371A Tripped at 212 F Rather than 200 F.Caused by Setpoint Drift.Switch Replaced

From kanterella
(Redirected from ML19338F086)
Jump to navigation Jump to search
/03L-0:on 800903,during Calibr Surveillance,Temp Switch TS 1-2371A Tripped at 212 F Rather than 200 F.Caused by Setpoint Drift.Switch Replaced
ML19338F086
Person / Time
Site: Quad Cities 
Issue date: 09/22/1980
From: Steffes C
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19338F078 List:
References
LER-80-022-03L-02, LER-80-22-3L-2, NUDOCS 8010070509
Download: ML19338F086 (1)


LER-1980-022, /03L-0:on 800903,during Calibr Surveillance,Temp Switch TS 1-2371A Tripped at 212 F Rather than 200 F.Caused by Setpoint Drift.Switch Replaced
Event date:
Report date:
2541980022R03 - NRC Website

text

5m. < wn

.ww (7 771, LICENSEE EVENT REPORT CONTROL BLOCA: l l

l l

l l

lh (PLEAss PRINT OR TYPE ALL REQUIRED INFORMATION) t 6

I'dTil l'il Ll a l A l 0 l 1 l@l 0 l 0 l 0 l - l 0 l 0 l 0 l-l0 l0 10 @l4l1l1l1l1l@l l

l@

7 8 9 LICENSEE COOE 14 15 LICENSE NupeER 2h 26 LICENSE TYP4 Jo 57 CAT 64 con *f IOTil O' "J l L i@l 015101010 l 2 I s 14 l@l 01910111 a l c l@l 019 l 2 l 2 l 810 l@

7 8

60 41 OOCK ET NUMggR 64 69 EVENT D ATE 74 76 REPOR T O ATE 80 EVENT OESCRIPTION AND PROBABLE CONSEQUENCES h 10 l 2 l l While performing HPCI Turbine Area High Te,riperature Calibration Surveillance Ql5 l

0 gl 27-l, temperature switch TS 1-2371A was found to trip above 212 F.

Technical l

gl Specification 3.2.1. specifies the trip setpoint to be less than 2000F. The 1

m i redundant switches would have initiated a HPCl isolation had the need arisen.

l gl Therefore, the consequences of this occurrence are minimal.

l 10171 l

__I 10181I l

80 7

ss susS"OOE sEYeE SOCE

  1. Y seE$5E CouPONENT CODE COO E

I S I F l@ l E l@

l,,[_,j h l I l N l S I T I R l U l@

l,5,, j@

l,, Z,,j @

7 8

9 10 ti 12 13 18 19 20 SEQUENTIAL OCCURRENCE REPORT REVISION LE R EVENT YEAR CEPORT NO.

COCE TvPE NO.

@ sug/RO I810 I l-l 10 I2 12 I lel 10 13 I It I L-j l0J at

,,,. 21 22 23 24 26 27 IS 23 31 32 K N A C

ONPL NT MT HOUR $' 22

$8 l POR S.

SUPPLIE MAN PAC RER IAl@ W @

W@

J@

l0l01010l W@

l Y l@

y@

lUl017l5l@

JJ J4 JS 06 31 4

41 4I e

u 47 CAUSE OESCRIPTION AND CORRECTIVE ACTIONS h li loi l The failure of TS 1-2371A was instrument setpoint drift. The temoerature switch I

8'l was replaced and tested satisfactorily on September 5. 1980.

I t

7 l I

8 mI I

uLi]I 1

80 7

8 P 5A $

% POWER OTHER STATUS 01 RY OISCOVERY OESCRIPTION li is ] lH l@ 10 l 0 l0 l@l NA J

lBl@l Surveillance Testing l

' A!riviry CderENT

'2 n

u 42 l tis ~l lZ l @O OP aELEASEl Z l@l RELEASE AMOUNT OP ACTIVITY LOCATION OP RELEASE NA

~

l l.

NA

[

7 8 9 to ti u

45 50 PERSONNEL EXPOSURES NUMBE.R TYPE DESCR.PTION e

l l0 l0 l0 l@l Z l@l N

l

, 7

,ERsON~E'L,wyks CEsCRiPfiON@

NuusER ETl 1010 10l@l NA l

n LOSS 08' OH D AMAGE TO PACIL TV

[

tvet O!5CRt#ff 0N R lZ [gl NA '.

t I

4,

,o w:

et CESCRIPTION l.2_L.J bE81 NA l

l l l l -l l l l l t l 1 l 3 i

. 2 8 0100m yey Curt Steffes 309-654-2241, ext. 175 i

7.....,.....,.,__

...m

+

e' l.

LER NUMBER:

LER/R0 80-22/03L 11.

LICENSEE NAME: Commonwealth Edison Company Quad-Cities Nuclear Power Station 111.

FACILITY NAME: Unit One IV.

DOCKET NUMBER: 050-254 V.

EVENT DESCRIPTION

On September 3, 1980, at 2 p.m., Refueling Outage Test QlS 27-l, HPCI Turbine Area High Temperature Switch Calibration was performed. Temperature Switch TS 1-2371A was found to trip above 2120F. Technical Specification 3.2.1.

specifies the trip point to be less than 2000F. This Instrument had drif ted 30F over the Technical Sr-ilfication limit on the previous test on August 13, 1979, and had been reau;usted successfully.

VI.

PROBABLE CONSEQUENCES OF THE OCCURRENCE:

The 16 HPCI turbine area high temperature switches are arranged in groups of four switches per monitoring channel connected in a one-out-of-two-twice logic.

Therefore, the other switches would have initiated isolation at or below 2000F as designed.

Vll.

CAUSE

The cause of this occurrence was instrument setpoint drif t of temperature switch TS 1-2371A. The switch is manufactured by United Electric Controls Company, Model F7-88.

Vill,

CORRECTIVE ACTION

The switch was replaced with a new one by the instrument Maintenance Department and tested satisfactorily in accordance with QlS 27-1 on September 5, 1980.