REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE CR0-I 08 RECOVER A DROPPED ROD CR0-i 08 Page 1 of 9 CANDIDATE EXAMINER

CR0-i 08 Page 2 of 9 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Recovery Of Dropped/Misaligned Safety Or Regulating Control Rod With Diamond in Automatic Alternate Path:

Yes Facility JPM #:

CRO-12 KIA Rating(s):

System:

APE 005 K/A:

AA2.03 Rating:

3.5/4.4 Task Standard:

Withdrawal of the dropped control rod is initiated in accordance with OP/1/A/1105/019 (Enclosure 4.15) and the reactor is manually tripped upon receipt of second dropped rod.

Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator X

In-Plant Perform X

Simulate

References:

AP/1 (Unit Runback)

OP/i/Ni 105/019 (Control Rod Drive System)

OMP 1-18 Validation Time: 15 minutes Time Critical: NO Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time Examiner:

NAME SIGNATURE DATE COMMENTS

SIMULATOR OPERATOR INSTRUCTIONS:

1.

RECALL Snap 220 2.

IMPORT files for CR0-I 08

3. G0t0RUN
4. Ensure all breaker flags are matched to current plant conditions.
5. Acknowledge computer alarms CR0-i 08 Page 3 of 9

CR0-i 08 Page 4 of 9 ToolslEguipmentlProcedures Needed:

OP/1/A/1105/019, Enclosure 4.15 (Recovery Of Dropped/Misaligned Safety Or Regulating Control Rod with Diamond In Automatic)

READ TO OPERATOR DIRECTION TO TRAINEE:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

Unit #1 dropped a Control Rod in Group 6 approximately one hour ago and the unit is stable at 52% RTP.

AP/1, Unit Runback, has been completed.

The problem with the Control Rod has been repaired.

Systems Duty Engineer has been notified and no special maneuvering instructions are required..15 (Recovery Of Dropped/Misaligned Safety Or Regulating Control Rod with Diamond In Automatic) of OP/I /A/1105/019 has been completed up to step 2.

INITIATING CUE:

The Control Room SRO directs you to recover the dropped rod using an Automatic Latch beginning at step 2.1 of Enclosure 4.15 of OP/i/A/i 105/019.

CR0-i 08 Page 5 of 9 START TIME:

NOTE: Use of this enclosure can affect core reactivity management due to changes in CRD position. (R.M.)

STEP 1:

Step2.1 SAT WHILE CRDs are moving, monitor the following indications:

CRD position Appropriate ranged NIs UNSAT Startup Rate (if applicable)

Neutron error (if applicable)

RCS temperature (if applicable)

STANDARD:

Candidate monitors the above indications on the OAC and control board.

COMMENTS:

STEP 2:

Step 2.2

  • CRITICAL STEP Select affected rod as follows: (R.M.)

Ensure GROUP SELECT SWITCH to desired group.

SAT Ensure SINGLE SELECT SWITCH to desired rod.

Ensure RUN is ON.

UNSAT Verify AUTO on Diamond is ON.

Verify MANUAL on Diamond is flashing.

STANDARD:

  • GROUP SELECT SWITCH is selected to group 6.
  • SINGLE SELECT SWITCH is selected to rod 6.

Ensure RUN is ON.

Verify AUTO on Diamond is ON.

Verify MANUAL on Diamond is flashing.

COMMENTS:

CR0-i 08 Page 6 of 9 STEP 3:

Step 2.3 If affected rod is fully inserted and Manual Latch and P1 Alignement SAT desired, perform the following:

STANDARD:

Determines Manual Latch is NOT desired.

UNSAT COMMENTS:

NOTE: When LATCH AUTO is selected, the following automatically occurs:

  • CRITICAL STEP With ICS in AUTO, CRD TRAVEL lights will only respond to the controlling group when Auto Latching.

Rod inserts to latch rod SAT Rod withdraws to test for latching Rod inserts RPI resets UNSAT STEP 4:

Step 2.4 IF affected rod is fully inserted, perform Auto Latch and P1 Alignment, as follows: (R.M.)

Select LATCH AUTO.

WHEN Auto Latch is complete, Verify LATCH AUTO is OFF.

Ensure desired rod API/RPI indications agree. (P1 Panel)

Select FAULT RESET.

STANDARD:

  • Depress the LATCH AUTO pushbutton on the Diamond.

WHEN Auto Latch is complete, Verify LATCH AUTO is OFF by observing LATCH AUTO light on the Diamond is NOT lit.

Use the toggle switch located on the P1 panel to verify Group 6 Rod 6 API/RPI indications agree.

  • Depress FAULT RESET pushbutton on the Diamond.

COMMENTS:

CR0-i 08 Page 7 of 9 CAUTION; If rod is known to have been dropped/misaligned for less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, rod

  • CRITICAL STEP can be withdrawn at 30 in./min. (RUN Speed). {i} (R.M.)

If rod has been dropped/misaligned for greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, rod can be withdrawn in SAT 10% withdrawal increments spaced 30 mm. apart at 30 in./min. (RUN Speed). {i} (R.M.)

NOTE: Controlling CRD Group will maintain Rx Power constant.

UNSAT Affected rod is considered recovered when rod position is group average and Manual light is no longer flashing.

STEP 5:

Step 2.5 Perform the following until affected rod is realigned with group: (R.M.)

Begin withdraw of affected rod.

As required, stop withdrawal of affected rod.

IF affected rod is in Group with OUT LIMIT, continue rod withdrawal until affected rod is fully withdrawn.

IF affected rod is in Group NOT at OUT LIMIT, continue rod withdrawal until affected rod aligned with group.

STANDARD:

  • Begin withdrawal of the affected rod using the Joy Stick on the Diamond.

NOTE: At 40% withdrawn, TIMER 3 will automatically fire to drop Group 4 Rod 6.

COMMENTS:

ALTERNATE PATH STEP 6:

Manually trip the reactor CRITICAL STEP SAT STANDARD:

The candidate recognizes the second control rod inserting and manually trips the reactor by depressing the Reactor Trip pushbutton and verifies that the reactor is shutdown.

This action is required by OMP 1-18 Attachment A (Licensed Operator UNSAT Memory Items) which states:

Initiate a manual reactor trip if any of the following conditions exist:

Two or more control rods drop into the core COMMENTS:

END TASK STOP TIME:

CR0-i 08 Page 8 of 9 CRITICAL STEP EXPLANATIONS:

STEP #

Explanation 2

Step is required to recover the dropped control rod.

4 Step is required to recover the dropped control rod.

5 Step is required to recover the dropped control rod.

6 Step is required to trip the reactor in response to the second dropped control rod as required by OMP 1-18.

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

Unit #1 dropped a Control Rod in Group 6 approximately one hour ago and the unit is stable at 52% RTP.

AP/1, Unit Run back, has been completed.

The problem with the Control Rod has been repaired.

Systems Duty Engineer has been notified and no special maneuvering instructions are required..15 (Recovery Of Dropped/Misaligned Safety Or Regulating Control Rod with Diamond In Automatic) of OP/I/A/I 105/019 has been completed up to step 2.

INITIATING CUE:

The Control Room SRO directs you to recover the dropped rod using an Automatic Latch beginning at step 2.1 of Enclosure 4.15 of OP/i/NI 105/019.

REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE CRO-306 ALIGN HPIILPI PIGGYBACK MODE CRO-306 Page 1 of 14 CANDIDATE EXAMINER

C RO-306 Page 2 of 14 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Align HPI/LPT Piggyback Mode Alternate Path:

Yes Facility JPM #:

C RO-305 KIA Rating(s):

System:

EPE 009 K/A:

EK3.21 Rating:

4.2/4.5 Task Standard:

Steps of EOP Enclosure 5.12 are properly completed by the candidate to align HPI/LPI piggyback mode and total HPI flow is throttled to less than 750 gpm.

Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator X

In-Plant Perform X

Simulate

References:

EOP Enclosure 5.12, ECCS Suction Swap to RBES Validation Time: 15 minutes Time Critical: NO Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

/

NAME SIGNATURE DATE COMMENTS

CRO-306 Page 3 of 14 SIMULATOR OPERATOR INSTRUCTIONS

1. Recall Snap 215
2. Import files for CRO-306 3.

Call up SHOWDIG 01 P1 600 on OAC 4.

Provide a clean copy of EOP Enclosure 5.12 5.

Ensure all LPI Pump Breaker switch flags are green and that all other breaker flags are set to current plant conditions.

6. When directed by the lead examiner, go to RUN

CRO-306 Page 4 of 14 Tools/Equipment/Procedures Needed:

EOP Enclosure 5.12, ECCS Suction Swap to RBES READ TO OPERATOR DIRECTION TO TRAINEE I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS A small break LOCA has occurred which is depleting the BWST.

The EOP is in progress.

IAAT Step 94 of LOSCM directs the initiation of Enclosure 5.12, ECCS Suction Swap to RBES at 19 in BWST.

INITIATING CUES The Control Room SRO directs you to perform Enclosure 5.12, ECCS Suction Swap to RBES to align HPI/LPI piggyback mode.

CRO-306 Page 5 of 14 START TIME:

STEP 1:

Step I CRITICAL STEP Start:

_1ALPI PUMP SAT

_1B LPI PUMP UNSAT STANDARD:

Candidate locates the controls for 1A and lB LPI pumps on 1UB2 and determines that 1 A and 1 B LPI pumps are off by observing the white trip light illuminated and red close lights OFF.

Candidate rotates control switch to the CLOSE position for 1A (Critical) and 18 (NOT Critical) LPI pumps. The red CLOSE lights are observed to be on and the white TRIP light is observed to be off.

Candidate observes the 1A LPIP amps are 20 amps and stable.

Candidate determines the 1 B LPIP did not start by no amps and the white TRIP light is still illuminated.

Candidate continues to Step 1 RNO COMMENTS:

STEP 2:

Step 1 RNO SAT

1. IF NO LPI pumps are operating, THEN GO TO step 85.
2. IF 1C LPI PUMP is operating, THEN GO TO step 87 UNSAT STANDARD:

Candidate determines that neither of the above are satisfied and continues to step 2.

COMMENTS:

CRO-306 Page 6 of 14 STEP 3:

Step 2 Verify either:

SAT LPI FLOW TRAIN A jjj LPI FLOW TRAIN B 3400 gpm Only one LPI header is operating, AND flow in that header is 2900 gpm UNSAT STANDARD:

Candidate locates LPI Flow Train A and B flow meters on I UB1.

Observes flow in both headers to be 0 gpm.

Candidate refers to Step 2 RNO.

COMMENTS:

STEP 4:

Step 2 RNO GO TO Step 4.

SAT STANDARD:

Candidate goes to Step 4.

UNSAT COMMENTS:

STEP 5:

Step 4 Verify three HPI pumps operating.

