s V

APPENDIX A NOTICE OF VIOLATION Power Authority of the State of New York Docket No. 50-333 Based on the results of an NRC inspection conducted on May 14-16,1980, it appears that one of your activities was not conducted in full compliance with NRC regulations and the conditions of your license as indicated below. This is, an infraction.

Environmental Technical Specification 2.3.b, " Airborne Effluents", states in Section 2, "The release rate of halogens and particulates with half-lives greater than eight days released to the environs as part of airborne effluents shall not exceed a rate Q in curies /sec of I-131 equivalent such that:

QsFITZ QsNMP-1 QvFITZ

+

2.6E-6 2.3E-6 8.9E-8 1

f Where:

QsFITZ = the release rate from the plant stack at the FitzPatrick facility; QsNMP-1 = the release rate from the plant stack at the Nine Mile Point, Unit 1, facility; and QvFITZ = the release rate from vents at the FitzPatrick facility.

Contrary to the above, over a period of 26 hours3.009259e-4 days <br />0.00722 hours <br />4.298942e-5 weeks <br />9.893e-6 months <br />, on May 12-13, 1980, the gaseous release rate of halogens and particulates exceeded the Technical Specification limit by a factor of 1.3.

)