NVMoHnwx CALCULATIONCOVER SHEET NUCLEARENGINEERING ATTACHhiEhIT G Page 1 ( Next~~

V'otal +~

Last ~g NINE MILEPOINT NUCLEARSTATION Unit(1,2orO=Both):

1 Discipline:

STRUCTURAL Ttue SCREENING EVALUATIONWORKSHEETS FOR TRANSFORMER 167A Calculauon No.

SO.OSEWS167A (Sub)system(s)

NA Building Fker Elev.

Index No.

RB 281 S0.0 Originator(s)

CARMEN R. AGOSTA Checker(s) /Aplxover(s) 0 Rev 00 Descrl tlon INITIALISSUE Design Chan eNo.

B Date Chk Date A

7-/-f7 N.

Date Computer Output/Microfilm Filed Separately (Yes / No / NA): NA Superseded Document(s):

NONE Safety Class (SR/ NSR/ Qxx): SR Document Cross Reference(s) - For additional references see page(s):

NA Ref No NER-1 S-012 Document No.

Doc T

NER Index Sheet Rev 00 2

SO.OSQUGANCHOR CALC S0.0 00 General Reference(s):

GENERIC IMPLIMENTATIONPROCEDURE (GIP)

4. NMPC Letter to NRC, File Code NMP1L 1044, dated March 11, 1996 Remarks:

NONE Confirmation Required (Yes / No): No Final Issue Status File Location Operations Acceptance See Page(s):

( APP / FIO/ VOI): APP

( Gale/ Hold ): Gale Required ( Yes / No ): No Evaluation Number(s) / Revision:

NR Copy ofApplicabilityReview Attached (Yes / N/R)'PN/R Component ID(s) / EPN(s) / Line Number(s):

NA Key Words: NMP-1, STRUCTURAL, SQUG, SEWS, SEISMIC VERIFICATION 9708070%27 97078K PDR ADOCK 05000220 g g~TJ r

PDR FORMAT¹ NEP-DES48-F0140

T NIAGARA 4 MOHAWK NUCLEAR ENGINEERING CALCULATIONCONTINUATIONSHEET Page ~>

(Next~

Nine Mile Point Nuclear Station Unit:

1 Disposition:

Originatorg/

ate l~

ef.

Checker/Date Caicuiation No.

Revision 7 I7 SO.OSEWS7&69 g /rg 00 PURPOSE'ocument the Screening Evaluation Work Sheets (SEWS) for the AP/600 TO 120/208 VTRANSFORMER, equipment number 167A.

This SEWS has been prepared as part of the commitment to use the SQUG (GIP) methodology to document the seismic adequacy of SSEL components.

CONCLUSION: The four welds and the four 5/8" diameter cinch anchors are adequate based on the anchor analysis in Attachment A, the cinch anchor capacities given in Calculation SO.OSQUGANCHOR (Ref. 2) and the anchor bolt tightness check results confirming these anchors are tight.

Therefore, the SQUG outlier for 167A is resolved.

ATTACHMENTS A. SEWS for Equipment ID Number 167A B.

The Outlier Seismic Verification Sheet (OSVS) for Equipment ID Number 167A I

FORMAT¹ NEP-DES-08, Rev. 01 (F02)

Niagara Mohawk Power Corporation - Nine Mile Point 1 SCREENING EVALUATIONWORK SHEET (SEWS)

CALC NO REVISION GIP Rev 2, Corrected, 2/14/9 Status: No Sheet 1 of 8 ID: TRANS 167A

( Rev. 0)

Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 VTRANSFORMER Building'B Manufacturer, Model, Etc.:

Floor El.: 281.00 Room, Row/Col: Q7,8 SEISMIC CAPACITYVS DEMAND Elevation where equipment receives seismic input 2.

Elevation of seismic input below about 40'rom grade (grade = 243.00)

Equipment has fundamental frequency above about 8 Hz (est. frequency = )

4.

Capacity based on:

1.00

  • Bounding Spectrum 5.

