PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE IN PLANT NRC Sim A LESSON TITLE:
Bypass a LPRM LESSON NUMBER:
LOT-SIM-JP-215-D07 REVISION NO:
2
/t 1
)
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE IN PLANT NRC Sim A LESSON TITLE:
Bypass a LPRM LESSON NUMBER:
LOT-SIM-JP-215-D07 REVISION NO:
2 J
Bypassing a LPRM SIMULATOR SETUP:
Recommended Initial Conditions IC-li, 100% Power, 8CC Required Plant Conditions Triggers Malfunctions Overrides Remotes IMPORTANT NOTE:
Resetting the simulator does not reset the PPC. The Scanning Enabled will have to be performed on PPC screen 861. This must be done after each performance of the JPM and prior to the next examinee starting this JPM.
To reset the PPC:
Select the 861 screen.
Select LPRM 04-21A and hit Control Point ID Select Scanning Disabled Type E Press Enter Verify value returns (changes from cyan to green)
Place PPC on the Main Menu LOT-SIM-JP-215-D07 Page 2 of 10 Rev. 2 SIMULATOR SETUP:
Recommended Initial Conditions I C-11, 100% Power, BOC Required Plant Conditions Triggers Malfunctions Overrides Remotes IMPORTANT NOTE:
Bypassing a LPRM Resetting the simulator does not reset the PPC. The Scanning Enabled will have to be performed on PPC screen 861. This must be done after each performance of the JPM and prior to the next examinee starting this JPM.
To reset the PPC:
Select the 861 screen.
Select LPRM 04-21A and hit Control Point ID Select Scanning Disabled Type E Press Enter Verify value returns (changes from cyan to green)
Place PPC on the Main Menu LOT-SIM-JP-215-007 Page 2 of 10 Rev. 2
Bypassing a LPRM SAFETY CONSIDERATIONS:
None EVALUATOR NOTES: (Do not read to performer) 1.
The applicable procedure section WILL be provided to the performer.
2.
If this is the first JPM of the JPM set, read theJPM briefing contained in NUREG 1021, Appendix E, or similar to the performer.
Read the following to the JPM performer.
TASK CONDITIONS:
1.LPRM 04-21A (APRM 1) operation has been erratic causing numerous upscale alarms but is currently reading normal.
INITIATING CUE:
You are directed by the Unit CRS to bypassLPRM 04-21A per 20P-09. Inform the CRS when all required actions have been completed.
LOT-SIM-JP-215-D07 Page 3 of 10 Rev. 2 Bypassing a LPRM SAFETY CONSIDERATIONS:
None EVALUATOR NOTES: (Do not read to performer)
- 1. The applicable procedure section WILL be provided to the performer.
- 2. If this is the first JPM of the JPM set, read the/JPM briefing contained in NUREG 1021, Appendix E, or similar to the performer.
Read the following to the JPM performer.
TASK CONDITIONS:
- 1.LPRM 04-21A (APRM 1) operation has been erratic causing numerous upscale alarms but is currently reading normal.
INITIATING CUE:
You are directed by the Unit CRS to bypassLPRM 04-21A per 20P-09. Inform the CRS when all required actions have been completed.
LOT-SIM-JP-215-D07 Page 3 of 10 Rev. 2
Bypassing a LPRM PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1
- Obtain current revision of 20P-09, Section 8.4.
Current revision of 20P-09, Section 8.4 obtained.
SAT!UNSAT*
TIME START Step 2 Identify the number of LPRMs in average.
The number of LPRMs is identified (31) using the APRM Bar graph on panel P608 or the PPC (screen 861 or 863).
SATIUNSAT
- PROMPT:
If asked Inform the examinee as the Unit CRS that the minimum number of LPRM inputs will be maintained for the affected APRM and OPRM.
Step 3 Confirm that the minimum number of LPRM inputs can be maintained.
The minimum number of LPRM inputs (17) is verified using the APRM Bar graph on panel P608 or the PPC (screen 861 or 863).
SATIUNSAT*
PROMPT:
If asked provide guidance as the Unit CRS to Bypass APRM 1.
I Step 4 Place APRM 1 in BYPASS.
APRM I is placed in BYPASS.
SATIU NSAT*
Step 5 Record the LPRM to be bypassed in step 4.
LPRM 04-2 IA recorded on procedure.
SAT/UNSAT*
Step 6 Confirm BYP is indicated for APRM 1.
APRM I BYP heading in inverse video is verified.
SAT/UNSAT*
LOT-SIM-JP-215-D07 Page 4 of 10 Rev. 2 Bypassing a LPRM PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 - Obtain current revision of 20P-09, Section 8A.
Current revision of 20P-09, Section 8.4 obtained.
SATIUNSAT*
TIME START ____ _
Step 2 - Identify the number of LPRMs in average.
The number of LPRMs is identified (31) using the APRM Bar graph on panel P608 or the PPC (screen 861 or 863).
SAT/UNSAT
- PROMPT:
If asked Inform the examinee as the Unit CRS that the minimum number of LPRMinputs will be.maintained for the affected APRM and OPRM.
Step 3 - Confirm that the minimum number of LPRM inputs can be maintained.
The minimum number of LPRM inputs (17) is verified using the APRM Bar graph on panel P608 or the PPC (screen 861 or 863).
SAT/UNSAT*
I PROMPT:
If asked provide guidance as the Unit CRS to Bypass APRM 1.
Step 4 - Place APRM 1 in BYPASS.
APRM 1 is placed in BYPASS.
SATIUNSAT*
Step 5 - Record the LPRM to be bypassed in step 4.LPRM 04-21A recorded on procedure.
SATIUNSAT*
Step 6 - Confirm 'BYP' is indicated for APRM 1.
APRM 1 BYP heading in inverse video is verified.
SAT/UNSAT*
LOT-SIM-JP-215-007 Page 4 of 10 Rev. 2
Bypassing a LPRM NOTE The ETC soft key will be toggled to display the BYPASS SELECTIONS soft key I
Step 7 Press ETC soft key to obtain BYPASS SELECTIONS soft key.
Bypass Selections soft key is obtained.
SATIU NSAT*
Step 8 Press BYPASS SELECTIONS soft key.
Bypass Selections soft key is pressed.
- CRITICAL STEP**SATIUNSAT*
NOTE:
If ten (10) seconds expires before the password is accepted (ENT is pressed on the numeric keypad) the screen will revert to the Main APRM Bar Graph display. The examinee must repeat steps to access the correct screen.
Step 9 Enter password 1 2 3 4 and press ENT.
Password (1234) is entered and ENT button is depressed.
- CRITICAL STEP**SATIUNSAT*
NOTE:
The right arrow key must be pressed repeatedly to obtain the correct LPRM. The down arrow key will not work.
Step 10 Using the cursor keys, Select LPRM 04-21A AND PRESS BYPASS/HV OFF soft key.
LPRM 04-2 IA is selected and bypass/HV Off soft key depressed.
- CRITICAL STEP**SATIUNSAT*
Step 11 Confirm LPRM status changes to BYPASS/HV OFF.
LPRM 04-2IA status is verified as Bypass/HV Off SATIU NSAT*
Step 12 Press EXIT soft key.
Exit soft key is pressed.
SATIUNSAT*
LOT-SIM-JP-215-D07 Page 5 of 10 Rev. 2 Bypassing a LPRM INOTE:
The ETC soft key will bEHoggled to display the BYPASS SELECTIONS soft key.
Step 7 - Press ETC soft key to obtain BYPASS SELECTIONS soft key.
Bypass Selections soft key is obtained.
SAT/UNSAT*
Step 8 - Press BYPASS SELECTIONS soft key.
NOTE:
Bypass Selections soft key is pressed.
- CRITICAL STEP**SAT/UNSAT*
If ten (10) seconds expires before the password is accepted (ENT is pressed on the numeric keypad) the screen will revert to the Main APRM Bar Graph display. The examinee must repeat steps to access the correct screen.
Step 9 - Enter password "1 234" and press ENT.
NOTE:
Password (1234) is entered and ENT button is depressed.
- CRITICAL STEP**SAT/UNSAT*
The right arrow key must be pressed repeatedly to obtain the correct LPRM. The down arrow key will not work.
Step 10 - Using the cursor keys, Select LPRM 04-21A AND PRESS BYPASS/HV OFF soft key.LPRM 04-21A is selected and bypasslHV Off soft key depressed.
- CRITICAL STEP**SAT/UNSAT*
Step 11 - Confirm LPRM status changes to BYPASS/HV OFF.LPRM 04-21A status is verified as BypasslHV Off.
SAT/UNSAT*
Step 12 - Press EXIT soft key.
Exit soft key is pressed.
SAT/UNSAT*
LOT-SIM-JP-215-007 Page 5 of 10 Rev. 2
Bypassing a LPRM Step 13 Verify that APRM GAFs are less than or equal to 1.
GAPs are < I (as observed on the PPC or the APRM chassis on P608 panel).
SAT!UNSAT*
PROMPT:
If notified, respond as the Reactor Engineer and/or Unit CRS as necessary.
I Step 14 Notify the Reactor Engineer that the LPRM is bypassed.
Reactor Engineer is notified.
SATIUNSAT*
SAT UNSAT a
Move the curser to the poke point for the LPRM to be bypassed b
Press the trackball <SELECT> button c
Confirm the point ID for the LPRM appears in the message area at the bottom of the window d
Press the <CONTROL POINT ID> hardkey e
Confirm the DATA POINT display appears showing data associated with the desired point ID.
f Place the curser on the green scanning ENABLED text and click g
Type D to disable h
Press keypad ENTER key i
Confirm scanning text changes to DISABLED j
Click on the value in the upper right hand area of the screen k
Type 0 for the substitute value I
Press keypad ENTER key rn Confirm the point value entered appears in cyan Data Point display for 04-2 IA indicates a value of zero and scanning disabled and PPC screen 861 displays the value in cyan.
- CRITICAL STEP**SATIUNSAT*
Step 15 Ensure computer point for the bypassed LPRM, on PPC Screen 861, has its scanning disabled AND a zero value inserted as follows.
LOT-SIM-JP-21 5-D07 Page 6 of 10 Rev. 2 Bypassing a LPRM Step 13 - Verify that APRM GAFs are less than or equal to 1.
GAF's are.::: 1 (as observed on the PPC or the APRM chassis on P608 panel).
SATIUNSAT*
PROMPT:
If notified, respond as the Reactor Engineer and/or Unit CRS as necessary.
Step 14 - Notify the Reactor Engineer that the LPRM is bypassed.
Reactor Engineer is notified.
SAT/UNSAT*
Step 15 - Ensure computer point for the bypassed LPRM, on PPC Screen 861, has its scanning disabled AND a zero value inserted as follows a
b c
d e
f g
h i
j k
I m
SAT UNSAT Move the curser to the poke point for the LPRM to be bypassed Press the trackball <SELECT> button Confirm the point 10 for the LPRM appears in the message area at the bottom of the window Press the <CONTROL POINT 10> hardkey Confirm the DATA POINT display appears showing data associated with the desired point 10.
Place the curser on the green scanning "ENABLED" text and click Type "0" to disable Press keypad "ENTER" key Confirm scanning text changes to "DISABLED" Click on the value in the upper right hand area of the screen Type "0" for the substitute value Press keypad "ENTER" key Confirm the point value entered appears in cyan Data Point display for 04-21A indicates a value of zero and scanning disabled and PPC screen 861 displays the value in cyan.
- CRITICAL STEP**SAT/UNSAT*
LOT-SIM-JP-215-007 Page 6 of 10 Rev. 2
Bypassing a LPRM Step 16 Ensure APRM 1 is removed from BYPASS.
APRM Bypass Joystick is returned to the center OPERA TE position.
- CRITICAL STEP**SATIUNSAT*
PROMPT:
Notify the Performer that another Operator will make the log entry and initiate the Work Request.
Step 17 Notify the Unit CRS that LPRM 04-21A is bypassed.
Unit CRS is notified.
SATIU NSAT*
TIME COMPLETED LOT-SIM-JP-21 5-D07 Page 7 of 10 Rev. 2 Bypassing a LPRM Step 16 - Ensure APRM 1 is removed from BYPASS.
APRM Bypass Joystick is returned to the center, OPERA TE, position.
- CRITICAL STEP**SAT/UNSAT*
PROMPT:
Notify the Performer that another Operator will make the log entry and initiate the Work Request.
Step 17 - Notify the Unit CRS that LPRM 04-21A is bypassed.
Unit CRS is notified.
SAT/UNSAT*
TERMINATING CUE: When LPRM 04-21A is bypassed and the APRM is removed from bypass, this JPM is complete.
TIME COMPLETED ____
LOT-SIM-JP-215-007 Page 7 of 10 Rev. 2
Bypassing a LPRM LIST OF REFERENCES RELATED TASKS:
21 5203B401 Respond To A LPRM Failure Per APP A-06 1-7 or 1-8.
KIA REFERENCE AND IMPORTANCE RATING:
215005 A2.02 (3.6/3.7).
Ability To Predict Impacts On APRM And Use Procedures To Correct, Control Or Mitigate Consequences
REFERENCES:
2APP A-06 1-8 2OP-09 TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2)
Safety Function 7, Instrumentation, APRM/LPRM REASON FOR REVISION:
Added steps for PPC.
LOT-SJM-JP-215-D07 Page 8 of 10 Rev. 2 Bypassing a LPRM LIST OF REFERENCES RELATED TASKS:
2152038401 Respond To A LPRM Failure Per APP A-06 1-7 or 1-8.
KIA REFERENCE AND IMPORTANCE RATING:
215005 A2.02 (3.6/3.7).
Ability To Predict Impacts On APRM And Use Procedures To Correct, Control Or Mitigate Consequences
REFERENCES:
2APP A-06 1-8 20P-09 TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2)
Safety Function 7, Instrumentation, APRM/LPRM REASON FOR REVISION:
Added steps for PPC.
LOT-SIM-JP-215-007 Page 8 of 10 Rev. 2
Bypassing a LPRM Time Required for Completion:
15 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate
Actual X
Unit:
2 Setting:
Control Room
Simulator X
In-Plant:
Time Critical:
Yes No X
Time Limit
Alternate Path:
Yes
No X
EVALUATION Performer:____________________________________
JPM:
Pass Fail Remedial Training Required: Yes No Did Performer Verify Procedure?
Yes No (Each Student should verify one JPM per evaluation set)
Comments:
Comments reviewed with Student Evaluator Signature:
Date:_____________
LOT-SIM-JP-215-D07 Page 9 of 10 Rev. 2 Bypassing a LPRM Time Required for Completion: ~
Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual L Unit:
2 Setting:
Control Room Simulator X
In-Plant:
Time Critical:
Yes No X
Time Limit Alternate Path:
Yes No X
EVALUATION Performer: _______________ _
JPM:
Pass __
Fail --
Remedial Training Required: Yes No __
Did Performer Verify Procedure? Yes No __
(Each Student should verify one JPM per evaluation set)
Comments:
Comments reviewed with Student Evaluator Signature: ______________ _
Date: ____ _
LOT-SIM-JP-215-D07 Page 9 of 10 Rev. 2
TASK CONDITIONS:
1.LPRM 04-21A (APRM 1) operation has been erratic causing numerous upscale alarms but is currently reading normal.
INITIATING CUE:
You are directed by the Unit CRS to bypassLPRM 04-21A per 20P-09. Inform the CRS when all required actions have been completed.
TASK CONDITIONS:
- 1.LPRM 04-21A (APRM 1) operation has been erratic causing numerous upscale alarms but is currently reading normal.
INITIATING CUE:
You are directed by the Unit CRS to bypassLPRM 04-21A per 20P-09. Inform the CRS when all required actions have been completed.
8.4 Bypassing a LPRM c
Continuous Use 8.4.1 Initial Conditions Initials Date/Time Started_______________
1.
LPRM is required to be bypassed (indication invalid, erratic, etc.).
8.4.2 Procedural Steps NOTE:
Bypassing an LPRM may cause an APRM, RBM, or OPRM Channel to be inoperable from too few inputs if additional LPRMs have been previously bypassed. The minimum number of inputs to APRM and OPRM can be identified using numerous PPC Displays
- Displays 863 (864, 865, 866),
- APRM 1 (2, 3, 4) and Displays 888 (889, 890,891)
OPRM 1 (2, 3, 4) STATUS/DATA, are examples.
1.
IDENTIFY the number of LPRM5 in average to APRM using the APRM BARGRAPH on Panel P608, or applicable PPC Display.
2.
CONFIRM the LPRM can be bypassed and minimum number of LPRM inputs maintained to the affected APRM and OPRM.
3.
PLACE applicable APRM in BYPASS.
4.
PERFORM the following to bypass an LPRM at Panel P608:
LPRM a.
CONFIRM BYP is indicated for the selected APRM channel.
b.
PRESS ETC soft key to obtain BYPASS SELECTIONS soft key.
c.
PRESS BYPASS SELECTIONS soft key.
20P-09 Rev. 28 Page 19 of 39 8.4 Bypassing a LPRM 8.4.1
- 1.
8.4.2 Initial Conditions Initials DatelTime Started -------
LPRM is required to be bypassed (indication invalid, erratic, etc.).
Procedural Steps NOTE:
Bypassing an LPRM may cause an APRM, RBM, or OPRM Channel to be inoperable from too few inputs if additional LPRMs have been previously bypassed. The minimum number of inputs to APRM and OPRM can be identified using numerous PPC Displays - Displays 863 (864, 865, 866),
LPRM BAR CHART - APRM 1 (2, 3, 4) and Displays 888 (889, 890,891)
OPRM 1 (2, 3,4) STATUS/DATA, are examples.
- 1.
IDENTIFY the number of LPRMs in average to APRM using the APRM BARGRAPH on Panel P608, or applicable PPC Display.
- 2.
CONFIRM the LPRM can be bypassed and minimum number of LPRM inputs maintained to the affected APRM and OPRM.
- 3.
PLACE applicable APRM in BYPASS.
- 4.
PERFORM the following to bypass an LPRM at Panel P608:
LPRM __ _
- a.
CONFIRM BYP is indicated for the selected APRM channel.
- b.
PRESS ETC soft key to obtain BYPASS SELECTIONS soft key.
- c.
PRESS BYPASS SELECTIONS soft key.
C Continuous Use 1 20 P-09 Rev. 28 Page 19 of 391
8.4.2 Procedural Steps d.
ENTER password 1 2 34 AND PRESS ENT.
e.
Using the cursor keys, SELECT the LPRM AND PRESS BYPASS/HV OFF soft key.
f.
CONFIRM LPRM status changes to BYPASS/HV OFF.
g.
PRESS EXIT soft key.
5.
ENSURE APRM GAF is less than or equal to 1.00, by performing Section 8.1 to adjust APRM GAFs, if required.
6.
NOTIFY Reactor Engineer LPRM is bypassed.
7.
ENSURE the computer point for the bypassed LPRM, on PPC Screen 861, has its scanning disabled AND a zero value inserted as follows:
a.
MOVE the curser to the poke point for the LPRM to be bypassed.
b.
PRESS the trackball <SELECT> button.
c.
CONFIRM the point ID for the LPRM appears in the message area at the bottom of the window.
d.
PRESS the <CONTROL POINT ID> hardkey.
e.
CONFIRM the DATA POINT display appears showing data associated with the desired point ID.
f.
PLACE the curser on the green scanning ENABLED text AND CLICK.
g.
TYPE D to disable.
h.
PRESS keypad ENTER key.
2OP-09 Rev. 28 Page 20 of 39 8.4.2 Procedural Steps
- d.
ENTER password "1 234" AND PRESS ENT.
- e.
Using the cursor keys, SELECT the LPRM AND PRESS BYPASS/HV OFF soft key.
- f.
CONFIRM LPRM status changes to BYPASS/HV OFF.
- g.
PRESS EXIT soft key.
- 5.
ENSURE APRM GAF is less than or equal to 1.00, by performing Section 8.1 to adjust APRM GAFs, if required.
- 6.
NOTIFY Reactor Engineer LPRM is bypassed.
- 7.
6NSURE the computer point for the bypassed LPRM, on PPC Screen 861, has its scanning disabled AND a zero value inserted as follows:
- a.
MOVE the curser to the poke point for the LPRM to be bypassed.
- b.
PRESS the trackball <SELECT> button.
- c.
CONFIRM the point 10 for the LPRM appears in the message area at the bottom of the window.
- d.
PRESS the <CONTROL POINT 10> hardkey.
- e.
CONFIRM the DATA POINT display appears showing data associated with the desired point 10.
- f.
PLACE the curser on the green scanning "ENABLED" text AND CLICK.
- g.
TYPE "0" to disable.
- h.
PRESS keypad "ENTER" key.
Rev. 28 Page 20 of 39/
8.4.2 Procedural Steps CONFIRM scanning text changes to DISABLED.
j.
CLICK on the value in the upper right hand area of the screen.
k.
TYPE 0 for the substitute value.
I.
PRESS keypad ENTER key.
m.
CONFIRM the point value entered appears in cyan.
8.
ENSURE applicable APRM is removed from BYPASS.
9.
ENSURE the Unit Status Database, LPRM Status, is updated to reflect the bypassed LPRM.
10.
ENSURE a W/R is initiated for the bypassed LPRM.
11.
NOTIFY Unit SCO the LPRM has been bypassed.
Date/Time Completed Performed By (Print)
Initials Reviewed By:
Unit SCO 20P-09 Rev. 28 Page 21 of 39]
8.4.2 Procedural Steps
- i.
CONFIRM scanning text changes to "DISABLED".
- j.
CLICK on the value in the upper right hand area of the screen.
- k.
TYPE "0" for the substitute value.
I.
PRESS keypad "ENTER" key.
- m.
CONFIRM the point value entered appears in cyan.
- 8.
ENSURE applicable APRM is removed from BYPASS.
- 9.
ENSURE the Unit Status Database, LPRM Status, is updated to reflect the bypassed LPRM.
- 10.
ENSURE a W/R is initiated for the bypassed LPRM.
- 11.
NOTIFY Unit SCQ the LPRM has been bypassed.
DatelTime Completed ______ _
Performed By (Print)
Reviewed By: __________ _
Unit SCQ Initials Rev. 28 Page 21 of 391
PROGRESS ENERGY - CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE CONTROL ROOM NRC Sim B LESSON TITLE:
SEP-04 Restart RB HVAC with Failure to Isolate LESSON PLAN:
LOT-SIM-JP-300-K1 1 REVISION NO:
01 LI/
LESSON TITLE:
LESSON PLAN:
REVISION NO:
PROGRESS ENERGY - CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE CONTROL ROOM NRC Sim B SEP Restart RB HVAC with Failure to Isolate LOT-SIM-JP-300-K11 01
SEP-04 Restart RB HVAC with Failure to Isolate B.
Required Plant Conditions A Secondary Containment leak that results in tripping the D12-R6O9AIB monitors on high radiation, which isolates RB HVAC. RPV water level is below LL2 or DW pressure is
>1.7 psig and the Rx Bldg Rad Monitors are tripped.
C.
Malfunctions Event System Tag Title Value Activate Deactivate (ramp Time Time (sec) rate)
(sec)
A RW RHOI3F RWCU Break in Triangle 100%14 00 NA Room mins A
NB NBOO6F MSL D Break before flow 1%I0 00 NA restrictor mins D.
Overrides Event Panel Tag Title Value Activate Deactivate (ramp Time Time (sec) rate)
(sec)
SIMULATOR SETUP:
A.
Initial Conditions:
1.
Recommended Initial Conditions IC 11 Rx. Pwr.
Core Age 100%
BOC LOT-SIM-JP-300-K1 I Page 2 of 11 REV. 1 SEP Restart RB HVAC with Failure to Isolate SIMULATOR SETUP:
A.
Initial Conditions:
- 1.
Recommended Initial Conditions IC Rx. Pwr.
Core Age 11 100%
BOC B.
Required Plant Conditions A Secondary Containment leak that results in tripping the D12-R609NB monitors on high radiation, which isolates RB HVAC. RPV water level is below LL2 or DW pressure is
>1.7 psig and the Rx Bldg Rad Monitors are tripped.
C Malfunctions Event System Tag Title Value Activate Deactivate (ramp Time Time (sec) rate)
(sec)
A RW RH013F RWCU Break in Triangle 100%/4 00 NA Room mins A
NB NB006F MSL D Break before flow 1%/0 00 NA restrictor mins D
Overrides Event Panel Tag Title Value Activate Deactivate (ramp Time Time (sec) rate)
(sec)
LOT-SIM-JP-300-K11 Page 2 of 11 REV. 1
SEP-04 Restart RB HVAC with Failure to Isolate El: Manually initiated. G5B25G1G to 0.7 over 1 minute Set up to cause the following:
RB Rad Monitor A indication (g5b25glg ) to start rising to 0.7 over a 1 minute time frame.
RB Rad Monitor B indication (g5b25g2g ) to start rising to 0.7 over a 1 minute time frame.
PROCESS RX BLDG VENT RAD HI Annunciator (ZUA345) to actuate after 50 sec.
PROCESS RX BLDG VENT RAD HI-HI Annunciator (ZUA335) to actuate after 55 sec.
E2: trc:2,aod:g5b25glg Set up the RB Rad Monitor A meter override to be deleted on depressing the RB Isolation Dampers close switch (K56O8JCV close is true).
E3: trc:3,aod:g5b25g2g Set up the RB Rad Monitor B meter override to be deleted on depressing the RB Isolation Dampers close switch (K56O8JCV close is true).
E.
Special Instructions
- 1. Place simulator in RUN and activate malfunctions.
Make sure level set is at 187 inches (this will go back to 170 inches after coming out of freeze)
Make sure that SEP-04 is cleaned.
LOT-SIM-JP-300-K1 I Page 3 of 11 REV. 1 SEP Restart RB HVAC with Failure to Isolate E1: Manually initiated. G5B25G1 G to 0.7 over 1 minute Set up to cause the following:
RB Rad Monitor A indication (g5b25g1g ) to start rising to 0.7 over a 1 minute time frame.
RB Rad Monitor B indication (g5b25g2g ) to start rising to 0.7 over a 1 minute time frame.
PROCESS RX BLDG VENT RAD HI Annunciator (ZUA345) to actuate after 50 sec.
PROCESS RX BLDG VENT RAD HI-HI Annunciator (ZUA335) to actuate after 55 sec.
E2: trc:2,aod:g5b25g1g Set up the RB Rad Monitor A meter override to be deleted on depressing the RB Isolation Dampers close switch (K5608JCV close is true).
E3: trc:3,aod:g5b25g2g Set up the RB Rad Monitor B meter override to be deleted on depressing the RB Isolation Dampers close switch (K5608JCV close is true).
E.
Special Instructions
- 1. Place simulator in RUN and activate malfunctions.
Make sure level set is at 187 inches (this will go back to 170 inches after coming out of freeze)
Make sure that SEP-04 is cleaned.
LOT-SIM-JP-300-K11 Page 3 of 11 REV. 1
SEP-04 Restart RB HVAC with Failure to Isolate SAFETY CONSIDERATIONS:
NONE.
EVALUATOR NOTES: (Do not read to examinee)
- 1. The applicable procedure section WILL be provided to the examinee marked up to step 2.3.
2.
If this is the first JPM of the JPM set, read the JPM briefing contained NUREG 1021, Appendix E, or similar to the examinee.
Read the following to trainee.
TASK CONDITIONS:
1.
SCCP has been entered on Unit Two.
2.
A high-radiation condition sensed by the RB Vent Radiation Monitors (D12-R6O9AIB) resulted in the isolation of Reactor Building HVAC.
3.
Reactor Building Exhaust temperature has not exceeded 135°F.
4.
The leak has been isolated and EOP-03-SCCP directs restoring RB HVAC.
5.
Instrument air pressure to the latch actuators for the reactor building ventilation isolation valves was never lost.
6.
SEP-04 is being performed and is complete through step 2.2.
INITIATING CUE:
The Unit SCO directs you to restart Reactor Building HVAC per SEP-04 (starting with step 2.3) and inform him when your actions are complete.
LOT-SIM-JP-300-K1 1 Page 4 of 11 REV. 1 SEP Restart RB HVAC with Failure to Isolate SAFETY CONSIDERATIONS:
NONE.
EVALUATOR NOTES: (Do not read to examinee)
- 1. The applicable procedure section WILL be provided to the examinee marked up to step 2.3.
- 2. If this is the first JPM of the JPM set, read the JPM briefing contained NUREG 1021, Appendix E, or similar to the examinee.
Read the following to trainee.
TASK CONDITIONS:
- 1.
SCCP has been entered on Unit Two.
- 2.
A high-radiation condition sensed by the RB Vent Radiation Monitors (D12-R609A1B) resulted in the isolation of Reactor Building HVAC.
- 3.
Reactor Building Exhaust temperature has not exceeded 135°F.
- 4.
The leak has been isolated and EOP-03-SCCP directs restoring RB HVAC.
- 5.
Instrument air pressure to the latch actuators for the reactor building ventilation isolation valves was never lost.
- 6.
SEP-04 is being performed and is complete through step 2.2.
INITIATING CUE:
The Unit SCO directs you to restart Reactor Building HVAC per SEP-04 (starting with step 2.3) and inform him when your actions are complete.
LOT-SIM-JP-300-K11 Page 4 of 11 REV. 1
SEP-04 Restart RB HVAC with Failure to Isolate PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step I
- Obtain current revision of OEOP-SEP-04.
Current revision of OEOP-SEP-04 obtained.
SATIU NSAT*
TIME START:
PROMPT:
If asked, indicate the peak radiation levels on D12-RR-R605 at 4mr/hr and the Reactor Building Exhaust temperature has not exceeded 135°F.
Step 2 Place the CAC PURGE VENT ISOL OVRD, CAC-CS-5519 switch to OVERRIDE.
CAC-CS-5519 switch in OVERRIDE.
- CRITICAL STEP ** SATIUNSAT*
NOTE:
When both Process RB Vent Exhaust Rad Monitors are reset, annunciators UA-03 3-5 (PROCESS RX BLDG VENT RAD HI-HI) clears and annunciators UA-05 3-5 (SBGT SYS B FAILURE) and 4-6 (SBGT SYS A FAILURE) alarm.
Step 3 Reset the Process Reactor Building Vent Exhaust Rad Monitors at Panel H12-P606.
D12-RM-K609A and D12-RM-K609B are reset at Panel H12-P606 by depressing the reset pushbutton and verifying that the red light extinguishes.
- CRITICAL STEP **
SATIUNSAT*
Step 4
- Reset the PCIS Group 6 Isolation on RTGB Panel P601.
PCIS Group 6 Isolation reset by depressing pushbuttons S32 and S33 on P60 1.
- CRITICAL STEP **
SATIUNSAT*
LOT-SIM-JP-300-K1 1 Page 5 of 11 REV. 1 SEP Restart RB HVAC with Failure to Isolate PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 - Obtain current revision of OEOP-SEP-04.
Current revision of OEOP-SEP-04 obtained.
SAT/UNSAT*
TIME START: ____
PROMPT:
If asked, indicate the peak radiation levels on D12-RR-R605 at 4mr/hr and the Reactor Building Exhaust temperature has not exceeded 135°F.
Step 2 Place the CAC PURGE VENT ISOL OVRD, CAC-CS-5519 switch to OVERRIDE.
NOTE:
CAC-CS-5519 switch in OVERRIDE.
- CRITICAL STEP ** SA TlUNSAT*
When both Process RB Vent Exhaust Rad Monitors are reset, annunciators UA-033-5 (PROCESS RX BLDG VENT RAD HI-HI) clears and annunciators UA-05 3-5 (SBGT SYS B FAILURE) and 4-6 (SBGTSYS A FAILURE) alarm.
Step 3 Reset the Process Reactor Building Vent Exhaust Rad Monitors at Panel H12-P606.
D12-RM-K609A and D12-RM-K6098 are reset at Panel H12-P606 by depressing the reset pushbutton and verifying that the red light extinguishes.
- CRITICAL STEP ** SA TlUNSAT*
Step 4 - Reset the PCIS Group 6 Isolation on RTGB Panel P601.
PCIS Group 6 Isolation reset by depressing pushbuttons S32 and S33 on P601.
- CRITICAL STEP ** SAT/UNSAT*
LOT-SIM-JP-300-K11 Page 5 of 11 REV. 1
SEP-04 Restart RB HVAC with Failure to Isolate PROMPT:
If asked, inform examinee that instrument air pressure to the Reactor Building ventilation isolation valve latch actuators was never lost, OR:
PROMPT:
If requested, inform the examinee as Reactor Building Auxiliary Operator that the tches for the Reactor Building Ventilation Isolation Dampers are in the Step 5
- Open RB Vent Isol Vlvs:
a.
C-BFIV-RB and A-BFIV-RB C-BFIV-RB, A-BFIV-RB are open (by depressing the upper lens cover for the valves).
- CRITICAL STEP **
SAT/UNSAT*
b.
D-BFIV-RB and B-BFIV-RB D-BFIV-RB, B-BFIV-RB are open (by depressing the upper lens cover for the valves).
- CRITICAL STEP **
SATIUNSAT*
NOTE:
The RB HVAC Exhaust Fans should be started prior to starting a Supply Fan.
(i.e. An exhaust should be started followed by a supply fan, then an exhaust fan started followed by a supply fan until all exhaust and supply fans are Step 8
- Start as many Reactor Building Exhaust and Supply Fans as possible to provide maximum ventilation.
All four Reactor Building Exhaust and Supply Fans are running.
- CRITICAL STEP **
SAT!UNSAT*
LOT-SIM-JP-300-K1 1 Page 6 of 11 REV. 1 SEP Restart RB HVAC with Failure to Isolate PROMPT:
If asked, inform examinee that instrumentair pressure to the Reactor Building ventilation isolation valve latch actuators was never lost, OR:
PROMPT:
If requested, inform the examinee as. Reactor Building Auxiliary Operator that the latches for the Reactor Building Ventilation Isolation Dampers are in the unlatched position.
Step 5 - Open RB Vent Isol Vlvs:
NOTE:
- a.
C-BFIV-RB and A-BFIV-RB C-BFIV-RB, A-BFIV-RB are open (by depressing the upper lens cover for the valves).
- CRITICAL STEP ** SAT/UNSAT*
- b.
D-BFIV-RB and B-BFIV-RB D-BFIV-RB, B-BFIV-RB are open (by depressing the upper lens cover for the valves).
- CRITICAL STEP ** SAT/UNSAT*
The RB HVAC Exhaust Fans should be started prior to starting a Supply Fan.
(i.e. An exhaust should be started followed by a supply fan, then an exhaust fan should be started followed by a supply fan until all exhaust and supply fans are running.
Step 8 - Start as many Reactor Building Exhaust and Supply Fans as possible to provide maximum ventilation.
All four Reactor Building Exhaust and Supply Fans are running.
- CRITICAL STEP ** SA TlUNSAT*
LOT-SIM-JP-300-K11 Page 6 of 11 REV. 1
SEP-04 Restart RB HVAC with Failure to Isolate SIM OP:
When all RB HVAC Supply Fans have been started insert Event Trigger El to cause REACTOR BLDG VENT RAD Monitor to start to rise and go above 4 mr/hr.
Step 9 Recognizes Reactor Building Vent Rad Monitor increasing.
Radiation monitor readings are rising.
SATIUNSAT*
NOTE:
Closing the BFIV-RB5 will cause the Reactor Building Vent and Supply fans to automatically trip.
Step 10 Manually stop the Reactor Building Supply and Exhaust Fans.
All Reactor Building Supply and Exhaust Fans are stopped.
SATIU NSAT*
NOTE:
Closing the BFIV-RBs will cause the RB Vent Rad Monitors overrides to be deleted and go to normal readings.
Step 11 Manually close RB Vent Isol VIvs:
a.
C-BFIV-RB and A-BFIV-RB C-BFIV-RB, A-BFIV-RB are closed (by depressing the lower lens cover for the valves).
- CRITICAL STEP **
SATIUNSAT*
b.
D-BFIV-RB and B-BFIV-RB D-BFIV-RB, B-BFIV-RB are closed (by depressing the lower lens cover for the valves).
- CRITICAL STEP **
SATIUNSAT*
LOT-SIM-JP-300-Kl 1 Page 7 of 11 REV. 1 SIM OP:
SEP Restart RB HVAC with Failure to Isolate When all RB HVAC Supply Fans have been started insert EvenfTrigger E1 to cause REACTOR BLDG VENT RAD Monitor to start to rise and go above 4 mr/hr.
Step 9 - Recognizes Reactor Building Vent Rad Monitor increasing.
Radiation monitor readings are rising.
SAT/UNSAT*
NOTE:
Closing the BFIV-RBs will cause the Reactor Building Ventand Supply fans to automatically trip.
Step 10 - Manually stop the Reactor Building Supply and Exhaust Fans.
NOTE:
All Reactor Building Supply and Exhaust Fans are stopped.
SAT/UNSAT*
Closing the BFIV-RBs will cause.the RB Vent Rad Monitors overrides to be deleted and go to normal readings.
Step 11 - Manually close RB Vent Isol Vlvs:
- a.
C-BFIV-RB and A-BFIV-RB C-BFIV-RB, A-BFIV-RB are closed (by depressing the lower lens cover for the valves).
- CRITICAL STEP ** SAT/UNSAT*
- b.
D-BFIV-RB and B-BFIV-RB D-BFIV-RB, B-BFIV-RB are closed (by depressing the lower lens cover for the valves).
- CRITICAL STEP ** SAT/UNSAT*
LOT-SIM-JP-300-K11 Page 7 of 11 REV. 1
SEP-04 Restart RB HVAC with Failure to Isolate Step 12
- Ensure initiated SBGT system.
Both SBGT trains are operating (verifies only, both trains were already in operation).
SATIUNSAT*
Step 13 Unit SCO informed that SEP-04, RB HVAC Restart procedure cannot be performed at this time.
Unit SCO informed.
SATIUNSAT*
IITERMINATING CUE:
RB HVAC has been isolated and SBGT has been verified running.
- Comments required for any step evaluated as UNSAT.
STOP TIME:
LOT-SIM-JP-300-K1 1 Page 8 of 11 REV. I SEP Restart RB HVAC with Failure to Isolate Step 12 - Ensure initiated SBGT system.
Both SBGT trains are operating (verifies only, both trains were already in operation).
SAT/UNSAT*
Step 13 - Unit SCQ informed that SEP-04, RB HVAC Restart procedure cannot be performed at this time.
Unit SeQ informed.
SATIUNSAT*
I TERMINATING CUE:
. RBHVAC has been isolated and SBGT has been verified running.
- Comments required for any step evaluated as UNSAT.
STOP TIME: ____ _
LQT-SIM-JP-300-K11 Page 8 of 11 REV. 1
SEP-04 Restart RB HVAC with Failure to Isolate LIST OF REFERENCES RELATED TASKS:
288205B501 Restart Reactor Building HVAC per EOP-01-SEP-04 K/A REFERENCE AND IMPORTANCE RATING:
288000 A3.01 3.8, 3.8 Ability to monitor Plant Ventilation System automatic isolation/initiation signals in the control room
REFERENCES:
OEOP-SEP-04 Rev. 11 TOOLS AND EQUIPMENT:
Plant Page SAFETY FUNCTION (from NUREG 1123, Rev 2):
9 Radioactivity Release REASON FOR REVISION:
Changed to rad signal vs high temperature for the alternate path.
LOT-SIM-JP-300-K1 1 Page 9 of 11 REV. 1 SEP Restart RB HVAC with Failure to Isolate LIST OF REFERENCES RELATED TASKS:
288205B501 Restart Reactor Building HVAC per EOP-01-SEP-04 KIA REFERENCE AND IMPORTANCE RATING:
288000 A3.01 3.8, 3.8 Ability to monitor Plant Ventilation System automatic isolation/initiation signals in the control room
REFERENCES:
OEOP-SEP-04 Rev. 11 TOOLS AND EQUIPMENT:
Plant Page SAFETY FUNCTION (from NUREG 1123, Rev 2):
9 - Radioactivity Release REASON FOR REVISION:
Changed to rad signal vs high temperature for the alternate path.
LOT-SIM-JP-300-K11 Page 9 of 11 REV. 1
SEP-04 Restart RB HVAC with Failure to Isolate Time Required for Completion:
20 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate
Actual X
Unit:
2 Setting:
Control Room Simulator X
(Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes X
No EVALUATION Trainee:_______________________________
JPM:
Pass Fail Remedial Training Required: Yes No Did Trainee Verify Procedure as Authorized Copy?:
Yes No (Each Student should verify one JPM per evaluation set)
Comments:
Comments reviewed with Student Evaluator Signature:
Date:___________
LOT-SIM-JP-300-K11 Page 10 of 11 REV. I SEP Restart RB HVAC with Failure to Isolate Time Required for Completion: ~
Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room Simulator~ (Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Alternate Path:
Yes X
No EVALUATION Trainee: --------------------------
JPM:
Pass ___
Fail __
Remedial Training Required: Yes No ___
Did Trainee Verify Procedure as Authorized Copy?: Yes __
(Each Student should verify one JPM per evaluation set)
Comments:
Comments reviewed with Student Time Limit N/A No -----
Evaluator Signature:
Date: ________ _
LOT-SIM-JP-300-K11 Page 10 of 11 REV. 1
TASK CONDITIONS:
1.
EOP-03-SCCP has been entered on Unit Two.
2.
A high-radiation condition sensed by the RB Vent Radiation Monitors (D12-R609A/B) resulted in the isolation of Reactor Building HVAC.
3.
Reactor Building Exhaust temperature has not exceeded 135°F.
4.
The leak has been isolated and EOP-03-SCCP directs restoring RB HVAC.
5.
Instrument air pressure to the latch actuators for the reactor building ventilation isolation valves was never lost.
INITIATING CUE:
The Unit SCO directs you to restart Reactor Building HVAC per SEP-04 and inform him when your actions are complete.
TASK CONDITIONS:
- 1.
EQP-03-SCCP has been entered on Unit Two.
- 2.
A high-radiation condition sensed by the RB Vent Radiation Monitors (012-R609A/B) resulted in the isolation of Reactor Building HVAC.
- 3.
Reactor Building Exhaust temperature has not exceeded 135°F.
- 4.
The leak has been isolated and EQP-03-SCCP directs restoring RB HVAC.
- 5.
Instrument air pressure to the latch actuators for the reactor building ventilation isolation valves was never lost.
INITIATING CUE:
The Unit SCQ directs you to restart Reactor Building HVAC per SEP-04 and inform him when your actions are complete.
Prngress Energy BRUNSWICK NUCLEAR PLANT PLANT OPERATING MANUAL VOLUME VI EMERGENCY OPERATING PROCEDURE UNIT 0
OEOP-01 -SEP-04 REACTOR BUILDING HVAC RESTART PROCEDURE REVISION 12 OEOP-O1-SEP-04 Rev. 12 Page 1 of 6
~
Progress Energy BRUNSWICK NUCLEAR PLANT PLANT OPERATING MANUAL VOLUME VI EMERGENCY OPERATING PROCEDURE UNIT o
OEOP-01-SEP-04 REACTOR BUILDING HVAC RESTART PROCEDURE REVISION 12 I OEOP-01-SEP-04 Rev. 12 Page 1 of 61
REACTOR BUILDING HVAC RESTART 1.0 ENTRY CONDITIONS As directed by Secondary Containment Control Procedure, EOP-03-SCCP OR As directed by Containment and Radioactivity Release Control, SAMG-02 2.0 OPERATOR ACTIONS NOTE:
Manpower:
1 Control Operator I Auxiliary Operator I Independent Verifier Special equipment:
2 jumpers (10 and 11)
CO:
2.1.
IF the reactor building ventilation radiation monitors have been off scale high as indicated on D12-RR-R605 OR the reactor building exhaust temperature has exceeded 135°F (UA-03, 6-2),
THEN EXIT this procedure.
CAUTION Installation of the following jumpers will also inhibit the automatic start of SBGT on reactor low water level and on high drywell pressure.
2.2 INSTALL the following jumpers to bypass the reactor low water level and drywell high pressure interlocks:
CO:
Jumper 10 in Panel XU-27, Terminal Board E, from the right side of Terminal 28 to the right side of Terminal 30 CO:
Jumper 11 in Panel XU-28, Terminal Board E, from the right side of Terminal 28 to the right side of Terminal 30 OEOP-0I-SEP-04 Rev. 12 Page 2 of 6 REACTOR BUILDING HVAC RESTART 1.0 ENTRY CONDITIONS As directed by Secondary Containment Control Procedure, EOP-03-SCCP OR As directed by Containment and Radioactivity Release Control, SAMG-02 2.0 OPERATOR ACTIONS NOTE:
Manpower:
Special equipment:
1 Control Operator 1 Auxiliary Operator 1 Independent Verifier 2 jumpers (10 and 11)
CO:
2.1.
IF the reactor building ventilation radiation monitors have been Iffi) off scale high as indicated on 012-RR-R605 OR the reactor building exhaust temperature has exceeded 135°F (UA-03, 6-2),
THEN EXIT this procedure.
CAUTION Installation of the following jumpers will also inhibit the automatic start of SBGT on reactor low water level and on high drywell pressure.
2.2 INSTALL the following jumpers to bypass the reactor low water level and drywell high pressure interlocks:
CO:
Jumper 10 in Panel XU-27, Terminal Board E, from the right side of Terminal 28 to the right side of Terminal 30 CO:
Jumper 11 in Panel XU-28, Terminal Board E, from the right side of Terminal 28 to the right side of Terminal 30 I OEOP-01-SEP-04 Rev. 12 Page 2 of 61
2.0 OPERATOR ACTIONS CO:
2.3 PLACE the affected units CAC PURGE VENT ISOL OVRD, CAC-CS-5519, switch to OVERRIDE.
2.4 IF necessary, THEN RESET the following reactor building ventilation radiation monitors at Panel H12-P606:
CO:
PROCESS REACTOR BLDG VENTILATION RADIATION MONITOR A, D12-RM-K609A CO:
PROCESS REACTOR BLDG VENTILATION RADIATION MONITOR B, D12-RM-K609B CO:
2.5 RESET the Group 6 isolation from the RTGB.
r NOTE:
IF the green indicator tab is against the yellow bar, THEN the valve is
[
unlatched and valve operation is permitted.
CAUTION Attempting to open reactor building ventilation isolation valves when the latches are engaged will damage the latch/damper assemblies.
2.6 IF instrument air pressure to the latch actuators for the reactor building ventilation isolation valves has been lost and restored, THEN DISPATCH an AC to ensure the latches for the following valves are in the unlatched position prior to performing Step 2.7:
AO:
RB VENT INBD SUPPLY ISOL VLV, A-BFIV-RB AO:
RB VENT OTBD SUPPLY ISOL VLV, B-BFIV-RB AO:
RB VENT INBD EXHAUST ISOL VLV, C-BFIV-RB AO:
RBVENTOTBDEXHAUSTISOLVLV,D-BFIV-RB OEOP-O1-SEP-04 Rev. 12 Page 3 of 6 2.0 OPERATOR ACTIONS CO:
2.3 PLACE the affected unit's CAC PURGE VENT ISOL OVRD, CAC-CS-5519, switch to OVERRIDE.
2.4 IF necessary, THEN RESET the following reactor building ventilation radiation monitors at Panel H12-P606:
CO:
PROCESS REACTOR BLDG VENTILA TlON RADIA TlON MONITOR A, D12-RM-K609A CO:
PROCESS REACTOR BLDG VENTILA TlON RADIA TlON MONITOR B, D12-RM-K609B CO:
2.5 RESET the Group 6 isolation from the RTGB.
NOTE:
IF the green indicator tab is against the yellow bar, THEN the valve is unlatched and valve operation is permitted.
CAUTION D
D D
D Attempting to open reactor building ventilation isolation valves when the latches are engaged will damage the latch/damper assemblies.
AO:
AO:
AO:
AO:
2.6 IF instrument air pressure to the latch actuators for the reactor building ventilation isolation valves has been lost and restored, THEN DISPATCH an AO to ensure the latches for the following valves are in the unlatched position prior to performing Step 2.7:
RB VENT INBD SUPPL Y ISOL VL V, A-BFIV-RB RB VENT OTBD SUPPL Y ISOL VL V, B-BFIV-RB RB VENT INBD EXHAUST ISOL VL V, C-BFIV-RB RB VENT OTBD EXHAUST ISOL VL V, D-BFIV-RB I OEOP-01-SEP-04 Rev. 12 D
D D
D Page 3 of 61
2.0 OPERATOR ACTIONS 2.7 OPEN the following valves:
CO:
RB VENT INBD ISOL VALVES, EXHAUST C-BFIV-RB, SUPPLY A-BFIV-RB CO:
RB VENT OTBD ISOL VALVES, EXHAUSTD-BFI V-RB, SUPPLY B-BFIV-RB NOTE:
In order to start a reactor building supply or exhaust fan, the control switch should be held in START until the discharge damper is full open.
CO:
2.8 START as many reactor building exhaust and supply fans as possible to provide maximum ventilation (OP-37.1).
2.9 IF PROCESS RX BLDG VENT RAD HI-HI annunciator (UA-03 3-5) (alarm setpoint at 4 mR/hr) OR f?)( BLDG VENT TEMP HIGH annunciator (UA-03 6-2) (alarm setpoint at 135°F) is received, THEN:
CO:
a.
ENSURE reactor building exhaust and supply fans are off.
b.
ENSURE the following valves are closed:
CO:
RB VENT INBD ISOL VALVES, EXHAUST C-BFIV-RB, SUPPLY A-BFIV-RB CO:
RB VENTOTBDISOL VALVES, EXHAUST D-BFIV-RB, SUPPLY B-BFIV-RB GO:
c.
ENSURE the SBGT System has initiated (OP-b).
OEOP-O1-SEP-04 Rev. 12 Page4of6 2.0 OPERATOR ACTIONS CO:
CO:
2.7 OPEN the following valves:
RB VENT INBD ISOL VALVES, EXHAUST C-BFIV-RB, SUPPL Y A-BFIV-RB RB VENT OTBD ISOL VALVES, EXHAUST D-BFIV-RB, SUPPL Y B-BFIV-RB o
o NOTE:
In order to start a reactor building supply or exhaust fan, the control switch should be held in START until the discharge damper is full open.
CO:
2.8 START as many reactor building exhaust and supply fans as 0
possible to provide maximum ventilation (OP-37.1).
2.9 IF PROCESS RX BLDG VENT RAD HI-HI annunciator (UA-03 3-5) (alarm setpoint at 4 mR/hr) OR RX BLDG VENT TEMP HIGH annunciator (UA-03 6-2) (alarm setpoint at 135°F) is received, THEN:
CO:
- a.
ENSURE reactor building exhaust and supply fans are off.
0
- b.
ENSURE the following valves are closed:
CO:
RB VENT INBD ISOL VALVES, EXHAUST 0
C-BFIV-RB, SUPPL Y A-BFIV-RB CO:
RB VENT OTBD ISOL VALVES, EXHAUST 0
D-BFIV-RB, SUPPL Y B-BFIV-RB CO:
- c.
ENSURE the SBGT System has initiated (OP-10).
0 I OEOP-01-SEP-04 Rev. 12 Page 4 of 61
2.0 OPERATOR ACTIONS Initials 2.10 WHEN reactor low water level and drywell high pressure conditions have cleared, THEN REMOVE the following jumpers:
GO:
Jumper 10 in Panel XU-27, Terminal Board E, from the I
right side of Terminals 28 and 30 Ind.Ver.
GO:
Jumper 11 in Panel XU-28, Terminal Board E, from the I
right side of Terminals 28 and 30 Ind.Ver.
GO:
2.11 WHEN PROCESS OG VENT PIPE RAD HI-HI annunciator
/
(UA-03 5-4) clears, THEN PLACE CAC PURGE VENT ISOL Ind.Ver.
OVRD, CAC-CS-5519, switch to OFF.
GO:
2.12 OPERATE the Reactor Building Ventilation System and the SBGT System as directed by the Unit SCO (OP-37.1 and OP-i 0).
CO:
2.13 EXIT this procedure AND CONTINUE in the procedure(s) in effect.
Date/Time Completed______________
Performed By (Print)
Initials Reviewed By:
Unit SCO OEOP-01-SEP-04 Rev. 12 Page 5 of 6 2.0 OPERA TOR ACTIONS Initials 2.10 WHEN reactor low water level and drywell high pressure conditions have cleared, THEN REMOVE the following jumpers:
CO:
Jumper 10 in Panel XU-27, Terminal Board E, from the
/
right side of Terminals 28 and 30 IndVer.
CO:
Jumper 11 in Panel XU-28, Terminal Board E, from the
/
right side of Terminals 28 and 30 IndVer.
CO:
2.11 WHEN PROCESS OG VENT PIPE RAO HI-HI annunciator
/
(UA-03 5-4) clears, THEN PLACE CAC PURGE VENT ISOL Ind.Ver.
OVRO, CAC-CS-5519, switch to OFF.
CO:
2.12 OPERATE the Reactor Building Ventilation System and the SBGT System as directed by the Unit SCO (OP-37.1 and OP-10).
CO:
2.13 EXIT this procedure AND CONTINUE in the procedure(s) in effect.
DatelTime Completed Performed By (Print)
Initials Reviewed By: _____________ _
Unit SCO I OEOP-01-SEP-04 Rev. 12 Page 5 of 61
REVISION
SUMMARY
Revision 12 converts the document and upgrades procedure format. Added independent verifier to manpower requirements.
Revision 11 incorporates changes required to support implementation of Severe Accident Management Guidelines. Entry conditions have been revised to reflect possible entry from Containment and Radioactivity Release Control, OSAMG-02.
Allowances to restart ventilation when 135°F has been exceeded have been deleted due to Reactor Building EQ concerns.
OEOP-01 -SEP-04 Rev. 12 Page 6 of 6 REVISION
SUMMARY
Revision 12 converts the document and upgrades procedure format. Added independent verifier to manpower requirements.
Revision 11 incorporates changes required to support implementation of Severe Accident Management Guidelines. Entry conditions have been revised to reflect possible entry from Containment and Radioactivity Release Control, OSAMG-02.
Allowances to restart ventilation when 135°F has been exceeded have been deleted due to Reactor Building EO concerns.
I OEOP-01-SEP-04 Rev. 12 Page 6 Of61
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim C LESSON TITLE:
Place B Loop RHR in Suppression Pool Cooling lAW Hard Card
NSW Header Failure LESSON NUMBER:
LOTSIM-JP-O17-A1O REVISION NO:
7 I
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim C LESSON TITLE: Place BLoop RHR in Suppression Pool Cooling lAW Hard Card-NSW Header Failure LESSON NUMBER: LOT-SIM-JP-017-A10 REVISION NO:
7
Place B Loop RHR in Suppression Pool Cooling lAW Hard Card NSW Header Failure A.
Initial Conditions:
1.
Recommended Initial Conditions IC 11 Rx. Pwr.
100%
Core Age BOC 2.
Required Plant Conditions Suppression Pool Temperature> 95°.
B.
Malfunctions None required C.
Overrides Switches Event Pane Tag Title Value Activate Deactivate I
(ramp rate)
Time (sec)
Time (sec)
NA P601 K1705A RHR SW Pmps BID Nu SW-V105 As Is 0
0 D.
Remote Function Event Panel Tag Title Value Activate Deactivate (ramp rate)
Time (sec)
Time (sec)
NA P601 ZVSW105M SW.V105 NSW to RHRSW 0
0 E.
Special Instructions
- 1. Open SRV(s) as necessary to raise Suppression Pool temperature above 95°.
- 2. Ensure Suppression Pool High Temperature alarm on Panel UA-12 is annunciated.
- 3. Place red caps on RHR Pump 2A and 2C.
LOT-SIM-JP-0l 7-Al 0 Page 2 of 9 Rev.7 Place BLoop RHR in Suppression Pool Cooling lAW Hard Card - NSW Header Failure A.
Initial Conditions:
- 1.
Recommended Initial Conditions IC Rx. Pwr.
Core Age 11 100%
- 2.
Required Plant Conditions Suppression Pool Temperature> 95°.
B.
Malfunctions None required*
C.
Overrides Switches Event Pane Tag Title I
NA P601 K1705A RHR SW Pmps BID Nu SW-V105 D.
Remote Function Event Panel Tag Title NA P601 ZVSW105M SW-V105 NSW to RHRSW E.
Special Instructions Value Activate Deactivate (ramp rate)
Time (sec)
Time (sec)
As Is 0
0 Value Activate Deactivate (ramp rate)
Time (sec)
Time (sec)
Off 0
0
- 1. Open SRV(s) as necessary to raise Suppression Pool temperature above 95°.
- 2. Ensure Suppression Pool High Temperature alarm on Panel UA-12 is annunciated.
- 3. Place red caps on RHR Pump 2A and 2C.
LOT-SIM-JP-017-A10 Page 2 of 9 Rev.7
Place B Loop RHR in Suppression Pool Cooling lAW Hard Card NSW Header Failure SAFETY CONSIDERATIONS:
NONE EVALUATOR NOTES: (Do not read to examinee)
- 1. The applicable procedure section WILL be provided to the examinee, once it is demonstrated he/she knows the correct procedure.
2.
If this is the first JPM of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the examinee.
Read the following to examinee.
TASK CONDITIONS:
- 1. Torus temperatures is >95°F due to SRV B failure.
2.
SRV B fuses have been pulled which closed the valve.
3.
Primary Containment Control Procedure requires Suppression Pool Cooling to be placed in service.
- 4. The standby NSW pump has been started.
5.
RHR Loop A is under clearance.
INITIATING CUE:
The Unit CRS has directed you to place B RHR Loop in suppression pooi cooling per the Emergency Suppression Pool Cooling Hard Card (One RHRSW pump and one RHR pump).
LOT-SIM-JP-017-A10 Page 3 of 9 Rev.7 Place BLoop RHR in Suppression Pool Cooling lAW Hard Card - NSW Header Failure SAFETY CONSIDERATIONS:
NONE EVALUATOR NOTES: (Do not read to examinee)
- 1. The applicable procedure section WILL be provided to the examinee, once it is demonstrated he/she knows the correct procedure.
- 2. If this is the first JPM of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the examinee.
Read the following to examinee.
TASK CONDITIONS:
- 1. Torus temperatures is >95°F due to SRV B failure.
- 2. SRV B fuses have been pulled which closed the valve.
- 3. Primary Containment Control Procedure requires Suppression Pool Cooling to be placed in service.
- 4. The standby NSW pump has been started.
- 5. RHR Loop A is under clearance.
INITIATING CUE:
The Unit CRS has directed you to place B RHR Loop in suppression pool cooling per the Emergency Suppression Pool Cooling Hard Card (One RHRSW pump and one RHR pump).
LOT -SIM-JP-01? -A 10 Page 3 of 9 Rev.?
Place B Loop RHR in Suppression Pool Cooling lAW Hard Card NSW Header Failure PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
PROMPT If asked, another RO is not available to perform peer checks I lVs I
Step 1 -Obtain current revision of Emergency Suppression Pool Cooling hard card for Loop B, if required.
Current revision of Emergency Suppression Pool Cooling hard card obtained.
NAISATIU NSAT*
TIME START:
Step 2
- Attempt to open suction valve to RHR SW pump from NSW SW-V105.
Recognize SW-V105 will not open.
SATIUNSAT*
PROMPT:
If requested to manually open SW-V105, report valve is mechanically bound and will not open by handwheel.
If requested to turn breaker OFF for SW-V105, activate REMOTE FUNCTION, ZVSWIO5M, SW-V105 NSW to RHRSW, OFF.
PROMPT:
If Examinee informs Unit CRS RHR cannot be placed into service using NSW, direct the examinee that EOP flowcharts require RHR Loop B to be placed in Suppression Pool Cooling now.
If asked, give permission to place B Loop in service using CSW header.
Step 3
- Open CSW SW-ViOl, Conventional Service Water to RHRSW Pumps.
CSW SW-VIOl opened.
- CRITICAL STEP ** SATIUNSAT*
Step 4
- Close SW-V143, RHR SW Well Water Supply Valve.
SW-V143 switch is placed in closed.
SATIU NSAT*
LOT-SIM-JP-017-A1O Page 4 of 9 Rev.7 Place BLoop RHR in Suppression Pool Cooling lAW Hard Card - NSW Header Failure PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
PROMPT:
If asked, another RO is not available to perform peer checks IIVs.
Step 1 -Obtain current revision of Emergency Suppression Pool Cooling hard card for Loop B, if required.
Current revision of Emergency Suppression Pool Cooling hard card obtained.
NAISAT/UNSAT*
TIME START: ____
Step 2 - Attempt to open suction valve to RHR SW pump from NSW SW-V105.
Recognize SW-V1 05 will not open.
. SAT/UNSAT*
PROMPT:
PROMPT:
If requested to manually open SW-V105, report valve is mechanically bound and will not open by handwheel. If requested to turn breaker OFF for SW-V105, activate REMOTE FUNCTION, ZVSW105M,SW-V105 NSW toRHRSW, OFF.
If Examinee informs Unit CRS RHR cannot be placed into service using NSW, direct the examinee that EOP flowcharts require RHR Loop B to be placed in Suppression Pool Cooling how.
If asked, give permission to place B Loop in service using CSW header.
Step 3 - Open CSW SW-V1 01, Conventional Service Water to RHRSW Pumps.
CSW SW-V1 01 opened.
- CRITICAL STEP ** SAT/UNSAT*
Step 4 - Close SW-V143, RHR SW Well Water Supply Valve.
SW-V143 switch is placed in closed.
SAT/UNSAT*
LOT-SIM-JP-01?-A 10 Page 4 of 9 Rev.?
Place B Loop RHR in Suppression Pool Cooling lAW Hard Card NSW Header Failure Step 5
- Open SW-V102, Conventional-Nuclear Header Cross-tie valve.
Crosstie valve SW-V102, switch placed in open.
- CRITICAL STEP ** SATIUNSAT*
Step 6
- If LOCA signal is present PLACE RHR SW Booster Pumps B & D LOCA Override Switch to Manual Override Recognize no LOCA signal is present (RPV Water Level / Reactor Pressure / DW Pressure / No initiation lights on RHR, etc.) and override is not required.
SAT!UNSAT*
NOTE:
Examinee may start an additional CSW pump on the Conventional Header. This would not be required for the performance of this JPM.
Step 7
- Start 2B or 2D RHR SW pumps.
28 or 2D RHR SW (Booster) pump started.
- CRITICAL STEP ** SATIUNSAT*
Step 8
- Adjust RHR HX 2B SW Discharge Valve, El l-PDV-F068B to obtain desired RHR SW flow.
Flow is adjusted using F068B to obtain 2000 - 4000 gpm.
- CRITICAL STEP ** SATIUNSAT*
Step 9 Supply cooling water to the Vital Header.
SW-V1 II or SW-VI 17 opened to supply cooling water to the Vital Header.(V1 17 valve is a throttle valve, VIII is not)
SATIUNSAT*
Step 10 If LOCA signal is present, Verify Spray Logic is made up.
Recognize Spray Logic not required.
SAT!UNSAT*
LOT-SIM-JP-017-A10 Page 5 of 9 Rev.7 Place BLoop RHR in Suppression Pool Cooling lAW Hard Card - NSW Header Failure Step 5 - Open SW-V102, Conventional-Nuclear Header Cross-tie valve.
Grosstie valve SW-V102, switch placed in open.
- CRITICAL STEP ** SAT/UNSAT*
Step 6 - If LOCA signal is present PLACE RHR SW Booster Pumps B & D LOCA Override Switch to Manual Override NOTE:
Recognize no LOGA signal is present (RPV Water Level/Reactor Pressure / OW Pressure / No initiation lights on RHR, etc.) and override is not required.
SAT/UNSAT*
Examinee may start an additional CSW pump on the Conventional Header. This would not be required for the performance of this JPM.
Step 7 - Start 2B or 2D RHR SW pumps.
2B or 20 RHR SW (Booster) pump started.
- CRITICAL STEP ** SAT/UNSAT*
Step 8 - Adjust RHR HX 2B SW Discharge Valve, E11-PDV-F068B to obtain desired RHR SW flow.
Flow is adjusted using F068B to obtain 2000 - 4000 gpm.
- CRITICAL STEP ** SAT/UNSAT*
Step 9 - Supply cooling water to the Vital Header.
SW-V111 or SW-V117 opened to supply cooling water to the Vital Header. (V117 valve is a throttle valve, V111 is not)
SAT/UNSAT*
Step 10 - If LOCA signal is present, Verify Spray Logic is made up.
Recognize Spray Logic not required.
SATIUNSAT*
LOT-SIM-JP-01?-A10 Page 5 of 9 Rev.?
Place B Loop RHR in Suppression Pool Cooling lAW Hard Card NSW Header Failure Step 11 If EII-FOI5B is open, then close El l-FO17B.
Recognize El l-FQI5B is not open and El 1-FOl 7B closure is not required.
SATIUNSAT*
Step 12 Start RHR Pump 2B or 2D.
RHR pump 28 or 2D started.
- CRITICAL STEP ** SATIUNSAT*
Step 13 Open Ell-F028B, Torus Discharge Isolation Valve.
El l-F028B keylock is placed in open.
- CRITICAL STEP ** SATIUNSAT*
Step 14Throttle open El1-F024B, Torus Cooling Isolation Valve, to establish desired flow.
El l-F024B throttled open to obtain 4000-10,000 gpm (I pump) (this is the green band for one pump operation on the indicator).
- CRITICAL STEP ** SATIUNSAT*
Step 15 Throttle closed El 1-F048B, HX Bypass Valve.
El l-F048B throttled fully closed.
SATIUNSAT*
Step 16
- Inform Unit CRS that B Loop RHR Suppression Pool Cooling is in service with one pump operation and cooling is aligned to the Conventional Service Water header.
Unit CRS notified.
SATIUNSAT*
I TERMINATING CUE: When the El 1-F024B has been opened and 6,000 to 10000 gpm flow has been established this JPM can be terminated.
- Comments required for any step evaluated as UNSAT.
TIME STOP:
LOT-SIM-JP-017-Al0 Page 6 of 9 Rev.7 Place BLoop RHR in Suppression Pool Cooling lAW Hard Card - NSW Header Failure Step 11 - If EII-F015B is open, then close E 11-F017B.
Recognize E11-F015B is not open and E11-F017B closure is not required.
SAT/UNSAT*
Step 12 - Start RHR Pump 2B or 2D.
RHR pump 2B or 20 started.
- CRITICAL STEP ** SAT/UNSAT*
Step 13 - Open E11-F028B, Torus Discharge Isolation Valve.
E11-F028B keylock is placed in open.
- CRITICAL STEP ** SAT/UNSAT*
Step 14 -Throttle open E 11-F024B, Torus Cooling Isolation Valve, to establish desired flow.
E11-F024B throttled open to obtain 4000-10,000 gpm (1 pump) (this is the green band for one pump operation on the indicator).
- CRITICAL STEP ** SAT/UNSAT*
Step 15 - Throttle closed E11-F048B, HX Bypass Valve.
E11-F048B throttled fully closed.
SAT/UNSAT*
Step 16 - Inform Unit CRS that BLoop RHR Suppression Pool Cooling is in service with one pump operation and cooling is aligned to the Conventional Service Water header.
Unit CRS notified.
SAT/UNSAT*
TERMINATING CUE: When the E11-F024B has been opened and 6,000 to 10,000 gpm flow has been established this JPMcan be terminated.
- Comments required for any step evaluated as UNSAT.
TIME STOP: ____
LOT-SIM-JP-01 ?-A1 0 Page 6 of 9 Rev.?
Place B Loop RHR in Suppression Pool Cooling lAW Hard Card NSW Header Failure LIST OF REFERENCES RELATED TASKS:
205 014 BI 01 Start Up RHR In Suppression Pool Cooling Mode Per OP-17 KIA REFERENCE AND IMPORTANCE RATING:
219000 A4.12 4.1,4.1 Ability to manually operate and/or monitor in the control room suppression pool temperature.
REFERENCES:
Emergency Suppression Pool Cooling hard card, S/i 064.
TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev 2):
Safety Function 5, Containment Integrity REASON FOR REVISION:
Changed to one pump vs. maximizing due to PU&A concerns.
LOT-SIM-JP-017-A10 Page 7 of 9 Rev.7 Place 8 Loop RHR in Suppression Pool Cooling lAW Hard Card - NSW Header Failure LIST OF REFERENCES RELATED TASKS:
20501481 01 Start Up RHR In Suppression Pool Cooling Mode Per OP-17 KIA REFERENCE AND IMPORTANCE RATING:
219000 A4.12 4.1,4.1 Ability to manually operate and/or monitor in the control room suppression pool temperature.
REFERENCES:
Emergency Suppression Pool Cooling hard card, S/1064.
TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev 2):
Safety Function 5, Containment Integrity REASON FOR REVISION:
Changed to one pump vs. maximizing due to PU&A concerns.
LOT-SIM-JP-017-A 10 Page 7 of 9 Rev.7
Place B Loop RHR in Suppression Pool Cooling lAW Hard Card NSW Header Failure Time Required for Completion: 15 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room Simulator X
(Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes X
No EVALUATION Examinee:______________________________
JPM:
Pass Fail Remedial Training Required: Yes No Did Examinee Verify Procedure?
Yes No (Each Student should verify one JPM per evaluation set)
Comments:
Comments reviewed with Student Evaluator Signature:
Date:___________
LOT-SIM-JP-017-A1O Page 8 of 9 Rev.7 Place BLoop RHR in Suppression Pool Cooling lAW Hard Card - NSW Header Failure Time Required for Completion:~ Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual l Unit:
2 Setting:
Control Room Simulator l (Not applicable to In-Plant JPMs)
Time Critical:
Yes No l Time Limit N/A Alternate Path:
Yes X
No EVALUATION Examinee: ____________ _
JPM:
Pass --
Fail __
Remedial Training Required: Yes No __
Did Examinee Verify Procedure? Yes __ No __ _
(Each Student should verify one JPM per evaluation set)
Comments: __________________________ _
Comments reviewed with Student Evaluator Signature: ____________ _
Date: ____ _
LOT-SIM-JP-01? -A 10 Page 8 of 9 Rev.?
TASK CONDITIONS:
- 1. Torus temperatures is >95°F due to SRV B failure.
2.
SRV B fuses have been pulled which closed the valve.
3.
Primary Containment Control Procedure requires Suppression Pool Cooling to be placed in service.
- 4. The standby NSW pump has been started.
5.
RHR Loop A is under clearance.
