Emergency Response Data System
ML13151A165
Person / Time
Site: Calvert Cliffs Constellation icon.png
Issue date: 05/29/2013
From: Fick M
Constellation Energy Nuclear Group, Calvert Cliffs, EDF Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML13151A165 (79)


Text

Calvert Cliffs Nuclear Power Plant 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 CENG.

a joint venture of Conste0ftUon

  • eDF

-- Enefgy 0

CALVERT CLIFFS NUCLEAR POWER PLANT May 29, 2013 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

SUBJECT:

Document Control Desk Calvert Cliffs Nuclear Power Plant Unit No. 2; Docket No. 50-318 Emergency Response Data System The attached revision to the Emergency Response Data System (ERDS) Data Point Library for the Calvert Cliffs Nuclear Power Plant is provided pursuant to 10 CFR Part 50, Appendix E, Section VI.3.a.

The table below provides a brief summary of the changes:

Point Identifier Unit Description Status All points 2

n/a All points were modified to include a unit designator "2" X2433 2

Wind Speed Deleted X2367 2

Wind Direction Deleted 2WS60#15M 2

Wind Speed 60 Meter 15 Minute Avg New 2WD60# 1 5M 2

Wind Direction 60 Meter 15 Minute New Avg 2WS10#15M 2

Wind Speed 10 Meter 15 Minute Avg New 2WD10#15M 2

Wind Direction 10 Meter 15 Minute New Avg 2MMSDTASTB 2

Wind Stability Based on Delta Temp New (A) 2MMS S60STB 2

60 Meter Wind Stability - Sigma-Theta New The "before" and "after" ERDS Data Point Library sheets are attached.

Document Control Desk May 29, 2013 Page 2 Should you have questions regarding this matter, please contact Mr. Douglas E. Lauver at (410) 495-5219.

Very truly yours, Michael J. Fick Director-Emergency Planning MJF/CAN/bjd

Attachment:

Emergency Response Data System Data Point Library (76 pages) cc:

N. S. Morgan, NRC Resident Inspector, NRC W. M. Dean, NRC S. Gray, DNR

ATTACHMENT EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY (76 pages)

Calvert Cliffs Nuclear Power Plant, LLC May 29, 2013

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 1

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital; ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

7/5/1991 CC2 CC21 NI POWER RNG SPI109 LOG POWER NI WIDE RANGE LOG REACTOR PWR A

% POWER N/A IE-7 200 N/A N/A P

4 AVG OF THE TWO CLOSEST CHANNEL VALUES N/A N/A N/A N/A N/A N

N/A WIDE RANGE NUCLEAR INSTRUMENTATION PROVIDES A LOGARITHMIC INDICATION OF REACTOR POWER AS A PERCENT OF REACTOR POWER.

START UP RATE REACTOR TRIP IS GIVEN FROM WIDE RANGE NUCLEAR INSTRUMENTS BETWEEN THE RANGE OF I E-4% TO 15% POWER. THESE DETECTORS ARE FISSION CHAMBERS WHICH DO NOT GET DEENERGIZED DURING NORMAL POWER OPERATIONS.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 2

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog / Digital:

ENGR Units / Digital States; ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

7/511991 CC2 CC21 REC VES LEV SP2112 REACTOR VESSEL LEVEL REACTOR VESSEL WATER LEVEL A

INCHES N/A N/A N/A FAP N/A P

32 RE:USD (REFERENCE UINQ SYS DESC) 185,153,112,71,50,29,19, & 10" ABOVE FAP VOID DETECTED N/A N/A NIA N

N/A 8 HEATED JUNCTION THERMOCOUPLES (HJTC) ARE SPACED STRATEGICALLY IN A VACANT CEA SHROUD ASSEMBLY NEAR THE VICINITY OF ONE HOT LEG OUTLET NOZZLE. AS HJTC IS UNCOVERED THE LVL THAT THE REACTOR HEAD IS UNCOVERED IS INDICATED IN INCREMENTAL STEPS. THE 1ST HJTC IS 185" FROM TOP OF FUEL ALIGNMENT PLATE(FAP); 8TH HJTC IS 10" FROM FAP; 5TH HJTC IS 50" FROM FAP WHICH IS THE CENTER LINE OF THE HOT LEGS. HOW PROCESSED: WHEN LVL DECREASES A VOID IN THE HJTC WILL PROVIDE AN OUTPUT SIGNAL FOR THAT SPECIFIC HJTC POSITION.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 3

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

5/16/2002 CC2 CC21 TEMP CORE EX SP2113 CORE EXIT TEMP HIGHEST TEMP AT THE CORE EXIT A

DEGF N/A 40 2300 N/A N/A P

35 AVG EACH QUADRANTS PTS.:4 QUADS-4 AVGS N/A X >= 650 N/A N/A N/A N

N/A CORE EXIT THERMOCOUPLES ARE LOCATED AT THE TOP OF THE INCORE INSTRUMENT DETECTOR ASSEMBLIES, THERE ARE 35 FIXED INCORE DETECTORS LOCATED IN THE CORE WITHIN SELECTED FUEL ASSEMBLIES. THIS POINT IS THE HIGHEST AVG CET READING IN THE QUADRANT.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 4

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sans:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Lever:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/26/2003 CC2 CC21 SUB MARGIN SP3123 CORE SUBCOOLED MARGIN SATURATION TEMPERATURE-HIGH CET A

DEGF N/A 40 2300 N/A N/A P

35 AVG EACH QUADRANT'S PTS.:4 QUADS-4 AVGS N/A N/A N/A N/A N/A N

N/A CORE SUBCOOLED MARGIN IS CALCULATED BY THE SATURATION TEMPERATURE AS DETERMINED FROM PRESSURIZER PRESSURE MINUS THE CORE EXIT TEMP (SP2113).

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 5

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

9/30/2003 CC2 CC21 CORE FLOW F131A RCS TOTAL FLOW CH A TOTAL REACTOR COOLANT FLOW A

% FLOW 100% RX COOLANT FLOW= 370,000 GPM

-54.35 153.68 N/A N/A S

1 N/A N/A N/A N/A N/A N/A N

N/A REACTOR COOLANT FLOW IS DETERMINED BY THE DIP ACROSS THE STEAM GENERATORS. WHERE TOTAL FLOW IS THE SUM OF BOTH LOOP FLOWS.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 6

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/18/2003 C02 CC2I SG LEVEL 1/A SP3117A SG LEVEL LOOP 21 STEAM GENERATOR 21 WATER LEVEL A

INCHES N/A

-401.0 63.5 N/A 0" = 60" ABOVE THE FEED RING P

2 AVG OF TWO CHANNELS N/A X;'=50 X<=-170 N/A N/A N/A N

WET A LOW LEVEL REACTOR TRIP OCCURS AT -50" AS READ ON THE NARROW RANGE LEVEL DETECTOR. AFAS WILL ACTUATE AT -170" AS READ ON THE WIDE RANGE SIG LVL DETECTOR. POINT ID SP3117A IS A WIDE RANGE LVL INDICATOR.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 7

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog i Digital:

ENGR Units [ Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/18/2003 CC2 CC21 SG LEVEL 2/B SP31178 SG LEVEL LOOP 22 STEAM GENERATOR 22 WATER LEVEL A

INCHES N/A

-401.0 63.5 N/A 0" = 60" ABOVE THE FEED RING P

2 AVG OF TWO CHANNELS N/A X>=50 Xc=-170 N/A N/A N/A N

WET A LOW LEVEL REACTOR TRIP OCCURS AT -50" AS READ ON THE NARROW RANGE LEVEL DETECTOR. AFAS WILL ACTUATE AT -170" AS READ ON THE WIDE RANGE SIG LVL DETECTOR. POINT ID SP3117B IS A WIDE RANGE LVL INDICATOR.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 8

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for OP Transmitters:

Level Reference Leg:

Unique System

Description:

7/511991 CC2 CC21 SG PRESS 1/A SP3116A SG PRESSURE LOOP 21 STEAM GENERATOR 21 PRESSURE A

PSIA N/A 0

1200 N/A N/A P

2 AVG OF TWO CHANNELS N/A X>=985 Xc=703 N/A N/A N/A N

N/A REACTOR TRIP OCCURS AT 703# TO PREVENT EXCESSIVE HEAT EXTRACTIONS FROM HIGH STEAM FLOW DUE TO STM LINE RUPTURE OR COMP FAILURE.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 9

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

71511991 CC2 CC21 SG PRESS 2/B SP3116B SG PRESSURE LOOP 22 STEAM GENERATOR 22 PRESSURE A

PSIA N/A 0

1200 N/A N/A P

2 AVG OF TWO CHANNELS N/A X>=985 X<=703 N/A N/A N/A N

N/A REACTOR TRIP OCCURS AT 703# TO PREVENT EXCESSIVE HEAT EXTRACTIONS FROM HIGH STEAM FLOW DUE TO STM LINE RUPTURE OF COMP FAILURE.

