ATTACHhiEhIT G Next~~

N V MoHnwx CALCULATIONCOVER SHEET NUCLEAR ENGINEERING Page V'otal Last

+~

1

~g

(

NINE MILE POINT NUCLEAR STATION Unit(1,2orO=Both): 1 Discipline: STRUCTURAL Ttue Calculauon No.

SCREENING EVALUATIONWORK SHEETS FOR TRANSFORMER SO.OSEWS167A 167A (Sub)system(s) Building Fker Elev. Index No.

NA RB 281 S0.0 Originator(s)

CARMEN R. AGOSTA Checker(s) /Aplxover(s) 0 Design Rev Descrl tlon Chan eNo. B Date Chk Date A Date 00 INITIALISSUE 7-/-f7 N.

Computer Output/Microfilm Filed Separately (Yes / No / NA): NA Safety Class (SR/ NSR/ Qxx): SR Superseded Document(s): NONE Document Cross Reference(s) - For additional references see page(s): NA Ref Doc No Document No. T Index Sheet Rev NER-1 S-012 NER 00 2 SO.OSQUGANCHOR CALC S0.0 00 General Reference(s): '.

GENERIC IMPLIMENTATIONPROCEDURE (GIP)

4. NMPC Letter to NRC, File Code NMP1L 1044, dated March 11, 1996 Remarks:

NONE Confirmation Required (Yes / No): No Final Issue Status File Location Operations Acceptance See Page(s): ( APP / FIO/ VOI ): APP ( Gale/ Hold ): Gale Required ( Yes / No ): No Evaluation Number(s) / Revision: NR Component ID(s) / EPN(s) / Line Number(s):

Copy of Applicability Review Attached (Yes / N/R)'PN/R NA Key Words: NMP-1, STRUCTURAL, SQUG, SEWS, SEISMIC VERIFICATION

¹ FORMAT NEP-DES48-F0140 9708070%27 97078K PDR ADOCK 05000220 PDR g g~TJ r

T NIAGARA 4 MOHAWK NUCLEAR ENGINEERING Nine Mile Point Nuclear Station CALCULATIONCONTINUATION SHEET Unit: 1 Disposition:

(Next ~

Page ~>

Originatorg/ ate Checker/Date Caicuiation No. Revision l~ 7 I 7 SO.OSEWS7&69 g /rg 00 ef.

PURPOSE'ocument the Screening Evaluation Work Sheets (SEWS) for the AP/600 TO 120/208 V TRANSFORMER, equipment number 167A.

This SEWS has been prepared as part of the commitment to use the SQUG (GIP) methodology to document the seismic adequacy of SSEL components.

CONCLUSION: The four welds and the four 5/8" diameter cinch anchors are adequate based on the anchor analysis in Attachment A, the cinch anchor capacities given in Calculation SO.OSQUGANCHOR (Ref. 2) and the anchor bolt tightness check results confirming these anchors are tight.

Therefore, the SQUG outlier for 167A is resolved.

ATTACHMENTS A. SEWS for Equipment ID Number 167A B. The Outlier Seismic Verification Sheet (OSVS) for Equipment ID Number 167A I

FORMAT ¹ NEP-DES-08, Rev. 01 (F02)

CALC NO REVISION Niagara Mohawk Power Corporation - Nine Mile Point 1 GIP Rev 2, Corrected, 2/14/9 SCREENING EVALUATIONWORK SHEET (SEWS) Status: No Sheet 1 of 8 ID: TRANS 167A ( Rev. 0) Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 V TRANSFORMER Building 'B Floor El.: 281.00 Room, Row/Col: Q7,8 Manufacturer, Model, Etc.:

SEISMIC CAPACITYVS DEMAND Elevation where equipment receives seismic input 281.00

2. Elevation of seismic input below about 40'rom grade (grade = 243.00) Yes Equipment has fundamental frequency above about 8 Hz (est. frequency = ) SRT
4. Capacity based on: 1.00
  • Bounding Spectrum
5. Demand based on: 1.00* Design Basis Ground Response Spectrum 8.0000 E-001