INITIATING CUE:
The Unit CRS has directed you to place B RHR Loop in suppression pool cooling per the Emergency Suppression Pool Cooling Hard Card (One RHRSW pump and one RHR pump).
TASK CONDITIONS:
- 1. Torus temperatures is >95°F due to SRV B failure.
- 2. SRV B fuses have been pulled which closed the valve.
- 3. Primary Containment Control Procedure requires Suppression Pool Cooling to be placed in service.
- 4. The standby NSW pump has been started.
- 5. RHR Loop A is under clearance.
INITIATING CUE:
The Unit CRS has directed you to place B RHR Loop in suppression pool cooling per the Emergency Suppression Pool Cooling Hard Card (One RHRSW pump and one RHR pump).
ATTACHMENT 8 Page 2 of 2 Emergency Suppression Pool Cooling START RHR SW B LOOP (NUC)
OPEN SW-V105 CLOSE SW-Vl43 IF LOCA SIGNAL IS PRESENT PLACE RHR SW BOOSTER PUMPS B & D LOCA OVERRIDE SWITCH TO MANUAL OVERRIDE START RHR SW PMP ADJUST El l-PDV-F068B SUPPLY CLG WTR TO VITAL HDR RHR SW B LOOP (CONV)
OPEN SWViOl CLOSE SW-V143 OPEN SW-V102 IF LOCA SIGNAL IS PRESENT PLACE RHR SW BOOSTER PUMPS B & D LOCA OVERRIDE SWITCH TO MANUAL OVERRIDE START RHR SW PMP ADJUST El I-PDV-F068B SUPPLY CLG WTR TO VITAL HDR START RHR LOOP B IF LOCA SIGNAL IS PRESENT, VERIFY SPRAY LOGIC IS MADE UP IF Ell-FOI5B IS OPEN, THEN CLOSE Ell-FOI7B START LOOP B RHR PMP OPEN Ell-F028B THROTTLE Ell-F024B THROTTLE Ell-F048B 2/1063 S11064 20P-17 Rev. 155 Page 288 of 297 ATTACHMENT 8 Page 2 of 2 Emergency Suppression Pool Cooling START RHR SW BLOOP (NUC)
- OPEN SW-V105
- CLOSE SW-V143
- ADJUST E11-PDV-F068B
- SUPPLY CLG WTR TO VITAL HDR START RHRLOOP B
- OPEN SW-V101
- CLOSE SW-V143
- OPEN SW-V102
- ADJUST E11-PDV-F068B
- SUPPLY CLG WTR TO VITAL HDR
__ : IF LOCA SIGNAL IS PRESENT, VERIFY SPRAY LOGIC IS MADE UP 120P-17
__ : IF E11-F015B IS OPEN, THEN CLOSE E11-F017B
- OPEN E11-F028B
- THROTTLE E11-F024B
- THROTTLE E11-F048B Rev. 155 2/1063 S/1064 Page 288 of 2971
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim 0 LESSON TITLE:
HPCI Start in Pressure Control Per The Hard Card
- Exhaust Diaphragm Failure.
LESSON NUMBER:
LOT-SIM-JP-019-14 REVISION NO:
0 0
LESSON TITLE:
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim D HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
LESSON NUMBER:
LOT-SIM-JP-019-14 REVISION NO:
0
HPCI Start in Pressure Control Per The Hard Card
- Exhaust Diaphragm Failure.
SIMULATOR SETUP Recommended Initial Conditions IC-il 100%, BOC Event Triggers El
- Activates all malfunctions/overrides when F008 is opened.
Malfunctions A,
ESO40F, HPCI Fail To Auto Start A,
ES053F
- E41-F002 Fail To Auto Close A,
ESO54F
- E41-F003 Fail To Auto Close El, ESO47F
- HPCI Stm Brk HPCI Room, 1%, 0 SEC Overrides Lamps El, P601, Ql 11 2SWL, Auto Isol Sig A White, ON with 5 sec activation time El, P601, QIIIISWL, Auto Isol Sig B White, ON with 5 sec activation time Alarms El, P601, ZAI 35, HPCI Isol Trip Sig A, ON with 5 sec activation time El, P601, ZA145, HPCI Isol Trip Sig B, ON with 5 sec activation time El, P601, ZA152, HPCI Turb Exh Diaph Press Hi, On Special Instructions
Perform scram immediate actions
- 3. Ensure RPV level is stable and >LL2 LOT-SIM-JP-0l9-l4 Page 2 of 10 REV. 0 HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
SIMULATOR SETUP Recommended Initial Conditions IC-11 100%, BOC Event Triggers E1 - Activates all malfunctions/overrides when FOOS is opened.
Malfunctions A, ES040F, HPCI Fail To Auto Start A, ES053F - E41-F002 Fail To Auto Close A,
ES054F - E41-F003 Fail To Auto Close E1, ES047F - HPCI Stm Brk HPCI Room, 1 %, 0 SEC Overrides Lamps E1, P601, Q1112SWL, Auto Isol Sig A White, ON with 5 sec activation time E1, P601, Q1111SWL, Auto Isol Sig B White, ON with 5 sec activation time Alarms E1, P601, ZA 135, HPCI Isol Trip Sig A, ON with 5 sec activation time E1, P601, ZA 145, HPCI Isol Trip Sig B, ON with 5 sec activation time E1, P601, ZA 152, HPCI Turb Exh Diaph Press Hi, On Special Instructions
- 2. Perform scram immediate actions
- 3. Ensure RPV level is stable and >LL2 LOT-SIM-JP-019-14 Page 2 of 10 REV. 0
HPCI Start in Pressure Control Per The Hard Card
- Exhaust Diaphragm Failure.
SAFETY CONSIDERATIONS:
None.
EVALUATOR NOTES: (Do not read to trainee)
- 1. The applicable procedure section WILL be provided to the trainee.
2.
If this is the first JPM of the JPM set, read the JPM briefing contained NUREG 1021, Appendix E, or similar to the trainee.
Read the following to trainee.
TASK CONDITIONS:
- 1. The reactor has scrammed due to MSIV closure.
2.
RPV water level is stable.
3.
HPCI is not required for RPV level control.
INITIATING CUE:
You are directed by the Unit CRS to start HPCI for pressure control and lower pressure to 800 psig per the Hard Card and inform the Unit CRS when the actions are complete.
LOT-SIM-JP-019-14 Page 3 of 10 REV. 0 HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
SAFETY CONSIDERATIONS:
None.
EVALUATOR NOTES: (Do not read to trainee)
- 1. The applicable procedure section WILL be provided to the trainee.
- 2. If this is the first JPM of the JPM set, read the JPM briefing contained NUREG 1021, Appendix E, or similar to the trainee.
Read the following to trainee.
TASK CONDITIONS:
- 1. The reactor has scrammed due to MSIV closure.
- 2. RPV water level is stable.
INITIATING CUE:
You are directed by the Unit CRS to start HPCI for pressure control and lower pressure to 800 psig per the Hard Card and inform the Unit CRS when the actions are complete.
LOT-SIM-JP-019-14 Page 3 of 10 REV. 0
HPCI Start in Pressure Control Per The Hard Card
- Exhaust Diaphragm Failure.
PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 Obtain Hard Card for HPCI Pressure Control In EOPs.
Hard Card for HPCI Pressure Control obtained.
SATIU NSAT Time Started:
Initial Reactor Pressure:
NOTE Auto Initiation signal can be verified to be reset by observing the white light is not illuminated or by depressing the reset pushbutton Step 2 Ensure HPCI auto initiation is reset.
HPCI auto initiation is already reset.
SATIU NSAT Step 3 Ensure Auxiliary Oil Pump is not running.
Auxiliary Oil Pump verified not running.
SATIUNSAT Step 4 Place HPCI Flow Control, E41-FIC-R600, in Manual (M), and adjust output demand to approximately midscale, using the Manual lever.
Manual selected and lever (moved to the left) lowered output to midscale.
SATIU NSAT Step 5 Ensure E41-V8 and E41-V9 are closed.
E41-V8 and E41-V9 indicate closed (Valves are already closed).
SATIU NSAT LOT-SIM-JP-019-14 Page 4 of 10 REV. 0 HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 Obtain Hard Card for HPCI Pressure Control In EOPs.
Hard Card for HPCI Pressure Control obtained.
SAT/UNSAT Time Started: ____ _
Initial Reactor Pressure: -----
NOTE:
Auto Initiation signal can be verified to be reset by observing the white light is not illuminated or by depressing the reseipushbutton.
Step 2 Ensure HPCI auto initiation is reset.
HPCI auto initiation is already reset.
SATIUNSAT Step 3 Ensure Auxiliary Oil Pump is not running.
Auxiliary Oil Pump verified not running.
SAT/UNSAT Step 4 Place HPCI Flow Control, E41-FIC-R600, in Manual (M), and adjust output demand to approximately midscale, using the Manual lever.
Manual selected and lever (moved to the left) lowered output to midscale.
SATIUNSAT Step 5 Ensure E41-V8 and E41-V9 are closed.
E41-V8 and E41-V9 indicate closed (Valves are already closed).
SATIUNSAT LOT -SIM-JP-019-14 Page 4 of 10 REV. 0
HPCI Start in Pressure Control Per The Hard Card
- Exhaust Diaphragm Failure.
Step 6 Open E41-FO11.
E41-FO1 I switch is placed to open and indicates full open.
- CRITICAL STEP
- SATIUNSAT Step 7 Open E41-F059.
E4 I-F059 switch is placed to open and indicates full open.
- CRITICAL STEP
- SATIUNSAT Step 8 Start Vacuum Pump and leave in start Vacuum Pump control switch placed in the START position SATIUNSAT Step 9 Open E41-F001.
E41-FOO1 switch is placed to open and indicates full open.
- CRITICAL STEP
- SATIUNSAT Step 10 Start Auxiliary Oil Pump and Leave in START.
Auxiliary Oil Pump control switch placed in the START position.
- CRITICAL STEP
- SATIUNSAT Step 11 Ensure E41-V8 and E41-V9 are open.
Verifies that the red light comes on and the green light goes out for both of these valves. (Auto action that occurs from starting AOP).
SATIU NSAT LOT-SIM-JP-019-14 Page 5 of 10 REV. 0 HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
Step 6 Open E41-F011.
E41-F011 switch is placed to open and indicates full open.
- CRITICAL STEP ** SATIUNSAT Step 7 Open E41-F059.
E41-F059 switch is placed to open and indicates full open.
- CRITICAL STEP ** SAT/UNSAT Step 8 Start Vacuum Pump and leave in start Vacuum Pump control switch placed in the START position SAT/UNSAT Step 9 Open E41-FOO 1.
E41-F001 switch is placed to open and indicates full open.
- CRITICAL STEP ** SAT/UNSAT Step 10 Start Auxiliary Oil Pump and Leave in START.
Auxiliary Oil Pump control switch placed in the START position.
- CRITICAL STEP ** SAT/UNSAT Step 11 Ensure E41-V8 and E41-V9 are open.
Verifies that the red light comes on and the green light goes out for both of these valves. (Auto action that occurs from starting AOP).
SAT/UNSAT LOT-SIM-JP-019-14 Page 5 of 10 REV. 0
HPCI Start in Pressure Control Per The Hard Card Exhaust Diaphragm Failure.
Step 12 When speed stops increasing, then adjust speed to approximately 2100 RPM.
Speed is adjusted to 2100 RPM using the manual adjust lever (slide bar).
SATIUNSAT Step 13 Ensure E41-F012 is closed when flow has increased above 800 gpm.
Verifies that the red light goes out and the green light comes on when flow indication is greater than 800 gpm.
SATIUNSAT Step 14 Ensure E41-F025 and E41-F026 are closed.
Verifies that the green lights are off for both of these valves.
SAT/UNSAT Step 15 Adjust HPCI Flow Control, E41-FIC-R600, setpoint to match system flow, and then Place E41-FIC-R600 in Auto (A).
Depresses Set up or down arrows as needed to match the black setpoint needle with the orange flow indicator needle. Then the Auto (A) button is depressed.
SAT/UNSAT Step 16 Start SBGT.
Places control switches for both trains of SBGT to ON. Verifies heaters red light and Fan On red lights come on for both trains and flow indicators show -3300 scfm.
SAT/UNSAT Step 17 Ensure Barometric Cndsr Condensate Pump is operating.
Observes that the pump auto starts as indicated by the red light on for the pump.
SAT/UNSAT LOT-SIM-JP-019-14 Page 6 of 10 REV. 0 HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
Step 12 When speed stops increasing, then adjust speed to approximately 2100 RPM.
Speed is adjusted to 2100 RPM using the manual adjust lever (slide bar).
SATIUNSAT Step 13 Ensure E41-F012 is closed when flow has increased above 800 gpm.
Verifies that the red light goes out and the green light comes on when flow indication is greater than 800 gpm.
SATIUNSAT Step 14 Ensure E41-F025 and E41-F026 are closed.
Verifies that the green lights are off for both of these valves.
SATIUNSAT Step 15 Adjust HPCI Flow Control, E41-FIC-R600, setpoint to match system flow, and then Place E41-FIC-R600 in Auto (A).
Depresses Set up or down arrows as needed to match the black setpoint needle with the orange flow indicator needle. Then the Auto (A) button is depressed.
SATIUNSAT Step 16 Start SBGT.
Places control switches for both trains of SBGT to ON. Verifies heaters red light and Fan On red lights come on for both trains and flow indicators show -3300 scfm.
SATIUNSAT Step 17 Ensure Barometric Cndsr Condensate Pump is operating.
Observes that the pump auto starts as indicated by the red light on for the pump.
SATIUNSAT LOT-SIM-JP-019-14 Page 6 of 10 REV. 0
HPCI Start in Pressure Control Per The Hard Card
- Exhaust Diaphragm Failure.
Step 18 Adjust HPCI as needed to control reactor pressure.
Adjusts HPCI flow by raising flow controller setpoint or by throttling the E41-F008 to establish the most flow through the smallest hole (F008 valve) as possible.
- CRITICAL STEP
- SATIUNSAT NOTE:
This starts the alternate path of the JPM. After the examinee has operated the HPCI controller to lower RPV pressure then insert the malfunction.
SIM OP:
Initiate trigger El when directed by the evaluator.
Step 19 Diagnose indications of a HPCI Exhaust Diaphragm rupture.
Determined the exhaust diaphragm has ruptured from the annunciators.
SATIU NSAT Step 20 Determine HPCI has failed to auto isolate and manually isolate HPCI by closing E41-F002 and F003.
Places control switches for either or both E41.-F002 or E41-F003 to closed. (At least one of these valves has to be closed to meet the critical task)
- CRITICAL STEP
CRS informed HPCI is unavailable for injection.
SATIUNSAT TERMINATING CUE: When HPCI steam leak is isolated by closing the E41-F002 or F003 this JPM is complete.
Comments required for any step evaluated as UNSAT.
Time completed:
LOT-SIM-JP-019-14 Page 7 of 10 REV. 0 HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
Step 18 Adjust HPCI as needed to control reactor pressure.
NOTE:
SIMOP:
Adjusts HPCI flow by raising flow controller setpoint or by throttling the E41-F008 to establish the most flow through the smallest hole (F008 valve) as possible.
Initiate trigger E1 when directed by the evaluator.
Step 19 Diagnose indications of a HPCI Exhaust Diaphragm rupture.
Determined the exhaust diaphragm has ruptured from the annunciators.
SAT/UNSAT Step 20 Determine HPCI has failed to auto isolate and manually isolate HPCI by closing E41-F002 and F003.
Places control switches for either or both E41-F002 or E41-F003 to closed. (At least one of these valves has to be closed to meet the critical task)
CRS informed HPCI is unavailable for injection.
SAT/UNSAT TERMINATING.CUE: When HPCI steam leak is isolated by closing the E41-F0020r F003 this JPMis complete.
Comments required for any step evaluated as UNSAT.
Time completed: ____ _
LOT-SIM-JP-019-14 Page 7 of 10 REV. 0
HPCI Start in Pressure Control Per The Hard Card
- Exhaust Diaphragm Failure.
RELATED TASKS:
206200B401, Place HPCI in Reactor Pressure control from the standby lineup per OP-i 9 KIA REFERENCE AND IMPORTANCE RATING:
295025 EA1.04 3.8/3.9 Ability to operate and/or monitor the following as they apply to High Reactor Pressure:
HPCI (plant specific)
REFERENCES:
20P-19, Section 8.2 Hard Card S/10i9, HPCI Pressure Control In EOPs TOOLS AND EQUIPMENT:
None.
SAFETY FUNCTION (from NUREG 1123, Rev 2.)
3
- Pressure Control (HPCI)
REASON FOR REVISION:
Modified JPM to have exhaust diaphragm failure.
LOT-SIM-JP-019-14 Page 8 of 10 REV. 0 HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
RELATED TASKS:
2062008401, Place HPCI in Reactor Pressure control from the standby lineup per OP-19 KIA REFERENCE AND IMPORTANCE RATING:
295025 EA 1.04 3.8/3.9 Ability to operate and/or monitor the following as they apply to High Reactor Pressure:
HPCI (plant specific)
REFERENCES:
20P-19, Section 8.2 Hard Card S/1019, HPCI Pressure Control In EOPs TOOLS AND EQUIPMENT:
None.
SAFETY FUNCTION (from NUREG 1123, Rev 2.)
3 - Pressure Control (HPCI)
REASON FOR REVISION:
Modified JPM to have exhaust diaphragm failure.
LOT-SIM-JP-019-14 Page 8 of 10 REV. 0
HPCI Start in Pressure Control Per The Hard Card
- Exhaust Diaphragm Failure.
Vailidation Time:
13 Minutes (approximate).
APPLICABLE METHOD OF TESTING Actual X
Unit:
2 SimulatorX( Not applicable to In-Plant JPMs)
No X
Time Limit N/A No JPM:
Pass Fail Remedial Training Required: Yes No Did Trainee Verify Procedure?
Yes No (Each Student should verify one JPM per evaluation set.)
Comments:
Comments reviewed with Student Evaluator Signature:
Date:.
Performance:
Simulate Setting:
Control Room Time Critical:
Yes Alternate Path:
Yes X
Trainee:
EVALUATION LOT-SIM-JP-O1 9-14 Page 9 of 10 REV. 0 HPCI Start in Pressure Control Per The Hard Card - Exhaust Diaphragm Failure.
Vailidation Time: ~
Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room SimulatorL( Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes L No EVALUATION Trainee: ------------------------------
JPM:
Pass Fail Remedial Training Required: Yes No __
Did Trainee Verify Procedure? Yes No __ _
(Each Student should verify one JPM per evaluation set.)
Comments:
Comments reviewed with Student Evaluator Signature:
Date: ______ _
LOT-SIM-JP-019-14 Page 9 of 10 REV. 0
TASK CONDITIONS:
- 1. The reactor has scrammed due to MSIV closure.
2.
RPV water level is stable.
3.
HPCI is not required for RPV level control.
INITIATING CUE:
You are directed by the Unit CRS to start HPCI for pressure control and lower pressure to 800 psig per the Hard Card and inform the Unit CRS when the actions are complete.
TASK CONDITIONS:
- 1. The reactor has scrammed due to MSIV closure.
- 2. RPV water level is stable.
INITIATING CUE:
You are directed by the Unit CRS to start HPCI for pressure control and lower pressure to 800 psig per the Hard Card and inform the Unit CRS when the actions are complete.
ATTACHMENT 8 Page 1 of I HPCI Instructional Aid OP-19 HPCI PRESSURE CONTROL IN EOPs 1.
ENSURE HPCI AUTO INITIATION IS RESET 2.
ENSURE AUXILIARY OIL PUMP IS NOT RUNNING 3.
PLACE HPCI FLOW CONTROL, E41-FIC-R600, IN MANUAL (M),
AND ADJUST OUTPUT DEMAND TO APPROXIMATELY MIDSCALE, USING THE MANUAL LEVER.
4.
ENSURE E41-V8 AND E41-V9 ARE CLOSED 5.
OPEN E41-FO11 6.
OPEN E41-F059 LI 7.
START VACUUM PUMP AND LEAVE IN START 8.
OPEN E41-F001 9.
START AUXILIARY OIL PUMP AND LEAVE IN START 10.
ENSURE E41-V8 AND E41V9 ARE OPEN 11.
WHEN SPEED STOPS INCREASING, THEN ADJUST SPEED TO APPROXIMATELY 2100 RPM 12.
THROTTLE OPEN E41-F008, UNTIL FLOW IS BETWEEN 1000 GPM AND 1500 GPM 13.
ENSURE E41-F012 IS CLOSED WHEN FLOW HAS INCREASED ABOVE 800 GPM 14.
ENSURE E41-F025 AND E41-F026 ARE CLOSED 15.
ADJUST HPCI FLOW CONTROL, E41-FIC-R600, SETPOINT TO MATCH SYSTEM FLOW, AND THEN PLACE E41-FIC-R600 IN AUTO (A) 16.
START SBGT (OP-lO) 17.
ENSURE BAROMETRIC CNDSR CONDENSATE PUMP IS LI OPERATING 18.
ADJUST HPCI AS NEEDED TO CONTROL REACTOR PRESSURE 2/1020 s/big 2OP-19 Rev. 124 Page lO7of 112 ATTACHMENT 8 Page 1 of 1 HPCI Instructional Aid OP-19 HPCI PRESSURE CONTROL IN EOPs
- 1.
ENSURE HPCI AUTO INITIATION IS RESET D
- 2.
ENSURE AUXILIARY OIL PUMP IS NOT RUNNING D
- 3.
PLACE HPCI FLOW CONTROL, E41-FIC-R600, IN MANUAL (M),
D AND ADJUST OUTPUT DEMAND TO APPROXIMATELY MIDSCALE, USING THE MANUAL LEVER.
- 4.
ENSURE E41-V8 AND E41-V9 ARE CLOSED D
- 5.
OPEN E41-F011 D
- 6.
OPEN E41-F059 D
- 7.
START VACUUM PUMP AND LEAVE IN START D
- 8.
OPEN E41-F001 D
- 9.
START AUXILIARY OIL PUMP AND LEAVE IN START D
- 10.
ENSURE E41-V8 AND E41-V9 ARE OPEN D
- 11.
WHEN SPEED STOPS INCREASING, THEN ADJUST SPEED TO D
APPROXIMATELY 2100 RPM
- 12.
THROTTLE OPEN E41-F008, UNTIL FLOW IS BETWEEN 1000 D
GPM AND 1500 GPM
- 13.
ENSURE E41-F012 IS CLOSED WHEN FLOW HAS INCREASED D
ABOVE 800 GPM
- 14.
ENSURE E41-F025 AND E41-F026 ARE CLOSED D
- 15.
ADJUST HPCI FLOW CONTROL, E41-FIC-R600, SETPOINT TO D
MATCH SYSTEM FLOW, AND THEN PLACE E41-FIC-R600 IN AUTO (A)
- 16.
D
- 17.
ENSURE BAROMETRIC CNDSR CONDENSATE PUMP IS D
OPERATING
- 18.
ADJUST HPCI AS NEEDED TO CONTROL REACTOR D
PRESSURE 2/1020 S/1019 120P-19 Rev. 124 Page 107 of 1121
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim E LESSON TITLE:
LESSON NUMBER:
REVISION NO:
Establish a UAT Backfeed.
LOT-S I M-JP-050-B03 02 PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE
,SIMULATOR NRC Sim E LESSON TITLE:
Establish a UAT Backfeed, LESSON NUMBER:
LOT-SIM-JP-050-B03 REVISION NO:
02
Establish a UAT Backfeed.
SIMULATOR SETUP A.
Initial Conditions:
1.
Recommended Initial Conditions Ic 11 RxPwr 100%
Core Age BOC 2.
Required Plant Conditions Mode 3 with SAT deenergized.
B.
Malfunctions EEO2OF, Unit 2 SAT Relay Failure, True C.
Overrides None D.
Remote Function EG_ZMGDIS, UAT Backfeed Logic & No Load Disconnect), Enable EG_86BAC, Main Generator Backup Liockout Relay, RESET F.
Special Instructions
- 1. Activate malfunctions and Remote Functions.
LOT-SIM-JP-050-B03 Page 2 of 13 REV. 1 Establish a UAT Backfeed.
SIMULATOR SETUP A.
Initial Conditions:
- 1.
Recommended Initial Conditions IC 11 Rx Pwr 100%
Core Age BOC
- 2.
Required Plant Conditions Mode 3 with SAT deenergized.
B.
Malfunctions EE020F, Unit 2 SAT Relay Failure, True C.
Overrides None D.
Remote Function EG_ZMGDIS, UAT Backfeed Logic & No Load Disconnect), Enable EG_86BAC, Main Generator Backup Liockout Relay, RESET E.
Special Instructions
- 1. Activate malfunctions and Remote Functions.
LOT-SIM-JP-050-B03 Page 2 of 13 REV. 1
Establish a UAT Backfeed.
SAFETY CONSIDERATIONS:
None.
EVALUATOR NOTES: (Do not read to trainee)
- 1. The applicable procedure section WILL be provided to the trainee.
2.
If this is the first JPM of the JPM set, read the JPM briefing contained NUREG 1021, Appendix E, or similar to the trainee.
- 3. A copy of 20P-50, Section 8.13, signed off through step 17 should be provided to the examinee.
Read the following to trainee.
TASK CONDITIONS:
- 1. The Unit 2 Startup Auxiliary Transformer has tripped and locked out, requiring a manual reactor scram and resulting in a Loss of Off-Site Power.
2.
Both 230 KV Bus 2A and Bus 2B are energized.
3.
Diesel Generators 3 and 4 are tied to 4KV Buses E3 and E4.
4.
Unit 2 is in process of establishing a UAT backfeed per AOP-36.1 and 20P-50 to re energize BOP Buses.
- 5. 20P-50, Section 8.13, has been completed through step 17.
INITIATING CUE:
You are directed by the Unit SCO to complete the steps for UAT backfeed from 230 Ky Bus 2B and inform the Unit SCO when 4160V Buses 2B, 2C and 2D are energized.
LOT-SIM-JP-050-B03 Page 3 of 13 REV. I Establish a UAT Backfeed.
SAFETY CONSIDERATIONS:
None.
EVALUATOR NOTES: (Do not read to trainee)
- 1. The applicable procedure section WILL be provided to the trainee.
- 2. If this is the first JPM of the JPM set, read the JPM briefing contained NUREG 1021, Appendix E, or similar to the trainee.
- 3. A copy of 20P-50, Section 8.13, signed off through step 17 should be provided to the examinee.
Read the following to trainee.
TASK CONDITIONS:
- 1. The Unit 2 Startup Auxiliary Transformer has tripped and locked out, requiring a manual reactor scram and resulting in a Loss of Off-Site Power.
- 2. Both 230 KV Bus 2A and Bus 2B are energized.
- 3. Diesel Generators 3 and 4 are tied to 4KV Buses E3 and E4.
- 4. Unit 2 is in process of establishing a UAT backfeed per AOP-36.1 and 20P-50 to re-energize BOP Buses.
- 5. 20P-50, Section 8.13, has been completed through step 17.
INITIATING CUE:
You are directed by the Unit SCO to complete the steps for UAT backfeed from 230 KV Bus 2B and inform the Unit SCO when 4160V Buses 2B, 2C and 20 are energized.
LOT -SIM-JP-050-B03 Page 3 of 13 REV. 1
Establish a UAT Backfeed.
PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
TIME START NOTE: The order for closing the Generator PCBs is at the discretion of the performer and in not critical for this JPM.
NOTE: Either step 3 or step 8 is critical. At least one generator PCB must be closed.
Step 1
- Place the Synchroscope for Generator PCB 29A(B) to the ON position.
Synchroscope switch placed to ON for PCB 29A(B).
- CRITICAL STEP **
SATIUNSAT Step 2 Confirm running voltage (230 KV Bus Voltage) is approx. 120 volts.
Running voltage verified to be approx. 120 volts.
SAT/UNSAT Step 3
- Close generator PCB 29A(B).
Generator PCB 29A(B) switch placed to CLOSE.
- CRITICAL STEP**
SATIUNSAT Step 4Confirm incoming voltage increases to approximately 120 volts.
Incoming voltage verified at approximately 120 volts.
SATIUNSAT Step 5
- Place Synchroscope switch for PCB 29A(B) to OFF.
Synchroscope for 29A(B) is placed to OFF.
SATIUNSAT LOT-SIM-JP-050-B03 Page 4 of 13 REV. 1 Establish a UA T Backfeed.
PERFORMANCE CHECKLIST I NOTE: Sequence is assumed unless denoted in the Comments.
TIME START ___
NOTE: The order for closing the Generator PCBs is at the discretion of the performer and in not critical for this JPM.
NOTE: Either step 30r step 8 is critical. At least one generator PCB must be closed.
Step 1 - Place the Synchroscope for Generator PCB 29A(B) to the ON position.
Synchroscope switch placed to ON for PCB 29A(B}.
- CRITICAL STEP ** SATIUNSAT Step 2 - Confirm running voltage (230 KV Bus Voltage) is approx. 120 volts.
Running voltage verified to be approx. 120 volts.
SAT/UNSAT Step 3 - Close generator PCB 29A(B).
Generator PCB 29A(B} switch placed to CLOSE.
- CRITICAL STEP** SATIUNSAT Step 4 - Confirm incoming voltage increases to approximately 120 volts.
Incoming voltage verified at approximately 120 volts.
SATIUNSAT Step 5 - Place Synchroscope switch for PCB 29A(B) to OFF.
Synchroscope for 29A(B} is placed to OFF.
SATIUNSAT LOT -SIM-JP-050-B03 Page 4 of 13 REV. 1
Establish a UAT Backfeed.
Step 6
- Place the Synchroscope for Generator PCB 29B(A) to the ON position.
Synchroscope switch placed to ON for PCB 298(A).
- CRITICAL STEP **
SATIUNSAT Step 7 Confirm running voltage (230 KV Bus Voltage) is approx. 120 volts.
Running voltage verified to be approx. 120 volts.
SAT/U NSAT Step 8
- Close generator PCB 29B(A).
Generator PCB 298(A) switch placed to CLOSE.
- CRITICAL STE P**
SAT/UNSAT Step 9
- Place Synchroscope switch for PCB 29B(A) to OFF.
Synchroscope for 298(A) is placed to OFF.
SATIU NSAT NOTE: The steps for the remaining PCB, 22 thru 26, are N/A. The sequence of energizing the BOP Buses is not critical. The generator lockouts are reset due to being an initial condition of the procedure.
PROMPT:
If requested, as Unit SCO direct examinee to NA steps for remaining PCB.
If requested the generator lockout relays are reset.
Step 10 If 4 KV Bus 2C or 2D is de-energized, then place the CW ISOL VALVES MODE SELECTOR switch to position A, to defeat the auto start of the Circulating Water Pumps Places the CWISOL VALVES MODE SELECTOR switch to position A.
- CRITICAL STEP**
SAT/UNSAT NOTE:
To energize 2C Bus go to page 6.
To energize 2D Bus go to page 8.
To energize 2B Bus go to page 10.
LOT-SIM-JP-050-B03 Page 5 of 13 REV. 1 Establish a UAT Backfeed.
Step 6 - Place the Synchroscope for Generator PCB 29B(A) to the ON position.
Synchroscope switch placed to ON for PCB 29B(A}.
- CRITICAL STEP ** SA T/UNSAT Step 7 - Confirm running voltage (230 KV Bus Voltage) is approx. 120 volts.
Running voltage verified to be approx. 120 volts.
SAT/UNSAT Step 8 - Close generator PCB 29B(A).
Generator PCB 29B(A} switch placed to CLOSE.
- CRITICAL STEP** SAT/UNSAT Step 9 - Place Synchroscope switch for PCB 29B(A) to OFF.
Synchroscope for 29B(A} is placed to OFF.
SAT/UNSAT NOTE: The steps for the remaining PCB, 22 thru 26, are N/A. The sequence of energizing the BOP Buses is not critical. The generator lockouts are reset due to being an initial condition of the prdcedure.
PROMPT:
If requested, as Unit SCO direct examinee to NA steps for remaining PCB. If requested the generator lockout relays are reset.
Step 10 - If 4 KV Bus 2C or 20 is de-energized, then place the CW ISOL VALVES MODE SELECTOR switch to position A, to defeat the auto start of the Circulating Water Pumps Places the CW ISOL VALVES MODE SELECTOR switch to position A.
NOTE:
To energize 2C Bus go to page 6.
To energize 2DBus go to page 8.
To energize 2B Bus go to page 10.
LOT-SIM-JP-050-B03 Page 5 of 13
- CRITICAL STEP** SAT/UNSAT REV. 1
Establish a UAT Backfeed.
To Energize 2C Bus:
Step 11 If 4 KV Bus 2C is de-energized then ensure mode control switches for the following pumps are in MAN:
a.
Condensate Booster Pump 2C Condensate Booster Pump 2C Mode Switch placed in in MAN.
- CRITICAL STEP**
SATIUNSAT b.
Condensate Booster Pump 2A Condensate Booster Pump 28 is already in MAN.
SAT/UNSAT c.
Condensate Pump 2B Condensate Pump 2B is already in MAN.
SAT/UNSAT Step 12
- Place Synchroscope for UAT to Bus 2C to ON.
Synchroscope for UA T to Bus 2C breaker placed to ON.
- CRITICAL STEP**
SATIUNSAT INOTE: The synchroscope will not be at the 12 Oclock position since Bus 2C is de-energized. I Step 13
- Close the UAT to Bus 2C breaker, AC4.
UA T to Bus 2C breaker is closed.
- CRITICAL STEP**
SATIUNSAT Step 14 Confirm UAT to Bus 2C breaker, AC4, is closed.
UA T to Bus 2C breaker verified closed.
SATIUNSAT LOT-SIM-JP-050-B03 Page 6 of 13 REV. I Establish a UAT Backfeed.
To Energize 2C Bus:
Step 11 - If 4 KV Bus 2C is de-energized then ensure mode control switches for the following pumps are in MAN:
- a.
Condensate Booster Pump 2C Condensate Booster Pump 2C Mode Switch placed in in MAN.
- CRITICAL STEP** SAT/UNSAT
- b.
Condensate Booster Pump 2A Condensate Booster Pump 2B is already in MAN.
SAT/UNSAT
- c.
Condensate Pump 2B Condensate Pump 2B is already in MAN.
SAT/UNSAT Step 12 - Place Synchroscope for UAT to Bus 2C to ON.
Synchroscope for UA T to Bus 2C breaker placed to ON.
- CRITICAL STEP** SAT/UNSAT I NOTE: The synchroscope will not be at the 12 O'clock position since Bus 2C is de-energized. I Step 13 - Close the UAT to Bus 2C breaker, AC4.
UA T to Bus 2C breaker is closed.
- CRITICAL STEP** SATIUNSAT Step 14 - Confirm UAT to Bus 2C breaker, AC4, is closed.
UA T to Bus 2C breaker verified closed.
SAT/UNSAT LOT-SIM-JP-050-B03 Page 6 of 13 REV. 1
Establish a UAT Backfeed.
Step 15 Confirm SAT to 2C breaker, AC6, is open.
SAT to 2C breaker verified open.
SATIU NSAT Step 16
- Place Synchroscope switch for UAT to 2C breaker to OFF.
Synchroscope switch for UA T to 2C breaker is placed to OFF.
SATIU NSAT NOTE: Performer should determine that step 30 is N/A.
