NG-16-0128, Inservice Testing Program for the Fifth Ten-Year Interval

From kanterella
(Redirected from ML16172A049)
Jump to navigation Jump to search
Inservice Testing Program for the Fifth Ten-Year Interval
ML16172A049
Person / Time
Site: Duane Arnold NextEra Energy icon.png
Issue date: 06/15/2016
From: Vehec T
NextEra Energy Duane Arnold
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NG-16-0128
Download: ML16172A049 (189)


Text

{{#Wiki_filter:NEXTeraM ENERGY~ DUANE ARNOLD June 15, 2016 NG-16-0128 10 CFR 50.55a U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Duane Arnold Energy Center Docket No. 50-331 Renewed Op. License No. DPR-49 Duane Arnold Energy Center lnservice Testing Program for the Fifth Ten-Year Interval Pursuant to 10 CFR 50.55a(f), NextEra Energy Duane Arnold, LLC (NextEra Energy Duane Arnold) updated the Duane Arnold Energy Center (DAEC) lnservice Testing (IST) Program for the fifth ten-year interval. -The IST program document identifies the inservice testing that will be performed at DAEC to meet the requirements of 10 CFR 50.55a during the fifth ten-year interval, whicli commenced on February 1, 2016. The ASME Code for Operation and Maintenance (OM) of Nuclear Power Plants applicable to DAEC's fifth interval IST program is the 2004 Edition through 2006 addendum. NextEra Energy Duane Arnold is submitting the attached IST program description in accordance with section ISTA-3200 of the ASME OM Code This letter makes no ne~ commitments or changes to existing-commitments. If you have any questions, please contact J. Michael Davis at (319) 851-7032. T~Ab~/f~J Vice President, Duane Arnold Energy Center NextEra Energy Duane Arnold, LLC Attachment cc: Regional Administrator, USNRC, Region Ill Project Manager, USNRC, Duane Arnold Energy Center - Senior Resident Inspector, USNRC, Duane Arnold Energy Center NextEra Energy Duane Arnold, lLC, 3277 DAEC Road, Palo, IA 52324

Attachment to NG-16-0128 Duane Arnold Energy Center lnservice Testing Program for the Fifth Ten-Year Interval 187 pages follow

NEXTera DUANE ARNOLD ENERGY CENTER (DAEC) DAEC Station 5th Interval In-Service Testing (IST) Program Commercial Service Date: February 1, 1975 (Docket no. 50-331) 3277 DAEC Road Palo, lowa52324 Page 1of14 Revision 00 I

NEXTera DAEC Station 5th Interval Duane Arnold Energy Center (DAEC) ln-Service_Testing (ISD Program INwSERVICE TESTING (!ST) PROGRAM PREPARATION ANP*APPROVAL Record the following: Date I Time: _ _ _ _ _ _ I _ _ _ _ Initials: _ __ i NOTE: User shall pefform and document a Temp Issue Rev. C/Jeck to ensure revision is current, in accordance with procedure use and adherence requirements.

  • Date: 6/ '6 / 'J...CJ/ 6 Reviewed By: o uruR.C. Date: 6 lnservice Testing Print Engineer Reviewed By: . h J: