MONTHYEARML13120A1052013-04-26026 April 2013 Response to Request for Information: Near-Term Task Force Recommendation 2.1, Seismic Reevaluation Project stage: Response to RAI ML13259A0442013-09-12012 September 2013 Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding the Seismic Aspects of Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident - 1.5 Year Response for CEUS Sites Project stage: Response to RAI ML14051A1072014-02-12012 February 2014 Update to Response to NRC Request for Information Pursuant to 10CFR50.54(f) Seismic Aspects of Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident - 1.5 Year Response for CEUS Sites Project stage: Response to RAI ML14125A3672014-03-12012 March 2014 Drawing LRA-M-2032-1, Rev. Aj, Sump Pump Diagram Radwaste System Project stage: Request BVY 14-019, Notification of Revised Regulatory Commitments Associated with Request for Information Per 10 CFR50.54(f) Regarding Recommendations 2.1, 2.3, & 9.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident .2014-03-12012 March 2014 Notification of Revised Regulatory Commitments Associated with Request for Information Per 10 CFR50.54(f) Regarding Recommendations 2.1, 2.3, & 9.3 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident . Project stage: Request SBK-L-14052, NextEra Energy Seabrook, LLC Seismic Hazard and Screening Report (CEUS Sites) Response to NRC Request for Information Per 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-2014-03-27027 March 2014 NextEra Energy Seabrook, LLC Seismic Hazard and Screening Report (CEUS Sites) Response to NRC Request for Information Per 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ich Project stage: Response to RAI NL-14-0343, Seismic Hazard and Screening Report for CEUS Sites2014-03-31031 March 2014 Seismic Hazard and Screening Report for CEUS Sites Project stage: Request NRC-14-0017, DTE Electric Companys Seismic Hazard and Screening Report, Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accide2014-03-31031 March 2014 DTE Electric Companys Seismic Hazard and Screening Report, Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident Project stage: Response to RAI NRC 2014-0024, NextEra Energy Point Beach, LLC - Seismic Hazard and Screening Report (CEUS Sites), Response NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the F2014-03-31031 March 2014 NextEra Energy Point Beach, LLC - Seismic Hazard and Screening Report (CEUS Sites), Response NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukush Project stage: Request NL-14-0344, Seismic Hazard and Screening Report for CEUS Sites2014-03-31031 March 2014 Seismic Hazard and Screening Report for CEUS Sites Project stage: Request CNL-14-038, Tennessee Valley Authoritys Seismic Hazard & Screening Report (CEUS Sites), Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Recommendation 2.1 of Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Acci2014-03-31031 March 2014 Tennessee Valley Authoritys Seismic Hazard & Screening Report (CEUS Sites), Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Recommendation 2.1 of Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accide Project stage: Response to RAI RNP-RA/14-0013, Seismic Hazard Evaluation, Response to NRC 10 CFR 50.54(f) Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f)Regarding Recommendations 2.1, 2.3 and 9.3 of the Near-Term Task Force Review of2014-03-31031 March 2014 Seismic Hazard Evaluation, Response to NRC 10 CFR 50.54(f) Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f)Regarding Recommendations 2.1, 2.3 and 9.3 of the Near-Term Task Force Review of Project stage: Request ML14099A1962014-03-31031 March 2014 Constellation Energy Nuclear Group, LLC - Seismic Hazard and Screening Report (CEUS Sites), Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Project stage: Response to RAI ML14092A4162014-03-31031 March 2014 Response to March 12, 2012 Information Request Seismic Hazard and Screening Report (CEUS Sites)For Recommendation 2.1 Project stage: Request L-MT-14-045, Seismic Hazard and Screening Report (CEUS Sites), Response to NRC Request for Information Pursuant to 10CFR50.54(f), Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident2014-05-14014 May 2014 Seismic Hazard and Screening Report (CEUS Sites), Response to NRC Request for Information Pursuant to 10CFR50.54(f), Regarding Recommendation 2.1 of the Near-Term Task Force Review of Insights from the Fukushima Dai-ichi Accident Project stage: Response to RAI RA-14-071, Supplemental Information Regarding Seismic Hazard and Screening Report (Central and Eastern United States (CEUS) Sites) - Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Tas2014-08-21021 August 2014 Supplemental Information Regarding Seismic Hazard and Screening Report (Central and Eastern United States (CEUS) Sites) - Response to NRC Request for Information Pursuant to 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term Task Project stage: Supplement ML14307B7072014-12-10010 December 2014 Supplemental Information Related to Development of Seismic Risk Evaluations for Information Request Pursuant to Title 10 of the Code of Federal Regulations 50.54(f) Regarding Seismic Hazard Reevaluations for Recommendation 2.1 of the Near-T Project stage: Other ML14349A4952014-12-10010 December 2014 Proposed Change to Technical Specifications Concerning the Safety Limit Minimum