ML14079A520
| ML14079A520 | |
| Person / Time | |
|---|---|
| Site: | Calvert Cliffs |
| Issue date: | 03/19/2014 |
| From: | Fick M Calvert Cliffs, Constellation Energy Nuclear Group, EDF Group |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| Download: ML14079A520 (79) | |
Text
A Calvert Cliffs Nuclear Power Plant 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 CENG.
a joint venture of CALVERT CLIFFS NUCLEAR POWER PLANT March 19, 2014 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:
SUBJECT:
Document Control Desk Calvert Cliffs Nuclear Power Plant Unit No. 1; Docket No. 50-317 Emergency Response Data System The attached revision to the Emergency Response Data System (ERDS) Data Point Library for the Calvert Cliffs Nuclear Power Plant is provided pursuant to 10 CFR Part 50, Appendix E,Section VI.3.a.
The revision is necessary based on the replacement of the Unit 1 Plant Computer during the Spring 2014 Refueling Outage.
The table below provides a brief summary of the changes:
Point Identifier Unit Description Old Range New Range 1SP1I09 1
LOG Power 1E 200 Same ISP2I 12 1
Reactor Vessel Level N/A Same 1SP2113 1
Core Exit Temp 40 - 2300 Same 1 SP3123 1
Core Subcooled Margin 40-2300 Same IF131A 1
RCS Total Flow Ch. A
-53.57 - 151.48 Same 1SP3117A I
SG Level Loop 11
-401.0 - 63.5 Same 1SP3117B 1
SG Level Loop 12
-401.0 - 63.5 Same 1 SP3I16A 1
SG Pressure Loop 11 0- 1200 Same 1SP3116B I
SG Pressure Loop 12 0 - 1200 Same 1F1111%
1 FW Flow to Steam Gen. 11 0-6000 Same 1F1121%
1 FW Flow to Steam Gen. 12 0-6000 Same 1SP3118A 1
Aux Feed Flow Loop I 1 0- 1500 Same 1SP3118B 1
Aux Feed Flow Loop 12 0- 1500 Same 1 SP0106A 1
THOT Loop 11 50 - 700 Same lSPOI06B 1
THOT Loop 12 50- 700 Same 1SP3113A 1
TCOLD Loop 11 50-700 Same ISP3113B 1
TCOLD Loop 12 50-700 Same 1 SP3120 1
Pressurizer Pressure 0 - 4000 Same 1 SP2109 1
Pressurizer Level 0 - 360 Same A(02,(.p
Document Control Desk March 19, 2014 Page 2 Point Identifier Unit Description Old Range New Range 1SPII14 1
CHG Pump Flow 0- 150 Same 1SP2I15 1
HPSI Flow 0 - 1600 Same 1SP2116 1
LPSI Flow 0 - 8000 Same 1SP4112 1
Cntmt Level 0- 120 Same 1 R5415!
1 WR EFF Monitor 1E1 - 1E13 Same 1 SP6120 1
Liquid Waste Rad 1E1 - 1E6 Same 1SP6117 1
Off Gas Rad 0-250 Same 1 SP6121 1
Cntmt Rad 1 - 1E8 Same 1R5202!
1 Process Rad Monitor 1EI - 1E6 Same 1R5421!
1 Main Stm Rad Lp 11 1E 1E4 IE 1E4 1R5422!
I Main Stm Rad Lp 12 IE IE4 1E 1E4 1R4014!
1 Stm Gen Blowdown Activity lE1 - 1E6 Same ISP4I10 1
Cntmt Pressure 150 Same 1SP4111 I
Cntmt Temperature 50 - 300 Same 1SPIRWLVL 1
Refueling Water Tank Level 0-40 Same X2433 (OLD)
I Wind Speed 60 Meter 15 Minute Avg 0 - 50 Same 1WS60# 15M X2367 (OLD) 1 Wind Direction 60 Meter 15 Minute 0 - 360 Same 1WD60#15M Avg 1WSI0#15M I
Wind Speed 10 Meter 15 Minute Avg N/A 0- 50 (new Point) 1WD10#15M I
Wind Direction 10 Meter 15 Minute N/A 0 - 360 (new Point)
Avg 1MMSDTASTB 1
Wind Stability Based on Delta Temp N/A 0 (A) - 6 (G)
(A)
IMMSS60STB 1
60 Meter Wind Stability - Sigma N/A 0 (A) - 6 (G)
Theta The "before" and "after" ERDS Data Point Library sheets are attached.
There are no regulatory commitments contained in this correspondence.
Should you have questions regarding this matter, please contact Mr. Douglas E. Lauver at (410) 495-5219.
Very truly yours, Michael J. Fick Director-Emergency Planning MJF/PSF/bjd
Attachment:
Emergency Response Data System Data Point Library (76 pages) cc:
N. S. Morgan, NRC W. M. Dean, NRC Resident Inspector, NRC S. Gray, DNR
ATTACHMENT EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY (76 pages)
Calvert Cliffs Nuclear Power Plant, LLC March 19,2014
&TC) r(f, PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 1
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CCl CCll1 NI POWER RNG SPi 109 LOG POWER NI WIDE RANGE LOG REACTOR PWR A
% POWER N/A 1 E-7 200 N/A N/A P
4 AVG OF THE TWO CLOSEST CHANNEL VALUES N/A N/A N/A N/A N/A N
N/A WIDE RANGE NUCLEAR INSTRUMENTATION PROVIDES A LOGARITHMIC INDICATION OF REACTOR POWER AS A PERCENT OF REACTOR POWER.
START UP RATE REACTOR TRIP IS GIVEN FROM WIDE RANGE NUCLEAR INSTRUMENTS BETWEEN THE RANGE OF 1E-4% TO 15% POWER. THESE DETECTORS ARE FISSION CHAMBERS WHICH DO NOT GET DEENERGIZED DURING NORMAL POWER OPERATIONS.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 2
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
3/10/2006 CC11 CCll REC VES LEV SP2112 REACTOR VESSEL LEVEL REACTOR VESSEL WATER LEVEL A
INCHES N/A N/A N/A FAP N/A P
32 RE:USD (REFERENCE UNIQ SYS DESC) 160,151,112,71,50,29,19, & 10" ABOVE FAP VOID DETECTED N/A N/A N/A N
N/A 8 HEATED JUNCTION THERMOCOUPLES (HJTC) ARE SPACED STRATEGICALLY NEAR THE VICINITY OF ONE HOT LEG OUTLET NOZZLE.
AS HJTC IS UNCOVERED THE LVL THAT THE REACTOR HEAD IS UNCOVERED IS INDICATED IN INCREMENTAL STEPS. THE 1ST HJTC IS 160" FROM TOP OF FUEL ALIGNMENT PLATE (FAP); 8TH HJTC IS 10" FROM FAP; 5TH HJTC IS 50" FROM FAP WHICH IS THE CENTER LINE OF THE HOT LEGS. HOW PROCESSED: WHEN LVL DECREASES A VOID IN THE HJTC WILL PROVIDE AN OUTPUT SIGNAL FOR THAT SPECIFIC HJTC POSITION.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 3
Date:
Reactor Unit:
Data Feeder:
NRC EROS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
6/26/2002 CC1 CCll TEMP CORE EX SP2113 CORE EXIT TEMP HIGHEST TEMP AT THE CORE EXIT A
DEGF N/A 40 2300 N/A N/A P
35 AVG EACH QUADRANT'S PTS.:4 QUADS-4 AVGS N/A X >= 650 N/A N/A N/A N
N/A CORE EXIT THERMOCOUPLES ARE LOCATED AT THE TOP OF THE INCORE INSTRUMENT DETECTOR ASSEMBLIES. THERE ARE 35 FIXED INCORE DETECTORS LOCATED IN THE CORE WITHIN SELECTED FUEL ASSEMBLIES. THIS POINT IS THE HIGHEST AVG CET READING IN THE QUADRANT.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 4
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
4/15/2004 CC1 CCll SUB MARGIN SP3123 CORE SUBCOOLED MARGIN SATURATION TEMPERATURE-HIGH CET A
DEGF N/A 40 2300 N/A N/A P
35 RE:USD (REFERENCE UNIQ SYS DESC)
N/A N/A N/A N/A N/A N
N/A CORE SUBCOOLED MARGIN IS CALCULATED BY THE SATURATION TEMPERATURE AS DETERMINED FROM PRESSURIZER PRESSURE MINUS THE CORE EXIT TEMP (SP2113).
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 5
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
10/22/2002 CC1 CCll CORE FLOW F131A RCS TOTAL FLOW CH A TOTAL REACTOR COOLANT FLOW A
% FLOW 100% RX COOLANT FLOW= 370,000 GPM
-53.57 151.48 N/A N/A S
1 N/A N/A N/A N/A N/A N/A N
N/A REACTOR COOLANT FLOW IS DETERMINED BY THE DIP ACROSS THE STEAM GENERATORS. WHERE TOTAL FLOW IS THE SUM OF BOTH LOOP FLOWS.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 6
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
4/18/2006 CC1 CClI SG LEVEL I/A SP3117A SG LEVEL LOOP 11 STEAM GENERATOR 11 WATER LEVEL A
INCHES N/A
-401.0 63.5 N/A 0" = 40" ABOVE THE FEED RING P
2 AVG OF TWO CHANNELS N/A X>=50 X<=-170 N/A N/A N/A N
WET A LOW LEVEL REACTOR TRIP OCCURS AT -50" AS READ ON THE NARROW RANGE LEVEL DETECTOR. AFAS WILL ACTUATE AT -170" AS READ ON THE WIDE RANGE S/G LVL DETECTOR. POINT ID SP3117A IS A WIDE RANGE LVL INDICATOR.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 7
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
4/18/2006 CC1 CCll SG LEVEL 2/B SP3117B SG LEVEL LOOP 12 STEAM GENERATOR 12 WATER LEVEL A
INCHES N/A
-401.0 63.5 N/A 0" = 40" ABOVE THE FEED RING P
2 AVG OF TWO CHANNELS N/A X>=50 X<=-170 N/A N/A N/A N
WET A LOW LEVEL REACTOR TRIP OCCURS AT -50" AS READ ON THE NARROW RANGE LEVEL DETECTOR. AFAS WILL ACTUATE AT -170" AS READ ON THE WIDE RANGE S/G LVL DETECTOR. POINT ID SP3117B IS A WIDE RANGE LVL INDICATOR.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 8
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCll SG PRESS I/A SP3116A SG PRESSURE LOOP 11 STEAM GENERATOR 11 PRESSURE A
PSIA N/A 0
1200 N/A N/A P
2 AVG OF TWO CHANNELS N/A X>=985 X<=703 N/A N/A N/A N
N/A REACTOR TRIP OCCURS AT 703# TO PREVENT EXCESSIVE HEAT EXTRACTIONS FROM HIGH STEAM FLOW DUE TO STM LINE RUPTURE OR COMP FAILURE.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 9
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCll SG PRESS 2/B SP3116B SG PRESSURE LOOP 12 STEAM GENERATOR 12 PRESSURE A
PSIA N/A 0
1200 N/A N/A P
2 AVG OF TWO CHANNELS N/A X>=985 X<=703 N/A N/A N/A N
N/A REACTOR TRIP OCCURS AT 703# TO PREVENT EXCESSIVE HEAT EXTRACTIONS FROM HIGH STEAM FLOW DUE TO STM LINE RUPTURE OF COMP FAILURE.
PWR Data Point Library Reference File Report Date:
10-22-2013 Page:
10 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CCl CCll MN FD FL 1/A F1111%
FW FLOW TO STEAM GEN. 11 STM GEN 11 MAIN FEEDWATER FLOW A
KLB/HR N/A 0
6000 N/A N/A P
6 COMPLEX N/A N/A N/A N/A N/A Y
N/A THIS IS A TEMPERATURE COMPENSATED FEED. 2 STEAM DRIVEN MAIN FEED PUMPS EACH CAPABLE OF SUPPLYING FEED WATER EXCEEDING 50% FEED FLOW DEMAND. UPON A MAIN TURBINE TRIP FEED REG VALVES CLOSE AND FEED REG BYPASS VALVES ARE POSITIONED TO MAINTAIN 5% OF MAIN FEED WATER FLOW WHEN FEED PUMPS ARE RUNNING.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 11 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCll MN FD FL 2/B F1121%
FW FLOW TO STEAM GEN. 12 STM GEN 12 MAIN FEEDWATER FLOW A
KLB/HR N/A 0
6000 N/A N/A P
6 COMPLEX N/A N/A N/A N/A N/A Y
N/A THIS IS A TEMPERATURE COMPENSATED FEED. 2 STEAM DRIVEN MAIN FEED PUMPS EACH CAPABLE OF SUPPLYING FEED WATER EXCEEDING 50% FEED FLOW DEMAND. UPON A MAIN TURBINE TRIP FEED REG VALVES CLOSE AND FEED REG BYPASS VALVES ARE POSITIONED TO MAINTAIN 5% OF MAIN FEED WATER FLOW WHEN FEED PUMPS ARE RUNNING.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 12 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCl 1 AX FD FL 1/A SP3118A AUX FEED FLOW LOOP 11 STM GEN 11 AUXILIARY FW FLOW A
GPM N/A 0
1500 N/A N/A P
2 SUM:MTR DRIVEN & TURB DRIVEN PMPS DISCH N/A N/A N/A N/A N/A N
N/A THERE ARE 2 STEAM TURBINE DRIVEN PUMPS AND ONE ELECTRIC DRIVEN PUMP. THE TURBINE DRIVEN PUMPS DISCHARGE TO A COMMON HEADER FOR BOTH #11 & #12 STM GENS. THE MOTOR DRIVEN PUMP DISCHARGES TO A SEPARATE HEADER FOR BOTH #11 & #12 STM GENS.
BOTH FLOW HEADERS COMBINE TO SUPPLY THE AUX FEED NOZZLE FOR EACH STM GEN. THE NORMAL SUPPLY TO AFW PUMP SUCTION IS FROM
- 12 CONDENSATE STORAGE TANK. ONLY 1 STEAM DRIVEN PUMP IS NORMALLY ALIGNED TO START.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 13 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CCl CC1 1 AX FD FL 2/B SP3118B AUX FEED FLOW LOOP 12 STM GEN 12 AUXILIARY FW FLOW A
GPM N/A 0
1500 N/A N/A P
2 SUM:MTR DRIVEN & TURB DRIVEN PMPS DISCH N/A N/A N/A N/A N/A N
N/A THERE ARE 2 STEAM TURBINE DRIVEN PUMPS AND ONE ELECTRIC DRIVEN PUMP. THE TURBINE DRIVEN PUMPS DISCHARGE TO A COMMON HEADER FOR BOTH #11 & #12 STM GENS. THE MOTOR DRIVEN PUMP DISCHARGES TO A SEPARATE HEADER FOR BOTH #11 & #12 STM GEN.
