ML17296B002
| ML17296B002 | |
| Person / Time | |
|---|---|
| Site: | Palo Verde |
| Issue date: | 09/29/1980 |
| From: | Engelken R NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V) |
| To: | Van Brunt E ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR |
| References | |
| NUDOCS 8010160086 | |
| Download: ML17296B002 (29) | |
Text
~~ AEQUI
~4 P0
~
~i g r
+>>*++
NUCLEAR REGULATORY COMMISSION REGION V 1990 N. CALIFORNIABOULEVARD SUITE 202, WALNUTCREEK PLAZA WALNUTCREEK, CALIFORNIA94596 September 29, 1980 Oocket Nos. 50-528, 50-529, 50-530 Arizona..Public Service Company P
0.
Box 21666 Phoenix Arizona 85036 Attention:
Mr.
E.
E.
Van Brunt, Jr.
Vice President, Nuclear Project Gentl emen; The, enclosed IE Supplement No. Z to Bulletin 79-01B is forwarded to you for information.
No written response. is required.
If you desire additional information regarding this matter, please contact this office.
Sincerely,.
~i PP. ~~D-R. H. Engelken Director
'sg-i g ~
Enclosures:
'l.
IE Suppl'ement No.
2 to Bulletin No 79-018 2.
Recently Issued: IE Bulletins cc w/o enclosures:,
F.
W.. Hartley, APS jW
~~X0 1 6' Ir<(y r
I
>>+r vrg4( r i5. A 8$4r r.r ';,p i...'~ fÃy.Can rip
'Jv + -t~kf'qW~Q.t~'~'g'r'~IIV'4L~r
~
- ~
~
~
<<J~
<<I
~I r,
<<4-"rr" '
~ r"
i I
l'
UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 September 29, 1980 S SINS:
6820 Accession No.:
80082202gl IEB 79-01B, Supple.
2 IE Supplement No.
2 to Bulletin 79-O1B ENYIRONMENTAL QUALIFICATION OF CLASS 1E EQUIPMENT Enclosed are the generic questions and answers which resulted from NRC/Licensee meetings in NRC Regional Offices during the week of July 14, 1980 regarding environmental qualification of Class lE equipment in use at power reactor facilities.
These answers address specific questions asked during the meetings.
Due to the generic nature of some of these questions, the staff is issuing them as a bulletin supplement.
The regional meetings highlighted the fact that in some cases, the scope and depth of the 79-01B review was not clear to licensees.
Therefore, -these answers may affect your 79-01B submittal.
These submittals are required by a separate order to be completed by November 1,.
1980.
Some answers given in Supplement No.,
1 to IEB-79-01B are superseded by these answers.
For example, in Bulletin Supplement No.
1,. issued on February 29,
- 1980, the answer to question No 5 specified that TMI lessons learned equipment was not included in the review.
- However, due to the extension of the response date from April 14, 1980 to November 1, 1980, this equipment is now being addressed since its installation is either complyte or required before the issuance of the February 1, 1981 SER.
(See Question No. 21 of this Supplement.)
No specific response is requested by this Supplement; however, all answers=
contained in the enclosure to this Supplement should be carefully reviewed and considered for applicability in your response to IEB 79-01B.
IE Bulletin No.79-01B was issued under a blanket GAO clearance (B180225 (R0072); clearance expired July 31; 1 80) specifically for identified generic.
problems.
'Supplement No.
2 to Bulletin 79-01B is for information,. hence.
no GAO clearance is required.
Enclosures:
1.
Generic Questions and Answers to IEB-79-01B and Memorandum and Order (CLI-80-21) dated.
May 23, 1980
V f
t
}
RECENTLY ISSUED IE BULLETINS IEB 79-01B, Supple.
2 September 29, 1980 Bu letsn No.
80-22 Sub'ect Automation Industries, Model 200-520-008 sealed-source connectors Date Issued Issued To 9/11/80 All.
radiography licensees 79-26 Revision 1
80-20 Boron loss from BWR control blades Failures of Westinghouse Type W-2 Spring Return to Neutral Control Switches 8/29/80'/31/80-AT1 BWR power facilities with an OL To each nuclear power facility in your region having an OL or a CP 80-19 80-18 Failures of Mercury-Wetted Matrix Relays in Reactor Protective Systems of Operating Nuclear Power Plants Designed, by Combus-tion Engineering Maintenance of Adequate
'7/24/80 Minimum Flow Thru. Centrifugal Charging Pumps-Following Secondary Side High Energy Line Rupture All nuclear power facilities having either an OL or a
CP All PWR power reactor faci 1 ities hol ding OLs and to those PWRs nearing licensing'upplement 2
to 80-17 Supplement 1
to 80-17 80-17 Failures Revealed by Testing Subsequent to Failure of Control Rods to Insert During a Scram.
at a BWR Failure of Contro'l Rods to Insert During a. Scram, at a
BWR Fail'ure of Control Rods to Insert, During a Scram at a BWR 7/22/80 7/18/80 7/3/80 All BWR power reactor facilities holding OLs All BWR power reactor facilities holding. OLs All BWR power reactor facilities holding OLs 80-16'otential Misapplication of 6/27/80 Rosemount Ihc., Models 1151 and 1152 Pressure Transmitters with Either "A" or "D" Output Codes Al,l Power Reactor Facilities with an OL or a CP
Q. I Q.2 A.2 Define the scope of review with respect to the June 1982 deadline.
Mhat is required beyond the June 1982 date for qualification?
8y June 30, 1982, all safety-related electrical equipment potentially exposed to a harsh environment in nuclear generating stations, licensed to operate on or before June 30, 1982, shall be qualified to either the DOR guidelines or NUREG-0588 (as applicable).
Safety-related electrical equipment are those required in bringing the plant to a. cold shutdown condition and to mitigate the consequences of the accident.
The qualification of safety-related electrical equipment to function in environmental extremes,, not associated with accident conditions, is the responsibility of the licensee to evaluate and document in a form that will be available for the NRC to audit Qualification to assure functioning in mild environments must be completed by June 30 1982.
The qualification schedules for consideration of the dynamic loading of safety-related equipment (electrical and mechanical) and the environmental qualification review of mechanical equipment are being developed.
It is the intention of the staff to initiate this effort as soon as possible.
Clarify the required. submittal dates for ORs,. NTOLs, and CPs What about OLs whose 100'X license is not expected by June 1982'?
The required schedule for submitting information in response to the Commission Order and memorandum (CLI-80-21) is provided below..
Plants who have received, an operating license, either for full or limited power operation, are required to meet the schedule for operating reactors Pl'ants who have committed,. to the NRC, to meet schedules in advance of those provided, below are required to meet that commitment.
In all cases, plants are required to have their equipment fully qualified-to the applicable standards either by June 30, 198Q, or by the time the operating license. is granted, whichever comes later.
Operatin Reactors and WTOL (operating license expected by February I, 1981 Submittal to be received, no later than November 1,. 1980 OLs (operating license expected by June-30,, 1982)
Submittal to be received no later than 4 months prior to issuance of operating license OLs and CPs (operating'icense expected after June 30, 1982)
Submittal to be received no later than 6 months prior to issuance of operating'icense.
j f
I i
l j
t Q.3 A.3 Define the requirements and applicable crit'eria for ORs, NTOLs, and OLs.
Specifically address the NTOLs whose CP SER is prior to July 1974 and after July 1974.
Can a
CP whose SER is prior to 1974 use the DOR guidelines?
Table I describes the application of each document; All operating reactors as of May 23, 1980,. will be evaluated against the DOR
'uidelines.
In cases where the DOR guidelines do not provide sufficient detail but NUREG-0588 Category II does, NUREG-0588 will be used.
TABLE 1 REQUIREMENTS ORs DOR GUIDELINES OLs CP SER CP SER
~//
'/
// /
CPs USE NUREG-0588 AS NECESSARY REPLACEMENT COMPONENTS USE. NUREG-0588 (CAT. I)
NUREG-0588(CAT. II.')
NUREG-0588(CAT. I)
NUREG-0588(CAT. I) or NEW RULE WHEN IN EFFECT Q.4 Al'1 plants 1'icensed after May 23 1980; shall conform to NUREG-0588.
