ML19211D510

From kanterella
Jump to navigation Jump to search

NRR E-mail Capture - Virgil C. Summer Nuclear Station, Unit No. 1 - Request for Additional Information LAR-16-01490 NFPA-805 (Supplement to PRA RAI 03)
ML19211D510
Person / Time
Site: Summer 
Issue date: 07/30/2019
From: Shawn Williams
Plant Licensing Branch II
To: Maria Moore
South Carolina Electric & Gas Co
References
L-2018-LLA-0233
Download: ML19211D510 (5)


Text

1 NRR-DRMAPEm Resource From:

Williams, Shawn Sent:

Tuesday, July 30, 2019 12:44 PM To:

MOORE, MICHAEL S Cc:

DALICK, SARA BETH

Subject:

Virgil C. Summer Nuclear Station, Unit No. 1 - Request for Additional Information RE:

LAR-16-01490 NFPA-805 (Supplement to PRA RAI 03) (EPID No. L-2018-LLA-0233)

Attachments:

Summer NFPA 805 supplement to PRA RAI 03 option (ii).docx

Dear Mr. Moore,

By letter dated August 29, 2018Property "Letter" (as page type) with input value "RC-18-0091, License Amendment Request - LAR-16-01490 National Fire Protection Association Standard 805 Program Revisions" contains invalid characters or is incomplete and therefore can cause unexpected results during a query or annotation process., as supplemented by letters dated April 29, 2019, and May 22, 2019, South Carolina Electric & Gas Company (SCE&G) submitted a license amendment request for the Virgil C. Summer Nuclear Station, Unit 1, to make changes to its approved fire protection program under 10 CFR 50.48(c), including changes to plant modifications, use of performance-based alternatives to the requirements of NFPA 805, Chapter 3, and several clarifications and editorial corrections.

Based on the information in the supplement dated May 22, 2019, on June 27, 2019, the U.S. Nuclear Regulatory Commission (NRC) issued a follow-up Request for Additional Information (RAI) to PRA RAI 03. On July 23, 2019, a public teleconference was held between SCE&G and NRC staff to discuss SCE&Gs proposed response to the June 27, 2019, RAI. During the teleconference, SCE&G stated they propose to utilize option (ii) of the June 27, 2019, RAI. Based on the discussion during the teleconference, the NRC staff is providing further clarification to PRA RAI 03, option (ii), in the attached.

If you have any questions, please contact me at 301-415-1009 or Shawn.Williams@nrc.gov.

Sincerely, Shawn A. Williams, Senior Project Manager Plant Licensing Branch II-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No.: 50-395

Enclosure:

Request for Additional Information cc: Listserv

Hearing Identifier:

NRR_DRMA Email Number:

148 Mail Envelope Properties (DM6PR09MB3178B9C3139279892B301B3390DC0)

Subject:

Virgil C. Summer Nuclear Station, Unit No. 1 - Request for Additional Information RE: LAR-16-01490 NFPA-805 (Supplement to PRA RAI 03) (EPID No. L-2018-LLA-0233)

Sent Date:

7/30/2019 12:43:41 PM Received Date:

7/30/2019 12:43:43 PM From:

Williams, Shawn Created By:

Shawn.Williams@nrc.gov Recipients:

"DALICK, SARA BETH " <SARA.DALICK@scana.com>

Tracking Status: None "MOORE, MICHAEL S" <MICHAEL.S.MOORE@scana.com>

Tracking Status: None Post Office:

DM6PR09MB3178.namprd09.prod.outlook.com Files Size Date & Time MESSAGE 1535 7/30/2019 12:43:43 PM Summer NFPA 805 supplement to PRA RAI 03 option (ii).docx 30759 Options Priority:

Standard Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received:

REQUEST FOR ADDITIONAL INFORMATION SUPPLEMENT TO PRA RAI 03 LICENSE AMENDMENT REQUEST TO REVISE NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 805 FIRE PROTECTION PROGRAM VIRGIL C. SUMMER NUCLEAR STATION, UNIT NO. 1 DOCKET NO. 50-395 By letter dated August 29, 2018Property "Letter" (as page type) with input value "RC-18-0091, License Amendment Request - LAR-16-01490 National Fire Protection Association Standard 805 Program Revisions" contains invalid characters or is incomplete and therefore can cause unexpected results during a query or annotation process. (Agencywide Document Access and Management System (ADAMS) Package Accession No. ML18242A657), and supplemented by letters dated April 29, 2019 (ADAMS Accession No. ML19119A365) and May 22, 2019 (ADAMS Accession No. ML19150A696), South Carolina Electric and Gas (SCE&G) submitted a license amendment request (LAR) for the Virgil C. Summer Nuclear Station, Unit 1 (VCSNS), to make changes to its approved fire protection program (FPP) under 10 CFR 50.48(c). In its LAR, the licensee proposed to make several changes to its FPP including changes to plant modifications, use of performance-based alternatives to the requirements of NFPA 805, Chapter 3, and several clarifications and editorial corrections.

Based on the information in the supplement dated May 22, 2019, on June 27, 2019 (ADAMS Accession No. ML19179A126), the U.S. Nuclear Regulatory Commission (NRC) issued a follow-up Request for Additional Information (RAI) to PRA RAI 03.

