ENCLOSURE SAFETY EVALUATION REPORT BY THE OFFICE OF NUCLEAR REACTOR REGULATION GENERIC LETTER 83-28, ITEM 1.2, POST-TRIP REVIEW (DATA AND INFORMATION CAPABILITY)

DUKE POWER COMPANY OCONEE NUCLEAR STATION, UNITS 1, 2 AND 3 DOCKET NOS. 50-269, 50-270 AND 50-287 I. INTRODUCTION On February 25, 1983, at the Salem Nuclear Power Plant (SNPP) Unit 1, both of the scram circuit breakers failed to open on an automatic reactor trip signal from the reactor protection system. This incident occurred during plant start-up and the operator tripped the reactor manually about thirty seconds after the initiation of the automatic trip signal.

The failure of the circuit breakers has been determined to be related to the sticking of the undervoltage trip attachment. On February 22, 1983, during start-up of SNPP, Unit 1, an automatic trip signal occurred as a result of steam generator low-low level.

In this case, the reactor was tripped manually by the operator almost coincidentally with the automatic trip. Following these incidents, on February 28, 1983, the staff started to investigate and report on the generic implications of these occurrences. The results of the staff's inquiry into these incidents are reported in NUREG-1000, "Generic Implications of ATWS Events at the Salem Nuclear Power Plant."

As a result of this investigation, the NRC requested (by Generic Letter 83-28 dated July 8, 1983) all licensees of operating reactors, applicants for an operating license, and holders of construction permits to respond to certain generic concerns. These concerns are categorized into four areas:

(1) Post-Trip Review, (2) Equipment Classification and Vendor Interface, (3) Post-Maintenance Testing, and (4)

Reactor Trip System Reliability Improvements.

The first action item, Post-Trip Review, consists of Action Item 1.1, "Program Description and Procedure" and Action Item 1.2, "Data and Information Capability."

This safety evaluation addresses Item 1.2 only.

II. REVIEW GUIDELINES The staff developed the review guidelines after initial evaluation of the various utility responses to Item 1.2 of Generic Letter 83-28 and incorporated the best features of these submittals. These guidelines represent a "good practices" approach to post-trip review. We have reviewed the licensee's response to Item 1.2 against these guidelines:

A. The equipment that provides the digital sequence of events (SOE) and the analog time history records of a reactor trip should provide a reliable source of information which would be used in the post-trip review. Each plant variable needed to determine the cause and development of the events following a plant trip should be monitored by at least one recorder (such as a sequence-of-events recorder or a plant process computer) for digital parameters; and strip charts, a plant process computer or analog recorder for analog (time history) variables.

Performance characteristics guidelines for SOE and time history recorders are as follows:

8609160432 860911 PDR ADOCK 05000269

-2 o

Each sequence of events recorder should be capable of detecting and recording the sequence of events with a sufficient time discrimination capability to ensure that the time responses associated with each monitored safety-related system can be ascertained, and that a determination can be made as to whether the time response is within acceptable limits based on the Final Safety Analysis Report, (FSAR)

Chapter 15:

Accident Analyses. The recommended guidelines for the SOE time discrimination is approximately 100 milliseconds. If current SOE recorders do not have this time discrimination capability, the licensee should show that the current time discrimination capability is sufficient for an adequate reconstruction of the course of the reactor trip and post-trip events. As a minimum this should include the ability to adequately reconstruct the transient and accident scenarios presented in Chapter 15 of the FSAR.

o Each analog time history data recorder should have a sample interval small enough so the incident can be accurately reconstructed following a reactor trip. As a minimum, the licensee should be able to reconstruct the course of the transient and accident sequences which have been evaluated in the accident analyses of Chapter 15 of the plant FSAR. The recommended guideline for the sample interval is ten seconds. If the time history equipment does not meet this guideline, the licensee should show that the time history capability is sufficient to accurately reconstruct the transient and accident sequences presented in Chapter 15 of the FSAR. To support the post trip analysis of the cause of the trip and the proper functioning of involved safety related equipment, each analog time history data recorder should be capable of updating and retaining information from approximately five minutes prior to the trip until at least ten minutes after the trip.

o All equipment used to record sequence of events and time history information, should be powered from a reliable and non-interruptible power source. The power source does not need to be Class IE.

B. The sequence of events and time history recording equipment should monitor sufficient digital and analog parameters to assure that the course of the reactor trip and post-trip events can be reconstructed.

The parameters should provide sufficient information to determine the root cause of the reactor trip, the development of the reactor trip, and the response of the protection and safety systems to the reactor trip.

Specifically, all parameters initiating reactor trips, safety injections and other safety-related systems and parameters monitoring the response of these systems should be recorded and used in the post-trip review. Table 1 lists those parameters which the licensee should know as a minimum, to perform a post-trip review that would determine if the plant remained within its safety limit design envelope. The staff selected these parameters based on engineering judgment and following complete evaluation of the utility submittals. If the licensee's SOE recorders and time history recorders do not monitor all of the parameters suggested in these tables, the licensee should show that the existing set of monitored parameters are sufficient to establish that the plant remained within the design envelope for the accident conditions analyzed in Chapter 15 of the plant FSAR.

-3 C. The information gathered by the sequence of events and time history recorders should be stored in a manner that will allow for data retrieval and analysis. The data may be retained in either hardcopy (e.g.,

computer printout, strip chart record), or in an accessible memory (e.g.,

magnetic disc or tape).

The licensee should be able to present this information in a readable and meaningful format, taking into consideration good human factors practices such as those outlined in NUREG-0700.

D. Data from all unscheduled shutdowns provide a valuable reference in determining the acceptability of plant vital parameters and equipment response at the next unscheduled shutdown. Information gathered during post-trip reviews should be saved for the life of the plant for post-trip.

review comparisons of subsequent events.

III. EVALUATION AND CONCLUSION By letters dated November 4, 1983 and February 27, 1986, Duke Power Company sent information on its post-trip review program for the Oconee Nuclear Station, Units 1, 2 and 3. We have evaluated the licensee's submittals against the review guidelines described in Section II. A brief description of the licensee's responses and the staff's evaluation of the response against each of the review guidelines follows:

A. The licensee has described the characteristics of the equipment used to record the sequence of events and time history data.

Based on our review of the licensee's submittals, we find that the sequence of events recorder and time history characteristics conform to the guidelines described n Section II. A, and are acceptable.

B. The licensee has identified the parameters to be monitored and recorded for post-trip review. Based on our review, we conclude that he has included all of those identified in Table 1. His parameters conform to the guidelines described in Section II.B and, therefore, are acceptable.

C. The licensee's submittals describe the method for both storing and retrieving the information gathered by the sequence of events and time history recorders, and presenting this information during post-trip review and analysis. We find that this information is being presented in a readable and meaningful format, and is being stored, retrieved and presented in conformance with the guidelines of Section II. C.

D. The licensee's February 27, 1986 letter states that typically, reports of non-routine events are kept for six years in accordance with ANSI 45.2.9. The licensee further states that it may be necessary to clarify retention requirements for post-trip reviews in this standard. Duke will pursue a definitive resolution of this issue with the appropriate ANSI Committee. While resolution of this issue is pending, the licensee has committed to keep indefinitely the data and information used in post-trip reviews. In the interim, the staff finds this acceptable.

-4 Based on our review of the-licensee's submittals, we conclude that the licensee's capabilities for post-trip review of data and information are acceptable for the Oconee Nuclear Station, Units 1, 2 and 3.

IV. IMPLEMENTATION In a letter dated August 12, 1986, Duke Power Company states that this action has been completed.

Dated:

Principal Contributor: J. Kramer

TABLE 1 PWR PARAMETER LIST SOE Time History Recorder Recorder Parameter/Signal (1) X Reactor Trip (1) x Safety Injection

.x Containment Isolation (1) 1x Turbine Trip x

Control Rod Position (I) x x

Neutron Flux, Power x

x Containment Pressure (2)

Containment Radiation x

Containment Sump Level (1) x x

Primary System Pressure (1) x x

Primary System Temperature

()

x Pressurizer Level (1 ).x Reactor Coolant Pump Status (1) X x

Primary System Flow (3)

Safety Inj.; Flow, Pump/Valve Status x

MSIV Position x

x Steam Generator Pressure (1) X x

Steam Generator Level (1) x x

Feedwater Flow (1) x x

Steam Flow L'

SOE Time History Recorder Recorder Parameter/Signal (3)

Auxiliary Feedwater System: Flow, Pump/Valve Status x

AC and DC System Status (Bus Voltage) x Diesel Generator Status (Start/Stop, On/Off) x PORV Position (1) Trip parameters (2) Parameter may be monitored by either an SE or time history recorder.

(3) Acceptable recorder options are; (a) system flow recorded on an SE recorder. (b) system flow recorded on a time history recorder, or (c) equipment status recorded on an SOE recorder.