In accordance with Regulatory Guide. 1.89, all such operating licenses for facilities whose construction permit SER is dated, July I, 1974 or later, are to be reviewed against IEEE Std. 323-1974.
Thus, for these 'licensees the operating license applicant is to qualify equipment to the Category I. col'umn in NUREG-0588.
For operating licenses issued after May 23, 1980,, whose construction permit SER is dated before July I,.'974', the operating license applicant is to qualify equipment to at least. Category II coTumn of NUREG-0588; unless the. licensee made commitment in the construction permit record to use the 1974 standard,. or unTess the operating licensee applica-tion record indicates that the 1974 standard is. to be used, in such cases Column I of NUREG-0588 is to be used.
While there are differences between the Category II column of NUREG-0588 and the DOR guidelines, the differences-are in detail's and in the optional part of the documents.
The minimum requirements set forth by these documents are general and compatible.
- Thus, the minimum standards set by either of the two documents are equally applicable-to ORs and NTOLs.
~Clarify the repor ting requirements for LERs.with respect to Part 50.55e vs79-01B.
Are only those items, known to be unqualified, immediately reportab'fe?
Are items,. for which there are no data or for which there are insuf-ficient data, open items to be resolved, but are not immediately reportable?
A.4 'he requirement for reporting in IEB 79-01B does not change the reporting requirements defined in the license conditions.
In general, CPs should report via 50.55e.
Operating plants should use the LER..
When a determination has been made that reasonable assurance does not exist to ensure that the Class IE-electrical equipment component(s) can perform their safety-related function, that is reportable.
Inadequate or no data are factors in this. determination.
The time.
and technical judgements required to make the determination should be based on the. significance of this. specific equipment,,
components, and the: discrepancies.
Q.,5 A.5 How does the "Q" list review interface with the.
EQB effort?
Can the NRC provide more specific guidance on how to pick out the required safety-related equipment?:,
The "Q" list provides a source from which the required equipment may be selected.
The information required to be submitted by November 1, 1980, is for safety-related electrical equipment potentially exposed to a harsh environment resulting from ae accident.
Safety-related equipment are. those required to help bring the plant to cold shutdown and to mitigate the accident (LOCA, HELB inside or. outside containment).
"Mitigate" includes safety-'related functions such as containment isolation, and prevention of significant release of radioactive material.
In order to "pick out" the safety-related equipment, the licensee should generate a list of'safety functions. typically performed by plant safety systems..
Examples are listed in Table II.
For each safety function identified in Table II, list the systems, subsystems,.
or components assumed available in the plant FSAR or emergency procedures to perform that: function during a LOCA or any HELB inside or outside containment.
If a plant. specific safety function not listed in Table II is identified, that function and the corresponding systems or equipment to perform the function should be added to the licensee's list.,
The systems and equipment identified above should be-included regardless of the original classification when the plant received its operating license; i.e.,
some control grade equipment will probably be named in emergency procedures.
However, if plant emergency procedures specify.
a preferred mode of'ccident mitigation involving equipment recognized by the licensee= as unlikely to meet environmental qualification criteria,, an alternate mode of performing the safety function and qualifiable equipment may. be identified.
!n such cases, the emergency procedures must clearly indicate how the
operator is to use environmentally qualified safety-related display instrumentation to diagnose failure to perform such safety functions.
Plant emergency procedures typically include orovisions for the operator to sample or monitor radioactivity levels or combustible gas levels, to confirm that valves are in the correct position, to monitor flow or temperature, etc.
Some of these functions are essential for correct-operator action, to mitigate accidents, and-prevent radioactive releases When this is the case, the radiation sensors,.
valve position indicators, pressure transmitters,,
thermo-couples, etc., should be qualified to function in the reTevant accident, environment.
Licensees should, therefore,. review their emergency procedures to determine the electrical components needed to perform the functions of Safety-Related Display Information, Post Accident Sampling and Monitoring, and Radiation Monitoring..
When equipment implied by the emergency procedures is not listed, justificiation must be provided that failure of such equipment would not prevent accident mitigation or release of radioactivity.
Equipment now indicated in emergency procedures in response to TMI-2 Lessons Learned should be listed.
Equipment which is or will be installed due to TMI Lessons Learned should be addressed, similar to other existing safety-related equipment (e.g., saturation
- meter, sump level indicators, torus water volte etc.).
The licensee should document anticipated. service conditions in every portion of the plant where-the environment could. be influenced by the accident, or its consequences.
These service conditions. should also be correlated with the safety-related systems and subsystems identified above..
Whenever an item of safety-related equipment may be located in an environment outside the range of normal conditions,.
due to the harsh environment resulting from the accident,,
and the equipment is needed to mitigate the consequences of the accident, place it on the list of equipment in a potentially hostile environ-ment.
Conclusions which show that equipment is unqualifi'ed should include a basis for continued plant operation.
TABLE II.
TYPICAL EQUIPMENT/FUNCTIONS NEEDED FOR MITIGATION F
LQC R MSLB CCIDE T Engineered Safeguards Actuation Reactor Protection Containment Isolation Steamline Isolation Main Feedwater Shutdown and Isolation Emergency Power
I I
l 1
f t
I I
f l
i t
(,
Emergency Core Cooling Containment Heat Removal Containment Fission Product Removal Containment Combustible Gas Control Auxiliary Feedwater Containment Ventilation Containment Radiation Monitoring Control Room Habitability Systems (e.g.,
HVAC, Radiation Filters)
Ventilation for Areas Containing Safety Equipment Component Cooling-Service Water.
Emergency Shutdown Post Accident Sampling and Monitoring Radiation Monitoring Safety Related Display Instrumentation (1)
These systems. will differ for PHRs and BWRs and, for older and newer plants.
In each case, the. system features which allow for transfer to recirculation cooling mode and establishment of 'long-term cooling with boron precipitation control are to be considered as part of the system to be: evaluated (2)
Emergency shutdown systems include those systems used to bring the plant to a cold shutdown condition following. acciQnts: which do not result in a breach of'he reactor coolant pressure boundary together with a rapid depressurization of the reactor coolant system.
Examples of such systems and equipment are the RHR system,.
chemical and volume control system,. and steam dump systems.
(3)
More specific identification of these types of equipment can be found in the plant emergency procedures Q.6 A.6 Q.7 A.7 NUREG-0588 was issued for comment Mi.ll any changes impact the requirements established by the Commission memorandum and order?
Will the daughter standards referenced be corrected/changed?
The requirement established by the-Commission memorandum and order will-'ot change as a result of'omments on NUREG-0588..
No substan-tive changes are anticipated in NUREG-0588 or in referenced daughter standards.
A revision is anticipated,.
making corrections.
Can IEEE Std-. 650 (Standards for Qualification of Class IE static battery chargers and invertors for nuclear power generating stations) be used for qualifying the balance of plant components which are not exposed to harsh environments?
The methods and procedures relating to design stress
- analysis, aging
. of electrical/electronic components and the stress test identified in this standard are'cceptable for qualifying the balance of plant
'omponents which are not exposed to harsh environments.
l f
f I
l I
Q.8 A.8 Provide the staff's definition of "central.location" for qualifica-tion documentation.
What documentation is expected to be maintained?
Will it be acceptable to maintain summary test reports at the utility central file and. provide a reference to the NSSS Vendor's file for the actual test reports?
Ooes NRC require test reports to be sub-mitted to support qualification?
The central 1'ocation should be at the util-ities 'corporate head-quarters or plant site.
Both the DOR guidelines and NUREG-0588 specify that sufficient information must be available to verify that the safety-related electrical equipment. has been qualified in accordance with the guidance and requirements.
Oetails for the information and documentation required for type tests, operating experience,, analysis,.
and extrapolation of test data from operating experience are provided in Section 5 of NUREG-0588 and Section 8 of IEEE Std.
323-74.
The staff will accept summary test reports.maintained at. the utility's. central file which reference the actual test reports and data available in a single location, at. the. HSSS vendor's facility.