On July 23, 2019, a public teleconference was held between SCE&G and NRC staff to discuss SCE&Gs proposed response to the June 27, 2019, RAI to PRA RAI 03. During the teleconference, SCE&G stated they propose to utilize option (ii) of the June 27, 2019, RAI.

Based on the discussion during the teleconference, the NRC staff is providing further clarification to PRA RAI 03, option (ii), below.

Follow-up Question to PRA RAI 03 [issued on June 27, 2019]:

Section 2.4.3.3 of NFPA 805 states that the probabilistic risk assessment (PRA) approach, methods, and data shall be acceptable to the NRC. Section 2.4.4.1 of NFPA 805 further states that the change in public health risk arising from transition from the current fire protection program to an NFPA 805 based program, and all future plant changes to the program, shall be acceptable to the NRC.

In the letter dated May 22, 2019, the licensee responded to PRA Request for Additional Information (RAI) 03 and stated, in part:

The longer the seals can withstand loss of seal cooling, the more time is available for operators to trip the RCPs [reactor coolant pumps], and the lower the failure probability of that action. Dynamic loss-of-seal-cooling tests of N-9000 RCP seals have shown that RCPs can operate in excess of 60 minutes with no measurable change in seal leakage. The Human Reliability Analysis (HRA) that supports the 2018 VCSNS FPRA [fire PRA] models a 60-minute system time window for the operator action to trip RCPs. The 60-minute system time window is retained in the current FPRA.

In the safety evaluation associated with Amendment No. 199, dated February 11, 2015 (ADAMS Accession No. ML14287A289), the NRC staff found acceptable the licensee's N-9000 RCP seal failure model applied in the FPRA, which is based on the RCP seal failure model and associated failure probabilities used in WCAP-16175-A, "Model for Failure of RCP Seals Given Loss of Seal Cooling in CE NSSS Plants (ADAMS Accession No. ML071130383). WCAP-16175-A indicates that the N-9000 RCP seals have been designed to survive 30 minutes of continued RCP operation without RCP seal cooling. Also, the response to RAI 1.15.1 documented in WCAP-16175-A states, [a]s data for RCP seal operation without seal cooling for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> is not available, this event will be redefined to require tripping the RCP within 20 minutes. Therefore, it appears that the licensees use of a 60-minute system time window for operator action to trip RCPs in the FPRA to support the LAR dated August 29, 2018 is not consistent with that used in the NRC-accepted RCP seal model (i.e., FPRA RCP seal failure model accepted in the safety evaluation associated with Amendment No. 199, which is based on WCAP-16175-A). Also, the basis for using the 60-minute system time window provided in the response to PRA RAI 03 is unclear to the NRC staff.

(i)

Provide the technical basis for use of a 60-minute system time window for operator action to trip RCPs without seal cooling for the N-9000 RCP seals installed at VCSNS. If results of any tests or performance data are used to support this basis, discuss these results and data, including how this information is used to substantiate the 60-minute system time window and is applicable for the VCSNS RCP seal design and operating conditions that can affect seal performance. Also discuss the sensitivity of the risk results to the system time window for operator action to trip RCPs (e.g., compare the total risk and change-in-risk of using a 60-minute system time window with that used in the FPRA RCP seal failure model accepted in the safety evaluation associated with Amendment No. 199). OR (ii)

Alternatively to part (i), provide updated risk results in Table PRA RAI 03-1 of letter dated May 22, 2019 that uses the system time window for operator action to trip RCPs based on the FPRA RCP seal failure model accepted in the safety evaluation associated with Amendment No. 199, and discuss how the updated risk results align with the risk acceptance guidelines of Regulatory Guide 1.205. Propose a mechanism that ensures an NRC-accepted RCP seal failure model is used in the FPRA for self-approval of post-transition changes.

Supplement to Option (ii) [based on July 23, 2019, teleconference discussion]:

Describe in sufficient detail any additional changes to the VCSNS PRA models (i.e., internal events, internal flooding, seismic, and fire) in support of the updated risk results that were not described in the LAR dated August 29, 2018, as supplemented by letters dated April 29, 2019 and May 22, 2019.

Explain and justify whether the changes are PRA maintenance or PRA upgrades as defined in ASME/ANS RA-Sa-2009, Section 1-5.4, as qualified by Regulatory Guide 1.200, Revision 2.

For all PRA changes that constitute a PRA upgrade, state if a peer review has been performed for any PRA upgrades in accordance with an NRC-accepted process. As applicable, provide the open facts and observations (F&Os) characterized as findings associated with this peer review and explain how the F&Os were dispositioned to Capability Category II for this application.

If a peer review was not performed for PRA upgrades, propose a license condition such that prior to implementing self-approval of post-NFPA-805 transition changes:

PRA upgrades will be appropriately peer reviewed and any finding-level F&Os are closed in accordance with an NRC-accepted process (e.g., focused-scope peer review, F&O closure review, direct submittal to the NRC), and, Confirm that the updated transition change-in-risk estimates for this application align with the risk acceptance guidelines of Regulatory Guide 1.205.