~

/

LOG

~

r

~ r 1.8000 E-002 2.0000 E-001 LOG Hz 1.0000 E+002 Capacity ..... Demand File Record Capaci F:tGIPtGIPtspectra.des Label Bounding S ectrum Demand 1 F:tGIPtPROJ003Rspectra.des UNIT:IPLANTiBLDG:iBUILDINGIEIQ:iSSEiELEV:iELEVATIONIROWI COL: LL DIR: DIR NODE: 1 Demand 2 F:>GIMP ROJ003Rspectra.des UNIT:IPLANTIBLDG:IBUILDINGIEIQ:ISSEIELEV:IELEVATIONIROWI COL: LL DIR: DIR NODE: 1 Does capacity exceed demand'

REVISION ao Niagara Mohawk Power Corporation - Nine Mile Point 1 GIP Rev 2, Corrected, 2/1 9 SCREENING EVALuATIONWORK SHEET (SEWS) Status: No Sheet 2 of 8 ID: TRANS167A (Rev. 0) Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 V TRANSFORMER Building RB Floor El.: 281.00 Room, Row/Col: Q7,8 Manufacturer, Model, Etc.:

CAVEATS - BOUNDING SPECTRUM TRN/BS Caveat 1 - Earthquake Experience Equipment Class Yes TRN/BS Caveat 2 - Rating of 4.16 KV or Less Yes TRN/BS Caveat 3- Transformer Coils Postively Restrained Within Cabinet Yes TRN/BS Caveat 4 - Coils Top Braced or Analyzed for Large Transformers. Yes TRN/BS Caveat 5- Clearance Between Energized Component and Cabinet. Yes TRN/BS Caveat 6- Adequate Slack in High Voltage Leads. Yes TRN/BS Caveat 7- Wall-Mounted Units Anchored Close to Enclosure Structure. Yes TRN/BS Caveat 8 - Weak-Way Bending of Thin Webs Evaluated. Yes TRN/BS Caveat 9 - Adjacent Cabinets Bolted Together. N/A TRN/BS Caveat 10- Doors Secured. N/A TRN/BS Caveat 11 - Adequate Anchorage. No*

TRN/BS Caveat 12- Potential Chatter of Essential Relays Evaluated. Yes TRN/BS Caveat 13 - No Other Concerns. Yes Is the intent of all the caveats met for Bounding Spectrum' ANCHORAGE

1. The sizes and locations of anchors have been determined N/A
2. Appropnate equipment characteristics have been determined (mass, CG, natural freq., Yes damping, center of rotation).
3. The type of anchorage is covered by the GIP No
4. The adequacy of the anchorage installation has been evaluated (weld quality and length, nuts Yes and washers, expansion anchor tightness, etc.)
5. Factors affecting anchorage capacity or margin of safety have been considered: embedment Yes length, anchor spacing, free-edge distance, concrete strength/condition, and concrete cracking.
6. For bolted anchorages, any gaps under the base are less than 1/4 N/A
7. Factors affecting essential relays have been considered: gaps under the base, capacity Yes reduction for expansion anchors.
8. The base has adequate stiffness and the effect of prying action on anchors has been Yes considered.
9. The strength of the equipment base and the load path to the CG is adequate. Yes
10. The adequacy of embedded steel, grout pads or large concrete pads have been evaluated. Yes
11. The anchorage capacity exceeds the demand. Yes Are anchorage requirements met'P

CALC NO REVISION PAGE NO Niagara Mohawk Power Corporation - Nine Mile Point 1 GIP Rev 2, Corrected, 2/14/92 SCREENING EVALUATIONWORK SHEET (SEWS) Status: No Sheet 3 of 8 ID: TRANS167A (Rev. 0) Class: 4. Transformers

Description:

AP/600 TO 120/208 V TRANSFORMER Building 'B Floor El.: 281.00 Room, Row/Col: Q7,8 Manufacturer, Model, Etc.:

INTERACTION EFFECTS

1. Soft targets are free from impact by nearby equipment or structures Yes
2. If the equipment contains sensitive relays, it is free from all impact by nearby equipment or N/A structures.
3. Attached lines have adequate flexibility Yes
4. Overhead equipment or distribution systems are not likely to collapse. Yes
5. No other adverse concerns were found. Yes Is equipment free of interaction effects?

CQ55JYLEHIR OUTLIER I MPORTANT NOTE: This SEWS is a composite of the original SQUG pilot plant walkdown conducted in January and February of 1988 by D. Moore, A. Ordonez, W Djordjevic, RF Oleck, J Valente, D Aelbrecht, J. Reddington, T.

Hester, D. Tahiliani, J. Raby, and F. Feng using the GIP, Revision 1; a supplementary walkdown conducted by RF Starck, F Feng and W Djordjevic in April 1989 still using Revision 1 of the GIP, and the final walkdown conducted in April 1993 by W Djordjevic and C Agosta to update the SEWS to Revision 2 GIP requirements as required by USNRC in SSER-2.

Anchorage: Transformer is anchored by four 1" welds 1/8" thick.

Evaluated by: Date:

ii> 8

Attachment:

Pictures

Attachment:

ANCHOR Report

REVISiOM PAGE NO Niagara Mohawk Power Corporation - Nine Mile Point 1 GIP Rev 2, Corrected, 2/14/92 SCREENING EVALUATIONWORK SHEET (SEWS) Status: No Sheet4of8 ID: TRANS167A" (Rev. 0) Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 V TRANSFORMER B 'Id' RB FI EI.. 281.00 R,R /C I.Q78 Manufacturer, Model, Etc.:

Panel 167A Transformer

REVISION 4'IP Niagara Mohawk Power Corporation - Nine Mile Point 1 Rev 2, Corrected, 2/14/92 SCREENING EVALUATIONWORK SHEET (SEWS) Status: No Sheet5of8 ID: TRANS 167A'( Rev. 0) Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 V TRANSFORMER B IdRB Floor El.: 281.00 Room, Row/Col: Q7,8 Manufacturer, Model, Etc.:

ANCHOR Report Response Spectrum: SSE Frequency: GIP - Flexible Damping: GIP - 5.00 Spectral Values:

Direction Acceleration (g's)

North - South 0.52 East - West 0.52 Vertical 0.16 Angle: 0.00 Combination Criteria: SRSS Number of Weights: 1 No Weight X Y Z 1 9.75E+002 2.00E+001 1.20E+001 2.00E+001 Em:ms Number of Forces: 0 Rhmants

~ of Moments: 0

'umber hlhMt Number of Anchor types: 1 Tension Shear Ultimate Ultimate Inter Inter Saf No. Dia Manufact Product Tension Shear Coeff Coeff Fact

CALC NO REVISION PA Niagara Mohawk Power Corporation - Nine Mile Point 1 GIP Rev 2, Corrected, 2/14/92 SCREENING EVALUATIONWORK SHEET (SEWS) Status: No Sheet6of8 ID: TRANS 167A" ( Rev. 0 ) Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 V TRANSFORMER B ilding. RB Floor El.: 281.00 Room, Row/Col: Q7,8 Manufacturer, Model, Etc.:

1 3/8 Other Unknown 1460.00 1420.00 1.00 0.30 1.00 Expansion Anchor Ultimate Stress: 4000.00 psi.

Reduction Factor: 0.85 Allowable Stress: 30600 psi.