Th'e Licensee/ Applicant must. make the. determination that. necessary information and documentation, to. support qualification of equipment, is in conformance with OOR guidelines and NUREG-0588.
This vendor information file must be maintained cu*ent, auditable and available throughout the life of'he referencing plant.
Test reports are not required to be submitted.
Test. report references-must be incl'uded in the. plant submittals and these reports must be available for staff review on demand.
Q.9 The staff was directed: to codify, by Technical Specification, some of the requirements of the Order.
Can you give some of the details of this requirement,.
how the staff expects to meet this directive and when?
A.9 Q. 10 A. 10 Q. 11 The staff has proposed to the Commission changes to the Technical Specifications (e.g.,
Appendix A Section 6..10 of the license) which require the establ'ishment and maintenance of a centrally located file which wil'1 contain the information necessary to verify the qualification adequacy of all safety-related electrical equipment.
With respect to the HRC data base, how wi11 utilities address and obtain information from it?
The industry access method for the data base will be addressed in the final stages of system development.
This information should be available by mid-1981.
Licensees will be informed at that time.
How should submittals containing data-and qualification information be submitted?
What format should we use if we have several facili-ties at different stages (OR, NTOL, CP)?
I il l
t I
The qualification information and data should be submitted with the appropriate officer's notarized sworn statements.
The format for the data should be in accordance with the format provided in. IEE Bulletin 79-01B or the letters provided to the plants in the SEP program.
Either format is acceptable.
Is testino required of equipment which completes its safety-related function within the first minute(s) of a LOCA or HELB?
(E.g.,
,nuclear instrumentation or other instruments providing RPS inputs,.
isolation valves, etc.)
The staff does not require that the nuclear instrumentation and its associated components be environmentally qualified for a LOCA or HELB.
The nuclear instrumentation system is used for transient conditions but is not required for a
The staff does require that equipment. designed. to perform its safety-related function within a short time into an event be qualified for a period of at least I houp in excess of the time assumed in the accident analysis.
The staff has indicated that time is the most significant factor in terms of the margins required to provide an acceptable confidence level that a safety-related function will be completed.
Our judgment of at least 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> is based on the acceptance of a type test for a single knit and the spectrum of accidents (small and large breaks) bounded by the single test.
Also see answer to question. 21.
Testing is currentTy being performed on some equipment,,
and contracts have been issued for testing additional equipment specifying confor-mance to IEEE Std 323-1971.
For sequential
- testing, how do we factor in aging?'f early test failure occurs. due to "non E-Q" mechanisms,.
can the. test be extrapolated using analytical methods?
Sequential testing requirements are specified in NUREG-0588 and the 00R guidelines.
Licensees must follow the test requirements of the applicable document.
l.
If the test has been completed without. aging in sequence, justification for such a deviation must be submitted.
2.
If testing of a given component has been scheduled but not initiated, the test sequence/program should be modified to include aging.
3.
Test programs in progress should be evaluated regarding the ability to comply by incorporating aging in the proper sequence.
These would then fall in the first or second category.
When a failure occurs due to a non-EQ related mechanism, acceptability of analysis to extrapolate the test data-would be dependent on several considerations (e.g., the specific function being demonstrated, the
failure mechanism, when the failure occurred, etc.),
may be very difficult to achieve.
If such a failure occurs it may be more prudent to correct the failure and continue with the test.
What is the definition of harsh environment'?
How are the environ-mental profiles defined outside containment?
Harsh environment is defined by the limiting conditions, as specified in IE Bulletin 79-01B, resulting from the entire spectrum of LOCAs HELBs..
Specifically,. the harsh environment from a LOCA considers the. worst parameters resulting over the spectrum of'ostulated break
- sizes, break locations and single failures.
Similarly, the HELBs inside and outside of containment consider the spectrum of breaks including main steam and feedwater line breaks.
The parameters to.
be considered are:
temperature,
- pressure, humidity, caustic spray, radiation,: duration of exposure, aging and submergence Mechanical and flow-induced vibrations and seismic. effects will be considered separately..
Environmental profiles for HELB outside. of containment have not been generically established, due to the uniqueness of each facility.
