Discusses Completion of Licensing Action for GL 92-08, Thermo-Lag 330-1 Fire Barriers. NRC Determined That Util Provided Info & Performed Actions Requested in GL & Actions Being Tracked by TAC M85609 Completed
ML17229A962
Person / Time
Site: Saint Lucie 
Issue date: 12/22/1998
From: Hebdon F
NRC (Affiliation Not Assigned)
To: Plunkett T
FLORIDA POWER & LIGHT CO.
References
GL-92-08, GL-92-8, TAC-M85609, NUDOCS 9812310195
Download: ML17229A962 (6)


Text

gP9 REGS+

~o Cy A.

(1 0

c O

IIA O

qO

++*++

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20mi0001

~ Pc7 December 22, 1998 Mr. T. F. Plunkett President - Nuclear Division Florida Power and Light Company P.O. Box 14000 Juno Beach, FL 33408-0420

SUBJECT:

COMPLETION OF LICENSING ACTION FOR GENERIC LE%i ER 92-08, "THERMO-LAG330-1 FIRE BARRIERS," DATED DECEMBER 17, 1992, FOR ST. LUCIE UNIT2 (TAC NO. M85609)

Dear Mr. Plunkett:

By letters dated April 16, 1993, February 11, April29, and November 4, 1994, March 28, and October 27, 1995, February 12, August 27, and December 19, 1996, March 17, 1997, June 23 and June 26, 1998, Florida Power & Light responded to Generic Letter (GL) 92-08, "Thermo-Lag 330-1 Fire Barriers," dated December 17, 1992, and follow-up requests for additional information dated November 5, and December 20, 1993, August 9, and December 28, 1994, and October 9, 1995, and November 6, 1996, regarding Thermo-Lag 330-1 fire barriers installed at St. Lucie Unit 2.

The U.S. Nuclear Regulatory Commission (NRC) staff has reviewed your letters. Your responses stated that the Thermo-Lag corrective actions taken at St. Lucie Unit 2 included verification of properly installed base layers and upgrades that consisted of reinforcement of seams and joints, addition of wire mesh and stress skins, and additional layers of Thermo-Lag 330-1, 770-1, and 770-1 trowel grade finish over base layers, where necessary.

In your letter dated June 23, 1998, you stated that all corrective actions for the resolution of the Thermo-Lag issues had been implemented at St. Lucie Unit 2. On the basis of its review, the staff has determined that you have provided the information and performed the actions requested in GL 92-08 and the actions tracked by TAC No. M85609 are complete.

Based on your letters dated April 16, 1993, February 11, April29, and November 4, 1994, March 28, and October 27, 1995, February 12, August 27, and December 19, 1996, March 17, 1997, June 26 and June 30, 1998, however, there remain open issues involving ampacity derating of Thermo-Lag 330-1 that emerged as a result of the GL 92-08 review. The resolution of these issues, currently under review, are tracked by TAC No. MA3367 for St. Lucie Unit 2.

You should retain all documentation related to the resolution of the concerns with Thermo-Lag 330-1 fire barrier systems for future NRC audits and/or inspections, You should retain all documentation related to the resolution of the concerns with Thermo-Lag 330-1 fire barrier systems for future NRC audits or inspections.

98i23i0i95 3ISi222 PDR ADQCK 05000389 PDR J I".6 $ 1$!f((y NCMCMMMV

T. F. Plunkett Ifyou have any questions regarding this matter, please contact BillGleaves, St. Lucie Project Manager, at (301) 415-1479.

Sincerely, Frederick J. Hebd n, Director Project Directorate II-3 Division of Reactor Projects I/II Office of Nuclear Reactor Regulation Docket No. 50-389 cc: See next page

T. F. Plunkett December 22, 1998 Ifyou have any questions regarding this matter,'lease contact BillGleaves, St. Lucie Project Manager, at (301) 415-1479.

Sincerely,

/s/

Frederick J. Hebdon, Director Project Directorate II-3

, Division of Reactor Projects I/II Office of Nuclear Reactor Regulation Docket No. 50-389 cc: See next page

%3ocOet:FiIH PUBLIC St. Lucie Reading File JZwolinski FHebdon BClayton WGleaves AKugler OGC ACRS DOudinot LPlisco, Rll DOCUMENT NAME: G:)STLUCIE(M85609.WPD To receive a copy of this document. indicate In the botu "C Copy without attachment/enclosure E

Copy with attachment/enclosure N

~ No copy DATE 12/ /98 12/9./98 OFFICE PD2-3:PM g

PD2-3:LA NAME WGleaves ~

BClayton SPLB LMarsh 12/ /98 OFFICIALRECORD COPY EELB JCalvo 12g$ 8 PD2-3:D FHebdon 12/y"/98

It I

Mr. T. F. Plunkett Florida Power and Light Company ST. LUCIE PLANT CC:

Senior Resident Inspector St. Lucie Plant U.S. Nuclear Regulatory Commission P.O. Box 6090 Jensen Beach, Florida 34957 Joe Myers, Director Division of Emergency Preparedness Department of Community Affairs 2740 Centerview Drive Tallahassee, Florida 32399-2100 M. S. Ross, Attorney Florida Power 8 Light Company P.O. Box 14000 Juno Beach, FL 33408-0420 John T. Butler, Esquire Steel, Hector and Davis 4000 Southeast Financial Center Miami, Florida 33131-2398 Mr. Douglas Anderson County Administrator St. Lucie County 2300 Virginia Avenue Fort Pierce, Florida 34982 Mr. WilliamA. Passetti, Chief Department of Health Bureau of Radiation Control 2020 Capital Circle, SE, Bin OC21 Tallahassee, Florida 32399-1741 Regional Administrator Region II U.S. Nuclear Regulatory Commission 61 Forsyth Street, SW., Suite 23T85 Atlanta, GA 30303-3415

/

J. A. Stall, Site Vice President St. Lucie Nuclear Plant 6351.South Ocean Drive Jensen Beach, Florida 34957 Mr. R. G. West Plant General Manager St. Lucie Nuclear Plant 6351 South Ocean Drive Jensen Beach, Florida 34957 Mr. Leonard D. Wert U.S. Nuclear Regulatory Commission 61 Forsyth Street, SW., Suite 23T85 Atlanta, GA 30303-3415 E. J. Weinkam Licensing Manager St. Lucie Nuclear Plant 6351 South Ocean Drive Jensen Beach, Florida 34957 Mr. John Gianfrancesco Manager, Administrative Support and Special Projects P.O. Box 14000 Juno Beach, FL 33408-0420 Mr. Rajiv S. Kundalkar Vice President - Nuclear Engineering Florida Povyer 8 Light Company P.O. Box 14000 Juno Beach, FL 33408-0420 Mr. J. Kammel Radiological Emergency Planning Administrator Department of Public Safety 6000 SE. Tower Drive Stuart, Florida 34997

Ca C

~

I v

~

0 y*