Surhzm Number of Surfaces: 1 Direction Direction Direction Comp Comp Com Ny Nz 1 O.OOE+000 O.OOE+ 000 1.00E+000 Anchor Pattern for Surface ¹ 1 IY Legend for Anchor Patterns

CAI.C NO oSE~

REVISION Niagara Mohawk Power Corporation - Nine Mile Point 1 GIP Rev 2, Corrected, 2/14/92 SCREENING EVALUATIONWORK SHEET (SEWS) Status: No Sheet 7 of 8 ID: TRANS167A (Rev. 0) Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 V TRANSFORMER Building: RB Floor El.: 281.00 Room, Row/Col: Q7,8 Manufacturer, Model, Etc.:

Anchors:

Concrete Uncs:

Concrete Points:

Vleld Uncs:

Number of Anchors: 0

¹ of elements per line: 1 Number of Concrete Lines: 4 stan sta~ stuart End End End sf Line No X-Coord Y-Coord Z-Coord X-Coord Y-Coord Z-Coord ld Width O.OOE+000 1.00E+ 000 O.OOE+000 4.00E+001 1.00E+000 O.OOE+000 1 2.00E+000 3.90E+001 O.OOE+ 000 O.OOE+000 3.90E+001 2.40E+001 O.OOE+000 1 2.00E+000 4.00E+001 2.30E+001 O.OOE+000 0.00E+000 2.30E+001 O.OOE+000 1 2.00E+000 1.00E+000 2.40E+001 0.00E+000 1.00E+000 0.00E+000 0.00E+000 1 2.00E+000 Number of Concrete Points: 0 Kaid.loom~

¹ of elements per line: 1 Number of Weld Lines: 4 start start start End End End sf Line No X-Coord Y-Coord Z-Coord X-Coord Y-Coord Z-Coord Id Width 1 1.00E+000 O.OOE+000 1.00E+000 1.00E+000 1.00E+000 1.00E+000 1 1.25E-001 2 3.90E+001 O.OOE+000 1.00E+000 3.90E+ 001 1.00E+000 1.00E+000 1 1.25E-001 3 1.00E+000 2.30E+001 1.00E+000 1.00E+000 2.40E+001 1.00E+000 1 1.25E-001 4 3.90E+001 2.30E+001 1.00E+000 3.90E+001 2.40E+001 1.00E+000 1 1 25E-001

REVISION Oo 4l PAGE NO Niagara Mohawk Power Corporation - Nine Mile Point 1 GIP Rev 2, Corrected, 2/14/92 SCREENING EVALUATIONWORK SHEET (SEWS) Status: No Sheet 8 of 8 ID: TRANS 167A' Rev. 0 ) Class: 4. Transformers

==

Description:==

AP/600 TO 120/208 V TRANSFORMER B ilding. RB Floor El.: 281.00 Room, Row/Col: Q7,8 Manufacturer, Model, Etc.:

Reduction Factors Data Current: Yes Analysis Performed: Yes Type of Analysis: Regular Spectral Accelerations (G's) Allowable No N-S E-W Vertical Load Factor 5.17E-001 2.07E-001 6.50E-002 12.824 2 -5.17E-001 -2.07E-001 -6.50E-002 13.885 3 -5.17E-001 2.07E-001 6.50E-002 12.824 5.17E-001 -2.07E-001 -6.50E-002 13.885 5.17E-001 -2.07E-001 6.50E-002 12.824 6 -5 17E-001 2 07E-001 4.50E-002 13.885 7 5.17E-001 2.07E-001 -6.50E-002 13.885 8 -5.17E-001 -2.07E-001 6.50E-002 12.824 9 2.07E-001 5.17E-001 6.50E-002 11.125 10 -2.07E-001 -5.17E-001 -6.50E-002 12.130 11 2.07E-001 -5.17E-001 6.50E-002 11.125 12 -2.07E-001 5.17E-001 -6.50E-002 12.130 13 -2.07E-001 5.17E-001 6.50E-002 11.125 14 2.07E-001 -5.17E-001  %.50E-002 12.130 15 2.07E-001 5.17E-001  %.50E-002 12.130 16 -2.07E-001 -5.17E-001 6.50E-002 11.125 17 2.07E-001 2.07E-001 1.63E-001 19.044 18 -2.07E-001 -2.07E-001 -1.63E-001 28.093 19 2.07E-001 2.07E-001 -1.63E-001 28.093 20 -2.07E-001 -2.07E-001 1.63E-001 19.044 21 -2.07E-001 2.07E-001 1.63E-001 19.044 22 2.07E-001 -2.07E-001 -1.63E-001 28.093 23 2.07E-001 -2.07E-001 1.63E-001 19.044 24 -2.07E-001 2.07E-001 -1.63E-001 28.093 Minimum Allowable Load Factor: 1.11E+001

