Amend 48 to License NPF-21,revising Tech Spec Table 3.3.2.2, Changing Allowable Temp Range for Trip Setpoint for Trip Function 1.d,primary Containment Isolation & Main Steam Line Tunnel Temp
ML17279A718
Person / Time
Site: Columbia 
(NPF-21-A-048, NPF-21-A-48)
Issue date: 12/04/1987
From: Knighton G
Office of Nuclear Reactor Regulation
To:
Shared Package
ML17279A719 List:
References
TAC-66074, NUDOCS 8712150266
Download: ML17279A718 (5)


Text

I

~p,g REoy, fp.0 Cy

~iflO e

O~

r+

+a*++

UNITEDSTATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 WASHINGTON PUBLIC POWER SUPPLY SYSTEM DOCKET NO. 50-397 WPPSS NUCLEAR PROJECT NO.

2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 48 License No. NPF-21 1.

The Nuclear Regulatory Commission (the Commission or the NRC) has found that:

A.

The application for amendment filed by the Washington Public Power Supply System (the Supply System, also the licensee),

dated September 1,

1987 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's regula-tions set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the regulations of the Commission; C.

There is reasonable assurance:

(i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Corrimission's regulations set forth in 10 CFR Chapter I; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifica-tions as indicated in the enclosure to this license amendment and paragraph 2.C.(2) of the Facility Operating License No. NPF-21 is hereby amended to read as follows:

~vmmo~ss-874204 1

'DR ADOCK 05000397 P

P+R L,

(2)

Technical S ecifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 48, and the Environmental Protection Plan contained in Appendix B, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This amendment is effective as of the date of issuance.

FOR THE NUCLEAR REGULATORY COYiNISSION

Enclosure:

Changes to,the Technical Specifications eorge

. Knighton, irector Projec Di~ectorate V

Division of Reactor Projects - III, IV, V and Special Projects Date of Issuance:

December 4, 1987

t

~

~

~

~

~,

~

~

~ h December 4, 1987 ENCLOSURE TO LICENSE AHENDMENT NO. 48 FACILITY OPERATING LICENSE NO. NPF-21 DOCKET NO. 50-397 Replace the following page of the Appendix "A" Technical Specifications with the enclosed page.

The revised page is identified by Amendment number and contains a vertical line indicating the area of change.

RENOVE 3/4 3-16 INSERT 3/4 3-16

TABLE 3.3.2-2 ISOLATION ACTUATION INSTRUMENTATION SETPOINTS d.

e.

2)

Pressure

- Low 3)

Flow - High Main Steam Line Tunnel Temperature - High Main Steam Line Tunnel b, Temperature - High Condenser Vacuum - Low g.

Manual Initiation 2.

SECONDARY CONTAINMENT ISOLATION TRIP FUNCTION 1.

PRIMARY CONTAINMENT ISOLATION a.

Reactor Vessel Water Level 1)

Low, Level 3

2)

Low Low, Level 2

b.

Drywell Pressure - High c.

Main Steam Line 1)

Radiation - High TRIP SETPOINT

> 13.0 inches*

> -50 inches"

< 1.68 psig

< 3.0 x full power background

> 831 psig

< 105.5 psid

<164F

< 80 F

> 23 inches Hg absolute pressure N.A.

ALLOWABLE VALUE

> 11.0 inches

> -57 inches

< 1.88 psig

< 3.6 x full power background

> 811 psig

< 108 psid

<170F

< 90'F

> 24.5 inches Hg absolute pressure N.A.

a e b.

C.

d.

Reactor Building Vent Exhaust Plenum Radiation - High Drywell Pressure - High Reactor Vessel Water Level -

Low Low, Level 2

Manual Initiation

< 13.0 mR/h

< 1.68 psig

> -50 inches" N.A.

< 16.0 mR/h

< 1.88 psig

> -57 inches N.A.