SAT STANDARD:

Candidate locates HPI pump controls on 1 UB1 and determines that all three HPI pumps are operating by observing the red ON lights illuminated and HPIP motor amps are stable.

UNSAT Candidate continues to Step 5.

COMMENTS:

CRO-306 Page 7 of 14 STEP 6:

Step 5 CRITICAL STEP Stop lB HPI PUMP.

SAT STANDARD:

Candidate locates the pump switch for the 1 B HPI Pump on 1 UB1 and stops the pump by rotating the switch to the OFF position.

Candidate verifies the red ON light goes out, the green OFF light is UNSAT illuminated, and motor amps go to zero.

NOTE: Candidate may throttle HPI per rule 6 guidance (<475 gpm) if flow in the A HPI Header is > 475 gpm.

Candidate continues to Step 6.

COMMENTS:

STEP 7:

Step 6 CRITICAL STEP Simultaneously open:

SAT 1LP-15 1LP-16 STANDARD:

Candidate locates 1 LP-1 5 and I LP-1 6 on 1 UB2 and opens both valves UNSAT simultaneously by taking each switch to the open position. Verify that the closed green light goes off and the red open light illuminates for each valve.

Candidate continues to Step 7.

COMMENTS:

CRO-306 Page 8 of 14 ALTERNATE PATH STEP 8:

Step 7 Verify two LPI pumps operating.

SAT STANDARD:

Candidate determines that ONLY the 1A LPI pump is operating by observing that the 1A LPIP has amps in indicates the breaker is closed UNSAT while the 1 B LPIP has no amps in the white TRIPPED light is illuminated..

Candidate continues to Step 7 RNO which directs the candidate to Step 10.

COMMENTS:

STEP9:

Step 10 Maximize total LPI flow < 3100 gpm by throttling HPI flow.

SAT STANDARD:

Candidate determines that there is 0 gpm LPI flow and since RCS pressure is above the shutoff head for the LPI pumps, LPI cannot inject and is therefore maximized.

UNSAT COMMENTS:

STEP 10:

Step 11 CRITICAL STEP Limit total HPI flow to <750 gpm including seal injection SAT STANDARD:

Candidate sums HPI header flows and seal injection flow and determines that total HPI flow is> 750 gpm and throttles 1 HP-26 and/or I HP-27 to reduce total HPI flow to < 750.

UN SAT As left flows: A header Seal Inj.

B header COMMENTS:

CRO-306 Page 9 of 14 STEPI1:

Stepl2 Place LDST LEVEL INTERLOCK switch in DISABLE.

SAT STANDARD:

Candidate places LDST LEVEL INTERLOCK switch located on 1 UB1 to DISABLE by taking the switch to the DISABLE position.

Candidate continues to Step 13.

UNSAT COMMENTS:

STEP 12:

Step 13 CRITICAL STEP Position valve switches to close until valve travel is initiated:

_IHP-23 SAT I HP-24 1HP-25 STANDARD:

Candidate positions the following valve switches located on 1 UB1 to UNSAT close until valve travel is initiated:

1HP-23 1 HP-24 1HP-25 Candidate recognizes valve travel has been initiated when the green close light illuminates.

Candidate continues to Step 14 after valve travel has been initiated for all three valves.

COMMENTS:

CRO-306 Page 10 of 14 STEP 13:

Step 14 CRITICAL STEP Simultaneously position valve switches to open until valve travel is initiated:

1HP-939 SAT 1 HP-940 STANDARD:

Candidate simultaneously positions the following valve switches located UNSAT on 1UB2 to open until valve travel is initiated:

1 HP-939 1 HP-940 Candidate recognizes valve travel has been initiated when the red open light illuminates.

Candidate continues to Step 15 after valve travel has been initiated for both valves.

COMMENTS:

STEP 14:

Step 15 Verify either fly open:

1LPSW-4 SAT 1LPSW-5 STANDARD:

Candidate locates 1LPSW-4 and 1LPSW-5 on 1VB2 and determines that UNSAT they are fully open by observing the red open light illuminated and green closed light OFF.

Candidate continues to Step 16.

COMMENTS:

CRO-306 Page 11 of 14 STEP 15:

Step 16 Verify both open:

_1LPSW-4

_SAT 1LPSW-5 STANDARD:

Candidate locates 1LPSW-4 and ILPSW-5 on IVB2 and determines that UNSAT they are both fully open by observing the red open light lit and green closed light OFF for both valves.

Continue to step 17.

COMMENTS:

STEP 16:

Step 17 GO TO Step 24 SAT STANDARD:

Candidate proceeds to step 24 COMMENTS:

UNSAT STEP 17:

Step 24 Verify both:

Step 8 RNO was used to secure an LPI pump due to low flow SAT conditions.

LPSW is aligned to cooler associated with stopped LPI pump.

STANDARD:

Candidate determines that neither condition is met and goes to step 24 UNSAT RNO which directs the candidate to Step 26.

COMMENTS:

CRO-306 Page 12 of 14 STEP 18:

Step 26 WHEN BWST level is < 9, AND RB level is rising, THEN continue in this enclosure.

SAT STANDARD:

Candidate begins to monitor BWST level.

UNSAT CUE: Another operator will continue with this procedure.

COMMENTS:

END OF TASK STOP TIME:

C RO-306 Page 13 of 14 CRITICAL STEP EXPLANATIONS STEP #

Explanation 1

Step 1 is required to start an LPI pump so LPI can supply suction to the HPI pumps.

6 Step 6 is required to reduce number of HPI pumps to two.

7 Step 7 is required to align a flow path from LPI pump discharge to HPI pump suction.

10 Step 11 is required to ensure proper HPI pump operation 12 Step 13 is required to isolate the suction flow path to the LPI pumps from the BWST and the LDST.

13 Step 14 is required to prevent over pressurizing the LDST.

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS A small break LOCA has occurred which is depleting the BWST.

The EOP is in progress.

IAAT Step 94 of LOSCM directs the initiation of Enclosure 5.12, ECCS Suction Swap to RBES at 19 in BWST.

INITIATING CUES The Control Room SRO directs you to perform Enclosure 5.12, ECCS Suction Swap to RBES to align HPI/LPI piggyback mode.

REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE CRO-408 START FOURTH REACTOR COOLANT PUMP CANDIDATE:

EXAMINER:

CRO-408 Page 1 of 9

CRO-408 Page 2 of 9 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Start the fourth RCP Alternate Path:

Yes Facility JPM #:

CRO-038 K/A Rating(s):

System: 003 K/A:

A4.03 Rating:

2.8/2.5 Task Standard:

1B2 RCP is started in accordance with OP/11A111031006 End. 4.4 (Starting 1B2 RCP) and DC Oil Lift Pump secured Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator X

In-Plant Perform X

Simulate

References:

OP/i /A/1 102/001 (Controlling Procedure for Unit Startup)

OP/1/A/1103/006 End. 4.4 (Starting 1B2 RCP)

Validation Time: 10 minutes Time Critical: No Candidate:

Time Start:

NAME Time Finish:

Performance Rating: SAT UNSAT Performance Time:

Examiner:

/

NAME SIGNATURE DATE COMMENTS

SIMULATOR OPERATOR INSTRUCTIONS

1. Recall Snap 202
2. Import files for CRO-408
3. Goto Run
4. Ensure all breaker flags are set to current plant conditions CRO-408 Page 3 of 9

CRO-408 Page 4 of 9 ToolslEguipmeritlProcedures Needed:

OP/i/Ni 102/001 (Controlling Procedure for Unit Startup)

OP/i/N11031006 End. 4.4 (Starting 1B2 RCP)

READ TO OPERATOR DIRECTION TO TRAINEE I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS OP/I/A/I 102/001 (Controlling Procedure for Unit Startup) Enclosure 4.6 (Unit Startup From 335°F1540 psig (MODE 3) To 532°F/2155 psig (MODE 3)) in progress and completed up to step 6.2 which directs starting the fourth RCP RCS Pressure = 1660 psig slowly increasing in accordance with OPI1IA/11021001 RCS Temperature = 474°F slowly increasing in accordance with OP/I/NI 102/001 INITIATING CUES The CRSRO directs you to start the 1B2 RCP per OP/i/Ni 103/006 End. 4.4 beginning with step 2.1.

CRO-408 Page 5 of 9 START TIME:

STEP1:

Step2.1.1 Announce Starting 1 B2 RCP via plant page.

SAT STANDARD:

Announces Starting 1 B2 RCP using the plant page system.

COMMENTS:

UNSAT STEP 2:

Step 2.1.2 IF AT ANY TIME Oil Lift Pump low discharge pressure clears, Go To Step 2.1.6 SAT STANDARD:

Reads IAAT step and determines it does not currently apply COMMENTS:

UNSAT NOTE: AC Oil Lift Pump may take > 2 minutes to develop adequate discharge pressure.

STEP 3:

Step 2.1.3 SAT IF available, start AC Oil Lift Pump on 1 B2 RCP.

STANDARD:

Determines AC Oil Lift Pump is available and:

UNSAT Rotates AC Oil Lift Pump switch to start Observes red light on and green light off Monitors discharge pressure status on OAC NOTE: The AC Oil Lift Pump will trip prior to clearing the low discharge pressure alarm.

COMMENTS:

CRO-408 Page 6 of 9 NOTE: Operating either AC or DC Oil Lift Pump is adequate to start RCP.

STEP4:

Step2.1.4

_SAT IF AC Oil Lift Pump is unavailable, start DC Oil Lift Pump STANDARD:

Determines AC Oil Lift Pump was available and N/As this step UNSAT COMMENTS:

ALTERNATE PATH

  • CRITICAL STEP STEP 5:

Step 2.1.5 IF AC Oil Lift Pump automatically trips prior to Oil Lift Pump low SAT discharge pressure clearing, start DC Oil Lift Pump.

STANDARD:

Determines the AC Oil Lift Pump has tripped and starts the DC Oil Lift UNSAT Pump by performing the following:

  • Rotates DC Oil Lift Pump switch to start Observes red light on and green light off Monitors discharge pressure status on OAC Time DC OLP started:

COMMENTS:

CRO-408 Page 7 of 9 STEP 6:

Step 2.1.6

  • CRITICAL STEP WHEN Oil Lift Pump low discharge pressure clears AND > 60 seconds has elapsed since starting oil lift pumps, start I B2 RCP.

SAT STANDARD:

Once the DC Oil Lift Pump low discharge pressure has cleared, start the I B2 RCP as follows:

  • Rotate 182 RCP switch to START UNSAT Verify red lights on and green light off Verify starting current Verify OAC indications support pump start COMMENTS:

STEP 7:

Step 2.1.7 After RCP is at full speed, perform the following:

A.

Ensure the following stopped SAT AC Oil Lift Pump DC Oil Lift Pump B. If AC Oil Lift Pump was operated, position AC Oil Lift Pump switch to UNSAT OFF C. If DC Oil Lift Pump was operated, position AC Oil Lift Pump switch to OFF STANDARD:

Once 182 RCP is at rated speed, Rotates AC Oil Lift Pump switch to OFF Rotates the DC Oil Lift Pump Switch to OFF CUE: Another operator will continue with this procedure.

COMMENTS:

END OF TASK STOP TIME:

CRITICAL STEP EXPLANATIONS STEP #

Explanation 5

Required to be able to start the I B2 RCP 6

Required to start 1B2 RCP CRO-408 Page 8 of 9

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS OP/i/All 102/001 (Controlling Procedure for Unit Startup) Enclosure 4.6 (Unit Startup From 335°F1540 psig (MODE 3) To 532°F/2155 psig (MODE 3)) in progress and completed up to step 6.2 which directs starting the fourth RCP RCS Pressure = 1660 psig slowly increasing in accordance with OP/11A111021001 RCS Temperature = 474°F slowly increasing in accordance with OPII/A11i021001 INITIATING CUES The CRSRO directs you to start the 1 B2 RCP per OP/i/Ni 103/006 End. 4.4 beginning with step 2.1.

CRO-41 3 Page 1 of 13 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE CRO-41 3 ALIGN MDEFDWP SUCTION TO THE HOTWELL AND FEED THE STEAM GENERATORS CANDIDATE EXAMINER

CRO-413 Page 2 of 13 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Align MDEFDWP Suction To The Hotwell And Feed The Steam Generators Alternate Path:

No Facility JPM #:

CRO-413 KIA Rating(s):

System: APE 054 K/A:

AA1.01 Rating:

4.5/4.4 Task Standard:

The MDEFDWPs are aligned to the hotwell and providing flow to the SOs within limits prior to reaching a level of 1 foot in the UST.

Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator X

In-Plant Perform X

Simulate

References:

EP/11A118001001 (Emergency Operating Procedure) Enclosure 5.9 (Extended EFDW Operaton)

Validation Time: 15 minutes Time Critical: NO Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

/

NAME SIGNATURE DATE COMMENTS

SIMULATOR OPERATOR INSTRUCTIONS:

1.

Recall Snap 223 2.

Import files for CR0413 3.

Place CST pump switches in RUN (the pumps are failed OFF)

4. G0toRUN 5.

Fire Timer #1

6. Verify UST level at 2.9 ft.
7. Freeze simulator
8. Verify Control Room radio communication with booth is available
9. Take simulator to RUN at direction of examiner cRo-413 Page 3 of 13

CRO-41 3 Page 4 of 13 ToolsIEguipmentlProcedures Needed:

EP/1/A/1800/OO1 (Emergency Operating Procedure) Enclosure 5.9 (Extended EFDW Operation)

READ TO OPERATOR DIRECTION TO TRAINEE:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

The TDEFDWP is unavailable.

Actions of the EOP have been completed..9 (Extended EFDW Operation) has been initiated per Rule 3 and is completed up to Step 63. (Operator has been dispatched to IC-573, the chain is removed, and communications established with the control room via radio).

Main FDW is not expected back for several hours. DW and CST makeup capability to the UST has been lost.

INITIATING CUES:

Procedure Director directs you to continue performance of Enclosure 5.9 (Extended EFDW Operation) beginning at step 63.

CRO-41 3 Page 5 of 13 START TIME:

STEP 1:

Step 63 WHEN UST level is <3 THEN continue SAT STANDARD:

Monitors UST level and determines that level is less than three feet.

UNSAT Continues to step 124.

COMMENTS:

STEP 2:

Step 64 CRITICAL STEP Open 1V-186 SAT STANDARD:

Locate valve switch and rotate to open position and verifies red open light illuminates.

UNSAT COMMENTS:

STEP 3:

Step 65 Stop aN main vacuum pumps.

SAT STANDARD:

Verifies all three MVPs are OFF UN SAT COMMENTS:

CRO-41 3 Page 6 of 13 STEP 4:

Step 66 Stop aN C BPs.

SAT STANDARD:

Stops Condensate Booster Pumps by ensuring all CBP switches are in the OFF position.

EXAMINER NOTE: IA CBP running. Leaving the standby CBP switch in the AUTO UNSAT position will result in the standby CBP automatically starting COMMENTS:

STEP 5:

Step 67 CRITICAL STEP Stop aN HWPs.

SAT STANDARD:

Stops the 1A Hotwell Pump by rotating the switch to the OFF position.

COMMENTS:

UNSAT STEP 6:

Step 68 Close the following:

SAT a

IMS-47 1AS-40 UNSAT STANDARD:

Rotates 1MS-47 switch in the closed direction.

Verifies 1AS-40 green closed light on and the red open light off.

COMMENTS:

CRO-41 3 Page 7 of 13 STEP 7:

Step 69 IAAT UST level < 1, AND 1C-573 (MD EFWPS SUCTION FROM UST) is open, SAT THEN perform Steps 70

- 71 STANDARD:

These conditions do not exist therefore continues to step 72 per RNO.

UNSAT COMMENTS:

STEP 8:

Step 72 Reduce MD EFDWP flow to <440 gpm per pump.

SAT Notify crew of MDEFWP flow limit while aligned to hotwell.

STANDARD:

Reduces MDEFWP flows to <440 gpm UN SAT Notifies crew of MDEFWP flow limit COMMENTS:

STEP 9:

Step 73 WHEN vacuum is broken (as indicated by vacuum no longer decreasing)

SAT THEN continue.

UNSAT STANDARD:

Once vacuum has stopped decreasing, continues to step 74 NOTE: It will take approximately 6 minutes from the time IV-186 is opened for condenser vacuum to decrease to O COMMENTS:

CRO-413 Page 8 of 13 STEP 10:

Step 74 IAAT MD EFDWPs are operating OR available to operate SAT THEN PERFORM step 75-77 STANDARD:

Since MDEFWPs are operating, continues to step 75 UNSAT COMMENTS:

STEP 11:

Step 75 CRITICAL STEP Locally close 1C-573 (MD EFDWPS SUCTION FROM UST).

SAT STANDARD:

Contacts NEO to close 1C-573.

UNSAT Booth Cue: FIRE TIMER 2 to close IC-573 over 20 seconds, then inform student that (using time compression) IC-573 is closed. DO NOT USE MANUAL VAVLES PROGRAM TO CLOSE IC-573.

COMMENTS:

STEP 12:

Step 76 Verify MD EFDWPS were stopped due to UST level < 1.

SAT STANDARD:

Verifies are still operating and continues to step 78 per RNO.

UNSAT COMMENTS:

CRO-41 3 Page 9 of 13 STEP 13:

Step 78 Verify I TD EFDW PUMP is operating.

SAT STANDARD:

Recognizes that TDEFDWP is OFF and continues to step 82 per RNO.

COMMENTS:

UNSAT STEP 14:

Step 82 Locally close 1 C-i 57 (TD EFDWP Suction from UST).

SAT STANDARD:

Dispatches an NEO to close iC-i 57.

Booth cue: Inform student that (using time compression) IC-157 is closed (IC-157 UNSAT not modeled)

COMMENTS:

STEP 15:

Step 83 OPEN 1C-391 SAT STANDARD:

Rotates the I C-39i switch located on VB3 in the open direction. Red light should illuminate and green light should extinguish.

UNSAT COMMENTS:

CRO-41 3 Page 10 of 13 STEP 16:

Step 84 IAAT 1 TDEFDWP operation is desired...

SAT STANDARD:

Recognizes from turnover that TDEFDWP is not available and continues to Step 85 UNSAT COMMENTS:

STEP 17:

Step 85 Dispatch an operator to open the following:

IC-i 88 (HOTWELL Emergency Makeup #1 Control Bypass)

SAT 1C-912 (UST RISER TO HW EMERG MAKEUP #2 AUTO ISOL.

BYPASS)

UNSAT STANDARD:

Dispatches an NEO to open IC-I 88.

Dispatches an NEC to open 1C-912.

Booth cue: Acknowledge that an operator has been dispatched to open IC-188 and IC-912.

COMMENTS:

STEP 18:

Step 86 Notify TSC to evaluate methods to maintain secondary inventory.

SAT STANDARD:

Notifies TSC Booth cue: Inform student: TSC will evaluate secondary inventory U N SAT COMMENTS:

CRO-41 3 Page 11 of 13 STEP 19:

Step 87 IAAT hotwell level is 1,

THEN stop all EFDWPs.

SAT STANDARD:

Determines that hotwell level is greater than 1 inch and continues to Step 88.

UN SAT COMMENTS:

STEP 20:

Step 88 Notify the CR SRO to direct the following as time and resources allow:

Transfer steam control from TBVs to ADVs.

SAT o

Operate ADVs per Ui EOP End 5.25 (Operation of ADVs).

Begin Unit cool down to LPI per OP/i 102/010 using the ADVs.

Break Vacuum per OP/i 106/016.

UNSAT Secure Steam Seals per OP/i106/013 STANDARD:

Cue: Inform candidate that another operator will continue with any of the above procedures that are to be performed as time and resources allow.

COMMENTS:

STEP 21:

Step 89 WHEN directed by CR SRO, THEN EXIT this enclosure.

SAT STANDARD:

Inform CR SRO that this enclosure is complete with outstanding IAATs.

COMMENTS:

UNSAT END TASK STOP TIME:

CRO-41 3 Page 12 of 13 CRITICAL STEP EXPLANATIONS:

STEP #

Explanation 2

Condenser vacuum must be broken thus increasing the NPSH to the EFDWPs. This prevents EFDWP damage due to not meeting suction head requirements when Hotwell level is < 3 ft.

5 STOP all HWPs to prevent damage to the MDEFDWP by decreasing NPSH 11 Closing I C-573 prevents air introduction into the pumps suction, thus preventing pump cavitation and possible pump damage.

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

The TDEFDWP is unavailable.

Actions of the EOP have been completed..9 (Extended EFDW Operation) has been initiated per Rule 3 and is completed up to Step 63. (Operator has been dispatched to IC-573, the chain is removed, and communications established with the control room via radio).

Main FDW is not expected back for several hours. DW and CST makeup capability to the UST has been lost.

INITIATING CUES:

Procedure Director directs you to continue performance of Enclosure 5.9 (Extended EFDW Operation) beginning at step 63.

REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE CRO-506 ESTABLISHING CONTAINMENT CLOSURE CRO-506 Page 1 ofl5 CANDIDATE EXAMINER

CRO-506 Page 2 of 15 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Establishing containment Closure Alternate Path:

Yes Facility JPM #:

CRO-006 K/A Rating(s):

System:

103 K/A:

A2.03 Rating:

3.5*/3.8*

Task Standard:

Components and systems aligned per Enclosure 5.1 of API1IA/1700126, Loss of Decay Heat Removal.

Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator X

In-Plant Perform X

Simulate

References:

AP111A11700126, Enclosure 5.1 Establishing RB Containment Closure.

Validation Time: 22 minutes Time Critical: NO Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

/

NAME SIGNATURE DATE COMMENTS

CRO-506 Page 3 of 15 SIMULATOR OPERATOR INSTRUCTIONS:

1. Recall Snap 224.

2.

Exit static check with I PR-5 not cleared.

3. Import files-CRO-506.
4. Place LTOP tags on 1 HP-26, 27, 409, & 410.
5. Ensure all breaker flags are set to current plant conditions.

6.

Go to RUN at the direction of the Examiner

7. At STEP 6 of this JPM, candidate may request closing the breaker for IRC-164. If so FIRE TIMER I to close the breaker and then FIRE TIMER 2 to re-open the breaker if requested by candidate.

CRO-506 Page 4 of 15 Tools/EguipmentlProcedures Needed:

AP/1 IA/I 700/26, Enclosure 5.1 Establishing RB Containment Closure.

READ TO OPERATOR DIRECTION TO TRAINEE:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

Unit I was on normal decay heat removal mode. Decay heat removal (DHR) on Unit I was lost due to LPI pump cavitation.

Plant conditions:

LPI pumps have been tripped due to indications of pump The RCS loops are full and intact.

The Steam Generators are available for heat transfer.

RCPs are secured.

HPI is secured.

RCS temperature was 120°F when LPI was secured. RCS pressure is 50 psig.

LPI suction is aligned to the Normal DHR suction path.

INITIATING CUES:

The Control Room SRO directs you to establish Reactor Building Closure per AP/1/N1 700/26,.1 (Establishing RB Containment Closure), starting at step 6.

CRO-506 Page 5 of 15 START TIME:

STEP 1:

Step6 Stop RB purge.

SAT STANDARD:

Candidate locates switch for Main Purge Fan on IAB3 and rotates switch to STOP. Red light extinguishes and Green light illuminates.

UNSAT COMMENTS:

  • CRITICAL STEP STEP 2:

Step 7 Close the following:

1PR-2 SAT IPR-5 STANDARD:

Candidate locates switches for 1 PR-2 and 1 PR-S.

UNSAT

  • Rotates switch for I PR-2 to CLOSE and verifies red light extinguishes and green light illuminates Rotates switch for I PR-5 to CLOSE, determines valve will not close, and refers to RNO COMMENTS:

ALTERNATE PATH CRITICAL STEP STEP 3:

Step7RNO IF 1 PR-2 NOT closed then close 1 PR-I SAT IF IPR-5 NOT closed then close 1PR-6 STANDARD:

Candidate Rotates switch for 1PR-6 to CLOSE and verifies red light UNSAT extinguishes and green light illuminates COMMENTS:

CRO-506 Page 6of 15 STEP 4:

Step 8 Verify RCS Loops are full.

SAT STANDARD:

Candidate determines loops are full based on initial conditions and/or 35 psig RCS pressure.

N AT COMMENTS:

STEP 5:

Step 9 Dispatch operators to perform the following enclosures:

SAT End. 5.2 (East Pen Room Valve Checklist)

End. 5.3 (West Pen Room Valve Checklist)

UNSAT End. 5.4 (Miscellaneous Valve Checklist)

STANDARD:

Candidate dispatches operators as required COMMENTS:

CRO-506 Page 7 of 15 STEP 6:

Step 10 Close the following:

SAT I RC-1 64 (already closed and breaker open)

I GWD-1 3 (already closed)

I RC-7 (already closed) 1 CS-6 (already closed)

UNSAT 1 FDW-1 06 (already closed) 1 FDW-1 08 (already closed) 1 FDW-1 03 (already closed) 1 FDW-1 04 (already closed) 1 PR-81 (already closed)

I PR-84 (already closed) 1 PR-87 (already closed) 1 PR-90 (already closed) 1 LWD-2 (already closed) 1 BS-1 (already closed) 1 BS-2 (already closed)

STANDARD:

Candidate locates and closes the above valves.

I RC-1 64 (already closed and breaker open) Que closed prior to breaker opening if asked) 1 GWD-1 3 (already closed) 1 RC-7 (already closed)

  • 1CS..6 (already closed)
  • 1 FDW-I 06 (already closed)

I FDW-1 08 (already closed) 1 FDW-1 03 (already closed) 1 FDW-1 04 (already closed)

I PR-81 (already closed) 1 PR-84 (already closed) 1 PR-87 (already closed)

I PR-90 (already closed)

  • 1 LWD-2 (already closed) 1 BS-1 (already closed) 1 BS-2 (already closed)

Booth Cue: If requested, Fire TIMER I to close breaker for IRC-164. Fire TIMER 2 to re-open the breaker.

COMMENTS:

CRO-506 Page 8 of 15 STEP 7:

Step 11 Verify gy RCP operating.

SAT STANDARD:

Candidate verifies no RCPs are running and continues to RNO.

UNSAT COMMENTS:

STEP 8:

Step 11 RNO CRITICAL STEP Close IHP-21.

SAT STANDARD:

Candidate closes 1 HP-21.

UNSAT COMMENTS:

STEP9:

Step 12 Verify RCS makeup supplied by HPI injection headers.

SAT STANDARD:

Candidate verified RCS makeup is not supplied by HPI injection headers and continues to RNO.

UNSAT COMMENTS:

CRO-506 Page 9 of 15 STEP 10:

Step 12RNO

1. Close the following:

1 HP-5 (already closed)

SAT 1 HP-26 (already closed with LTOP tags) 1 HP-41 0 (already closed with LTOP tags) 1 HP-409 (already closed with LTOP tags)

UNSAT 1 HP-27 (already closed with LTOP tags) 1 HP-i 20 (already closed)

2. Dispatch an operator to close the following (East Pen Rm, pen #9):

1 HP-i 22 (RC VOLUME CONTROL BYPASS)

STANDARD:

Candidate verifies the above valves are already closed and dispatches an operator to 1 HP-i22.

Booth Cue: When asked, inform candidate that operator has been dispatched to close IHP-122.

COMMENTS:

STEP Ii:

Step 13 Verify LPI in sump recirculation mode.

SAT STANDARD:

Candidate verifies LPI is NOT in the sump recirculation mode and continues to the RNO.

UNSAT COMMENTS:

STEP 12:

Step 13 RNO Close 1 LP-20.

GO TO Step 15.

SAT STANDARD:

Candidate locates and verifies closed 1LP-20 Continues to Step 15.

UNSAT COMMENTS:

CRO-506 Page 10 of 15 STEP 13:

Step 15 Verify alternate LP( suction aligned.

STANDARD:

Candidate verifies alternate LPI suction is NOT aligned and continues to SAT RNO.

CUE: If asked, LPI is in normal decay heat removal (DHR) alignment.

UNSAT COMMENTS:

STEP 14:

Step 15 RNO Close ILP-19 STANDARD:

Candidate locates and verifies closed I LP-1 9 SAT COMMENTS:

UNSAT STEP 15:

Step 16 Verify RB radiation monitors in service.

STANDARD:

Candidate verifies RB radiation monitors in service at the radiation SAT monitor panel. RB radiation monitors are 1 RIA-47, 48, 49, 49A. Radiation

monitors should indicate green or blue.

UNSAT COMMENTS:

STEP 16:

Step 17 Verify CC system operating.

STANDARD:

Candidate verifies CC system operating by observing 1A CC pump SAT running, CC Total Flow 750 gpm located on 1AB3.

COMM ENTS:

UNSAT

CRO-506 Page 11 of 15 STEP 17:

Step 18 Verify 1A RBCU operating with LPSW aligned.

STANDARD:

Candidate verifies 1A RBCU operating with LPSW aligned by observing SAT red ON lights illuminated for RBCU 1A and 1LPSW-16 OPEN and 1LPSW-18 Throttled located on 1AB3 UNSAT COMMENTS:

STEP 18:

Step 19 Verify 18 RBCU operating with LPSW aligned.

SAT STANDARD:

Candidate verifies I B RBCU is NOT operating by red ON light is not illuminated and 1LPSW-19 Open and 1LPSW-21 Throttled on 1AB3.

Continues to RNO.

UNSAT COMMENTS:

STEP 19:

Step 19 RNO

1. Close the following:

CRITICAL STEP 1LPSW-19 SAT 1LPSW-21

2. Dispatch an operator to close the following valves:

1LPSW-242 (lB RBCU OUTLET SAMPLE BLOCK PENE (35))

UNSAT 1LPSW-259 (lB RBCU OUTLET PENE (35))

STANDARD:

Candidate locates and closes ILPSW-19 and 1LPSW-21 located on 1 AB3 and dispatches an operator to closel LPSW-242 and 1 LPSW-259 Examiner Cue: Student action causes OAC alarm 01E0506 (LPSW Leakage Accumulator Level), which says to refer to OP/1/AJIIO4IOIO Low Pressure Service Water. Inform the candidate another operator will respond to this alarm response.

Booth Cue: When asked, inform candidate that NEO has been dispatched to close ILPSW-242 and ILPSW-259.

COMMENTS:

CRO-506 Page 12 of 15 STEP 20:

Step 20 Verify 1C RBCU operating with LPSW aligned.

SAT STANDARD:

Candidate verifies 1 C RBCU operating with LPSW aligned by observing red ON lights illuminated for 1C RBCU and 1LPSW-22 OPEN and 1LPSW-24 Throttled located on 1AB3 UNSAT COMMENTS:

STEP2I:

Step2l Verify RB AUX Coolers in service.

SAT STANDARD:

Candidate locates RB AUX Coolers on 1AB3 and verifies in service by observing red ON lights illuminated.

UNSAT COMMENTS:

STEP 22:

Step 22 Verify any RCP operating.

SAT STANDARD:

Candidate verifies no RCPs are operating by verifying no red ON lights illuminated located on lABland continues to RNO.

UNSAT COMMENTS:

CRO-506 Page 13 of 15 STEP 23:

Step 22 RNO Close the following:

CRITICAL STEP 1LPSW-6 SAT 1LPSW-15 STANDARD:

Candidate locates and closes I LPSW-6 and 1 LPSW-1 5 on 1 UB2 UNSAT COMMENTS:

Cue: Inform the candidate that another operator will continue with this procedure END TASK STOP TIME:

CRITICAL STEP EXPLANATIONS:

STEP #

Explanation 2

This step must be performed to establish containment closure.

3 This step must be performed to establish containment closure.

8 This step must be performed to establish containment closure.

19 This step must be performed to establish containment closure.

23 This step must be performed to establish containment closure CRO-506 Page l4of 15

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

Unit 1 was on normal decay heat removal mode. Decay heat removal (DHR) on Unit I was lost due to LPI pump cavitation.

Plant conditions:

LPI pumps have been tripped with suctions aligned in a normal DHR alignment..

The RCS loops are full and intact.

The Steam Generators are available for heat transfer.

RCPsaresecured.

HPI is secured.

RCS temperature was 120°F when LPI was secured. RCS pressure is 50 psig.

INITIATING CUES:

The Control Room SRO directs you to establish Reactor Building Closure per AP/1/A/1 700/26,.1 (Establishing RB Containment Closure), starting at step 6.

CRO-604 Page 1 of 10 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE CRO-604 ENERGIZING MFB FROM CT 4 USING LIVE BUS TRANSFER CANDIDATE EXAMINER

CRO-604 Page 2 of 10 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Energizing MFBs From CT-4 Using Live Bus Transfer Alternate Path:

No Facility JPM #:

CRO-604 KIA Rating(s):

System: 062 K/A:

A4.01 Rating:

3.3/3.1 Task Standard:

MFBs are energized from CT-4 using a live bus transfer per procedure.

Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator X

In-Plant Perform X

Simulate

References:

0P101A111061019 (Keowee Hydro At Oconee) End. 4.11 (Energizing MFB From CT 4 Using Live Bus Transfer)

Validation Time: 15 minutes Time Critical: NO Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

NAME SIGNATURE DATE COMM ENTS

SIMULATOR OPERATOR INSTRUCTIONS:

1.

Recall SNAP 205

2. Ensure all breaker flags are set to current plant conditions..
3. Goto RUN CRO-604 Page 3 of 10

C R0-604 Page 4 of 10 Tools/EguipmentlProcedures Needed:

OP/0/A/1 106/019 (Keowee Hydro At Oconee) End. 4.11 (Energizing MFB From CT 4 Using Live Bus Transfer)

READ TO OPERATOR DIRECTION TO TRAINEE:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

Unit I is in MODE 5 Troubleshooting of 6900 kv and 4160 kv electrical systems is in progress OP/0/A11106/019 Enclosure 4.11 (Energizing MFB From CT 4 Using Live Bus Transfer) is complete up to step 2.4 INITIATING CUES:

The Control Room SRO directs you to energize Unit ls MFBI and MFB2 from CT4 via KHU-2 utilizing Enclosure 4.11 (Energizing MFB From CT 4 Using Live Bus Transfer) of OP/0/A/1 106/019 beginning at Step 2.4.

CRO-604 Page 5 of 10 START TIME:

CAUTION:

DO NOT allow closure of SLI and SKi OR SL2 and SK2 simultaneously. When CT-4 and CT-5 AUTO/MAN transfer switches are in MAN, this configuration is not prevented by SAT interlock.

UNSAT STEP 1:

Step 2.4 Energize 4160V Standby Buses:

Step 2.4.1 Notify all three Units that the Standby Bus is about to be powered from CT 4.

STANDARD:

The candidate communicates to all three units, the Standby Bus is about to be powered from CT-4.

Examiner Cue: As student attempts to make first call, inform him that all 3 Units have been notified.

COMMENTS:

NOTE:

AUTO/MAN transfer switches are three position switches.

Take care to ensure correct position is selected prior to continuina.

STEP 2:

Step 2.4 (cont)

Energize 4160V Standby Buses:

2.4.2

  • Place CT 4 BUS 1 AUTO/MAN switch in MAN.

2.4.3

  • Place STBY BUS 1 SYNCHRONIZING SWITCH to ON.

2.4.4

  • Close 5K 1 CT 4 STBY BUS 1 FEEDER breaker.

2.4.5 Verify 4160V on STANDBY BUS I STANDBY BUS I VOLTS.

(not critical) 2.4.6 Place STBY BUS I SYNCHRONIZING SWITCH to OFF.

2.4.7 Place CT4 BUS I AUTO/MAN switch in AUTO.

STANDARD:

The candidate places the listed switches to the required position in the order specified.

CRO-604 Page 6 of 10

  • CRITICAL STEP SAT UNSAT COMMENTS:

C RO-604 Page 7 of 10

  • CRITICAL TASK NOTE:

AUTO/MAN transfer switches are three position switches. Take care to ensure correct position is selected prior to continuing.

SAT STEP 3:

Step 2.4 (cont)

Energize 4160V Standby Buses:

UN SAT 2.4.8

  • Place CT4 BUS 2 AUTO/MAN switch in MAN.

2.4.9

  • Place STBY BUS 2 SYNCHRONIZING SWITCH to RON.

2.4.10

  • Close SK 2 CT4 STBY BUS 2 FEEDER.

2.4.11 Verify 4160V on STANDBY BUS 2 STANDBY BUS 2 VOLTS.

(not critical) 2.4.12 Place STBY BUS 2 SYNCHRONIZING SWITCH to OFF.

2.4.13 Place CT 4 BUS 2 AUTO/MAN switch in AUTO.

STANDARD:

The candidate places the listed switches to the required position in the order specified.

COMMENTS:

CRO-604 Page 8 of 10 CAUTION:

El (1,2,3) E2 (1,2,3) will NOT open automatically when the SI

  • CRITICAL STEP (1,2,3) or S2 (1,2,3) breakers are closed. Minimize time during which both of these sets of breakers are closed. CT 1, 2, or 3 Transformer will be paralleled with CT4 from the time the first 5 SAT breaker is closed until the last E breaker is opened.

STEP 4:

Step 2.5 UNSAT For the desired Oconee Units, perform a Live Bus transfer from the Startup Transformer (CT1, CT2, or CT3) to the Standby Bus:

A.

  • Place STANDBY 1 AUTO/MAN switch in MAN.

B.

  • Place STANDBY 2 AUTO/MAN switch in MAN.

C.

Place MFB I AUTO/MAN switch in MAN.

D.

Place MFB 2 AUTO/MAN switch in MAN.

E.

  • Open El 1 (MFB1 STARTUP FDR).

F.

  • CIose Si 1 (STBY BUS1 TO MFBI).

G.

  • Open E2 1 (MFB2 STARTUP FDR).

H.

  • Close S2 (STBY BUS2 TO MFB2).

I.

Place STANDBY 1 AUTO/MAN switch in AUTO.

J.

Place STANDBY 2 AUTO/MAN switch in AUTO.

STANDARD:

The candidate places the listed switches to the required position in the order specified.

COMMENTS:

END TASK STOP TIME:

CRITICAL STEP EXPLANATIONS:

STEP #

Explanation 2

Required to energize MFBs from CT-4 3

Required to energize MFBs from CT-4 4

Required to energize MFBs from CT-4 CRO-604 Page 9 of 10

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

Unit I is in MODE 5 Troubleshooting of 6900 kv and 4160 kv electrical systems is in progress OP/0/AI1 106/019 Enclosure 4i I (Energizing MFB From CT 4 Using Live Bus Transfer) is complete up to step 2.4 INITIATING CUES:

The Control Room SRO directs you to energize Unit ls MFBI and MFB2 from CT4 via KHU-2 utilizing Enclosure 4.11 (Energizing MFB From CT 4 Using Live Bus Transfer) of OP/0/A/1 106/019 beginning at Step 2.4.

CRO-703 Page 1 of 8 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE CRO-703 REMOVAL OF ES SUBSYSTEM 2 FROM SERVICE CANDIDATE EXAMINER

CRO-703 Page 2 of 8 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Remove ES Subsystem 2 from service.

Alternate Path:

No Facility JPM #:

New KIA Rating(s):

System:

016 K/A:

A4.01 Rating:

2.9*12.8*

Task Standard:

The candidate will remove the ES Subsystem 2 from service in accordance with 0P111A111051014 Enclosure 4.9 (Removal and restoration of ES channels) beginning with step 3.3.

Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator X

In-Plant Perform X

Simulate

References:

OP/1/A11105/014 Enclosure 4.9 (Removal and restoration of ES channels)

Validation Time: 10 mm.

Time Critical: No Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

I NAME SIGNATURE DATE Comments

CRO-703 Page 3 of 8 SIMULATOR OPERATOR INSTRUCTIONS:

1. Recall IC-41
2. Verify the Examiner has the ES cabinet key (#317) and both ES bypass keys (#316).
3. Ensure all breaker flags are in the current plant condition.
4. Got0RUN.

CRO-703 Page 4 of 8 ToolslEguipmentlProcedures Needed:

OPI1IAI11O5/014 Enclosure 4.9 Removal and restoration of ES channels READ TO OPERATOR DIRECTIONS TO STUDENT:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

The Unit I Reactor is at 100% power.

A failure has occurred in ES subsystem 2 that will require ALL the subsystem 2 to be removed from service.

The failure did NOT result in an actuation of any ES equipment nor did it result in any change in reactor power.

OP/Ill 105/014 Enclosure 4.9 has been completed up to step 3.3.

INITIATING CUE:

The Control Room SRO directs you to remove ES Subsystem 2 from service per OP/I/A/I 105/014 Enclosure 4.9 beginning with step 3.3.

START TIME:

STEP 1:

Step3.3 If removal of any or all of Only ES subsystem 2 channels from service is required, perform Section 6 Removal of Only ES Subsystem 2 SAT STANDARD:

Candidate proceeds to Section 6 COMMENTS:

STEP2:

Step6.l:

IF Unit 1 ES Subsystem 2 is NOT required per TS 3.3.5 and 3.3.7, SAT perform the following to remove from service any or all of only Unit I ES Subsystem 2 channels.

STANDARD:

Candidate determines that ES Subsystem 2 is not required by TS 3.3.5 UNSAT and 3.3.7 COMMENTS:

STEP 3:

Step 6.1.1 IF Unit 1 ES Subsystem 1 is required per TS 3.3.5 and 3.3.7, verify the following:

SAT Voter Odd I NOT bypassed (1SA-7)

Voter Even 1 NOT bypassed (1SA-7)

ES channel Al operable or tripped (1 SA-7)

UNSAT ES channel Bl operable or tripped (1SA-7)

ES channel Cl operable or tripped (1SA-7)

STANDARD:

The candidate determines that the Unit 1 ES Subsystem is required per TS 3.3.5 and 3.3.7 and verifies there are no alarms present on ISA-7.

Examiner cue: Student may elect to perform a STAT alarm test to help ensure no alarms are present on ISA-7. If asked, give him permission (as CR SRO) to perform alarm test. (The other RO will be required to help perform the test).

COMMENTS:

CRO-703 Page 5 of 8

CRO-703 Page 6 of 8 STEP 4:

Step 6.1.2.A Declare Unit 1 ES Subsystem 2 channels inoperable SAT STANDARD:

Candidate reports that procedure requires declaration of ES Subsystem 2 channels inoperable Cue: Acknowledge Unit I ES Subsystem 2 channel inoperable.

UNSAT COMMENTS:

STEP 5:

Step 6.1.2.B Obtain MAN BYPASS 2 Key #316 (2 keys are required to bypass both SAT voters).

STANDARD:

Candidate obtains correct keys (examiner provides)

UNSAT Cue: Provide the candidate with the correct keys.

COMMENTS:

STEP 6:

Step 6.1.2.C CRITICAL STEP IF bypassing Odd Voter 2, place MAN BYPASS 2 keyswitch in BYP.

(Cabinet 12)

SAT STANDARD:

Student places the MAN BYPASS 2 keyswitch in Cabinet 12 in the BYP position UNSAT COMMENTS:

STEP 7:

Step 6.1.2.D CRITICAL STEP IF bypassing Even Voter 2, place MAN BYPASS 2 keyswitch in BYP.

(Cabinet 14)

SAT STANDARD:

Student places the MAN BYPASS 2 keyswitch in Cabinet 14 in the BYP position UNSAT COMMENTS:

END OF TASK TIME STOP:

CRO-703 Page 7 of 8 CRITICAL STEP EXPLANATIONS STEP #

Explanation 6

This step is critical because it is part I of removing all of ES Subsystem 2 from service 7

This step is critical because it is part 2 of removing all of ES Subsystem 2 from service

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

The Unit I Reactor is at 100% power.

A failure has occurred in ES subsystem 2 that will require ALL the subsystem 2 to be removed from service.

The failure did NOT result in an actuation of any ES equipment nor did it result in any change in reactor power.

OP/i/l 105/014 Enclosure 4.9 has been completed up to step 3.3.

INITIATING CUE:

The Control Room SRO directs you to remove ES Subsystem 2 from service per OP/I/A/i 105/014 Enclosure 4.9 beginning with step 3.3.

CRO-801 Page 1 of 13 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE CRO-801 ALIGN INTAKE CANAL FOR RECIRC ON DAM FAILURE CANDIDATE EXAMINER

CRO-801 Page 2 of 13 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

ALIGN INTAKE CANAL FOR RECIRC ON DAM FAILURE Alternate Path:

No Facility JPM #:

CRO-801 KIA Rating(s):

System: 075 K/A:

A2.01 Rating:

3.0*13.2 Task Standard:

COW Intake Canal is aligned for recirc Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator X

In-Plant Perform X

Simulate

References:

API1IAII700I13 (CCW Dam Failure)

Validation Time: 15 mm.

Time Critical: No Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

I NAME SIGNATURE DATE Comments

CRO-801 Page 3 of 13 SIMULATOR OPERATOR INSTRUCTIONS:

1. Recall snap 221
2. Import simulator files for CRO-801
3. Ensure all breaker flags are set to current plant conditions.
4. Go to RUN as directed by examiner
5. When asked to dispatch an operator to close the breaker for ICCW-12 (at step 16)

Fire Timer #1 and inform student that using time compression the breaker is closed.

CRO-801 Page 4 of 13 ToolsIEguipmentlProcedures Needed:

AP/1 IA/I 700/013 (Dam Failure)

READ TO OPERATOR DIRECTIONS TO STUDENT:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

Security reports that a failure of the Newry Dam has occurred.

The CCW Intake Canal is intact Subsequent Actions of AP/I/A/1 700/013 (Dam Failure) have been completed up to step 4.4.

INITIATING CUE:

The Control Room SRO directs you to align the CCW Intake Canal for recirc, using the 1C CCW pump, beginning at step 4.4 of AP/1/A/1 700/013.

CRO-801 Page 5 of 13 START TIME:

STEP 1:

Step 4.4 CRITICAL STEP Depress the CCW DAM FAILURE pushbutton.

STANDARD:

The CCW DAM FAILURE pushbutton is located by the student on SAT 1AB3 and depressed.

COMMENTS:

UNSAT STEP 2:

Step 4.5 Dispatch an individual to the area of the dam failure to report damage to the Control Rooms.

SAT STANDARD:

An individual is dispatched to report damage to the Control Rooms.

Booth Cue: When asked, report that an Individual has been dispatched to the UNSAT Newry dam COMMENTS:

STEP 3:

Step 4.6 GO TO step 4.49 SAT STANDARD:

Student goes to step 4.49 COMMENTS:

UNSAT STEP 4:

Step 4.49

  • CRITICAL STEP
  • Stop aM RCPs Notify the CR SRO that for EOP purposes, RCPs should be considered SAT unavailable for restart until LPSW is restored STANDARD:
  • The control switches for RCPs IAI, 1A2, 1 Bi and I B2 are located by the student on 1AB1 and rotated counter-clockwise to the TRIP position.

UNSAT CR SRO notified of RCP status COMMENTS:

CRO-801 Page 6 of 13 STEP 5:

Step 4.50 Stop CCW pumps.

SAT STANDARD:

1 A, 1 B, IC, and 1 D CCW Pump switches are located by the student on 1AB3.

Student ensures all CCW pump Red ON lights are extinguished and White OFF lights are illuminated.

UNSAT COMMENTS:

STEP 6:

Step 4.51 Open 1CCW-1-6 (WATERBOX EMER DISCH VALVES).

SAT STANDARD:

Student locates ICCW-1-6 (WATERBOX EMER DISCH) control and indication on IAB3 and ensures red OPEN indication is illuminated and green CLOSED indication is extinguished.

UNSAT COMMENTS:

STEP 7:

Step 4.52 Verifies a Condenser Outlet valves indicate closed (GD AP13):

SAT 1 CCW-20 (Condenser 1A1 Outlet) (O1D0273)

I CCW-21 (Condenser 1A2 Outlet) (O1D0275) 1 CCW-22 (Condenser 1 Bi Outlet) (01 D0277) 1 CCW-23 (Condenser 1 B2 Outlet) (01 D0279)

UNSAT 1 CCW-24 (Condenser 1C1 Outlet) (O1D0281) 1 CCW-25 (Condenser 1C2 Outlet) (O1D0283)

STANDARD:

The student monitors the Operator Aid Computer to verify the following:

1 CCW-20 (Condenser 1A1 Outlet) closed (01D0273) 1 CCW-21 (Condenser 1A2 Outlet) closed (O1D0275) 1 CCW-22 (Condenser 1 Bi Outlet) closed (01 D0277) 1 CCW-23 (Condenser 1 B2 Outlet) closed (01 D0279) 1 CCW-24 (Condenser 1C1 Outlet) closed (O1D0281) 1 CCW-25 (Condenser 1C2 Outlet) closed (01D0283)

COMMENTS:

CRO-80 1 Page 7 of 13 STEP 8:

Step 4.53 Dispatch an operator to place all condenser outlet valves in HAND.

SAT 1 CCW-20 1CCW-21 1CCW-22 1CCW-23

_UNSAT 1 CCW-24 1CCW-25 STANDARD:

An operator is dispatched to place the condenser outlet valves in HAND.

Booth Cue: When called, acknowledge that an operator has been dispatched to place the valves in HAND.

COMMENTS:

STEP 9:

Step 4.54 Verify CCW-8 is open.

SAT STANDARD:

CCW-8 switch and indication is located by the student on 2AB3 verifying red OPEN indication illuminated and green CLOSED indication extinguished.

UNSAT COMMENTS:

STEP 10:

Step 4.55 Notify Unit 2 that emergency CCW siphon flow has been established on Uniti.

SAT STANDARD:

Unit 2 Control Room is notified that siphon flow has been established on Unit 1.

UNSAT Examiner/Booth Cue: When candidate contacts Unit 2, acknowledge the notification that CW siphon flow has been established on Unit 1.

COMMENTS:

CRO-801 Page 8 of 13 STEP 11:

Step 4.56 Dispatch operator(s) to perform Enclosure 5.2 (CCW Inventory Conservation).

SAT STANDARD:

Operator(s) are dispatched to perform Enclosure 5.2.

Booth Cue: When contacted by the candidate, acknowledge that operators will UNSAT perform Enclosure 5.2 COMMENTS:

STEP 12:

Step 4.57 IAAT Unit 2 CR has directed Unit 1 to supply CCW recirculation, THEN perform Steps 4.57-4.72 to start one CCW Pump and establish SAT recirculation.

STANDARD:

Student continues to step 4.57.

U N SAT Cue: Unit 2 Control Room has directed Unit I to supply CCWrecirculation.

COMMENTS:

STEP 13:

Step 4.58 Determine which CCW Pump will be started.

SAT STANDARD:

The student determines from the turnover that the 1 C CCWP will be started COMMENTS:

UNSAT STEP 14:

Step 4.59 Place aH CCW Pump switches in the trip position.

SAT STANDARD:

Student places all Unit 1 CCW Pump switches in the tripped position.

COMMENTS:

UNSAT

CRO-801 Page 9 of 13 STEP 15:

Step 4.60 Verify the 1A or lB CCW Pump is to be started.

SAT STANDARD:

Student determines from initiating cue that the IC CCW pump will be started and goes to the RNO column and therefore goes to step 4.63.

COMMENTS:

UNSAT STEP 16:

Step 4.63 Verify both of the following CCW pump discharge valves are closed.

1CCW-12 1CCW-13 STANDARD:

The student notes that the discharge valve for the I C CCW pump (1CCW-12) is not closed and proceeds to the RNO.

UNSAT COMMENTS:

STEP 17:

Step 4.63 RNO

  • CRITICAL STEP Locally close the discharge valve from the breaker switch for 1CCW-12 (Unit 1 Equipment room) (1CCW-13 is already closed)

SAT STANDARD:

The student dispatches an operator to locally close 1CCW-12 from the breaker switch (1XS3-2E).

UNSAT Booth Cue: When an operator is dispatched, fire TIMER #1, then inform candidate that ICCW-12 is closed (use time compression)

COMMENTS:

STEP 18:

Step 4.64

  • CRITICAL STEP Start the selected CCW Pump.

SAT STANDARD:

  • The student starts 1 C CCW pump by rotating the control switch to the CLOSE position.

The student verifies the 1 C CCW Pump White light OFF and Red RUN UNSAT lights ON and that pump amps are normal for this plant configuration (see procedure note).

COMMENTS:

CRO-801 Page 10 of 13 STEP 19:

Step 4.65 Verify the started CCW Pump Discharge valve opened.

SAT STANDARD:

The IC CCW Pump Discharge valve (CCW-12) Red OPEN light Comes ON and the Green CLOSED light goes OFF.

COMMENTS:

UNSAT STEP 20:

Step 4.66 Ensure CCWP LOAD SHED DEFEAT switch is positioned to a running CCWP.

SAT STANDARD:

The student ensures the CCWP LOAD SHED DEFEAT switch is in the 1C CCW Pump position UNSAT COMMENTS:

STEP 21:

Step 4.67 Verify CCW-9 opens.

SAT STANDARD:

The student locates CCW-9 switch and indication on 2AB3 verifying red OPEN indication illuminated and green CLOSED indication extinguished.

UNSAT COMMENTS:

STEP 22:

Step 4.68 Verify CCW-8 is closed.