PWR Data Point Library Reference File Report Date:

05-20-2013 Page :

10 Date:

Reactor Unit; Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

811511991 CC2 CC21 MN FD FL 1/A F1111%

FW FLOW TO STEAM GEN. 21 STM GEN 21 MAIN FEEDWATER FLOW A

KLB/HR N/A 0

6000 N/A N/A P

6 COMPLEX N/A N/A N/A N/A N/A Y

N/A THIS IS A TEMPERATURE COMPENSATED FEED. 2 STEAM DRIVEN MAIN FEED PUMPS EACH CAPABLE OF SUPPLYING FEED WATER EXCEEDING 50% FEED FLOW DEMAND. UPON A MAIN TURBINE TRIP FEED REG VALVES CLOSE AND FEED REG BYPASS VALVES ARE POSITIONED TO MAINTAIN 5% OF MAIN FEED WATER FLOW WHEN FEED PUMPS ARE RUNNING.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 11 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for OP Transmitters:

Level Reference Leg:

Unique System

Description:

8/15/1991 CC2 CC21 MN FO FL 2fB F1121%

FW FLOW TO STEAM GEN. 22 STM GEN 22 MAIN FEEDWATER FLOW A

KLB/HR N/A 0

6000 N/A N/A P

6 COMPLEX N/A N/A N/A N/A N/A Y

N/A THIS IS A TEMPERATURE COMPENSATED FEED. 2 STEAM DRIVEN MAIN FEED PUMPS EACH CAPABLE OF SUPPLYING FEED WATER EXCEEDING 50% FEED FLOW DEMAND. UPON A MAIN TURBINE TRIP FEED REG VALVES CLOSE AND FEED REG BYPASS VALVES ARE POSITIONED TO MAINTAIN 5% OF MAIN FEED WATER FLOW WHEN FEED PUMPS ARE RUNNING.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 12 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

71511991 CC2 CC21 AX FD FL 1/A SP3118A AUX FEED FLOW LOOP 21 STM GEN 21 AUXILIARY FW FLOW A

GPM N/A 0

1500 N/A N/A P

2 SUM:MTR N/A N/A DRIVEN & TURB DRIVEN PMPS DISCH N/A N/A NIA N

N/A THERE ARE 2 STEAM TURBINE DRIVEN PUMPS AND ONE ELECTRIC DRIVEN PUMP. THE TURBINE DRIVEN PUMPS DISCHARGE TO A COMMON HEADER FOR BOTH #21 & #22 STM GENS. THE MOTOR DRIVEN PUMP DISCHARGES TO A SEPARATE HEADER FOR BOTH #21 & #22 STM GENS, BOTH FLOW HEADERS COMBINE TO SUPPLY THE AUX FEED NOZZLE FOR EACH STM GEN. THE NORMAL SUPPLY TO AFW PUMP SUCTION IS FROM

  1. 12 CONDENSATE STORAGE TANK. ONLY 1 STEAM DRIVEN PUMP IS NORMALLY ALIGNED TO START.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 13 Date:

Reactor Unit:

Data Feeder; NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

7/5/1991 CC2 CC21 AX FO FL 2/B SP3118B AUX FEED FLOW LOOP 22 STM GEN 22 AUXILIARY FW FLOW A

GPM N/A 0

1500 N/A N/A P

2 SUM:MTR DRIVEN & TURB DRIVEN PMPS ODSCH N/A N/A N/A N/A N/A N

N/A THERE ARE 2 STEAM TURBINE DRIVEN PUMPS AND ONE ELECTRIC DRIVEN PUMP. THE TURBINE DRIVEN PUMPS DISCHARGE TO A COMMON HEADER FOR BOTH #21 & #22 STM GENS. THE MOTOR DRIVEN PUMP DISCHARGES TO A SEPARATE HEADER FOR BOTH #21 & #22 STM GENS.

BOTH FLOW HEADERS COMBINE TO SUPPLY THE AUX FEED NOZZLE FOR EACH STM GEN. THE NORMAL SUPPLY TO AFW PUMP SUCTION IS FROM

  1. 12 CONDENSATE STORAGE TANK. ONLY 1 STEAM DRIVEN PUMP IS NORMALLY ALIGNED TO START.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 14 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/18/2003 CC2 CC21 HL TEMP V/A SP0106A THOT LOOP 21 STM GEN 21 INLET TEMPERATURE A

DEGF N/A 50 700 N/A NIA P

2 AVG OF TWO CHANNELS N/A N/A N/A N/A NIA N/A N

N/A THOT IS THE COOLANT TEMPERATURE MEASURED AT THE INLET TO THE STEAM GEN. THOT PROVIDES INPUT TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TMILP) CIRCUIT FOR A TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 15 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/18/2003 CC2 CC21 HL TEMP 2/B SP01066 THOT LOOP 22 STM GEN 22 INLET TEMPERATURE A

DEGF N/A 50 700 N/A N/A P

2 AVG OF TWO CHANNELS N/A N/A N/A N/A N/A N

N/A THOT IS THE COOLANT TEMPERATURE MEASURED AT THE INLET TO THE STEAM GEN. THOT PROVIDES INPUT TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TMILP) CIRCUIT FOR A TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM.

PWR Data Point Library Reference File Reporl Date:

Page :

05-20-2013 16 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/1812003 CC2 CC21 CL TEMP 1/A SP3113A TCOLD LOOP 21 STM GEN 21 OUTLET TEMPERATURE A

DEOF N/A 50 700 N/A N/A P

3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)

N/A X'=560 Xc=504 N/A N/A N/A N

N/A THE ALARM/TRIP SET POINTS SUPPLIED ABOVE ARE SPDS ALARM SET POINTS. TCOLD PROVIDES CONTROL ROOM AND AUX SHUTDOWN PANEL INDICATION. TCOLD ALSO SUPPLIES SIGNALS TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP)

CIRCUIT FOR TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM. AS A DNS PARAMETER TCOLD IS REQUIRED TO BE LESS THAN 548 DEG WITH 4 REACTOR COOLANT PUMPS RUNNING.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 17 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog / Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NJ Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/18/2003 CC2 CC21 CL TEMP 2/8 SP3113B TCOLD LOOP 22 STM GEN 22 OUTLET TEMPERATURE A

DEGF N/A 50 700 N/A N/A P

3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)

N/A X"=560 X<=504 N/A N/A N/A N

N/A THE ALARM/TRIP SET POINTS SUPPLIED ABOVE ARE SPDS ALARM SET POINTS. TCOLD PROVIDES CONTROL ROOM AND AUX SHUTDOWN PANEL INDICATION. TCOLD ALSO SUPPLIES SIGNALS TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP)

CIRCUIT FOR TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM. AS A DNB PARAMETER TCOLD IS REQUIRED TO BE LESS THAN 548 DEG WITH 4 REACTOR COOLANT PUMPS RUNNING.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 18 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Log:

Unique System

Description:

7/511991 CC2 CC21 RCS PRESSURE SP312O PRESSURIZER PRESSURE REACTOR COOLANT SYSTEM PRESSURE A

PSIA N/A 0

4000 N/A N/A P

2 AVG OF TWO CHANNELS N/A X >= 2400 X <= 1740 N/A N/A N/A N

N/A REACTOR COOLANT PRESSURE IS THE AVERAGE OF 2 WIDE RANGE PRESSURIZER PRESSURE DETECTORS. THE SAFETY VALVES ARE SET TO OPEN AT 2500#. HIGH PRESSURE REACTOR TRIP OCCURS AT 2400#.

