ML18078A968
| ML18078A968 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 02/09/1979 |
| From: | Robert Carlson NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| To: | Martin T Public Service Enterprise Group |
| Shared Package | |
| ML18078A969 | List: |
| References | |
| NUDOCS 7903130239 | |
| Download: ML18078A968 (2) | |
See also: IR 05000311/1978046
Text
UNITED STATES
NUCLEAR REGULATORY COMMISSION
REGION I
631 PARK AVENUE
KING OF PRUSSIA, PENNSYLVANIA 19406
Docket No. 50-311) 7f6-i-f &
FEB 0 9 1979
Public Service Electric & Gas Company
ATTN:
Mr. T. *J. Martin
Vice President
Engineering and Construction
80 Park Place
Newark, New Jersey
07101
Gentlemen:
Subject:
Inspection 50-311/78-46
This refers to your letter dated January 16, 1979, in response to our
letter dated December 15, 1978~
Your letter states that strain gage measurements
11were not considered a
formal *part of the Structural Integrity Test
11
However, your commitments
in Amendent 38 of the Salem Generating Station FSAR (Question 5.20)
indicate that due to equipment layo~t it is not possible to run trans-
ducer wires at six points at each circumference for growth measurements
and,
11 numerous additional strain gages will be used on the liner plate
and rebar to supplement the measurements".
As noted in IE Inspection
Report No. 50-311/78-51, we observed that these strain gage commitments
were met during the test, and data/evaluations will b~ included in the
final test r~port. *
In a telephone conversation between Mr. R. Evans of your staff and Mr.
Toth of this office we were advised that a review of all Salem 2 struc-
tural specifications was completed on January 18, 1979 to identify any
process/test related requirements which may have been inadvertently
omitted from other procedures.
We understand that no such cases were
identified.
Should you have any questions or clarifications regarding the above
understandings, please contact this office.
Your corrective and pre-
ventive actions documented in your letter and described above will be
examined during a subsequent inspection of your licensed program .
190313 o ;;_ 3 ;
Public Service Electric & Gas
Company
2
FEB O 9 1979
Your cooperation with us is appreciated.
Sincerely,
~i)~ '4 ~-
Robert T. Car~ief
Reactor Construction and Engineering
Support Branch
cc:
E. N. Schwalje, Manager - Quality Assurance,
- E.ngineering *and Construction Department