PROMPT:
There is no need to energize all three busses.
After 2C Bus is energized inform examinee that Another operator will take over from here.
ITERMINATING CUE: BOP Bus 2C has been energized from the UAT.
I TIME COMPLETED NOTE: Comments required for any step evaluated as UNSAT LOT-SIM-JP-050-B03 Page 7 of 13 REV. 1 Establish a UAT Backfeed.
Step 15 - Confirm SAT to 2C breaker, AC6, is open.
SA T to 2C breaker verified open.
SAT/UNSAT Step 16 - Place Synchroscope switch for UAT to 2C breaker to OFF.
Synchroscope switch for UA T to 2C breaker is placed to OFF.
SAT/UNSAT I NOTE: Performer should determine that step 30 is N/A.
PROMPT:
There is no need to energize all three busses. After 2C Bus is energized inform examinee that "Another operator will take over from here".
I TERMINATING CUE: BOP Bus 2C has been energized from the UA T.
TIME COMPLETED ___
NOTE: Comments required for any step evaluated as UNSAT LOT-SIM-JP-050-B03 Page 7 of 13 REV. 1
Establish a UAT Backfeed.
To energize 20 Bus:
Step 17 If 4 KV Bus 2D is de-energized then ensure mode control switches for the following pumps are in MAN:
a.
Condensate Pump 2C Condensate Pump 2C Mode Switch is placed in MAN.
- CRITJCAL STEP**
SATIUNSAT b.
Condensate Pump 2A Condensate Pump 2A is already in MAN.
SATIU NSAT c.
Condensate Booster Pump 2B Condensate Booster Pump 2B is already in MAN.
SATIUNSAT Step 18
- Place Synchroscope for UAT to Bus 2D to ON.
Synchroscope for UA T to Bus 2D breaker placed to ON.
- CRITICAL STEP**
SATIUNSAT NOTE The synchroscope will not be at the 12 Oclock position since Bus 2D is de-energized I
Step 19
- Close the UAT to Bus 2D breaker, AD6.
UA T to Bus 2D breaker is closed.
- CRITICAL STEP**
SATIUNSAT Step 20 Confirm UAT to Bus 2D breaker, AD6, is closed.
UA T to Bus 2D breaker verified closed.
SATIU NSAT LOT-SlM-JP-050-B03 Page 8 of 13 REV. I Establish a UAT Backfeed.
To energize 2D Bus:
Step 17 - If 4 KV Bus 20 is de-energized then ensure mode control switches for the following pumps are in MAN:
- a.
Condensate Pump 2C Condensate Pump 2C Mode Switch is placed in MAN.
- CRITICAL STEP** SAT/UNSAT
- b.
Condensate Pump 2A Condensate Pump 2A is already in MAN.
SAT/UNSAT
- c.
Condensate Booster Pump 2B Condensate Booster Pump 2B is already in MAN.
SAT/UNSAT Step 18 - Place Synchroscope for UAT to Bus 20 to ON.
Synchroscope for UA T to Bus 20 breaker placed to ON.
- CRITICAL STEP** SAT/UNSAT I NOTE: The synchroscope will not be at the 12 O'clock position since Bus 20 is de-energized. I Step 19 - Close the UAT to Bus 20 breaker, A06.
UA T to Bus 20 breaker is closed.
- CRITICAL STEP** SAT/UNSAT Step 20 - Confirm UAT to Bus 20 breaker, A06, is closed.
UA T to Bus 20 breaker verified closed.
SAT/UNSAT LOT-SIM-JP-050-B03 Page 8 of 13 REV. 1
Establish a UAT Backfeed.
Step 21 Confirm the SAT to Bus 2D breaker, AD4, is open.
SAT to Bus 2D breaker is verified open.
SATIU NSAT Step 22
- Place Synchroscope switch for UAT to 2D breaker to OFF.
Synchroscope switch for UA T to 2D breaker is placed to OFF.
SATIUNSAT NOTE: Performer should determine that Step 32 is N/A.
PROMPT:
There is no need to energize all three busses.
After 2D Bus is energized inform examinee that Another operator will take over from here.
I TERMINATING CUE: BOP Bus 2D has been energized from the UAT.
I TIME COMPLETED NOTE: Comments required for any step evaluated as UNSAT LOT-SIM-JP-050-B03 Page 9 of 13 REV. 1 Establish a UAT Backfeed.
Step 21 - Confirm the SAT to Bus 20 breaker, A04, is open.
SA T to Bus 20 breaker is verified open.
SAT/UNSAT Step 22 - Place Synchroscope switch for UAT to 20 breaker to OFF.
Synchroscope switch for UA T to 20 breaker is placed to OFF.
SAT/UNSAT I NOTE: Performer should determine that Step 32 is N/A.
PROMPT:
There is no need to energize all three busses. After 20 Bus is energized inform examinee that "Another operator will take over from here".
I TERMINATING CUE: BOP Bus 20 has been energized from the UAT.
TIME COMPLETED ___
NOTE: Comments required for any step evaluated as UNSAT LOT-SIM-JP-050-B03 Page 9 of 13 REV. 1
Establish a UAT Backfeed.
To energize 2B Bus:
Step 23
- Place Synchroscope for UAT to Bus 2B to ON.
Synchroscope for UA T to Bus 2B breaker placed to ON.
- CRITICAL STEP**
SATIUNSAT NOTE: The synchroscope will not be at the 12 Oclock position since Bus 2B is de-energized. I Step 24
- Close the UAT to Bus 2B breaker, ABO.
UA T to Bus 28 breaker is closed.
- CRITICAL STEP**
SATIUNSAT Step 25 Confirm UAT to Bus 2B breaker, ABO, is closed.
UA T to Bus 2B breaker verified to be closed.
SATIU NSAT Step 26
- Confirm SAT to Bus 2B breaker, AB2, is open.
SAT to Bus 2B breaker verified to be open.
SATIU NSAT Step 27
- Place Synchroscope switch for UAT to 2B breaker to OFF.
Synchroscope switch for UA T to 28 breaker is placed to OFF.
SATIU NSAT Step 28
- Confirm Isophase Bus Ground Fault UAT Backfeed Mode, UA-13 3-6, is clear UA-13 3-6 verified to be clear.
SAT!UNSAT PROMPT:
There is no need to energize all three busses.
After 2B Bus is energized inform examinee that Another operator will take over from here.
ITERMINATING CUE: BOP Bus 2B has been energized from the UAT.
I TIME COMPLETED NOTE: Comments required for any step evaluated as UNSAT LOT-SIM-JP-050-B03 Page 10 of 13 REV. 1 Establish a UAT Backfeed.
To energize 2B Bus:
Step 23 - Place Synchroscope for UAT to Bus 2B to ON.
Synchroscope for UA T to Bus 2B breaker placed to ON.
- CRITICAL STEP** SATIUNSAT I NOTE: The synchroscope will not be at the 12 O'clock position since Bus 2B is de-energized.
Step 24 - Close the UAT to Bus 2B breaker, ABO.
UA T to Bus 2B breaker is closed.
- CRITICAL STEP** SAT/UNSAT Step 25 - Confirm UAT to Bus 2B breaker, ABO, is closed.
UA T to Bus 2B breaker verified to be closed.
SAT/UNSAT Step 26 - Confirm SAT to Bus 2B breaker, AB2, is open.
SAT to Bus 2B breaker verified to be open.
SAT/UNSAT Step 27 - Place Synchroscope switch for UAT to 2B breaker to OFF.
Synchroscope switch for UA T to 2B breaker is placed to OFF.
SAT/UNSAT Step 28 - Confirm Isophase Bus Ground Fault UAT Backfeed Mode, UA-13 3-6, is clear UA-13 3-6 verified to be clear.
SATIUNSAT PROMPT:
There is no need to energize all three busses. After 2B Bus is energized inform examinee that "Another operator will take over from here".
I TERMINATING CUE: BOP Bus 2B has been energized from the UAT.
TIME COMPLETED ___ _
NOTE: Comments required for any step evaluated as UNSAT LOT -SIM-JP-050-B03 Page 10 of 13 REV. 1
Establish a UAT Backfeed.
RELATED TASKS:
245601 Bi 01, Place the Auxiliary Transformer in Backfeed Operation per OP-50.
K/A REFERENCE AND IMPORTANCE RATING:
226001 A2.03 3.9/4.3 Use procedures to mitigate consequences of loss of off-site power.
REFERENCES:
AOP-36.1 2OP-50 Rev. 79 TOOLS AND EQUIPMENT:
None.
SAFETY FUNCTION (from NUREG 1123, Rev 2.):
6
- Electrical (AC Electrical Distribution)
REASON FOR REVISION:
Included steps for resetting generator lockout with remote functions. Periodic review to ensure current procedure is reflected.
LOT-SIM-JP-050-B03 Page 11 of 13 REV. 1 Establish a UAT Backfeed.
RELATED TASKS:
245601 B1 01, Place the Auxiliary Transformer in Backfeed Operation per OP-50.
KIA REFERENCE AND IMPORTANCE RATING:
226001 A2.03 3.9/4.3 Use procedures to mitigate consequences of loss of off-site power.
REFERENCES:
AOP-36.1 20P-50 Rev. 79 TOOLS AND EQUIPMENT:
None.
SAFETY FUNCTION (from NUREG 1123, Rev 2.):
6 - Electrical (AC Electrical Distribution)
REASON FOR REVISION:
Included steps for resetting generator lockout with remote functions. Periodic review to ensure current procedure is reflected.
LOT-SIM-JP-050-B03 Page 11 of 13 REV. 1
Establish a UAT Backfeed.
Validation Time: 18 Minutes (approximate).
Time Taken:
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual Unit:
2 Setting:
Control Room Simulator Time Critical:
Yes
No Time Limit N/A Alternate Path:
Yes
No EVALUATION Trainee:_______________________________________________
JPM:
Pass Fail Remedial Training Required: Yes No Comments:
Comments reviewed with Student Evaluator Signature:
Date:
LOT-SIM-JP-050-B03 Page 12 of 13 REV. 1 Establish a UAT Backfeed.
Validation Time:~ Minutes (approximate).
Time Taken: ----
APPLICABLE METHOD OF TESTING Performance:
Simulate Setting:
Control Room Unit:
2 Time Critical:
Yes Actual
'01 Simulator '01 No
'01 No
'01 Time Limit N/A Alternate Path:
Yes EVALUATION Trainee: __________________ _
JPM:
Pass --
Fail __
Remedial Training Required: Yes No __
Comments:
Comments reviewed with Student Evaluator Signature:
LOT -S I M-J P-050-B03 Page 12 of 13 Oate: ____ _
REV. 1
TASK CONDITIONS:
- 1. The Unit 2 Startup Auxiliary Transformer has tripped and locked out, requiring a manual reactor scram and resulting in a Loss of Off-Site Power.
2.
Both 230 KV Bus 2A and Bus 2B are energized.
3.
Diesel Generators 3 and 4 are tied to 4KV Buses E3 and E4.
4.
Unit 2 is in process of establishing a UAT backfeed per AOP-36.1 and 20P-50 to re energize BOP Buses.
- 5. 2OP-50, Section 8.13, has been completed through step 17.
INITIATING CUE:
You are directed by the Unit SCO to complete the steps for UAT backfeed from 230 KV Bus 2B and inform the Unit SCO when 4160V Buses 2B, 2C and 2D are energized.
TASK CONDITIONS:
- 1. The Unit 2 Startup Auxiliary Transformer has tripped and locked out, requiring a manual reactor scram and resulting in a Loss of Off-Site Power.
- 2. Both 230 KV Bus 2A and Bus 2B are energized.
- 3. Diesel Generators 3 and 4 are tied to 4KV Buses E3 and E4.
- 4. Unit 2 is in process of establishing a UAT backfeed per AOP-36.1 and 20P-50 to re-energize BOP Buses.
- 5. 20P-50, Section 8.13, has been completed through step 17.
INITIATING CUE:
You are directed by the Unit SCO to complete the steps for UAT backfeed from 230 KV Bus 2B and inform the Unit SCO when 4160V Buses 2B, 2C and 20 are energized.
R49 8.13 Unit Auxiliary Transformer Backfeed C
R50 Continuous 8.13.1 Initial Conditions Date/Time Started Today Use 1.
All applicable prerequisites as listed in Section 4.0 are RC met.
2.
The switchyard is energized in accordance with RC Section 5.1.
3.
Generator Primary, Backup and Differential Lockout RC relays are reset.
4.
Plant is in Mode 3, 4, or 5.
RC 5.
Unit CRSs permission granted to implement this RC procedure; refer to Tech Specifications 3.8.1, 3.8.2, 3.8.7, and 3.8.8.
8.13.2 Procedural Steps NOTE:
UAT Backfeed keys will be required for performance of this section. UAT Backfeed keys are located in the Main Control Room keylocker (keys 43 and
- 44) and the WCC key locker (TEM3O &3095). Only ONE set of keys is required to perform UAT Backfeed field operations. One CO key will be required to unlock the No-Load Disconnect Switch. One set of keys must remain in the control room for UAT Backfeed activities.
1.
ENSURE generator side disconnect for Generator RC/RT PCB 29A is locked closed.
Ind.Ver.
2.
ENSURE generator side disconnect for Generator RCi RT PCB 29B is locked closed.
Jnd.Ver.
3.
ENSURE bus side disconnect for Generator PCB 29A RCRT is locked closed.
Ind.Ver.
4.
ENSURE bus side disconnect for Generator PCB 29B RC/ RT is locked closed.
Ind.Ver.
20P-50 Rev. 114 Page 100 of 206 IR491 R50 8.13 Unit Auxiliary Transformer Backfeed 8.13.1
- 1.
- 2.
- 3.
- 4.
- 5.
8.13.2 Initial Conditions DatelTime Started Today All applicable prerequisites as listed in Section 4.0 are met.
The switchyard is energized in accordance with Section 5.1.
Generator Primary, Backup and Differential Lockout relays are reset.
Plant is in Mode 3, 4, or 5.
Unit CRS's permission granted to implement this procedure; refer to Tech Specifications 3.8.1, 3.8.2, 3.8.7, and 3.8.8.
Procedural Steps RC RC RC RC RC NOTE:
UAT Backfeed keys will be required for performance of this section. UAT Backfeed keys are located in the Main Control Room keylocker (keys 43 and
- 44) and the WCC key locker (TEM30 &3095). Only ONE set of keys is required to perform UAT Backfeed field operations. One CO key will be required to unlock the No-Load Disconnect Switch. One set of keys must remain in the control room for UAT Backfeed activities.
- 1.
- 2.
- 3.
- 4.
\\20P-50 ENSURE generator side disconnect for Generator PCB 29A is locked closed.
ENSURE generator side disconnect for Generator PCB 29B is locked closed.
ENSURE bus side disconnect for Generator PCB 29A is locked closed.
ENSURE bus side disconnect for Generator PCB 29B is locked closed.
RCjRT Ind.ver.
RCjRT Ind.ver.
RCjRT Ind.ver.
RCjRT Ind.ver.
Rev. 114 Page 100 of 2061 C
Continuous Use
8.13.2 Procedural Steps NOTE:
The following step:
a.
Disables EDG auto starts from SAT undervoltage and allows the Diesel Generators to be shut down if the SAT is de-energized, b.
Disables trip of 4 KV Bus 2C Breaker AC8 and trip of 4 KV Bus E4 Breaker AJ9 if a LOCA signal is initiated concurrent with a loss of the
- SAT, c.
Disables synchronization check between SAT and UAT 4 KV breakers.
5.
IF SAT is de-energized OR it will be de-energized by RCiRT means other than Section 7.4 after UAT backfeed is Ind.Ver.
established, THEN PLACE 2C-AC5-SS-43BF switch, at 4 KV Switchgear 2C Compt. AC5, in BACKFEED.
NOTE:
The following step:
a.
Disables EDG auto starts from SAT undervoltage and allows the Diesel Generators to be shut down if the SAT is de-energized, b.
Disables trip of 4 KV Bus 2D Breaker AD1 and trip of 4 KV Bus E3 Breaker A12 if a LOCA signal is initiated concurrent with loss of the SAT.
6.
IF SAT is de-energized OR it will be de-energized by RCRT means other than Section 7.4 after UAT backfeed is Ind.Ver.
established, THEN PLACE 2D-AD5-SS-43BF switch, at 4 KV Switchgear 2D Compt. AD5, in BACKFEED.
20P-50 Rev. 114 Page 101 of 206 8.13.2 Procedural Steps NOTE:
The following step:
- a.
Disables EDG auto starts from SAT undervoltage and allows the Diesel Generators to be sh ut down if the SAT is de-energ ized,
- b.
Disables trip of 4 KV Bus 2C Breaker AC8 and trip of 4 KV Bus E4 Breaker AJ9 if a LOCA signal is initiated concurrent with a loss of the
- SAT,
- c.
Disables synchronization check between SAT and UAT 4 KV breakers.
- 5.
IF SAT is de-energized OR it will be de-energized by means other than Section 7.4 after UAT backfeed is established, THEN PLACE 2C-AC5-SS-43BF switch, at 4 KV Switchgear 2C Compt. AC5, in BACKFEEO.
RC/RT IndVer.
NOTE:
The following step:
- a.
Disables EDG auto starts from SAT undervoltage and allows the Diesel Generators to be shut down if the SAT is de-energized,
- b.
Disables trip of 4 KV Bus 20 Breaker AD1 and trip of 4 KV Bus E3 Breaker AI2 if a LOCA signal is initiated concurrent with loss of the SAT.
- 6.
IF SAT is de-energized OR it will be de-energized by RC I RT means other than Section 7.4 after UAT backfeed is IndVer.
established, THEN PLACE 20-A05-SS-43BF switch, at 4 KV Switchgear 20 Compt. AD5, in BACKFEEO.
Rev. 114 Page 101 of 2061
8.13.2 Procedural Steps 1R451 NOTE:
The two silver padlock pins, located under the operator gearbox, are required to be in the UP DETENT position to prevent damaging the padlock pins when opening the No-Load Disconnect Switch.
NOTE:
To prevent over-travel past stops, the stops under the operator gearbox should be observed while operating the No-Load Disconnect Switch.
7.
PERFORM the following on the 38 elevation of the Turbine Building:
a.
ENSURE both silver padlock pins (located under RC 1 RT the operator gearbox) are in the UP DETENT Ind.Ver.
position.
b.
OPEN NO-LOAD DISCONNECT SWITCH, RC 1 RT 2-ISO-GEN-MPT-DISC-SW.
ind.Ver.
c.
CONFIRM correct position of NO-LOAD RC 1
RT DISCONNECT SWITCH, Ind.Ver.
2-ISO-GEN-MPT-DISC-SW, main contacts.
d.
LOCK NO-LOAD DISCONNECT SWITCH, RC RT 2-ISO-GEN-MPT-DISC-SW, in OPEN.
Ind.Ver.
NOTE:
The following step provides permissives to close PCBs 29A and 29B AND allows auto start of the Main Transformer Cooling Fans with the Generator Field Breaker open.
8.
PLACE switch GEN-SS-43BF, at Generator Excitation RC1 RT Cabinet on the 70 elevation of the Turbine Building, in Ind.Ver.
BA CKFEED.
NOTE:
The following step prevents tripping PCBs 29A and 29B with turbine valves closed, activates ground fault alarm relay (59BF) for isophase bus when in backfeed position, and allows operation of the turbine turning gear motor with the generator output breakers closed.
9.
PLACE switch ISOPH-SS-43BF, on Generator and RC RT UAT Relay Panel XU-8 (HJ6), in BACKFEED.
Ind.Ver.
20P-50 Rev. 114 Page 102 of 206 8.13.2 Procedural Steps NOTE:
The two silver padlock pins, located under the operator gearbox, are required to be in the UP DETENT position to prevent damaging the padlock pins when opening the No-Load Disconnect Switch.
NOTE:
To prevent over-travel past stops, the stops under the operator gearbox should be observed while operating the No-Load Disconnect Switch.
- 7.
PERFORM the following on the 38' elevation of the Turbine Building:
- a.
ENSURE both silver padlock pins (located under RC/RT the operator gearbox) are in the UP DETENT Ind.ver.
position.
- b.
OPEN NO-LOAD DISCONNECT SWITCH, RC/RT 2-ISO-GEN-MPT-DISC-SW.
Ind.ver.
- c.
CONFIRM correct position of NO-LOAD RC/RT DISCONNECT SWITCH, Ind.Ver.
2-ISO-GEN-MPT-DISC-SW, main contacts.
- d.
LOCK NO-LOAD DISCONNECT SWITCH, RC/RT 2-ISO-GEN-MPT-DISC-SW, in OPEN.
Ind.ver.
NOTE:
The following step provides permissives to close PCBs 29A and 29B AND allows auto start of the Main Transformer Cooling Fans with the Generator Field Breaker open.
- 8.
PLACE switch GEN-SS-43BF, at Generator Excitation Cabinet on the 70' elevation of the Turbine Building, in BACKFEED.
RC/RT Ind.ver.
NOTE:
The following step prevents tripping PCBs 29A and 29B with turbine valves closed, activates ground fault alarm relay (59BF) for isophase bus when in backfeed position, and allows operation of the turbine turning gear motor with the generator output breakers closed.
- 9.
PLACE switch ISOPH-SS-43BF, on Generator and RC / RT UAT Relay Panel XU-8 (HJ6), in BACKFEED.
Ind.ver.
/20P-50 Rev. 114 Page 102 of 2061
8.13.2 Procedural Steps CAUTION The 120 VAC knife switches operated in the following step are de-energized whenever the UAT is de-energized. As a good safety practice, caution should be used to avoid inadvertent contact with switch contacts and SAF-NGGC-21 75 identifies PPE requirements. Switch contacts will be energized when the UAT is energized from off-site power.
10.
PERFORM the following to prevent SEL-300G Digital Relay 21G-2/78 from sealing-in annunciator DGTL RELAY TRIP/TROUBLE ALARM, UA-13 4-1 during backfeed restoration:
a.
REMOVE the cover from 21G-2/78 TEST RT DEVICE #1, 2-GEN-21G-2/78-TD-1, located at the top of Panel XU-8.
b.
FULLY OPEN all knife switches within the test RT block.
c.
REATTACH the cover to test block.
RT NOTE:
The following 2 steps eliminate the possibility of tripping the Reverse Power Relay (32-2) while in BACKFEED. Tripping the Reverse Power Relay initiates a primary generator lockout which starts all four EDGs and trips the generator breakers, 29A and 29B. Relay plugs on protection relays are removed by removing cover on relay and pulling relay plugs completely out.
11.
REMOVE the bottom relay plug (Generator Reverse RC I RT Power Device AH 32-2) on Generator Protection Ind.Ver.
relays at Generator and Main Transformer Relay Panel XU-8 12.
REMOVE the top relay plug (Generator Reverse RC 1 RT Power Device AH 32-2) on Generator Protection Ind.Ver.
relays at Generator and Main Transformer Relay Panel XU-8 20P-50 Rev. 114 Page 103 of 206 8.13.2 Procedural Steps CAUTION The 120 VAC knife switches operated in the following step are de-energized whenever the UAT is de-energized. As a good safety practice, caution should be used to avoid inadvertent contact with switch contacts and SAF-NGGC-2175 identifies PPE requirements. Switch contacts will be energized when the UAT is energized from off-site power.
NOTE:
- 10.
PERFORM the following to prevent SEL-300G Digital Relay 21 G-2/78 from sealing-in annunciator DGTL RELAY TRIPITROUBLE ALARM, UA-13 4-1 during backfeed restoration:
- a.
REMOVE the cover from 21 G-2/78 TEST DEVICE #1, 2-GEN-21 G-2/78-TD-1, located at the top of Panel XU-8.
- b.
FULLY OPEN all knife switches within the test block.
- c.
REATTACH the cover to test block.
RT RT RT The following 2 steps eliminate the possibility of tripping the Reverse Power Relay (32-2) while in BACKFEED. Tripping the Reverse Power Relay initiates a primary generator lockout which starts all four EDGs and trips the generator breakers, 29A and 29B. Relay plugs on protection relays are removed by removing cover on relay and pulling relay plugs completely out.
- 11.
REMOVE the bottom relay plug (Generator Reverse RC / RT Power Device AH 32-2) on Generator Protection IndVer.
relays at Generator and Main Transformer Relay Panel XU-8
- 12.
REMOVE the top relay plug (Generator Reverse RC / RT Power Device AH 32-2) on Generator Protection IndVer.
relays at Generator and Main Transformer Relay Panel XU-8 120P-50 Rev. 114 Page 103 of 2061
8.13.2 Procedural Steps NOTE:
The following step prevents the automatic selection of 1800 rpm main turbine speed if the main turbine is reset while in UAT BACKFEED mode. Auto selection of 1800 rpm opens the stop valves initiating a Group I isolation.
13.
PLACE UATBACKFEED switch EHC-SS-43BF, on RC 1
RT EHC Panel P644 Bay A rear panel door, in Ind.Ver.
BACKFEED.
14.
CONFIRM Generator PCB trip signals (2-UA-13 2-7 RC and 2-UA-13 2-8) are clear.
15.
NOTIFY the Dispatcher of impending circuit breaker RC operations.
16.
IF both Transformer Bus PCBs (26A and 26B) are RC closed, THEN OPEN either PCB 26A OR PCB 26B.
17.
CONFIRM selected PCB has opened by observing the RC indicating light.
NOTE:
The first generator PCB selected to be closed should be from the 230 KV Bus that is NOT feeding the Startup Auxiliary Transformer. The other PCB will be closed later.
CAUTION All synchronizing switches on the RTGB should be in OFF prior to placing any synchroscope keylock switch in ON.
18.
PLACE synchroscope switch in ON for the selected Generator PCB.
19.
CONFIRM running voltage is approximately 120 volts (230 KV Bus Voltage).
20P-50 Rev. 114 Page 104 of 206 8.13.2 Procedural Steps NOTE:
The following step prevents the automatic selection of 1800 rpm main turbine speed if the main turbine is reset while in UAT BACKFEED mode. Auto selection of 1800 rpm opens the stop valves initiating a Group 1 isolation.
- 13.
PLACE UA T BACKFEED switch EHC-SS-43BF, on RC/RT EHC Panel P644 Bay A rear panel door, in Ind.ver.
BACKFEED.
- 14.
CONFIRM Generator PCB trip signals (2-UA-13 2-7 RC and 2-UA-13 2-8) are clear.
- 15.
NOTIFY the Dispatcher of impending circuit breaker RC operations.
- 16.
IF both Transformer Bus PCBs (26A and 26B) are RC closed, THEN OPEN either PCB 26A OR PCB 26B.
- 17.
CONFIRM selected PCB has opened by observing the RC indicating light.
NOTE:
The first generator PCB selected to be closed should be from the 230 KV Bus that is NOT feeding the Startup Auxiliary Transformer. The other PCB will be closed later.
CAUTION All synchronizing switches on the RTGB should be in OFF prior to placing any synchroscope keylock switch in ON.
- 18.
PLACE synchroscope switch in ON for the selected Generator PCB.
- 19.
CONFIRM running voltage is approximately 120 volts (230 KV Bus Voltage).
Rev. 114 Page 104 of 2061
8.13.2 Procedural Steps NOTE:
The synchroscope will NOT be in the 12 oclock position AND there will be no incoming voltage.
20.
CLOSE the selected Generator PCB.
Ind.Ver.
21.
CONFIRM incoming voltage increases to approximately 120 volts.
22.
PLACE synchroscope switch to OFF.
23.
PLACE synchroscope switch to ON for the remaining Generator PCB.
24.
CONFIRM synchroscope is at the 12 oclock position.
25.
CONFIRM running and incoming voltages are approximately 120 Volts.
26.
CLOSE the remaining Generator PCB.
I nd.Ver.
27.
PLACE synchroscope switch to OFF.
28.
IF 4 KV Bus 2C or 2D is de-energized, THEN PLACE the CWISOL VALVES MODE SELECTOR switch to position A, to defeat the auto start of the Circulating Water Pumps.
NOTE:
UAT to 2C, 2D and 2B feeder breakers will NOT close if Generator Primary Backup and Differential Lockout Relays are tripped.
29.
PERFORM the following steps to reenergize or transfer power to 4 KV Bus 2C:
a.
IF 4 KV Bus 2C is de-energized, THEN ENSURE mode control switches for the following pumps are in MAN:
Condensate Booster Pump 2C.
Condensate Booster Pump 2A.
Condensate Pump 2B.
20P-50 Rev. 114 Page 105 of 206 8.13.2 Procedural Steps NOTE:
The synchroscope will NOT be in the "12 o'clock" position AND there will be no incoming voltage.
- 20.
CLOSE the selected Generator PCB.
t Ind.ver.
- 21.
CONFIRM incoming voltage increases to approximately 120 volts.
- 22.
PLACE synchroscope switch to OFF.
- 23.
PLACE synchroscope switch to ON for the remaining Generator PCB.
- 24.
CONFIRM synchroscope is at the "12 o'clock" position.
- 25.
CONFIRM running and incoming voltages are approximately 120 Volts.
- 26.
CLOSE the remaining Generator PCB.
t Ind.ver.
- 27.
PLACE synchroscope switch to OFF.
- 28.
IF 4 KV Bus 2C or 20 is de-energized, THEN PLACE the CW ISOL VALVES MODE SELECTOR switch to position A, to defeat the auto start of the Circulating Water Pumps.
NOTE:
UAT to 2C, 20 and 2B feeder breakers will NOT close if Generator Primary, Backup and Differential Lockout Relays are tripped.
J 120P-50
- 29.
PERFORM the following steps to reenergize or transfer power to 4 KV Bus 2C:
- a.
IF 4 KV Bus 2C is de-energized, THEN ENSURE mode control switches for the following pumps are in MAN:
Condensate Booster Pump 2C.
Condensate Booster Pump 2A.
Condensate Pump 2B.
Rev. 114 Page 105 of 2061
8.13.2 Procedural Steps b.
PLACE UAT TO BUS 2C SYNCHRONIZING SWITCH to ON.
NOTE:
IF 4 KV Bus 2C is de-energized, the synchroscope will NOT be in the 12 oclock position.
c.
CONFIRM synchroscope is in the 12 oclock position AND CLOSE UAT TO BUS 2C BREAKER, AC4.
d.
CONFIRM UAT TO BUS 2C BREAKER, AC4, I
has closed.
Ind.Ver.
e.
CONFIRM SAT TO BUS 2C BREAKER, AC6, is
/
open.
Ind.Ver.
f.
PLACE UA T TO BUS 2C SYNCHRONIZING SWITCH to OFF.
30.
IF 4 KV Bus E4 is deenergized AND is to be reenergized from 4 KV Bus 20, THEN PERFORM the following:
NOTE:
WHEN reenergizing the E-bus from its normal power supply (BOP-Bus), the Diesel Generator must be in the AUTO Mode to close the master/slave breakers.
a.
ENSURE Diesel Generator 4 is in AUTO mode on Panel XU-2.
b.
PLACE BUS 2C TO BUS E4 SYNCHRONIZING SWITCH to ON.
c.
PLACE AND HOLD breaker control switch for BUS 2C TO BUS E4 in CLOSED until both Master (2-AC8) AND Slave (AJ9) breakers indicate closed.
d.
CONFIRM Master breaker (2-AC8) has closed.
I Ind.Ver.
e.
CONFIRM Slave breaker (AJ9) has closed.
/
I nd.Ver.
f.
PLACE BUS 2C TO BUS E4 SYNCHRONIZING SWITCH to OFF.
20P-50 Rev. 114 Page 106 of 206 8.13.2 Procedural Steps
- b.
PLACE UA T TO BUS 2C SYNCHRONIZING SWITCH to ON.
NOTE:
IF 4 KV Bus 2C is de-energized, the synchroscope will NOT be in the "12 o'clock" position.
- c.
CONFIRM synchroscope is in the "12 o'clock" position AND CLOSE UA T TO BUS 2C BREAKER, AC4.
- d.
CONFIRM UA T TO BUS 2C BREAKER, AC4, has closed.
- e.
CONFIRM SAT TO BUS 2C BREAKER, AC6, is open.
- f.
PLACE UA T TO BUS 2C SYNCHRONIZING SWITCH to OFF.
- 30.
IF 4 KV Bus E4 is deenergized AND is to be reenergized from 4 KV Bus 2C, THEN PERFORM the following:
/
Ind.ver.
/
Ind.ver.
NOTE:
WHEN reenergizing the E-bus from its normal power supply (BOP-Bus), the Diesel Generator must be in the AUTO Mode to close the master/slave breakers.
- a.
ENSURE Diesel Generator 4 is in AUTO mode on Panel XU-2.
- b.
PLACE BUS 2C TO BUS E4 SYNCHRONIZING SWITCH to ON.
- c.
PLACE AND HOLD breaker control switch for BUS 2C TO BUS E4 in CLOSED until both Master (2-AC8) AND Slave (AJ9) breakers indicate closed.
- d.
CONFIRM Master breaker (2-AC8) has closed.
- e.
CONFIRM Slave breaker (AJ9) has closed.
- f.
PLACE BUS 2C TO BUS E4 SYNCHRONIZING SWITCH to OFF.
Rev. 114
/
Ind.ver.
/
Ind.ver.
Page 106 of 2061
8.13.2 Procedural Steps 31.
PERFORM the following steps to reenergize or transfer power for 4 KV Bus 2D:
a.
IF 4 KV Bus 2D is de-energized, THEN ENSURE mode control switches for the following pumps are in MAN:
Condensate Pump 2C.
Condensate Pump 2A.
Condensate Booster Pump 2B.
b.
PLACE UAT TO BUS 2D SYNCHRONIZING SWITCH to ON.
NOTE:
IF 4 KV Bus 2D is deenergized, the synchroscope will NOT be in the 12 oclock position.
c.
CONFIRM synchroscope is at the 12 oclock position AND CLOSE UAT TO BUS 2D BREAKER, AD6.
d.
CONFIRM UAT TO BUS 2D BREAKER, AD6,
/
has closed.
Ind.Ver.
e.
CONFIRM SAT TO BUS 2D BREAKER, AD4, is I
open.
Ind.Ver.
f.
PLACE UAT TO BUS 2D SYNCHRONIZING SWITCH to OFF.
32.
IF 4 KV Bus E3 is de-energized AND is to be reenergized from 4 KV Bus 2D, THEN PERFORM the following:
NOTE:
WHEN reenergizing the E-bus from its normal power supply (BOP-Bus), the Diesel Generator must be in the AUTO Mode to close the master/slave breakers.
a.
ENSURE Diesel Generator 3 is in AUTO mode on Panel XU-2.
20P-50 Rev. 114 Page 107 of 206 8.13.2 Procedural Steps
- 31.
PERFORM the following steps to reenergize or transfer power for 4 KV Bus 2D:
- a.
IF 4 KV Bus 2D is de-energized, THEN ENSURE mode control switches for the following pumps are in MAN:
Condensate Pump 2C.
Condensate Pump 2A.
Condensate Booster Pump 2B.
- b.
PLACE UA T TO BUS 20 SYNCHRONIZING SWITCH to ON.
NOTE:
IF 4 KV Bus 2D is deenergized, the synchroscope will NOT be in the "12 o'clock" position.
- c.
CONFIRM synchroscope is at the "12 o'clock" position AND CLOSE UA T TO BUS 20 BREAKER, A06.
- d.
CONFIRM UAT TO BUS 20 BREAKER, A06, has closed.
- e.
CONFIRM SA T TO BUS 20 BREAKER, A04, is open.
- f.
PLACE UA T TO BUS 20 SYNCHRONIZING SWITCH to OFF.
- 32.
IF 4 KV Bus E3 is de-energized AND is to be reenergized from 4 KV Bus 2D, THEN PERFORM the following:
/
Ind.Ver.
/
Ind.ver.
NOTE:
WHEN reenergizing the E-bus from its normal power supply (BOP-Bus), the Diesel Generator must be in the AUTO Mode to close the master/slave breakers.
- a.
ENSURE Diesel Generator 3 is in AUTO mode on Panel XU-2.
Rev. 114 Page 107 of 2061
813.2 Procedural Steps b.
PLACE BUS 2D TO BUS E3 SYNCHRONIZING SWITCH to ON.
c.
PLACE AND HOLD breaker control switch for BUS 2D TO BUS E3 in CLOSED until both Master (2-AD 1) AND Slave (AI2) breakers indicate closed.
d.
CONFIRM Master breaker (2-AD 1) has closed.
I nd.Ver.
e.
CONFIRM Slave breaker (AI2) has closed.
Ind.Ver.
f.
PLACE BUS 2D TO BUS E3 SYNCHRONIZING to OFF.
33.
PERFORM the following steps to reenergize or transfer power for 4 KV Bus 2B:
a.
PLACE UAT TO BUS 2B SYNCHROSCOPE SWITCH to ON.
NOTE:
IF 4 KV Bus 2B is de-energized, the synchroscope will NOT be at the 12 oclock position.
b.
CONFIRM synchroscope is at the 12 oclock position AND CLOSE UAT TO BUS 2B BREAKER, ABO.
c.
CONFIRM UAT TO BUS 2B BREAKER, ABO, has closed.
d.
CONFIRM SAT TO BUS 2B BREAKER, AB2, is open.
e.
PLACE UAT TO BUS 2B SYNCHROSCOPE SWITCH to OFF.
34.
CONFIRM ISOPHASE BUS GROUND FAULT UAT BACKFEED MODE, (UA-1 3 3-6), is clear.
35.
IF the SAT is to be de-energized, THEN DEENERGIZE in accordance with Section 7.4.
20P-50 Rev. 114 Page 108 of 206 8.13.2 Procedural Steps
- b.
PLACE BUS 20 TO BUS E3 SYNCHRONIZING SWITCH to ON.
- c.
PLACE AND HOLD breaker control switch for BUS 20 TO BUS E3 in CLOSED until both Master (2-AD1) AND Slave (AI2) breakers indicate closed.
- d.
CONFIRM Master breaker (2-AD1) has closed.
- e.
CONFIRM Slave breaker (AI2) has closed.
- f.
PLACE BUS 20 TO BUS E3 SYNCHRONIZING to OFF.
- 33.
PERFORM the following steps to reenergize or transfer power for 4 KV Bus 2B:
- a.
PLACE UAT TO BUS 2B SYNCHROSCOPE SWITCH to ON.
/
Ind.ver.
/
Ind.Ver.
NOTE:
IF 4 KV Bus 2B is de-energized, the synchroscope will NOT be at the "12 o'clock" position.
- b.
CONFIRM synchroscope is at the "12 o'clock" position AND CLOSE UA T TO BUS 2B BREAKER, ABO.
- c.
CONFIRM UA T TO BUS 2B BREAKER, ABO, has closed.
- d.
CONFIRM SAT TO BUS 2B BREAKER, AB2, is open.
- e.
PLACE UA T TO BUS 2B SYNCHROSCOPE SWITCH to OFF.
- 34.
CONFIRM ISOPHASE BUS GROUND FAUL T UA T BACKFEED MODE, (UA-13 3-6), is clear.
- 35.
IF the SAT is to be de-energized, THEN DEENERGIZE in accordance with Section 7.4.
Rev. 114 Page 108 of 2061
8.13.2 Procedural Steps 36.
IF the SAT is to remain energized, THEN CLOSE the PCB (either 26A OR 26B) that was opened in Step 8.13.2.16 as follows.
a.
PLACE TRANSFORMER BUS 230 KV PCB 26A/26B SYNCHRONIZING SWITCH to ON.
b.
WHEN synchroscope indicates that bus 2A OR 2B are synchronized, THEN CLOSE PCB 26A 0R26B.
c.
CONFIRM 230 KV breaker has closed by observing the indicating light.
d.
PLACE TRANSFORMER BUS 230KV PCB 26A/26B SYNCHRONIZING SWITCH in OFF.
37.
REFER to OOP-50.1 for transfer of emergency power supply from Diesel Generator to Normal Feeder.
38.
NOTIFY Generator Isolated Phase Bus System Engineer that UAT Backfeed is in service on Unit 2.
Date/Time Completed Performed By (Print)
Initials Reviewed By:
Unit CRS/SRO 20P-50 Rev. 114 Page 109 of 206 8.13.2
- 36.
- 37.
- 38.
1 20 P-50 Procedural Steps IF the SAT is to remain energized, THEN CLOSE the PCB (either 26A OR 26B) that was opened in Step 8.13.2.16 as follows.
- a.
PLACE TRANSFORMER BUS 230 KV PCB 26A126B SYNCHRONIZING SWITCH to ON.
- b.
WHEN synchroscope indicates that bus 2A OR 2B are synchronized, THEN CLOSE PCB 26A OR 26B.
- c.
CONFIRM 230 KV breaker has closed by observing the indicating light.
- d.
PLACE TRANSFORMER BUS 230KV PCB 26A126B SYNCHRONIZING SWITCH in OFF.
REFER to OOP-50.1 for transfer of emergency power supply from Diesel Generator to Normal Feeder.
NOTIFY Generator Isolated Phase Bus System Engineer that UAT Backfeed is in service on Unit 2.
DatelTime Completed Performed By (Print)
Reviewed By: ___________ _
Unit CRS/SRO Initials Rev. 114 Page 109 of 2061
PROGRESS ENERGY - CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE CONTROL ROOM NRC Sim F LESSON TITLE:
Main Turbine Shutdown With PCB Failure LESSON NUMBER:
LOT-SIM-JP-26.O-O1 REVISION NO:
00 I
\\R; PROGRESS ENERGY - CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE CONTROL ROOM NRC Sim F LESSON TITLE:
Main Turbine Shutdown With PCB Failure LESSON NUMBER:
LOT-SIM-JP-26.0-01 REVISION NO:
00
Main Turbine Shutdown SIMULATOR SETUP:
A.
Initial Conditions:
1.
Recommended Initial Conditions IC 15 Rx. Pwr.
15%
Core Age EOC 2.
Required Plant Conditions None B.
Overrides Tag ID Description Position/
Actual Override Rmptime Actime Dactime Trig Target Value Value Q3101UR8 BUS 2A GEN 2 230 KV BKR ON ON/OFF ON ON RED Q31O1DG8 BUS 2A GEN 2 230 KV BKR OFF ON/OFF ON OFF GREEN Q8182LG8 230 KV Bkr ON Red (XU-5 Panel)
ON/OFF ON ON Q81 82RR8 230 KV Bkr ON Green (XU-.5 ON/OFF ON OFF Panel)
D.
Remote Function None E.
Special Instructions El PCB 29A CS not in Normal will delete Q31O1UR8 (trc:1,dod:q3lOlur8)
E2 PCB 29A CS in TRIP will delete Q31O1DG8 (trc:2,dod:q3lOldg8).
E3 PCB 29A CS not in Normal will delete Q8182LG8 (trc:3 1
dod: Q8182LG8)
E4 PCB 29A CS in TRIP will delete Q8182RR8 (trc:4,dod: Q8182RR8).
LOT-SIM-JP-26.O-O1 Page 2 of 10 Rev. 00 Main Turbine Shutdown SIMULATOR SETUP:
A.
Initial Conditions:
- 1.
Recommended Initial Conditions IC 15 Rx. Pwr.
15%
Core Age EOC
- 2.
Required Plant Conditions None B.
Overrides Tag ID Description Position/
Actual Override Rmptime Actime Dactime Trig Target Value Value Q3101UR8 BUS 2A GEN 2 230 KV BKR ON ON/OFF ON ON RED Q3101DG8 BUS 2A GEN 2 230 KV BKR OFF ON/OFF ON OFF GREEN Q8182LG8 230 KV Bkr ON Red (XU-5 Panel)
ON/OFF ON ON Q8182RR8 230 KV Bkr ON Green (XU-5 ON/OFF ON OFF Panel)
O.
Remote Function None E.
Special Instructions E1 PCB 29A CS not in Normal will delete 03101URS (trc:1,dod:q3101urS)
E2 PCB 29A CS in TRIP will delete 031010GS (trc:2,dod:q3101dgS).
E3 PCB 29A CS not in Normal will delete OS1S2LGS (trc:3,dod: OS1S2LGS)
E4 PCB 29A CS in TRIP will delete OS1S2RRS (trc:4,dod: OS1S2RRS).
LOT-SIM-JP-26.0-01 Page 2 of 10 Rev. 00
Main Turbine Shutdown SAFETY CONSIDERATIONS:
None EVALUATOR NOTES: (Do not read to examinee)
- 1. The applicable procedure section WILL be provided to the examinee, once it is demonstrated he/she knows the correct procedure.
2.
If this is the first JPM of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the examinee.
Read the following to examinee.
TASK CONDITIONS:
1.
Auxiliary power has been transferred to the SAT.
2.
Load Dispatcher has been notified of impending grid separation.
3.
OGP-05, Unit Shutdown is in progress.
4.
Turbine load has been reduced to between 100 to 110 MWe.
5.
Second stage reheat has been removed from service.
6.
20P-26 Section 7.1 has been completed through step 7.1.2.2.
INITIATING CUE:
You are directed to shutdown Main Turbine in accordance with 20P-26 and inform the Unit SCO when the actions are complete.
LOT-SIM-JP-26.0-01 Page 3 of 10 Rev. 00 Main Turbine Shutdown SAFETY CONSIDERATIONS:
None EVALUATOR NOTES: (Do not read to examinee)
- 1. The applicable procedure section WILL be provided to the examinee, once it is demonstrated he/she knows the correct procedure.
- 2. If this is the first JPM of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the examinee.
Read the following to examinee.
TASK CONDITIONS:
- 1.
Auxiliary power has been transferred to the SAT.
- 2.
Load Dispatcher has been notified of impending grid separation.
- 3.
OGP-05, Unit Shutdown is in progress.
- 4.
Turbine load has been reduced to between 100 to 110 MWe.
- 5.
Second stage reheat has been removed from service.
- 6.
20P-26 Section 7.1 has been completed through step 7.1.2.2.
INITIATING CUE:
You are directed to shutdown Main Turbine in accordance with 20P-26 and inform the Unit seo when the actions are complete.
LOT-SIM-JP-26.0-01 Page 3 of 10 Rev. 00
Main Turbine Shutdown PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 Obtain/provide a copy of 20P-26, Section 7.1.
Procedure obtained.
Time Started:
Step 2
- Open the foIIowinc drain valves located on Panel XU-3 Drain valve control switches are placed in open.
SAT/UNSAT SAT/U NSAT LOT-SIM-JP-26.O-O1 NOTE:
Turbine load can be verified / monitored on PPC, ERFIS, Control Panel XU-O1 (GEN-MW-727), or XU-04 (GEN-WMR-760)
NOTE:
Steps 2-4 may be performed in any order prior to tripping the main turbine.
NOTE:
The MN STM LEAD AFTER CV-3 DRN, MVD-DV3, operates with the limit switch position of the CV-1/CV-2 drain valves and the position can be confirmed with the indicating light on Panel XU-3.
Valve Position SAT UNSAT MN STM LN BEFORE SV DRNS, MS-V46/47/48/49 Open MAIN SV & CV ABOVE SEAT DRN, MVD-CV Open MN STM LEAD AFTER CV-1 DRN, MVD-CV2 Open MN STM LEAD AFTER CV-2 DRN, MVD-CV4 Open Page4oflO Rev. 00 Main Turbine Shutdown PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 -Obtain/provide a copy of 20P-26, Section 7.1.
NOTE:
NOTE:
NOTE:
Procedure obtained.
SATIUNSAT Time Started: ____ _
Turbine load can be verified / monitored on PPC, ERFIS, Control Panel XU-01 (GEN-MW-727), or XU-04 (GEN-WMR-760)
Steps 2-:4 may be performed in any order prior to tripping the main turbine.
The MN STM LEAD AFTER CV-3 DRN, MVD-DV3, operates with the limit switch position of the CV-1/CV-2 drain valves and the position can be confirmed with the indicating light on Panel XU-3.
Step 2 - 0 'pen th f II d.
t d P
I XU 3 e 0 oWing rain va ves oca e on ane Valve Position SAT UNSAT MN STM LN BEFORE SV DRNS, MS-V46/47/48/49 Open MAIN SV & CV ABOVE SEAT DRN, MVD-CV Open MN STM LEAD AFTER CV-1 DRN, MVD-CV2 Open MN STM LEAD AFTER CV-2 DRN, MVD-CV4 Open Drain valve control switches are placed in open.
SATIUNSAT LOT-SIM-JP-26.0-01 Page 4 of 10 Rev. 00
Main Turbine Shutdown Step 3
- Perform the following to align the Turbine Lube Oil System:
PROMPT:
Inform examinee that the Turbine Building AC has rotated the Cuno filters T handles.
- a. Rotate the five Cuno filters T-handles clockwise two complete revolutions to clean the lift pumps Cuno filters.
TB AO communicates Cuno filters rotated.
SATIU NSAT NOTE:
Alarm UA-02 (2-3) MOTOR SUCTION PUMP RUNNING will annunciate when the MSP is started, examinee may review the alarm prior to starting the MSP
- b. Start the motor suction pump.
Motor suction pump start switch pushbutton is depressed.
SAT!U NSAT NOTE:
Alarm UA-02 (4-2) TURNING GEAR OIL PUMP RUNNING will annunciate when the TGOP is started, examinee may review the alarm prior to starting the TGOP.
- c. Start the turning gear oil pump and ensure the lift pumps start by observing all six amber PRESS NORM lights come on.
Turning gear oil pump Start Switch pushbutton is depressed and all Six lift pump Press Norm lights are verified on.
SATIU NSAT Step 4
- Perform the following to test the operation of LOW CONDENSER VACUUM SWITCHES, OG-PS-11O and OG-PS-111, the pressure set control, and the bypass valves:
- a. Depress Bypass Valve Opening Jack INCREASE push button to open a bypass valve 12% to 18%.
Turbine Bypass Valve opened 12% to 18%.
SATIUNSAT LOT-SI M-JP-26.0-01 Page 5 of 10 Rev. 00 Main Turbine Shutdown Step 3 - Perform the following to align the Turbine Lube Oil System:
PROMPT: Inform examinee that the Turbine Building AO has rotated the Cuno filters T-handles.
NOTE:
NOTE:
- a. Rotate the five Cuno filter's T-handles clockwise two complete revolutions to clean the lift pumps' Cuno filters.
TB A 0 communicates Cuno filters rotated.
SATIUNSAT Alarm UA-02 (2-3) MOTOR SUCT,ION PUMP RUNNING will annunciate when the MSP is started, examinee may review the alarm prior to starting the MSP.
- b. Start the motor suction pump.
Motor suction pump start switch pushbutton is depressed.
SAT/UNSAT Alarm UA-02 (4-2)TURNING GEAR OIL PUMP RUNNING will annunciate when the TGOP is started, examinee may review the alarm prior to starting the TGOP.
- c. Start the turning gear oil pump and ensure the lift pumps start by observing all six amber PRESS NORM lights come on.
Turning gear oil pump Start Switch pushbutton is depressed and all Six lift pump Press Norm lights are verified on.
SATIUNSAT Step 4 - Perform the following to test the operation of LOW CONDENSER VACUUM SWITCHES, OG-PS-110 and OG-PS-111, the pressure set control, and the bypass valves:
- a. Depress Bypass Valve Opening Jack INCREASE push button to open a bypass valve 12% to 18%.
Turbine Bypass Valve opened 12% to 18%.
SATIUNSAT LOT-SIM-JP-26.0-01 Page 5 of 10 Rev. 00
Main Turbine Shutdown
- b. Depress Bypass Valve Opening Jack DECREASE push button to fully close the bypass valve.
Turbine Bypass Valve closed.
SATIUNSAT Step 5
- Monitor main generator megawatts using computer point B059 or Net Unit Megawatts 2-GEN-WMR-760.
Monitors main generator megawatts chart recorder on the XU-4 Panel or establishes monitoring of the computer point on PPC.
SATIU NSAT NOTE:
This starts the alternate path portion to diagnose failure of PCB 29A.
NOTE:
Steps 6 and 7 should be reviewed prior to performing step 6. This happens in a very short time period.
Step 6
- Depress the Emergency Trip System push button Emergency Trip System push button depressed.
And ensure the following:
Valve positions verified.
- CRITICAL STEP ** SATIUNSAT SATIU NSAT Valve Position SAT UNSAT All four main stop valves Closed All four control valves Closed Bypass valves maintain reactor pressure constant at Throttled 928 psig All four intercept valves Closed LOT-SI M-JP-26.0-01 Page 6 of 10 Rev. 00 Main Turbine Shutdown
- b. Depress Bypass Valve Opening Jack DECREASE push button to fully close the bypass valve.
Turbine Bypass Valve closed.
SAT/UNSAT Step 5 - Monitor main generator megawatts using computer point B059 or Net Unit Megawatts 2-GEN-WMR-760.
NOTE:
NOTE:
Monitors main generator megawatts chart recorder on the XU-4 Panel or establishes monitoring of the computer point on PPC.
SATIUNSAT This starts the alternate path portion to diagnose failure of PCB29A.
Steps 6 and 7 should be reviewed prior to performing step 6. This happens in a very short time* period.
Step 6 - Depress the Emergency Trip System push button Emergency Trip System push button depressed.
- CRITICAL STEP ** SATIUNSAT A d th f II n ensure e 0 oWing:
Valve Position SAT UNSAT All four main stop valves Closed All four control valves Closed Bypass valves maintain reactor pressure constant at Throttled 928 psig All four intercept valves Closed Valve positions verified.
SATIUNSAT LOT-SIM-JP-26.0-01 Page 6 of 10 Rev. 00
Main Turbine Shutdown NOTE:
Examinee may determine the PCB 29A failed to open and decide to implement
[
20P-50.0, Section 8.31 (Emergency Isolation of 230KV Bus 2A).
Step 7
- When main generator MWe decrease to zero, then ensure both generator output breakers GENERATOR 2 TO BUS 2A 230 KV PCB 29A and GENERATOR 2 TO BUS 2B 230 KV PCB 29B, are open.
Recognizes PCB 29A failed to open and takes control switch to trip.
- CRITICAL STEP ** SAT/UNSAT NOTE:
Acknowledge PCB 29A failure and direct examinee another operator will continue with Main Turbine shutdown.
Step 8 Notifies SRO PCB 29A failed to automatically open and was manually opened.
SRO notified of PCB 29A failure.
SATIU NSAT TERMINATING CUE: When both main generator output breakers (PCB 29A & 29B) are open, this JPM is complete.
Comments required for any step evaluated as UNSAT.
Time completed:
LOT-SIM-JP-26.0-01 Page 7 of 10 Rev. 00 NOTE:
Main Turbine Shutdown Examinee may determine the PCB 29A failed to.open and decide to implement 20P-50.0, Section 8.31 (Emergency Isolation of 230KV Bus 2A).
Step 7 - When main generator MWe decrease to zero, then ensure both generator output breakers GENERA TOR 2 TO BUS 2A 230 KV PCB 29A and GENERA TOR 2 TO BUS 2B 230 KV PCB 29B, are open.
Recognizes PCB 29A failed to open and takes control switch to trip.
- CRITICAL STEP ** SAT/UNSAT NOTE:
Acknowledge PCB 29A failure and direct examinee another operator will continue with Main Turbine shutdown.
Step 8 - Notifies SRO PCB 29A failed to automatically open and was manually opened.
SRO notified of PCB 29A failure.
SAT/UNSAT TERMINATING CUE: When both main generator output breakers (PCB29A & 29B) are open, this JPM is complete.
Comments required for any step evaluated as UNSAT.
Time completed: ____ _
LOT-SIM-JP-26.0-01 Page 7 of 10 Rev. 00
Main Turbine Shutdown RELATED TASKS:
245012B101, Shutdown the Main Turbine per 20P-26 KIA REFERENCE AND IMPORTANCE RATING:
245000 A2.01 3.7/3.9 Ability to (a) predict the impacts of the following on the MAIN TURBINE GENERATOR AND AUXILIARY SYSTEMS ; and (b) based on those predictions, use procedures to correct, control, or mitigate the consequences of those abnormal conditions or operations: Turbine trip
REFERENCES:
GP-05 OP-26 TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2) 4, Heat Removal REASON FOR REVISION:
New LOT-SIM-JP-26.0-01 Page 8 of 10 Rev. 00 Main Turbine Shutdown RELATED TASKS:
245012B101, Shutdown the Main Turbine per 20P-26 KIA REFERENCE AND IMPORTANCE RATING:
245000 A2.01 3.7/3.9 Ability to (a) predict the impacts of the following on the MAIN TURBINE GENERATOR AND AUXILIARY SYSTEMS; and (b) based on those predictions, use procedures to correct, control, or mitigate the consequences of those abnormal conditions or operations: Turbine trip
REFERENCES:
GP-05 OP-26 TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2) 4, Heat Removal REASON FOR REVISION:
New LOT-SIM-JP-26.0-01 Page 8 of 10 Rev. 00
Main Turbine Shutdown Validation Time:
12 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room Simulator X (Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes X
No
EVALUATION Examinee:_______________________________________________
JPM:
Pass Fail Remedial Training Required: Yes No Did Examinee Verify Procedure?
Yes No (Each Student should verify one JPM per evaluation set)
Comments:
Comments reviewed with Student Evaluator Signature:
Date:_______________
LOT-SIM-JP-26.O-O1 Page 9 of 10 Rev. 00 Main Turbine Shutdown Validation Time: 12 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room Simulator X (Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes X
No EVALUATION Examinee: ____________________ _
JPM:
Pass __
Fail __
Remedial Training Required: Yes No __
Did Examinee Verify Procedure? Yes No __ _
(Each Student should verify one JPM per evaluation set)
Comments:
Comments reviewed with Student Evaluator Signature:
Date: -------
LOT-SIM-JP-26.0-01 Page 9 of 10 Rev. 00
TASK CONDITIONS:
- 1. Auxiliary power has been transferred to the SAT.
2.
Load Dispatcher has been notified of impending grid separation.
3.
OGP-05, Unit Shutdown, is complete up to Step 5.2.3.
- 4. Turbine load has been reduced to between 100 to 110 MWe.
- 5. Second stage reheat has been removed from service.
- 6. 20P-26 Section 7.1 has been completed through step 7.1.2.2.
INITIATING CUE:
You are directed to shutdown Main Turbine in accordance with 2OP26 and inform the Unit SCO when the actions are complete.
TASK CONDITIONS:
- 1. Auxiliary power has been transferred to the SAT.
- 2. Load Dispatcher has been notified of impending grid separation.
- 3. OGP-05, Unit Shutdown, is complete up to Step 5.2.3.
- 4. Turbine load has been reduced to between 100 to 110 MWe.
- 5. Second stage reheat has been removed from service.
- 6. 20P-26 Section 7.1 has been completed through step 7.1.2.2.
INITIATING CUE:
You are directed to shutdown Main Turbine in accordance with 20P-26 and inform the Unit seo when the actions are complete.
7.0 SHUTDOWN C
Continuous Use 7.1 Normal Shutdown 7.1.1 Initial Conditions 1.
Turbine load has been reduced in accordance with OGP-05 to between 100 and 110 MWe.
2.
Second stage reheat has been removed from service in accordance with 20P-36.
7.1.2 Procedural Steps NOTE:
Steps 7.1.2.1 through 7.1.2.5 may be performed in any order as long as they are completed prior to tripping the turbine.
CAUTION Operation at less than 33% turbine load AND less than 25 Hg Vacuum (greater than 5 HGA backpressure) can cause damage to the last stage buckets and should be avoided.
1.
PLACE TURBINE SUPERVISORY INSTRUMENTS Trip/Disable switch to ON.
2.
CONFIRM TURBCVFASTCLOS/SV/RPT TRIP BYPASS (A-05, 6-7) is in alarm.
NOTE:
The MN STM LEAD AFTER CV-3 DRN, MVD-DV3, operates with the limit switch position of the CV-1/CV-2 drain valves and the position can be confirmed with the indicating light on Panel XU-3.
3.
OPEN the following drain valves located on Panel XU-3:
a.
MNSTMLNBEFORESVDRNS, MS-V46/4 7/48/49 b.
MAINSV&CVABOVESEATDRN,MVD-CV 2OP-26 Rev. 116 Page 52 of 159 7.0 SHUTDOWN 7.1 Normal Shutdown 7.1.1 Initial Conditions
- 1.
- 2.
Turbine load has been reduced in accordance with OGP-05 to between 100 and 110 MWe.
Second stage reheat has been removed from service in accordance with 20P-36.
7.1.2 Procedural Steps NOTE:
Steps 7.1.2.1 through 7.1.2.5 may be performed in any order as long as they are completed prior to tripping the turbine.
CAUTION Operation at less than 33% turbine load AND less than 25" Hg Vacuum (greater than 5" HGA backpressure) can cause damage to the last stage buckets and should be avoided.
- 1.
- 2.
PLACE TURBINE SUPERVISORY INSTRUMENTS Trip/Disable switch to ON.
CONFIRM TURB CV FAST CLOS/SV/RPT TRIP BYPASS (A-05, 6-7) is in alarm.
NOTE:
The MN STM LEAD AFTER CV-3 DRN, MVO-DV3, operates with the limit switch position of the CV-1/CV-2 drain valves and the position can be confirmed with the indicating light on Panel XU-3.
- 3.
OPEN the following drain valves located on Panel XU-3:
- a.
MS-V46/47/48/49
- b.
MAIN SV & CV ABOVE SEAT ORN, MVO-CV D
1 20 P-26 Rev. 116 Page 52 of 1591 C
Continuous Use
7.1.2 Procedural Steps c.
MN STM LEAD AFTER CV-1 DRN, MVD-CV2 d.
MNSTMLEADAFTERCV-2DRN, MVD-CV4 4.
PERFORM the following to align the Turbine Lube Oil System:
a.
ROTATE the five Cuno filters T-handles clockwise two complete revolutions to clean the lift pumps Cuno filters.
b.
START the motor suction pump.
c.
START the turning gear oil pump AND ENSURE the lift pumps start by observing all six amber PRESS NORM lights come on.
CAUTION IF the bypass valve does NOT open, THEN tripping the main turbine may result in a main turbine trip without bypass valves with resultant high reactor pressure and APRM upscale alarms or trips.
5.
PERFORM the following to test the operation of LOW CONDENSER VACUUM SWITCHES, OG-PS-1 10 and OG-PS-111, the pressure set control, and the bypass valves:
a.
DEPRESS Bypass Valve Opening Jack INCREASE push button to open a bypass valve 12% to 18%.
b.
DEPRESS Bypass Valve Opening Jack DECREASE push button to fully close the bypass valve.
6.
MONITOR main generator megawatts using computer point U2GENBO59 OR Net Unit Megawatts 2-GEN-WMR-760.
2OP-26 Rev. 116 Page 53 of 159 7.1.2 Procedural Steps
- c.
- d.
MN STM LEAD AFTER CV-1 DRN, MVD-CV2 MN STM LEAD AFTER CV-2 DRN, MVD-CV4
- 4.
PERFORM the following to align the Turbine Lube Oil System:
- a.
- b.
- c.
ROTATE the five Cuno filter's T-handles clockwise two complete revolutions to clean the lift pumps' Cuno filters.
START the motor suction pump.
START the turning gear oil pump AND ENSURE the lift pumps start by observing all six amber PRESS NORM lights come on.
CAUTION D
D D
D D
IF the bypass valve does NOT open, THEN tripping the main turbine may result in a main turbine trip without bypass valves with resultant high reactor pressure and APRM upscale alarms or trips.
- 5.
PERFORM the following to test the operation of LOW CONDENSER VACUUM SWITCHES, OG-PS-110 and OG-PS-111, the pressure set control, and the bypass valves:
- a.
- b.
DEPRESS Bypass Valve Opening Jack INCREASE push button to open a bypass valve 12% to 18%.
DEPRESS Bypass Valve Opening Jack DECREASE push button to fully close the bypass valve.
D D
- 6.
MONITOR main generator megawatts using computer D
point U2GENB059 OR Net Unit Megawatts 2-GEN-WMR-760.
Rev. 116 Page 53 of 1591
7.1.2 Procedural Steps 7.
DEPRESS the Emergency Trip System push button AND ENSURE the following:
a.
All four main stop valves go full closed.
b.
All four control valves go full closed.
c.
The bypass valves throttle open to maintain reactor pressure constant at 928 psig.
d.
All four intercept valves go closed.
8.
WHEN main generator MWe decrease to zero, THEN ENSURE both generator output breakers GENERATOR 2 TO BUS 2A 230 KVPCB 29A AND GENERATOR 2 TO BUS 2B 230 KVPCB 29B, are open.
9.
PLACE REGULATOR MODE SELECTOR, 43 CS, in MAN.
10.
OPEN EXCITER FIELD BREAKER, 41 CS.
11.
PLACE GEN MANUAL VOLT ADJ RHEO, 70 CS, in the full lower position.
12.
PLACE GEN AUTO VOLTADJ RHEO, 90 CS, in the full lower position.
13.
NOTIFY System Operations Load Dispatcher that the unit is separated from the system.
14.
ENSURE the following extraction nonreturn valves on Panel XU-2, are closed:
a.
LP Turbine A 9th Stage Extraction Nonreturn Valves, EX-Vil and EX-V13 b.
LP Turbine B 9th Stage Extraction Nonreturn Valves, EX-V12 and EX-V14 c.
7th Stage Extraction To FW heater4A Nonreturn LI Valve, EX-V19 20P-26 Rev. 116 Page 54 of 159 7.1.2 Procedural Steps
- 7.
DEPRESS the Emergency Trip System push button AND D
ENSURE the following:
- a.
All four main stop valves go full closed.
D
- b.
All four control valves go full closed.
D
- c.
The bypass valves throttle open to maintain D
reactor pressure constant at 928 psig.
- d.
All four intercept valves go closed.
D
- 8.
WHEN main generator MWe decrease to zero, THEN D
ENSURE both generator output breakers GENERA TOR 2 TO BUS 2A 230 KV PCB 29A AND GENERA TOR 2 TO BUS 2B 230 KV PCB 29B, are open.
- 9.
PLACE REGULA TOR MODE SELECTOR, 43 CS, in D
MAN.
- 10.
OPEN EXCITER FIELD BREAKER, 41 CS.
D
- 11.
PLACE GEN MANUAL VOL T ADJ RHEa, 70 CS, in the D
full lower position.
- 12.
PLACE GEN AUTO VOL T ADJ RHEa, 90 CS, in the full D
lower position.
- 13.
NOTIFY System Operations Load Dispatcher that the D
unit is separated from the system.
- 14.
ENSURE the following extraction nonreturn valves on Panel XU-2, are closed:
- a.
LP Turbine A 9th Stage Extraction Nonreturn D
Valves, EX-V11 and EX-V13
- b.
LP Turbine B 9th Stage Extraction Nonreturn D
Valves, EX-V12 and EX-V14
- c.
7th Stage Extraction To FW Heater 4A Nonreturn D
Valve, EX-V19 120P-26 Rev. 116 Page 54 of 1591
7.1.2 Procedural Steps d.
7th Stage Extraction To FW Heater 4B Nonreturn Valve, EX-V20 e.
4th Stage Extraction To FW Heater 5A Nonreturn Valve, EX-V23 f.
4th Stage Extraction To FW Heater 5B Nonreturn Valve, EX-V24 15.
ENSURE the following moisture removal valves, located on Panel XU-2, are open:
a.
LP Turbine A 11th Stage Extraction Moisture Removal Valve, LV-262 b.
LP Turbine A 11th Stage Extraction Moisture Removal Valve, LV-263 c.
LP Turbine B 11th Stage Extraction To Heater Drains Deaerator Moisture Removal Valve, LV-264 d.
LP Turbine B 11th Stage Extraction To Heater Drains Deaerator Moisture Removal Valve, LV-265 e.
LP Turbine A 9th Stage Extraction To Heater Drains Deaerator Moisture Removal Valve, MVD-L V-266 f.
LP Turbine B 9th Stage Extraction To Heater Drains Deaerator Moisture Removal Valve, MVD-L V-267 g.
4th Stage Extraction to FW Heater 5A Moisture Removal Valve, MVD-LV-268 h.
4th Stage Extraction to FW Heater 5B Moisture Removal Valve, MVD-LV-269 FW Heater 1A Moisture Removal Valve to Condenser, HD-LV-216 20P-26 Rev. 116 Page 55 of 159 7.1.2 Procedural Steps
- d.
7th Stage Extraction To FW Heater 4B Nonreturn D
Valve, EX-V20
- e.
4th Stage Extraction To FW Heater 5A Nonreturn D
Valve, EX-V23
- f.
4th Stage Extraction To FW Heater 5B Nonreturn D
Valve, EX-V24
- 15.
ENSURE the following moisture removal valves, located on Panel XU-2, are open:
- a.
LP Turbine A 11 th Stage Extraction Moisture D
Removal Valve, L V-262
- b.
LP Turbine A 11th Stage Extraction Moisture D
Removal Valve, L V-263
- c.
LP Turbine B 11th Stage Extraction To Heater D
Drains Deaerator Moisture Removal Valve, LV-264
- d.
LP Turbine B 11th Stage Extraction To Heater D
Drains Deaerator Moisture Removal Valve, LV-265
- e.
LP Turbine A 9th Stage Extraction To Heater D
Drains Deaerator Moisture Removal Valve, MVO-LV-266
- f.
LP Turbine B 9th Stage Extraction To Heater D
Drains Deaerator Moisture Removal Valve, MVO-LV-267
- g.
4th Stage Extraction to FW Heater 5A Moisture D
Removal Valve, MVO-L V-268
- h.
4th Stage Extraction to FW Heater 5B Moisture D
Removal Valve, MVO-L V-269
- i.
FW Heater 1A Moisture Removal Valve to D
Condenser, HO-LV-216 120P-26 Rev. 116 Page 55 of 1591
7.1.2 Procedural Steps j.
FW Heater 1 B Moisture Removal Valve to El Condenser, HD-LV-217 k.
HP TURB 7TH STAGE EXHAUST DRAIN VLVS, MVD-MO V-CA-2/1/3/4 16.
ENSURE the exhaust hood spray system maintains exhaust hood temperatures less than 175°F on recorder TSI-TXR-638, Points 8 and 9.
17.
MONITOR turbine bearing metal temperatures during turbine coastdown for spikes greater than 50°F on recorder TSI-TR-642.
18.
IF a turbine bearing metal temperature spike of greater than 50°F is indicated, THEN PERFORM the following:
a.
IF turbine speed is greater than 900 rpm, THEN MANUALLY start the lift pumps.
b.
IF turbine speed is less than 900 rpm, THEN ENSURE the lift pump associated with the high temperature bearing is operating.
c.
NOTIFY the Unit CRS of the condition.
19.
WHEN turbine speed decreases to less than 900 rpm, THEN ENSURE all six turbine bearing lift pumps are running.
20.
IF turbine bearing metal temperature spikes greater than 10°F/minute are detected, THEN NOTIFY the System Engineer to investigate.
21.
MONITOR vibration of turbine bearings on recorder TSI-XR-640 during turbine coastdown.
22.
IF vibration greater than 10 mils is detected, THEN NOTIFY the System Engineer.
23.
ADJUST TBCCW TO MAIN TURB OIL COOLER temperature controller to maintain bearing oil inlet temperature at 90°F.
20P-26 Rev. 116 Page 56 of 159 7.1.2 Procedural Steps
- j.
FW Heater 1 B Moisture Removal Valve to D
Condenser, HD-LV-217
- k.
HP TURB 7TH STAGE EXHAUST DRAIN VLVS, D
MVD-MO V-CA-2/1/3/4
- 16.
ENSURE the exhaust hood spray system maintains D
exhaust hood temperatures less than 175°F on recorder TSI-TXR-638, Points 8 and 9.
- 17.
MONITOR turbine bearing metal temperatures during D
turbine coastdown for spikes greater than 50°F on recorder TSI-TR-642.
- 18.
IF a turbine bearing metal temperature spike of greater than 50°F is indicated, THEN PERFORM the following:
- a.
IF turbine speed is greater than 900 rpm, THEN D
MANUALLY start the lift pumps.
- b.
IF turbine speed is less than 900 rpm, THEN D
ENSURE the lift pump associated with the high temperature bearing is operating.
- c.
NOTIFY the Unit CRS of the condition.
D
- 19.
WHEN turbine speed decreases to less than 900 rpm, D
THEN ENSURE all six turbine bearing lift pumps are running.
- 20.
IF turbine bearing metal temperature spikes greater than D
10°F/minute are detected, THEN NOTIFY the System Engineer to investigate.
- 21.
MONITOR vibration of turbine bearings on recorder D
TSI-XR-640 during turbine coastdown.
- 22.
IF vibration greater than 10 mils is detected, THEN D
NOTIFY the System Engineer.
- 23.
ADJUST TBCCW TO MAIN TURB OIL COOLER D
temperature controller to maintain bearing oil inlet temperature at 90°F.
120P-26 Rev. 116 Page 56 of 1591
7.1.2 Procedural Steps NOTE:
Oil temperature should be maintained at 80-90°F. MAIN TURBINE OIL COOLER TBCCWOUTLETISOLATION VALVE, TCC-V117, may require throttling to maintain this temperature.
24.
IF required, THEN THROTTLE MAIN TURBINE OIL COOLERS TBCCW OUTLET ISOLATION VALVE, TCC V117, to maintain oil temperature at 90°F.
25.
WHEN turbine speed decreases to zero, as indicated by the TURBINE AT ZERO SPEED (UA-02 1-4) alarm, THEN ENSURE the following:
a.
The turning gear piggy back motor starts AND engages.
b.
Approximately 10 seconds after the piggy back motor starts, the turning gear main motor starts.
26.
IF the turning gear will NOT remain engaged, THEN REMOVE lift pumps from service in accordance with Section 8.22.
27.
WHEN the turbine is on the turning gear, THEN PERFORM the following actions once per hour:
a.
ENSURE the appropriate lift pumps are operating LI in accordance with Section 8.22.
b.
ENSURE all bearing metal temperatures, as indicated on recorder TSI-TR-642, are within 95°F to 110°F for turning gear operation.
c.
IF any bearing metal temperature exceeds 110°F, THEN NOTIFY the Unit CRS.
28.
ENSURE either Bus Duct Fan 2A-1 or 2A-2 is in-service AND PLACE Isophase Bus Heater switch in ON at the equipment cabinet on Turbine Building 38 el.
29.
WHEN the turbine is operating on the turning gear, LI THEN CLEAN the lift pumps Cuno filters once per shift by rotating the five Cuno filters T-handles clockwise two complete revolutions.
20P-26 Rev. 116 Page57of159 7.1.2 Procedural Steps NOTE:
Oil temperature should be maintained at 80-90°F. MAIN TURBINE OIL COOLER TBCCW OUTLET ISOLA TlON VAL VE, TCC-V117, may require throttling to maintain this temperature.
- 24.
IF required, THEN THROTTLE MAIN TURBINE OIL D
COOLERS TBCCW OUTLET ISOLA TlON VAL VE, TCC-V117, to maintain oil temperature at 90°F.
- 25.
WHEN turbine speed decreases to zero, as indicated by the TURBINE AT ZERO SPEED (UA-02 1-4) alarm, THEN ENSURE the following:
- a.
The turning gear piggy back motor starts AND D
engages.
- b.
Approximately 10 seconds after the piggy back D
motor starts, the turning gear main motor starts.
- 26.
IF the turning gear will NOT remain engaged, THEN D
REMOVE lift pumps from service in accordance with Section 8.22.
- 27.
WHEN the turbine is on the turning gear, THEN PERFORM the following actions once per hour:
- a.
ENSURE the appropriate lift pumps are operating D
in accordance with Section 8.22.
- b.
ENSURE all bearing metal temperatures, as D
indicated on recorder TSI-TR-642, are within 95°F to 110°F for turning gear operation.
- c.
IF any bearing metal temperature exceeds 110°F, D
THEN NOTIFY the Unit CRS.
- 28.
ENSURE either Bus Duct Fan 2A-1 or 2A-2 is in-service D
AND PLACE Isophase Bus Heater switch in ON at the equipment cabinet on Turbine Building 38' el.
- 29.
WHEN the turbine is operating on the turning gear, D
THEN CLEAN the lift pumps' Cuno filters once per shift by rotating the five Cuno filters' T-handles clockwise two complete revolutions.
!20P-26 Rev. 116 Page 57 of 1591
7.1.2 Procedural Steps NOTE:
The Main Lube Oil System should be operated continuously except for shutdowns required for Maintenance or inspection.
30.
REMOVE the turbine from turning gear operation in accordance with Section 8.1.
20P-26 Rev. 116 Page 58 of 159 NOTE:
7.1.2 Procedural Steps The Main Lube Oil System should be operated continuously except for shutdowns required for Maintenance or inspection.
- 30.
REMOVE the turbine from turning gear operation in D
accordance with Section 8.1.
120 P-26 Rev. 116 Page 58 of 1591
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim G LESSON TITLE:
Place SULCV In Service Following a Reactor Scram LESSON NUMBER:
LOT-SIM-JP-32A-07 REVISION NO:
01
)
H PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim G LESSON TITLE:
Place SULCV In Service Following a Reactor Scram LESSON NUMBER:
LOT-SIM-JP-32A-07 REVISION NO:
01
Place SULCV In Service Following a Reactor Scram.
SIMULATOR SETUP A.
Initial Conditions 1.
Recommended Initial Conditions IC 11 Rx. Pwr.
100%
Core Age BOC 2.
Required Plant Conditions RPV water level <170, REP high-level trips sealed-in B.
Malfunctions None C.
Overrides None.
D.
Special Instructions 1.
Trip the Main Turbine to insert a reactor scram and perform immediate actions with exception of tripping one REP; allow REPs to trip on high level.
2.
Lower RPV level to <170. Ensure RCIC is tripped and HPCI AOP is in PTL.
3.
Perform actions of the SULCV Hard card up to step 9.
LOT-SIM-JP-03A2-A07 Page 2 of 9 Rev. 01 Place SULCV In Service Following a Reactor Scram.
SIMULATOR SETUP A.
Initial Conditions
- 1.
Recommended Initial Conditions IC 11 Rx. Pwr.
100%
Core Age BOC
- 2.
Required Plant Conditions RPV water level <170", RFP high-level trips sealed-in B.
Malfunctions None C.
Overrides None.
D.
Special Instructions
- 1.
Trip the Main Turbine to insert a reactor scram and perform immediate actions with exception of tripping one RFP; allow RFPs to trip on high level.
- 2.
- 3.
Lower RPV level to <170". Ensure RCIC is tripped and HPCI AOP is in PTL.
Perform actions of the SULCV Hard card up to step 9.
LOT-SIM-JP-03A2-A07 Page 2 of 9 Rev. 01
Place SULCV In Service Following a Reactor Scram.
SAFETY CONSIDERATIONS:
NONE EVALUATOR NOTES: (Do not read to trainee) 1.
The applicable procedure section WILL NOT be provided to the trainee.
2.
If this is the first set of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the trainee.
TASK CONDITIONS:
Read the following to the trainee 1.
A reactor scram has occurred.
2.
RPV water level has dropped below +170 and Feedwater is required to restore RPV water level to the normal band.
3.
HPCI and RCIC are not available.
4.
Feedwater Level Control Following A Reactor Scram Hard Card was started and completed up through step 8.
INITIATING CUE:
You are directed by the Unit CRS to:
(1) restart Reactor Feed Pump A, (2) complete the actions to place the Startup Level Control Valve in service, and (3) restore RPV water level to +170
- +200.
Inform the Unit CRS when RPV water level has been restored above 170.
LOT-SI M-J P-03A2-A07 Page3of9 Rev. 01 Place SULCV In Service Following a Reactor Scram.
SAFETY CONSIDERATIONS:
NONE EVALUATOR NOTES: (Do not read to trainee)
- 1.
The applicable procedure section WILL NOT be provided to the trainee.
- 2.
If this is the first set of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the trainee.
Read the following to the trainee TASK CONDITIONS:
- 1. A reactor scram has occurred.
- 2. RPV water level has dropped below +170" and Feedwater is required to restore RPV water level to the normal band.
- 4. Feedwater Level Control Following A Reactor Scram Hard Card was started and completed up through step 8.
INITIATING CUE:
You are directed by the Unit CRS to:
(1) restart Reactor Feed Pump A, (2) complete the actions to place the Startup Level Control Valve in service, and (3) restore RPV water level to +170" - +200".
Inform the Unit CRS when RPV water level has been restored above 170".
LOT-SIM-JP-03A2-A07 Page 3 of 9 Rev. 01
Place SULCV In Service FoNowing a Reactor Scram.
PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 -Obtain Hard Card S11205.
Hard Card S/1205 obtained.
SATIUNSAT*
TIME START NOTE:
The Operator needs to flip the hard card over to the other side for REACTOR FEED PUMP STARTUP instructions.
Step 2 Open RFP A Recirc Valve FW-FV-V46.
RFP A Recirc Valve FW-FV-V46control switch is placed to open and verified to indicate full open.
- CRITICAL STEP ** SATIUNSAT*
Step 3 Ensure open RFP A Discharge Valve FW-V3.
RFP A Discharge Valve FW-V3 verified to already indicate full open.
SATIU NSAT*
Step 4 Place RFPT A SP CTL, C32-SIC-R6O1A in MANUAL at its lower limit.
RFPTA SP CTL, C32-SIC-R6OIA indicates M with output at O%.
SATIU NSAT*
Step 5 Place A MAN/DFCS Control Switch to MANUAL.
MAN/DFCS Control Switch in MANUAL forA RFP.
- CRITICAL STEP ** SATIUNSAT*
LOT-SIM-JP-03A2-A07 Page 4 of 9 Rev. 01 Place SULCV In Service Following a Reactor Scram.
PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 - Obtain Hard Card S/1205.
Hard Card SI1205 obtained.
SATIUNSAT*
TIME START ____ _
NOTE:
The Operator needs to flip the hard card over to the other side for REACTOR FEED PUMP STARTUP instructions.
Step 2 - Open RFP A Recirc Valve FW-FV-V46.
RFP A Recirc Valve FW-FV-V46control switch is placed to open and verified to indicate full open.
- CRITICAL STEP ** SAT/UNSAT*
Step 3 - Ensure open RFP A Discharge Valve FW-V3.
RFP A Discharge Valve FW-V3 verified to already indicate full open.
SAT/UNSAT*
Step 4 - Place RFPT ASP CTL, C32-SIC-R601A in MANUAL at its lower limit.
RFPT ASP CTL, C32-SIC-R601A indicates M with output at ~%.
SAT/UNSAT*
Step 5 -Place A MAN/DFCS Control Switch to MANUAL.
MANIDFCS Control Switch in MANUAL for A RFP.
- CRITICAL STEP ** SAT/UNSAT*
LOT -SI M-J P-03A2-A07 Page 4 of 9 Rev. 01
Place SULCV In Service Following a Reactor Scram.
NOTE Step 14 may not be required based on plant conditions Step 6 Ensure Reactor Water Level is less than +206 inches AND RFPT A&B High Level Trip/Reset Pushbuttons are reset.
Observes RPV water level is <206 inches using indications on the P603 Panel and depresses at least 2 of 3 reset push buttons are depressed and amber high level trip amber lamps on P603 are extinguished.
SATIU NSATIN E*
Step 7 Depress RFPT A RESET pushbutton.
RFPT A reset pushbutton on XU-2 depressed and RFP Tripped annunciator cleared.
- CRITICAL STEP ** SATIUNSAT*
Step 8 Ensure RFP A LP and HP Stop Valves are open.
Verifies RFPT A LP and HP Stop Valves automatically open on XU-2.
SATIU NSAT*
Step 9 Depress the REP A START Pushbutton.
RFP A START Pushbutton depressed and RFP speed rises to 1000 rpm.
- CRITICAL STEP ** SATIUNSAT*
Step 10 Raise REP A speed to 2550 rpm using the LOWER/RAISE Control Switch.
RFP A speed is raised to 2550 rpm.
- CRITICAL STEP ** SATIUNSAT*
LOT-SIM-JP-03A2-A07 Page 5 of 9 Rev. 01 Place SULCV In Service Following a Reactor Scram.
!iOTE:
Step 14 may not be required based on plant conditions.
Step 6 - Ensure Reactor Water Level is less than +206 inches AND RFPT A&B High Level Trip/Reset Pushbuttons are reset.
Observes RPV water level is <206 inches using indications on the P603 Panel and depresses at least 2 of 3 reset push buttons are depressed and amber high level trip amber lamps on P603 are extinguished.
SAT/U NSATIN E*
Step 7 - Depress RFPT A RESET pushbutton.
RFPT A reset pushbutton on XU-2 depressed and RFP Tripped annunciator cleared.
- CRITICAL STEP ** SAT/UNSAT*
Step 8 - Ensure RFP A LP and HP Stop Valves are open.
Verifies RFPT A LP and HP Stop Valves automatically open on XU-2.
SAT/UNSAT*
Step 9 - Depress the RFP A START Pushbutton.
RFP A START Pushbutton depressed and RFP speed rises to -1000 rpm.
- CRITICAL STEP ** SAT/UNSAT*
Step 10 - Raise RFP A speed to 2550 rpm using the LOWER/RAISE Control Switch.
RFP A speed is raised to -2550 rpm.
- CRITICAL STEP ** SATIUNSAT*
LOT-SIM-JP-03A2-A07 Page 5 of 9 Rev. 01
Place SULCV In Service Following a Reactor Scram.
Step 11 Depress the RFPT DFCS CTRL RESET Pushbutton and place MAN/DFCS Control Switch to DFCS.
Depresses RFPT DFCS CTRL RESET Pushbutton and verifies DFCS CTRL light is illuminated then places MAN/DFCS Control Switch in DFCS.
- CRITICAL STEP ** SATIUNSAT*
Step 12 Selects RFP DEMAND on RFPT A SP CTL, C32-SIC-R6O1A and raises RFP A speed, until discharge pressure is greater than or equal to 100 psig above reactor pressure.
Raises RFP A discharge pressure to 100 psig above reactor pressure.
- CRITICAL STEP ** SATIUNSAT*
NOTE:
The Operator needs to flip the hard card over to the other side for Feedwater Level Control Following a Reactor Scram and continue at step 10.
Step 13 Manually adjust the SULCV, FW-LIC-3269, for desired reactor water level.
SULCV is adjusted in manual to open the valve. Master controller verified to be at 187 inches.
- CRITICAL STEP ** SATIUNSAT*
Step 14 Place SULCV, FW-LIC-3269, in AUTO.
SULCV is in AUTO.
SATIUNSAT*
Step 15 Inform Unit CRS that RPV water level is above +170.
Unit CRS informed.
SAT/UNSAT*
TERMINATING CUE: RPV water level has been restored to >+170 using SULCV.
- Comments required for any step evaluated as UNSAT.
TIME COMPLETED LOT-SIM-JP-03A2-A07 Page 6 of 9 Rev. 01 Place SULCV In Service Following a Reactor Scram.
Step 11 - Depress the RFPT DFCS CTRL RESET Pushbutton and place MAN/DFCS Control Switch to DFCS.
Depresses RFPT DFCS CTRL RESET Pushbutton and verifies DFCS CTRL light is illuminated then places MANIDFCS Control Switch in DFCS.
- CRITICAL STEP ** SATIUNSAT*
Step 12 - Selects RFP DEMAND on RFPT ASP CTL, C32-SIC-R601A and raises RFP A speed, until discharge pressure is greater than or equal to 100 psig above reactor pressure.
NOTE:
Raises RFP A discharge pressure to 2100 psig above reactor pressure.
- CRITICAL STEP ** SA TlUNSAT*
The Operator needs to flip the hard card over to the other side for Feedwater Level Control Following a Reactor Scram and continue at step 1 O.
Step 13 - Manually adjust the SULCV, FW-UC-3269, for desired reactor water level.
SULCV is adjusted in manual to open the valve. Master controller verified to be at 187 inches.
- CRITICAL STEP ** SATIUNSAT*
Step 14 - Place SULCV, FW-UC-3269, in AUTO.
SULCV is in AUTO.
SATIUNSAT*
Step 15 -Inform Unit CRS that RPVwater level is above +170".
Unit CRS informed.
SAT/UNSAT*
II TIERMII~A'TI".GCLIE:. RPV water level has been restored to >+170" using SULCV.
Comments required for any step evaluated as UNSAT.
TIME COMPLETED ____
LOT-SIM-JP-03A2-A07 Page 6 of 9 Rev. 01
Place SULCV In Service Following a Reactor Scram.
RELATED TASKS:
2592028101 Start the First Reactor Feed Pump per OP-32 KIA REFERENCE AND IMPORTANCE RATING:
295001 A4.02 3.9, 3.7 Ability to manually start/control a REP in the control room.
REFERENCES:
ATTACHMENT 6 of 20P-32, Rev 165 TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2)
Safety Function 2, Inventory Control REASON FOR REVISION:
Removed the steps prior to starting the feed pump..
LOT-SIM-JP-03A2-A07 Page 7 of 9 Rev. 01 Place SULCV In Service Following a Reactor Scram.
RELATED TASKS:
259202B101 Start the First Reactor Feed Pump per OP-32 KIA REFERENCE AND IMPORTANCE RATING:
295001 A4.02 3.9, 3.7 Ability to manually start/control a RFP in the control room.
REFERENCES:
ATTACHMENT 6 of 20P-32, Rev 165 TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2)
Safety Function 2, Inventory Control REASON FOR REVISION:
Removed the steps prior to starting the feed pump..
LOT-SIM-JP-03A2-A07 Page 7 of 9 Rev. 01
Place SULCV In Service Following a Reactor Scram.
Time required for Completion:
18 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room
SimulatorX (Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes No X
EVALUATION Trainee:_________________________________
JPM:
Pass Fail Remedial Training Required: Yes No Did Trainee Verify Procedure as Authorized Copy?
Yes No (Each Student should verify one JPM per evaluation set.)
Comments:
Comments Reviewed With Trainee Evaluator Signature:
Date:____________
LOT-SIM-JP-03A2-A07 Page 8 of 9 Rev. 01 Place SULCV In Service Following a Reactor Scram.
Time required for Completion:
18 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room Simulator1 (Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Alternate Path:
Yes No X
EVALUATION Trainee: _____________ _
JPM:
Pass Fail Remedial Training Required: Yes No __
Did Trainee Verify Procedure as Authorized Copy? Yes __ No __
(Each Student should verify one JPM per evaluation set.)
Comments:
Comments Reviewed With Trainee Time Limit N/A Evaluator Signature: _____________ Date: ____ _
LOT -SIM-JP-03A2-A07 Page 8 of 9 Rev. 01
TASK CONDITIONS:
1.
A reactor scram has occurred.
2.
RPV water level has dropped below +170 and Feedwater is required to restore RPV water level to the normal band.
3.
HPCI and RCIC are not available.
4.
Feedwater Level Control Following A Reactor Scram Hard Card was started and completed up through step 8.
INITIATING CUE:
You are directed by the Unit CRS to:
(1) restart Reactor Feed Pump A, (2) complete the actions to place the Startup Level Control Valve in service, and (3) restore RPV water level to +170
- +200.
Inform the Unit CRS when RPV water level has been restored above 170.
TASK CONDITIONS:
- 1.
A reactor scram has occurred.
- 2.
RPV water level has dropped below +170" and Feedwater is required to restore RPV water level to the normal band.
- 3.
HPCI and RCIC are not available.
- 4.
Feedwater Level Control Following A Reactor Scram Hard Card was started and completed up through step 8.
INITIATING CUE:
You are directed by the Unit CRS to:
(1) restart Reactor Feed Pump A, (2) complete the actions to place the Startup Level Control Valve in service, and (3) restore RPV water level to +170" - +200".
Inform the Unit CRS when RPV water level has been restored above 170".
ATTACHMENT 6 Page 1 of 2 Feedwater Level Control Following a Reactor Scram
- Reactor Feed Pump Startup RO 1.
IF NECESSARY, THEN DISPATCH AN OPERATOR TO REP A(B) TO RESPOND TO ANY LOCAL ANNUNCIATOR PANEL ALARMS.
RO 2.
CLOSE (FW-V6 AND FW-V8) OR (FW-V1 18 AND FW-V1 19).
RO 3.
ENSURE FW-FV-177 IS CLOSED.
RO 4.
OPEN FW-V10.
RO 5.
PLACE FEEDWATER CONTROL MODE SELECT TO I ELEM.
RO RO 6.
IF BOTH RFPs HAVE TRIPPED, THEN ENSURE MSTR RFPT SP/RX LVL CTL, C32-SIC-R600, IS IN M (MANUAL) AND SET TO MAINTAIN 187 INCHES.
7.
ENSURE SULCV, FW-LIC-3269, IN M (MANUAL) AND SULCV CLOSED.
RO 8.
ENSURE B21-F032A AND B21-F032B ARE OPEN.
9.
IF AN RFP IS RUNNING, THEN PLACE RFPT A (B) SP CTL, C32-SIC-R6O1A (B), IN M (MANUAL) AND ADJUST REP A (B) SPEED UNTIL DISCHARGE PRESSURE IS APPROXIMATELY 100 PSI GREATER THAN REACTOR PRESSURE.
10.
ADJUST SULCV, FW-LIC-3269, FOR DESIRED REACTOR WATER LEVEL.
11.
IF DESIRED, THEN PLACE SULCV, FW-LIC-3269, IN A (AUTO).
12.
ADJUST FW-FV-177 TO MAINTAIN SULCV, FW-LIC-3269, OUTPUT DEMAND SIGNAL BETWEEN 25% AND 55%.
13.
IF SULCV, FW-LIC-3269, FAILS TO CONTROL LEVEL, THEN USE ONE OR MORE OF THE FOLLOWING VALVES TO AID IN LEVEL CONTROL:
FW-V1 20, (FW-V1 18 AND FW-V6), (FW-V1 19 AND FW-V8).
2/1204 S/1205 20P-32 Rev. 166 Page 292 of 301 FEEDWATER LEVEL CONTROL FOLLOWING A REACTOR SCRAM ATTACHMENT 6 Page 1 of 2 Feedwater Level Control Following a Reactor Scram - Reactor Feed Pump Startup NOTE:
This attachment is also applicable to the Simulator.
NOTE:
This attachment is NOT to be used for routine system operation.
FEEDWATER LEVEL CONTROL FOLLOWING A REACTOR SCRAM RO
- 1.
IF NECESSARY, THEN DISPATCH AN OPERATOR TO RFP A(B) TO RESPOND TO ANY LOCAL ANNUNCIATOR PANEL ALARMS.
- 2.
CLOSE (FW-V6 AND FW-V8) OR (FW-V118 AND FW-V119).
- 3.
ENSURE FW-FV-177IS CLOSED.
- 4.
OPEN FW-V10.
- 5.
PLACE FEEDWATER CONTROL MODE SELECT TO 1 ELEM.
- 6.
IF BOTH RFPs HAVE TRIPPED, THEN ENSURE MSTR RFPT SP/RX LVL CTL, C32-SIC-R600, IS IN M (MANUAL) AND SET TO MAINTAIN 187 INCHES.
- 7.
ENSURE SULCV, FW-LlC-3269, IN M (MANUAL) AND SULCV CLOSED.
- 8.
ENSURE B21-F032A AND B21-F032B ARE OPEN.
1 20 P-32
- 9.
IF AN RFP IS RUNNING, THEN PLACE RFPT A (B) SP CTL, C32-SIC-R601A (B), IN M (MANUAL) AND ADJUST RFP A (B) SPEED UNTIL DISCHARGE PRESSURE IS APPROXIMATELY 100 PSI GREATER THAN REACTOR PRESSURE.
- 10.
ADJUST SULCV, FW-LlC-3269, FOR DESIRED REACTOR WATER LEVEL.
- 11.
IF DESIRED, THEN PLACE SULCV, FW-LlC-3269, IN A (AUTO).
- 12.
ADJUST FW-FV-177 TO MAINTAIN SULCV, FW-LlC-3269, OUTPUT DEMAND SIGNAL BETWEEN 25% AND 55%.
- 13.
IF SULCV, FW-LlC-3269, FAILS TO CONTROL LEVEL, THEN USE ONE OR MORE OF THE FOLLOWING VALVES TO AID IN LEVEL CONTROL:
FW-V120, (FW-V118 AND FW-V6), (FW-V119 AND FW-V8).
2/1204 S/1205 Rev. 166 Page 292 of 301 I
ATTACHMENT 6 Page 2 of 2 Feedwater Level Control Following a Reactor Scram
- Reactor Feed Pump Startup NOTE:
This attachment is also applicable to the Simulator.
NOTE:
This attachment is NOT to be used for routine system operation.
REACTOR FEED PUMP STARTUP RO 1.
IF NECESSARY, THEN DISPATCH AN OPERATOR TO RFP A(B) TO RESPOND TO ANY LOCAL ANNUNCIATOR PANEL ALARMS.
RO 2.
ENSURE A FEEDWATER FLOW PATH IS ESTABLISHED TO THE REACTOR VESSEL.
3.
OPEN RFP A (B) RECIRC VLV, FW-FV-46 (FW-FV-47).
4.
ENSURE RFP A (B) DISCH VLV, FW-V3 (FW-V4) IS OPEN.
5.
PLACE RFPT A (B) SP CTL, C32-SIC-R6O1A (B), IN M (MANUAL) AT ITS LOWER LIMIT.
6.
PLACE RFPT A(B) MAN/DFCS CONTROL SWITCH IN MAN.
7.
ENSURE REACTOR WATER LEVEL IS LESS THAN +206 INCHES AND RFPT A&B HIGH LEVEL TRIP/RESET PUSHBUTTONS ARE RESET.
8.
DEPRESS RFPT A (B) RESET PUSHBUTTON 9.
ENSURE RFPT A (B) LP AND HP STOP VLVS ARE OPEN.
10.
ROLL RFPT A (B) TO 1000 RPM BY DEPRESSING RFP A(B) START PUSHBUTTON.
11.
RAISE RFPT A(B) SPEED TO APPROXIMATELY 2550 RPM USING THE LOWER/RAISE CONTROL SWITCH.
12.
DEPRESS RFPTA(B) DFCS CTRL RESET AND PLACE MAN/DFCS CONTROL SWITCH TO DFCS.
13.
RAISE RFPT A (B) SPEED WITH RFPT A (B) SP CTL, C32-SIC-R6OIA (B),
UNTIL DISCHARGE PRESSURE IS GREATER THAN OR EQUAL TO 100 PSIG ABOVE REACTOR PRESSURE.
2/1 204 S/I 205 2OP-32 Rev. 166 Page 293 of 301 ATTACHMENT 6 Page 2 of 2 Feedwater Level Control Following a Reactor Scram - Reactor Feed Pump Startup NOTE:
This attachment is also applicable to the Simulator.
NOTE:
This attachment is NOT to be used for routine system operation.
- 1.
- 2.
- 3.
- 4.
- 5.
- 6.
- 7.
- 8.
- 9.
- 10.
- 11.
- 12.
- 13.
120P-32 REACTOR FEED PUMP STARTUP IF NECESSARY, THEN DISPATCH AN OPERATOR TO RFP A(B) TO RESPOND TO ANY LOCAL ANNUNCIATOR PANEL ALARMS.
ENSURE A FEEDWATER FLOW PATH IS ESTABLISHED TO THE REACTOR VESSEL.
OPEN RFP A (B) RECIRC VLV, FW-FV-46 (FW-FV-47).
ENSURE RFP A (B) DISCH VLV, FW-V3 (FW-V4) IS OPEN.
PLACE RFPT A (B) SP CTL, C32-SIC-R601A (B), IN M (MANUAL) AT ITS LOWER LIMIT.
PLACE RFPT A(B) MAN/DFCS CONTROL SWITCH IN MAN.
ENSURE REACTOR WATER LEVEL IS LESS THAN +206 INCHES AND RFPT A&B HIGH LEVEL TRIP/RESET PUSHBUTTONS ARE RESET.
DEPRESS RFPT A (B) RESET PUSHBUTTON ENSURE RFPT A (B) LP AND HP STOP VLVS ARE OPEN.
ROLL RFPT A (B) TO 1000 RPM BY DEPRESSING RFP A(B) START PUSHBUTTON.
RAISE RFPT A(B) SPEED TO APPROXIMATELY 2550 RPM USING THE LOWER/RAISE CONTROL SWITCH.
DEPRESS RFPT A(B) DFCS CTRL RESET AND PLACE MAN/DFCS CONTROL SWITCH TO DFCS.
RAISE RFPT A (B) SPEED WITH RFPT A (B) SP CTL, C32-SIC-R601A (B),
UNTIL DISCHARGE PRESSURE IS GREATER THAN OR EQUAL TO 100 PSIG ABOVE REACTOR PRESSURE.
Rev. 166 2/1204 S/1205 Page 293 of 301 I
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim H LESSON TITLE:
Restart CRD Following CRD Pump Trip LESSON NUMBER:
LOT-SIM-JP-008--BO1 REVISION NO:
I J/i
/
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE SIMULATOR NRC Sim H LESSON TITLE:
Restart CRD Following CRD Pump Trip LESSON NUMBER: LOT-SIM-JP-008-B01 REVISION NO:
1
Restart CRD Following CRD Pump Trip SIMULATOR SETUP Initial Conditions 1.
Recommended Initial Conditions IC 11 Rx. Pwr.
100%
Core Age BOC 2.
Required Plant Conditions No CRD pumps in operation.
Special Instructions Turn off the operating CRD pump.
Isolate Seal Purge to the Recirc Pumps LOT-OJT-JP-002-AO1 Page 2 REV. 0 Restart CRD Following CRD Pump Trip SIMULATOR SETUP Initial Conditions
- 1.
Recommended Initial Conditions IC 11 Rx. Pwr.
100%
Core Age BOC
- 2.
Required Plant Conditions No CRD pumps in operation.
Special Instructions Turn off the operating CRD pump.
Isolate Seal Purge to the Recirc Pumps LOT -OJT -JP-002-A01 Page 2 REV. 0
Restart CRD Following CRD Pump Trip SAFETY CONSIDERATIONS:
NONE EVALUATOR NOTES: (Do not read to trainee) 1.
The applicable procedure section WILL NOT be provided to the trainee.
When the trainee has identified the proper procedure and section to be used a working copy of the procedure WILL be given to the trainee.
2.
If this is the first set of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the trainee.
Read the following to the trainee TASK CONDITIONS:
1.
The operating CRD Pump (2B) tripped on low suction pressure.
2.
OAOP-02.0 has been entered due to Control Rod Malfunction/Misposition.
3.
The standby CRD Suction Filter has been placed in service.
4.
Recirculation Pump seal purge has been isolated, and another operator has been assigned to perform 20P-02 actions for seal purge restoration.
5.
20P-08 Section 8.17 has been completed up to Step 3.
INITIATING CUE:
You are directed by the Unit CRS to restart the CRD system per 20P-08, and inform him when CRD has been returned to service.
LOT-OJT-JP-002-AO1 Page 3 REV. 0 Restart CRD Following CRD Pump Trip SAFETY CONSIDERATIONS:
NONE EVALUATOR NOTES: (Do not read to trainee)
- 1.
The applicable procedure section WILL NOT be provided to the trainee.
When the trainee has identified the proper procedure and section to be used a working copy of the procedure WILL be given to the trainee.
- 2.
If this is the first set of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the trainee.
Read the following to the trainee TASK CONDITIONS:
- 1.
The operating CRD Pump (28) tripped on low suction pressure.
- 2.
OAOP-02.0 has been entered due to Control Rod Malfunction/Misposition.
- 3.
The standby CRD Suction Filter has been placed in service.
- 4.
Recirculation Pump seal purge has been isolated, and another operator has been assigned to perform 20P-02 actions for seal purge restoration.
- 5.
20P-OS Section S.17 has been completed up to Step 3.
INITIATING CUE:
You are directed by the Unit CRS to restart the CRD system per 20P-OS, and inform him when CRD has been returned to service.
LOT-OJT-JP-002-A01 Page 3 REV. 0
Restart CRD Following CRD Pump Trip PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1
- Obtain current revision of 20P-08 section 8.17.
Current revision of 20P-08, Section 8.17 obtained.
SATIUNSAT*
TIME START:
Step 2-Place CRD Flow Control, C12-FC-R600, in MAN and reduce potentiometer to minimum setting.
C12-FC-R600 is placed in MAN, thumbwheel adjusted counter clockwise until manual output meter on controller indicates 0.
- CRITICAL STEP ** SATIUNSAT*
Step 3
- Open Drive Pressure control valve C12-PCV-F003.
C12-PCV-FOO3control switch is placed in open until full open indication is obtained on P603 (this is a throttle valve).
SATIUNSAT*
PROMPT:
If requested as AC, report cooling water valves to CRD pumps are open.
Step 4
- Ensure RBCCW in operation to supply cooling water to CRD pumps.
RBCCW checked in operation as indicated by pumps running and RBCCW discharge header pressure is normal as indicated on RCC-Pl 671-1 on XU-2.
SATIU NSAT*
NOTE:
After starting the pump, alarms A-5 (6-1) CRD PUMP INLET FILTER 1P HIGH will come in and clear and alarm A-05 (2-1) CRD CHARGING WTR PRESS HI will come in until the flow control valve is opened. This may be reviewed prior to starting the pump and announced as expected alarms.
LOT-OJT-JP-002-AO1 Page 4 REV. 0 Restart CRD Following CRD Pump Trip PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 - Obtain current revision of 20P-OB section B.17.
Current revision of 20P-OB, Section B. 17 obtained.
SAT/UNSAT*
TIME START: _____ _
Step 2 - Place CRD Flow Control, C12-FC-R600, in MAN and reduce potentiometer to minimum setting.
C12-FC-R600 is placed in MAN, thumbwheel adjusted counter-clockwise until manual output meter on controller indicates O.
- CRITICAL STEP ** SAT/UNSAT*
Step 3 - Open Drive Pressure control valve C12-PCV-F003.
PROMPT:
C12-PCV-F003control switch is placed in open until full open indication is obtained on P603 (this is a throttle valve).
SAT/UNSAT*
If requested as AO, report cooling water valves to CRD pumps are open.
Step 4 - Ensure RBCCW in operation to supply cooling water to CRD pumps.
RBCCW checked in operation as indicated by pumps running and RBCCW discharge header pressure is normal as indicated on RCC-PI-671-1 on XU-2.
SAT/UNSAT*
NOTE:
After starting the pump, alarms A-5(6-1) CRD PUMP INLET FILTER LlP HIGH will come in and clear and alarm A-05 (2-1) CRD CHARGING WTR PRESS HI will come in until the flow control valve is opened. This may be reviewed prior to starting the pump and announced as expected alarms.
LOT-OJT-JP-002-A01 Page 4 REV. 0
Restart CRD Following CRD Pump Trip PROMPT:
If requested as AC, report prestart checks completed SAT.
If requested, as Unit CRS inform examinee to start the 2B CRD Pump.
Step 5
- Start non operating CRD Pump.
CRD Pump A or B started and indicates running by red light on P603.
- CRITICAL STEP ** SATIUNSAT*
Step 6
- Raise CRD flow rate to 30-60 GPM using manual potentiometer on CRD FLOW CONTROL, C12-FC-R600.
CRD flow raised using manual potentiometer and indicates between 30 and 60 GPM on flow controller C12-FC-R600.
SATIU NSAT*
SIM OP:
When asked to restore recirc pump seal purge perform the following by initiating Trigger 1:
- 1. Open SEAL INJECTION VALVE, B32-V22, for Recirc Pump A.
- 2. Open SEAL INJECTION VALVE, B32-V30, for Recirc Pump B.
PROMPT:
When the Sim Op has opened the recirc seal purge valves, Inform examinee that recirc pump seal purge has been restored.
Step 7
- Null CRD FLOW CONTROL, C12-FC-R600, using the setpoint tape.
C12-FC-R600 setpoint tape adjusted to bring red needle within green band of setpoint tape.
SATIU NSAT*
Step 8
- Shift CRD FLOW CONTROL, C12-FC-R600 to Auto.
Select switch on C12-FC-R600 is placed to AUTO.
- CRITICAL STEP ** SATIUNSAT*
LOT-OJT-JP-002-AO1 Page 5 REV. 0 Restart CRD Following CRD Pump Trip PROMPT:
If requested as AO, report prestart checks completed SAT.
If requested, as Unit CRS inform examinee to start the 2B CRD Pump.
Step 5 - Start non operating CRD Pump.
CRD Pump A or 8 started and indicates running by red light on P603.
- CRITICAL STEP ** SAT/UNSAT*
Step 6 - Raise CRD flow rate to 30-60 GPM using manual potentiometer on CRD FLOW CONTROL, C12-FC-R600.
SIM OP:
PROMPT:
CRD flow raised using manual potentiometer and indicates between 30 and 60 GPM on flow controller C12-FC-R600.
SAT/UNSAT*
When asked to restore recirc pump seal purge perform the following by initiating Trigger 1 :
- 1. Open SEAL INJECTION VAL VE, 832-V22, for Recirc Pump A.
- 2. Open SEAL INJECTION VAL VE, 832-V30,for Recirc Pump B.
When the Sim Op has opened the recirc seal purge valves, Inform examinee that recirc pump seal purge has been restored.
Step 7 - Null CRD FLOW CONTROL, C12-FC-R600, using the setpoint tape.
C12-FC-R600 setpoint tape adjusted to bring red needle within green band of setpoint tape.
SATIUNSAT*
Step 8 - Shift CRD FLOW CONTROL, C12-FC-R600 to Auto.
Select switch on C12-FC-R600 is placed to AUTO.
- CRITICAL STEP ** SAT/UNSAT*
LOT-OJT-JP-002-A01 Page 5 REV. 0
Restart CRD Following CRD Pump Trip Step 9
- Adjust setpoint tape on CRD FLOW CONTROL, C12-FC-R600, to maintain cooling water differential pressure betweenl0-26 psid as read on C12-PDI-R603 on Panel P603.
Cooling Water dp reads between 10 and 26 psid on C12-PDI-R603 on Panel P603.
- CRITICAL STEP ** SATIUNSAT*
Step 10
- Ensure CRD flow rate is between 30 and 60 gpm.
C12-FC-R600 flow meter reads between 30-60 GPM.
SATIUNSAT*
Step 11
- Establish drive water header differential pressure between 260 and 275 psid as read on C12-PDI-R602 on Panel P603 by throttling closed DRIVE PRESS VLV, Cl 2-PCV-F003.
Throttles closed DRIVE PRESS VL C12-PCV-F003, until drive water dp indicates 260-2 75 psid as indicated on C12-PDI-R602 on panel P603.
- CRITICAL STEP ** SATIUNSAT*
Step 12
- Monitor operation of CRD Hydraulic System in accordance with section 6.0.
2 OP-08, Section 6.0 referred to for proper operational parameters.
SATIUNSAT*
Step 13 Inform Unit CRS that CRD has been returned to service per 20P-08.
Unit CRS informed.
SATIUNSAT*
TERMINATING CUE CRD has been returned to service per 2OP-08 Comments required for any step evaluated as UNSAT.
TIME STOP:
LOT-OJT-JP-002-AO1 Page 6 REV. 0 Restart CRD Following CRD Pump Trip Step 9 - Adjust setpoint tape on CRD FLOW CONTROL, C12-FC-R600, to maintain cooling water differential pressure between 1 0-26 psid as read on C12-PDI-R603 on Panel P603.
Cooling Waterdp reads between 10 and 26 psid on C12-PDI-R603 on Panel P603.
- CRITICAL STEP ** SAT/UNSAT*
Step 10 - Ensure CRD flow rate is between 30 and 60 gpm.
C12-FC-R600 flow meter reads between 30-60 GPM.
SAT/UNSAT*
Step 11 - Establish drive water header differential pressure between 260 and 275 psid as read on C12-PDI-R602 on Panel P603 by throttling closed DRIVE PRESS VLV, C12-PCV-F003.
Throttles closed DRIVE PRESS VL V, C12-PCV-F003, until drive water dp indicates 260-275 psid as indicated on C12-PDI-R602 on panel P603.
- CRITICAL STEP ** SAT/UNSAT*
Step 12 - Monitor operation of CRD Hydraulic System in accordance with section 6.0.
20P-08, Section 6.0 referred to for proper operational parameters.
SAT/UNSAT*
Step 13 - Inform Unit CRS that CRD has been returned to service per 20P-OB.
Unit CRS informed.
SATIUNSAT*
TERMINATING CUE: CRD has been returned to service per 20P-OB.
Comments required for any step evaluated as UNSAT.
TIME STOP: _____ _
LOT-OJT-JP-002-A01 Page 6 REV. 0
Restart CRD Following CRD Pump Trip RELATED TASKS:
201023B101 Restart the CRD Hydraulic System Following a Loss of a CRD Pump Per OP-08.
KIA REFERENCE AND IMPORTANCE RATING:
201001 A2.01 3.2/3.2 Ability to predict the impact of a CRD pump trip on the CRD Hydraulic System and use procedures to correct, control or mitigate the consequences.
REFERENCES:
20P-08, Section 8.17, Rev. 78 TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2)
Safety Function 1, Reactivity Control REASON FOR REVISION:
LOT-OJT-JP-002-AO1 Page 7 REV. 0 Restart CRD Following CRD Pump Trip RELATED TASKS:
2010238101 Restart the CRD Hydraulic System Following a Loss of a CRD Pump Per OP-08.
KIA REFERENCE AND IMPORTANCE RATING:
201001 A2.01 3.2/3.2 Ability to predict the impact of a CRD pump trip on the CRD Hydraulic System and use procedures to correct, control or mitigate the consequences.
REFERENCES:
20P-08, Section 8.17, Rev. 78 TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2)
Safety Function 1, Reactivity Control REASON FOR REVISION:
LOT-OJT-JP-002-A01 Page 7 REV. 0
Restart CRD Following CRD Pump Trip Time required for Completion:
10 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room
SimulatorX (Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes No X
EVALUATION Trainee:_________________________________
JPM:
Pass Fail Remedial Training Required: Yes No Did Trainee Verify Procedure as Authorized Copy?
Yes No (Each Student should verify one JPM per evaluation set.)
Comments:
Comments Reviewed With Trainee Evaluator Signature:
Date:____________
LOT-OJT--JP-002-AO1 Page 8 REV. 0 Restart CRD Following CRD Pump Trip Time required for Completion:
10 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual X
Unit:
2 Setting:
Control Room Simulator 1 (Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes No X
EVALUATION Trainee: ---------------------------
JPM:
Pass __
Fail Remedial Training Required: Yes No __
Did Trainee Verify Procedure as Authorized Copy? Yes No ___ _
(Each Student should verify one JPM per evaluation set.)
Comments:
Comments Reviewed With Trainee Evaluator Signature: _________________________ Date: ____ _
LOT-OJT-JP-002-A01 Page 8 REV. 0
TASK CONDITIONS:
1.
The operating CRD Pump tripped on low suction pressure.
2.
OAOP-02.O has been entered due to Control Rod Malfunction/Misposition.
3.
The standby CRD Suction Filter has been placed in service.
4.
Recirculation Pump seal purge has been isolated, and another operator has been assigned to perform 20P-02 actions for seal purge restoration.
5.
20P-08 Section 8.17 has been completed up to Step 3.
INITIATING CUE:
You are directed by the Unit CRS to restart the CRD system per the Operating Procedure, and inform him when CRD has been returned to service.
TASK CONDITIONS:
- 1.
The operating CRD Pump tripped on low suction pressure.
- 2.
OAOP-02.0 has been entered due to Control Rod Malfunction/Misposition.
- 3.
The standby CRD Suction Filter has been placed in service.
- 4.
Recirculation Pump seal purge has been isolated, and another operator has been assigned to perform 20P-02 actions for seal purge restoration.
- 5.
20P-08 Section 8.17 has been completed up to Step 3.
INITIATING CUE:
You are directed by the Unit CRS to restart the CRD system per the Operating Procedure, and inform him when CRD has been returned to service.
8.17 Restarting CRD Hydraulic System Following Loss of CRD Pump R
Reference Use 8.17.1 Initial Conditions 1.
CRD System was in operation in accordance with Section 5.1.
2.
Operating CRD pump has stopped.
8.17.2 Procedural Steps 1.
CLOSE SEAL INJECTION VALVE, B32-V22, for Recirc PumpA.
2.
CLOSE SEAL INJECTION VALVE, B32-V30, for Recirc Pump B.
3.
PLACE CRD FLOW CONTROL, C12-FC-R600, in MAN AND REDUCE potentiometer to minimum setting.
4.
ENSURE DRIVE PRESS VLV, C12-PCV-F003, is fully open.
5.
ENSURE RBCCW is in operation to supply cooling water to CRD pumps.
6.
START non-operating (desired) CRD Pump A or B.
NOTE:
Following startup of the non-operating CRD pump, CRD accumulator recharge may momentarily delay the ability to perform CRD flow rate adjustments.
NOTE:
IF a reactor scram is sealed in, THEN the following steps can NOT be performed until the scram is reset.
7.
RAISE CRD flow rate to between 30 and 60 gpm, by Ej adjusting manual potentiometer on CRD FLOW CONTROL, C 12-FC-R600.
8.
RESTORE recirc pump seal purge in accordance with 20P-02 concurrently with performance of this section.
20P-08 Rev. 78 Page 79 of 335 8.17 Restarting CRD Hydraulic System Following Loss of CRD Pump 8.17.1
- 1.
- 2.
8.17.2
- 1.
- 2.
- 3.
- 4.
- 5.
- 6.
Initial Conditions CRD System was in operation in accordance with Section 5.1.
Operating CRD pump has stopped.
Procedural Steps CLOSE SEAL INJECTION VALVE, 832-V22, for Recirc Pump A.
CLOSE SEAL INJECTION VALVE, 832-V30, for Recirc Pump B.
PLACE CRD FLOW CONTROL, C12-FC-R600, in MAN AND REDUCE potentiometer to minimum setting.
ENSURE DRIVE PRESS VL V, C12-PCV-F003, is fully open.
ENSURE RBCCW is in operation to supply cooling water to CRD pumps.
START non-operating (desired) CRD Pump A or B.
NOTE:
Following startup of the non-operating CRD pump, CRD accumulator recharge may momentarily delay the ability to perform CRD flow rate adjustments.
NOTE:
IF a reactor scram is sealed in, THEN the following steps can NOT be performed until the scram is reset.
D D
D D
- 7.
RAISE CRD flow rate to between 30 and 60 gpm, by D
adjusting manual potentiometer on CRD FLOW CONTROL, C12-FC-R600.
- 8.
RESTORE recirc pump seal purge in accordance with D
20P-02 concurrently with performance of this section.
120P-08 Rev. 78 Page 79 of 3351 R
Reference Use
8.172 Procedural Steps 9.
NULL CRD FLOW CONTROL, C12-FC-R600, by adjusting the setpoint tape.
10.
SHIFT CRD FLOW CONTROL, C12-FC-R600, to AUTO.
11.
ADJUST setpoint tape on CRD FLOW CONTROL, C12-FC-R600, to maintain cooling water differential pressure between 10 and 26 psid on C12-PDI-R603 on Panel P603.
12.
ENSURE CRD flow rate is between 30 and 60 gpm.
13.
ESTABLISH drive water header differential pressure between 260 and 275 psid on C12-PDI-R602 on Panel P603, by throttling closed DRIVE PRESS VLV, Cl 2-PC V-F003.
14.
MONITOR operation of CRD System in accordance with Section 6.0.
20P-08 Rev. 78 Page 80 of 335 8.17.2 Procedural Steps
- 9.
NULL CRD FLOW CONTROL, C12-FC-R600, by D
adjusting the setpoint tape.
- 10.
SHIFT CRD FLOW CONTROL, C12-FC-R600, to AUTO.
D
- 11.
ADJUST setpoint tape on CRD FLOW CONTROL, C12-FC-R600, to maintain cooling water differential D
pressure between 10 and 26 psid on C12-PDI-R603 on Panel P603.
- 12.
ENSURE CRD flow rate is between 30 and 60 gpm.
D
- 13.
ESTABLISH drive water header differential pressure D
between 260 and 275 psid on C12-PDI-R602 on Panel P603, by throttling closed DRIVE PRESS VL V, C12-PCV-FOO3.
- 14.
MONITOR operation of CRD System in accordance with D
Section 6.0.
120P-08 Rev. 78 Page 80 of 3351
6.0 SYSTEM OPERATION Information Use 6.1 During normal operation of the Control Rod Drive Hydraulic System, the following parameters should be routinely monitored:
CRD flow rate 30 to 60 gpm during normal C12-FC-R600 power operations; up to 199 gpm Panel P603 (max flow) during various other applications, such as vessel fill, accumulator charging, etc Drive water differential 260 to 275 psid pressure Cl2-PDI-R602 Panel P603 Cooling water differential 10 to 26 psid (may be less pressure than 10 psid if reactor C12-PDI-R603 vessel temperature is less Panel P603 than 250°F)
Charging water pressure Less than 1510 psig Cl2-PI-R60I Panel P603 Drive water flow rate Approximately 0 gpm (flow C12-FI-R604 rate < 5.0 gpm during rod Panel P603 movement)
Cooling water flow rate 30 to 60 gpm (flow rates C12-FI-R605 above 50 gpm must be Panel P603 obtained from C12-FC-R600 on Panel P603)
CRD temperature Less than 250°F C12-TR-R018 Panel H21-P007 Pressure controlvalve l5to35psig CO-PC V-4 105 (outlet pressure)
CO-PI-4 106 Radwaste Bldg.
- 23 El.
- Southwest 20P-08 Rev. 78 Page 15 of 335 6.0 SYSTEM OPERATION 6.1 During normal operation of the Control Rod Drive Hydraulic System, the following parameters should be routinely monitored:
CRD flow rate C12-FC-R600 PanelP603 Drive water differential pressure C12-PDI-R602 PanelP603 Cooling water differential pressure C12-PDI-R603 PanelP603 Charging water pressure C12-PI-R601 PanelP603 Drive water flow rate C12-FI-R604 PanelP603 Cooling water flow rate C12-FI-R605 PanelP603 CRD temperature C12-TR-R018 Panel H21-P007 30 to 60 gpm during normal power operations; up to 199 gpm (max flow) during various other applications, such as vessel fill, accumulator charging, etc 260 to 275 psid 10 to 26 psid (may be less than 10 psid if reactor vessel temperature is less than 250°F)
Less than 1510 psig Approximately 0 gpm (flow rate < 5.0 gpm during rod movement) 30 to 60 gpm (flow rates above 50 gpm must be obtained from C12-FC-R600 on Panel P603)
Less than 250°F Pressure control valve 15 to 35 psig CO-PCV-4105 (outlet pressure)
CO-PI-4106 Radwaste Bldg. - 23' EI. - Southwest Information Use 1 20 P-08 Rev. 78 Page 15 of 3351
CAROLINA POWER & LIGHT COMPANY BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE IN PLANT NRC In-Plant I LESSON TITLE:
LEP-Ol; Alternate Coolant Injection
- SLC Pumps Using Fire Protection Water LESSON NUMBER: AOT-OJT-JP-300-J1 I REVISION NO:
03 LESSON TITLE:
CAROLINA POWER & LIGHT COMPANY BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE IN PLANT NRC In-Plant I LEP-01; Alternate Coolant Injection - SLC Pumps Using Fire Protection Water LESSON NUMBER: AOT-OJT-JP-300-J11 REVISION NO:
03
LEP-01; Alternate Coolant Injection
- SLC Pumps Using Fire Protection Water SAFETY CONSIDERATIONS 1.
Boron is a caustic substance. Avoid contact with SLC solutions and precipitated sodium pentaborate salts. A portable eyewash station is present in the area and should be verified as being ready for use PRIOR to allowing trainee to potentially contact boron.
2.
Radiation levels in this area are subject to rapid changes, especially during refuel outages.
3.
Some areas may be inaccessible during CRD Rebuild evolutions.
4.
Hearing protection may be required to access and then egress the plant locations associated with this JPM.
EVALUATOR NOTES: (Do not read to trainee) 1.
The applicable procedure section WILL be provided to the trainee. The trainee should be given a current copy of EOP-01-LEP-01, Section 1, with the applicable steps marked off as complete.
2.
If this is the first JPM of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the trainee.
3.
The trainee may desire to open the LEP Toolbox on the Reactor Building 80 elevation, near the RWCU Panel. To open this toolbox the trainee must obtain an LSV key, obtainable from the SRO or the Work Control Center, or normally carried by the duty Auxiliary Operator.
If this toolbox is opened, Operations may require the toolbox to be inventoried.
4.
All operations are conducted on the Reactor Building 80 elevation unless otherwise noted.
AOT-OJT-JP-300-J1 I Page 2 of 10 Rev. 03 LEP-01; Alternate Coolant Injection - SLC Pumps Using Fire Protection Water SAFETY CONSIDERATIONS
- 1.
Boron is a caustic substance. Avoid contact with SLC solutions and precipitated sodium pentaborate salts. A portable eyewash station is present in the area and should be verified as being ready for use PRIOR to allowing trainee to potentially contact boron.
- 2.
Radiation levels in this area are subject to rapid changes, especially during refuel outages.
- 3.
Some areas may be inaccessible during CRD Rebuild evolutions.
- 4.
Hearing protection may be required to access and then egress the plant locations associated with this JPM.
EVALUATOR NOTES: (Do not read to trainee)
- 1.
The applicable procedure section WILL be provided to the trainee. The trainee should be given a current copy of EOP-01-LEP-01, Section 1, with the applicable steps marked off as complete.
- 2.
If this is the first JPM of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the trainee.
- 3.
The trainee may desire to open the LEP Toolbox on the Reactor Building 80' elevation, near the RWCU Panel. To open this toolbox the trainee must obtain an LSV key, obtainable from the SRO or the Work Control Center, or normally carried by the duty Auxiliary Operator. If this toolbox is opened, Operations may require the toolbox to be inventoried.
- 4.
All operations are conducted on the Reactor Building 80' elevation unless otherwise noted.
AOT-OJT-JP-300-J11 Page 2 of 10 Rev. 03
LEP-Ol; Alternate Coolant Injection
- SLC Pumps Using Fire Protection Water Read the following to the trainee TASK CONDITIONS:
1.
This task is to be performed on Unit 2.
The Reactor Vessel Control Procedure, EOP-O1-RVCP, has been entered and is directing the crew to perform OEOP-O1-LEP-O1; Alternate Coolant Injection, (LEP-Ol) in order to maintain RPV water level above TAF.
3.
ALL control rods are fully inserted.
4.
The Fire Protection System is OPERABLE.
5.
SLC Pumps are available to support LEP-Ol activities.
6.
The Demineralized Water System is damaged and is NOT available for use.
INITIATING CUE:
The Unit RO has directed you to perform the AO actions associated with lining up the SLC System to inject with Fire Protection Water per LEP-Ol, Section 1, Coolant Injection With SLC Pumps.
You are to notify the Control Room when the required steps of the procedure have been completed to allow the starting of the SLC Pumps.
AOT-OJT-JP-300-J11 Page 3 of 10 Rev. 03 LEP-01; Alternate Coolant Injection - SLC Pumps Using Fire Protection Water Read the following to the trainee TASK CONDITIONS:
- 1.
This task is to be performed on Unit __.
- 2.
The Reactor Vessel Control Procedure, EOP-01-RVCP, has been entered and is directing the crew to perform OEOP-01-LEP-01; Alternate Coolant Injection, (LEP-01) in order to maintain RPV water level above TAF.
- 3.
ALL control rods are fully inserted.
- 4.
The Fire Protection System is OPERABLE.
- 5.
SLC Pumps are available to support LEP-01 activities.
- 6.
The Demineralized Water System is damaged and is NOT available for use.
INITIATING CUE:
The Unit __ RO has directed you to perform the AO actions associated with lining up the SLC System to inject with Fire Protection Water per LEP-01, Section 1, Coolant Injection With SLC Pumps.
You are to notify the Control Room when the required steps of the procedure have been completed to allow the starting of the SLC Pumps.
AOT-OJT-JP-300-J11 Page 3 of 10 Rev. 03
LEP-Ol; Alternate Coolant Injection
- SLC Pumps Using Fire Protection Water PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
NOTE:
A marked up copy of LEP-Ol, Section 1, is to be provided to the trainee.
Step 1
- Obtain marked up copy of LEP-Ol, Section 1 from Control Operator.
LEP-Ol, Section 1 obtained from the Control Operator.
SAT!UNSAT*
TIME START:
PROMPT:
IF asked, as the RO, inform the trainee that demineralized water is NOT available and fire protection water is available.
Step 2-UNLOCK and CLOSE SLC Storage Tank Outlet Isolation Valve, C41-FOO1.
SLC Storage Tank Outlet Isolation Valve, C41-FOO1, is UNLOCKED and CLOSED.
SATIU NSAT*
NOTE:
The procedure has a note that informs the trainee of the location of Fire Hose Stations on the Reactor Building 80elv. One station is on the south wall and the other station is on the north wall of the CRD Rebuild Room.
NOTE:
The trainee does not need to OPEN the LEP Toolbox, they should however explain what equipment is needed.
IF THIS TOOLBOX IS OPENED, an inventory of the toolbox may be required by Operations. The trainee will need an LSV Key for opening the toolbox which is normally carried by the duty Auxiliary Operator or is obtained from the SRO or the Work Control Center. No equipment should be removed from the toolbox for the performance of this JPM.
PROMPT:
A picture of the Fire Hose to SLC Connector is provided once obtained from the LEP toolbox Step 4
- Trainee determines which fire hose station to use.
Fire hose station is selected for use.
SATIU NSAT*
AOT-OJT-JP-300-J1 1 Page 4 of 10 Rev. 03 LEP-01; Alternate Coolant Injection - SLC Pumps Using Fire Protection Water PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
NOTE:
A marked up copy of LEP-01, Section 1, is to be provided to the trainee.
Step 1 - Obtain marked up copy of LEP-01, Section 1 from Control Operator.
LEP-01, Section 1 obtained from the Control Operator.
SATIUNSAT*
TIME START: _______ _
PROMPT:
IF asked, as the RO, inform the trainee that demineralized water is NOT available and fire protection water is available.
Step 2 - UNLOCK and CLOSE SLC Storage Tank Outlet Isolation Valve, C41-F001.
SLC Storage Tank Outlet Isolation Valve, C41-F001, is UNLOCKED and CLOSED.
SAT/UNSAT*
NOTE:
The procedure has a note that informs the trainee of the location of FireHose Stations on the Reactor Building 80'elv. One station is on the south wall and the other station is on the north wall of the CRD Rebuild Room.
NOTE:
The trainee does not need to OPEN the LEP Toolbox, they should however explain what equipment is needed. IF THIS TOOLBOX IS OPENED, an inventory of the toolbox may be required by Operations. The trainee will need an "LSV" Key for opening the toolbox which is normally carried by the duty Auxiliary Operator or is obtained from the SRO or the Work Control Center. No equipment should be removed from the toolbox for the performance of this JPM.
PROMPT:
A picture of the Fire Hose to SLC Connector is provided once obtained from the LEP toolbox Step 4 - Trainee determines which fire hose station to use.
Fire hose station is selected for use.
SAT/UNSAT*
AOT-OJT-JP-300-J11 Page 4 of 10 Rev. 03
LEP-Ol; Alternate Coolant Injection
- SLC Pumps Using Fire Protection Water Step 5
- REMOVE the fire hose nozzle for the fire hose to be used.
Fire hose nozzle removed.
- CRITICAL STEP ** SATIUNSAT*
Step 6
- CONNECT the Fire Hose to SLC Connector to the threaded connection upstream of SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014.
Fire Hose to SLC Connector connected to the piping.
- CRITICAL STEP ** SATIUNSAT*
Step 7
- CONNECT the Fire Hose to SLC Connector to the selected fire hose.
Fire hose connected to the Fire Hose to SLC Connector.
- CRITICAL STEP ** SATIUNSAT*
Step 8
- OPEN the hose reel angle valve for the fire hose.
Opens angle valve counterclockwise (to the left).
- CRITICAL STEP ** SATIUNSAT*
Step 9-UNLOCK AND OPEN SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014.
C41-F014 is open.
- CRITICAL STEP ** SATIUNSAT*
PROMPT:
IF asked, air sparging is not in progress. Or the examinee may ask the status of SLC STORAGE TANK SERVICE AIR STOP VALVE, C41-F012, at which time indicate that it is closed (or indicate that it looks as is if closed).
AOT-OJT-JP-300-J1 1 Page 5 of 10 Rev. 03 LEP-01; Alternate Coolant Injection - SLC Pumps Using Fire Protection Water Step 5 - REMOVE the fire hose nozzle for the fire hose to be used.
Fire hose nozzle removed.
- CRITICAL STEP ** SA TlUNSAT*
Step 6 - CONNECT the Fire Hose to SLC Connector to the threaded connection upstream of SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPL Y ISOLATION VALVE, C41-F014.
Fire Hose to SLC Connector connected to the piping.
- CRITICAL STEP ** SAT/UNSAT*
Step 7 - CONNECT the Fire Hose to SLC Connector to the selected fire hose.
Fire hose connected to the Fire Hose to SLC Connector.
- CRITICAL STEP ** SAT/UNSAT*
Step 8 - OPEN the hose reel angle valve for the fire hose.
Opens angle valve counterclockwise (to the left).
- CRITICAL STEP ** SAT/UNSAT*
Step 9 - UNLOCK AND OPEN SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014.
C41-F014 is open.
- CRITICAL STEP ** SAT/UNSAT*
PROMPT:
IF asked, air sparging is not in progress. Or the examinee may ask the status of SLC STORAGE TANK SERVICE AIR STOP VALVE, C41-F012, at which time indicate that it is closed (or indicate that it looks as is if closed).
AOT-OJT-JP-300-J11 Page 5 of 10 Rev. 03
LEP-Ol; Alternate Coolant Injection
- SLC Pumps Using Fire Protection Water Step 10- Notify the Control Room that the required AC actions per LEP-Ol, Section 1, are complete and that the SLC Pumps may be started.
Control Room notified that AO steps of LEP-Ol are complete and the SLC Pumps can be started.
- CRITICAL STEP ** SATIUNSAT*
TERMINATING CUE: When the Auxiliary Operator actions are complete per LEP-Ol, Section 1 to allow the Control Operator to start the SLC Pumps, this JPM is complete.
TIME STOP:
- Comments required for any step evaluated as UNSAT.
AOT-OJT-JP-300-J11 Page 6 of 10 Rev. 03 LEP-01; Alternate Coolant Injection - SLC Pumps Using Fire Protection Water Step 10 - Notify the Control Room that the required AO actions per LEP-01, Section 1, are complete and that the SLC Pumps may be started.
Control Room notified that AO steps of LEP-01 are complete and the SLC Pumps can be started.
- CRITICAL STEP ** SATIUNSAT*
TERMINATING CUE: When the Auxiliary Operator actions are complete per LEP-01, Section 1 to allow the Control Operator to start the SLC Pumps, this JPM is complete.
TIME STOP: _______ _
- Comments required for any step evaluated as UNSAT.
AOT-OJT-JP-300-J11 Page 6 of 10 Rev. 03
LEP-Ol; Alternate Coolant Injection
- SLC Pumps Using Fire Protection Water RELATED TASK:
211 006 B5 Perform Alternate Coolant Injection With SLC Pumps Per EOP-LEP-01 KIA REFERENCE AND IMPORTANCE RATING:
295031 EAI.08 3.8/3.9 Ability To Operate/Monitor Alternate Coolant Injection Systems
REFERENCES:
20P-05, Standby liquid Control System operating Procedure SD-05, Standby Liquid Control System Description OEOP-01-LEP-01, Alternate Coolant Injection Rev. 23 P&ID 9527-D-25047, Unit 1 SLC System P&ID 9527-D-2547, Unit 2 SLC System TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2)
Safety Function 2, Reactor Water Inventory Control REASON FOR REVISION:
Modified this JPM for use of the new connection piece.
AOT-OJT-JP-300-J11 Page 7 of 10 Rev. 03 LEP-01; Alternate Coolant Injection - SLC Pumps Using Fire Protection Water RELATED TASK:
211 00685 Perform Alternate Coolant Injection With SLC Pumps Per EOP-LEP-01 KIA REFERENCE AND IMPORTANCE RATING:
295031 EA 1.08 3.8/3.9 Ability To Operate/Monitor Alternate Coolant Injection Systems
REFERENCES:
20P-05, Standby liquid Control System operating Procedure SO-05, Standby Liquid Control System Description OEOP-01-LEP-01, Alternate Coolant Injection - Rev. 23 P&IO 9527-0-25047, Unit 1 SLC System P&IO 9527-0-2547, Unit 2 SLC System TOOLS AND EQUIPMENT:
None SAFETY FUNCTION (from NUREG 1123, Rev. 2)
Safety Function 2, Reactor Water Inventory Control REASON FOR REVISION:
Modified this JPM for use of the new connection piece.
AOT-OJT-JP-300-J11 Page 7 of 10 Rev. 03
LEP-Ol; Alternate Coolant Injection
- SLC Pumps Using Fire Protection Water Time required for Completion:
15 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate X
Actual
Unit:
Setting:
Control Room
Simulator_ (Not applicable to In-Plant JPMs)
Time Critical:
Yes
No X
Time Limit N/A Alternate Path:
Yes
No X
EVALUATION Trainee:_______________________________________
JPM:
Pass Fail Remedial Training Required: Yes No Did Trainee Verify Procedure?
Yes No (Each Student should verify one JPM per evaluation set.)
Comments:
Comments Reviewed With Trainee Evaluator Signature:
Date:____________
AOT-OJT-JP-300-J11 Page 8 of 10 Rev. 03 LEP-01; Alternate Coolant Injection - SLC Pumps Using Fire Protection Water Time required for Completion:
15 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate L Actual Unit:
Setting:
Control Room Simulator_ (Not applicable to In-Plant JPMs )
Time Criti.cal:
Yes No X
Time Limit N/A Alternate Path:
Yes No X
EVALUATION Trainee: ________________ _
JPM:
Pass Fail --
Remedial Training Required: Yes No __
Did Trainee Verify Procedure? Yes __ No __ _
(Each Student should verify one JPM per evaluation set.)
Comments:
Comments Reviewed With Trainee Evaluator Signature: _________________ Date: ____ _
AOT-OJT-JP-300-J11 Page 8 of 10 Rev. 03
-n
-I CDI 0
C)
CD 0
U)I C-)
CD 0
CD C,
0 Fire Hose to SLC Connector
TASK CONDITIONS:
1.
This task is to be performed on Unit 2.
The Reactor Vessel Control Procedure, EOP-O1-RVCP, has been entered and is directing the crew to perform OEOP-O1-LEP-O1; Alternate Coolant Injection, (LEP-Ol) in order to maintain RPV water level above TAR 3.
ALL control rods are fully inserted.
4.
The Fire Protection System is OPERABLE.
5.
SLC Pumps are available to support LEP-Ol activities.
6.
The Demineralized Water System is damaged and is NOT available for use.
INITIATING CUE:
The Unit RO has directed you to perform the AO actions associated with lining up the SLC System to inject with Fire Protection Water per LEP-Ol, Section 1, Coolant Injection With SLC Pumps.
You are to notify the Control Room when the required steps of the procedure have been completed to allow the starting of the SLC Pumps.
TASK CONDITIONS:
- 1.
This task is to be performed on Unit __.
- 2.
The Reactor Vessel Control Procedure, EOP-01-RVCP, has been entered and is directing the crew to perform OEOP-01-LEP-01; Alternate Coolant Injection, (LEP-01) in order to maintain RPV water level above TAF.
- 3.
ALL control rods are fully inserted.
- 4.
The Fire Protection System is OPERABLE.
- 5.
SLC Pumps are available to support LEP-01 activities.
- 6.
The Demineralized Water System is damaged and is NOT available for use.
INITIATING CUE:
The Unit __ RO has directed you to perform the AO actions associated with lining up the SLC System to inject with Fire Protection Water per LEP-01, Section 1, Coolant Injection With SLC Pumps.
You are to notify the Control Room when the required steps of the procedure have been completed to allow the starting of the SLC Pumps.
Section 1 Coolant Injection with SLC Pumps NOTE:
Manpower:
I Reactor Operator I Auxiliary Operator I Independent Verifier Special equipment:
1 LEP toolbox key 80 Rx Bldg LEP Toolbox 3 locking tabs I pipewrench I Demineralized Water to SLC Jumper Hose 1 Fire Hose to SLC Connector RO:
1.
INFORM the Unit CRS of the performance of this section.
RO:
2.
IF directed by the Unit CRS to inject with SLC pumps while aligned to the SLC storage tank, THEN GO TO Step 6, on page 7.
RO:
3.
IF it has been determined the reactor will remain shutdown under all conditions without boron, THEN CONTINUE in this procedure.
4.
IF directed to inject demineralized water, THEN PERFORM the following steps:
AO:
a.
