Letter Sequence Approval |
|---|
CAC:MF8260, (Approved, Closed) EPID:L-2016-LLA-0007, Enclosure 3 - Licensees Presentation-Seabrook Station, License Amendment Request 16-03 ASR Structural Evaluation Methodology (Approved, Closed) |
Initiation
- Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request, Request
- Acceptance, Acceptance
- Supplement
Results
Other: ML17199T383, ML17283A040, ML18135A046, ML18204A242, ML18353A954, ML19044A768, ML19058A216, NRC-2019-0075, Federal Register Notice - License Amendment; Issuance (CAC No. MF8260; EPID L-2016-LLA-0007), SBK-L-16013, License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program, SBK-L-16181, License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program, SBK-L-17101, Update to Reply to a Notice of Violation; EA-16-101 Corrective Action Plan
|
MONTHYEARSBK-L-16013, License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program2016-08-0909 August 2016 License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program Project stage: Other ML16258A0222016-09-19019 September 2016 Supplemental Information Needed for Acceptance of Requested Licensing Action Alkali-Silica Reaction Project stage: Acceptance Review ML16279A0482016-09-30030 September 2016 Supplement to License Amendment Request 16-03 to Revise Current Licensing Basis to Adopt a Methodology for the Analysis of Seismic Category I Structures with Concrete Affected by Alkali-Silica Reaction Project stage: Supplement ML16265A4402016-10-12012 October 2016 Acceptance of Requested Licensing Action Alkali-Silica Reaction Project stage: Acceptance Review SBK-L-16181, License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program2016-12-23023 December 2016 License Renewal Application Relating to the Alkali-Silica Reaction Monitoring Program Project stage: Other SBK-L-17101, Update to Reply to a Notice of Violation; EA-16-101 Corrective Action Plan2017-06-16016 June 2017 Update to Reply to a Notice of Violation; EA-16-101 Corrective Action Plan Project stage: Other ML17199T3832017-07-26026 July 2017 Site Visit Report Regarding Regulatory Audit for Alkali Silica Reaction License Amendment Request Project stage: Other ML17214A0852017-08-0404 August 2017 Request for Additional Information Regarding License Amendment Request Related to Alkali-Silica Reaction Project stage: RAI ML17283A0412017-08-24024 August 2017 Enclosure 3 - Licensees Presentation-Seabrook Station, License Amendment Request 16-03 ASR Structural Evaluation Methodology Project stage: Request SBK-L-17156, Response to Request for Additional Information Regarding License Amendment Request 16-03 Related to Alkali-Silica Reaction2017-10-0303 October 2017 Response to Request for Additional Information Regarding License Amendment Request 16-03 Related to Alkali-Silica Reaction Project stage: Response to RAI SBK-L-17155, 8 - Response to Request for Additional Information for the Review of the License Renewal Application - Building Deformation Analyses Related to Concrete Alkali-Silica Reaction2017-10-0303 October 2017 8 - Response to Request for Additional Information for the Review of the License Renewal Application - Building Deformation Analyses Related to Concrete Alkali-Silica Reaction Project stage: Response to RAI ML17283A0402017-10-10010 October 2017 Enclosure 2 - NRCs Presentation Slides-Seabrook Station, License Amendment Request, Stage 3 Methodology Project stage: Other ML17261B2172017-10-11011 October 2017 Request for Additional Information Regarding License Amendment Request Related to Alkali-Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: RAI ML17278A7482017-10-13013 October 2017 Summary of August 24, 2017, Meeting with NextEra Energy Regarding License Amendment Request on Alkali Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Meeting ML17310A1142017-10-17017 October 2017 La - (External_Sender) Name Correction: Summary of August 24, 2017, Meeting with NextEra Energy Regarding License Amendment Request on Alkali Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Meeting ML17310B5402017-11-0303 November 2017 La - (External_Sender) SBK-L-17180 Supplement 58 - Revised Alkali-Silica Reaction Aging Management Program Project stage: Request SBK-L-17180, 8, Revised Alkali-Silica Reaction Aging Management Program2017-11-0303 November 2017 8, Revised Alkali-Silica Reaction Aging Management Program Project stage: Request ML17341A0622017-11-17017 November 2017 NextEra Energy Seabrook Presentation Slides - Seabrook Station ASR Methodology LAR: Structural Deformation - LAR 16-03, Methodology and Responses to Rais D2-D8 - for November 17, 2017, Public Meeting Project stage: Response to RAI SBK-L-17204, Response to Request for Additional Information Regarding License Amendment Request Related to Alkali-Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007)2017-12-11011 December 2017 Response to Request for Additional Information Regarding License Amendment Request Related to Alkali-Silica Reaction (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Response to RAI ML17340A1862017-12-14014 December 2017 Summary of November 17, 2017, Meeting with NextEra Energy Regarding License Amendment Request on Alkali Silica Reaction - Requests for Additional Information (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: RAI ML18058A1142018-02-27027 February 2018 NRR E-mail Capture - Site Visit Plan for the Week of March 19th Project stage: Other 05000443/LER-2018-001, Re Pressurizer Safety Valve Outside of Technical Specification Limits Discovered During As-Found Set Point Testing2018-04-0505 April 2018 Re Pressurizer Safety Valve Outside of Technical Specification Limits Discovered During As-Found Set Point Testing Project stage: Request ML18102A0972018-04-12012 April 2018 Commission Memorandum and Order CLI-18-04 Project stage: Request ML18113A5292018-04-18018 April 2018 NRR E-mail Capture - Draft - Request for Additional Information Regarding ASR Amendment Request Project stage: Draft RAI ML18121A3992018-05-0101 May 2018 NRR E-mail Capture - Request for Additional Information Regarding ASR Amendment Request Project stage: RAI SBK-L-18072, Revised Structures Monitoring Aging Management Program2018-05-18018 May 2018 Revised Structures Monitoring Aging Management Program Project stage: Request ML18135A0462018-05-21021 May 2018 Site Visit Report Regarding Regulatory Audit for License Amendment Request Alkali Silica Reaction License Amendment Request and License Renewal Alkali-Silica Reaction Aging Management Program Review (CAC No. MF8260; EPID L-2016-LLA-007) Project stage: Other SBK-L-18074, Response to Request for Additional Information Regarding License Amendment Request 16-032018-06-0707 June 2018 Response to Request for Additional Information Regarding License Amendment Request 16-03 Project stage: Response to RAI ML17088A6742018-08-17017 August 2018 Request for Withholding Information from Public Disclosure Project stage: Withholding Request Acceptance ML18226A2052018-09-28028 September 2018 Redacted, Submission of Alkali-Silica Reaction License Amendment Request Draft Safety Evaluation to Support Advisory Committee on Reactor Safeguards Review of Seabrook License Renewal (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Draft Approval ML18271A0692018-09-28028 September 2018 Attachment 2 NRC Staff Draft Safety Evaluation (Non-Proprietary) Project stage: Request ML18330A0812018-11-14014 November 2018 La - Seabrook Station, Unit No. 1: Integrated Inspection Report 05000443/2018003 Project stage: Request ML18348A9512018-12-14014 December 2018 License Renewal Application: Review of Licensee Program Addressing Alkali-Silica Reaction Project stage: Approval ML18353A9542018-12-19019 December 2018 Report on the Safety Aspects of the License Renewal Application for the Seabrook Station, Unit 1 Project stage: Other ML19011A3562019-01-11011 January 2019 Board Notification Project stage: Request ML19022A4002019-01-22022 January 2019 NRC Staff Board Notification Project stage: Request ML19050A4602019-02-13013 February 2019 Handouts from the Public at the February 13, 2019, Seabrook ASR Public Meeting Project stage: Meeting ML19042A1102019-02-13013 February 2019 Presentation Slides - 2019 Seabrook Public Meeting Project stage: Request ML19044A7682019-02-13013 February 2019 Emergency Petition by C-10 Research and Education Foundation for Exercise of Commissions Supervisory Authority to Reverse No Significant Hazards Determination and Immediately Suspend License Amendment and License Renewal Decisions Project stage: Other ML19050A3202019-02-13013 February 2019 Package from Stephen B. Comley, Sr. at February 13, 2019 Seabrook Station, Unit 1, Public Meeting Project stage: Request ML19056A4772019-02-13013 February 2019 Transcript of Public Meeting on the Seabrook Alkali Silica Reaction (ASR) License Amendment Request and License Renewal Application, February 13, 2019, Pages 1-158 Project stage: Meeting ML19056A5862019-02-25025 February 2019 NextEras Answer Opposing C-10 Emergency Petition Project stage: Request ML19056A5882019-02-25025 February 2019 NRC Staff Answer to C-10s Emergency Petition Project stage: Request ML19046A3832019-02-26026 February 2019 Meeting Summary of February 13, 2019, Public Meeting in Hampton, New Hampshire Alkali-Silica Reaction License Amendment Request and License Renewal Application Project stage: Meeting ML19058A2162019-03-0404 March 2019 Update to Proposed Issuance of a Final No Significant Hazards Consideration Determination and License Amendment Regarding Which a Hearing Has Been Requested (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Other ML19057A3832019-03-0404 March 2019 Renewal of Full-Power Operating License for Seabrook Station, Unit No. 1 Project stage: Request ML19015A1832019-03-11011 March 2019 Notice of Issuance of License Amendment to Facility Operating License No. NPF-86 (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Approval ML18204A2912019-03-11011 March 2019 Issuance of Amendment No. 159 Methodology for Analysis of Seismic Category I Structures with Concrete Affected by Alkali-Silica Reaction Project stage: Approval ML18204A2422019-03-12012 March 2019 Federal Register Notice - License Amendment; Issuance (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Other NRC-2019-0075, Federal Register Notice - License Amendment; Issuance (CAC No. MF8260; EPID L-2016-LLA-0007)2019-03-12012 March 2019 Federal Register Notice - License Amendment; Issuance (CAC No. MF8260; EPID L-2016-LLA-0007) Project stage: Other 2018-12-14
[Table View] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 March 12, 2019 Mr. Mano Nazar President and Chief Nuclear Officer Nuclear Division NextEra Energy Seabrook, LLC Mail Stop: EX/JB 700 Universe Blvd.
Juno Beach, FL 33408
SUBJECT:
SEABROOK STATION, UNIT NO. 1 -NOTICE OF ISSUANCE OF LICENSE AMENDMENT TO FACILITY OPERA TING LICENSE NO. NPF-86 (CAC NO. MF8260; EPID L-2016-LLA-0007)
Dear Mr. Nazar:
The U.S. Nuclear Regulatory Commission has forwarded the enclosed Notice of Issuance of Amendment to Facility Operating License No. NPF-86 to the Office of the Federal Register for publication.
The amendment consists of changes to the license in response to your application dated August 1, 2016, as supplemented by letters dated September 30, 2016; October 3, 2017; October 17, 2017; December 11, 2017; and June 7, 2018. The amendment revises the Updated Final Safety Analysis Report to adopt a methodology for the analysis of seismic Category I structures with concrete affected by alkali-silica reaction.
If you have any questions, please contact me at 301-415-2048 or Justin.Poole@nc.gov.
Sincerely,
~-* -
/
~~,r
..... ~.........,
Docket No. 50-443
Enclosure:
Notice of Issuance of License Amendment cc: Listserv Justin C. Poole, Project Manager Plant Licensing Branch I Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
NUCLEAR REGULATORY COMMISSION
[Docket No. 50-443; NRC-2019-0075)
NextEra Energy Seabrook, LLC; Seabrook Station, Unit No. 1 AGENCY: Nuclear Regulatory Commission.
ACTION: License amendment; issuance.
[7590-01-P]
SUMMARY
- The U.S. Nuclear Regulatory Commission (NRC) has issued an amendment to Facility Operating License No. NPF-86, issued to NextEra Energy Seabrook, LLC, for operation of the Seabrook Station, Unit No. 1. The amendment revised the Facility Operating License and Updated Final Safety Analysis Report to adopt a methodology for the analysis of seismic Category I structures with concrete affected by alkali-silica reaction.
DATE: The amendment was issued on March 11, 2019.
ADDRESSES: Please refer to Docket ID NRC-2019-0075 when contacting the NRC about the availability of information regarding this document. You may obtain publicly-available information related to this document using any of the following methods:
Federal Rulemaking Web Site: Go to http://www.regulations.gov and search for Docket ID NRC-2019-0075. Address questions about NRC Docket IDs in Regulations.gov to Krupskaya Castellon; telephone: 301-287-9221; e-mail:
Krupskaya.Castellon@nrc.gov. For technical questions, contact the individual listed in the FOR FURTHER INFORMATION CONTACT section of this document.
NRC's Agencywide Documents Access and Management System (ADAMS): You may obtain publicly-available documents online in the ADAMS Public Documents collection at http://www.nrc.gov/reading-rm/adams.html. To begin the search, select "Begin Web-based ADAMS Search." For problems with ADAMS, please
contact the NRC's Public Document Room (PDR) reference staff at 1-800-397-4209, 301-415-4737, or by e-mail to pdr.resource@nrc.gov. The ADAMS accession number for each document referenced in this document (if that document is available in ADAMS) is provided the first time that a document is referenced.
NRC's PDR: You may examine and purchase copies of public documents at the NRC's PDR, Room 01-F21, One White Flint North, 11555 Rockville Pike, Rockville, Maryland 20852.
FOR FURTHER INFORMATION CONTACT: Justin C. Poole, U.S. Nuclear Regulatory Commission, Washington DC 20555-0001; telephone: 301-415-2048, e-mail:
Justin. Poole@nre.gov.
SUPPLEMENTARY INFORMATION:
The NRC has issued Amendment No.159 to NextEra Energy Seabrook, LLC, which revised the Facility Operating License and Updated Final Safety Analysis Report for operation of the Seabrook Station, Unit No. 1, located in Rockingham County, New Hampshire. A publicly-available version is available in ADAMS under Accession No. ML18204A291. Documents related to this amendment are listed in the safety evaluation enclosed with the amendment. The amendment was effective as of the date of its issuance.
The application for the amendment complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations. The Commission has made appropriate findings as required by the Act and the Commission's rules and regulations in chapter I of title 10 of the Code of Federal Regulations ( 10 CFR), which are set forth in the license amendment.
2
A Notice of Consideration of Issuance of Amendment and Proposed No Significant Hazards Consideration Determination and Opportunity for Hearing in connection with this action was published in the Federal Register on February 7, 2017 (82 FR 9604). A request for a hearing was filed on April 10, 2017, by C-10 Research and Education Foundation, Inc.
Under its regulations, the Commission may issue and make an amendment immediately effective, notwithstanding the pendency before it of a request for a hearing from any person, in advance of the holding and completion of any required hearing, where it has determined that no significant hazards consideration is involved.
The Commission has applied the standards of 10 CFR 50.92 and has made a final determination that the amendment involves no significant hazards consideration.
The basis for this determination is contained in the safety evaluation related to this action. Accordingly, as described above, the amendment has been issued and made immediately effective and any hearing will be held after issuance.
The Commission has determined that this amendment satisfies the criteria for categorical exclusion in accordance with 1 O CFR 51.22. Therefore, pursuant to 1 O CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared for this amendment.
3
For further details with respect to this action, see the application for amendment dated August 1, 2016 (ADAMS Package Accession No. ML16216A250), as supplemented by letters dated September 30, 2016; October 3, 2017; October 17, 2017; December 11, 2017; and June 7, 2018 (ADAMS Accession Nos. ML16279A047 (Package), ML17277A337, ML17291B136, ML17345A641, and ML18158A540, respectively).
Dated at Rockville, Maryland, this 121h day of March, 2019.
For the Nuclear Regulatory Commission.
IRA/
Justin C. Poole, Project Manager, Plant Licensing Branch I, Division of Operating Reactor Licensing, Office of Nuclear Reactor Regulation.
4
SUBJECT:
SEABROOK STATION, UNIT NO. 1 - NOTICE OF ISSUANCE OF LICENSE AMENDMENT TO FACILITY OPERATING LICENSE NO. NPF-86 (CAC NO. MF8260; EPID L-2016-LLA-0007) DATED MARCH 12, 2019 DISTRIBUTION:
PUBLIC PM File Copy RidsACRS_MailCTR Resource RidsNrrDorllpl1 Resource RidsNrrLALRonewicz Resource RidsRgn1 MailCenter Resource RidsNrrPMSeabrook Resource ADAMS A ccess1on N LTR ML19015A183 FRN ML18204A242
>v e-ma1 OFFICE DORL/LPL 1 /PM DORL/LPL 1 /LA OGC-NLO*
DORL/LPL 1/BC DORL/LPL 1 /PM NAME JPoole LRonewicz JWachutka JDanna JPoole DATE 01/15/2019 01/15/2019 01/03/2019 03/11/2019 03/12/2019 OFFICIAL RECORD COPY!