PORVS OPEN AT 2400 PSIA ON A REACTOR TRIP FROM HIGH PRESSURE.

SPRAY VALVE SETPOINT IS DEPENDENT ON CONTROLLER SETPOINT, BOTH SPRAY VALVES CLOSE AT 2300 PSIA. ESFAS ACTUATION IS iNITIATED AT 1740#.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 19 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units i Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

7/5/1991 CC2 CC21 PRZR LEVEL SP2109 PRESSURIZER LEVEL PRIMARY SYSTEM PRESSURIZER LEVEL A

INCHES N/A 0

360 RE:USD N/A P

2 AVG OF TWO CHANNELS N/A X>=300 X<=50 N/A N/A N/A N

WET PRESSURIZER LEVEL IS NORMALLY CONTROLLED IN A BAND BETWEEN 160" TO 216" DURING NORMAL POWER OPERATIONS. PRESSURIZER HEATERS CUTOUT AT A LEVEL OF 101" IN THE PRESSURIZER.

PRESSURIZER HEATERS WILL START TO BE UNCOVERED AT APPROX 84" OF INDICATED LEVEL. ZERO REFERENCE POINT: BOTTOM OF PRESSURIZER.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 20 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

7/5/1991 CC2 CC21 RCS CHG/MU SP1114 CHG PUMP FLOW PRIMARY SYSTEM CHARGING/MAKEUP F A

GPM N/A 0

150 N/A N/A P

4 RE:USD (REFERENCE UNIQ SYS DESC)

N/A N/A N/A N/A N/A N

N/A THERE ARE 3 CHARGING PUMPS THAT ARE RATED TO SUPPLY 44 GPM EACH TO THE RCS (REACTOR COOLANT SYSTEM). THE CHARGING FLOW IS DETERMINED FROM AN "A" CONTACT OF EACH CHARGING PUMP CIRCUIT BREAKER. SPDS DETERMINES THE FLOW BY SUMMING THE RATED FLOW OF EACH CHARGING PUMP THAT HAS IT'S CIRCUIT BREAKER CLOSED. CHARGING PUMP #23 CAN BE POWERED FROM ONE OF TWO BUSSES #21 OR #24. WHICH MUST BE MANUALLY SELECTED BY A "KIRK" KEY INTERLOCK SCHEME.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 21 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level; Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

6/30/1993 CC2 CC21 HP SI FLOW SP2115 HPSI FLOW HIGH PRESSURE SAFETY INJECTION F A

GPM N/A 0

1600 N/A N/A P

4 SUM OF FLOW LOOPS 21A, 21B, 22A, 228 N/A N/A N/A N/A N/A N

N/A 3 HIGH PRESSURE SAFETY INJECTION PUMPS DELIVER EMERGENCY COOLANT TO ALL FOUR COLD LEGS. SHUTOFF HEAD PRESSURE IS 1275 PSIA. ONLY TWO PUMPS WILL START. 22 HPSI IS MAINTAINED IN PULL TO LOCK. 2 INDEPENDENT SUCTION HEADERS SUPPLY WATER FROM THE REFUELING WATER TANK UNTIL THE TANK IS DOWN TO 10% FULL. AFTER THE RWT IS DOWN TO 10% FULL THE HPSI LINE IS CHANGED TO PROVIDE SUCTION FROM THE CONTAINMENT SUMP.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 22 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

7/5/1991 CC2 CC21 LP SI FLOW SP2116 LPSI FLOW LOW PRESSURE SAFETY INJECTION FL A

GPM N/A 0

8000 N/A N/A P

I INSTRUMENT VALUE N/A N/A N/A N/A NIA N/A N

NIA 2 LOW PRESSURE SAFETY INJECTION PUMPS SUPPLY LOW HEAD/HIGH VOLUME COOLANT TOTHE COLD LEGS. EACH LPSI PUMP TAKES A SUCTION OFF A SEPARATE HEADER FROM THE RWT. DURING RECIRCULATION MODE (APPROX 36 MIN AFTER A 0.8-A.) THE LPSI PUMPS ARE SHUT DOWN AND THE HPSI PUMPS TAKE SUCTION FROM THE CONTAIMENT SUMP TO RECIRCULATE WATER THROUGH THE SYSTEM.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 23 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog i Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sons:

Number of Sensors:

How Processed:

Sensor Locations Alarm ( Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

71511991 CC2 CC21 CTMNT SMP WR SP4112 CNTMT LEVEL CONTAINMENT SUMP WIDE RNG LEVEL A

INCHES N/A 0

120 N/A N/A P

2 AVG OF TWO CHANNELS NIA N/A N/A N/A N/A N

N/A THE CONTAINMENT EMERGENCY SUMP PROVIDES ADEQUATE NPSH TO BOTH HPSI AND CONTAINMENT SPRAY PUMPS WHEN IN THE RECIRCULATION MODE. TWO 24" DIAMETER RECIRC LINES SUPPLY WATER TO THE CONTAINMENT SPRAY AND SAFETY INJECTION SYSTEM, THE SUMP IS COVERED WITH A METAL GRATING TO PREVENT DEBRIS FROM ENTERING THE SUMP.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 24 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

8/15/1991 CC2 CC21 EFF GAS RAD R5415!

WR EFF MONITOR RADIOACTIVITY OF RELEASED GASSES A

UCI/SEC N/A 1E1 1E13 N/A N/A P

I INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N

N/A THE EFFLUENT GAS RADIATION MONITOR MEASURES MAIN VENT STACK EFFLUENT GROSS ACTIVITY. 3 CHANNELS: LOW, MEDIUM, & HIGH ARE USED TO PROVIDE AN OUTPUT TO A FOURTH PSEUDO CHANNEL. THE RANGE OF ACTIVITY DETECTED DETERMINES WHICH CHANNEL (L,M,H) IS SELECTED. THE OUTPUT OF THE FOURTH CHANNEL COMBINES GASIOUS FLOW WITH THE MEASURED ACTIVITY TO PROVIDE THE EFFECTIVE EFFLUENT GROSS ACTIVITY.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 25 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

8/1511991 CC2 CC21 EFF LIQ RAD SP6120 LIQUID WASTE RAD RADIOACTIVITY OF RELEASED LIQUID A

CPM N/A 1E1 1 E6 N/A N/A P

3 INSTRUMENT VALUE N/A X > 4E5 N/A N/A N/A N

N/A LIQUID WASTE PROCESSING MONITORS THE COMMON DISCHARGE HEADER FROM REACTOR. COOLANT WASTE PROCESSING AND MISC WASTE PROCESS. 29000 CPM WILL AUTOMATICALLY CLOSE 2 DISCHARGE VALVES 0o-CV-2201 & 0-CV-2202 TO ISOLATE FLOW TO THE CIRCULATION WATER DISCHARGE CONDUITS. ALARM LIMIT GIVEN IN ALARM/TRIP SET POINT IS THE SPDS ALARM LIMIT.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 26 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpolnts:

Ni Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

10/8/2002 CC2 CC21 COND AlE RAD SP6117 OFF GAS RAD CONDENSER AIR EJECTOR RADIOACTIV A

GPD N/A 0

250 N/A N/A P

4 INSTRUMENT VALUE N/A X > 5 N/A N/A N/A N

N/A THE CONDENSER AIR EJECTOR DISCHARGE MONITOR INCLUDES FOUR RADIATION SENSORS. ONE SENSOR IS INSTALLED IN THE SUCTION SIDE OF EACH OF THE FOUR CONDENSER AIR REMOVAL PUMPS. OUTPUT SIGNALS ARE DISPLAYED IN THE CONTROL ROOM. THE AUCTIONEERED HIGH SIGNAL IS CONVERTED FROM CPM TO GALLONS PER DAY (GPD)

AND IS USED AS AN EARLY INDICATION OF A PRIMARY TO SECONDARY LEAK THROUGH THE S/G TUBES.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 27 Date:

Reactor Unit-Data Feeder:

NRC EROS Parameter, Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

8/15/1991 CC2 CC21 CNTMNT RAD SP5121 CNTMT RAD RADIATION LEVEL IN CONTAINMENT A

R/HR N/A 1

1EO N/A N/A P

2 AVG OF TWO CHANNELS N/A X >= 3 N/A NIA N/A N

N/A THESE CONTAINMENT RADIATION MONITORS MEASURE GAMMA RADIATION LEVELS IN CONTAINMENT UNDER ACCIDENT CONDITIONS.

THE DETECTORS ARE LOCATED AT THE 73-FOOT LEVEL AND ARE PLACED NEAR THE PRESSURIZER AND #11 STEAM GEN.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 28 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

111311992 CC2 CC21 RCS LTDN RAD R52021 PROCESS RAD MONITOR RAD LEVEL OF RCS LETDOWN LINE A

KCPM N/A 1 E-2 1E3 N/A NIA P

1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N

N/A THE CVCS LTDN RAD MONITOR IS INSTALLED IN THE LET DOWN LINE TO MONITOR GROSS REACTOR COOLANT ACTIVITY INDICATING A POTENTIAL FUEL ELEMENT FAILURE.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 29 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

5/2911997 CC2 CC21 MAIN SL 1/A R5421!

MAIN STM RAD LP 21 STM GEN 21 STEAM LINE RAD LEVEL A

R/HR N/A 1 E-4 1 E4 N/A N/A P

1 INVERSE LOG OF INSTRUMENT VALUE NIA N/A N/A N/A N/A N

N/A THE MAIN STEAM EFFLUENT RADIATION DETECTORS MONITOR FOR NOBLE GASSES WITHIN THE MAIN STEAM LINE. THE MONITORS ARE LOCATED ON THE 27-FOOT LEVEL OF THE AUX 8UILDING IN THE MSIV ROOM.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 30 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

512911997 CC2 CC21 MAIN SL 2/B R5422!

MAIN STM RAD LP 22 STM GEN 22 STEAM LINE RAD LEVEL A

R/HR N/A I E-4 1E4 N/A N/A P

1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N

N/A THE MAIN STEAM EFFLUENT RADIATION DETECTORS MONITOR FOR NOBLE GASSES WITHIN THE MAIN STEAM LINE. THE MONITORS ARE LOCATED ON THE 27-FOOT LEVEL OF THE AUX BUILDING IN THE MSIV ROOM.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 31 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

11/311992 CC2 CC21 SG BD RAD 1A R4014!

STM GEN BLOWDOWN ACTIVITY STM GEN 21 BLOWDOWN RAD LEVEL A

KCPM N/A 1 E-2 1E8 N/A N/A P

1 INVERSE LOG OF INSTRUMENT VALUE N/A 1000 CPM N/A N/A N/A N

N/A THIS DETECTOR MONITORS A SMALL PORTION OF THE STM GEN BLOWDOWN TO PROVIDE OPERATORS WITH AN EARLY INDICATION OF STM GEN U-TUBE LEAKAGE. ACTUATION OF THE HIGH ALARM AUTOMATICALLY SHUT THE SURFACE BLOWDOWN AND THE BOTTOM BLOWDOWN ISOLATION VALVES. OF BOTH #11 & #12 STEAM GENERATORS THIS MONITOR IS IN THE LINE OF THE BLOWDOWN TANK AND IS COMMON TO BOTH STM GEN.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 32 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Atarm / Trip Setpoints:

Ni Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

71511991 CC2 CC21 CTMNT PRESS SP4110 CNTMT PRESSURE CONTAINMENT PRESSURE A

PSIG N/A

-6 150 N/A N/A P

3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)

N/A X -= 2.8 N/A N/A N/A N

N/A THERE ARE A TOTAL OF 3 CONTAINMENT PRESSURE INDICATORS. TWO PROVIDE WIDE RANGE PRESSURE INDICATION 0-150 PSIG FOR POST ACCIDENT MONITORING. THE THIRD INDICATOR IS A NARROW RANGE INDICATION -5 TO +5 PSIG WHICH PROVIDES CONTAINMENT DIFFERENTIAL PRESSURE. ACTUATIONS OCCUR: CIS @ 2.8 PSIG, CSAS @

4.25 PSIG; SIAS @ 2.8 PSIG; RPS @ 2.4 PSIG.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 33 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

715/1991 CC2 CC21 CTMNT TEMP SP4[11 CNTMT TEMPERATURE CONTAINMENT TEMPERATURE A

DEGF N/A 50 300 N/A N/A P

2 AVG OF TWO CHANNELS N/A X >= 160 N/A N/A N/A N

N/A THERE ARE 2 CONTAINMENT TEMP DETECTORS. ONE MEASURES DOME TEMP, ANOTHER MEASURES THE REACTOR CAVITY TEMP. BOTH OF THESE PROVIDE INDICATION TO THE CONTROL ROOM OPERATORS.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 34 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

311/1997 CC2 CC21 BWST LEVEL SP2RWLVL REFUELING WATER TANK LEVEL BORATED WATER STORAGE TANK LEVEL A

FEET N/A 0

40 RE:USD RE:USD (REFERENCE UNIQ SYS DESC)

P 2

N/A N/A N/A N/A N/A N/A N

WET THE REFUELING WATER TANK SUPPLIES 2300-2700 PPM BORATED WATER TO THE SAFETY INJECTION SYSTEM AND ALSO SUPPLIES WATER FOR USE DURING REFUELING. TANK CAPACITY IS 420.000 GALS. AT 2.5 FEET THE SAFETY INJECTION LINE-UP IS SWITCHED TO THE RECIRCULATION MODE. THIS LEVEL IS EQUAL TO APPROK 10% OF TANK VOLUME.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 35 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic f Condition

Description:

Analog / Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sons:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

Ni Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters; Level Reference Leg:

Unique System

Description:

2/24/1994 CC2 CC21 WIND SPEED X2433 WIND SPEED (DELETED)

WIND SPEED AT REACTOR SITE A

MPH N/A 0

100 NIA N/A S

1 N/A N/A N/A N/A NIA LOW N

N/A WIND SPEED INDICATION TO PLANT COMPUTER IS SUPPLIED FROM THE BACK-UP MET TOWER LOCATED ON SITE.

THIS POINT WAS DELETED DUE TO REMOVAL OF METEOROLOGICAL INFORMATION FROM THE UNIT TWO PLANT COMPUTER.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 36 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

2/24/1994 CC2 CC21 WIND DIR X2367 WIND DIRECTION (DELETED)

WIND DIRECTION AT REACTOR SITE A

DEG N/A 0

1080 NIA N/A S

1 N/A N/A N/A N/A N/A 0 DEGREES (NORTH)

N N/A WIND DIRECTION TO PLANT COMPUTER IS SUPPLIED FROM THE BACK-UP MET TOWER ON SITE.

THIS POINT WAS DELETED DUE TO REMOVAL OF METEOROLOGICAL DATA FROM THE UNIT TWO PLANT COMPUTER.

PWR Data Point Library Reference File Report Date:

05-20-2013 Page :

1 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power SUpply Cut-Off Power Level:

Nl Detector Power Supply Turn-on Power Level:

instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

11/4/1992 C.C2 CC21 NI POWER RNG 2SP109 LOG POWER NI WIDE RANGE LOG REACTOR PWR A

% POWER N/A 1E-7 200 N/A N/A P

4 AVG OF THE TWO CLOSEST CHANNEL VALUES N/A N/A N/A N/A N/A N

N/A WIDE RANGE NUCLEAR INSTRUMENTATION PROVIDES A LOGARITHMIC INDICATION OF REACTOR POWER AS A PERCENT OF REACTOR POWER.

