Other: ML17199T383, ML17283A040, ML18135A046, ML18204A242, ML18353A954, ML19044A768, ML19058A216, NRC-2019-0075, Federal Register Notice - License Amendment; Issuance (CAC No. MF8260; EPID L-2016-LLA-0007), SBK-L-16013, License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program, SBK-L-16181, License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program, SBK-L-17101, Update to Reply to a Notice of Violation; EA-16-101 Corrective Action Plan
|
MONTHYEARSBK-L-16013, License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program2016-08-0909 August 2016 License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program Project stage: Other ML16258A0222016-09-19019 September 2016 Supplemental Information Needed for Acceptance of Requested Licensing Action Alkali-Silica Reaction Project stage: Acceptance Review ML16279A0482016-09-30030 September 2016 Supplement to License Amendment Request 16-03 to Revise Current Licensing Basis to Adopt a Methodology for the Analysis of Seismic Category I Structures with Concrete Affected by Alkali-Silica Reaction Project stage: Supplement ML16265A4402016-10-12012 October 2016 Acceptance of Requested Licensing Action Alkali-Silica Reaction Project stage: Acceptance Review SBK-L-16181, License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program2016-12-23023 December 2016 License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program Project stage: Other SBK-L-17101, Update to Reply to a Notice of Violation; EA-16-101 Corrective Action Plan2017-06-16016 June 2017 Update to Reply to a Notice of Violation; EA-16-101 Corrective Action Plan Project stage: Other ML17199T3832017-07-26026 July 2017 Site Visit Report Regarding Regulatory Audit for Alkali Silica Reaction License Amendment Request Project stage: Other ML17214A0852017-08-0404 August 2017 Request for Additional Information Regarding License Amendment Request Related to Alkali-Silica Reaction Project stage: RAI ML17283A0412017-08-24024 August 2017 Enclosure 3 - Licensees Presentation-Seabrook Station, License Amendment Request 16-03 ASR Structural Evaluation Methodology Project stage: Request SBK-L-17156, Response to Request for Additional Information Regarding License Amendment Request 16-03 Related to Alkali-Silica Reaction2017-10-0303 October 2017 Response to Request for Additional Information Regarding License Amendment Request 16-03 Related to Alkali-Silica Reaction Project stage: Response to RAI SBK-L-17155, 8 - Response to Request for Additional Information for the Review of the License Renewal Application - Building Deformation Analyses Related to Concrete Alkali-Silica Reaction2017-10-0303 October 2017 8 - Response to Request for Additional Information for the Review of the License Renewal Application - Building Deformation Analyses Related to Concrete Alkali-Silica Reaction Project stage: Response to RAI ML17283A0402017-10-10010 October 2017 Enclosure 2 - NRCs Presentation Slides-Seabrook Station, License Amendment Request, Stage 3 Methodology Project stage: Other ML17261B2172017-10-11011 October 2017 Request for Additional Information Regarding License Amendment Request Related to Alkali-Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: RAI ML17278A7482017-10-13013 October 2017 Summary of August 24, 2017, Meeting with NextEra Energy Regarding License Amendment Request on Alkali Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Meeting ML17310A1142017-10-17017 October 2017 La - (External_Sender) Name Correction: Summary of August 24, 2017, Meeting with NextEra Energy Regarding License Amendment Request on Alkali Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Meeting ML17310B5402017-11-0303 November 2017 La - (External_Sender) SBK-L-17180 Supplement 58 - Revised Alkali-Silica Reaction Aging Management Program Project stage: Request SBK-L-17180, 8, Revised Alkali-Silica Reaction Aging Management Program2017-11-0303 November 2017 8, Revised Alkali-Silica Reaction Aging Management Program Project stage: Request ML17341A0622017-11-17017 November 2017 NextEra Energy Seabrook Presentation Slides - Seabrook Station ASR Methodology LAR: Structural Deformation - LAR 16-03, Methodology and Responses to Rais D2-D8 - for November 17, 2017, Public Meeting Project stage: Response to RAI SBK-L-17204, Response to Request for Additional Information Regarding License Amendment Request Related to Alkali-Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007)2017-12-11011 December 2017 Response to Request for Additional Information Regarding License Amendment Request Related to Alkali-Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Response to RAI ML17340A1862017-12-14014 December 2017 Summary of November 17, 2017, Meeting with NextEra Energy Regarding License Amendment Request on Alkali Silica Reaction - Requests for Additional Information (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: RAI 05000443/LER-2018-001, Re