BOTH FLOW HEADERS COMBINE TO SUPPLY THE AUX FEED NOZZLE FOR EACH STM GEN. THE NORMAL SUPPLY TO AFW PUMP SUCTION IS FROM
- 12 CONDENSATE STORAGE TANK. ONLY 1 STEAM DRIVEN PUMP IS NORMALLY ALIGNED TO START.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 14 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
4/15/2004 CC1 CCll HL TEMP 1/A SPOI06A THOT LOOP 11 STM GEN 11 INLET TEMPERATURE A
DEGF N/A 50 700 N/A N/A P
2 AVG N/A N/A OF TWO CHANNELS N/A N/A N/A N
N/A THOT IS THE COOLANT TEMPERATURE MEASURED AT THE INLET TO THE STEAM GEN. THOT PROVIDES INPUT TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP) CIRCUIT FOR A TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 15 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
4/15/2004 CCl CC11 HL TEMP 2/B SPOI06B THOT LOOP 12 STM GEN 12 INLET TEMPERATURE A
DEGF N/A 50 700 N/A N/A P
2 AVG OF TWO CHANNELS N/A N/A N/A N/A N/A N
N/A THOT IS THE COOLANT TEMPERATURE MEASURED AT THE INLET TO THE STEAM GEN. THOT PROVIDES INPUT TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP) CIRCUIT FOR A TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 16 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
4/15/2004 CC1 CCll CL TEMP I/A SP3113A TCOLD LOOP 11 STM GEN 11 OUTLET TEMPERATURE A
DEGF N/A 50 700 N/A N/A P
3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)
N/A X>=560 X<=504 N/A N/A N/A N
N/A THE ALARM/TRIP SET POINTS SUPPLIED ABOVE ARE SPDS ALARM SET POINTS. TCOLD PROVIDES CONTROL ROOM AND AUX SHUTDOWN PANEL INDICATION. TCOLD ALSO SUPPLIES SIGNALS TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP)
CIRCUIT FOR TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM. AS A DNB PARAMETER TCOLD IS REQUIRED TO BE LESS THAN 548 DEG WITH 4 REACTOR COOLANT PUMPS RUNNING.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 17 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
4/15/2004 Cc1 CCll CL TEMP 2/B SP3113B TCOLD LOOP 12 STM GEN 12 OUTLET TEMPERATURE A
DEGF N/A 50 700 N/A N/A P
3 AVG OF TWO CHNLS (AUCTION EERED:WR OR NR)
N/A X>=560 X<=504 N/A N/A N/A N
N/A THE ALARM/TRIP SET POINTS SUPPLIED ABOVE ARE SPDS ALARM SET POINTS. TCOLD PROVIDES CONTROL ROOM AND AUX SHUTDOWN PANEL INDICATION. TCOLD ALSO SUPPLIES SIGNALS TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP)
CIRCUIT FOR TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM. AS A DNB PARAMETER TCOLD IS REQUIRED TO BE LESS THAN 548 DEG WITH 4 REACTOR COOLANT PUMPS RUNNING.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 18 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/411992 CC1 CCll RCS PRESSURE SP3120 PRESSURIZER PRESSURE REACTOR COOLANT SYSTEM PRESSURE A
PSIA N/A 0
4000 N/A N/A P
2 AVG OF TWO CHANNELS N/A X >= 2400 X <= 1740 N/A N/A N/A N
N/A REACTOR COOLANT PRESSURE IS THE AVERAGE OF 2 WIDE RANGE PRESSURIZER PRESSURE DETECTORS. THE SAFETY VALVES ARE SET TO OPEN AT 2500#. HIGH PRESSURE REACTOR TRIP OCCURS AT 2400#.
PORVS OPEN AT 2400 PSIA ON A REACTOR TRIP FROM HIGH PRESSURE.
SPRAY VALVE SETPOINT IS DEPENDENT ON CONTROLLER SETPOINT.
BOTH SPRAY VALVES CLOSE AT 2300 PSIA. ESFAS ACTUATION IS INITIATED AT 1740#.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 19 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CCl CCll PRZR LEVEL SP2109 PRESSURIZER LEVEL PRIMARY SYSTEM PRESSURIZER LEVEL A
INCHES N/A 0
360 RE:USD N/A P
2 AVG OF TWO CHANNELS N/A X>=300 X <=50 N/A N/A N/A N
WET PRESSURIZER LEVEL IS NORMALLY CONTROLLED IN A BAND BETWEEN 160" TO 216" DURING NORMAL POWER OPERATIONS. PRESSURIZER HEATERS CUTOUT AT A LEVEL OF 101" IN THE PRESSURIZER.
PRESSURIZER HEATERS WILL START TO BE UNCOVERED AT APPROX 84" OF INDICATED LEVEL. ZERO POINT
REFERENCE:
BOTTOM OF PRESSURIZER
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 20 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCll RCS CHG/MU SP1114 CHG PUMP FLOW PRIMARY SYSTEM CHARGING/MAKEUP F A
GPM N/A 0
150 N/A N/A P
4 RE:USD (REFERENCE UNIQ SYS DESC)
N/A N/A N/A N/A N/A N
N/A THERE ARE 3 CHARGING PUMPS THAT ARE RATED TO SUPPLY 44 GPM EACH TO THE RCS (REACTOR COOLANT SYSTEM). THE CHARGING FLOW IS DETERMINED FROM AN "A" CONTACT OF EACH CHARGING PUMP CIRCUIT BREAKER. SPDS DETERMINES THE FLOW BY SUMMING THE RATED FLOW OF EACH CHARGING PUMP THAT HAS ITS CIRCUIT BREAKER CLOSED. CHARGING PUMP #13 CAN BE POWERED FROM ONE OF TWO BUSSES #11 OR #14. WHICH MUST BE MANUALLY SELECTED BY A "KIRK" KEY INTERLOCK SCHEME.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 21 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
6/30/1993 CC1 CCll HP SI FLOW SP2115 HPSI FLOW HIGH PRESSURE SAFETY INJECTION F A
GPM N/A 0
1600 N/A N/A P
4 SUM OF FLOW LOOPS 11A, 11B, 12A, 12B N/A N/A N/A N/A N/A N
N/A 3 HIGH PRESSURE SAFETY INJECTION PUMPS DELIVER EMERGENCY COOLANT TO ALL FOUR COLD LEGS. SHUTOFF HEAD PRESSURE IS 1275 PSIA. ONLY 2 PUMPS WILL START. 12 HPSI IS MAINTAINED IN PULL TO LOCK. 2 INDEPENDENT SUCTION HEADERS SUPPLY WATER FROM THE REFUELING WATER TANK UNTIL THE TANK IS DOWN TO 10% FULL. AFTER THE RWT IS DOWN TO 10% FULL THE HPSI LINE IS CHANGED TO PROVIDE SUCTION FROM THE CONTAINMENT SUMP.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 22 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CClI LP SI FLOW SP2116 LPSI FLOW LOW PRESSURE SAFETY INJECTION FL A
GPM N/A 0
8000 N/A N/A P
1 INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A 2 LOW PRESSURE SAFETY INJECTION PUMPS SUPPLY LOW HEAD/HIGH VOLUME COOLANT TO THE COLD LEGS. EACH LPSI PUMP TAKES A SUCTION OFF A SEPARATE HEADER FROM THE RWT. DURING RECIRCULATION MODE (APPROX 36 MIN AFTER A D.B.A.) THE LPSI PUMPS ARE SHUT DOWN AND THE HPSI PUMPS TAKE SUCTION FROM THE CONTAIMENT SUMP TO RECIRCULATE WATER THROUGH THE SYSTEM.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 23 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCll CTMNT SMP WR SP4112 CNTMT LEVEL CONTAINMENT SUMP WIDE RNG LEVEL A
INCHES N/A 0
120 N/A N/A P
2 AVG OF TWO CHANNELS N/A N/A N/A N/A N/A N
N/A THE CONTAINMENT EMERGENCY SUMP PROVIDES ADEQUATE NPSH TO BOTH HPSI AND CONTAINMENT SPRAY PUMPS WHEN IN THE RECIRCULATION MODE. TWO 24" DIAMETER RECIRC LINES SUPPLY WATER TO THE CONTAINMENT SPRAY AND SAFETY INJECTION SYSTEM.
THE SUMP IS COVERED WITH A METAL GRATING TO PREVENT DEBRIS FROM ENTERING THE SUMP.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 24 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
N! Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCll EFF GAS RAD R5415!
WR EFF MONITOR RADIOACTIVITY OF RELEASED GASSES A
UCI/SEC N/A 1E1 1E13 N/A N/A P
1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A THE EFFLUENT GAS RADIATION MONITOR MEASURES MAIN VENT STACK EFFLUENT GROSS ACTIVITY. 3 CHANNELS: LOW, MEDIUM, & HIGH ARE USED TO PROVIDE AN OUTPUT TO A FOURTH PSEUDO CHANNEL. THE RANGE OF ACTIVITY DETECTED DETERMINES WHICH CHANNEL (L,M,H) IS SELECTED. THE OUTPUT OF THE FOURTH CHANNEL COMBINES GASIOUS FLOW WITH THE MEASURED ACTIVITY TO PROVIDE THE EFFECTIVE EFFLUENT GROSS ACTIVITY.
PWR Data Point Library Report Date:
Page:
Reference File 10-22-2013 25 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
4/18/2006 CC1 CCll EFF LIQ RAD SP6120 LIQUID WASTE RAD RADIOACTIVITY OF RELEASED LIQUID A
CPM N/A 1E1 1E6 N/A N/A P
3 INSTRUMENT VALUE N/A X >= 4E5 N/A N/A N/A N
N/A LIQUID WASTE PROCESSING MONITORS THE COMMON DISCHARGE HEADER FROM REACTOR COOLANT WASTE PROCESSING AND MISC WASTE PROCESS. 50000 CPM WILL AUTOMATICALLY CLOSE 2 DISCHARGE VALVES 0-CV-2201 & 0-CV-2202 TO ISOLATE FLOW TO THE CIRCULATION WATER DISCHARGE CONDUITS. ALARM LIMIT GIVEN IN ALARM/TRIP SET POINT IS THE SPDS ALARM LIMIT.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 26 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
10/8/2002 CCl Ccli COND NE RAD SP6117 OFF GAS RAD CONDENSER AIR EJECTOR RADIOACTIV A
GPD N/A 0
250 N/A N/A P
4 INSTRUMENT VALUE N/A X >= 5 N/A N/A N/A N
N/A THE CONDENSER AIR EJECTOR DISCHARGE MONITOR INCLUDES FOUR RADIATION SENSORS. ONE SENSOR IS INSTALLED IN THE SUCTION SIDE OF EACH OF THE FOUR CONDENSER AIR REMOVAL PUMPS. OUTPUT SIGNALS ARE DISPLAYED IN THE CONTROL ROOM. THE AUCTIONEERED HIGH SIGNAL IS CONVERTED FROM CPM TO GALLONS PER DAY (GPD)
AND IS USED AS AN EARLY INDICATION OF A PRIMARY TO SECONDARY LEAK THROUGH THE S/G TUBES.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 27 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CC11I CNTMNT RAD SP6121 CNTMT RAD RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 1
1E8 N/A N/A P
2 AVG OF TWO CHANNELS N/A X >= 3 N/A N/A N/A N
N/A THESE CONTAINMENT RADIATION MONITORS MEASURE GAMMA RADIATION LEVELS IN CONTAINMENT UNDER ACCIDENT CONDITIONS.
THE DETECTORS ARE LOCATED AT THE 73-FOOT LEVEL AND ARE PLACED NEAR THE PRESSURIZER AND #11 STEAM GEN.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 28 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CCl CCl1 RCS LTDN RAD R5202!
PROCESS RAD MONITOR RAD LEVEL OF RCS LETDOWN LINE A
CPM N/A 1E1 1E6 N/A N/A P
1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A THE CVCS LTDN RAD MONITOR IS INSTALLED IN THE LET DOWN LINE TO MONITOR GROSS REACTOR COOLANT ACTIVITY INDICATING A POTENTIAL FUEL ELEMENT FAILURE.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 29 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
5/29/1997 CC11 MAIN SL 1/A R5421!
MAIN STM RAD LP 11 STM GEN 11 STEAM LINE RAD LEVEL A
R/HR N/A 1 E-4 1 E4 N/A N/A P
1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A THE MAIN STEAM EFFLUENT RADIATION DETECTORS MONITOR FOR NOBLE GASSES WITHIN THE MAIN STEAM LINE. THE MONITORS ARE LOCATED ON THE 27-FOOT LEVEL OF THE AUX BUILDING IN THE MSIV ROOM.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 30 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
5/29/1997 CC1 CClI MAIN SL 2/B R5422!
MAIN STM RAD LP 12 STM GEN 12 STEAM LINE RAD LEVEL A
R/HR N/A 1 E-4 1 E4 N/A N/A P
1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A THE MAIN STEAM EFFLUENT RADIATION DETECTORS MONITOR FOR NOBLE GASSES WITHIN THE MAIN STEAM LINE. THE MONITORS ARE LOCATED ON THE 27-FOOT LEVEL OF THE AUX BUILDING IN THE MSIV ROOM.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 31 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCll SG BD RAD 1A R4014!
STEAM GEN BLOWDOWN ACTIVITY STM GEN 11 BLOWDOWN RAD LEVEL A
CPM N/A 1E1 1 E6 N/A N/A P
1 INVERSE LOG OF INSTRUMENT VALUE N/A 1000 CPM N/A N/A N/A N
N/A THIS DETECTOR MONITORS A SMALL PORTION OF THE STM GEN BLOWDOWN TO PROVIDE OPERATORS WITH AN EARLY INDICATION OF STM GEN U-TUBE LEAKAGE. ACTUATION OF THE HIGH ALARM AUTOMATICALLY SHUT THE SURFACE BLOWDOWN AND THE BOTTOM BLOWDOWN ISOLATION VALVES. OF BOTH #11 & #12 STEAM GENERATOR THIS MONITOR IS IN THE LINE OF THE BLOWDOWN TANK AND IS COMMON TO BOTH STM GEN.
PWR Data Point Library Reference File Report Date:
10-22-2013 Page:
32 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCl1 CTMNT PRESS SP4110 CNTMT PRESSURE CONTAINMENT PRESSURE A
PSIG N/A
-5 150 N/A N/A P
3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)
N/A X >= 2.8 N/A N/A N/A N
N/A THERE ARE A TOTAL OF 3 CONTAINMENT PRESSURE INDICATORS. TWO PROVIDE WIDE RANGE PRESSURE INDICATION 0-150 PSIG FOR POST ACCIDENT MONITORING. THE THIRD INDICATOR IS A NARROW RANGE INDICATION -5 TO +5 PSIG WHICH PROVIDES CONTAINMENT DIFFERENTIAL PRESSURE. ACTUATIONS OCCUR: CIS @ 2.8 PSIG; CSAS @
4.25 PSIG; SIAS @ 2.8 PSIG; RPS @ 2.4 PSIG.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 33 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/4/1992 CC1 CCll CTMNT TEMP SP4111 CNTMT TEMPERATURE CONTAINMENT TEMPERATURE A
DEGF N/A 50 300 N/A N/A P
2 AVG OF TWO CHANNELS N/A X >= 160 N/A N/A N/A N
N/A THERE ARE 2 CONTAINMENT TEMP DETECTORS. ONE MEASURES DOME TEMP, ANOTHER MEASURES THE REACTOR CAVITY TEMP. BOTH OF THESE PROVIDE INDICATION TO THE CONTROL ROOM OPERATORS.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 34 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
10/20/2000 CC1 CCll BWST LEVEL SP2RWLVL REFUELING WATER TANK LEVEL BORATED WATER STORAGE TANK LEVEL A
FEET N/A 0
40 RE:USD RE:USD (REFERENCE UNIQ SYS DESC)
P 2
N/A N/A N/A N/A N/A N/A N
WET THE REFUELING WATER TANK SUPPLIES 2300-2700 PPM BORATED WATER TO THE SAFETY INJECTION SYSTEM AND ALSO SUPPLIES WATER FOR USE DURING REFUELING. TANK CAPACITY IS 420,000 GALS. AT 2.5 FEET THE SAFETY INJECTION LINE-UP IS SWITCHED TO THE RECIRCULATION MODE. THIS LEVEL IS EQUAL TO APPROX 10% OF TANK VOLUME.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 35 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
12/6/2006 CCl CC21 WIND SPEED X2433 WIND SPEED WIND SPEED AT REACTOR SITE A
M/S N/A 0
50 N/A N/A S
1 N/A N/A N/A N/A N/A LOW N
N/A WIND SPEED INDICATION IN METERS PER SECOND TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER LOCATED ON SITE. 60 METER ELEVATION
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 36 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
12/6/2006 CC1 CC21 WIND DIR X2367 WIND DIRECTION WIND DIRECTION AT REACTOR SITE A
DEG N/A 0
540 N/A N/A S
1 N/A N/A N/A N/A N/A 0 DEGREES (NORTH)
N N/A WIND DIRECTION TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER ON SITE. 60 METER ELEVATION
PWR Data Point Library Reference File A -f kcf Report Date:
Page :
10-22-2013 1
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll NI POWER RNG 1SP1109 LOG POWER NI WIDE RANGE LOG REACTOR PWR A
% POWER N/A 1 E-7 200 N/A N/A P
4 AVG OF THE TWO CLOSEST CHANNEL VALUES N/A N/A N/A N/A N/A N
N/A WIDE RANGE NUCLEAR INSTRUMENTATION PROVIDES A LOGARITHMIC INDICATION OF REACTOR POWER AS A PERCENT OF REACTOR POWER.
START UP RATE REACTOR TRIP IS GIVEN FROM WIDE RANGE NUCLEAR INSTRUMENTS BETWEEN THE RANGE OF 1E-4% TO 15% POWER. THESE DETECTORS ARE FISSION CHAMBERS WHICH DO NOT GET DEENERGIZED DURING NORMAL POWER OPERATIONS.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 2
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll REC VES LEV 1SP2112 REACTOR VESSEL LEVEL REACTOR VESSEL WATER LEVEL A
INCHES N/A N/A N/A FAP N/A P
32 RE:USD (REFERENCE UNIQUE SYS DESC) 160,151,112,71,50,29,19, & 10" ABOVE FAP VOID DETECTED N/A N/A N/A N
N/A 8 HEATED JUNCTION THERMOCOUPLES (HJTC) ARE SPACED STRATEGICALLY NEAR THE VICINITY OF ONE HOT LEG OUTLET NOZZLE.
AS HJTC IS UNCOVERED THE LVL THAT THE REACTOR HEAD IS UNCOVERED IS INDICATED IN INCREMENTAL STEPS. THE 1ST HJTC IS 160" FROM TOP OF FUEL ALIGNMENT PLATE(FAP); 8TH HJTC IS 10" FROM FAP; 5TH HJTC IS 50" FROM FAP WHICH IS THE CENTER LINE OF THE HOT LEGS. HOW PROCESSED: WHEN LVL DECREASES A VOID IN THE HJTC WILL PROVIDE AN OUTPUT SIGNAL FOR THAT SPECIFIC HJTC POSITION.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 3
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sersor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CcO CCll TEMP CORE EX 1SP2113 CORE EXIT TEMP HIGHEST TEMP AT THE CORE EXIT A
DEGF N/A 40 2300 N/A N/A P
35 AVG EACH QUADRANT'S PTS.:4 QUADS-4 AVGS N/A X >= 650 N/A N/A N/A N
N/A CORE EXIT THERMOCOUPLES ARE LOCATED AT THE TOP OF THE INCORE INSTRUMENT DETECTOR ASSEMBLIES. THERE ARE 35 FIXED INCORE DETECTORS LOCATED IN THE CORE WITHIN SELECTED FUEL ASSEMBLIES. THIS POINT IS THE HIGHEST AVG CET READING IN THE QUADRANT.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 4
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CClI SUB MARGIN 1 SP3123 CORE SUBCOOLED MARGIN SATURATION TEMPERATURE-HIGH CET A
DEGF N/A 40 2300 N/A N/A P
35 RE:USD (REFERENCE UNIQUE SYS DESC)
N/A N/A N/A N/A N/A N
N/A CORE SUBCOOLED MARGIN IS CALCULATED BY THE SATURATION TEMPERATURE AS DETERMINED FROM PRESSURIZER PRESSURE MINUS THE CORE EXIT TEMP (SP2113).
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 5
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CC11 CORE FLOW 1F131A RCS TOTAL FLOW CH A TOTAL REACTOR COOLANT FLOW A
% FLOW 100% RX COOLANT FLOW= 370,000 GPM
-53.57 151.48 N/A N/A S
1 N/A N/A N/A N/A N/A N/A N
N/A REACTOR COOLANT FLOW IS DETERMINED BY THE D/P ACROSS THE STEAM GENERATORS. WHERE TOTAL FLOW IS THE SUM OF BOTH LOOP FLOWS.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 6
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll SG LEVEL 1/A 1SP3117A SG LEVEL LOOP 11 STEAM GENERATOR 11 WATER LEVEL A
INCHES N/A
-401.0 63.5 N/A 0" = 40" ABOVE THE FEED RING P
2 AVG OF TWO CHANNELS N/A X>=50 X<=-170 N/A N/A N/A N
WET A LOW LEVEL REACTOR TRIP OCCURS AT -50" AS READ ON THE NARROW RANGE LEVEL DETECTOR. AFAS WILL ACTUATE AT -170" AS READ ON THE WIDE RANGE S/G LVL DETECTOR. POINT ID SP3117A IS A WIDE RANGE LVL INDICATOR.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 7
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 Cc1 Ccll SG LEVEL 2/B 1SP3117B SG LEVEL LOOP 12 STEAM GENERATOR 12 WATER LEVEL A
INCHES N/A
-401.0 63.5 N/A 0" = 40" ABOVE THE FEED RING P
2 AVG OF TWO CHANNELS N/A X>50 X<=-170 N/A N/A N/A N
WET A LOW LEVEL REACTOR TRIP OCCURS AT -50" AS READ ON THE NARROW RANGE LEVEL DETECTOR. AFAS WILL ACTUATE AT -170" AS READ ON THE WIDE RANGE S/G LVL DETECTOR. POINT ID SP3117B IS A WIDE RANGE LVL INDICATOR.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 8
Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll SG PRESS 1/A 1SP3116A SG PRESSURE LOOP 11 STEAM GENERATOR 11 PRESSURE A
PSIA N/A 0
1200 N/A N/A P
2 AVG OF TWO CHANNELS N/A X>=950 X<=703 N/A N/A N/A N
N/A REACTOR TRIP OCCURS AT 703# TO PREVENT EXCESSIVE HEAT EXTRACTIONS FROM HIGH STEAM FLOW DUE TO STM LINE RUPTURE OR COMP FAILURE.
PWR Data Point Library Reference File Report Date:
10-22-2013 Page:
9 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll SG PRESS 2/B 1SP3116B SG PRESSURE LOOP 12 STEAM GENERATOR 12 PRESSURE A
PSIA N/A 0
1200 N/A N/A P
2 AVG OF TWO CHANNELS N/A X>=950 X<= 703 N/A N/A N/A N
N/A REACTOR TRIP OCCURS AT 703# TO PREVENT EXCESSIVE HEAT EXTRACTIONS FROM HIGH STEAM FLOW DUE TO STM LINE RUPTURE OF COMP FAILURE.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 10 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CC11 MN FD FL 1/A 1F1111%
FW FLOW TO STEAM GEN. 11 STM GEN 11 MAIN FEEDWATER FLOW A
KLB/HR N/A 0
6000 N/A N/A P
6 COMPLEX N/A N/A N/A N/A N/A Y
N/A THIS IS A TEMPERATURE COMPENSATED FEED. 2 STEAM DRIVEN MAIN FEED PUMPS EACH CAPABLE OF SUPPLYING FEED WATER EXCEEDING 50% FEED FLOW DEMAND. UPON A MAIN TURBINE TRIP FEED REG VALVES CLOSE AND FEED REG BYPASS VALVES ARE POSITIONED TO MAINTAIN 5% OF MAIN FEED WATER FLOW WHEN FEED PUMPS ARE RUNNING.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 11 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll MN FD FL 2/B 1F1121%
FW FLOW TO STEAM GEN. 12 STM GEN 12 MAIN FEEDWATER FLOW A
KLB/HR N/A 0
6000 N/A N/A P
6 COMPLEX N/A N/A N/A N/A N/A Y
N/A THIS IS A TEMPERATURE COMPENSATED FEED FLOW. 2 STEAM DRIVEN MAIN FEED PUMPS EACH CAPABLE OF SUPPLYING FEED WATER EXCEEDING 50% FEED FLOW DEMAND. UPON A MAIN TURBINE TRIP FEED REG VALVES CLOSE AND FEED REG BYPASS VALVES ARE POSITIONED TO MAINTAIN 5% OF MAIN FEED WATER FLOW WHEN FEED PUMPS ARE RUNNING.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 12 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll AX FD FL 1/A 1SP3118A AUX FEED FLOW LOOP 11 STM GEN 11 AUXILIARY FW FLOW A
GPM N/A 0
1500 N/A N/A P
2 SUM:MTR DRIVEN & TURB DRIVEN PMPS DISCH N/A N/A N/A N/A N/A N
N/A THERE ARE 2 STEAM TURBINE DRIVEN PUMPS AND ONE ELECTRIC DRIVEN PUMP. THE TURBINE DRIVEN PUMPS DISCHARGE TO A COMMON HEADER FOR BOTH #11 & #12 STM GENS. THE MOTOR DRIVEN PUMP DISCHARGES TO A SEPARATE HEADER FOR BOTH #11 & #12 STM GENS.
BOTH FLOW HEADERS COMBINE TO SUPPLY THE AUX FEED NOZZLE FOR EACH STM GEN. THE NORMAL SUPPLY TO AFW PUMP SUCTION IS FROM
- 12 CONDENSATE STORAGE TANK. ONLY 1 STEAM DRIVEN PUMP IS NORMALLY ALIGNED TO START.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 13 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll1 AX FD FL 2/B 1SP3118B AUX FEED FLOW LOOP 12 STM GEN 12 AUXILIARY FW FLOW A
GPM N/A 0
1500 N/A N/A P
2 SUM:MTR DRIVEN & TURB DRIVEN PMPS DISCH N/A N/A N/A N/A N/A N
N/A THERE ARE 2 STEAM TURBINE DRIVEN PUMPS AND ONE ELECTRIC DRIVEN PUMP. THE TURBINE DRIVEN PUMPS DISCHARGE TO A COMMON HEADER FOR BOTH #11 & #12 STM GENS. THE MOTOR DRIVEN PUMP DISCHARGES TO A SEPARATE HEADER FOR BOTH #11 & #12 STM GENS.
BOTH FLOW HEADERS COMBINE TO SUPPLY THE AUX FEED NOZZLE FOR EACH STM GEN. THE NORMAL SUPPLY TO AFW PUMP SUCTION IS FROM
- 12 CONDENSATE STORAGE TANK. ONLY 1 STEAM DRIVEN PUMP IS NORMALLY ALIGNED TO START.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 14 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll HL TEMP 1/A 1 SPOI06A THOT LOOP 11 STM GEN 11 INLET TEMPERATURE A
DEGF N/A 50 700 N/A N/A P
2 AVG OF TWO CHANNELS N/A N/A N/A N/A N/A N
N/A THOT IS THE COOLANT TEMPERATURE MEASURED AT THE INLET TO THE STEAM GEN. THOT PROVIDES INPUT TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP) CIRCUIT FOR A TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 15 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll HL TEMP 2/B 1SPOI06B THOT LOOP 12 STM GEN 12 INLET TEMPERATURE A
DEGF N/A 50 700 N/A N/A P
2 AVG OF TWO CHANNELS N/A N/A N/A N/A N/A N
N/A THOT IS THE COOLANT TEMPERATURE MEASURED AT THE INLET TO THE STEAM GEN. THOT PROVIDES INPUT TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP) CIRCUIT FOR A TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 16 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll CL TEMP 1/A 1SP3113A TCOLD LOOP 11 STM GEN 11 OUTLET TEMPERATURE A
DEGF N/A 50 700 N/A N/A P
3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)
N/A X>=560 X<=525 N/A N/A N/A N
N/A THE ALARM/TRIP SET POINTS SUPPLIED ABOVE ARE SPDS ALARM SET POINTS. TCOLD PROVIDES CONTROL ROOM AND AUX SHUTDOWN PANEL INDICATION. TCOLD ALSO SUPPLIES SIGNALS TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP)
CIRCUIT FOR TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM. AS A DNB PARAMETER TCOLD IS REQUIRED TO BE LESS THAN 548 DEG WITH 4 REACTOR COOLANT PUMPS RUNNING.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 17
- Date, Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll CL TEMP 2/B 1SP3113B TCOLD LOOP 12 STM GEN 12 OUTLET TEMPERATURE A
DEGF N/A 50 700 N/A N/A P
3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)
N/A X>=560 X<=525 N/A N/A N/A N
N/A THE ALARM/TRIP SET POINTS SUPPLIED ABOVE ARE SPDS ALARM SET POINTS. TCOLD PROVIDES CONTROL ROOM AND AUX SHUTDOWN PANEL INDICATION. TCOLD ALSO SUPPLIES SIGNALS TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP)
CIRCUIT FOR TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM. AS A DNB PARAMETER TCOLD IS REQUIRED TO BE LESS THAN 548 DEG WITH 4 REACTOR COOLANT PUMPS RUNNING.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 18 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll RCS PRESSURE 1 SP3120 PRESSURIZER PRESSURE REACTOR COOLANT SYSTEM PRESSURE A
PSIA N/A 0
4000 N/A N/A P
2 AVG OF TWO CHANNELS N/A X >= 2400 X <= 1740 N/A N/A N/A N
N/A REACTOR COOLANT PRESSURE IS THE AVERAGE OF 2 WIDE RANGE PRESSURIZER PRESSURE DETECTORS. THE SAFETY VALVES ARE SET TO OPEN AT 2500#. HIGH PRESSURE REACTOR TRIP OCCURS AT 2400#.
PORVS OPEN AT 2400 PSIA ON A REACTOR TRIP FROM HIGH PRESSURE.
SPRAY VALVE SETPOINT IS DEPENDENT ON CONTROLLER SETPOINT.
BOTH SPRAY VALVES CLOSE AT 2300 PSIA. ESFAS ACTUATION IS INITIATED AT 1740#.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 19 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog i Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CC11 PRZR LEVEL 1SP2109 PRESSURIZER LEVEL PRIMARY SYSTEM PRESSURIZER LEVEL A
INCHES N/A 0
360 RE:USD N/A P
2 AVG OF TWO CHANNELS N/A X>=305 X<=50 N/A N/A N/A N
WET PRESSURIZER LEVEL IS NORMALLY CONTROLLED IN A BAND BETWEEN 160" TO 216" DURING NORMAL POWER OPERATIONS. PRESSURIZER HEATERS CUTOUT AT A LEVEL OF 101" IN THE PRESSURIZER.
PRESSURIZER HEATERS WILL START TO BE UNCOVERED AT APPROX 84" OF INDICATED LEVEL. ZERO POINT
REFERENCE:
BOTTOM OF PRESSURIZER.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 20 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll RCS CHG/MU 1SP1114 CHG PUMP FLOW PRIMARY SYSTEM CHARGING/MAKEUP F A
GPM N/A 0
150 N/A N/A P
4 RE:USD (REFERENCE UNIQ SYS DESC)
N/A N/A N/A N/A N/A N
N/A THERE ARE 3 CHARGING PUMPS THAT ARE RATED TO SUPPLY 44 GPM EACH TO THE RCS (REACTOR COOLANT SYSTEM). THE CHARGING FLOW IS DETERMINED FROM AN "A" CONTACT OF EACH CHARGING PUMP CIRCUIT BREAKER. SPDS DETERMINES THE FLOW BY SUMMING THE RATED FLOW OF EACH CHARGING PUMP THAT HAS ITS CIRCUIT BREAKER CLOSED. CHARGING PUMP #13 CAN BE POWERED FROM ONE OF TWO BUSSES #11 OR #14. WHICH MUST BE MANUALLY SELECTED BY A "KIRK" KEY INTERLOCK SCHEME.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 21 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CC11 HP SI FLOW 1SP2115 HPSI FLOW HIGH PRESSURE SAFETY INJECTION F A
GPM N/A 0
1600 N/A N/A P
4 SUM N/A N/A OF FLOW LOOPS I1A, 11B, 12A, 12B N/A N/A N/A N
N/A 3 HIGH PRESSURE SAFETY INJECTION PUMPS DELIVER EMERGENCY COOLANT TO ALL FOUR COLD LEGS. SHUTOFF HEAD PRESSURE IS 1275 PSIA. ONLY TWO PUMPS WILL START. 12 HPSI IS MAINTAINED IN PULL TO LOCK. 2 INDEPENDENT SUCTION HEADERS SUPPLY WATER FROM THE REFUELING WATER TANK UNTIL THE TANK IS DOWN TO 10% FULL. AFTER THE RWT IS DOWN TO 10% FULL THE HPSI LINE IS CHANGED TO PROVIDE SUCTION FROM THE CONTAINMENT SUMP.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 22 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CC11 LP SI FLOW 1SP2116 LPSI FLOW LOW PRESSURE SAFETY INJECTION FL A
GPM N/A 0
8000 N/A N/A P
1 INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A 2 LOW PRESSURE SAFETY INJECTION PUMPS SUPPLY LOW HEAD/HIGH VOLUME COOLANT TO THE COLD LEGS. EACH LPSI PUMP TAKES A SUCTION OFF A SEPARATE HEADER FROM THE RWT. DURING RECIRCULATION MODE (APPROX 36 MIN AFTER A D.B.A.) THE LPSI PUMPS ARE SHUT DOWN AND THE HPSI PUMPS TAKE SUCTION FROM THE CONTAIMENT SUMP TO RECIRCULATE WATER THROUGH THE SYSTEM.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 23 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CClI CTMNT SMP WR 1 SP4112 CNTMT LEVEL CONTAINMENT SUMP WIDE RNG LEVEL A
INCHES N/A 0
120 N/A N/A P
2 AVG N/A N/A OF TWO CHANNELS N/A N/A N/A N
N/A THE CONTAINMENT EMERGENCY SUMP PROVIDES ADEQUATE NPSH TO BOTH HPSI AND CONTAINMENT SPRAY PUMPS WHEN IN THE RECIRCULATION MODE. TWO 24" DIAMETER RECIRC LINES SUPPLY WATER TO THE CONTAINMENT SPRAY AND SAFETY INJECTION SYSTEM.
THE SUMP IS COVERED WITH A METAL GRATING TO PREVENT DEBRIS FROM ENTERING THE SUMP.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 24 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll EFF GAS RAD 1R5415!
WR EFF MONITOR RADIOACTIVITY OF RELEASED GASSES A
UCI/SEC N/A 1E1 1E13 N/A N/A P
1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A THE EFFLUENT GAS RADIATION MONITOR MEASURES MAIN VENT STACK EFFLUENT GROSS ACTIVITY. 3 CHANNELS: LOW, MEDIUM, & HIGH ARE USED TO PROVIDE AN OUTPUT TO A FOURTH PSEUDO CHANNEL. THE RANGE OF ACTIVITY DETECTED DETERMINES WHICH CHANNEL (L,M,H) IS SELECTED. THE OUTPUT OF THE FOURTH CHANNEL COMBINES GASIOUS FLOW WITH THE MEASURED ACTIVITY TO PROVIDE THE EFFECTIVE EFFLUENT GROSS ACTIVITY.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 25 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll EFF LIQ RAD 1 SP6120 LIQUID WASTE RAD RADIOACTIVITY OF RELEASED LIQUID A
CPM N/A 1E1 1E6 N/A N/A P
3 INSTRUMENT VALUE N/A X >= 4.21 E5 N/A N/A N/A N
N/A LIQUID WASTE PROCESSING MONITORS THE COMMON DISCHARGE HEADER FROM REACTOR COOLANT WASTE PROCESSING AND MISC WASTE PROCESS. 50000 CPM WILL AUTOMATICALLY CLOSE 2 DISCHARGE VALVES 0-CV-2201 & 0-CV-2202 TO ISOLATE FLOW TO THE CIRCULATION WATER DISCHARGE CONDUITS. ALARM LIMIT GIVEN IN ALARM/TRIP SET POINT IS THE SPDS ALARM LIMIT.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 26 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll COND A/E RAD 1SP6117 OFF GAS RAD CONDENSER AIR EJECTOR RADIOACTIV A
GPD N/A 0
250 N/A N/A P
4 INSTRUMENT VALUE N/A X >= 5 N/A N/A N/A N
N/A THE CONDENSER AIR EJECTOR DISCHARGE MONITOR INCLUDES FOUR RADIATION SENSORS. ONE SENSOR IS INSTALLED IN THE SUCTION SIDE OF EACH OF THE FOUR CONDENSER AIR REMOVAL PUMPS. OUTPUT SIGNALS ARE DISPLAYED IN THE CONTROL ROOM. THE AUCTIONEERED HIGH SIGNAL IS CONVERTED FROM CPM TO GALLONS PER DAY (GPD)
AND IS USED AS AN EARLY INDICATION OF A PRIMARY TO SECONDARY LEAK THROUGH THE S/G TUBES.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 27 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC11 CCll CNTMNT RAD 1 SP6121 CNTMT RAD RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 1
1E8 N/A N/A P
2 AVG OF TWO CHANNELS N/A X >= 6 N/A N/A N/A N
N/A THESE CONTAINMENT RADIATION MONITORS MEASURE GAMMA RADIATION LEVELS IN CONTAINMENT UNDER ACCIDENT CONDITIONS.
THE DETECTORS ARE LOCATED AT THE 73-FOOT LEVEL AND ARE PLACED NEAR THE PRESSURIZER AND #11 STEAM GEN.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 28 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll RCS LTDN RAD 1 R5202!
PROCESS RAD MONITOR RAD LEVEL OF RCS LETDOWN LINE A
CPM N/A 1E1 1 E6 N/A N/A P
1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A THE CVCS LTDN RAD MONITOR IS INSTALLED IN THE LET DOWN LINE TO MONITOR GROSS REACTOR COOLANT ACTIVITY INDICATING A POTENTIAL FUEL ELEMENT FAILURE.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 29 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll1 MAIN SL 1/A 1 R5421!
MAIN STM RAD LP 11 STM GEN 11 STEAM LINE RAD LEVEL A
uCi/cc N/A 1 E-2 1 E4 N/A N/A P
1 INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A THE MAIN STEAM EFFLUENT RADIATION DETECTORS MONITOR FOR NOBLE GASSES WITHIN THE MAIN STEAM LINE. THE MONITORS ARE LOCATED ON THE 27-FOOT LEVEL OF THE AUX BUILDING IN THE MSIV ROOM.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 30 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 Cc1 CCll MAIN SL 2/B 1 R5422!
MAIN STM RAD LP 12 STM GEN 12 STEAM LINE RAD LEVEL A
uCi/cc N/A 1 E-2 1 E4 N/A N/A P
1 INSTRUMENT VALUE N/A N/A N/A N/A N/A N
N/A THE MAIN STEAM EFFLUENT RADIATION DETECTORS MONITOR FOR NOBLE GASSES WITHIN THE MAIN STEAM LINE. THE MONITORS ARE LOCATED ON THE 27-FOOT LEVEL OF THE AUX BUILDING IN THE MSIV ROOM.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 31 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 Ccli SG BD RAD 1A 1R4014!
STM GEN BLOWDOWN ACTIVITY STM GEN 11 BLOWDOWN RAD LEVEL A
CPM N/A 1E1 1 E6 N/A N/A P
1 INVERSE LOG OF INSTRUMENT VALUE N/A 5E4 CPM N/A N/A N/A N
N/A THIS DETECTOR MONITORS A SMALL PORTION OF THE STM GEN BLOWDOWN TO PROVIDE OPERATORS WITH AN EARLY INDICATION OF STM GEN U-TUBE LEAKAGE. ACTUATION OF THE HIGH ALARM AUTOMATICALLY SHUT THE SURFACE BLOWDOWN AND THE BOTTOM BLOWDOWN ISOLATION VALVES. OF BOTH #11 & #12 STEAM GENERATORS THIS MONITOR IS IN THE LINE OF THE BLOWDOWN TANK AND IS COMMON TO BOTH STM GEN.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 32 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll1 CTMNT PRESS 1SP4110 CNTMT PRESSURE CONTAINMENT PRESSURE A
PSIG N/A
-5 150 N/A N/A P
3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)
N/A X >= 2.8 N/A N/A N/A N
N/A THERE ARE A TOTAL OF 3 CONTAINMENT PRESSURE INDICATORS. TWO PROVIDE WIDE RANGE PRESSURE INDICATION 0-150 PSIG FOR POST ACCIDENT MONITORING. THE THIRD INDICATOR IS A NARROW RANGE INDICATION -5 TO +5 PSIG WHICH PROVIDES CONTAINMENT DIFFERENTIAL PRESSURE. ACTUATIONS OCCUR: CIS @ 2.8 PSIG; CSAS @
4.25 PSIG; SIAS @ 2.8 PSIG; RPS @ 2.4 PSIG.
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 33 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll CTMNT TEMP 1SP4111 CNTMT TEMPERATURE CONTAINMENT TEMPERATURE A
DEGF N/A 50 300 N/A N/A P
2 AVG OF TWO CHANNELS N/A X >= 220 N/A N/A N/A N
N/A THERE ARE 2 CONTAINMENT TEMP DETECTORS. ONE MEASURES DOME TEMP, ANOTHER MEASURES THE REACTOR CAVITY TEMP. BOTH OF THESE PROVIDE INDICATION TO THE CONTROL ROOM OPERATORS.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 34 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units / Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll BWST LEVEL 1 SP2RWLVL REFUELING WATER TANK LEVEL BORATED WATER STORAGE TANK LEVEL A
FEET N/A 0
40 RE:USD RE:USD (REFERENCE UNIQ SYS DESC)
P 2
N/A N/A N/A N/A N/A N/A N
WET THE REFUELING WATER TANK SUPPLIES 2300-2700 PPM BORATED WATER TO THE SAFETY INJECTION SYSTEM AND ALSO SUPPLIES WATER FOR USE DURING REFUELING. TANK CAPACITY IS 420,000 GALS. AT 2.5 FEET THE SAFETY INJECTION LINE-UP IS SWITCHED TO THE RECIRCULATION MODE. THIS LEVEL IS EQUAL TO APPROX 10% OF TANK VOLUME.
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 35 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 Cci CCll1 WIND SPEED 1WS60#15M WIND SPEED 60 METER 15 MINUTE AVG WIND SPEED AT REACTOR SITE A
M/S N/A 0
50 N/A N/A S
1 N/A N/A X >- 22 N/A N/A LOW N
N/A WIND SPEED INDICATION IN METERS PER SECOND TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER LOCATED ON SITE. 60 METER ELEVATION
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 36 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CC11 WIND DIR 1 WD60#1 5M WIND DIRECTION 60 METER 15 MINUTE AVG WIND DIRECTION AT REACTOR SITE A
DEG N/A 0
360 N/A N/A S
1 N/A N/A N/A N/A N/A 0 DEGREES (NORTH)
N N/A WIND DIRECTION TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER ON SITE. 60 METER ELEVATION
PWR Data Point Library Reference File Report Date:
Page :
10-22-2013 37 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic / Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll WIND SPEED 1WS10#15M WIND SPEED 10 METER 15 MINUTE AVG WIND SPEED AT REACTOR SITE A
M/S N/A 0
50 N/A N/A S
1 N/A N/A X >= 22 N/A N/A LOW N
N/A WIND SPEED INDICATION IN METERS PER SECOND TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER LOCATED ON SITE. 10 METER ELEVATION
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 38 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CC11 WIND DIR 1WD10#15M WIND DIRECTION 10 METER 15 MINUTE AVG WIND DIRECTION AT REACTOR SITE A
DEG N/A 0
360 N/A N/A S
1 N/A N/A N/A N/A N/A 0 DEGREES (NORTH)
N N/A WIND DIRECTION TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER ON SITE. 10 METER ELEVATION
PWR Data Point Library Reference File Report Date Page:
10-22-2013 39 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog I Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm I Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll ATMOSPHERIC STABILITY 1MMSDTASTB WIND STABILITY BASED ON DELTA TEMP (A)
AIR STABILITY AT REACTOR SITE A
N/A N/A 0 (A) 6 (G)
N/A N/A P
1 COMPLEX N/A N/A N/A N/A N/A N
N/A ATMOSPHERIC STABILITY BASED ON DELTA T (60 METER TEMPERATURE MINUS 10 METER TEMPERATURE, CHANNEL A). CALCULATED ON THE PLANT COMPUTER. VALUES 0 TO 6 CORRESPOND TO STABILITY CLASSES A (EXTREMELY UNSTABLE) TO G (EXTREMELY STABLE). 0=A, 1=B, 2=C, 3=D, 4=E, 5=F, 6=G
PWR Data Point Library Reference File Report Date:
Page:
10-22-2013 40 Date:
Reactor Unit:
Data Feeder:
NRC ERDS Parameter:
Point ID:
Plant Specific Point
Description:
Generic I Condition
Description:
Analog / Digital:
ENGR Units I Digital States:
ENGR Units Conversion:
Minimum Instrument Range:
Maximum Instrument Range:
Zero Point
Reference:
Reference Point Notes Proc or Sens:
Number of Sensors:
How Processed:
Sensor Locations Alarm / Trip Setpoints:
NI Detector Power Supply Cut-Off Power Level:
NI Detector Power Supply Turn-on Power Level:
Instrument Failure Mode:
Temperature Compensation for DP Transmitters:
Level Reference Leg:
Unique System
Description:
11/2/2012 CC1 CCll ATMOSPHERIC STABILITY 1MMS_S60STB 60 METER WIND STABILITY - SIGMA-THETA AIR STABILITY AT REACTOR SITE A
NIA N/A 0 (A) 6 (G)
N/A N/A P
1 COMPLEX N/A N/A N/A N/A N/A N
N/A ATMOSPHERIC STABILITY BASED ON SIGMA-THETA. CALCULATED ON THE PLANT COMPUTER. VALUES 0 TO 6 CORRESPOND TO STABILITY CLASSES A (EXTREMELY UNSTABLE) TO G (EXTREMELY STABLE). 0=A, 1=B, 2=C, 3=D, 4=E, 5=F, 6=G