SAT STANDARD:

CCW-8 switch and indication are located by the student on 2AB3 verifying green CLOSED indication illuminated and red OPEN indication extinguished.

UNSAT COMMENTS:

STEP 23:

Step 4.69 Verify an operator has been dispatched to open 1 DP-F5C (CCW-8 BKR (EMERG CCW DISCH TO TAILRACE)).

SAT STANDARD:

An operator has not yet been dispatched so the student proceeds to the RNO.

UNSAT COMMENTS:

CRO-801 Page 11 of 13 STEP 24:

Step 4.69 RNO Dispatch an operator to open I DP-F5C (CCW-8 BKR (EMERG CCW DISCH TO TAILRACE)).

SAT STANDARD:

Operator dispatched.

Booth Cue: When contacted, inform the student that an operator has been UNSAT dispatched to open the breaker for CCW-8 COMMENTS:

STEP 25:

Step 4.70 Ensure the discharge valves on a stopped CCW Pumps are closed.

SAT CCW-10 (1A CCW PUMP DISCHARGE VLV)

CCW-1 1 (1 B CCW PUMP DISCHARGE VLV)

CCW-12 (1C CCW PUMP DISCHARGE VLV)

UNSAT STANDARD:

CCW pump discharge valve indications are located by the student on 1AB3.

Valves associated with tripped CCW pumps (white lights lit) will have the green CLOSED indication illuminated.

COMMENTS:

STEP 26:

Step 4.71 Notify Unit 2 and 3 to ensure all Unit 2 and 3 CCW pump discharge valves are closed.

SAT STANDARD:

Unit 2 and 3 are notified to ensure their CCW Pump Discharge valves are closed.

UNSAT Booth Cue: Unit 2 and Unit 3 report that their CCW pump discharge valves are closed.

Examiner Cue: Another operator will continue with this procedure COMMENTS:

END TASK TIME STOP:

CRO-801 Page 12 of 13 CRITICAL STEP EXPLANATIONS STEP #

Explanation I

This step is critical because depressing this pushbutton trips all operating CCW Pumps and sets up system logic for CCW recirculation flow.

4 This step is critical because RCPs must be stopped to reduce primary heat load.

17 This step is critical because it provides the necessary head to establish CCW recirculation flow in later steps.

18 This step is critical because the pump provides the necessary recirculation flow.

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

Security reports that a failure of the Newry Dam has occurred.

The CCW Intake Canal is intact Subsequent Actions of AP/IIA/1700113 have been completed up to step 4.4.

INITIATING CUE:

The Control Room SRO directs you to align the CCW Intake Canal for recirc, using the IC CCW pump, beginning at step 4.4 of APII IA/I 700/13.

REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE N LO-200 ALIGN HPI PUMP SUCTION TO BWST DURING A BLACKOUT N LO-200 Page 1 of 9 CANDIDATE EXAMINER

NLO-200 Page 2 of 9 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Align HPI Pump Suction to BWST During a Blackout Alternate Path:

No Facility JPM #:

N LO-200 KIA Rating(s):

System: APE 022 K/A:

G2.4.35 Rating:

3.8/4.0 Task Standard:

HPI Pump suction is correctly aligned to BWST per the EOP End. 5.7, HPI Pump Operations from ASW Pump Switchgear.

Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator In-Plant X

Perform Simulate X

References:

EOP End. 5.7, HPI Pump Operations from ASW Pump Switchgear Validation Time: 20 minutes Time Critical: NO Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

/

NAME SIGNATURE DATE COMMENTS

None SIMULATOR OPERATOR INSTRUCTIONS:

NLO-200 Page 3 of 9

N LO-200 Page 4 of 9 ToolslEquipmentlProcedures Needed:

EOP End. 5.7, HPI Pump Operations from ASW Pump Switchgear READ TO OPERATOR DIRECTION TO TRAINEE:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

Blackout is in progress on Unit 2 Blackout Tab of the EOP is in progress INITIATING CUES:

The SRO directs you to perform Enclosure 5.7 (HPI Pump Operation from ASW Pump Switchgear) and align HPI pump suction to the BWST.

START TIME:

NLO-200 Page 5 of 9 STEP 1:

STANDARD:

Step I Close 2HP-139 (RCP SEAL FLOW CONTROL OUTLET) (A-3-327, CRD Filter Rm)

Locate 2HP-139 in Unit 2s CRD Filter Room and indicates engaging the lever and rotating handwheel clockwise until it reaches a hard stop.

Threaded valve stem will become more visible as the handwheel is rotated.

CRITICAL STEP SAT UNSAT Cue: Valve has reached a hard stop.

COMMENTS:

STEP 2:

Step 2 Verify 1 gpm cooling water flow to HPI pump motor coolers on local indication (HPI Pump Rm):

SAT UNSAT 2A HPI Pump (2LPS-PS-1013) 2B HPI Pump (2LPS-PS-1014)

Cue:

Indicate to the candidate that cooling water flow to the 2A and 2B HPI pumps coolers is 2 gpm.

STANDARD:

Locate the local indication of HPI pump motor coolers flow located on the west wall of the HPI Pump Room and determine that flow is 1 gpm.

NOTE Cooling water to HPI Motor Coolers will be supplied by the following:

HPSW via head from EWST Station ASW Pump, if operating, via 2CCW-265 COMMENTS:

COMMENTS:

GO TO applicable step based on HP! pump suction source specified by Control Room:

-J Desired Suction Applicable Step Source BWST 4

LDST 7

SEP 9

STEP 4:

Step 4 Open the following (A-i -118, 1 &2 HP! Hatch Area, East wall):

2HP-24 (2A HP! BWST SUCTION) 2HP-25 (2B HPI BWST SUCTION)

CRITICAL STEP SAT UNSAT STANDARD:

Proceed to the East wall of the I &2 HP! Hatch Area and open 2HP-24 and 2HP-25 by engaging the hand wheel and turning counterclockwise until the valve reaches a hard stop. Handwheel is engaged by pushing the lever down and turning the handwheel.

Cue: Indicate that the valve has reached a hard stop.

STEP 3:

Step 3 NLO-200 Page 6 of 9 SAT UNSAT STANDARD:

Determine the suction GO TO Step 4.

source is the BWST based on the cue sheet and COMMENTS:

NLO-200 Page 7 of 9 STEP 5:

Step 5 Proceed to East Penetration Room and notify Control Room of the following:

SAT HPI suction aligned to BWST HPI pump cooling water status UNSAT Available to throttle 2HP-26 STANDARD:

Proceed to East Penetration Room...

Cue:

Once the candidate reaches the Unit 2 penetration room, inform the candidate that another operator will go to the penetration room COMMENTS:

END TASK STOP TIME:

NLO-200 Page 8 of 9 CRITICAL STEP EXPLANATIONS:

STEP #

Explanation 1

This step is required to prevent damaging the RCP seals when the HPI pump starts.

4 This step is required to align the BWST to the HPI pump suction.

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

Blackout is in progress on Unit 2 Blackout Tab of the EOP is in progress INITIATING CUES:

The SRO directs you to perform Enclosure 5.7 (HPI Pump Operation from ASW Pump Switchgear) and align HPI pump suction to the BWST.

N LO-032 Page 1 of 10 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE N LO-032 Align Vacuum Pumps to a Units Vacuum System CANDIDATE EXAMINER

NLO-032 Page 2 of 10 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Align Vacuum Pumps to a Units Vacuum System Alternate Path:

No Facility JPM #:

NLO-032 KIA Rating(s):

System: APE 051 K/A:

G2.1.20 Rating:

4.6/4.6 Task Standard:

Vacuum pumps are aligned to designated unit Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator In-Plant X

Perform Simulate X

References:

AP/1/A/1700/027 (Loss of Vacuum)

Validation Time: 10 minutes Time Critical: NO Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

I NAME SIGNATURE DATE COMM ENTS

None SIMULATOR OPERATOR INSTRUCTIONS:

NLO-032 Page 3 of 10

NLO-032 Page 4 of 10 Tools/Equipment/Procedures Needed:

APIIIA!17001027 (Loss of Vacuum) Enclosure 5.1 (Main Vacuum Pump Alignment)

READ TO OPERATOR DIRECTION TO TRAINEE:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications. I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

All three units are operating at 100% power.

Unit 2, which is operating with a steam generator tube leak, experiences a loss of vacuum, requiring that the vacuum pumps be placed in service immediately to prevent a turbine trip on low vacuum, and subsequent loss of the turbine bypass valves.

INITIATING CUES:

A, B, and C Main Vacuum Pumps are operating.

The control room BOP directs you to perform Enclosure 5.1 (Main Vacuum Pump Alignment),

of AP/1/A/1 700/027 (Loss of Vacuum) and align A, B, and C vacuum pumps to Unit 2.

START TIME:

Step 1 Candidate locates the pre-staged procedure and proceeds to verify any Main Vacuum Pump is operating.

STANDARD:

A Main Vacuum Pump is verified to be operating.

Cue: Once candidate locates the pre-staged End. 5.1, provide the attached working copy to use for the JPM.

Cue: Once the candidate locates the pumps, indicate that each Main Vacuum Pump is operating.

COMMENTS:

NLO-032 Page 5 of 10 Pump q

Gauge Location A

OLPS PG 1053 T-11K25, SE B

OLPS PG 1054 T-11K26, SE C

OLPS PG 1055 T-1/K28, SE STANDARD:

Seal water pressure verified 10 psig for each Main Vacuum Pump.

Pump A GAUGE LOCATION T-11K25, SE Pump B GAUGE LOCATION T-1/K26, SE Pump C GAUGE LOCATION T-11K28, SE Determine Pump B is < 10 psig and perform the RNO step.

Cue: Inform student that A and C Main Vacuum Pump INDICATES 14 psig seal water pressure.

Indicate that B Main Vacuum Pump INDICATES 0.0 psig seal water pressure.

COMMENTS:

STEP 1:

SAT UNSAT STEP 2:

Step 2 Verify all operating Main Vacuum Pumps seal water pressure 10 psig:

SAT U N SAT

NLO-032 Page 6 of 10 STEP 3:

Step 2 RNO CRITICAL STEP IF Main Vacuum Pump A seal water pressure is < 10 psig, SAT THEN throttle LPSW-269 (A MAIN VACUUM PUMP SOLENOID

OUTLET) as necessary to establish 10 psig (T-11J251K25).

IF Main Vacuum Pump B seal water pressure is < 10 psig, UNSAT THEN throttle LPSW-273 (B MAIN VACUUM PUMP SOLENOID

OUTLET) as necessary to establish 10 psig (T-11J261K26).

IF Main Vacuum Pump C seal water pressure is < 10 psig, THEN throttle LPSW-277 (C MAIN VACUUM PUMP SOLENOID OUTLET) as necessary to establish 10 psig (T-1/J28/K28).

STANDARD:

Locates and rotates counterclockwise the handwheel for LPSW-273 (B MAIN VACUUM PUMP SOLENOID OUTLET) as necessary to establish 10 psig (T-1/J26/K26).

Cue: After candidate has throttled open on LPSW-273 indicate that Main Vacuum Pump B seal water pressure is 14 psig COMMENTS:

STEP 4:

Step 3 CRITICAL STEP Close the drain valve on all operating Main Vacuum Pumps:

SAT V-187 (A MAIN VACUUM PUMP DRAIN) (T-11K25 SE)

V-188 (B MAIN VACUUM PUMP DRAIN) (T-1/K26 SE)

V-189 (C MAIN VACUUM PUMP DRAIN) (T-1/K28 E)

UNSAT STANDARD:

The candidate locates and closes the following drain valves on the operating Main Vacuum Pumps.

V-I 87 (MVP A Drain)

V-188 (MVP B Drain)

V-189 (MVP C Drain)

COMMENTS:

N LO-032 Page 7 of 10 CAUTION CRITICAL STEP Valving in a Main Vacuum Pump that is NOT pulling 24 Hg may increase the loss of vacuum.

SAT STEP 5:

Step 4

_UNSAT IAAT a Main Vacuum Pump is pulling 24 Hg vacuum (gauges at T 1 1K26),

THEN open the associated inlet valve:

V-26 (A MAIN VACUUM PUMP INLET) (T-1/K26 E)

V-28 (B MAIN VACUUM PUMP INLET) (T-1/K27 NE)

V-30 (C MAIN VACUUM PUMP INLET) (T-1/K28/K29 E)

STANDARD:

The candidate locates and opens the following inlet valves on the operating Main Vacuum Pump.

V-26 (Main Vacuum Pump A Inlet)

V-28 (Main Vacuum Pump B Inlet)

V-30 (Main Vacuum Pump C Inlet)

Cue:

When candidate locates pressure gauges, indicate a pressure reading of 26s Hg.

COMMENTS:

NOTE This enclosure is used to support loss of condenser vacuum on any Oconee unit.

Main Vacuum Pumps may already be aligned to another unit or need to be coordinated SAT and aligned to more than one unit.

STEP 6:

Step 5 UNSAT IAAT any Main Vacuum Pump is pulling 24 Hg vacuum,

AND Unit 1 requires alignment...

STANDARD:

Determines that Unit I does not need to be aligned and continues to step 6.

COMMENTS:

NLO-032 Page 8 of 10 NOTE CRITICAL STEP This enclosure is used to support loss of condenser vacuum on any Oconee unit.

Main Vacuum Pumps may already be aligned to another unit or need to be coordinated SAT and aligned to more than one unit.

STEP 7:

Step 6 UNSAT IAAT any Main Vacuum Pump is pulling 24 Hg vacuum,

AND Unit 2 requires alignment, THEN ensure the following are open:

V-25 (VACUUM PUMP HDR TIE TO UNITS 2/3) (T-1/J29 W) 2V-22 (UNIT 2 VACUUM HDR TIE TO VACUUM PUMP) (T.i/J29 5) 2V-24 (UNIT 2 VACUUM HDR TIE TO VACUUM PUMP) (T-1/J29 S)

STANDARD:

Candidate indicates they will:

Rotate V-25 in the counterclockwise direction Rotate 2V-22 in the counterclockwise direction Rotate 2V-24 in the counterclockwise direction Cue: As each valve is rotated, indicate the valve reaches a hard stop.

Cue: Once all 3 valves have been opened, inform the candidate that another operator will continue with this enclosure.

COMMENTS:

END TASK STOP TIME:

NLO-032 Page 9 of 10 CRITICAL STEP EXPLANATIONS:

STEP #

Explanation 3

Step is required to ensure proper operation of vacuum pumps.

4 Step is required to ensure proper operation of vacuum pumps.

5 Establish proper alignment to provide adequate suction pressure to the Main Vacuum Pumps 7

Establish proper alignment to provide suction to the Main Vacuum Pumps

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

All three units are operating at 100% power. Unit 2, which is operating with a steam generator tube leak, experiences a loss of vacuum, requiring that the vacuum pumps be placed in service immediately to prevent a turbine trip on low vacuum, and subsequent loss of the turbine bypass valves.

INITIATING CUES:

A, B, and C Main Vacuum Pumps are operating.

The control room BOP directs you to perform Enclosure 5.1 (Main Vacuum Pump Alignment), of AP111A117001027 (Loss of Vacuum) and align A, B, and C vacuum pumps to Unit 2.

REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE NLO-700 RESTORATION OF ICS AUTO POWER NLO-700 fnl Page 1 of 9 CANDIDATE EXAMINER

NLO-700 fnl Page 2 of 9 REGION II INITIAL LICENSE EXAMINATION JOB PERFORMANCE MEASURE Task:

Restoration of ICS AUTO Power Alternate Path:

Yes Facility JPM #:

NLO-700 KIA Rating(s):

System:

BW/A02 K/A:

AA1.1 Rating:

4.0/3.8 Task Standard:

ICS AUTO power is restored per API1IA/1 700/023, Loss of ICS Power.

Preferred Evaluation Location:

Preferred Evaluation Method:

Simulator In-Plant X

Perform Simulate X

References:

AP/1/A/1700/023 (Loss of ICS Power) Enclosure 5.2 (Restoration of ICS AUTO Power)

Validation Time: 16 minutes Time Critical: NO Candidate:

Time Start:

NAME Time Finish:

Performance Rating:

SAT UNSAT Performance Time:

Examiner:

/

NAME SIGNATURE DATE COMM ENTS

SIMULATOR OPERATOR INSTRUCTIONS:

NONE NLO-700 fnl Page 3 of 9

NLQ-700 fnl Page 4 of 9 Tools/Equipment/Procedures Needed:

AP/1 IA/i 700/023 (Loss of ICS Power) Enclosure 5.2 (Restoration of ICS AUTO Power)

READ TO OPERATOR DIRECTION TO TRAINEE:

I will explain the initial conditions, and state the task to be performed. All control room steps shall be performed for this JPM, including any required communications.

I will provide initiating cues and reports on other actions when directed by you. Ensure you indicate to me when you understand your assigned task. To indicate that you have completed your assigned task return the handout sheet I provided you.

INITIAL CONDITIONS:

Unit I operating at 100% power I SA-2/B-I 1 (ICS AUTO POWER FAILURE) is actuated INITIATING CUES:

The Control Room SRO directs you to use AP111A117001023 (Loss of ICS Power) Enclosure 5.2 (Restoration of ICS AUTO Power) to restore ICS AUTO power on Unit I.

NLO-700 fnl Page 5 of 9 START TIME:

STEP 1:

Step 1 Verify the following breakers closed (Unit 1 Cable Rm):

1KRA breaker #1 (IOOA IP, POWER PANELBOARD 1KI)

SAT 1 KI BREAKER #1 (30A I P, AUTO POWER (ICS))

UN SAT STANDARD:

Locate 1 KRA panel board and breaker #1 and verify it is closed.

Cue: Indicate to the candidate that IKRA breaker #1 is CLOSED.

Locate I KI panel board and breaker #1 and verify it is closed.

Cue: Indicate to the candidate that 1K! breaker #1 is tripped OPEN.

Continue Step I RNO.

COMMENTS:

STEP 2:

Step 1 RNO Reset and close the affected breakers (Unit 1 Cable Rm):

SAT 1 KI BREAKER #1 (30A 1 P, AUTO POWER (ICS))

STANDARD:

Resets and closes 1 Kl BREAKER #1 by taking the breaker to the open UNSAT position and then closing it.

Continue to Step 2.

COMMENTS:

NLO-700 fnl Page 6 of 9 ALTERNATE PATH STEP 3:

Step 2 SAT Contact Unit I CR to verify ICS AUTO power has been restored as indicated by I SA-2/B-1 1 (ICS AUTO POWER FAILURE) off.

UNSAT STANDARD:

Contacts Unit 1 CR to verify ICS AUTO power has been restored as indicated by 1 SA-218-l I (ICS AUTO POWER FAILURE) off.

Cue: Inform candidate that ISA-21B-11 (ICS AUTO POWER FAILURE) remains actuated.

Continue to Step 2 RNO.

COMMENTS:

STEP 4:

Step 2 RNO IF ICS AUTO power has NOT been restored, THEN bypass I KI inverter as follows: (BYP SW I KI cabinet, Unit 1 Equip Rm, Southwest of col Q72):

SAT STANDARD:

Determine CS AUTO power has NOT been restored by actuation of 1SA-2/B-1 1 (ICS AUTO POWER FAILURE) in previous step UNSAT THEN bypasses 1 Kl inverter as follows: (BYP SW I KI cabinet, Unit I Equip Rm, Southwest of col Q72): (steps 5, 6, & 7 below)

COMMENTS:

STEP 5:

Step 2 RNO A CRITICAL TASK A.

Position SW#1 OFF(left switch).

SAT STANDARD:

Positions SW#1 OFF (left switch).

Cue: Indicate to the candidate that SW#1 is OFF.

UNSAT COMMENTS:

NLO-700 fnl Page 7 of 9 STEP 6:

Step 2 RNO B CRITICAL TASK B.

Position SW#3 OFF (right switch).

SAT STANDARD:

Positions SW#3 OFF (right switch).

Cue: Indicate to the candidate that SW#3 is OFF.

UNSAT COMMENTS:

STEP 7:

Step 2 RNO C CRITICAL TASK C.

Position SW#2 ON (center switch).

SAT STANDARD:

Positions SW#2 ON (center switch).

Cue: Indicate to the candidate that SW#2 is ON.

UNSAT Continue to Step 3.

COMMENTS:

STEP 8:

Step 3 Notify Unit I CR that all applicable steps of this enclosure have been completed.

_SAT STANDARD:

Using a phone or radio, Notify Unit 1 CR that all applicable steps of this enclosure have been completed.

UNSAT Cue: Inform candidate that the Control Room has been notified.

COMMENTS:

END TASK STOP TIME:

CRITICAL STEP EXPLANATIONS:

STEP #

Explanation 5

Step is required in proper sequence to align power to the I KI bus.

6 Step is required in proper sequence to align power to the 1 KI bus.

7 Step is required in proper sequence to align power to the 1 KI bus.

NLO-700 fnl Page 8 of 9

CANDIDATE CUE SHEET (TO BE RETURNED TO EXAMINER UPON COMPLETION OF TASK)

INITIAL CONDITIONS:

Unit 1 operating at 100% power 1 SA-2/B-1 1 (ICS AUTO POWER FAILURE) is actuated INITIATING CUES:

The Control Room SRO directs you to use AP/1/A/1700/023 (Loss of ICS Power) Enclosure 5.2 (Restoration of ICS AUTO Power) to restore ICS AUTO power on Unit 1.