ML17130A969
| ML17130A969 | |
| Person / Time | |
|---|---|
| Site: | Prairie Island (DPR-042, DPR-060) |
| Issue date: | 05/08/2017 |
| From: | Northard S Northern States Power Company, Minnesota, Xcel Energy |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML17130A980 | List: |
| References | |
| L-Pl-17-018 | |
| Download: ML17130A969 (19) | |
Text
1717 Wakonade Drive Welch, MN 55089 800.895.4999 xcelenergy.com MAY 0 8 2017 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Prairie Island Nuclear Generating Plant, Units 1 and 2 Docket Nos. 50-282 and 50-306 Renewed Operating License Nos. DPR-42 and DPR-60
(},, Xcel Energy*
R ES P 0 NS I B LE B Y NAT U R E L-Pl-17-018 TS 5.5.1.c TS 5.6.3 2016 Annual Radioactive Effluent Report and Offsite Dose Calculation Manual Pursuant to the applicable Prairie Island Nuclear Generating Plant (PINGP) Technical Specifications (TS), Appendix A to Renewed Operating Licenses DPR-42 and DPR-60, and the requirements of the Offsite Dose Calculation Manual (ODCM), Northern States Power Company, a Minnesota corporation, doing business as Xcel Energy (hereafter "NSPM"),
submits the 2016 Annual Radioactive Effluent Report which is comprised of the following: contains the Off-Site Radiation Dose Assessment for the period January 1, 2016, through December 31, 2016, in accordance with ODCM sections 8.1.1c, d, e, f, g, h, i, j, k, m and n.
' contains the Annual Radioactive Effluent Report, Supplemental Information, for the period January 1, 2016, through December 31, 2016, in accordance with TS 5.6.3 and ODCM section 8.1.1 b. contains a complete and legible copy of the entire ODCM revision 30, issued on 2/27 /2016, in accordance with ODCM section 8.1.11. contains a complete and legible copy of the entire ODCM revision 31, issued on 10/13/2016, in accordance with ODCM section 8.1.11.
On May 4, 2016, PINGP identified a potential issue regarding the operability of the Waste Gas Holdup System Gas (Oxygen) Monitors listed in ODCM Table 3.2. This issue has been entered into the PINGP Corrective Action Program for evaluation. Evaluation identified errata data for 2014 and 2015 Annual Radioactive Effluent Reports, in the form of omission of reporting of operability, in accordance with ODCM section 8.1.1 h. The errata data is reported with this submittal and in accordance with ODCM section 8.7 guidance for reporting of errata data.
- Document Control Desk Page 2 Summary of Commitments This letter makes no new commitments and no revisions to existing commitments.
&ritJ~
Scott Northard Vice President, Prairie Island Nuclear Generating Plant Northern States Power Company - Minnesota Enclosures (4) cc:
Regional Administrator, USNRC, Region Ill Project Manager, Prairie Island Nuclear Generating Plant, USN RC, NRR NRC Resident Inspector - Prairie Island Nuclear Generating Plant Department of Health, State of Minnesota Pl Dakota Community Environmental Coordinator
ENCLOSURE 1 OFF-SITE RADIATION DOSE ASSESSMENT January 1, 2016 - December 31, 2016 7 pages to follow
PRAIRIE ISLAND NUCLEAR GENERA TING PLANT OFF-SITE RADIATION DOSE ASSESSMENT FOR January 1, 2016-December31, 2016 Page 1of7 An Assessment of the radiation dose due to releases from Prairie Island Nuclear Generating Plant during 2016 was performed, in accordance with the Offsite Dose Calculation Manual, arid as required by Technical Specifications. Computed doses were well below the 40 CFR Part 190 Standards and 10 CFR Part 50 Appendix I Guidelines.
Off-site dose calculation formulas and historical meteorological data were used in making this assessment. Source terms were obtained from the Annual Radioactive Effluent and Waste Disposal Report and prepared for NRG review, for the. year of 2016.
OFFSITE DOSES FROM GASEOUS RELEASE:
Computed doses due to gaseous releases are reported in Table 1.
Critical receptor location and pathways for organ doses are reported in Table 2. Gaseous release doses are a small percentage of Appendix I Guidelines.