START UP RATE REACTOR TRIP IS GIVEN FROM WIDE RANGE NUCLEAR INSTRUMENTS BETWEEN THE RANGE OF IE-4% TO IS% POWER. THESE DETECTORS ARE FISSION CHAMBERS WHICH DO NOT GET DEENERGIZED DURING NORMAL POWER OPERATIONS.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 2

Date:

Reactor Unit:

Data Feeder; NRC EROS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion; Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3112/2007 CC2 CC21 REC VES LEV 2SP2112 REACTOR VESSEL LEVEL REACTOR VESSEL WATER LEVEL A

INCHES N/A N/A N/A FAP N/A P

32 RE:USD (REFERENCE UNIQUE SYS DESC) 160,151.112,71,50,29,19, & 10' ABOVE FAP VOID DETECTED N/A N/A N/A N

N/A 8 HEATED JUNCTION THERMOCOUPLES (HJTC) ARE SPACED STRATEGICALLY IN A VACANT CEA SHROUD ASSEMBLY NEAR THE VICINITY OF ONE HOT LEG OUTLET NOZZLE. AS HJTC IS UNCOVERED THE LVL THAT THE REACTOR HEAD IS UNCOVERED IS INDICATED IN INCREMENTAL STEPS. THE 1ST HJTC IS 160" FROM TOP OF FUEL ALIGNMENT PLATE(FAP); 8TH HJTC IS 10" FROM FAP; 5TH HJTC IS 50" FROM FAP WH(CH IS THE CENTER LINE OF THE HOT LEGS. HOW PROCESSED: WHEN LVL DECREASES A VOID IN THE HJTC WILL PROVIDE AN OUTPUT SIGNAL FOR THAT SPECIFIC HJTC POSITION.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 3

Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

5116/2002 CC2 CC21 TEMP CORE EX 2SP2113 CORE EXIT TEMP HIGHEST TEMP AT THE CORE EXIT A

DEGF N/A 40 2300 N/A N/A P

35 AVG EACH QUADRANT'S PTS.:4 QUADS-4 AVGS N/A X ;= 650 N/A N/A N/A N

N/A CORE EXIT THERMOCOUPLES ARE LOCATED AT THE TOP OF THE INCORE INSTRUMENT DETECTOR ASSEMBLIES. THERE ARE 35 FIXED INCORE DETECTORS LOCATED IN THE CORE WITHIN SELECTED FUEL ASSEMBLIES. THIS POINT IS THE HIGHEST AVG CET READING IN THE QUADRANT.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 4

Date; Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/2612003 CC2 CC21 SUB MARGIN 2SP3123 CORE SUBCOOLED MARGIN SATURATION TEMPERATURE-HIGH CET A

DEGF N/A 40 2300 N/A N/A P

35 AVG EACH QUADRANT'S PTS.:4 QUADS-4 AVGS N/A N/A N/A N/A N/A N

N/A CORE SUBCOOLED MARGIN IS CALCULATED BY THE SATURATION TEMPERATUREAS DETERMINED FROM PRESSURIZER PRESSURE MINUS THE CORE EXiT TEMP (SP2113).

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 5

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

9/30/2003 CC2 CC21 CORE FLOW 2F131A RCS TOTAL FLOW CH A TOTAL REACTOR COOLANT FLOW A

% FLOW 100% RX COOLANT FLOW = 370.000 GPM

-54.35 153.68 N/A N/A S

1 N/A N/A N/A N/A N/A N/A N

N/A REACTOR COOLANT FLOW IS DETERMINED BY THE DfP ACROSS THE STEAM GENERATORS. WHERE TOTAL FLOW IS THE SUM OF BOTH LOOP FLOWS.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 6

Date:

Reactor Unit:

Date Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

4/18/2006 CC2 CC21 SG LEVEL 1/A 2SP3117A SG LEVEL LOOP 21 STEAM GENERATOR 21 WATER LEVEL A

INCHES N/A

-401.0 63.5 N/A 0" = 40" ABOVE THE FEED RING P

2 AVG OF TWO CHANNELS N/A X>=50 Xc=-170 N/A N/A N/A N

WET A LOW LEVEL REACTOR TRIP OCCURS AT -50" AS READ ON THE NARROW RANGE LEVEL DETECTOR. AFAS WILL ACTUATE AT -170" AS READ ON THE WIDE RANGE S/G LVL DETECTOR. POINT ID SP3117A IS A WIDE RANGE LVL INDICATOR.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 7

Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

4/18/2006 CC2 CC21 SG LEVEL 2/B 2SP3117B SG LEVEL LOOP 22 STEAM GENERATOR 22 WATER LEVEL A

INCHES N/A

-401.0 63.5 N/A 0" = 40" ABOVE THE FEED RING P

2 AVG OF TWO CHANNELS N/A X>=50 Xc=-170 N/A N/A N/A N

WET A LOW LEVEL REACTOR TRIP OCCURS AT -50" AS READ ON THE NARROW RANGE LEVEL DETECTOR. AFAS WILL ACTUATE AT -170" AS READ ON THE WIDE RANGE S/G LVL DETECTOR. POINT ID SP3117B IS A WIDE RANGE LVL INDICATOR,

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 8

Date; Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic f Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters; Level Reference Leg:

Unique System

Description:

11/4/1992 CC2 CC21 SG PRESS 1/A 2SP311SA SG PRESSURE LOOP 21 STEAM GENERATOR 21 PRESSURE A

PSIA N/A 0

1200 N/A N/A P

2 AVG OF TWO CHANNELS N/A X>=985 X<=703 N/A N/A N/A N

N/A REACTOR TRIP OCCURS AT 703# TO PREVENT EXCESSIVE HEAT EXTRACTIONS FROM HIGH STEAM FLOW DUE TO STM LINE RUPTURE OR COMP FAILURE-

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 9

Date:

Reactor Unit:

Data Feeder; NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

11/4/1992 CC2 CC21 SG PRESS 2/1 2SP31168 SG PRESSURE LOOP 22 STEAM GENERATOR 22 PRESSURE A

PSIA N/A 0

1200 N/A N/A P

2 AVG OF TWO CHANNELS N/A X>=985 X<= 703 N/A N/A N/A N

N/A REACTOR TRIP OCCURS AT 703# TO PREVENT EXCESSIVE HEAT EXTRACTIONS FROM HIGH STEAM FLOW DUE TO STM LINE RUPTURE OF COMP FAILURE.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 10 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

11/4/1992 CC2 CC21 MN FD FL 1/A 2F1111%

FW FLOW TO STEAM GEN. 21 STM GEN 21 MAIN FEEDWATER FLOW A

KLB/HR N/A 0

6000 N/A N/A P

6 COMPLEX N/A N/A N/A N/A N/A Y

N/A THIS IS A TEMPERATURE COMPENSATED FEED. 2 STEAM DRIVEN MAIN FEED PUMPS EACH CAPABLE OF SUPPLYING FEED WATER EXCEEDING 50% FEED FLOW DEMAND, UPON A MAIN TURBINE TRIP FEED REG VALVES CLOSE AND FEED REG BYPASS VALVES ARE POSITIONED TO MAINTAIN 5% OF MAIN FEED WATER FLOW WHEN FEED PUMPS ARE RUNNING.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 11 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic ) Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints; Ni Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

1114/1992 CC2 CC21 MN FD FL 2/B 2F1121%

FW FLOW'TO STEAM GEN. 22 STM GEN 22 MAIN FEEDWATER FLOW A

KLB/HR N/A 0

6000 N/A N/A COMPLEX N/A N/A N/A N/A N/A N/A THIS IS A TEMPERATURE COMPENSATED FEED. 2 STEAM DRIVEN MAIN FEED PUMPS EACH CAPABLE OF SUPPLYING FEED WATER EXCEEDING 50% FEED FLOW DEMAND. UPON A MAIN TURBINE TRIP FEED REG VALVES CLOSE AND FEED REG BYPASS VALVES ARE POSITIONED TO MAINTAIN 5% OF MAIN FEED WATER FLOW WHEN FEED PUMPS ARE RUNNING.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 12 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-an Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

11/4/1992 CC2 CC21 AX FD FL 1/A 2SP3118A AUX FEED FLOW LOOP 21 STM GEN 21 AUXILIARY FW FLOW A

GPM N/A 0

1500 NIA N/A P

2 SUM:MTR DRIVEN & TURB DRIVEN PMPS DISCH N/A N/A N/A N/A N/A N

N/A THERE ARE 2 STEAM TURBINE DRIVEN PUMPS AND ONE ELECTRIC DRIVEN PUMP. THE TURBINE DRIVEN PUMPS DISCHARGE TO A COMMON HEADER FOR BOTH #21 & #22 STM GENS. THE MOTOR DRIVEN PUMP DISCHARGES TO A SEPARATE HEADER FOR BOTH #21 & #22 STM GENS.

