05000321/LER-1980-057-03, /03L-0:on 800525,while Performing Procedure HNP-1-1114,RHR Shutdown Cooling Mode,Shutdown Cooling Suction Valve Failed to Open.Caused by Faulty Auxiliary Contact Block.Contact Block Replaced

From kanterella
(Redirected from ML19324A087)
Jump to navigation Jump to search
/03L-0:on 800525,while Performing Procedure HNP-1-1114,RHR Shutdown Cooling Mode,Shutdown Cooling Suction Valve Failed to Open.Caused by Faulty Auxiliary Contact Block.Contact Block Replaced
ML19324A087
Person / Time
Site: Hatch 
Issue date: 06/13/1980
From: Nix R
GEORGIA POWER CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19324A084 List:
References
LER-80-057-03L, LER-80-57-3L, NUDOCS 8006200461
Download: ML19324A087 (2)


LER-1980-057, /03L-0:on 800525,while Performing Procedure HNP-1-1114,RHR Shutdown Cooling Mode,Shutdown Cooling Suction Valve Failed to Open.Caused by Faulty Auxiliary Contact Block.Contact Block Replaced
Event date:
Report date:
3211980057R03 - NRC Website

text

l1111 LICENSEE EVENT REPORT COF TROL CLOCK: l l

l l

l l

l (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION) g 1

6 i cl Al El I l 11l 1 l@l 0 l 0 l -l 0 l 0 l 0 l 0 l 0 l - l O ! 0 l@l 4 l 1 l 1 l 1 l 1 l@l l

l@

o 8 9 LICENSE E CODE 14 lb LICENSE NUMBEH 24 26 LICENSE TYPE JO b7 CAI bli CON'T 011l

"$n",' l Ll@l 0l 5 l 0 l O l 0 l 3l 21 1 @[ 0 l S l 2 l S l 810 l@l 0 l 6 l 1 l 3 l 8 l 0 l@

8 60 61 DOCKET NUMBER Gi 63 EVENT DATE 14

~15 HEPORT DATE SO EVENT DESCRIPTION AND PRODABLE CONSEQUENCES h

[ OE l With the reactor in the shutdown mode. while nerforming Procedure liNP-1 0131 l l-1114. RilR Shutdown Cooling Mode, on the

'B' division, the Shutdown Cool-l o 4 l

ing Suction Valve, I E l l-F006B_, for the

'B' RilR pump failed to open. The l

O s l

'B' RilR pump was declared inoperable.

As the 'A' division of RilR was out l

[TITl l for maintenance, both pumps in the

'B' division were required to be operable i

10 l 7 l l per Tech Spec 3. 5.B. I.b.

This event was not repetitive and there were 1

0 s l no effects to public health and safety.

1 7

8 9 80 SYST E M

CAUSE

CAUSE COMP.

VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SU8 CODE E

I Cl Fl@ [_E_j@ l A l@ l Cl Kl Tl Bl Rl Klh [B_J@ l Zl @

r 8

9 10 11 12 13 18 19 20 SEQUENTI AL OCCURRENCE REPORT REVISION l VENT YE A R

[--.]

l 0l 5l7l y

l 0l 3l lL l

[-j l0 l LER RO E

REPORT NO.

CODE TYPE N O.

l

@lg 8l0l

_ 21 22 23 24 26 21 28 29 30 31 32 q

AAEN A O

O PL NT ET i HOURh S BP IT D FO tb B.

5 PPL1 MAN A TLFER l_^-]@W@

lzi@

I z lO Lo l o l o l o l W@

l Y l@

l N l@

l A l 1 l 8 l 0 [g 33 34 3:a 3t>

3/

40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS 1 O l

The f ailure of the lEll-F006B valve to open was due to a faulty auxiliarv l

5 5 l

cantact block. The ncrually cloacd contact, which is in the open circuit, i

i 7

l was found stuck in the open position. The auxiliary contact block was l

i 3 l

replaced and the valve returned to service. The

'B' RilR pump was then l

i 4 l

placed back in operation.

l 7

8 9 80 S

S

% POWER OTHE R STATUS I O FY DISCOVERY DESCRIPTION

] lG lQ l 0 l 0 l 0 ]@l NA l

lAl@l Operator observation l

ACTIVITY CONTENT RELE ASFD OF HELE ASE AMOUNT OF ACTIVITY LOCATION OF RELE ASE

] Q @ Wgl NA l

l NA l

7 8 9 10 11 44 45 80 Pt RSONNEL E XPoSUHES NUMHER TYPE DE SCRIPTION -

] l0 l0 l0 l@l Zl @ l NA l

PtnSON.a'E l~;u'4ES So DESCRIP TION @

NUM6fR

] l0 l0 l0 l@l NA l

P 8 9 11 12 80 LOSS Of OH DAMAGE TO FACtLITY Q TY;E DESCHiPTION

%,e IIB lzJ@L..

NA l

r a w iO So B,d33gfU"I'$ESCniPTION 8 0 0 62 00 N[NA NRC USE ONLY g

l lllllllllllll}

P 8 9 10 68 69 80 E NAME OF PREPARER R. T. Nix PHONE: 912-367-7781 E,

O

U5' u
li, w.-

NARRATIVE

REPORT.

Georgia Power _ Company Plant E.1. Hatch

.Bax1cy,' Georgia 31513-Reportabic-Occurrence Report No. 50-321/1980-057.

~

aOn May 25,1980, with the reactor in the shutdown mode, while performing procedure HNP-1-lll4,.RHR Shutdown Cooling Mode, on the

'B' division, the Shutdown Cooling Valve, IEll-F006B, for the

'B' RHR pump failed to open.

The 'B' 'RHR' pump was declared inoperabic. The

'B' pump was required to be operabic per Tech. Spec 3.5.B. I.b due to the ' A' division of the RHR system being out for maintenance.

Upon investigation of the failure, personnel discovered that a normally-closed auxiliary contact in the open circuit was stuck open. The auxiliary contact block, located on the motor control center starter, was replaced and the valve returned to service. The

'B' RHR pump was then placed back in_ operation.

This was not a repetitive event nor were there any effects to public health and safety.

b 4._