OFFSITE DOSES FROM LIQUID RELEASE:
Computed doses due to liquid releases are reported in Table 1.
Critical receptor information is reported in Table 2. Liquid release doses, both whole body and organ, are a small percentage of Appendix I Guidelines.
DOSES TO INDIVIDUALS DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY:
- Occasionally sportsmen enter the Prairie Island Site Boundary for recreational activities.
These individuals are not expeded to spend more than a few hours per year within the site boundary. Commercial and recreational river traffic exists through this area, For purposes of estimating the dose, due to recreational and river water transportation activities within the site boundary, it is assumed that the limiting dose within the site boundary would be received by an individual who spends a total of seven days per year on the river just off-shore from the plant buildings (ESE at 0.2 miles). The gamma dose from noble gas releases and the whole body and organ doses from the inhalation pathway due to Iodine 131, lodine-133, tritium, long-lived particulates and Carbon-14 were calculated for this location and occupancy time. These doses are reported in Table 1.
Critical Receptor location and pathways for organ doses are reported in Table 2.
Page 2of7 ABNORMAL RELEASES
- There were no (0) abnormal releases for 2016.
40 CFR 190 COMPLIANCE REMP environmental TLD results for 2016 were reviewed 'perANSl/HPS N13.37-2014 methodology for determining any plant effect above ambient gamma radiation measurements. All measurements ar~ considered to be within the range of variations in natural background radiation.
Neutron sky shine dose from the ISFSI was evaluated. The maximum sky shine dose was determined to be 0.71 mrem; to the nearest resident, at 724 meters from the ISFS(
Neutron sky shine dose is greater than the effluent dose to the Critical Receptor, therefore, 40 CFR 190 compliance was evaluated to the location of the maximum neutron sky shine dose.
The 40CFR190 evaluation location was determined to be 0.7 miles west ofthe plant.
Dose due to gaseous effluents were calculated to the 40 CFR 190 evaluation location.
Gamma Direct Radiation Dose:
Neutron sky shine Dose:
Garrima Air Dose:
Beta Air Dose:
lodrne, particulate, H-3 and C-14 Dose:
O.OOE+OO MREM 7.10E-01 MREM 2.0SE-12 MREM 1.37E-11 MREM 1.04E-02 MREM*
- Calculated values identical for Whole Body, Thyroid and Maximum "Other" Organs 40CFR190 DOSE EVALUATION:
40CFR190 LIMIT 40CFR 190 DOSE (MREM)
(MREM)
WHOLE BODY 25 7.20E-01 THYROID 75 7.20E-01 OTHER ORGANS 25 7.20E-01 (TEEN - WHOLE BODY)
I SAMPLING, ANALYSIS AND LLD REQUIREMENTS The lower limit of detection (LLD) requirements, as specified in ODCM Table 2.11 and 3.1 were met for 2016. The minimum sampling frequency requirements, as specified in ODCM Table 2.1 and 3.1 were met for 2016.
.Page 3 of 7
. MONITORING INSTRUMENTATION For 2016, there was one (1) occurrence, when less than the minimum required radioactive liquid and/or gaseous effluent monitoring instrumentation channels were operable, as required by ODCM Tables 2.2 and 3.2.
From 1/24/16 to 4/14/16, less than the minimum channels required for Explosive Gas Monitoring Instrumentation were available, as specified in H4, Offsite Dose Calculation Manual.
Special Report L-16-058 was submitted to NRG on July22, 2016. An apparent cause evaluation was initiated.
- The apparent cause evaluation found that a lack of clarity between the ODCM, Administrative Work 1.nstructions and Operations Procedures was the cause.
Actions were initiated to clarify requirements.
DOSES TO INDIVIDUALS DUE TO EFFLUENT RELEASES FROM THE INDEPENDENT SPENT FUEL STORAGE FACILITY (ISFSI):
Zero (0) fuel casks were loaded and placed in the storage facility during the 2016 calendar year. The total number of casks in the ISFSI, as of 12/31/16, was forty (40).
. There were no (0) releases of radioactive effluents from the ISFSI.
