Forwards Amend 104 to License DPR-13 & Safety Evaluation. Amend Approves Diesel Generator Rating of 5,250 Kw for Both Generators Until Next Refueling Outage Provided Main Journal Bearings Inspected Prior to Plant Operation
ML13316B043
Person / Time
Site: San Onofre 
Issue date: 07/22/1988
From: Trammell C
Office of Nuclear Reactor Regulation
To: Baskin K
Southern California Edison Co
Shared Package
ML13316B045 List:
References
TAC-68439 NUDOCS 8808120223
Download: ML13316B043 (4)


Text

July 22, 1988 Docket No. 50-206 DISTRIBUTION Docket 7E_(T50-2O6)BGrimes NRC & LPDRs Mr. Kenneth P. Baskin PD5 Plant File TBarnhart (4)

Vice President GHolahan EButcher Southern California Edison Company JLee (3)

ACRS (10) 2244 Walnut Grove Avenue OGC-WF GPA/PA Post Office Box 800 DHagan ARM/LFMB Rosemead, California 91770 Edordan WJones CTrammel 1

Dear Mr. Baskin:

SUBJECT:

ISSUANCE OF AMENDMENT NO. 104 TO PROVISIONAL OPERATING LICENSE SAN ONOFRE NUCLEAR GENERATING STATION, UNIT NO. 1 (TAC NO. 68439)

The Commission has issued the enclosed Amendment No. 104 to Provisional Operating License No. DPR-13 for San Onofre Nuclear Generating Station, Unit No. 1. The amendment consists of changes to the license and the Technical Specifications in response to your application dated June 22, 1988, as supplemented by letters dated July 15, 19, 21, and 22,1988.

The amendment approves a diesel generator rating of 5250 KW +/-5% for both generators until the next refueling outage, provided that main journal bearings no. 8 and 9 on diesel-generator no. 1 and main journal bearings no. 9 and 10 on diesel-generator no. 2 are inspected prior to plant operation and found to be free of cracks.

The amendment also requires (1) journals no. 8 through 12 to be inspected on both units at the next refueling outage and thereafter until the long-term issue of crankshaft cracking has been resolved, (2) piston skirts to be replaced with type AE at the next refueling outage, (3) all diesel test starts to be slow starts except for the one performed at 18-month intervals, (4) confirmatory load measurements for the largest loads, amd (5) resolution of the charging pump overload issue.

The largest rejected load is also modified from 2611 KW to 3220 KW.

A copy of our related Safety Evaluation is also enclosed.

The Notice of Issuance will be included in the Commission's next regular biweekly Federal Register notice.

Sincerely, original signed by Charles M. Trammell, Senior Project Manager

'00 Project Directorate V Division of Reactor Projects

III, S

C S

E MIVU V and Special Projects 0

Enclosures:

Th C

1. Amendment No. 104 to P v o

O r License No. DPR-13 i

2. Safety Evaluation

/a hcc w/enclosures:

g LC eeneator uniphaetrfulnguaeeroie htmijunlbaig See ne8 age concurrences.

nd bn P5DRSP/PD5 OGCD a

1 o e e e

a 7/.

2 218 in ple foun to be fre of crcs The8 amendmen also/8 reuies()ounlsno

July 22, 1988 Docket No. 50-206 DISTRIBUTION Docket File (50-206)BGrimes NRC & LPDRs Mr. Kenneth P. Baskin PD5 Plant File TBarnhart (4)

Vice President GHolahan EButcher Southern California Edison Company JLee (3)

ACRS (10) 2244 Walnut Grove Avenue OGC-WF GPA/PA Post Office Box 800 DHagan ARM/LFMB Rosemead, California 91770 EJordan WJones CTramme 11

Dear Mr. Baskin:

SUBJECT:

ISSUANCE OF AMENDMENT NO. 104 TO PROVISIONAL OPERATING LICENSE SAN ONOFRE NUCLEAR GENERATING STATION, UNIT NO. 1 (TAC NO. 68439)'

The Commnission has issued the enclosed Amendment No. 104 to Provisional Operating License No. DPR-13 for San Onofre Nuclear Generating Station, Unit No. 1. The amendment consists of changes to the license and the Technical Specifications in response to your application dated June 22, 1988, as supplemented by letters dated July 15, 19, 21, and 22, 1988.