BOTH FLOW HEADERS COMBINE TO SUPPLY THE AUX FEED NOZZLE FOR EACH STM GEN. THE NORMAL SUPPLY TO AFW PUMP SUCTION IS FROM

  1. 12 CONDENSATE STORAGE TANK. ONLY 1 STEAM DRIVEN PUMP IS NORMALLY ALIGNED TO START.

(4 PWR Data Point Library Reference File Reporl Date:

Page :

05-20-2013 13 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

111411992 CC2 CC21 AX FD FL 2/B 2SP3118B AUX FEED FLOW LOOP 22 STM GEN 22 AUXILIARY FW FLOW A

GPM N/A 0

1500 N/A NIA P

2 SUM:MTR DRIVEN & TURS DRIVEN PMPS DESCH N/A N/A N/A N/A N/A N

N/A THERE ARE 2 STEAM TURBINE DRIVEN PUMPS AND ONE ELECTRIC DRIVEN PUMP. THE TURBINE DRIVEN PUMPS DISCHARGE TO A COMMON HEADER FOR BOTH #21 & #22 STM GENS. THE MOTOR DRIVEN PUMP DISCHARGES TO A SEPARATE HEADER FOR BOTH #21 & #22 STM GENS.

BOTH FLOW HEADERS COMBINE TO SUPPLY THE AUX FEED NOZZLE FOR EACH STM GEN. THE NORMAL SUPPLY TO AFW PUMP SUCTION IS FROM

  1. 12 CONDENSATE STORAGE TANK. ONLY 1 STEAM DRIVEN PUMP IS NORMALLY ALIGNED TO START.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 14 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/1812003 CC2 CC21 HL TEMP 1/A 2SP0106A THOT LOOP 21 STM GEN 21 INLET TEMPERATURE A

DEGF N/A 50 700 N/A N/A P

2 AVG OF TWO CHANNELS N/A N/A N/A N/A N/A N

N/A THOT IS THE COOLANT TEMPERATURE MEASURED AT THE INLET TO THE STEAM GEN. THOT PROVIDES INPUT TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGINILOW PRESSURE (TM/LP) CIRCUIT FOR A TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 15 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/18/2003 CC2 CC21 HL TEMP 2/B 2SPOI06B THOT LOOP 22 STM GEN 22 INLET TEMPERATURE A

DEGF N/A 50 700 NIA N/A P

2 AVG OF TWO CHANNELS N/A N/A N/A N/A N/A N

N/A THOT IS THE COOLANT TEMPERATURE MEASURED AT THE INLET TO THE STEAM GEN, THOT PROVIDES INPUT TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGINJLOW PRESSURE (TMILP) CIRCUIT FOR A TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 16 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units / Digital States; ENGR Units Conversion; Minimum Instrument Range:

Maximum Instrument Range; Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

Ni Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/1812003 CC2 CC21 CL TEMP 1/A 2SP3113A TCOLD LOOP 21 STM GEN 21 OUTLET TEMPERATURE A

DEGF N/A 5o 700 N/A N/A P

3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)

N/A X>=560 X<-504 N/A N/A N/A N

N/A THE ALARM/TRIP SET POINTS SUPPLIED ABOVE ARE SPDS ALARM SET POINTS. TCOLD PROVIDES CONTROL ROOM AND AUX SHUTDOWN PANEL INDICATION. TCOLD ALSO SUPPLIES SIGNALS TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TMJLP)

CIRCUIT FOR TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM, AS A DNS PARAMETER TCOLD IS REQUIRED TO BE LESS THAN 548 DEG WITH 4 REACTOR COOLANT PUMPS RUNNING.

PWR Data Point Library Reference File Report Date :

Page :

05-20-2013 17 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/18/2003 CC2 CC21 CL TEMP 2/B 2SP3113B TOOLD LOOP 22 STM GEN 22 OUTLET TEMPERATURE A

DEGF N/A 50 700 N/A N/A P

3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)

N/A X>=560 X<=504 N/A N/A N/A N

N/A THE ALARM/TRIP SET POINTS SUPPLIED ABOVE ARE SPDS ALARM SET POINTS, TCOLD PROVIDES CONTROL ROOM AND AUX SHUTDOWN PANEL INDICATION. TCOLD ALSO SUPPLIES SIGNALS TO THE SUBCOOLED MARGIN MONITOR AND THE THERMAL MARGIN/LOW PRESSURE (TM/LP)

CIRCUIT FOR TOTAL POWER CALCULATION IN THE REACTOR PROTECTION SYSTEM. AS A DNB PARAMETER TOOLD IS REQUIRED TO BE LESS THAN 548 DEG WITH 4 REACTOR COOLANT PUMPS RUNNING.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 18 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range; Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level; Instrument Failure Mode:

Temperature Compensation for OP Transmitters:

Level Reference Leg:

Unique System

Description:

1114/1992 CC2 CC21 RCS PRESSURE 2SP3120 PRESSURIZER PRESSURE REACTOR COOLANT SYSTEM PRESSURE A

PSIA N/A 0

4000 N/A N/A P

2 AVG OF TWO CHANNELS N/A X = 2400 X - 1740 N/A N/A N/A N

NIA REACTOR COOLANT PRESSURE IS THE AVERAGE OF 2 WIDE RANGE PRESSURIZER PRESSURE DETECTORS. THE SAFETY VALVES ARE SET TO OPEN AT 2500#. HIGH PRESSURE REACTOR TRIP OCCURS AT 2400#.

PORVS OPEN AT 2400 PSIA ON A REACTOR TRIP FROM HIGH PRESSURE.

SPRAY VALVE SETPOINT IS DEPENDENT ON CONTROLLER SETPOINT.

BOTH SPRAY VALVES CLOSE AT 2300 PSLA. ESFAS ACTUATION IS INITIATED AT 1740#.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 19 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

11/4/1992 CC2 CC21 PRZR LEVEL 2SP2109 PRESSURIZER LEVEL PRIMARY SYSTEM PRESSURIZER LEVEL A

INCHES N/A 0

360 RE:USD N/A P

2 AVG OF TWO CHANNELS N/A X"=300 X <=50 N/A N/A N/A N

WET PRESSURIZER LEVEL IS NORMALLY CONTROLLED IN A BAND BETWEEN 160" TO 216" DURING NORMAL POWER OPERATIONS. PRESSURIZER HEATERS CUTOUT AT A LEVEL OF 101" IN THE PRESSURIZER.

PRESSURIZER HEATERS WILL START TO BE UNCOVERED AT APPROX 84" OF INDICATED LEVEL. ZERO REFERENCE POINT: BOTTOM OF PRESSURIZER.

PWR Data Point Library Reference File Report Date:

05-20-2013 Page:

20 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

111411992 CC2 CC21 RCS CHGIMU 2SP1 114 CHG PUMP FLOW PRIMARY SYSTEM CHARGING/MAKEUP F A

GPM N/A 0

150 N/A N/A P

4 RE:USD (REFERENCE UNIQ SYS DESC)

N/A N/A N/A N/A N/A N

N/A THERE ARE 3 CHARGING PUMPS THAT ARE RATED TO SUPPLY 44 GPM EACH TO THE RCS (REACTOR COOLANT SYSTEM). THE CHARGING FLOW IS DETERMINED FROM AN "A" CONTACT OF EACH CHARGING PUMP CIRCUIT BREAKER, SPOS DETERMINES THE FLOW BY SUMMING THE RATED FLOW OF EACH CHARGING PUMP THAT HAS IT'S CIRCUIT BREAKER CLOSED. CHARGING PUMP #23 CAN BE POWERED FROM ONE OF TWO BUSSES #21 OR #24-WHICH MUST BE MANUALLY SELECTED BY A "KIRK" KEY INTERLOCK SCHEME.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 21 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

613011993 CC2 CC21 HP SI FLOW 2SP2115 HPSI FLOW HIGH PRESSURE SAFETY INJECTION F A

GPM N/A 0

1600 N/A N/A P

4 SUM OF FLOW LOOPS 21A, 21B, 22A, 22B N/A N/A N/A N/A N/A N

N/A 3 HIGH PRESSURE SAFETY INJECTION PUMPS DELIVER EMERGENCY COOLANT TO ALL FOUR COLD LEGS. SHUTOFF HEAD PRESSURE IS 1275 PSIA. ONLY IWO PUMPS WILL START. 22 HPSI IS MAINTAINED IN PULL TO LOCK. 2 INDEPENDENT SUCTION HEADERS SUPPLY WATER FROM THE REFUELING WATER TANK UNTIL THE TANK IS DOWN TO 10% FULL. AFTER THE RWT IS DOWN TO 10% FULL THE HPSI LINE IS CHANGED TO PROVIDE SUCTION FROM THE CONTAINMENT SUMP.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 22 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode; Temperature Compensation for OP Transmitters:

Level Reference Leg:

Unique System

Description:

11/4/1992 CC2 CC21 LP SI FLOW 2SP2116 LPSI FLOW LOW PRESSURE SAFETY INJECTION FL A

GPM N/A 0

8000 N/A N/A P

I INSTRUMENT VALUE N/A N/A N/A N/A N/A N

N/A 2 LOW PRESSURE SAFETY INJECTION PUMPS SUPPLY LOW HEAD/HIGH VOLUME COOLANT TO THE COLD LEGS. EACH LPSI PUMP TAKES A SUCTION OFF A SEPARATE HEADER FROM THE RWT. DURING RECIRCULATION MODE (APPROX 36 MIN AFTER A D.B.A.) THE LPSI PUMPS ARE SHUT DOWN AND THE HPSI PUMPS TAKE SUCTION FROM THE CONTAIMENT SUMP TO RECIRCULATE WATER THROUGH THE SYSTEM.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 23 Date:

Reactor Unit; Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode; Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

11/4/1992 CC2 CC21 CTMNT SMP WR 2SP4112 CNTMT LEVEL CONTAINMENT SUMP WIDE RNG LEVEL A

INCHES N/A 0

120 N/A N/A P

2 AVG OF TWO CHANNELS N/A N/A N/A N/A N/A N

N/A THE CONTAINMENT EMERGENCY SUMP PROVIDES ADEQUATE NPSH TO BOTH HPSI AND CONTAINMENT SPRAY PUMPS WHEN IN THE RECIRCULATION MODE. TWO 24" DIAMETER RECIRC LINES SUPPLY WATER TO THE CONTAINMENT SPRAY AND SAFETY INJECTION SYSTEM.

THE SUMP IS COVERED WITH A METAL GRATING TO PREVENT DEBRIS FROM ENTERING THE SUMP.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 24 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

114/41992 CC2 CC21 EFF GAS RAD 2R5415!

WR EFF MONITOR RADIOACTIVITY OF RELEASED GASSES A

UCI/SEC N/A 1El IE13 N/A N/A P

1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N

N/A THE EFFLUENT GAS RADIATION MONITOR MEASURES MAIN VENT STACK EFFLUENT GROSS ACTIVITY. 3 CHANNELS: LOW, MEDIUM, & HIGH ARE USED TO PROVIDE AN OUTPUT TO A FOURTH PSEUDO CHANNEL. THE RANGE OF ACTIVITY DETECTED DETERMINES WHICH CHANNEL (L,M,H) IS SELECTED. THE OUTPUT OF THE FOURTH CHANNEL COMBINES GASIOUS FLOW WITH THE MEASURED ACTIVITY TO PROVIDE THE EFFECTIVE EFFLUENT GROSS ACTIVITY.

PWR Data Point Library Reference File Report Date:

Page:.

05-20-2013 25 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog / Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

4/18/2006 CC2 CC21 EFF LIQ RAD 2SP6120 LIQUID WASTE RAD RADIOACTIVfTY OF RELEASED LIQUID A

CPM N/A 1E1 1E6 NIA N/A P

3 INSTRUMENT VALUE N/A X >= 4E5 N/A N/A N/A N

N/A LIQUID WASTE PROCESSING MONITORS THE COMMON DISCHARGE HEADER FROM REACTOR COOLANT WASTE PROCESSING AND MISC WASTE PROCESS. 50000 CPM WILL AUTOMATICALLY CLOSE 2 DISCHARGE VALVES 0-CV-2201 & 0-CV-2202 TO ISOLATE FLOW TO THE CIRCULATION WATER DISCHARGE CONDUITS. ALARM LIMIT GIVEN IN ALARM/TRIP SET POINT IS THE SPDS ALARM LIMIT.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 26 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range; Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for OP Transmitters:

Level Reference Leg:

Unique System

Description:

10/812002 CC2 CC21 COND AlE RAD 2SP6117 OFF GAS RAD CONDENSER AIR EJECTOR RAD1OACTIV A

GPD N/A 0

250 N/A N/A P

4 INSTRUMENT VALUE N/A X >= 5 N/A N/A N/A N

N/A THE CONDENSER AIR EJECTOR DISCHARGE MONITOR INCLUDES FOUR RADIATION SENSORS. ONE SENSOR IS INSTALLED IN THE SUCTION SIDE OF EACH OF THE FOUR CONDENSER AIR REMOVAL PUMPS. OUTPUT SIGNALS ARE DISPLAYED IN THE CONTROL ROOM. THE AUCTIONEERED HIGH SIGNAL IS CONVERTED FROM CPM TO GALLONS PER DAY (GPD)

AND IS USED AS AN EARLY INDICATION OF A PRIMARY TO SECONDARY LEAK THROUGH THE S/G TUBES.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 27 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units i Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

4/18/2006 CC2 CC21 CNTMNT RAD 2SP6121 CNTMT RAD RADIATION LEVEL IN CONTAINMENT A

R/HR N/A 1

1E8 N/A N/A P

2 AVG OF TWO CHANNELS N/A X >= 3 N/A N/A N/A N

N/A THESE CONTAINMENT RADIATION MONITORS MEASURE GAMMA RADIATION LEVELS iN CONTAINMENT UNDER ACCIDENT CONDITIONS.

THE DETECTORS ARE LOCATED AT THE 73-FOOT LEVEL AND ARE PLACED NEAR THE PRESSURIZER AND #21 STEAM GEN.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 28 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

1113/1992 CC2 CC21 RCS LTDN RAD 2R52021 PROCESS RAD MONITOR RAD LEVEL OF RCS LETDOWN LINE A

KCPM NIA 1E-2 1E3 N/A N/A P

1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N

N/A THE OVCS LTDN RAD MONITOR IS INSTALLED IN THE LET DOWN LINE TO MONITOR GROSS REACTOR COOLANT ACTIVITY INDICATING A POTENTIAL FUEL ELEMENT FAILURE.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 29 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic ( Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

5/29/1997 CC2 CC21 MAIN SL 1/A 2R54211 MAIN STM RAD LP 21 STM GEN 21 STEAM LINE RAD LEVEL A

R/HR N/A 1 E-4 1E4 N/A N/A P

1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N

N/A THE MAIN STEAM EFFLUENT RADIATION DETECTORS MONITOR FOR NOBLE GASSES WITHIN THE MAIN STEAM LINE. THE MONITORS ARE LOCATED ON THE 27-FOOT LEVEL OF THE AUX BUILDING IN THE MSIV ROOM.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 30 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

Nf Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

5/2911997 CC2 CC21 MAIN SL 2/B 2R5422!

MAIN STM RAD LP 22 STM GEN 22 STEAM LINE RAD LEVEL A

R/HR N/A 1 E-4 1E4 N/A N/A P

1 INVERSE LOG OF INSTRUMENT VALUE N/A N/A N/A N/A N/A N

N/A THE MAIN STEAM EFFLUENT RADIATION DETECTORS MONITOR FOR NOBLE GASSES.WITHIN THE MAIN STEAM LINE, THE MONITORS ARE LOCATED ON THE 27-FOOT LEVEL OF THE AUX BUILDING IN THE MSIV ROOM.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 31 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for OP Transmitters:

Level Reference Leg:

Unique System

Description:

4118/2006 CC2 CC21 SG BD RAD 1A 2R4014!

STM GEN BLOWDOWN ACTIVITY STM GEN 21 BLOWDOWN RAD LEVEL A

CPM N/A 1El 1E6 N/A N/A P

1 INVERSE LOG OF INSTRUMENT VALUE N/A 1000 CPM NIA N/A N/A N

N/A THIS DETECTOR MONITORS A SMALL PORTION OF THE STM GEN BLOWDOWN TO PROVIDE OPERATORS WITH AN EARLY INDICATION OF STM GEN U-TUBE LEAKAGE. ACTUATION OF THE HIGH ALARM AUTOMATICALLY SHUT THE SURFACE SLOWDOWN AND THE BO1-OM SLOWDOWN ISOLATION VALVES. OF BOTH #11 & #12 STEAM GENERATORS THIS MONITOR IS IN THE LINE OF THE SLOWDOWN TANK AND IS COMMON TO BOTH STM GEN.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 32 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpolnts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

111411992 CC2 CC21 CTMNT PRESS 2SP4110 CNTMT PRESSURE CONTAINMENT PRESSURE A

PSIG N/A

-5 150 N/A NIA P

3 AVG OF TWO CHNLS (AUCTIONEERED:WR OR NR)

N/A X >= 2.8 N/A N/A N/A N

NIA THERE ARE A TOTAL OF 3 CONTAINMENT PRESSURE INDICATORS, TWO PROVIDE WIDE RANGE PRESSURE INDICATION 0-150 PSIG FOR POST ACCIDENT MONITORING, THE THIRD INDICATOR IS A NARROW RANGE INDICATION -5 TO +5 PSIG WHICH PROVIDES CONTAINMENT DIFFERENTIAL PRESSURE. ACTUATIONS OCCUR: CIS @ 2.8 PSIG; CSAS @

4.25 PSIG; SIAS @ 2.8 PSIG; RPS @ 2.4 PSIG.

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 33 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip SetpoInts:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

11/4/1992 CC2 CC21 CTMNT TEMP 2SP4111 CNTMT TEMPERATURE CONTAINMENT TEMPERATURE A

DEGF N/A 50 300 NIA N/A P

2 AVG OF TWO CHANNELS N/A X >= 160 N/A N/A N/A N

N/A THERE ARE 2 CONTAINMENT TEMP DETECTORS. ONE MEASURES DOME TEMP. ANOTHER MEASURES THE REACTOR CAVITY TEMP. BOTH OF THESE PROVIDE INDICATION TO THE CONTROL ROOM OPERATORS.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 34 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

3/111997 CC2 CC21 BWST LEVEL 2SP2RWLVL REFUELING WATER TANK LEVEL BORATED WATER STORAGE TANK LEVEL A

FEET N/A 0

40 RE:USD RE:USD (REFERENCE UNIQ SYS DESC)

P 2

N/A N/A N/A N/A N/A N/A N

WET THE REFUELING WATER TANK SUPPLIES 2300-2700 PPM BORATED WATER TO THE SAFETY INJECTION SYSTEM AND ALSO SUPPLIES WATER FOR USE DURING REFUEUNG. TANK CAPACITY IS 420,000 GALS. AT 2.5 FEET THE SAFETY INJECTION LINE-UP IS SWITCHED TO THE RECIRCULATION MODE. THIS LEVEL IS EQUAL TO APPROX 10% OF TANK VOLUME.

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 35 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Specific Point

Description:

Generic / Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

12/6/2012 CC2 CC21 WIND SPEED 60 METER 15 MINUTE AVG 2WS60#1 SM WIND SPEED 60 METER 15 MINUTE AVG 60 METER WIND SPEED AT REACTOR SITE A

MIS N/A 0

50 N/A N/A S

1 N/A N/A N/A N/A N/A LOW N

N/A WIND SPEED INDICATION IN METERS PER SECOND TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER LOCATED ON SITE. 60 METER ELEVATION

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 36 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

12/6/2012 CC2 CC21 WIND DIRECTION 60 METER 15 MINUTE AVG 2WD60#15M WIND DIRECTION 60 METER 15 MINUTE AVG 60 METER WIND DIRECTION AT REACTOR SITE A

DEG NIA 0

360 N/A N/A S

1 N/A N/A N/A N/A N/A 0 DEGREES (NORTH)

N N/A WIND DIRECTION TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER ON SITE. 60 METER ELEVATION

PWR Data Point Library Reference File Report Date:

Page :

05-20-2013 37 Date:

Reactor Unit:

Data Feeder:

NRC EROS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm / Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

N1 Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

12/6/2012 CC2 CC21 WIND SPEED 10 METER 2WS10#15M WIND SPEED 10 METER 15 MINUTE AVG 10 METER WIND SPEED AT REACTOR SITE A

M/S N/A 0

5o N/A N/A S

1 N/A N/A N/A NIA N/A LOW N

N/A WIND SPEED INDICATION IN METERS PER SECOND TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER LOCATED ON SITE. 10 METER ELEVATION

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 38 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog I Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

Ni Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

12/6/2012 CC2 CC21 WIND DIRECTION 10 METER 2WD10#15M WIND DIRECTION 10 METER 15 MINUTE AVG 10 METER WIND DIRECTION AT REACTOR SITE A

DEG N/A 0

360 NIA N/A S

1 N/A N/A N/A N/A N/A 0 DEGREES (NORTH)

N N/A WIND DIRECTION TO PLANT COMPUTER IS SUPPLIED FROM THE PRIMARY MET TOWER ON SITE. 10 METER ELEVATION

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 39 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog / Digital:

ENGR Units / Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point Reference; Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

12/6/2012 CC2 CC21 WIND STABILITY BASED ON DELTA TEMP (A) 2MMDTASTB WIND STABILITY BASED ON DELTA TEMP (A)

DELTA TEMPERATURE BASED ATMOSPHERIC STA A

N/A NIA 0

6 N/A N/A S

I N/A N/A N/A N/A N/A N/A N

N/A DELTA TEMPERATURE BASED ATMOSPHERIC STABILITY AT REACTOR SITE

PWR Data Point Library Reference File Report Date:

Page:

05-20-2013 40 Date:

Reactor Unit:

Data Feeder:

NRC ERDS Parameter:

Point ID:

Plant Specific Point

Description:

Generic I Condition

Description:

Analog i Digital:

ENGR Units I Digital States:

ENGR Units Conversion:

Minimum Instrument Range:

Maximum Instrument Range:

Zero Point

Reference:

Reference Point Notes Proc or Sens:

Number of Sensors:

How Processed:

Sensor Locations Alarm I Trip Setpoints:

NI Detector Power Supply Cut-Off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Compensation for DP Transmitters:

Level Reference Leg:

Unique System

Description:

12/6/2012 CC2 CC21 60 METER WIND STABILITY - SIGMA-THETA 2MMS S60STB 60 METER WIND STABILITY - SIGMA-THETA SIGMA-THETA BASED ATMOSPHERIC STABILITY AT A

N/A N/A 0

6 N/A N/A S

1 N/A N/A N/A NIA N/A NIA N

N/A SIGMA-THETA BASED ATMOSPHERIC STABILITY AT REACTOR SITE