Demand based on:

1.00* Design Basis Ground Response Spectrum 281.00 Yes SRT 8.0000 E-001 LOG

~/

~r 1.8000 E-002

~r 2.0000 E-001 LOG Hz Capacity

..... Demand 1.0000 E+002 Capaci Demand 1

Demand 2 File F:tGIPtGIPtspectra.des F:tGIPtPROJ003Rspectra.des F:>GIMP ROJ003Rspectra.des Record Label Bounding S ectrum UNIT:IPLANTiBLDG:iBUILDINGIEIQ:iSSEiELEV:iELEVATIONIROWI COL:

LLDIR: DIR NODE: 1 UNIT:IPLANTIBLDG:IBUILDINGIEIQ:ISSEIELEV:IELEVATIONIROWI COL:

LLDIR: DIR NODE: 1 Does capacity exceed demand'

Niagara Mohawk Power Corporation - Nine Mile Point 1 SCREENING EVALuATIONWORK SHEET (SEWS)

REVISION ao GIP Rev 2, Corrected, 2/1 9

Status: No Sheet 2 of 8 ID: TRANS167A (Rev. 0)

Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 VTRANSFORMER Building RB Floor El.: 281.00 Room, Row/Col: Q7,8 Manufacturer, Model, Etc.:

CAVEATS - BOUNDING SPECTRUM TRN/BS Caveat 1 - Earthquake Experience Equipment Class TRN/BS Caveat 2 - Rating of4.16 KVor Less TRN/BS Caveat 3-Transformer Coils Postively Restrained Within Cabinet TRN/BS Caveat 4 - Coils Top Braced or Analyzed for Large Transformers.

TRN/BS Caveat 5-Clearance Between Energized Component and Cabinet.

TRN/BS Caveat 6-Adequate Slack in High Voltage Leads.

TRN/BS Caveat 7-Wall-Mounted Units Anchored Close to Enclosure Structure.

TRN/BS Caveat 8 - Weak-Way Bending of Thin Webs Evaluated.

TRN/BS Caveat 9 - Adjacent Cabinets Bolted Together.

TRN/BS Caveat 10- Doors Secured.

TRN/BS Caveat 11 - Adequate Anchorage.

TRN/BS Caveat 12-Potential Chatter of Essential Relays Evaluated.

TRN/BS Caveat 13 - No Other Concerns.

Yes Yes Yes Yes Yes Yes Yes Yes N/A N/A No*

Yes Yes Is the intent of all the caveats met for Bounding Spectrum' ANCHORAGE

1. The sizes and locations of anchors have been determined
2. Appropnate equipment characteristics have been determined (mass, CG, natural freq.,

damping, center of rotation).

3. The type of anchorage is covered by the GIP
4. The adequacy of the anchorage installation has been evaluated (weld quality and length, nuts and washers, expansion anchor tightness, etc.)
5. Factors affecting anchorage capacity or margin of safety have been considered: embedment length, anchor spacing, free-edge distance, concrete strength/condition, and concrete cracking.
6. For bolted anchorages, any gaps under the base are less than 1/4
7. Factors affecting essential relays have been considered: gaps under the base, capacity reduction for expansion anchors.
8. The base has adequate stiffness and the effect of prying action on anchors has been considered.
9. The strength of the equipment base and the load path to the CG is adequate.
10. The adequacy of embedded steel, grout pads or large concrete pads have been evaluated.
11. The anchorage capacity exceeds the demand.

N/A Yes No Yes Yes N/A Yes Yes Yes Yes Yes Are anchorage requirements met'P

Niagara Mohawk Power Corporation - Nine Mile Point 1 SCREENING EVALUATIONWORK SHEET (SEWS)

CALC NO REVISION PAGE NO GIP Rev 2, Corrected, 2/14/92 Status: No Sheet 3 of 8 ID: TRANS167A (Rev. 0)

Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 VTRANSFORMER Building'B Manufacturer, Model, Etc.:

Floor El.: 281.00 Room, Row/Col: Q7,8 INTERACTION EFFECTS

1. Soft targets are free from impact by nearby equipment or structures
2. Ifthe equipment contains sensitive relays, it is free from all impact by nearby equipment or structures.
3. Attached lines have adequate flexibility
4. Overhead equipment or distribution systems are not likely to collapse.
5. No other adverse concerns were found.

Is equipment free of interaction effects?

Yes N/A Yes Yes Yes CQ55JYLEHIR OUTLIER IMPORTANT NOTE: This SEWS is a composite of the original SQUG pilot plant walkdown conducted in January and February of 1988 by D. Moore, A. Ordonez, W Djordjevic, RF Oleck, J Valente, D Aelbrecht, J. Reddington, T.

Hester, D. Tahiliani, J. Raby, and F. Feng using the GIP, Revision 1; a supplementary walkdown conducted by RF Starck, F Feng and W Djordjevic in April 1989 still using Revision 1 of the GIP, and the final walkdown conducted in April 1993 by W Djordjevic and C Agosta to update the SEWS to Revision 2 GIP requirements as required by USNRC in SSER-2.

Anchorage:

Transformer is anchored by four 1" welds 1/8" thick.

Evaluated by:

Date:

ii> 8

Attachment:

Pictures

Attachment:

ANCHOR Report

Niagara Mohawk Power Corporation - Nine Mile Point 1 SCREENING EVALUATIONWORK SHEET (SEWS)

REVISiOM PAGE NO GIP Rev 2, Corrected, 2/14/92 Status: No Sheet4of8 ID: TRANS167A" (Rev. 0)

Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 VTRANSFORMER B 'Id' RB Manufacturer, Model, Etc.:

FI EI.. 281.00 R,R

/C I.Q78 Panel 167A Transformer

Niagara Mohawk Power Corporation - Nine Mile Point 1 SCREENING EVALUATIONWORK SHEET (SEWS)

REVISION 4'IP Rev 2, Corrected, 2/14/92 Status: No Sheet5of8 ID: TRANS 167A'( Rev. 0)

Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 VTRANSFORMER B IdRB Manufacturer, Model, Etc.:

ANCHOR Report Floor El.: 281.00 Room, Row/Col: Q7,8 Response Spectrum: SSE Frequency: GIP - Flexible Damping: GIP - 5.00 Spectral Values:

Direction North - South East - West Vertical Acceleration (g's) 0.52 0.52 0.16 Angle: 0.00 Combination Criteria: SRSS Number ofWeights:

1 No Weight X

Y Z

1 9.75E+002 2.00E+001 1.20E+001 2.00E+001 Em:ms Number of Forces: 0 Rhmants

'umber of Moments: 0 hlhMt~

Number ofAnchor types:

1 Tension Shear Saf Ultimate Ultimate Inter Inter No.

Dia Manufact Product Tension Shear Coeff Coeff Fact

Niagara Mohawk Power Corporation - Nine Mile Point 1 SCREENING EVALUATIONWORK SHEET (SEWS)

CALC NO REVISION PA GIP Rev 2, Corrected, 2/14/92 Status: No Sheet6of8 ID: TRANS 167A" ( Rev. 0 )

Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 VTRANSFORMER B ilding. RB Manufacturer, Model, Etc.:

Floor El.: 281.00 Room, Row/Col: Q7,8 1

3/8 Other Unknown Expansion Anchor 1460.00 1420.00 1.00 0.30 1.00 Ultimate Stress: 4000.00 psi.

Reduction Factor: 0.85 Allowable Stress:

30600 psi.