The amendment approves a diesel generator rating of 5250 KW +/-5% for both generators until the next refueling outage, provided that main journal bearings no. 8 and 9 on diesel-generator no. 1 and main journal bearings no. 9 and 10 on diesel-generator no. 2 are inspected prior to plant operation and found to be free of cracks. The amendment also requires (1) journals no. 8 through 12 to be inspected on both units at the next refueling outage and thereafter until the long-term issue of crankshaft cracking has been resolved, (2) piston skirts to be replaced with type AE at the next refueling outage, (3) all diesel test starts to be slow starts except for the one performed at 18-month intervals, (4) confirmatory load measurements for the largest loads, amd (5) resolution of the charging pump overload issue. The largest rejected load is also modified from 2611 KW to 3220 KW.

A copy of our related Safety Evaluation is also enclosed. The Notice of Issuance will be included in the Commission's next regular biweekly Federal Register notice.

Sincerely, original signed by Charles M. Trammell, Senior Project Manager Project Directorate V Division of Reactor Projects

III, IV, V and Special Projects

Enclosures:

1. Amendment No. 104 to License No. DPR-13
2. Safety Evaluation cc w/enclosures:

See next page

  • See previous concurrences.

D PD DRSP/PD5 OGC o"P found CTrammell:

Gn r

e (1jura

/87

/22/88

-7/22/88 7/'2/88

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 July 22, 1988 Docket No. 50-206 Mr. Kenneth P. Baskin Vice President Southern California Edison Company 2244 Walnut Grove Avenue Post Office Box 800 Rosemead, California 91770

Dear Mr. Baskin:

SUBJECT:

ISSUANCE OF AMENDMENT NO.104 TO PROVISIONAL OPERATING LICENSE SAN ONOFRE NUCLEAR GENERATING STATION, UNIT NO. 1 (TAC NO. 68439)

The Commission has issued the enclosed Amendment No.104 to Provisional Operating License No. DPR-13 for San Onofre Nuclear Generating Station, Unit No. 1. The amendment consists of changes to the license and the Technical Specifications in response to your application dated June 22, 1988, as supplemented by letters dated July 15, 19, 21, and 22, 1988.

The amendment approves a diesel generator rating of 5250 KW +/-5% for both

.generators until the next refueling outage, provided that main journal bearings no. 8 and 9 on diesel-generator no. 1 and main journal bearings no. 9 and 10 on diesel-generator no. 2 are inspected prior to plant operation and found to be free of cracks. The amendment also requires (1) journals no. 8 through 12 to be inspected on both units at the next refueling outage and thereafter until the long-term issue of crankshaft cracking has been resolved, (2) piston skirts to be replaced with type AE at the next refueling outage, (3) all diesel test starts to be slow starts except for the one performed at 18-month intervals, (4) confirmatory load measurements for the largest loads, and (5) resolution of the charging pump overload issue. The largest rejected load is also modified from 2611 KW to 3220 KW.

A copy of our related Safety Evaluation is also enclosed. The Notice of Issuance will be included in the Commission's next regular biweekly Federal Register notice.

Sincerely, Charles M. Trammell, Senior Project Manager PrGject Directorate V Division of Reactor Projects -

III, IV, V and Special Projects

Enclosures:

1. Amendment No. 104 to License No. DPR-13
2.

Safety Evaluation cc w/enclosures:

See next page

Mr. Kenneth P. Baskin San Onofre Nuclear Generating Southern California Edison Company Station, Unit No. 1 cc Charles R. Kocher, Assistant Mr. Jack McGurk, Acting Chief General Counsel Radiological Health Branch James Beoletto, Esquire State Department of Health Southern California Edison Company Services Post Office Box 800 714 P Street, Office Bldg. 8 Rosemead, California 91770 Sacramento, California 95814 David R. Pigott Mr. Hans Kaspar, Executive Director Orrick, Herrington & Sutcliffe Marine Review Comittee, Inc.

600 Montgomery Street 531 Encinitas Boulevard, Suite 105 San Francisco, California 94111 Encinitas, California 92024 Mr. Robert G. Lacy Mr. Dennis M. Smith, Chief Manager, Nuclear Radiological Programs Division San Diego Gas & Electric Company Governor's Office of Emergency Svcs.

P. 0. Box 1831 State of California San Diego, California 92112 2800 Meadowview Road Sacramento, California 95832 Resident Inspector/San Onofre NPS U.S. NRC P. 0. Box 4329 San Clemente, California 92672 Mayor City of San Clemente San Clemente, California 92672 Chairman Board of Supervisors County of San Diego 1600 Pacific Highway Room 335 San Diego, California 92101 Director Energy Facilities Siting Division Energy Resources Conservation &

Development Commission 1516 - 9th Street Sacramento, California 95814 Regional Administrator, Region V U.S. Nuclear Regulatory Commission 1450 Maria Lane, Suite 210 Salnut Creek, California 94596