CURRENT OFFSITE DOSE CALCULATIONS MANUAL (ODCM) REVISION:
The Offsite Dose Calculation Manual was revised two (2) times in 2016. Revision 30 is dated February 27, 2016. Revision 31 is dated October 13, 2016. Both revisions are
- submitted with this report:
CRITICAL RECEPTOR Based on the Annual Land Use Census*, the critical receptor did change. The critical receptor is defined as The Suter Residence, at 0.6 miles, in fhe SSE sector.
2016 is evaluated using the Critical Receptor identification of the Glazier Residence,. at 0.6 miles in the NNW sector.
2017 will.be evaluated using the newly identified Critical Receptor identification of the Suter Residence, at 0.6 miles in the SSE direction.
. Page 4of7 ERRATA DATA:
For 2014, ~here was one (1) occurrence, when less than the minimum required radioactive liquid and/or gaseous effluent monitoring instrumentation channels were
. operable, as required by ODCM Tables 2.2 and 3.2.
For 2015, there was one (1) occurrence, when less than the minimum reqLJired radioactive liquid and/or gaseous effluent monitoring instrumentation channels were operable, as required by ODCM Tables 2.2 and 3.2.
These out of service periods were incorrectly omitted from their respective annual reports.
From 9/25/14 to 10/26/14 and from 7/12/15 to 8/18/15, less than the minimum channels required for Explosive Gas Monitoring Instrumentation were available, as specified in H4, Offsite Dose Calculation Manual.
Special Report L-16-058 was submitted to NRC on July 22, 2016. An apparent cause evaluation was initiated.
The apparent cause evaluation found that a lack of clarity between the ODCM, Administrative Work Instructions and Operations Procedures was the cause.
Actions were initiated to clarify requirements.
- ERRATA DATA:
The volume fdr the geometry employed in the evaluation of noble gas samples was
- inaccurate. This value is canned in the software and the inaccuracy went undetected for an extended period of time.
The inaccuracy would have generated results with a conservatively high bias. No underreporting occurred.
Inaccurate reporting of dose equated to significantly less than 1 % of the applicable 10 CFR 50 Appendix I design objectives and significantly less than 1 % of the EPA public dose criterion. Over reporting did NOT impede Prairie Island's ability to adequately assess the information supplied.
Corrective actions have been implemented.
INDUSTRY INITIATIVE ON GROUND WATER PROTECTION:
There was zero (0) events for inclusion in the Annual Effluent Report, as part of the NEI Ground Water Initiative.
Page 5of7 LOW LEVEL WASTE DISPOSAL ANNUAL REPORT SOLID WASTE AND IRRADIATED COMPONENTS SHIPMENTS PERIOD: 1/1/16 TO 12/31/16 LICENSE NUMBER: DPR-42/60 SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (NOT IRRADIATED FUEL):
Resins, Filters and Volume Evaporator Bottoms Waste Class FT3
. M3 A
2.91E+02 8.25E+OO B
4.37E+02 1.24E+01 c
O.OOE+OO O.OOE+OO ALL 7.29E+02 2.06E+01 Major Nuclides.
H-3, Mn-54, Fe-55, Co-57, Co-58, Co-60, Ni-63, Sb-125, Cs-137 Dry Active Waste Volume Waste Class FT3 M3 A
2.82E+04 7.97E+02 8
O.OOE+OO O.OOE+OO c
O.OOE+OO O.OOE+OO ALL 2.82E+04 7.97E+02 Major Nuclides Fe-55, Co-58, Co-60,.Ni-63, Zr-95, Nb-95 Irradiated Components Volume Waste Class FT3 M3 A
O.OOE+OO O.OOE+OO 8
O.OOE+OO O.OOE+OO c
O.OOE+OO O.OOE+OO ALL O.OOE+OO O.OOE+OO Major Nuclides Other Waste Volume Waste Class FT3 M3 A
O.OOE+OO O.OOE+OO 8
O.OOE+OO O.OOE+OO c
O.OOE+OO O.OOE+OO ALL O.OOE+OO O.OOE+OO Major Nuclides Sum of All Low Level Waste Volume Shipped from Site Waste Class FT3 M3 A
2.85E+04 8.06E+02 8
4.37E+02 1.24E+01 c
O.OOE+OO O.OOE+OO ALL 2.89E+04 8.18E+02 Major Nuclides Mn-54, Fe-55, Co-58, Co-60, Ni-63, Zr-95, Nb-95, Sb-125, Cs-137 PROCESS CONTROL PROGRAM Curies Shipped Curies 1.93E-01 2.00E+02 O.OOE+OO 2.00E+02 Curies Shipped Curies 2.76E-01 O.OOE+OO O.OOE+OO 2.76E-01 Curies Shipped Curies O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO Curies Shipped Curies O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO Curies Shipped Curies 4.68E-01 2.00E+02 O.OOE+OO 2.00E+02 The Process Control Program for Solidification/Dewatering of Radioactive Waste from Liquid Systems (D 59) was not revised in 2016. Current manual revision is 11. The revision date is October 23, 2014. Revision 11 was submitted with the 2014 report.
Page 6of7 Table 1 OFF-SITE RADIATION DOSE ASSESSMENT - PRAIRIE ISLAND PERIOD: JANUARY 2016 through DECEMBER 2016.
Gaseous Releases Maximum Site Boundary Gamma Air Dose (mrad}
Maximum Site Boundary Beta Air Dose (mrad)
Maximum Off-site Dose to any Organ (mrem}*
Organ:.
Offshore Location Gamma Dose (mrad}
Total Body- (mrem)
Maximum Off-site Dose to any Organ (mrem)*
Organ:
Liquid Releases Maximum Off-site Dose Total Body (mrem)
Maximum Off-site Dose to any Organ (mrem)
Organ 2.48E-05 1.65E-04 8.03E-02 Child - bone 4.97E-07 4.15E-07 6.90E-03 Teen -Lung 1.64E-03 10 CFR Part 50 Appendix I Guidelines (2-unit site per year) 20 40 30 20 10 30
.6 2.13E-03 Adult - Gi-LLi 20
Page 7of7 Table 2 OFF-SITE RADIATION DOSE ASSESSMENT - PRAIRIE ISLAND SUPPLEMENTAL INFORMATION January 1, 2016 - December 31, 2016 Gaseous Releases Maximum Site Boundary Dose Location (From Building Vents)
Sector Distance (miles)
Offshore Location Within Site Boundary Sector Distance (miles)
Pathway Maximum Off-site Sector Distance (miles)
Pathways Age Group Liquid Releases.
. Maximum Off-site Dose Location Downstream Pathway w
0.36 ESE 0.2 Inhalation NNW 0.60
- Ground, Inhalation Vegetable Child Fish
ENCLOSURE 2 ANNUAL RADIOACTIVE EFFLUENT REPORT SUPPLEMENTAL INFORMATION January 1, 2016 - December 31, 2016 8 pages to follow
ANNUAL RADIOACTIVE EFFLUENT REPORT 01-JAN-16 THROUGH 31-DEC-16 SUPPLEMENTAL INFORMATION Facility:
Prairie Island Nuclear Generating Plant Licensee:
Northern States Power Company License Numbers: DPR-42 & DPR-60 A. Regulatory Limits
- i.
Liquid Effluents:
- a.
The dose or dose commitment to an individual from radioactive materials in liquid effluents released from the site shall be limited to:
for the quarter for the year
- 2.
Gaseous Effluents:
3.0 mrem to the total body 10.0 mrem to any organ 6.0 mrem to the total body 20.0 mrem to any organ
- a.
The dose rate due to radioactive materials released in gaseous effluents from the site shall be limited to:
noble gases
~ 500 mrem/year total body
$3000 mrem/year skin I-131, I-133, H-3, LLP
$1500 mrem/year to any organ
- b.
The dose due to radioactive gaseous effluents released from the site shall be limited to:
noble gases I-131, I-133,.H-3, LLP
$10 mrad/quarter gamma
$20 mrad/quarter beta
$20 mrad/year gamma
$40 mrad/year beta
$15 mrem/quarter to any organ
$30 mrem/year to any organ Page 1 of 8
B.
Effluent Concentration
- 1.
Fission and activation gases in gaseous releas.es:
10 CFR 20, Appendix B, Table 2, Column 1
- 2.
Iodine and particulates with half lives greater than 8 days in gaseous releas.es :
10 CFR 20, Appendix B, Table 2, Column 1
- 3.
Liquid effluents for radionuclides other than dissolved or entrained gases:
10 CFR 20, Appendix B., Table 2, Column 2
- 4.
Liquid effluent dissolved and entrained gases:
2.0E-04 uCi/ml Total Activity C.
Average Energy Not applicable to Prairie Island regulatory limits.
D.
Measurements and approximations of total activity
- 1.
Fission and activation gases Total Gem in gaseous releases:
Nuclide Gem
- 2.
Iodines in gaseous releases:
Total Gem Nuclide Gem
- 3.
Particulates in gaseous releases:
Total Gem Nuclide Gem
- 4.
Liquid effluents Total Gem Nuclide Gem E.
Manual Revisions
- 1.
Offsite Dose Calculations Manual:
Latest Revision number:
31 Revision date October 13, 2016 Page 2 of 8.
+/-25%
+/-25%
+/-25%
+/-25%
Liquid Releases Total Time for All Maximum Time for All Average Time for All Minimum Time for All Gaseous Releases Total Time for All Maximum Time for All Average Time for All Minimum Time for All Liquid Releases Number of Total Activity for Gaseous Releases Number of Total Activity for Prairie Island Nuclear Generating Station 2016 Annual. Release Summary Batch Release Surnniary Qtr 1 Qtr 2 Number of Releases:
21 21 Releases (Minutes):
1607.0 1624. 0 Releases (Minutes):
117. 0 103.0 Releases (Minutes):
76.5 77.3 Releases (Minutes):
50.0
- 62. 0 Qtr 1 Qtr 2 Number of Releases:
65 5
Releases (Minutes):
90055.0 1070.0 Releases (Minutes):
1440.0 300.0 Releases (Minutes):
1385.5 214.0 Releases (Minutes):
- 71. 0
- 71. 0 Abnormal Release Summary Abnormal Releases:
0 Abnormal Releases:
O.OOE+OO Curies Abnormal Releases:
0 Abnormal Releases:
O.OOE+OO Curies Page 3 of 8 Qtr 3 Qtr 4 Year 35 48 125 2516.0 4156.0 9903.0
-89.0 140.0 140.0
- 71. 9 86.6 79.2
- 61. 0 63.0 50.0 Qtr 3 Qtr 4 Year 1
c*
18 89 60.0 21472.0 112657.0 60.0 1660.0 1660.0 60.0 1192.9 12 65. 8.
60.0 220.0 60.0
Prairie Island Nuclear Generating Station 2016 Annual Release Summary Gaseous Effluents-Sununation of All Releases Type of Effluent Units Qtr l Qtr 2 A. Fission & Activation Gases
- 1. Total Release Curies 9.42E-04 5.00E-'04
- 2. Average Release Rate for Period
µCi/sec
- 1. 20E-04 6.35E-05
- 3. Percent of Applicable Limit 2.65E-05 l.39E-05 B. Iodines
- 1. Total Iodine-131 Curies O.OOE+OO O.OOE+OO
- 2. Average Release Rate for Period
µCi/sec O.OOE+OO O.OOE+OO
- 3. Percent of Applicable Limit O.OOE+OO O.OOE+OO
- c. Particulates
- 1. Total Particulates (Half-lives > 8 days)
Curies O.OOE+OO O.OOE+OO
- 2. Average Release Rate for Period
µCi/sec O.OOE+OO O.OOE+OO
- 3. Percent of Applicable. Limit 0.00E+OO O.OOE+OO
- 4. Gross Alpha Activity Curies O.OOE+OO O.OOE+OO D. Tritium
- 1. Total Release Curies 5.13E+OO 5.51E+OO
- 2. Average Release Rate for Period
µCi/sec 6.52E-01 7.0lE-01
- 3. Percent of Applicable Limit 3.64E-02 3.83E-02 E. carbon-14
- 1. Total Release Curies 2.02E+OO 2.89E+OO Page 4 of 8 Est. Tota)-
Qtr 3 Qtr 4 Error,.%
3.88E-02 O.OOE+OO 2.SOE+Ol 4.89E-03 0.00E+OO 7.87E-04 O.OOE+OO O.OOE+OO 2.09E-07 2.50E+Ol O.OOE+OO 2.62E-08 O.OOE+OO 2.09E-05 O.OOE+OO 2.42E-06 2.50E+Ol O.OOE+OO 3.04E-07 O.OOE+OO 2.46E-05 O.OOE+OO O.OOE+OO 2.50E+Ol 6.99E+OO
- 1. 09E+Ol 2.50E+Ol 8.79E-01 1.37E+OO 4.86E-02 7.70E-02 2.93E+00 2.32E+OO 2.SOE+Ol
Nuclides Released Units Qtr Prairie Island Nuclear Generating Station 2016 Annual Release Summary Gaseous Effluents -
Ground Level Releases Continuous Mode 1
Qtr 2 Qtr 3 Qtr 4 Qtr. 1
- 1.
Fission and Activation Gases Kr-85 Curies O.OOE+OO O.OOE+OO
- 1. 43E-02 O.OOE+OO 9.42E-04 Xe-133 Curies 0.00E+OO O.OOE+OO 2.36E-02 O.OOE+OO O.OOE+OO Total for Period Curies O.OOE+OO O.OOE+OO 3.79E-02 O.OOE+OO 9.42E-04
- 2. Iodines I-131 Curies 0.00E+OO O.OOE+OO 0.00E+OO 2.09E-07 O.OOE+OO Total for Period Curies O.OOE+OO O.OOE+OO 0.00E+OO 2.09E-07 O.OOE+OO
- 3. Particulates Cd-109 Curies O.OOE+OO O.OOE+OO O.OOE+OO 4.93E-07 O.OOE+OO
. Co-58 Curies O.OOE+OO O.OOE+OO O.OOE+OO 1.34E-06 O.OOE+OO Co-60 Curies O.OOE+OO O.OOE+OO O.OOE+OO 3.27E-07 O.OOE+OO Cr-51 Curies O.OOE+OO O.OOE+OO O.OOE+OO
- 1. 72E-07 O.OOE+OO Mn-54 Curies O.OOE+OO O.OOE+OO O.OOE+OO 2.50E-08 O.OOE+OO Nb-95 Curies O.OOE+OO O.OOE+OO O.OOE+OO 3.59E-08 O.OOE+OO Zr-95 Curies O.OOE+OO O.OOE+OO O.OOE+OO 2.32E-08 O.OOE+OO Total for Period Curies O.OOE+OO O.OOE+OO. O.OOE+OO 2.42E-06 O.OOE+OO
- 4.
Tritium H-3 Curies 5.09E+OO 5.51E+OO 6.99E+OO
- 1. 09E+Ol 3.36E-02
- 5. Carbon-14 C-14 Curies 2.02E+00 2.89E+OO 2.93E+OO 2.32E+OO O.OOE+OO Page 5 of 8 Batch Mode Qtr 2 Qtr 3 Qtr 4 4.89E-04 9.80E-04 0.00E+OO l.07E-05 0.00E+OO O.OOE+OO 5.00E-04 9.80E-04 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 0.00E+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+oo*
- 1. 09E-04 1.lOE-03 4.90E-02 O.OOE+OO O.OOE+OO O.OOE+OO
- Prairie Island Nuclear Generating Station 2016 Annual Release Summary Liquid Ef.fluerits -
Summation of All Releases Type of Effluent A. Fission & Activation Products
- 1. Total Release (not including Tritium, Gases, and Alpha)
- 2.
Average Diluted Concentration During Period
- 3.
Percent of Applicable Limit B. Tritium
- 1. Total.Release
- 2.
Average Diluted Concentration During Period
- 3.
Percent of Applicable Limit C. Dissolved and Entrained Gases
- 1.
Total Release
- 2.
Average Diluted Concentration During Period
- 3.
Percent of Applicable Limit D. Gross Alpha Radioactivity L
Total Release E. Waste Volume Released (Pre-Dilution)
F. Volume of Dilution Water Used Units
- Curies
µCi/ml Curies
µCi/ml Qtr 1 Qtr 2 Qtr 3 Qtr 4 7.09E-03 2.41E-03 l.43E-03 7.34E-03 7.29E-ll 3.05E-ll l.94E-ll 7.73E-ll l.42E-01 4.82E-02 2.87E-02 l.47E-01 l.02E+02 l.20E+02 l.06E+02 6.85E+Ol l.05E-06 l.52E-06 l.44E-06 7.21E-07 I°. 05E-02
- 1. 52E-02
- 1. 44E-02
- 7. 21,_E-03 Curies O.OOE+OO 5.95E-05 4.34E-05 3.41E-05
µCi/sec O.OOE+OO 7.52E-13 5.BBE-13 3.59E-13 O.OOE+OO 3.76E-07 2.94E-07 l.79E-07 Curies O.OOE+OO O.OOE+OO 0.00E+OO O.OOE+OO Liters 5.67E+07 4.03E+07 5.94E+08 5.38E+07
.Liters 9.72E+l0 7.90E+l0 7.32E+l0 9.49E+l0 Page 6 of 8 Est. Total Error~ %
2.50E+Ol 2.SOE+Ol 2.50E+Ol 2.50E+Ol 2.50E+Ol 2.50E+Ol
Nuclides Released Units Ag-110m Curies Ar-41 Curies As-76 Curies Co-57 Curies Co-58 Curies Co-60 Curies Cr-51 Curies Fe-55 Curies Fe-59 Curies H-3 Curies Mn-54 Curies Nb-95 Curies Nb-97 Curies Ni-63 Curies Sb-124 Curies Sb-125 Curies Sn-113 Curies Sr-92 Curies Te-123M Curies W-187 Curi.es Xe-127 Curies Xe-133 Curies Xe-135 Curies Zr-95 Curies Total for Period Curies.
Prairie Island Nuclear Generating Station 2016 Annual Release Summary Liquid Effluents Continuous Mode Qtr 1 Qtr 2 Qtr 3 Qtr 4 Qtr 1 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 1.20E-04 0.00E+OO o*.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 0.00E+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO o:ooE+oo 3.41E-04 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 6.41E-04 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 1.60E-05 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 3.88E-03 O.OOE+OO
.0. OOE+OO O.OOE+OO O.OOE+OO 2.14E-06 1.45E-01 1.60E-01 2.99E+OO 1.46E-01 1.02E+02 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 1.26E-05 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 3.49E-06 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 6.87E-06 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 1.97E-03 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 6.30E-05 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO
- 1. 71E-06 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 0.00E+OO
- 0. OOE+o*o O.OOE+OO O.OOE+OO O.OOE+OO 3.24E-06 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 2.50E-05 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 2.32E-06
- 1. 45E-01 1.60E-01 2.99E+OO
- 1. 4 6E-01 1.02E+02 Page 7 of 8 Batch Mode Qtr 2 Qtr 3 Qtr 4 9.39E-05 2.61E-05 2.73E-05 7.62E-07 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 1.47E-06 O.OOE+OO O.OOE+OO 6.35E-06 2.67E-04 4.95E-05 3.05E-03 2.33E-04 2.83E-04 3.38E-04 7.95E-06 O.OOE+OO 5.40E-05
- 1. 44E-03 9.49E-04
- 1. 49E-03 5.50E-06 O.OOE+OO O.OOE+OO 1.20E+02 1.03E+02 6.83E+01 1.47E-05 2.90E-05 2.06E-05 3.76E-05 O.OOE+OO 4.. 04E-06 6.48E-06
- 1. 37E-05
- 1. 09E-05
- 1. 22E-04 O.OOE+OO 7.35E-04 6.45E-07 O.OOE+OO 1.65E-06
- 1. 23E-04 s.15E-0*5
- 1. 55E-03 3.32E-05 O.OOE+OO 2.0lE-06
- 1. 32E-06
- 1. llE-06 1.65E-06 O.OOE+OO
- 1. 46E-06
- 4. 73E-05 4.64E-06 O.OOE+OO O.OOE+OO O.OOE+OO O.OOE+OO 2.95E-06 5.48E-05 4.28E-05 2.99E-05 3.BBE-06 5.17E-07 1.27E-06 1.77E-05 O.OOE+OO O.OOE+OO
- 1. 20E+02 1.03E+02 6.83E+01
Parameter Qtr 1 Gamma Air Dose (mrad)
Beta Air Dose (mrad)
Total Body Dose (mrem)
Skin Dose (mrem)
Max Organ Dose (mrem)
Child - Liver Qtr 2 Gamma Air Dose (mrad)
Beta Air Dose (mrad)
Total Body Dose (mrem)
Skin Dose (mrem)
Max Organ Dose (mrem)
Child -
Bone Qtr*3 Gamma Air.Dose (mrad)
Beta Air Dose (mrad)
Total Body Dose (mrem)
Skin Dose (mrem)
Max Organ Dose (mrem)
Child -
Bone Qtr 4 Gamma Air Dose (mrad)
Beta Air Dose (mrad)
Total Body Dose (mrem)
Skin Dose (mrem)
Max Organ Dose (mrem)
Child -
Thyroid Year Gamma Air Dose (mrad)
Beta Air Dose (mrad)
Total Body Dose (mrem)
Skin Dose (mrem)
Max Organ Dose (mrem)
Child -
Bone Parameter Qtr 1 Max Organ Dose (mrem)
Total Body Dose (mrem)
Qtr 2 Max Organ Dose (mrem)
Total Body Dose (mrem)
Qtr 3 Max Organ Dose.(mrem)
Total Body Dose (mrem)
Qtr 4 Max Organ Dose (mrem)
Total Body Dose (mrem)
Year Max Organ Dose (mrem)
Total Body Dose (mrem)
Prairie Island Nuclear Generating Station 2016 Annual Dose Summary Gaseous Effluents Location Dose 0.58 km w 4.67E-08 0.58 km w 5.30E-06 0.58 km w 4.37E-08 0.58 km w 3.69E-06 0.97 km NNW 5.76E-03 0.58 km w 3.51E-08 0.58 km w 2.78E-06 0.58 km w 3.18E-08 0.58 km w 1.94E-.06 0.97 km NNW 3.20E-02 0.58 km w 2.47E-05 0.58 km w 1.57E-04 0.58 km w 2.07E-05 0.58 km W l.07E-04 0.97 km NNW 4.83E-02 0.58 km w O.OOE+OO 0.58 km w O.OOE+OO 0.58 km w O.OOE+OO 0.58 km W O.OOE+OO 0.97 km NNW 1.22E-02 0.58 km w 2.48E-05 0.58 km W 1.65E-04 0.58 km w 2.08E-05 0.58 km w 1.13E-04 0.97 km NNW 8.03E-02 Liquid Effluents Max Receptor Dose Adult -
Bone
- 1. 21E-03 Adult ~ Total Body 4.64E-04 Adult -
Gi-LLi 9.17E-04 Adult - Total Body 6.15E-04 Adult -
Gi-LLi 2.49E-04 Adult - Total Body 2.34E-04 Adult -
Bone 5.23E-04 Adult - Total Body 3.23E-04 Adult -
Gi-LLi 2.13E-03 Adult - Total Body l.64E-03 Page 8 of 8 Dose Limit
% of Limit
- 1. OOE+Ol 0.00 2.00E+Ol 0.00 5.00E+OO 0.00
- 1.50E+Ol 0.00 1
- 1. 50E+Ol 0.04 1.00E+Ol 0.00 2.00E+Ol 0.00 5.00E+OO 0.00
- 1. 50E+Ol 0.00
- 1. 50E+Ol 0.21
- 1. OOE+Ol 0.00 2.*00E+o1 0.00 5.00E+OO 0.00
- 1. 50E+Ol 0.00 1.50E+Ol 0.32 1.00E+Ol 0.00 2.00E+Ol 0.00 5.00E+OO 0.00 l.50E+Ol 0.00 1.50E+Ol 0.08 2.00E+Ol 0.00 4.00E+Ol 0.00 1.00E+Ol 0.00 3.00E+Ol 0.00 3.00E+Ol 0.27 Dose Limit
% of Limit 1.00E+Ol 0.01 3.00E+OO 0.02
- 1. OOE+Ol 0.01 3.00E+OO 0.02 l.OOE+Ol 0.00 3.00E+OO 0.01
- 1. OOE+Ol 0.01 3.00E+OO 0.01 2.00E+Ol 0.01 6.00E+OO 0.03