Service conditions for areas outside containment exposed to a HELB must be evaluated on a plant-by-plant basis.
Each of the parameters listed above must, be considered.,
Acceptable. engineering methods should be used for this calculation.
Temperature and pressure history may be available from earlier HE).B evalations The radiation.
source terms are discussed under Question 18 below.
Further guidance for selecting the piping systems and conducting the review are delineated in Regulatory Guide 1.46 and Standard Review Plans 3.6. 1 and 3.6.2 The DOR Guidelines and l)UREG-0588 give time and. temperature parameters.
Can we use different values of these parameters?.
Will plant-specific profiles still be with the guidance provided?
For minimum high temperature conditions in pressure-suppression-type containments, we do not require that 340 F for 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> be-used for BWR drywells or that 340 F for 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />, be used for PWR ice condenser lower compartments.
These values. are a screening
- device, per the Guidelines, and can be used'n lieu of a plant-specif'ic profile provided that expected pressure and humidity-conditions as a function of time are accounted for.
In general,. the containment temperature and pressure-conditions as a
function of time should be based on analyses in the FSAR.
- However, these conditions. should bound those expected for coolant and steam Tine breaks inside the containment with due consideration of analytical'ncertainties.
The steam line break condition should include superheated conditions:
the peak temperature, and subsequent temperature/
pressure profile as a function,of time. If containment spray is to be used, the impact of the spray on required equipment should be accounted for.
The adequacy of a plant-specific profile is dependent on the assump-tion and design considerations at the time the profiles were developed.
The DOR guidelines and NUREG-0588 provide guidance and considerations reauired to determine if the plant-specific profiles encompass the LOCA and HELB inside containment.
Could you elaborate on what the staff expects with regard to quality assurance?
If parts or subcomponents are purchased.
from a vendor who does not have a quality assurance
- program, can it be qualified to meet IEEE Std.
323-74 requirements?
The QA programs should. accommodate any increased scope due to the new environmental qualification documentation requirements.
Proce-dures incorporated by the licensee for data acquisition should be documented and available for staff review upon request.
Requirements for QA programs are provided in Part 50, Appendix B,. of the Code of Federal'egulations.
i Part 50, Appendix B of the Code of Federal Regulations states
- that, the applicant/licensee shall be responsible for the establishment and execution of quality assurance programs.
Specifically in purchasing parts or components, it is the responsibility of the licensee/applicant to ensure that the applicable qual.ity assurance procedures for their plant are met.
In determining the qualification status of existing equipment purchased from a vendor, where
- a. QA program did not exist,, the util'ity should consider the fol'iowing:
I.
The complexity of design, complexity of manufacturing
- process, and end use.
2.
Past performance of'endor.
3.
Past operating history of products,, especially similar products, made by vendor.,
4.
Procedures,.equipment, and resul'ts of environmental qualifica-tion testing relative to those f'r other equipment for which a QA program was app'lied.
Define the requirements for "replacement parts."
Are they the same for "spare" parts?
Clearly discuss the alternatives for existing inventories of parts/components.
If equipment is ordered to meet IEEE Std. 323-1974 standard but lea'd time exceeds June
- 1982, can we use IEEE Std. 323-1971 qualified components in the interim?
The requirements for "replacement" and "spare" parts are the same for the purposes of complying with the Commission order and
1 t
I memorandum.
After May 1,980, all parts used to replace presently installed parts shall be qualified to Category I of NUREG-0588 "unless there are sound reasons to the contrary."
Nonavailabi lity and/or the fact that the part to be used as a replacement is a spare par t purchased prior to May 23,
- 1980, and is in stock are among the factors to be considered in weighing whether there are "sound reasons to the contrary."
All'eplacement parts shalT as a minimum conform to the requirements described in the answer to question 3.
Justifica-tion for deviation from Category I or NUREG-0588 shall be documented by the licensee and records shall'e available for audit, upon request by the NRC.
DOR Guidelines,. NUREG-0588 and NUREG-0578, -define-or give guidance for calculating radiation source terms.
However; since one is-more restrictive than the other, which do we use?