Pressurizer Safety Valve Outside of Technical Specification Limits Discovered During As-Found Set Point Testing2018-04-0505 April 2018 Re Pressurizer Safety Valve Outside of Technical Specification Limits Discovered During As-Found Set Point Testing Project stage: Request ML18102A0972018-04-12012 April 2018 Commission Memorandum and Order CLI-18-04 Project stage: Request SBK-L-18072, Revised Structures Monitoring Aging Management Program2018-05-18018 May 2018 Revised Structures Monitoring Aging Management Program Project stage: Request ML18135A0462018-05-21021 May 2018 Site Visit Report Regarding Regulatory Audit for License Amendment Request Alkali Silica Reaction License Amendment Request and License Renewal Alkali-Silica Reaction Aging Management Program Review (CAC No. MF8260; EPID L-2016-LLA-007) Project stage: Other SBK-L-18074, Response to Request for Additional Information Regarding License Amendment Request 16-032018-06-0707 June 2018 Response to Request for Additional Information Regarding License Amendment Request 16-03 Project stage: Response to RAI ML17088A6742018-08-17017 August 2018 Request for Withholding Information from Public Disclosure Project stage: Withholding Request Acceptance ML18226A2052018-09-28028 September 2018 Redacted, Submission of Alkali-Silica Reaction License Amendment Request Draft Safety Evaluation to Support Advisory Committee on Reactor Safeguards Review of Seabrook License Renewal (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Draft Approval ML18271A0692018-09-28028 September 2018 Attachment 2 NRC Staff Draft Safety Evaluation (Non-Proprietary) Project stage: Request ML18330A0812018-11-14014 November 2018 La - Seabrook Station, Unit No. 1: Integrated Inspection Report 05000443/2018003 Project stage: Request ML18348A9512018-12-14014 December 2018 License Renewal Application: Review of Licensee Program Addressing Alkali-Silica Reaction Project stage: Approval ML18353A9542018-12-19019 December 2018 Report on the Safety Aspects of the License Renewal Application for the Seabrook Station, Unit 1 Project stage: Other ML19011A3562019-01-11011 January 2019 Board Notification Project stage: Request ML19022A4002019-01-22022 January 2019 NRC Staff Board Notification Project stage: Request ML19044A7682019-02-13013 February 2019 Emergency Petition by C-10 Research and Education Foundation for Exercise of Commissions Supervisory Authority to Reverse No Significant Hazards Determination and Immediately Suspend License Amendment and License Renewal Decisions Project stage: Other ML19056A4772019-02-13013 February 2019 Transcript of Public Meeting on the Seabrook Alkali Silica Reaction (ASR) License Amendment Request and License Renewal Application, February 13, 2019, Pages 1-158 Project stage: Meeting ML19050A3202019-02-13013 February 2019 Package from Stephen B. Comley, Sr. at February 13, 2019 Seabrook Station, Unit 1, Public Meeting Project stage: Request ML19042A1102019-02-13013 February 2019 Presentation Slides - 2019 Seabrook Public Meeting Project stage: Request ML19056A5862019-02-25025 February 2019 NextEras Answer Opposing C-10 Emergency Petition Project stage: Request ML19056A5882019-02-25025 February 2019 NRC Staff Answer to C-10s Emergency Petition Project stage: Request ML19046A3832019-02-26026 February 2019 Meeting Summary of February 13, 2019, Public Meeting in Hampton, New Hampshire Alkali-Silica Reaction License Amendment Request and License Renewal Application Project stage: Meeting ML19057A3832019-03-0404 March 2019 Renewal of Full-Power Operating License for Seabrook Station, Unit No. 1 Project stage: Request ML19058A2162019-03-0404 March 2019 Update to Proposed Issuance of a Final No Significant Hazards Consideration Determination and License Amendment Regarding Which a Hearing Has Been Requested (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Other ML19015A1832019-03-11011 March 2019 Notice of Issuance of License Amendment to Facility Operating License No. NPF-86 (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Approval ML18204A2422019-03-12012 March 2019 Federal Register Notice - License Amendment; Issuance (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Other NRC-2019-0075, Federal Register Notice - License Amendment; Issuance (CAC No. MF8260; EPID L-2016-LLA-0007)2019-03-12012 March 2019 Federal Register Notice - License Amendment; Issuance (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Other ML19205A3942019-07-24024 July 2019 NRC046 - Summary of August 24, 2017, Meeting with NextEra Energy Regarding License Amendment Request on Alkali Silica Reaction (CAC No. MF8260; EPID l-2016-lla-0007) (Oct. 13, 2017) Project stage: Meeting 2018-11-14
[Table View] |
Text
June 16, 2017 10 CFR 54 Docket No. 50-443 SBK-L-17101 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555-0001 Seabrook Station Update to Reply to a Notice of Violation; EA-16-101 Corrective Action Plan
References:
- 1.