Surhzm Number of Surfaces:

1 Direction Comp Direction Comp Ny Direction Com Nz 1

O.OOE+000 O.OOE+ 000 1.00E+000 Anchor Pattern for Surface ¹ 1 IY Legend forAnchor Patterns

Niagara Mohawk Power Corporation - Nine Mile Point 1 SCREENING EVALUATIONWORK SHEET (SEWS)

CAI.C NO REVISION GIP Rev 2, Corrected, 2/14/92 Status: No Sheet 7 of 8 oSE~

ID: TRANS167A (Rev. 0)

Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 VTRANSFORMER Building: RB Manufacturer, Model, Etc.:

Floor El.: 281.00 Room, Row/Col: Q7,8 Anchors:

Concrete Uncs:

Concrete Points:

Vleld Uncs:

Number ofAnchors: 0

¹ of elements per line: 1 Number of Concrete Lines: 4 No stan X-Coord sta~

Y-Coord stuart Z-Coord End X-Coord End Y-Coord End Z-Coord sf ld Line Width O.OOE+000 1.00E+ 000 3.90E+001 O.OOE+ 000 4.00E+001 2.30E+001 1.00E+000 2.40E+001 O.OOE+000 4.00E+001 1.00E+000 O.OOE+000 1

O.OOE+000 3.90E+001 2.40E+001 O.OOE+000 1

O.OOE+000 0.00E+000 2.30E+001 O.OOE+000 1

0.00E+000 1.00E+000 0.00E+000 0.00E+000 1

2.00E+000 2.00E+000 2.00E+000 2.00E+000 Number of Concrete Points: 0 Kaid.loom~

¹ of elements per line: 1 Number ofWeld Lines: 4 start No X-Coord start Y-Coord start Z-Coord End X-Coord End Y-Coord End Z-Coord sf Id Line Width 1

1.00E+000 2

3.90E+001 3

1.00E+000 4

3.90E+001 O.OOE+000 O.OOE+000 2.30E+001 2.30E+001 1.00E+000 1.00E+000 1.00E+000 1.00E+000 1.00E+000 1.00E+000 3.90E+ 001 1.00E+000 1.00E+000 2.40E+001 3.90E+001 2.40E+001 1.00E+000 1.00E+000 1.00E+000 1.00E+000 1

1.25E-001 1

1.25E-001 1

1.25E-001 1

1 25E-001

Niagara Mohawk Power Corporation - Nine Mile Point 1 SCREENING EVALUATIONWORK SHEET (SEWS) 4l REVISION Oo PAGE NO GIP Rev 2, Corrected, 2/14/92 Status: No Sheet 8 of 8 ID: TRANS 167A' Rev. 0 )

Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 VTRANSFORMER B ilding. RB Manufacturer, Model, Etc.:

Floor El.: 281.00 Room, Row/Col: Q7,8 Reduction Factors Data Current: Yes Analysis Performed: Yes Type ofAnalysis: Regular Spectral Accelerations (G's)

Allowable No N-S E-W Vertical Load Factor 5.17E-001 2.07E-001 2

-5.17E-001

-2.07E-001 6.50E-002

-6.50E-002 12.824 13.885 3

-5.17E-001 2.07E-001 6.50E-002 12.824 5.17E-001

-2.07E-001 5.17E-001

-2.07E-001

-6.50E-002 6.50E-002 13.885 12.824 6

-5 17E-001 2 07E-001 4.50E-002 13.885 7

5.17E-001 2.07E-001 8

-5.17E-001

-2.07E-001

-6.50E-002 6.50E-002 13.885 12.824 9

2.07E-001 10

-2.07E-001 5.17E-001

-5.17E-001 6.50E-002

-6.50E-002 11.125 12.130 11 2.07E-001

-5.17E-001 6.50E-002 11.125 12

-2.07E-001 13

-2.07E-001 5.17E-001 5.17E-001

-6.50E-002 6.50E-002 12.130 11.125 14 2.07E-001

-5.17E-001

%.50E-002 12.130 15 2.07E-001 5.17E-001

%.50E-002 12.130 21

-2.07E-001 2.07E-001 22 2.07E-001

-2.07E-001 23 2.07E-001

-2.07E-001 24

-2.07E-001 2.07E-001 16

-2.07E-001

-5.17E-001 17 2.07E-001 2.07E-001 18

-2.07E-001

-2.07E-001 19 2.07E-001 2.07E-001 20

-2.07E-001

-2.07E-001 6.50E-002 1.63E-001

-1.63E-001

-1.63E-001 1.63E-001 1.63E-001

-1.63E-001 1.63E-001

-1.63E-001 11.125 19.044 28.093 28.093 19.044 19.044 28.093 19.044 28.093 Minimum Allowable Load Factor:

1.11E+001

ATTACHMENT CANR0 REVISION PAGE NQ Ib Response Spectrum: User Frequency: User- 0.00 Percent Damping: User- 0.00 S ectral Values:

Direction North - South East - West Vertical Acceleration

's 1.100 1.050 0.170 Angle (N-S Direction makes with the XAxis): 0.00 Combination Criteria: SRSS

~Wsl hts:

Number ofWeights: 1 No Wei ht 1

975.00 X

15.500 18.000 18.750 Forces Number of External Forces: 0

~Mome ts:

Number of External Moments: 0

~ttowabtes.

Anchor Number ofAnchor types:

1 Ultimate Ultimate Tension Inter Shear Inter Saf No Dia 518 Manufact Other Product Unknown Expansion Anchor Tension 970.00 Shear 1400.00 Coeff 1.00 Coeff 0.30 Fact 1.00 Concrete Ultimate Stress: 3500.00 psL Reduction Factor: 0.85 Weld Allowable Stress:

30600 psl.

Surfaces:

Number of Surfaces:

1 Surface Orientation Direction Com 0.000 Direction Com N

0.000 Direction Com Nz 1.000

ATTACHMENT CAI.C NO REVISION PAGE NO Anchor Pattern for Surface ¹ 1 Le end forAnchor Patterns

~Geomet

~ocher Number of Anchors: 4 Anch ld X

Coord 12.000 22.000 12.000 Coord 2.000 17.500 33.000 Coord 0.000 0.000 0.000 Surf ld 2.000 17.500 0.000 1

¹ of elements per line: 4 Number of Concrete Lines: 4

E

ATTACHMENT CALC NO 4'S d-~

REVISION Start Start Start End End End Sf Line X&oord 0.000 22.000 24.000 2.000 Y-Coord 2.000 0.000 33.000 35.000 Z-Coord 0.000 0.000 0.000 0.000 X-Coord 24.000 22.000 0.000

2. 00 Y-Coord 2.000 35.000 33.000 0.000 Z-Coord Id 0.000 1

0.000 0.000 1

0.000 1

Width 4.000 4.000 4.000 4.000 "Number of Concrete Points: 0

~Weld ee

¹ of elements per line: 4 Number of Weld LInes: 0 Determinatio of eductio Factors Reduction Factor Input forAnchor¹ 1 No Input - Reduction factors needing user input are not used.

Reduction Factor Input forAnchor¹ 2 No Input - Reduction factors needing user input are not used.

'I Reduction Factor Input forAnchor¹ 3 No Input - Reduction factors needing user input are not used.

Reduction Factor Input forAnchor¹ 4 No Input - Reduction factors needing user input are not used.

Reduction Factors Data Current: Yes No Le end Pall/

Vali 970.00 970.00 970.00 Pallrl Vallr N/A N/A N/A NIA RT RN RL X

X X

X X

X X

X X

X X

X X

X X

X RG RS X

X X

X X

X X

X X

X X

X X

X X

X RE RF RC X

X X

X X

X X

X X

X X

X X

X X

X RR RP X

X X

X X

X X

X X

X X

X X

X X

X RB RM X

X X

X X

X X

X X

X X

X X

X X

X N/A

= Not A licable Pall

= Allowable Pull without Reduced Ins ction Vali

= Allowable Shear without Reduced Ins ction Pallr

= Allowable Pull with Reduced Ins ection Vallr

= Allowable Shear with Reduced Ins ection

= Outlier

= Reduction Factor Not Used RT

= Reduction Factor forT e of Anchora e

RN

= Reduction Factor for Installation Ade uac RL

= Reduction Factor for Embedment

ArlACHMENf CALC HO REVELS(OM PAGE NO RG

= Reduction Factor for Ga at Anchors RS

= Reduction Factor for S acin RE

= Reduction Factor for Ed e Distance RF

= Reduction Factor for Concrete Stren h

RC

= Reduction Factor for Concrete Cracks RR

= Reduction Factor for Essential Rela s RP

= Reduction Factor for Base Stiffness and P in Action RB

= Reduction Factor for Base Stren th and Load Path RM

= Reduction Factor for Embed. Steel and Pads Anal sis Results.