Both the DOR guidelines and NUREG-0588 are similar in that they provide the methods for determining the radiation source term 'when considering LOCA events inside containment (100% noble gases/50%
iodine/1% particulates).
These methods consider the radiation source term resulting from an event which completely depressurizes the-primary system and releases the source term inventory to the containment NUREG-0578 provides the radiation-source term to be used. for deter-mining the quaTification doses for equipment in close proximity to recirculting fluid, systems. inside and outside of containment as a
result. of LOCA..
This method considers a
LOCA event in which the primary system may not depressurize and the source term inventory remains in the coolant NUREG-0588 also provides the radiation source term to be used for qualifying equipment foll'owing non-LOCA events both inside and outside containment (10% nobl'e gases/10'1.
iodine/0% particulates).
When developing radiation source terms for equipment qualification,,
the licensee must ensure consideration is given to those events which provide. the most: bounding conditions.
The following table summarizes these considerations:
Outside Containment LOCA NUREG-0578 (100/50/1 in RCS)
NON-LOCA HELB NUREG-0588 (10/10/0 in RCS)
~
~
(p Inside Containment Laraer of NUREG-0588 NUREG-0588 (100/50/1 (10/10/0 in containment) in RCS) ol NUREG-0578 (100/50/1 in RCS)
Can gamma equivalents be used rather than beta exposure for radiation qualification?
Yes.
Gamma, equivalents may be used when consideration of the contri-butions of beta exposure have been included in accordance with the guidance given in the DOR guidelines'nd NUREG-0588.
CobaTt 60 is one acceptable-gamma radiation source for environmental qualification of safety-related equipment.
Cesium 137 may also be. used..
If a piece of equipment will become submerged after completing its required action,. must it be qualified for =submergence?
If the equipment (1) meets the guiadaneh and requirements. of the DOR guidelines or NUREG-0588 for the LOCA and, HELB (small and large breaks) accidents and (2) licensees demonstrate that its failure will not adversely affect any safety-related function or mislead the operator after submergence, the equipment could be considered exempt from that portion (submergence) of qualification.
What qualification is required of Reactor Pressure Vessel internal instrumentation (e.g.,
thermocouples) and new instruments required as. the result of THI Lessons.
Learned?
Tt<I Lessons Learned instrumentation will be considered in the February 1,. 1981. SER.
This equipment is subject to the same require-ments as other safety-related el'ectri'cal equipment.
The guidance and requirements, of. NUREG-0588 referenced. daughter standards, and Reg Guides will be used by the staff in assessing the adequacy of the qualifi'cation information..
The in-core environment should consider the worst source term for radiation effects, the worst humidity for the corresponding temperature,,
and high temperatures consistent with that of a 'damaged core.
Is qualification "by use" an acceptable method (e.g
, CRDN's in BWRs)?
Qualification by use has limited application.
Often the equipment has neve~
seen the harsh environment and no conclusions can be drawn as to its operability in a harsh environment.
Some qualification
~,
~
based on operating experience is a recognized method subject to the requirements of NOREG-0588 and the Guidelines.
Credit can be taken for the natural aging of the equipment and for the location of the equipment or other portions of the overall qualification information.
How long should "long term" equipment be qualified for environmental qualification?
"Long term" for the purpose of aualifying equipment for a harsh environment is variable.
A determination of "long term" for qualifi-cation of equipment should be. based on the-considerations listed below for each postulated accident scenario.
Justification for the
.value used should be provided with the equipment qualification documentation.
1.
The time period over which the equipment is required to bring the plant to cold shutdown and to mitigate the consequences of the accident 2.
The ability to change,, modify or add. equipment during the course of the accident or in mitigating its effects which will provide the same safety-related function.
llhy do we want component surfa'ce. temperature rather than the bulk environment temperature?
Temperature measurements are required, dbring the qualification testing to establish that the component was subjected to the most severe temperature environment postul'ated, to occur.
These temperature measurements.
are required to be made as close to the component surface as practicab'le to ensure that they are representative of the environment in which the, component. is tested.
The surface temperature of the component, aTthough not specifically required, is considered to be a conservative measurement of the test temperature environment..
(
!'