Seabrook Station, Inspection Report 05000443/2016008 Related to Alkali-Silica Reaction Affects on Safety-Related Concrete Structures and Notice of Violation (Accession Number ML16127A155)
- 2.
NextEra Energy Seabrook, LLC letter SBK-L-16076, Reply to a Notice of Violation; EA-16-101, August 1, 2016 (Accession Number ML16161A534)
- 3.
NRC, Seabrook Station, Unit No. 1 -Acceptance Of Requested Licensing Amendment Action Re: Alkali-Silica Reaction (CAC No. MF8260), October 12, 2016 (Accession Number ML16265A440)
In Reference 1, the staff cited in a Notice of Violation a violation of very low safety significance (Green) related to the timely update of initial and prompt operability determinations when new information is received.
Reference 2, Attachment 2, provided a comprehensive and integrated ASR corrective action plan for resolving ASR-induced non-conformances with the current licensing basis. Based on the complexity of performing the building susceptibility evaluations and the current Staff schedule for review of LAR 16-03 (Reference 3) actions related to these items will require more time than initially expected.
Attached is the corrective action plan with revised completion dates for items 4 and 5. If there are any questions regarding this letter, please contact Mr. Kenneth Browne, Licensing Manager, at (603) 773-7932.
NextEra Energy Seabrook, LLC PO Box 300, Seabrook, NH 03874
United States Nuclear Regulatory Commission SB.K-t-17iQ_L/Page 2 Sincerely, NextEra Energy Seabrook, LLC cc:
NRC Region I Administrator NRC Project Manager NRC Senior Resident Inspector
Attachment to SBK-L-17101
SBK-L-17101 Attachment Page 1 of 1 A comprehensive and integrated ASR corrective action plan for resolving ASR induced non-conformances with the current licensing basis and the date when the structures monitoring program will be revised to monitor the progression of ASR degradation related to bulk expansion and deformation:
- 1. Submit a License Amendment Request to reconcile current licensing basis to address ASR impacts on structures inclusive of a methodology change for evaluating structural deformation of Seismic Category 1 structures. Complete
- 2. Revise ASR Structures Monitoring Program to include ASR induced deformation effects monitoring and methodology. Complete
- 3. Conduct Core Bore Sampling and Installation of extensometers to monitor out of plane expansion in various plant locations to be representative of plant structures conditions and to allow monitoring of levels of ASR. Complete
- 4. Perform Susceptibility Evaluations on all Seismic Category 1 structures in a risk ranked progression order. Due Date: June 30, 2018
- 5. Complete Final Detailed Analysis Calculations of record for all Required Structures for ACI Code 318-71 Compliance. Due Date: August 31, 2018 Note:
As shown in reference 3 the staff has projected a twenty two month review schedule for LAR 16-03. The final calculation of record is dependent on the completion of this review and acceptance of the proposed methodology change.