Letter Sequence RAI |
|---|
|
|
MONTHYEARML12220A1662012-08-0606 August 2012 ASME Code Update for the Fourth Ten-Year Interval, Inservice Testing Program Project stage: Request ML12261A0532012-09-17017 September 2012 Acceptance Review Email, Relief Request Nos. IST-4-P1 (ME9201-ME9202), IST-4-P2 (ME9203-ME9204), IST-4-P-3 (ME9205-ME9206), IST-4-V-1 (ME9207-ME9208), and IST-4-V-2 (ME9209-ME9210), Fourth 10-Year Inservice Testing Interval Project stage: Acceptance Review ML12313A4752012-11-0808 November 2012 Request for Additional Information Email, Relief Request IST-4-P-2, ASME OM Code Requirements for Testing CSS and LPSI Pumps, Fourth 10-Year Inservice Inspection Interval Project stage: RAI ML12348A2872012-11-28028 November 2012 Confirmatory Action Letter Response - Proprietary Documents Project stage: Request ML12292A6242012-12-0404 December 2012 Final Response to SONGS TIA 2011-008 Project stage: Request ML12341A2782012-12-0404 December 2012 Relief Request: American Society of Mechanical Engineers (Asme), Code Case N-770-1 Project stage: Request ML12362A1982012-12-26026 December 2012 (Songs), Units 2 and 3 - Request to NRC for Digital Upgrade Phase 0 Meeting Project stage: Request ML13002A0082012-12-27027 December 2012 Revision to Reactor Vessel Surveillance Capsule Withdrawal Schedule Project stage: Request ML13007A2152013-01-0707 January 2013 Acceptance Review Email, Relief Request from Volumetric Exam Requirements Specified in ASME Code Case N-770-1 for Dissimilar Metal Piping Welds for the Third 10-Year Inservice Inspection Interval Project stage: Acceptance Review ML13098A0432013-04-0505 April 2013 License Amendment Application Number 263, Revise Technical Specifications to Require Compliance Project stage: Other ML13136A0082013-05-15015 May 2013 (SONGS) Units 2 and 3 - NRC Generic Letter 2004-02 Closure Path and Schedule Project stage: Request ML13212A2502013-07-30030 July 2013 Withdrawal of Licensing Actions Due to Permanent Cessation of Operations Project stage: Request ML13226A3612013-08-27027 August 2013 Withdrawal of Several Applications for Relief Requests and Revision to Reactor Vessel Surveillance Capsule Withdrawal Schedule (TAC Nos. ME9201-ME9210, MF0335-MF0336, and MF0438-MF0439) Project stage: Withdrawal 2012-08-06
[Table View] |
Text
From:
Benney, Brian To:
"Linda.Conklin@sce.com" Cc:
Chen, Qiao-Lynn; Burkhardt, Janet; Broaddus, Doug; Hall, Randy; Warnick, Greg; Reynoso, John
Subject:
ME9204-05 RAIs Date:
Thursday, November 08, 2012 3:42:03 PM
Dear Ms. Conklin:
By letter dated August 6, 2012 (Agencywide Documents Access and Management System (ADAMS) accession number ML12220A166), Southern California Edison (the licensee) requested relief from certain American Society of Mechanical Engineers Code requirements.
The U.S. Nuclear Regulatory Commission (NRC) staff has reviewed the information provided by the licensee and determined that the additional information identified in the attachment is needed in order for the NRC staff to complete its review. The staff is requesting a written response to the RAls no later than December 15, 2012.
Please contact me if you would like to have a clarifying conference call.
Thank you, Brian Benney
REQUEST FOR ADDITIONAL INFORMATION (RAI)
SOUTHERN CALIFORNIA EDISON SAN ONOFRE NUCLEAR GENERATING STATION (SONGS), UNITS 2 AND 3 REQUEST IST-4-P-2 DOCKET NUMBERS 50-361 AND 50-362 (TAC NOS. ME9204 AND ME9205)
Reference:
Letter from Richard J. St. Onge of Southern California Edison to NRC, Docket Nos. 50-361 and 50-362, ASME Code Update for the Fourth Ten-Year Interval, Inservice Testing Program, San Onofre Nuclear Generating Station Units 2 and 3 dated August 6, 2012.
RAI IST-4-P-2-1
State the type of pump (horizontal centrifugal, vertical line shaft, positive displacement, etc.) for each pump listed in the request referenced above.