Analysis Performed: Yes of Anal sis: Re ular S

ctral Accelerations G's No N-S E-W Vertical Safet Factor 10 12 13 14 15 16 17 18 19 20 21 23 24 1.100

-1.100

-1.100 1.100 1.100

<<1.100 1.100

-1.100 0.440

-OA40 0.440

-0.440

-0.440 OA40 0.440

-0.440 0.440

-0.440 0.440

-0.440

-0.440 0.440 0.440

-0.440 0.420

-0.420 0.420

-0.420

-0.420 0.420 0.420

-0.420 1.050

-1.050

-1.050 1.050 1.050

-1.050 1.050

-1.050 0.420

-0.420 0.420

-0.420 0.420

-0.420

-0.420 0.420 0.068

-0.068 0.068

-0.068 0.068

-0.068

-0.068 0.068 0.068

-0.068 0.068

-0.068 0.068

-0.068

-0.068 0.068 0.170

-0.170

<<0.170 0.170 0.170

-0.170 0.170

-0.170 2.177 2.485 2.351 2.235 2.177 2.485 2.235 2.351 2.992 3 187 3.013 3.155 2.992 3.179 3.155 3.013 4.750 6.439 5.544 4.677 4.627 4.750 6.352 Minimum Safety Factor:

2.177 The anchorage can withstand 2.177 times greater seismic demand

OUTLIER SEISMIC VERIFICATIONSHEET (OSVS)

GIP Rev Sheet 1 of 2 CALC NO REVISION PAGE ID: TRANS 167A Rev. 0 Class: 4. Transformers Descri tion: AP/600 TO 120/208 VTRANSFORMER Buiidin: RB Floor El.: 281.00 Room Row/Col: Q7,8

1. OUTLIER ISSUE DEFINITION-Mechanical and Electrical E ui ment a.

Identify all the screening guidelines which are not met. (Check more than one ifseveral guidelines could not be satisfied.)

Ca acit vs. Demand Caveats Anchora e

Seismic Interaction Other b.

Describe all the reasons forthe outlier (I.e., ifall the listed outlier issues were resolved, then the signatories would consider this item of equipment to be verified for seismic adequacy)

~

Cast-in-place (embedded) channels are anchored by Cinch (leaded) type expansion anchors.

The GIP does not cover this anchor t ificall it rovides no known ca acit for this anchor t

2. PROPOSED METHOD OF OUTLIER RESOLUTION 0 tional a.

Defined proposed method(s) for resolving outlier.

Establish an allowable capacity for this anchor type by reviewing appropriate documentation and compare this ca acit to the seismic demand, and/or retrofit the anchors e.

b.

Provide information needed to implement proposed method(s) for resolving outlier (e.g., estimate of fundamental frequency).

3. COMMENTS
4. CERTIFICATION:

I The information on this OSVS is, to the best of our knowledge and belief, correct and accurate, and resolution of the outlier issues listed on the previous page willsatisfy the requirments for this item of equipment to be verified for seismic adequacy:

Approved by:

Date:

/u

Attachment:

Pictures

CALC WO REVISION PAGE NO OUTLIER SEISMIC VERIFICATIONSHEET (OSVS)

GIP Rev Sheet 2 of 2 ID: TRANS167A* Rev. 0 Class: 4. Transformers Descri tion: AP/600 TO 120/208 VTRANSFORMER Buildin: RB Floor El.: 281.00 PICTURES Room, Row/Col: Q7,8 Panel 167A Transformer