SAN ONOFRE NUCLEAR GENERATING STATION UNIT 1 ADDENDUM 1 TO SUPPLEMENTAL STUDY REPORT ON EFFECTS OF A PIPING SYSTEM BREAK OUTSIDE THE CONTAINMENT AUGUST 19, 1983 PREPARED BY BECHTEL POWER CORPORATION FOR THE SOUTHERN CALIFORNIA EDISON COMPANY 8310130323 830919 PDR ADOCK 05000206 p
ADDENDUM1 1 Addendum 1 comprises insert pages that provide text, table and figure changes to the Supplemental Study Report on Effects of a Piping System Break Outside the Containment, March 1983, San Onofre Nuclear Generating Station, Unit 1. These changes have been made to reflect the following items:
- 1)
Deletion of the gland steam lines as high energy lines - the normal operating pressure of these lines is below the threshold pressure of 5 psig required for analysis.
The previous evaluation was based on the pressure at upset condition specified in the Line Designation List for SONGS 1.
- 2)
Inclusion of the evaluation of pipe break effects on the main steam lines between the air wrench isolation valves and the turbine main stop valves the previous evaluation did not include an analysis of this portion of the line.
- 3)
Addition (in Table 8.1) of all break locations analyzed whether essential components are affected or not - the existing supplemental study report only lists those break locations affecting essential components.
- 4)
Deletion (in Table 8.1) of full break forces for pipe whip interactions and jet impingement loads for jet impingement interactions.
The following is a listing of all changes:
Page/Figure No.
Changes i
Contents revised iii Tables revised iv Figures revised 2-1 Text revised 2-2 Text revised 2-4 Text revised 2-5 Text revised 2-6 Text revised 5-1 Text revised 5-4 Table 5.3 deleted 7-2 Text revised 8-1 Text revised 8-15 Text revised 8-16 thru 8-43 Table 8.1 revised Fig. 3, 4 and 6 Revised Fig. 11 Deleted Fig. 20 thru 25 Deleted All changes are indicated on affected pages with change bars and the number "1"s.
When an insert page in this Addendum has the same number as an existing page in the report, the existing page has been superseded-and should be deleted-. --When an -insert page does not duplicate an existing QW page, the insert page is new and should be placed in its proper location in the report.
Addendum 1
CONTENTS SUPPLEMENTAL STUDY REPORT ON EFFECTS OF A PIPING SYSTEM BREAK OUTSIDE THE CONTAINMENT Page
1.0 INTRODUCTION
1-1 1.1 GENERAL 1-1
1.2 BACKGROUND
1-1 1.3 SCOPE OF WORK 1-3 2.0
SUMMARY
AND CONCLUSIONS 2-1 2.1
SUMMARY
2-1 2.2 EVALUATION RESULTS 2-1 2.3 FURTHER ANALYSIS 2-6 3.0 CRITERIA 3-1 3.1 GENERAL 3-1 3.2 DEFINITION OF HIGH ENERGY SYSTEMS 3-1 3.3 BREAK POINT LOCATIONS AND TYPES 3-2 3.4 CASCADING EFFECTS 3-4 3.5 SINGLE ACTIVE COMPONENT FAILURE CRITERIA 3-5 4.0 ASSUMPTIONS 4-1 4.1 LOSS OF OFFSITE POWER 4-1 4.2 LIMITED ENERGY RESERVOIR 4-1 4.3 PIPE WHIP AND JET IMPINGEMENT 4-1 5.0 HIGH ENERGY LINES 5-1 5.1 HIGH ENERGY LINES ANALYZED 5-1 5.2 SEISMIC AND QUALITY CLASSIFICATIONS 5-1 6.0 SAFETY-RELATED SYSTEMS AND STRUCTURES 6-1 6.1 SAFETY-RELATED SYSTEMS 6-1 6.2 SAFETY-RELATED STRUCTURES 6-2 7.0 PLANT EMERGENCY SHUTDOWN PROCEDURES 7-1 7.1 GENERAL 7-1 7.2 EXTRACTION STEAM LINE BREAK 7-1 7.3 TURBINE CYCLE VENTS AND DRAIN LINE BREAK 7-2 7.4 (Deleted) 7-2 7.5 AUXILIARY FEEDWATER PUMP DISCHARGE LINE BREAK 7-3 i
Addendum 1
TABLES Page 5.1 Extraction Steam Lines 5-3 5.2 Turbine Cycle Vents and Drain Lines 5-3 5.3 (Deleted) 5-4 1
5.4 Auxiliary Feedwater Discharge Lines 5-4 8.1 Pipe Break and Jet Impingement Analysis 8-16 111 Addendum 1
FIGURES
- 1. General Arrangement Plan of Elevation 35'-6"
- 2. General Arrangement Plan of Elevation 14'-0"
- 3. Turbine Area 2 Plan at Elevation 42'-0" to Elevation 20'-0"
- 4. Turbine Area 5 Plan at Elevation 35'-6" to Elevation 21'-10"
- 5. Turbine Area 5 Plan at Elevation 21'-10" to Elevation 8'-6"
- 6. Turbine Area 6 Plan at Elevation 35'-6" to Elevation 21'-10"
- 7. Turbine Area 6 Plan at Elevation 21'-10" to Elevation 8'-6"
- 8. P&I Diagram Turbine Cycle Vents and Drains System
- 9. P&I Diagram Auxiliary Feedwater System
- 10.
P&I Diagram Steam System
- 11.
(Deleted) 1 12 -
- 14.
Extraction Steam Lines Postulated Break Locations 15 -
- 19.
Turbine Cycle Vents and Drain Lines Postulated Break W
Locations 20 - 25.
(Deleted) 1
- 26.
Auxiliary Feedwater Lines Postulated Break Locations
- 27.
Auxiliary Feedwater Pump Steam Supply Pipe Break Interactions iv Addendum 1
2.0
SUMMARY
AND CONCLUSIONS 2.1
SUMMARY
Phase II HELBA postulated a total of 266 break point locations in the Category II and III high energy lines and the Auxiliary Feedwater discharge lines analyzed. These postulated break locations resulted in a total of 158 interactions (48 for pipe whip and 110 for jet impingement) with safety related non-electrical components (e.g., piping, structural steel, etc.).
Of these 158 interactions 102 (34 for pipe whip and 68 for jet impingement) remain unresolved and require further analysis. The remaining 56 pipe whip and jet impingement interactions are determined to be acceptable and no further analysis is needed.
2.2 EVALUATION RESULTS 2.2.1 Category II and III Line Breaks All Category II and III high energy lines analyzed in the Phase II HELBA are in the Turbine Building below elevation 35'-6" under the heater decks.
Category II and III high energy lines located in other areas of the plant are eliminated from the analysis because they have a limited energy reservoir and therefore have negligible ability to damage safety-related components or because they are routed in areas in which there are no safety related components (e.g. above the Turbine Building heater decks).
2-1 Addendum I
Safety-related components located below the Turbine Building heater decks and adjacent to the high energy lines analyzed in the Phase II HELBA include the following:
A.
Auxiliary Feedwater System Auxiliary Feedwater Pumps, pump suction and discharge lines, associated valves, instruments, and controls Steam supply line and associated valves, instruments and controls for the turbine driven Auxiliary Feedwater Pump B.
Safety Injection System Feedwater Pumps, associated piping, valves, instruments, and controls C.
Main Steam System 1
Steam lines upstream of the turbine main stop valves D.
Instrument Air Backup System Nitrogen bottles and associated valves and tubing for safety related pneumatic control valves E.
Turbine Building Structural Steel Members F.
Electrical Raceways 2-2 Addendum 1
Eight pipe break interactions are identified for the Auxiliary Feedwater Pump steam supply line (69-3"-EG) within a 25 foot pipe span. These interactions are illustrated in Figure 27 with break numbers and load information. The four jet impingement loads are not analyzed because they are bounded by the four pipe whip interactions at both ends of the 25 foot pipe span. These pipe whip interactions are unresolved and will require further analysis.
During postulated pipe breaks outside the containment, the Safety Injection System is required for plant shutdown only during steam line and feedwater line ruptures.
Consequently, the feedwater pumps and associated safety injection components are evaluated only when main steam lines or feedwater lines and safety injection system components are concurrently impacted by a postulated Category II or III line break. This situation is not encountered for Phase II KELBA.
The portions of the main steam lines, including branch lines, between the containment penetrations and the main steam stop valves are safety-related 1
impactees. Twenty-seven pipe break interactions (16 for pipe whip and 11 for jet impingement) have been identified for these portions of main steam piping. These interactions are unresolved and will require further analysis.
The only nitrogen backup to the instrument air system located in the Turbine Building is for the Auxiliary Feedwater System control valves.
The nitrogen bottles are located outside the Turbine Building and are not affected by postulated Category II and III pipe breaks. Three jet impingement interactions are identified for the 1/2 inch stainless steel tubing. It is 2-4 Addendum 1
judged that the jet force could potentially damage the line. These jet impingement interactions are unresolved and will require further analysis.
Eight pipe whip and 59 jet impingement interactions have been identified and analyzed for safety-related Turbine Building structural steel members. All eight pipe whip and 37 of the 59 jet impingement inter 1
actions are determined to be acceptable by analyses indicating that the impactees (structural members) are able to withstand the pipe break loads.
Twenty-two unresolved jet impingement interactions remain which involve a total of 12 structural members.
2.2.2 Auxiliary Feedwater Pump Discharge The Category I portions of the Auxiliary Feedwater Pump discharge lines (between the check valves and the main feedwater lines) are located between the Reactor Sphere and the Turbine Building. Safety-related components in this area include the safety injection lines, feedwater lines, main steam lines, reactor sphere, electrical conduit and cable trays. The safety injection, feedwater, and main steam lines are not affected by the three Auxiliary Feedwater Pump discharge lines (381A, B, C-3"-EG) because sufficient separation exists between these systems and the auxiliary feedwater discharge piping. The three discharge pipes are routed in close proximity to each other, however, and may be adversely affected following a line break. The reactor sphere is affected by three jet impingement and two pipe whip interactions with a jet force of 18 kips in each case. These interactions are addressed in Table 8.1.
2-5 Addendum 1
The Auxiliary Feedwater Pump discharge piping, up to the check valves adjacent to the main feedwater lines, is normally not pressurized and carries cold water when either of the Auxiliary Feedwater Pumps is running. The limited energy in the pipe at the centrifugal pump discharge will not cause any pipe whip or jet impingement problems.
Therefore, this portion of piping is excluded from the full pipe break analysis.
2.3 FURTHER ANALYSIS One hundred and two unresolved interactions are identified in this report and are summarized in Table 8.1.
Phase III HELBA will further analyze these interactions in order to determine the need for modifications.
Electrical components and raceways will be evaluated concurrently with SCE's 10 CFR 50 Appendix R program. The need to perform further analysis and the schedule will be determined during the Integrated Assessment.
2-6 Addendum 1
5.0 HIGH ENERGY LINES 5.1 HIGH ENERGY LINES ANALYZED Category II and III high energy lines outside the containment, are analyzed to determine the effects of a postulated rupture on the safe shutdown of the plant. The systems or portions of systems containing the lines analyzed include:
A.
Turbine Cycle Vents and Drain Lines B.
Auxiliary Feedwater Discharge Lines (the Category I portion)
C.
Extraction Steam Lines Process and Instrumentation Diagrams for these systems are shown in Figures 8 through 11.
Tables 5.1 through 5.4 identify by systems the major lines and branch lines considered for this study.
5.2 SEISMIC AND QUALITY CLASSIFICATIONS As outlined in Section 9.2.3 of the Final Safety Analysis (refer ence 9) for San Onofre Unit 1, the objective of the seismic design of the plant is to ensure that the most adverse conditions of stress and deflection 5-1 Addendum 1
TABLE 5.3 (Deleted)
TABLE 5.4 AUXILIARY FEEDWATER DISCHARGE LINES Lin NuberDesripioneismiic Quality Lin NuberDesripionClassification IClassification 381A-3"-EG Aux Feedwater Discharge A
Safety-related 381B-3"-EG Aux Feedwater Discharge A
38C3-G Aux Feedwater Discharge A
5-4 Addendum 1
Time Manual Actions 10 hrs.
When RCS temperature reaches 350'F, go on the resi dual heat removal system.
14 hrs.
Stabilize the reactor coolant system at 140 0F.
7.3 TURBINE CYCLE VENTS AND DRAIN LINE BREAK The operator would manually trip the reactor if it has not been tripped automatically. The turbine would be tripped and steam dump would be initiated automatically. The manual actions and the times associated with these opera tions are the same as those given for an extraction steam line break.
7.4 (Deleted) 1 7-2 Addendum I
8.0 EVALUATION 8.1 GENERAL By using the methods outlined below, structural and mechanical inter actions that could directly or indirectly result in the plant's inability to mitigate the consequences of an accident and place the reactor in a cold shutdown condition are identified.
Method of analysis:
A.
Identify all Category II and III lines based on the maximum tempera ture and pressure conditions.
B.
Eliminate Category II and III lines that contain limited energy reservoirs.
C.
Develop isometric drawings of high energy systems to be analyzed, based on piping plan and section drawings.
D.
Field verify isometrics to ensure that they reflect the as-built conditions.
E.
Identify all safety-related items (equipment, systems, structural steel, etc.) in the vicinity of the Category II and III lines.
8-1 Addendum 1
Table 8.1 provides a listing of the pipe break and jet impingement analysis as indicated below:
A.
Breakpoint numbers -
locations of postulated breaks (Fig ures 11-26).
B.
Impactor Line No. -
high energy line in which break is postulated.
C.
Description of Impactee or Impingee - general description of essential items affected by the high energy line, or indication that essential components are not affected. Essential components are those required to function to achieve and maintain cold shut down of the plant for a specific pipe break event.
D.
Type of Interaction - identification of pipe whip, jet impingement from break, or both.
E.
Evaluation Results - brief description of acceptable interaction and indication of unresolved interaction.
8-15 Addendum 1
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 1 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 EXTRACTION STEAM LINES 1016-23-16"-HH No essential impactees for these postu-Not Applicable No further evaluation 1025 lated break locations required 1026 23-16"-HH Structural beam W24 x 68 Pipe Whip Beam withstands impact between column lines E and F, between column lines 3 and 5 Main steam line 17-8"-EG Impingement &
Interactions unresolved Pipe Whip MOV-14 in main steam line 17-6"-EG Impingement &
Interactions unresolved Pipe Whip MOV-15 in Main steam line 19-6"-EG Impingement Interaction unresolved 1027 23-16"-HH Structural beam W24 x 68 Impingement Interaction unresolved between column lines E and F, between column lines 3 and 5 Structural beam W24 x 68 Pipe Whip Beam withstands impact between column lines E and F, between column lines 3 and 5 Structural beam W24 x 110 Impingement Interaction unresolved along column line 3, between column lines E and F
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 2 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 EXTRACTION STEAM LINES 1027 23-16"-HH Main steam line 17-8"-EG Pipe Whip Interaction unresolved Cont.
MOV-14 in main steam line 17-6"--EG Pipe Whip Interaction unresolved 1028 23-16"-HH Structural beam W24 x 84 Pipe Whip Beam determined to not between column lines E and F, be impacted by pipe on between column lines 1 and 2 whip I.A Main steam line 17-8"-EG Pipe Whip Interaction unresolved MOV-14 in main steam line 17-6"-EG Pipe Whip Interaction unresolved 1029 23-16"-HH Main steam line 17-8"-EG Pipe Whip Interaction unresolved MOV-14 in main steam line 17-6"-EG Pipe Whip Interaction unresolved 1030 23-16"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required
- 1031, 25-18"-HH No essential impactees for these postu-Not Applicable No further evaluation 1032 lated break location required 1033 1034 25-18"-HH Structural beam W24 x 84 Impingement Beam withstands jet along column line 5, between load column lines J and K
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 3 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 EXTRACTION STEAM LINES 1035 25-18"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required 1037 25-18"-HH Column F5 Impingement Column withstands jet W24 x 130 load Structural beam W24 x 84 Impingement Beam withstands jet along column 5, between column load lines F and G 1038-25-18"-HH No essential impactees for these postu-Not Applicable No further evaluation 1042 lated break locations required 1043 25-18"-HH Structural brace W12 x 170 Impingement Brace withstands jet at column line 2, between load column lines F and G 1044 25-18"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required 1045 25-18"-HH Structural brace W12 x 170 Impingement Brace withstands jet at column line F, load between column lines 1 and 2
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 4 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 EXTRACTION STEAM LINES 1045 25-18"-HH Structural brace W24 x 68 Impingement Beam withstands jet Cont.
between column line F and G, load between column lines 1 and 2 1046 25-18"-HH Structural brace W12 x 170 Impingement Brace withstands jet along column line F between column load between column lines 1 and 2 I-1 1047-25-18"-HH No essential impactees for these Not Applicable No further evaluation 1049 postulated break locations required
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 5 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 EXTRACTION STEAM LINES 1001-24-16"-HH No essential impactees for these postu-Not Applicable No further evaluation 1010 lated break locations required 1011 24-16"-HH Main steam line 18-10"-EG Impingement &
Interactions unresolved Pipe Whip Auxiliary feedwater turbine-driven Impingement Interaction unresolved pump steam supply line 69-3"-EG Auxiliary feedwater turbine-driven Pipe Whip Interaction unresolved pump steam supply line 69-3"-EG Structural beam W24 x 68 Pipe Whip Beam withstands impact between column lines E and F; between column lines 9 and 11 MOV-16 in main steam line 18-6"-EG Impingement &
Interactions unresolved Pipe Whip MOV-17 in main steam line 20-6"-EG Impingement Interaction unresolved 0
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 6 of 27)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 EXTRACTION STEAM LINES 1012 24-16"-HH Auxiliary feedwater turbine-driven Pipe Whip Interaction unresolved pump steam supply line 69-3"-EG Main steam line 18-10"-EG Pipe Whip Interaction unresolved MOV-16 in main steam line 18-6"-EG Pipe Whip Interaction unresolved Structural Beam W24 x 68 Pipe Whip Beam withstands impact between column lines E and F, between column lines 9 and 11 Structural Beam W24 x 68 Impingement Interaction unresolved between column lines E and F, between column lines 9 and 11 Structural Beam W24 x 110 Impingement Interaction unresolved along column line 11, between column lines E and F 1013 24-16"-HH Structural Beam W24 x 84 Pipe Whip Beam determined to not between column lines E and F; be impacted by pipe between column lines 11 and 13 whip a
I
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 7 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 EXTRACTION STEAM LINES 1013 24-16"-HH Auxiliary feedwater turbine-driven Pipe Whip Interaction unresolved Cont.
pump steam supply line 69-3"-EG Main steam line 18-10"-EG Pipe Whip Interaction unresolved MOV-16 in main steam line 18-6"-EG Pipe Whip Interaction unresolved 1014 24-16"-HH Main steam line 18-10"-EG Pipe Whip Interaction unresolved MOV-16 in main steam line 18-6"-EG Pipe Whip Interaction unresolved 1015 24-16"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required
- 1051, 26-18"-HH No essential impactees for these postu-Not Applicable No further evaluation 1052 lated break locations required 1055 26-18"-HH Structural Beam W18 x 45 Impingement Interaction unresolved between column lines F and G; between column lines 9 and 11
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 8 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 EXTRACTION STEAM LINES 1055 26-18"-HH Main steam line 15-6"-EGX Impingement Interaction unresolved Cont.
CV-4 in main steam line 15-6"-EGX Impingement Interaction unresolved 1056 26-18"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required 1057 26-18"-HH Main steam line 15-6"-EGX Impingement Interaction unresolved CV-4 in main steam line 15-6"-EGX Impingement Interaction unresolved 1058 26-18"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required 1059 26-18"-HH Structural Beam W18 x 45 Impingement Beam withstands jet between column lines F and C; load between column lines 9 and 11 1060 26-18"-HH Structural beam W18 x 45 Impingement Beam withstands jet between column lines F and G, load between column lines 9 and 11 1061-26-18"--HH No essential impactees for these postu-Not Applicable No further evaluation 1064 lated break locations required
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 9 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 EXTRACTION STEAM LINES 1065 26-18"-HH Structural beam W24 x 68 Impingement Beam withstands jet between column lines F and G, load between column lines 11 and 13 Auxiliary Feedwater Pumps Pipe Whip Barrier withstands Barrier impact 00 1066-26-18"-HH No essential impactees for these postu-Not Applicable No further evaluation 1069 lated break points required 0L
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 10 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 TURBINE CYCLE VENTS AND DRAIN LINES 1501-113-14"-HH No essential impactees for these postu-Not Applicable No further evaluation 1505 lated break locations required 1506 113-14"-HH Structural Brace W12 x 170 Impingement Brace withstands jet at column line 2, between load column lines F and G 1507 113-14"-HH Structural Brace W12 x 170 Pipe Whip Brace withstands impact at column line 2, between column lines F and G 1508 113-14"-HH Column F5 Impingement Column withstands jet W24 x 130 load 1509-113-14"-HH No essential impactees for these postu-Not Applicable No further evaluation 1516 lated break locations required 1517-129-14"-HH No essential impactees for these postu-Not Applicable No further evaluation 1526 lated break locations required 2001-109-8"-HH No essential impactees for these postu-Not Applicable No further evaluation 2006 lated break locations required
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 11 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 TURBINE CYCLE VENTS AND DRAIN LINES 2007 109-8"-HH Structural Beam W24 x 84 Impingement Interaction unresolved between column lines E and F, between column lines 1 and 3 Structural Beam W24 x 100 Impingement Interaction unresolved between column lines E and F, between column lines l and 3 2008 109-8"-HH Structural Beam W24 x 84 Impingement Interaction unresolved between column lines E and F, between column lines 1 and 3 Structural Beam W24 x 100 Impingement Beam withstands jet between column lines E and F, load between column lines 1 and 3 2009 109-8"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required 2010 109-8"-HH Structural Beam W24 x 100 Impingement Beam withstands jet between column lines E and F, load between column lines 1 and 3
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 12 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 TURBINE CYCLE VENTS AND DRAIN LINES 2010 109-8"-HH Structural Beam W24 x 130 Impingement Interaction unresolved Cont.
along column line F, between column lines 1 and 2 2011 109-8"-HH Structural Beam W24 x 100 Impingement Beam withstands jet between column lines E and F, load between column lines 1 and 3 Structural Beam W24 x 76 Impingement Interaction unresolved between column lines E and F, between column lines 1 and 3 Structural Beam W24 x 130 Impingement Interaction unresolved along column line F, between column lines 1 and 2 2012 109-8"-HH Structural Beam W24 x 76 Impingement Interaction unresolved between column lines E and F, between column lines 1 and 3 2013 109-8"-HH Structural Beam WV24 x 76 Impingement Interaction unresolved between column lines E and F, between column lines l and 3
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 13 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 TURBINE CYCLE VENTS AND DRAIN LINES 2014-109-8"-HH No essential impactees for these postu-Not Applicable No further evaluation 2017 lated break locations required 2018-111-14"-HHX No essential impactees for these postu-Not Applicable No further evaluation 2021 lated break locations required 2022-109-8"-HH No essential impactees for these postu-Not Applicable No further evaluation 2024 lated break locations required
- 2025, 109-6"-HH Structural Beam W24 x 130 Impingement Interaction unresolved 2026 along column line F, between column lines 1 and 2 Structural Beam W24 x 68 Impingement Beam withstands jet between column lines F and G, load between column lines 1 and 2
- 2095, 111-14"--HHX No essential impactees for these postu-Not Applicable No further evaluation 2096 lated break locations required 2501-121-8"--HH No essential impactees for these postu-Not Applicable No further evaluation 2503 lated break locations required 2504-205-8"-HH No essential impactees for these postu-Not Applicable No further evaluation 2506 lated break locations required
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 14 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 TURBINE CYCLE VENTS AND DRAIN LINES 2507-121-8"-HH No essential impactees for these postu-Not Applicable No further evaluation 2515 lated break locations required 2516-127-10"-HH No essential impactees for these postu-Not Applicable No further evaluation 2520 lated break locations required 2521 127-10"-HHX Structural Beam W24 x 130 Impingement Beams withstand jet along column line F, between load column lines 3 and 5 (there are two beams between column lines 3 and 5 affected by this postulated break location)
Structural Beam W18 x 45 Impingement Beam withstands jet between column lines F and G, load between lines 3 and 5 2522 127-10"-HH No essential impactees for these postu-Not Applicable No further evaluation lated break locations required 2523 127-10"-HHX Structural Beam W18 x 45 Impingement Beam withstands jet between column lines F and G, load between column lines 3 and 5
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 15 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 5 TURBINE CYCLE VENTS AND DRAIN LINES 2525 127-10"-HHK Structural Beam W24 x 68 Impingement Beam withstands jet between column lines F and G, load between column lines 1 and 2 2526 127-10"-HHX No essential impactees for this postu-Not Applicable No further evaluation lated break location required 2527-127-14"-HHX No essential impactees for this postu-Not Applicable No further evaluation 2529 lated break location required 2530-123-8"-HH No essential impactees for this postu-Not Applicable No further evaluation 2535 lated break location required 2536-205-8"-HH No essential impactees for this postu-Not Applicable No further evaluation 2537 lated break location required
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 16 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES
- 1600, 114-14"-HH No essential impactees for these Not Applicable No further evaluation 1601 postulated break locations required 1602 114-14"-HH Structural Beam W24 x 68 Pipe Whip Beam determined not between column lines F and G, to be impacted by between column lines 12 and 13 pipe whip Structural beam W24 x 68 Impingement Beam withstands jet between column lines F and G, load between column lines 12 and 13 1603 114-14"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required 1604 114-14"-HH Auxiliary Feedwater Pumps Impingement Barrier withstands jet Barrier load 1605 114-14"-HH Auxiliary feedwater pumps suction lines No evaluation per 723-8"-HP Impingement formed:
Impactees 380-4"-HP Impingement non-safety related due 723-8"-HP Pipe Whip to installation of new 380-4"-HP Pipe Whip suction lines
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 17 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES 1606 114-14"-HH Auxiliary feedwater pumps suction lines No evaluation per 380-4"-HP Impingement formed:
Impactees 380-4"-HP Pipe Whip non-safety related due 723-8"-HP Pipe Whip to installation of new suction lines S
1607 114-14"-HH Auxiliary feedwater turbine-driven pump steam supply line 69-3"-EG (impinged upon by two separ-Impingement Interactions unresolved ate jets from this postulated break location) 69-3"-EG Pipe Whip Interaction unresolved 1608 114-14"-HH Auxiliary feedwater turbine-driven pump steam supply line 69-3"-EG Impingement Interaction unresolved 1609-114-14"-HH No essential impactees for these postu-Not Applicable No further evaluation 1613 lated break locations required 1614 130-14"-HH No essential impactees for these postu-Not Applicable No further evaluation lated break locations required
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 18 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES 1615 130-14"-HH Auxiliary Feedwater Pumps Pipe Whip Barrier determined to Barrier not be Impacted by pipe whip 1616-130-14"-HH No essential impactees for these postu-Not Applicable No further evaluation 1623 lated break locations required 2027-110-8"-HH No essential impactees for these postu-Not Applicable No further evaluation 2033 lated break locations required
- 2034, 110-8"-HH Structural Beam W24 x 84 Impingement Interaction unresolved 2035 between column lines E and F, between column lines 11 and 13 Nitrogen backup Impingement Interaction unresolved instrument air to auxiliary feedwater pumps 2035 110-8"-HH Structural Beam W24 x 100 Impingement Beam withstands jet between column lines E and F, load between column lines 11 and 13 Structural Beam W24 x 130 Impingement Beam withstands jet along column line F, between load column lines 12 and 13
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 19 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES 2036 110-8"-HH Nitrogen backup Impingement Interaction unresolved instrument air to auxiliary feedwater pumps 110-8"-HH Structural beam W24 x 76 Impingement Interaction unresolved between column lines E and F, between column lines 11 and 13 Structural beam W24 x 100 Impingement Beam withstands jet between column lines E and F, load between column lines 11 and 13 Structural beam W24 x 130 Impingement Interaction unresolved along column line F, between column lines 11 and 13
- 2037, 110-8"-HH Structural beam W24 x 76 Impingement Interaction unresolved 2038 between column lines E and F, between column lines 11 and 13 2039-110-8"-HH No essential impactees for these postu-Not Applicable No further evaluation 2041 lated break locations required 2042-112-10"-HH No essential impactees for these postu-Not Applicable No further evaluation 2047 lated break locations required
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 20 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES
- 2048, 110-6"-HH No essential impactees for these postu-Not Applicable No further evaluation 2049 lated break locations required 2050 110-6"-HH Structural beam W24 x 68 Impingement Beam withstands jet between column lines F and G, load between column lines 11 and 13 LA Structural beam W24 x 130 Impingement Interaction unresolved along column line F, between column lines 11 and 13 2051 110-6"-HH Structural beam W24 x 68 Impingement Beam withstands jet between column lines F and G, load between column lines 11 and 13
- 2091, 110-8"-HH No essential impactees for these postu-Not Applicable No further evaluation 2092 lated break locations required a
'-I
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 21 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES
- 2550, 122-8"-HH No essential impactees for these postu-Not Applicable No further evaluation
- 2555, lated break locations required
- 2560, 2565,
- 2570, 2575,
- 2580, 0
- 2585, 2590, 2595
- 2600, 206-8"-HH No essential impactees for these postu-Not Applicable No further evaluation
- 2605, lated break locations required
- 2610, 2615, 2620
- 2625, 128-10"-HH No essential impactees for these postu-Not Applicable No further evaluation
- 2628, lated break locations required 2630
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 22 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES 2635 128-10"-HHX Auxiliary feedwater pump suction line Impingement No evaluation performed:
723-8"-HP Impactee non-safety related due to installation of new suction lines Main steam line 15-8"-EG Impingement Interaction unresolved 2640 128-10"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required 2645 128-10"-HHX Structural Beam W24 x 130 Impingement Beam withstands jet along column line F, load between column lines 9 and 11 2650 128-10"-HHX Structural Beam W18 x 45 Impingement Beam withstands jet between column lines F and G, load between column lines 9 and 11 Structural Beams W24 x 130 Impingement Beams withstand jet along column line F, load between column lines 9 and 11 (there are two beams between column lines 9 and 11 affected by this postulated break location)
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 23 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES 2655 128-10"-HHX No essential impactees for this postu-Not Applicable No further evaluation lated break location required 2660 128-10"-HHX Structural Beam W24 x 130 Impingement Beam withstands jet along column line F, load between column lines 9 and 11 Structural Beam W18 x 45 Impingement Beam withstands jet between column lines F and G, load between column lines 9 and 11 2670 128-10"-HHX Structural Beam W24 x 68 Impingement Beam withstands jet between column line F and G, load between column lines 12 and 13 Structural Beam W18 x 45 Impingement Beam withstands jet between column lines F and G, load between column lines 11 and 13 Structural Beam W24 x 130 Impingement Beam withstands jet along column line F, load between column lines 12 and 13 Go
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 24 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 6 TURBINE CYCLE VENTS AND DRAIN LINES
- 2675, 128-10"-HHX No essential impactees for these postu-Not Applicable No further evaluation
- 2680, lated break locations required
- 2685, 2690
- 2695, 124-8"-HH No essential impactees for these postu-Not Applicable No further evaluation
- 2700, lated break locations required
- 2705, 2710,
- 2715, 2720 2725 206-8"-HH No essential impactees for this postu-Not Applicable No further evaluation lated break location required 2730 122-6"-HH No essential impactees for these postu-Not Applicable No further evaluation lated break locations required
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 25 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 2 AUXILIARY FEEDWATER DISCHARGE LINES 3001 381A-3"-EG No essential impactees for this postu-Not Applicable No further evaluation lated break location required 3002 381C-3"-EG No essential impactees for this postu-Not Applicable No further evaluation lated break location required 3003 381B-3"-EG No essential impactees for this postu-Not Applicable No further evaluation lated break location required 3004 381A-3"-EG 381B-3"-EG Impingement Interaction unresolved 381C-3"-EG Impingement Interaction unresolved 3005 381C-3"-EG 381B-3"-EG Impingement Interaction unresolved Reactor sphere Pipe Whip Interaction unresolved 3006 381B-3"-EG No essential impactees for this postu-Not Applicable No further evaluation lated break location required 3007 381A-3"-EG 381C-3"-EG Impingement Interaction unresolved 381B-3"-EG Impingement Interaction unresolved
0 TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 26 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 2 AUXILIARY FEEDWATER DISCHARGE LINES 3008 381C-3"-EG Reactor sphere Pipe Whip Interaction unresolved 381B-3"-EG Impingement Interaction unresolved 3009 381B-3"-EG No essential impactees for this postu-Not Applicable No further evaluation lated break location required 3n 3010 381A-3"--EG 381B-3"-EG Impingement Interaction unresolved 381A-3"-EG Impingement Interaction unresolved 381B-3"-EG Impingement Interaction unresolved 3011 381B-3"-EG 381A-3"-EG Impingement Interaction unresolved 381C-3"-EG Impingement Interaction unresolved 38C
" GImpingement Interaction unresolved 3013 381A-3"-EG 381C-3"-EG Pipe Whip Interaction unresolved Reactor sphere Impingement Interaction unresolved 3014 381C-3"-EG 3818-3"-EG Impingement Interaction unresolved 381A-3"-EG Impingement Interaction unresolved
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 27 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 2 AUXILIARY FEEDWATER DISCHARGE LINES 3014 381C-3"-EG 381B-3"-EG Pipe Whip Interaction unresolved Cont.
Reactor sphere Impingement Interaction unresolved 3015 381B-3"-EG 381C-3"-EG Impingement Interaction unresolved Reactor sphere Impingement Interaction unresolved 3016 381A-3"-EG 381C-3"-EG Impingement Interaction unresolved 381C-3 "-EG Pipe Whip Interaction unresolved 3017 381C-3"-EG 381A-3"-EG Impingement Interaction unresolved 381B-3" -EG Impingement Interaction unresolved 381B-3"-EG Pipe Whip Interaction unresolved 381A-3"-EG Pipe Whip Interaction unresolved 3018 381B-3"-EG 381C-3"-EG Impingement Interaction unresolved 381C-3"-EG Pipe Whip Interaction unresolved 3019 381A-3"-EG 381C-3"-EG Impingement Interaction unresolved I
TABLE 8.1 PIPE WHIP AND JET IMPINGEMENT ANALYSIS (Sheet 28 of 28)
Break Location Impactor Type of Number Line No.
Description of Impactee or Impingee Interaction Evaluation Results AREA 2 AUXILIARY FEEDWATER DISCHARGE LINES 3020 381C-3"-EG 381B-3"-EG (there are two jets from this Impingement Interaction unresolved postulated break location which affect this line) 381A-3"-EG Pipe Whip Interaction unresolved 3021 381B-3"-EG 381C-3"-EG Pipe Whip Interaction unresolved 3022 381A-3"-EG 381C-3"-EG Impingement Interaction unresolved 381C-3"-EG Pipe Whip Interaction unresolved 3023 381C-3"-EG 381B-3"-EG Impingement Interaction unresolved 381A-3"-EG Impingement Interaction unresolved 381B-3"-EG Pipe Whip Interaction unresolved 381A-3"-EG Pipe Whip Interaction unresolved 3024 3818-3"-EG 381C-3"-EG Impingement Interaction unresolved 381C-3"-EG Pipe Whip Interaction unresolved
'a