Critical Power Ratio Project stage: Request ML15034A1062015-02-0303 February 2015 Supplemental Information Needed for Acceptance of Requested Licensing Action Regarding the Safety Limit Minimum Critical Power Ratio License Amendment Request Project stage: Acceptance Review ML15050A2452015-02-13013 February 2015 Response to Request for Supplemental Information Needed for Acceptance of Requested Licensing Action Regarding the Safety Limit Minimum Critical Power Ratio License Amendment Request Project stage: Supplement ML15051A2832015-02-19019 February 2015 NRR E-mail Capture - Pilgrim - Acceptance Review Safety Limit Minimum Critical Power Ratio (MF5431) Project stage: Acceptance Review ML15051A0232015-02-25025 February 2015 Request for Withholding Information from Public Disclosure (Tac No. MF5431) Project stage: Withholding Request Acceptance ML15051A0322015-02-25025 February 2015 Request for Additional Information Regarding the Safety Limit Minimum Critical Power Ratio License Amendment Request Project stage: RAI NRC-2015-0053, Federal Register Notice - License Amendment Application; Opportunity to Comment, Request a Hearing, and Petition for Leave to Intervene; Order for Entergy Nuclear Operations, Inc. Pilgrim Nuclear Power Station2015-03-0606 March 2015 Federal Register Notice - License Amendment Application; Opportunity to Comment, Request a Hearing, and Petition for Leave to Intervene; Order for Entergy Nuclear Operations, Inc. Pilgrim Nuclear Power Station Project stage: Other ML15051A0242015-03-0606 March 2015 Individual Notice of Consideration of Issuance of Amendment to Facility Operating License, Proposed No Significant Hazards Consideration Determination & Opportunity for a Hearing & Order Imposing Procedures for Document Access (MF5431) Project stage: Other ML15051A0272015-03-0606 March 2015 Federal Register Notice - License Amendment Application; Opportunity to Comment, Request a Hearing, and Petition for Leave to Intervene; Order for Entergy Nuclear Operations, Inc. Pilgrim Nuclear Power Station Project stage: Other ML15075A0332015-03-11011 March 2015 Response to NRC Request for Additional Information Regarding the Safety Limit Minimum Critical Power Ratio License Amendment Request Project stage: Response to RAI ML15037A5232015-03-27027 March 2015 Request for Withholding Information from Public Disclosure Project stage: Withholding Request Acceptance ML15114A0212015-05-0606 May 2015 Issuance of Amendment Regarding the Minimum Critical Power Ratio License Amendment Request Project stage: Approval 2014-08-21
[Table View] |
Text
1 NRR-PMDAPEm Resource From:
Morgan, Nadiyah Sent:
Thursday, February 19, 2015 4:34 PM To:
Williams, Murray (mwill13@entergy.com)
Subject:
PILGRIM - ACCEPTANCE REVIEW RE: Safety Limit Minimum Critical Power Ratio (MF5431)
- Murray, By letter dated December 10, 2014 (Agencywide Document Access and Management System (ADAMS)
Accession No. ML14349A495), as supplemented by letter dated February 13, 2015 (ADAMS Accession No. ML15050A245), Entergy Nuclear Operations, Inc. submitted a license amendment request (LAR) for Pilgrim Nuclear Power Station. The LAR would change the Safety Limit Minimum Critical Power Ratio from > 1.08 to >
1.10 for two recirculation loop operation and from > 1.11 to > 1.12 for single loop operation. The purpose of this e-mail is to provide the results of the Nuclear Regulatory Commission (NRC) staffs acceptance review of PRR-26. The acceptance review was performed to determine if there is sufficient technical information in scope and depth to allow the NRC staff to complete its detailed technical review. The acceptance review is also intended to identify whether the application has any readily apparent information insufficiencies in its characterization of the regulatory requirements or the licensing basis of the plant.
The NRC staff has reviewed your application and the supplement, and concluded that it does provide technical information in sufficient detail to enable the NRC staff to complete its detailed technical review and make an independent assessment regarding the acceptability of the proposed amendment in terms of regulatory requirements and the protection of public health and safety and the environment. Given the lesser scope and depth of the acceptance review as compared to the detailed technical review, there may be instances in which issues that impact the NRC staffs ability to complete the detailed technical review are identified despite completion of an adequate acceptance review. If additional information is needed, you will be advised by separate correspondence.
If you have any issues regarding this matter, please contact me.
- Thanks, Dee Nadiyah S. Morgan Calvert Cliffs and Pilgrim Project Manager, NRR US Nuclear Regulatory Commission O-8F4 (301) 415-1016 Nadiyah.Morgan@NRC.GOV
Hearing Identifier:
NRR_PMDA Email Number:
1884 Mail Envelope Properties (Nadiyah.Morgan@nrc.gov20150219163300)
Subject:
PILGRIM - ACCEPTANCE REVIEW RE: Safety Limit Minimum Critical Power Ratio (MF5431)
Sent Date:
2/19/2015 4:33:53 PM Received Date:
2/19/2015 4:33:00 PM From:
Morgan, Nadiyah Created By:
Nadiyah.Morgan@nrc.gov Recipients:
"Williams, Murray (mwill13@entergy.com)" <mwill13@entergy.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 2099 2/19/2015 4:33:00 PM Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received: