MONTHYEARNLS2024006, Response to Nuclear Regulatory Commission'S Request for Additional Information for Relief Request RC3-022024-01-25025 January 2024 Response to Nuclear Regulatory Commission'S Request for Additional Information for Relief Request RC3-02 NLS2024007, Emergency Plan Implementing Procedure 5.7.1, Revision 732024-01-16016 January 2024 Emergency Plan Implementing Procedure 5.7.1, Revision 73 NLS2024003, 30 Day Report - Unauthorized Disassembly of Liquid Scintillation Detector2024-01-15015 January 2024 30 Day Report - Unauthorized Disassembly of Liquid Scintillation Detector NLS2024004, Annual Report of Changes and Errors in Emergency Core Cooling System Evaluation Models for 20232024-01-10010 January 2024 Annual Report of Changes and Errors in Emergency Core Cooling System Evaluation Models for 2023 NLS2023053, ISFSI, Supplement to Exemption Request from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation2023-11-30030 November 2023 ISFSI, Supplement to Exemption Request from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation NLS2023050, Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation2023-11-22022 November 2023 Request for Exemption from Enhanced Weapons, Firearms Background Checks, and Security Event Notifications Implementation NLS2023045, Application to Revise Technical Specifications to Adopt TSTF-374, Revision to Diesel Fuel Oil Testing Program2023-11-15015 November 2023 Application to Revise Technical Specifications to Adopt TSTF-374, Revision to Diesel Fuel Oil Testing Program NLS2023051, Response to Nuclear Regulatory Commission Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements2023-10-10010 October 2023 Response to Nuclear Regulatory Commission Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements NLS2023049, 10 CFR Part 21 Report Regarding HGA Relays2023-09-0606 September 2023 10 CFR Part 21 Report Regarding HGA Relays NLS2023029, License Amendment Request to Revise Technical Specifications to Support Inspection of Diesel Fuel Oil Storage Tanks2023-09-0606 September 2023 License Amendment Request to Revise Technical Specifications to Support Inspection of Diesel Fuel Oil Storage Tanks NLS2023047, Licensee Guarantees of Payment of Deferred Premiums2023-07-26026 July 2023 Licensee Guarantees of Payment of Deferred Premiums NLS2023033, 10 CFR 50.55a Relief Request RC3-022023-06-27027 June 2023 10 CFR 50.55a Relief Request RC3-02 NLS2023039, Preparation and Scheduling of Operator Licensing Examinations2023-06-0101 June 2023 Preparation and Scheduling of Operator Licensing Examinations NLS2023038, Nebraska Public Power District 2022 Financial Report2023-05-22022 May 2023 Nebraska Public Power District 2022 Financial Report NLS2023031, Annual Radiological Environmental Report2023-05-11011 May 2023 Annual Radiological Environmental Report NLS2023017, Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements2023-05-0303 May 2023 Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements NLS2023018, Application to Revise Technical Specifications to Adopt TSTF-580, Provide Exception from Entering Mode 4 with No Operable RHR Shutdown Cooling2023-05-0303 May 2023 Application to Revise Technical Specifications to Adopt TSTF-580, Provide Exception from Entering Mode 4 with No Operable RHR Shutdown Cooling NLS2023030, Annual Radioactive Effluent Release Report2023-04-27027 April 2023 Annual Radioactive Effluent Release Report NLS2023007, Technical Specification Bases Changes2023-04-17017 April 2023 Technical Specification Bases Changes NLS2023027, Annual Report of Individual Exposure Monitoring2023-04-13013 April 2023 Annual Report of Individual Exposure Monitoring NLS2023021, Quality Assurance Program Changes2023-04-10010 April 2023 Quality Assurance Program Changes NLS2023020, Decommissioning Funding2023-03-29029 March 2023 Decommissioning Funding NLS2023019, Property Insurance Coverage2023-03-23023 March 2023 Property Insurance Coverage NLS2023010, Inservice Inspection OAR-1 Owner'S Activity Report for Cooper Nuclear Station2023-02-0909 February 2023 Inservice Inspection OAR-1 Owner'S Activity Report for Cooper Nuclear Station NLS2023005, Annual Report of Changes and Errors in Emergency Core Cooling System Evaluation Models for 20222023-01-19019 January 2023 Annual Report of Changes and Errors in Emergency Core Cooling System Evaluation Models for 2022 NLS2022054, Preparation and Scheduling of Operator Licensing Examinations2023-01-0505 January 2023 Preparation and Scheduling of Operator Licensing Examinations NLS2022055, Emergency Plan, Revision 812023-01-0404 January 2023 Emergency Plan, Revision 81 NLS2022053, CNS-2022-11 Post Exam Submittal2022-11-22022 November 2022 CNS-2022-11 Post Exam Submittal NLS2022050, Notification of Revision to Cooper Nuclear Station Emergency Response Data System Data Point Library2022-11-0909 November 2022 Notification of Revision to Cooper Nuclear Station Emergency Response Data System Data Point Library NLS2022048, Management Change and Correspondence Update2022-11-0101 November 2022 Management Change and Correspondence Update NLS2022047, Core Operating Limits Report, Cycle 33, Revision 02022-10-14014 October 2022 Core Operating Limits Report, Cycle 33, Revision 0 NLS2022042, 10 CFR 50.59(d)(2) and 10 CFR 72.48(d)(2) Summary Report2022-10-0707 October 2022 10 CFR 50.59(d)(2) and 10 CFR 72.48(d)(2) Summary Report NLS2022037, Emergency Plan, Revision 80, Summary of 50.54(q) Analyses2022-08-18018 August 2022 Emergency Plan, Revision 80, Summary of 50.54(q) Analyses NLS2022035, Evacuation Time Estimate Report for Cooper Nuclear Station2022-08-16016 August 2022 Evacuation Time Estimate Report for Cooper Nuclear Station NLS2022031, Licensee Guarantees of Payment of Deferred Premiums2022-07-19019 July 2022 Licensee Guarantees of Payment of Deferred Premiums NLS2022005, Application to Revise Technical Specifications to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements2022-06-16016 June 2022 Application to Revise Technical Specifications to Adopt TSTF-554, Revision 1, Revise Reactor Coolant Leakage Requirements NLS2022025, Nebraska Public Power District Letter (NLS2022010) to U.S. Nuclear Regulatory Commission Dated April 5, 2022, Annual Report of Individual Exposure Monitoring2022-06-0606 June 2022 Nebraska Public Power District Letter (NLS2022010) to U.S. Nuclear Regulatory Commission Dated April 5, 2022, Annual Report of Individual Exposure Monitoring NLS2022016, Annual Radiological Environmental Report2022-05-10010 May 2022 Annual Radiological Environmental Report NLS2022020, Nebraska Public Power District, Cooper Nuclear Station, 2021 Financial Report2022-05-0202 May 2022 Nebraska Public Power District, Cooper Nuclear Station, 2021 Financial Report NLS2022014, Annual Radioactive Effluent Release Report2022-04-27027 April 2022 Annual Radioactive Effluent Release Report NLS2022010, Annual Report of Individual Exposure Monitoring2022-04-0505 April 2022 Annual Report of Individual Exposure Monitoring NLS2022009, Property Insurance Coverage2022-03-23023 March 2022 Property Insurance Coverage NLS2022011, Preparation and Scheduling of Operator Licensing Examinations2022-03-18018 March 2022 Preparation and Scheduling of Operator Licensing Examinations NLS2022004, Response to Nuclear Regulatory Commission'S Request for Additional Information Regarding Relief Request RR5-01, Revision 12022-02-0707 February 2022 Response to Nuclear Regulatory Commission'S Request for Additional Information Regarding Relief Request RR5-01, Revision 1 NLS2022003, Annual Report of Changes and Errors in Emergency Core Cooling System Evaluation Models for 20212022-01-20020 January 2022 Annual Report of Changes and Errors in Emergency Core Cooling System Evaluation Models for 2021 NLS2021067, ISFSI - Independent Spent Fuel Storage Installation Decommissioning Funding Plan2021-12-16016 December 2021 ISFSI - Independent Spent Fuel Storage Installation Decommissioning Funding Plan NLS2021069, Withdrawal of Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements2021-12-15015 December 2021 Withdrawal of Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements NLS2021066, Response to Nuclear Regulatory Commission'S Request for Additional Information Regarding Alternative Request RI5-02, Revision 32021-12-10010 December 2021 Response to Nuclear Regulatory Commission'S Request for Additional Information Regarding Alternative Request RI5-02, Revision 3 NLS2021065, Clarification of Response to Nuclear Regulatory Commission'S Request for Additional Information for Alternative Request RS-012021-12-0606 December 2021 Clarification of Response to Nuclear Regulatory Commission'S Request for Additional Information for Alternative Request RS-01 NLS2021056, Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements2021-11-16016 November 2021 Application to Revise Technical Specifications to Adopt TSTF-551, Revise Secondary Containment Surveillance Requirements 2024-01-25
[Table view] Category:Licensee Response to Notice of Violation
MONTHYEARNLS2015084, Reply to Notice of Violation; EA-15-0892015-07-22022 July 2015 Reply to Notice of Violation; EA-15-089 NLS2014092, Response to NRC Security Inspection Report 05000298/2014202, Denial of Non-Cited Violation No. 05000298/2014202-12014-10-22022 October 2014 Response to NRC Security Inspection Report 05000298/2014202, Denial of Non-Cited Violation No. 05000298/2014202-1 NLS2013061, Reply to Notice of Violation EA- 13-0752013-06-0606 June 2013 Reply to Notice of Violation EA- 13-075 IR 05000298/20120042013-03-21021 March 2013 Reply to Notice of Violation (NRC Inspection Report 05000298-12-004) NLS2012127, Reply to Notice of Violation IR 05000298-12-004-02; EA-12-2062012-12-10010 December 2012 Reply to Notice of Violation IR 05000298-12-004-02; EA-12-206 NLS2011091, Reply to Notice of Violation 05000298-11-006-052011-09-0707 September 2011 Reply to Notice of Violation 05000298-11-006-05 NLS2011070, Reply to a Notice of Violation2011-07-0808 July 2011 Reply to a Notice of Violation NLS2011050, Reply to Notice of Violation 2011002-02; EA-2011-0902011-06-0202 June 2011 Reply to Notice of Violation 2011002-02; EA-2011-090 IR 05000298/20080022008-09-12012 September 2008 Reply to a Notice of Violation for Failing to Perform Maintenance Affecting Performance of Safety-related Equipment with Written Procedures or Documented Instructions Appropriate to the Circumstances - NRC IR 05000298-08-002 NLS2008068, Reply to a Notice of Violation for Failing to Perform Maintenance Affecting Performance of Safety-related Equipment with Written Procedures or Documented Instructions Appropriate to the Circumstances - NRC IR 05000298-08-0022008-09-12012 September 2008 Reply to a Notice of Violation for Failing to Perform Maintenance Affecting Performance of Safety-related Equipment with Written Procedures or Documented Instructions Appropriate to the Circumstances - NRC IR 05000298-08-002 NLS2008029, Triennial Fire Protection Unresolved Issue2008-03-10010 March 2008 Triennial Fire Protection Unresolved Issue NLS2007072, Reply to Notice of Violation; EA-07-0902007-10-15015 October 2007 Reply to Notice of Violation; EA-07-090 IR 05000298/20050022005-08-29029 August 2005 Letter to Nebraska Public Power District IR 05000298/2005-02 Denial of Noncited Violation, 05000298/2005002-02 NLS2004089, Reply to a Notice of Violation NRC Letter No. EA-04-1202004-07-26026 July 2004 Reply to a Notice of Violation NRC Letter No. EA-04-120 NLS2004021, Contesting of Finding in Inspection Report 05000298/2003-0072004-02-26026 February 2004 Contesting of Finding in Inspection Report 05000298/2003-007 NLS2002123, Reply, IR 05000298-02-007, Dated 09/20/02, Cooper Nuclear Station2002-10-18018 October 2002 Reply, IR 05000298-02-007, Dated 09/20/02, Cooper Nuclear Station NLS2002048, Reply to a Notice of Violation, NRC Letter No. EA-01-2982002-04-15015 April 2002 Reply to a Notice of Violation, NRC Letter No. EA-01-298 NLS2002037, Reply to a Notice of Violation2002-04-0101 April 2002 Reply to a Notice of Violation 2015-07-22
[Table view] |
Text
N Nebraska Public Power District Always there when you need us NLS2011091 2.201 September 7, 2011 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555-0001
Subject:
Reply to Notice of Violation 05000298/2011006-05; EA-2011-176 Cooper Nuclear Station, Docket No. 50-298, DPR-46
References:
- 1. Letter to Brian J. O'Grady (Nebraska Public Power District) from Dr. Dale A.
Powers (U.S. Nuclear Regulatory Commission) dated August 8, 2011, "Cooper Nuclear Station - NRC Problem Identification and Resolution Inspection Report 05000298/2011006 and Notice of Violation"
- 2. Letter to Brian J. O'Grady (Nebraska Public Power District) from Thomas R.
Farnholtz (U.S. Nuclear Regulatory Commission) dated December 3, 2010, "Cooper Nuclear Station - NRC Component Design Bases Inspection Report 05000298/2010007"
Dear Sir or Madam:
The purpose of this correspondence is to provide Nebraska Public Power District's (NPPD) reply to a Notice of Violation in accordance with 10 CFR 2.201. By letter dated August 8, 2011 (Reference 1), the Nuclear Regulatory Commission cited NPPD for being in violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control.
The violation is concerned with Cooper Nuclear Station failing to assure that applicable regulatory requirements and the design basis were correctly translated into specifications, drawings, procedures and instructions within a reasonable amount of time after a previous noncited violation (Reference 2) documented the same issue.
NPPD accepts the violation and recognizes the importance of its responsibilities with respect to design basis control. As discussed in the attachment to this letter, NPPD has taken prompt action to return to compliance with 10 CFR Part 50, Appendix B, Criterion III, and to prevent recurrence of this violation.
COOPER NUCLEAR STATION P.O. Box 98 / Brownville, NE 68321-0098
\
Telephone: (402) 825-3811 / Fax: (402) 825-5211 www.nppd.com
NLS2011091 Page 2 of 2 If you have any questions concerning this matter, please contact David Van Der Kamp, Licensing Manager, at (402) 825-2904.
Sinc rely, Brian J.O'Gra y Vice President - Nuclear and Chief Nuclear Officer
/bk Attachment cc: Regional Administrator w/ attachment USNRC - Region IV Cooper Project Manager w/ attachment USNRC - NRR Project Directorate IV-1 Senior Resident Inspector w/ attachment USNRC - CNS NPG Distribution w/ attachment CNS Records w/ attachment
NLS2011091 Attachment Page 1 of3 REPLY TO NOTICE OF VIOLATION 05000298/2011006-05; EA-2011-176 COOPER NUCLEAR STATION, DOCKET NO. 50-298, DPR-46 During Nuclear Regulatory Commission (NRC) inspection activities conducted June 6 through June 24, 2011, a violation of NRC requirements was identified. The violation and Nebraska Public Power District's (NPPD) reply are set forth below:
Restatement of the Violation "Title 10 CFR 50, Appendix B, CriterionIII, "Design Control,"requires, in part,measures shall be establishedto assure that applicableregulatory requirements and the design basis, as defined in 10 CFR 50.2 and as specified in the license application,.forthose components to which this appendix applies, are correctly translatedinto specifications, drawings,procedures,and instructions.
Contrary to the above, since December 3, 2010, the licenseefailed to assure that applicable regulatoryrequirements and the design basis were correctly translatedinto specifications, drawings,procedures,and instructions. Specificallv, the licensee failed to correctly translate regulatoryand design basis requirements, associatedwith tornado and high wind generated missiles, into design information necessary to protect the emergency diesel generatorfuel oil day tank vent line components.
This violation is associatedwith a Green SignificanceDeterminationProcessfinding."
Background
During the 2010 Component Design Bases (CDB) Inspection, conducted July 21, 2010, to October 20, 2010, at Cooper Nuclear Station (CNS), NRC personnel questioned whether analysis existed for a postulated tornado-induced missile strike on the number one emergency diesel generator's (EDG) fuel oil day tank vent line. The EDG fuel oil day tank vent lines at CNS are made of six-inch diameter, schedule 40 thick steel pipe. The vent lines run from each EDG's fuel oil day tank to outside of the EDG rooms, and extend upward along the exterior wall of the turbine building and terminate at a vent cap. CNS determined the current configuration of the EDG fuel oil day tank lines acceptable based on an original Bums and Roe civil design specification which documented the worst case for the tornado-induced missile scenario; i.e.,
impact of a wooden utility pole traveling at 200 miles per hour. CNS did not have a formal design basis calculation on record to support this conclusion and initiated a corrective action to develop one.
In the CDB Inspection Report dated December 3, 2010 (Reference 2), the NRC documented seven examples as a green noncited violation (NCV) of 10 CFR Part 50, Appendix B, Criterion III, "Design Control," for failure to establish measures to ensure that applicable regulatory requirements and the design bases were correctly translated into specifications, drawings, procedures, and instructions. Reference 2 specified that this finding applied to the tornado and high wind impact on the EDG fuel oil storage facilities.
NLS2011091 Attachment Page 2 of 3 On December 14, 2010, CNS design engineering completed a calculation, and associated engineering evaluation, to evaluate a postulated tornado-induced missile impact on the EDG fuel oil day tank vent lines. The evaluation concluded that the existing EDG day tank vent lines were adequate after a postulated tornado strike and able to provide venting.
From June 6, 2011, to June 24, 2011, the NRC conducted a Problem Identification and Resolution inspection at CNS. During this inspection, the NRC noted that the design basis calculation performed in December 2010, and subsequent revisions, contained non-conservative assumptions related to net positive suction head and head loss, that could affect the outcome of the calculation. CNS reviewed the calculation and determined additional clarifying engineering analysis would be required to resolve the NRC's concern.
In Reference 1 the NRC discussed its review of the December 2010 calculation and corrective actions taken in response to the CDB Inspection NCV, and concluded that CNS had failed to restore compliance within a reasonable time after the NCV was identified on December 3, 2010.
Specifically, CNS failed to correctly translate regulatory and design basis requirements, associated with tornado and high wind generated missiles, into design information necessary to protect the EDG fuel oil day tank vent line components.
Reason for Violation NPPD accepts the cited violation.
CNS performed an evaluation utilizing root cause analysis. The root cause team reviewed the December 2010 calculation, associated engineering evaluation, and subsequent revisions. The team identified that the calculation was inadequate. When the December 2010 calculation was being prepared, a decision was made by CNS engineering supervision to pursue the worst case approach; i.e., assuming the EDG fuel oil day tank steel vent line would be flattened and pinched off. The engineer assigned to prepare the calculation was provided with this presumed result and was not tasked with determining the result of the impact based upon the original design basis scenario. Rather, the evaluation attempted to demonstrate no adverse effect to EDG operation.
The root cause for the condition, cited in Reference 1, is underestimation of the scope and task to address an NCV. In summary, CNS failed to resolve a design basis issue in a timely manner because an initial decision had been made by CNS engineering supervision to develop an operability type evaluation. This decision resulted in a calculation that focused on addressing the operability of the vent pipe after impact, rather than generation of the missing design basis analysis of the impact.
Corrective Steps Taken and Results Achieved CNS has performed a new calculation to evaluate the design basis tornado-induced missile impact on the EDG fuel oil day tank vent lines. This calculation is approved and implemented, and supersedes the December 2010 calculation and associated engineering evaluation.
NLS2011091 Attaclunent Page 3 of 3 Corrective Steps That Will Be Taken to Avoid Further Violations The action described above will prevent further violations related to translating regulatory and design basis requirements for tornado and high wind generated missiles into design information necessary to protect the EDG fuel oil day tank vent line components.
Additional Corrective Actions CNS will deliver a case study of the decision making aspects of this issue to design engineering supervisors. CNS will also review calculation assignments in the civil engineering department made in the past 18 months to determine if any were directed towards establishing operability rather than addressing design basis.
Date When Full Compliance Will Be Achieved NPPD has restored compliance with 10 CFR Part 50, Appendix B, Criterion III.
References
- 1. Letter to Brian J. O'Grady (Nebraska Public Power District) from Dr. Dale A. Powers (U.S.
Nuclear Regulatory Commission) dated August 8, 2011, "Cooper Nuclear Station - NRC Problem Identification and Resolution Inspection Report 05000298/2011006 and Notice of Violation"
- 2. Letter to Brian J. O'Grady (Nebraska Public Power District) from Thomas R. Farnholtz (U.S.
Nuclear Regulatory Commission) dated December 3, 2010, "Cooper Nuclear Station - NRC Component Design Bases Inspection Report 05000298/2010007"
ATTACHMENT 3 LIST OF REGULATORY COMMITMENTSC 4 ATTACHMENT3 LIST OF REGULATORY COMMITMENTSN4 Correspondence Number: NLS2011091 The following table identifies those actions committed to by Nebraska Public Power District (NPPD) in this document. Any other actions discussed in the submittal represent intended or planned actions by NPPD. They are described for information only and are not regulatory commitments. Please notify the Licensing Manager at Cooper Nuclear Station of any questions regarding this document or any associated regulatory commitments.