ATTACHMENT CANR0 REVISION PAGE NQ Ib Response Spectrum: User Frequency: User- 0.00 Percent Damping: User- 0.00 S ectral Values:

Direction Acceleration 's North - South 1.100 East - West 1.050 Vertical 0.170 Angle (N-S Direction makes with the X Axis): 0.00 Combination Criteria: SRSS

~Wsl hts:

Number of Weights: 1 No Wei ht X 1 975.00 15.500 18.000 18.750 Forces Number of External Forces: 0

~Mome ts:

Number of External Moments: 0

~ttowabtes .

Anchor Number of Anchor types: 1 Tension Shear Ultimate Ultimate Inter Inter Saf No Dia Manufact Product Tension Shear Coeff Coeff Fact 518 Other Unknown 970.00 1400.00 1.00 0.30 1.00 Expansion Anchor Concrete Ultimate Stress: 3500.00 psL Reduction Factor: 0.85 Weld Allowable Stress: 30600 psl.

Surfaces:

Number of Surfaces: 1 Surface Orientation Direction Direction Direction Com Com Com N Nz 0.000 0.000 1.000

ATTACHMENT CAI.C NO REVISION PAGE NO Anchor Pattern for Surface ¹ 1 Le end for Anchor Patterns

~Geomet

~ocher .

Number of Anchors: 4 Anch X Surf ld Coord Coord Coord ld 12.000 2.000 0.000 22.000 17.500 0.000 12.000 33.000 0.000 2.000 17.500 0.000 1

¹ of elements per line: 4 Number of Concrete Lines: 4

E ATTACHMENT CALC NO 4'S d-~

REVISION Start Start Start End End End Sf Line X&oord Y-Coord Z-Coord X-Coord Y-Coord Z-Coord Id Width 0.000 2.000 0.000 24.000 2.000 0.000 1 4.000 22.000 0.000 0.000 22.000 35.000 0.000 4.000 24.000 33.000 0.000 0.000 33.000 0.000 1 4.000 2.000 35.000 0.000 2. 00 0.000 0.000 1 4.000 "Number of Concrete Points: 0

~Weld ee

¹ of elements per line: 4 Number of Weld LInes: 0 Determinatio of eductio Factors Reduction Factor Input for Anchor 1 ¹ No Input - Reduction factors needing user input are not used.

Reduction Factor Input for Anchor ¹2 No Input - Reduction factors needing user input are not used.

'I Reduction Factor Input for Anchor ¹3 No Input - Reduction factors needing user input are not used.

Reduction Factor Input for Anchor ¹4 No Input - Reduction factors needing user input are not used.

Reduction Factors Data Current: Yes Pall/ Pallrl No Vali Vallr RT RN RL RG RS RE RF RC RR RP RB RM 970.00 X X X X X X X X X X N/A X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 970.00 X X X X X X X X X X N/A X X X X X X X X X X 970.00 N/A X X X X X X X X X X NIA X X X X X X X X X X Le end N/A = Not A licable Pall = Allowable Pull without Reduced Ins ction Vali = Allowable Shear without Reduced Ins ction Pallr = Allowable Pull with Reduced Ins ection Vallr = Allowable Shear with Reduced Ins ection

= Outlier

= Reduction Factor Not Used RT = Reduction Factor for T e of Anchora e RN = Reduction Factor for Installation Ade uac RL = Reduction Factor for Embedment

ArlACHMEN CALC HO f

REVELS(OM PAGE NO RG = Reduction Factor for Ga at Anchors RS = Reduction Factor for S acin RE = Reduction Factor for Ed e Distance RF = Reduction Factor for Concrete Stren h RC = Reduction Factor for Concrete Cracks RR = Reduction Factor for Essential Rela s RP = Reduction Factor for Base Stiffness and P in Action RB = Reduction Factor for Base Stren th and Load Path RM = Reduction Factor for Embed. Steel and Pads Anal sis Results.

