05000321/LER-1980-063-03, /03L-0:on 800612,while Performing Surveillance Procedure HNP-1-3102,reactor High Pressure Shutdown Cooling Mode Switch 1B31-N0l8B Found to Actuate Higher than Limit. Caused by Setpoint Drift.Switch Recalibr

From kanterella
(Redirected from ML19329F973)
Jump to navigation Jump to search
/03L-0:on 800612,while Performing Surveillance Procedure HNP-1-3102,reactor High Pressure Shutdown Cooling Mode Switch 1B31-N0l8B Found to Actuate Higher than Limit. Caused by Setpoint Drift.Switch Recalibr
ML19329F973
Person / Time
Site: Hatch 
Issue date: 07/03/1980
From: Nix R
GEORGIA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19329F965 List:
References
LER-80-063-03L-01, LER-80-63-3L-1, NUDOCS 8007110426
Download: ML19329F973 (2)


LER-1980-063, /03L-0:on 800612,while Performing Surveillance Procedure HNP-1-3102,reactor High Pressure Shutdown Cooling Mode Switch 1B31-N0l8B Found to Actuate Higher than Limit. Caused by Setpoint Drift.Switch Recalibr
Event date:
Report date:
3211980063R03 - NRC Website

text

F HM 3G6 stShM5LLMWUmiu;LnAh

'w LICENSEE EVENT REPORT CONfROL BLOCK: l l

l l

l l

lh (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATIOM) 1 0

E la la le II in 11 l@lo lo l-Io lo lo lo lo l-Io lo l@l 4 l ll li 1l 1l@l l

Ig 8 9 LICENSEE CODE 14 15 LICENSL NUMBER 25 26 LICENSE TYPE JU b 7 CAI t,8

ON'T LLJ

%I?s IL l@lo 15 lo lo lo 1312 11 l@l ol el 1121 al ol@l ol vi 01 al el 01@

8 60 61 DOCKET NUMBER 95 69 LVENT DATE 14 75 RE* ORT DATE 80 EVENT DESCRIPTION AND PROllADLE CONSEQUENCES h gl While performing normal surveillance procedure HNP-1-3102, Reactor High l

0la] l Pressure Shutdown Cooling Mode, switch 1B31-No18B was found to actuate at l

o i4 l l 167 psi. The Technical Specifications limit is </=157.3 psi.

There was l

qT] l no effect on public health or safety. The redundant switch was operable.

l 0 In 1 l This switch is a Static-O-Ring.

This is not a repetitive occurrence on l

,3 l 7 l l this switch.

l 0]H] l 60 8 9 DE CODE S BC E COMPONENT CODE SUBCOdE S

E r191 I c I n l@ lLJ@ La]@ 111 N i s I T I R l u l@ W@ U @

8 9

to 11 12 13 18 19 20 SEQUEN11 AL OCCURRENCE REPORT REVISION L E R rRO EVENT YEAR REPORT NO.

CODE TYPE NO.

@,gg I si of L--J l o i s i 31 l'l 1o13I IL I l-l loI

_ 28 22 23 24 26 27 28 29 30 31 32 A EN ACT

( PL T TI O HOURS SB IT D FORIbuB.

SUPPL 1 MANIFA URER l@

l ZlQ l Zl@

l o l o l o l oj lYl@

lY\\@

lNl@

lSl3l8l2l@

lE lgl34Z 35 36 3/

40 41 42 43 44 47 3J CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h Ql The cause of the occurrence was setpoint drift. The switch was recalibrated l

lt It l l and tested successfully. The switches on Unit II were tested successfully.

I i 2 l

The unit is now in full compliance and no further reporting is required.

f l

i 131 l 1

EI 80 P

B 9

% POWE R OTHER ST ATUS Dis O RY DISCOVERY DESCRIPTION NA l

l B lhl Surveillance Tests l

il5l Wh l ol ol olhl AMOUNT OF ACTIVITY @ l LOCATION OF RELEASE @

A TIVITY CO TENT REMASED OF RELE ASE n^

I u^

l Bij Lz_]@ l zl@l 7

8 9 10.

11 44 45 80 PERSONNEL FXPOSURES NUVHFR TYPE

DESCRIPTION

NA l

E lololol@lzl@l PinSONNd'IN;uFiES DESCniPTiON@

. NUMnER NA I

E lololol@l P

8 9

- 11 12 80 E OSS Or OR DAMAGE TO F ACilli f TYPE DEScillPilON

"^

l E Lz_i @ l 80 P

H 9 10 8007110 D7.l>

l l l l l l l l l l l l l :}

"S' 13SlE

DESCRIPTION

I NA l

B LN, hl 68 09 80 ;

_O D.

10 NAME OF PREPARER.

PHONE:

e

NARRATIVE

REPORT Georgia Power Company Plant E.

I. I!atch Baxley, Georgia Reportable Occurrence Report No. 50-321/1980-063.

While performing normal surveillance procedure IINP-1-3102, Reactor Iligh Pressure Shutdown Cooling Mode Functional Test and Calibration, switch IB31-N018B actuated at 167 psi increasing.

The setpoint on this switch is 147.3 psig 15.

The Technical Specification limit is </=157.3 psig.

This switch is a reactor pressure permissive to operate valve lEll-F015.

The 1B31-N018A switch is a redundan't switch in a parallel circuit'with the IB31-N018B switch and worked correctly.

The corresponding switches on Unit II were checked and operated correctly. Switch IB31-N018B was recalibrated and returned to service.

The unit is now is full compliance with the requirements and no further reporting is required.

This is a non-repetitive occurrence on this switch.

This switch is a Static-O-Ring.