O Commonwealth Edison Quad Cities Nuclear Power Station 22710 206 Avenue North Corcova, Illinois 61242 Telephone 309/654-2241 NJK-80-280 August 13, 1980 J. Keppler, Regional Director Office of inspection and Enforcement Region ill U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 Reference: Quad-Cities Nuclear Power Station Docket No. 50-265, DPR-30, Unit 2 Appendix A, Sections 3.7.A.3.a.

Enclosed please find Reportable Occurrence Report Number R0 80-17/03L for Quad-Cities Nuclear Power Station.

This report is submitted to you in accordance with the requirements of Technical Speci fication 6.6.B.2.b., as a condition leading to operation in a degraGed. mode permitted by a limiting condition for operation.

Very trul) yours, COMMONWEALTH EDISON COMPANY QUAD-CITIES NUCLEAR OWER STATION b

df c

N. J. Kalivianakis Station Superintendent NJK:JW/bb Enclosure cc R. F. Janecek gr6 I

/

8000080@A g

l.

LER NUMBER: LER/R0 80-17/03L 11.

LICENSEE NAME: Commonwealth Edison Company Quad-Cities Nuclear Power Station Ill.

FACILITY NAME: Unit Two IV.

DOCKET NUMBER: 050-265 V.

EVENT DESCRIPTION

On July 24, 1980, at 2:30 p.m., with Unit Two operating at 625 MWe in the RUN mode, routine surveillance test QlS-48, Pressure Suppression Chamber and Reactor Building Vacuum Breaker Actuation and Functional Test was performed. Pressure switch PS-2-1622B was found to actuate at 20.3 inches of water. Technical Specification 3 7.A.3.a. specifies that the pressure suppression chamber to Reactor Building vacuum breakers shall actuate at less than 0.5 psid (13.8 inches of water).

Proper recalibration was not successful; the switch was lef t set at 9.4 Inches of water until replaced

'I th a new swi tch. The pressure switch setpoint drif ted previously on

.uly 24, 1979, and was re-adjusted successfully.

VI.

PROBABLE CONSEQUENCES OF THE OCCURRENCE:

The Torus to Reactor Building vacuum breaker system consists of two 100 percent flow capacity systems. Pressure switch PS-2-1622A would have actuated at the required setpoint opening vacuum breaker A0-2-1601-20A had the need arisen. Safe operation was not affected by this occurrence.

Vll.

CAUSE

The cause of this occurrence was setpoint drift of pressure switch PS 16228. The switch could not be reset properly due to wide fluctuations in the setpoint. The switches are manufactured by Static-0-Ring Company, model number 12BB-KK215V.

Vill.

CORRECTIVE ACTION

The faulty pressure switch was replaced with a new one by Instrument Maintenance and tested satisfactorily in accordance with 415-48 on July 24, 1980.