Analysis Performed: Yes of Anal sis: Re ular S ctral Accelerations G's No N-S E-W Vertical Safet Factor 1.100 0.420 0.068 2.177

-1.100 -0.420 -0.068 2.485

-1.100 0.420 0.068 2.351 1.100 -0.420 -0.068 2.235 1.100 -0.420 0.068 2.177

<<1.100 0.420 -0.068 2.485 1.100 0.420 -0.068 2.235

-1.100 -0.420 0.068 2.351 0.440 1.050 0.068 2.992 10 -OA40 -1.050 -0.068 3 187 0.440 -1.050 0.068 3.013 12 -0.440 1.050 -0.068 3.155 13 -0.440 1.050 0.068 2.992 14 OA40 -1.050 -0.068 3.179 15 0.440 1.050 -0.068 3.155 16 -0.440 -1.050 0.068 3.013 17 0.440 0.420 0.170 4.750 18 -0.440 -0.420 -0.170 6.439 19 0.440 0.420 <<0.170 5.544 20 -0.440 -0.420 0.170 4.677 21 -0.440 0.420 0.170 4.627 0.440 -0.420 -0.170 23 0.440 -0.420 0.170 4.750 24 -0.440 0.420 -0.170 6.352 Minimum Safety Factor: 2.177 The anchorage can withstand 2.177 times greater seismic demand

CALC NO REVISION PAGE OUTLIER SEISMIC VERIFICATION SHEET (OSVS) GIP Rev Sheet 1 of 2 ID: TRANS 167A Rev. 0 Class: 4. Transformers Descri tion: AP/600 TO 120/208 V TRANSFORMER Buiidin: RB Floor El.: 281.00 Room Row/Col: Q7,8

1. OUTLIER ISSUE DEFINITION - Mechanical and Electrical E ui ment
a. Identify all the screening guidelines which are not met. (Check more than one if several guidelines could not be satisfied.)

Ca acit vs. Demand Caveats Anchora e Seismic Interaction Other

b. Describe all the reasons for the outlier (I.e., if all the listed outlier issues were resolved, then the signatories would consider this item of equipment to be verified for seismic adequacy) ~

Cast-in-place (embedded) channels are anchored by Cinch (leaded) type expansion anchors. The GIP does not cover this anchor t ificall it rovides no known ca acit for this anchor t

2. PROPOSED METHOD OF OUTLIER RESOLUTION 0 tional
a. Defined proposed method(s) for resolving outlier.

Establish an allowable capacity for this anchor type by reviewing appropriate documentation and compare this ca acit to the seismic demand, and/or retrofit the anchors e.

b. Provide information needed to implement proposed method(s) for resolving outlier (e.g., estimate of fundamental frequency).
3. COMMENTS
4. CERTIFICATION:

I The information on this OSVS is, to the best of our knowledge and belief, correct and accurate, and resolution of the outlier issues listed on the previous page will satisfy the requirments for this item of equipment to be verified for seismic adequacy:

Approved by: Date:

/u

Attachment:

Pictures

CALC WO REVISION PAGE NO OUTLIER SEISMIC VERIFICATION SHEET (OSVS) GIP Rev Sheet 2 of 2 ID: TRANS167A* Rev. 0 Class: 4. Transformers Descri tion: AP/600 TO 120/208 V TRANSFORMER Buildin: RB Floor El.: 281.00 Room, Row/Col: Q7,8 PICTURES Panel 167A Transformer