UNLOCK AND CLOSE SLC STORAGE TANK OUTLET ISOLATION VALVE, C41-FOO1.
AO:
b.
CONNECT one end of the DEMINERALIZED WATER TO SLC JUMPER HOSE to the threaded connection at SLC DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-V5000.
AO:
c.
CONNECT the other end of the DEMINERALIZED WATER TO SLC JUMPER HOSE to the threaded connection upstream of SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014.
OEOP-0I-LEP-01 Rev. 30 Page 5 of 38 Section 1 Coolant Injection with SLC Pumps NOTE:
Manpower:
1 Reactor Operator 1 Auxiliary Operator RO:
RO:
RO:
AO:
AO:
AO:
1 Independent Verifier Special equipment:
1 LEP toolbox key
- 1.
- 2.
- 3.
- 4.
80' Rx Bldg LEP Toolbox 3 locking tabs 1 pipewrench 1 Demineralized Water to SLC Jumper Hose 1 Fire Hose to SLC Connector INFORM the Unit CRS of the performance of this section.
D IF directed by the Unit CRS to inject with SLC pumps D
while aligned to the SLC storage tank, THEN GO TO Step 6, on page 7.
IF it has been determined the reactor will remain D
shutdown under all conditions without boron, THEN CONTINUE in this procedure.
IF directed to inject demineralized water, THEN PERFORM the following steps:
- a.
UNLOCK AND CLOSE SLC STORAGE TANK D
OUTLET ISOLATION VALVE, C41-FOO1.
- b.
CONNECT one end of the DEMINERALIZED D
WATER TO SLC JUMPER HOSE to the threaded connection at SLC DEMINERALIZED WATER SUPPL Y ISOLA TlON VALVE, C41-V5000.
- c.
CONNECT the other end of the DEMINERALIZED D
WATER TO SLC JUMPER HOSE to the threaded connection upstream of SLC TEST TANK OUTLET DEMINERALIZED WA TER SUPPL Y ISOLA TlON VALVE, C41-F014.
I OEOP-01-LEP-01 Rev. 30 Page 5 of 381
Section 1 (Continued)
AC:
d.
OPEN SLC DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-V5000.
AO:
e.
UNLOCK AND OPEN SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014.
5.
IF demineralized water is NOT available AND fire protection water is available, THEN PERFORM the following:
AC:
a.
UNLOCK AND CLOSE SLC STORAGE TANK OUTLET ISOLATION VALVE, C41-FOO1.
NOTE:
Fire hose stations are located on the north wall of the CRD rebuild room and the south wall of the 80 elevation.
AO:
b.
DISCONNECT the nozzle from the fire hose selected for supplying SLC.
AO:
c.
CONNECT one end of the FIRE HOSE TO SLC CONNECTOR to the threaded connection upstream of SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014.
AO:
d.
CONNECT the other end of the FIRE HOSE TO SLC CONNECTOR to the fire hose selected in Step 5.b above.
AO:
e.
ENSURE the temporary valve on the FIRE HOSE TO SLC CONNECTOR is closed.
AC:
f.
OPEN the hose reel angle valve for the fire hose LI selected in Step 5.b above.
AO:
g.
OPEN the temporary valve on the FIRE HOSE TO SLC CONNECTOR until a stream of water issues from the valve, THEN CLOSE the temporary valve.
AO:
h.
UNLOCK AND OPEN SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014.
OEOP-01-LEP-01 Rev. 30 Page 6 of 38 Section 1 (Continued)
AO:
AO:
AO:
- d.
OPEN SLC DEMINERALIZED WATER SUPPL Y ISOLATION VALVE, C41-V5000.
- e.
UNLOCK AND OPEN SLC TEST TANK OUTLET DEMINERALIZED WA TER SUPPL Y ISOLA TlON VALVE, C41-F014.
- 5.
IF demineralized water is NOT available AND fire protection water is available, THEN PERFORM the following:
- a.
UNLOCK AND CLOSE SLC STORAGE TANK OUTLET ISOLATION VALVE, C41-F001.
D D
D NOTE:
Fire hose stations are located on the north wall of the CRD rebuild room and the south wall of the 80' elevation.
AO:
- b.
DISCONNECT the nozzle from the fire hose D
selected for supplying SLC.
AO:
- c.
CONNECT one end of the FIRE HOSE TO SLC D
CONNECTOR to the threaded connection upstream of SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014.
AO:
- d.
CONNECT the other end of the FIRE HOSE TO D
SLC CONNECTOR to the fire hose selected in Step 5.b above.
AO:
- e.
ENSURE the temporary valve on the FIRE HOSE D
TO SLC CONNECTOR is closed.
AO:
- f.
OPEN the hose reel angle valve for the fire hose D
selected in Step 5.b above.
AO:
- g.
OPEN the temporary valve on the FIRE HOSE TO D
SLC CONNECTOR until a stream of water issues from the valve, THEN CLOSE the temporary valve.
AO:
- h.
UNLOCK AND OPEN SLC TEST TANK OUTLET D
DEMINERALIZED WATER SUPPL Y ISOLA TlON VALVE, C41-F014.
IOEOP-01-LEP-01 Rev. 30 Page 6 of 381
Section 1 (Continued)
AO:
6.
IF sparging of the SLC tank is in progress, THEN CLOSE SLC STORAGE TANK SERVICE AIR STOP VALVE, C41-F012.
RO:
7.
START SLC Pumps A and B from the RTGB.
Initials 8.
WHEN SLC pumps are NOT required for coolant injection, THEN PERFORM the following:
RO:
a.
PLACE SLC PUMPS A & B, C41-CS-S1, to STOP.
AO:
b.
SECURE the fire protection water supply to SLC, if necessary.
c.
PERFORM the following for all valves that were operated:
AO:
(1)
ENSURE SLC STORAGE TANK SERVICE I
AIR STOP VALVE, C41-F012, is locked Ind.Ver.
closed.
AO:
(2)
CLOSEANDLOCKSLCTESTTANK I
OUTLET DEMINERALIZED WATER Ind.Ver.
SUPPLY ISOLATION VALVE, C41-F014.
AO:
(3)
CLOSE SLC DEMINERALIZED WATER I
SUPPLY ISOLATION VALVE, C41-V5000.
I nd.Ver.
AO:
(4)
OPENANDLOCKSLCSTORAGETANK I
OUTLET ISOLATION VALVE, C41-FOO1.
Ind.Ver.
AO:
d.
IF installed, THEN REMOVE the FIRE HOSE TO SLC CONNECTOR from the fire hose selected in Step 5.b above.
AO:
e.
IF installed, THEN REMOVE the FIRE HOSE TO I
SLC CONNECTOR from the threaded connection Ind.Ver.
upstream of SLC TEST TANK OUTLET DEMINERALIZED WATER SUPPLY ISOLATION VALVE, C41-F014, AND INSTALL the pipe cap.
OEOP-O1-LEP-O1 Rev. 30 Page 7 of 38 Section 1 (Continued)
AO:
- 6.
IF sparging of the SLC tank is in progress, THEN CLOSE D
SLC STORAGE TANK SERVICE AIR STOP VALVE, C41-F012.
RO:
- 7.
START SLC Pumps A and B from the RTGB.
D Initials
- 8.
WHEN SLC pumps are NOT required for coolant injection, THEN PERFORM the fol/owing:
RO:
- a.
PLACE SLC PUMPS A & B, C41-CS-S1, to STOP.
AO:
- b.
SECURE the fire protection water supply to SLC, if necessary.
- c.
PERFORM the fol/owing for aI/ valves that were operated:
AO:
(1 )
ENSURE SLC STORAGE TANK SERVICE
/
AIR STOP VALVE, C41-F012, is locked IndVer.
closed.
AO:
(2)
CLOSE AND LOCK SLC TEST TANK
/
OUTLET DEMINERALIZED WATER IndVer.
SUPPL Y ISOLA TlON VALVE, C41-F014.
AO:
(3)
CLOSE SLC DEMINERALIZED WATER
/
SUPPL Y ISOLA TlON VALVE, C41-V5000.
IndVer.
AO:
(4)
OPEN AND LOCK SLC STORAGE TANK
/
OUTLET ISOLATION VALVE, C41-FOO1.
Ind.Ver.
AO:
- d.
IF instal/ed, THEN REMOVE the FIRE HOSE TO SLC CONNECTOR from the fire hose selected in Step 5.b above.
AO:
- e.
IF instal/ed, THEN REMOVE the FIRE HOSE TO
/
SLC CONNECTOR from the threaded connection IndVer.
upstream of SLC TEST TANK OUTLET DEMINERALIZED WA TER SUPPL Y ISOLA TlON VALVE, C41-F014, AND INSTALL the pipe cap.
I OEOP-01-LEP-01 Rev. 30 Page 7 of 381
Section 1 (Continued)
Initials AO:
f.
IF removed, THEN INSTALL the fire hose nozzle
/
removed in Step 5.b on the fire hose used for Ind.Ver.
supplying SLC.
AO:
g.
IF Step 5.b was performed, THEN COORDINATE with Fire Protection personnel to perform an inspection of the fire hose station used for supplying SLC.
AO:
h.
IF installed, THEN REMOVE the
/
DEMINERALIZED WATER TO SLC JUMPER Ind.Ver.
HOSE and connections, AND INSTALL the pipe caps.
AO:
i.
RETURN any LEP tool box equipment to storage AND PERFORM inventory of LEP tool boxes.
RO:
j.
COORDINATE with L&RC to sample the SLC tank for proper concentration OR to refill the SLC tank in accordance with 1 (2)OP-05.
AO:
k.
INITIATE a WO to replace both squib valves.
RO:
I.
EXIT this section AND CONTINUE in this procedure at Step 2.1 on page 3.
Date/Time Completed Performed By (Print)
Initials Reviewed By:
Unit CRS/SRO OEOP-O1-LEP-O1 Rev. 30 Page 8 of 38 Section 1 (Continued)
Initials AO:
- f.
AO:
- g.
AO:
- h.
AO:
- i.
RO:
- j.
AO:
- k.
RO:
I.
\\ OEOP-01-LEP-01 IF removed, THEN INSTALL the fire hose nozzle removed in Step S.b on the fire hose used for supplying SLC.
IF Step S.b was performed, THEN COORDINATE with Fire Protection personnel to perform an inspection of the fire hose station used for supplying SLC.
IF installed, THEN REMOVE the DEMINERALIZED WATER TO SLC JUMPER HOSE and connections, AND INSTALL the pipe caps.
RETURN any LEP tool box equipment to storage AND PERFORM inventory of LEP tool boxes.
COORDINATE with E&RC to sample the SLC tank for proper concentration OR to refill the SLC tank in accordance with 1 (2)OP-OS.
INITIATE a WO to replace both squib valves.
EXIT this section AND CONTINUE in this procedure at Step 2.1 on page 3.
DatelTime Completed Performed By (Print)
Reviewed By: ______ _
Unit CRS/SRO
/
IndVer.
/
IndVer.
Initials Rev. 30 Page 8 of 38\\
PROGRESS ENERGY - CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE IN-PLANT NRC In-Plant J LESSON TITLE:
Manually transferring the Electric Fire Pump power supply and Starting the DDFP with battery failure.
LESSON NUMBER:
AOT-OJT-JP-041-A07 REVISION NO:
02 PROGRESS ENERGY - CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE IN-PLANT NRC In-Plant J LESSON TITLE:
Manually transferring the Electric Fire Pump power supply and Starting the DDFP with battery failure.
LESSON NUMBER:
AOT-OJT-JP-041-A07 REVISION NO:
02
Manually transferring the Electric Fire Pump power supply.
SAFETY CONSIDERATIONS:
Use caution in the vicinity of operating equipment.
Use caution in vicinity of energized electrical equipment.
EVALUATOR NOTES: (Do not read to trainee)
- 1. The applicable procedure section WILL be provided to the trainee.
2.
If this is the first JPM of the JPM set, read the JPM briefing contained NUREG 1021, Appendix E, or similar to the trainee.
Read the following to trainee.
TASK CONDITIONS:
1.
Off-Site Power is unavailable to either unit. DG2 is tripped, and Bus E2 is de energized, and cannot be energized by cross-tie.
2.
Buses El, E3, and E4 are energized by their respective DG5. Buses E5 and E6 have been cross-tied.
- 3. The Diesel Driven Fire Pump is unavailable.
4.
RVCP directs aligning all available alternate coolant injection per EOP-0l-LEP-01.
Reactor pressure is 10 psig.
- 5. The Electric Fire Pump is aligned to its normal power supply. The Electric Fire Pump cannot be started from the control room.
- 6. The Electric Fire Pump Normal and Alternate Feed Breakers are open and indicate off on the XU-69 panel.
7.
All applicable prerequisites listed in Section 4.0 of OP-41 are met.
INITIATING CUE:
You are directed by the Unit CO to transfer the Electric Fire Pump to its alternate power supply in accordance with OP-41 and inform the CO when your actions are complete.
AOT-OJT-JP-041-A07 Page 2 of 8 REV. 02 Manually transferring the Electric Fire Pump power supply.
SAFETY CONSIDERATIONS:
Use caution in the vicinity of operating equipment.
Use caution in vicinity of energized electrical equipment.
EVALUATOR NOTES: (Do not read to trainee)
- 1. The applicable procedure section WILL be provided to the trainee.
- 2. If this is the first JPM of the JPM set, read the JPM briefing contained NUREG 1021, Appendix E, or similar to the trainee.
Read the following to trainee.
TASK CONDITIONS:
- 1. Off-Site Power is unavailable to either unit. DG2 is tripped, and Bus E2 is de-energized, and cannot be energized by cross-tie.
- 2. Buses E1, E3, and E4 are energized by their respective DGs. Buses E5 and E5 have been cross-tied.
- 3. The Diesel Driven Fire Pump is unavailable.
- 4. RVep directs aligning all available alternate coolant injection per EOP-01-LEP-01.
Reactor pressure is 10 psig.
- 5. The Electric Fire Pump is aligned to its normal power supply. The Electric Fire Pump cannot be started from the control room.
- 5. The Electric Fire Pump Normal and Alternate Feed Breakers are open and indicate off on the XU-59 panel.
- 7. All applicable prerequisites listed in Section 4.0 of OP-41 are met.
INITIATING CUE:
You are directed by the Unit CO to transfer the Electric Fire Pump to its alternate power supply in accordance with OP-41 and inform the CO when your actions are complete.
AOT -OJT -JP-041-A07 Page 2 of 8 REV. 02
Manually transferring the Electric Fire Pump power supply.
PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1
- Obtain a current revision of OP-41, Section 8.58.
Current Revision of OP-41, Section 8.58.
SATIU NSAT*
TIME START:
PROMPT:
Inform the examinee that the switches on XU-69 are tripped and breakers indicate OFF.
Step 2 Shift the Electric Fire Pump to the alternate supply at the 2-FP-P2-XFER-SW cabinet as follows:
a.
Confirm normal transfer switch operating oil level.
Oil level is normal.
SATIUNSAT*
- b. Remove the transfer switch locking device.
Locking device removed.
CRITICAL STEP
- SATIUNSAT*
c.
Disengage position pin from position plate.
Position pin is disengaged.
CRITICAL STEP
- SATIUNSAT*
d.
Place the Transfer switch located on front of cabinet in position A.
Transfer switch located on front of cabinet placed in position A.
CRITICAL STEP
- SATIUNSAT*
AOT-OJT-JP-041-A07 Page 3 of 8 REV. 02 Manually transferring the Electric Fire Pump power supply.
PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1 - Obtain a current revision of OP-41, Section 8.58.
Current Revision of OP-41, Section 8.58.
SAT/UNSAT*
TIME START: _____ _
PROMPT:
Inform the examinee that the switches on XU-69 are tripped and breakers indicate OFF.
Step 2 - Shift the Electric Fire Pump to the alternate supply at the 2-FP-P2-XFER-SW cabinet as follows:
- a. Confirm normal transfer switch operating oil level.
Oil level is normal.
SAT/UNSAT*
- b. Remove the transfer switch locking device.
Locking device removed.
- CRITICAL STEP ** SA TlUNSAT*
- c. Disengage position pin from position plate.
Position pin is disengaged.
- CRITICAL STEP ** SAT/UNSAT*
- d. Place the Transfer switch located on front of cabinet in position A.
Transfer switch located on front of cabinet placed in position A.
- CRITICAL STEP ** SAT/UNSAT*
AOT -OJT -J P-041-A07 Page 3 of 8 REV. 02
Manually transferring the Electric Fire Pump power supply.
- e. Ensure position pin engages position plate.
Position pin engaged.
SATIU NSAT*
f.
Install the transfer switch locking device.
Locking device installed.
SATIU NSAT*
PROMPT:
When requested, Inform the examinee that the switches on XU-69 are closed and breakers indicate ON.
PROMPT:
As the SCO inform the examinee that another operator will perform Attachment Step 3 Inform CO that Fire Pump has been transferred to alternate power.
CO informed actions for fire pump are complete.
SATIUNSAT*
PROMPT:
Inform the examinee that the Electric Fire Pump has tripped when it was started.
You are directed to start the Diesel Driven Fire Pump locally.
PROMPT:
If asked for the procedure section for local start of the Diesel Driven Fire pump provide the examinee with OP41 Section 8.1. The examinee may use the local Instructional Aid which is posted at the Diesel Fire Pump and is based on OP-41, Section 8.1. Inform trainee that the prerequisites for OP-41, Section 8.1 are met and that the Fire Protection System is in operation per Section 5.1.
NOTE:
The Diesel Fire pump panel should not be opened.
It is equipped with a breakaway lock.
In the event of an emergency, the glass could also be broken to obtain access to pump controls.
Step 4
- Unlock the diesel control cabinet and place the diesel mode switch in the MAN A or MAN B position.
Diesel control cabinet unlocked and Diesel Fire Pump mode switch placed in MAN A or MAN B position.
- CRITICAL STEP ** SATIUNSAT*
AOT-OJT-JP-041-A07 Page 4 of 8 REV. 02 Manually transferring the Electric Fire Pump power supply.
- e. Ensure position pin engages position plate.
Position pin engaged.
SATIUNSAT*
- f.
Install the transfer switch locking device.
Locking device installed.
SAT/UNSAT*
PROMPT:
When requested, Inform the examinee that the switches on XU-69 are closed and breakers indicate ON.
PROMPT:
As the seo inform the examinee that another operator will perform Attachment
- 47.
Step 3 - Inform eo that Fire Pump has been transferred to alternate power.
CO informed actions for fire pump are complete.
SAT/UNSAT*
PROMPT:
Inform the examinee that the Electric Fire Pump has tripped when it was started.
You are directed to start the Diesel Driven Fire Pump locally.
PROMPT:
If asked for the procedure section for local start of the Diesel Driven Fire pump provide the examinee with OP-41 Section 8.1. The examinee may use the local Instructional Aid which is posted atthe Diesel Fire Pump and is based on OP-41,
Section 8.1. Inform trainee that the prerequisites for OP-41, Section 8.1 are met and that the Fire Protection System is in operation per Section 5.1.
NOTE:
The Diesel Fire pump panel should not.be opened. It is equipped with a breakaway lock. In the event of an emergency, the glass could also be broken to obtain access to pump controls.
Step 4 - Unlock the diesel control cabinet and place the diesel mode switch in the MAN A or MAN B position.
Diesel control cabinet unlocked and Diesel Fire Pump mode switch placed in MAN A or MAN B position.
- CRITICAL STEP ** SAT/UNSAT*
AOT-OJT-JP-041-A07 Page 4 of 8 REV. 02
Manually transferring the Electric Fire Pump power supply.
PROMPT: When the start button is depressed, indicate DDFP is NOT running as indicated by absence of noise, vibration or discharge pressure as requested. (This starts the Alternate Path for this JPM)
Step 5
- Depress and hold the manual start push button.
Manual start push button is depressed.
- CRITICAL STEP ** SAT/UNSAT*
Step 6
- Place the diesel mode switch in the MAN A or MAN B position (opposite of initially selected).
Diesel control cabinet unlocked and Diesel Fire Pump mode switch placed in MAN A or MAN B position. (Position opposite of initially selected).
- CRITICAL STEP **
SATIUNSAT*
PROMPT: If asked, inform the examinee that Diesel Fire Pump operating parameters are normal. (Normal engine parameters are: water temperature
- 165°F, oil pressure 85 psig, and engine rpm
- 1750 rpm).
PROMPT: If requested, inform examinee that another operator will monitor and control fire protection tank level.
Step 7
- Depress and hold the manual start push button until the diesel engine starts.
Diesel Fire Pump placed into operation.
- CRITICAL STEP **
SATIUNSAT*
TERMINATING CUE: Fire pump has been transferred to alternate power and the DDFP has been started locally per OP-41.
- Comments required for any step evaluated as UNSAT.
TIME COMPLETED:
AOT-OJT-JP-041-A07 Page 5 of 8 REV. 02 Manually transferring the Electric Fire Pump power supply.
PROMPT: When the start button is depressed, indicate DDFP is NOT running as indicated by absence of noise, vibration or discharge pressure as requested. (This starts. the Alternate Path for this JPM)
Step 5 - Depress and hold the manual start push button.
Manual start push button is depressed.
- CRITICAL STEP ** SA T1UNSAT*
Step 6 - Place the diesel mode switch in the MAN A or MAN B position (opposite of initially selected).
Diesel control cabinet unlocked and Diesel Fire Pump mode switch placed in MAN A or MAN B position. (Position opposite of initially selected).
- CRITICAL STEP ** SAT/UNSAT*
PROMPT: If asked, inform the examinee that Diesel Fire Pump operating parameters are normal. (Normal engine parameters are: water temperature - 165°F, oilpressure-85 psig, and engine rpm - 1750 rpm).
PROMPT: If requested, inform examinee that another operator will monitor and control fire protection tank level.
Step 7 - Depress and hold the manual start push button until the diesel engine starts.
Diesel Fire Pump placed into operation.
- CRITICAL STEP ** SATIUNSAT*
TERMINATING CUE: Fire pump has been transferred to alternate. power and the DDFP has been started locally per OP-41.
- Comments required for any step evaluated as UNSAT.
TIME COMPLETED: _____ _
AOT -OJT -J P-041-A07 Page 5 of 8 REV. 02
Manually transferring the Electric Fire Pump power supply.
RELATED TASKS:
200075B504, Perform Alternate Coolant Injection With Fire Water Per LEP-Ol KIA REFERENCE AND IMPORTANCE RATING:
286000 A1.05 3.2/
3.2 REFERENCES
OP-41 TOOLS AND EQUIPMENT:
None.
SAFETY FUNCTION (from NUREG 1123, Rev 2.):
8 Fire Protection AOT-OJT-JP-041-A07 Page 6 of 8 REV. 02 Manually transferring the Electric Fire Pump power supply.
RELATED TASKS:
2000758504, Perform Alternate Coolant Injection With Fire Water Per LEP-01 KIA REFERENCE AND IMPORTANCE RATING:
286000 A1.05 3.2/
3.2 REFERENCES
OP-41 TOOLS AND EQUIPMENT:
None.
SAFETY FUNCTION (from NUREG 1123, Rev 2.):
8 - Fire Protection AOT -OJT -J P-041-A07 Page 6 of 8 REV. 02
Manually transferring the Electric Fire Pump power supply.
Time Required for Completion:
15 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate X
Actual Unit:
0 Setting:
Control Room Simulator____ ( Not applicable to In-Plant JPMs)
Time Critical:
Yes
No X
Time Limit N/A Alternate Path:
Yes X
No EVALUATION Trainee:_______________________________________________
JPM:
Pass Fail Remedial Training Required: Yes No Comments:
Comments reviewed with Student Evaluator Signature:
Date:_____________
AOT-OJT-JP-041-A07 Page 7 of 8 REV. 02 Manually transferring the Electric Fire Pump power supply.
Time Required for Completion: ~
Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate X
Actual Unit:
o Setting:
Control Room Simulator __ ( Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit N/A Alternate Path:
Yes X
No EVALUATION Trainee:, ___________________ _
JPM:
Pass __
Fail __
Remedial Training Required: Yes No __
Comments:
Comments reviewed with Student Evaluator Signature:
AOT-OJT-JP-041-A07 Page 7 of 8 Date: ____ _
REV. 02
TASK CONDITIONS:
1.
Off-Site Power is unavailable to either unit. DG2 is tripped, and Bus E2 is de energized, and cannot be energized by cross-tie.
- 2. Buses El E3, and E4 are energized by their respective DG5. Buses E5 and E6 have been cross-tied.
- 3. The Diesel Driven Fire Pump is unavailable.
4.
RVCP directs aligning all available alternate coolant injection per EOP-0l-LEP-0l.
Reactor pressure is 10 psig.
- 5. The Electric Fire Pump is aligned to its normal power supply. The Electric Fire Pump cannot be started from the control room.
- 6. The Electric Fire Pump Normal and Alternate Feed Breakers are open and indicate off on the XU-69 panel.
7.
All applicable prerequisites listed in Section 4.0 of OP-41 are met.
INITIATING CUE:
You are directed by the Unit CO to transfer the Electric Fire Pump to its alternate power supply in accordance with OP-41 and inform the CO when your actions are complete.
TASK CONDITIONS:
- 1. Off-Site Power is unavailable to either unit. DG2 is tripped, and Bus E2 is de-energized, and cannot be energized by cross-tie.
- 2. Buses E1, E3, and E4 are energized by their respective DGs. Buses E5 and E6 have been cross-tied.
- 3. The Diesel Driven Fire Pump is unavailable.
- 4. RVCP directs aligning all available alternate coolant injection per EOP-01-LEP-01.
Reactor pressure is 10 psig.
- 5. The Electric Fire Pump is aligned to its normal power supply. The Electric Fire Pump cannot be started from the control room.
- 6. The Electric Fire Pump Normal and Alternate Feed Breakers are open and indicate off on the XU-69 panel.
- 7. All applicable prerequisites listed in Section 4.0 of OP-41 are met.
INITIATING CUE:
You are directed by the Unit CO to transfer the Electric Fire Pump to its alternate power supply in accordance with OP-41 and inform the CO when your actions are complete.
4.0 PREREQUISITES 4.1 Instrument and Service Air System in operation in accordance with OOP-46.
4.2 Plant Electric System in operation in accordance with 1 (2)OP-50.
4.3 DC Electrical System in operation in accordance with 1(2)OP-51.
4.4 12OVAC UPS, Emergency and Conventional Electrical Systems in operation in accordance with 1(2)OP-52.
4.5 Diesel Generator Emergency Power System in operation in accordance with OOP-50. 1.
4.6 AC Lighting and Communications System in operation in accordance with 1(2)OP-52.1.
4.7 Fire Protection System Electrical Lineup complete in accordance with.
4.8 Fire Protection System Panel Lineup complete in accordance with.
4.9 Fire Protection System Valve Lineup complete in accordance with.
OOP-41 Rev. 102 Page 10 of 272 4.0 PREREQUISITES 4.1 Instrument and Service Air System in operation in accordance with OOP-46.
4.2 Plant Electric System in operation in accordance with 1 (2)OP-50.
4.3 DC Electrical System in operation in accordance with 1 (2)OP-51.
4.4 120V AC UPS, Emergency and Conventional Electrical Systems in operation in accordance with 1 (2)OP-52.
4.5 Diesel Generator Emergency Power System in operation in accordance with OOP-50.1.
4.6 AC Lighting and Communications System in operation in accordance with 1 (2)OP-52.1.
4.7 Fire Protection System Electrical Lineup complete in accordance with.
4.8 Fire Protection System Panel Lineup complete in accordance with.
4.9 Fire Protection System Valve Lineup complete in accordance with.
IOOP-41 Rev. 102 Page 10 of 2721
5.0 STARTUP 5.1 Startup of Fire Protection System C
Continuous Use 5.1.1 Initial Conditions 1.
All applicable prerequisites listed in Section 4.0 are met.
2.
Fire Protection Tank level greater than 249W.
3.
Demineralized Water Tank greater than 14O.
LI 4.
The Diesel Fire Pump Fuel Oil Day Tank contains a LI minimum of 520 gallons of No. 2 fuel oil.
5.1.2 Procedural Steps NOTE:
The following actions are performed in the MWT Building.
1.
ENSURE following for the Diesel Fire Pump:
Crankcase oil level at full on dipstick Engine coolant level is visible in reservoir 2.
PLACE JOCKEY PUMP P-4 in HAND.
3.
WHEN system pressure increases to greater than LI 110 psig, THEN PLACE JOCKEY PUMP P-3 in AUTO.
4.
OPEN FIRE PUMP NORMAL FEED CIRCUIT LI BREAKER, located on Bus E2, Compt AH7.
5.
OPEN FIRE PUMP ALTERNATE FEED CIRCUIT LI BREAKER, located on Bus E4, Compt AL3.
OOP-41 Rev. 102 Page 11 of 272 5.0 STARTUP 5.1 Startup of Fire Protection System C
Continuous Use 5.1.1 Initial Conditions
- 1.
All applicable prerequisites listed in Section 4.0 are met.
D
- 2.
Fire Protection Tank level greater than 24'9%".
D
- 3.
Demineralized Water Tank greater than 14'0".
D
- 4.
The Diesel Fire Pump Fuel Oil Day Tank contains a D
minimum of 520 gallons of No.2 fuel oil.
5.1.2 Procedural Steps I NOTE:
The following actions are performed in the MWT Building.
- 1.
ENSURE following for the Diesel Fire Pump:
Crankcase oil level at full on dipstick D
Engine coolant level is visible in reservoir D
- 2.
PLACE JOCKEY PUMP P-4 in HAND.
D
- 3.
WHEN system pressure increases to greater than D
110 psig, THEN PLACE JOCKEY PUMP P-3 in AUTO.
- 4.
OPEN FIRE PUMP NORMAL FEED CIRCUIT D
BREAKER, located on Bus E2, Compt AH7.
- 5.
OPEN FIRE PUMP AL TERNA TE FEED CIRCUIT D
BREAKER, located on Bus E4, Compt AL3.
IOOP-41 Rev. 102 Page 11 of 2721
5.1.2 Procedural Steps CAUTION The Electric and Diesel Fire Pumps should NOT be started unless the system has been pressurized by the jockey pumps.
6.
PLACE Electric Fire Pump disconnect switch in ON.
7.
CLOSE FIRE PUMP NORMAL FEED CIRCUIT BREAKER, located on Bus E2 Compt AH7.
8.
CLOSE FIRE PUMP ALTERNATE FEED CIRCUIT BREAKER, located on Bus E4, Compt AL3.
9.
PLACE DIESEL FIRE PUMP MODE SWITCH in AUTO.
NOTE:
The following actions are performed from the fire protection panel in the control room.
10.
CONFIRM FIRE MONITOR ON light is ON for the following:
SBGT IA heat detection monitor SBGT 1 B heat detection monitor SBGT 2A heat detection monitor SBGT 2B heat detection monitor 11.
CONFIRM the following lights for the Electric Fire Pump are illuminated:
POWER AVAILABLE PUMP OFF 12.
CONFIRM AUTO light for Diesel Fire Pump is illuminated.
OOP-41 Rev. 102 Page 12 of 272 5.1.2 Procedural Steps CAUTION The Electric and Diesel Fire Pumps should NOT be started unless the system has been pressurized by the jockey pumps.
- 6.
PLACE Electric Fire Pump disconnect switch in ON.
D
- 7.
CLOSE FIRE PUMP NORMAL FEED CIRCUIT D
BREAKER, located on Bus E2 Compt AH7.
- 8.
CLOSE FIRE PUMP AL TERNA TE FEED CIRCUIT D
BREAKER, located on Bus E4, Compt AL3.
- 9.
PLACE DIESEL FIRE PUMP MODE SWITCH in AUTO.
D NOTE:
The following actions are performed from the fire protection panel in the control room.
- 10.
CONFIRM FIRE MONITOR ON light is ON for the following:
SBGT 1A heat detection monitor D
SBGT 1 B heat detection monitor D
SBGT 2A heat detection monitor D
SBGT 2B heat detection monitor D
- 11.
CONFIRM the following lights for the Electric Fire Pump are illuminated:
POWER AVAILABLE D
PUMP OFF D
- 12.
CONFIRM AUTO light for Diesel Fire Pump is D
illuminated.
IOOP-41 Rev. 102 Page 12 of 272/
8.0 INFREQUENT OPERATIONS R
Reference Use 8.1 Manual Starting of Diesel Fire Pump NOTE:
A local Instructional Aid is posted at the Diesel Fire Pump based on this section.
8.1.1 Initial Conditions 1.
All applicable prerequisites listed in Section 4.0 are met.
2.
Fire Protection System in operation in accordance with Section 5.1.
8.1.2 Procedural Steps CAUTION The Diesel Fire Pump has no automatic shutdowns other than diesel engine overspeed.
WHEN the engine is run during non-emergency conditions, THEN engine parameters should be monitored regularly.
1.
PLACE DIESEL FIRE PUMP MODE SWITCH in MAN A or MAN B.
NOTE:
Upon manual start, the Diesel Fire Pump should accelerate to 1750 RPM.
Do NOT attempt to regulate the manual throttle control lever (local to engine governor).
2.
DEPRESS AND HOLD MANUAL START push button until the diesel engine starts.
3.
IF the Diesel Fire Pump does NOT start on the selected battery, THEN PERFORM the following:
a.
SELECT the other battery by placing DIESEL El FIRE PUMP MODE SWITCH in MAN A or MAN B.
b.
DEPRESS AND HOLD MANUAL START push El button until the diesel engine starts.
OOP-41 Rev. 102 Page 15 of 272 8.0 INFREQUENT OPERATIONS 8.1 Manual Starting of Diesel Fire Pump NOTE:
A local Instructional Aid is posted at the Diesel Fire Pump based on this section.
8.1.1 Initial Conditions
- 1.
- 2.
All applicable prerequisites listed in Section 4.0 are met.
Fire Protection System in operation in accordance with Section 5.1.
8.1.2 Procedural Steps CAUTION D
D The Diesel Fire Pump has no automatic shutdowns other than diesel engine overspeed.
WHEN the engine is run during non-emergency conditions, THEN engine parameters should be monitored regularly.
- 1.
PLACE DIESEL FIRE PUMP MODE SWITCH in MAN A or MAN B.
D NOTE:
Upon manual start, the Diesel Fire Pump should accelerate to 1750 RPM.
Do NOT attempt to regulate the manual throttle control lever (local to engine governor).
- 2.
DEPRESS AND HOLD MANUAL START push button until the diesel engine starts.
- 3.
IF the Diesel Fire Pump does NOT start on the selected battery, THEN PERFORM the following:
- a.
- b.
SELECT the other battery by placing DIESEL FIRE PUMP MODE SWITCH in MAN A or MAN B.
DEPRESS AND HOLD MANUAL START push button until the diesel engine starts.
D D
D R
Reference Use IOOP-41 Rev. 102 Page 15 of 272/
8.1.2 Procedural Steps NOTE:
Diesel engine overspeed indication is NOT normal during starting of the Diesel Fire Pump. IF overspeed indication is present AND Diesel Fire Pump continues to run, THEN engine speed should be checked by observing local tachometer on engine panel.
4.
IF diesel engine speed exceeds 2100 RPM AND the pump is NOT needed to support an actual emergency situation, THEN STOP Diesel Fire Pump in accordance with Section 8.2.
OOP-41 Rev. 102 Page 16 of 272 8.1.2 Procedural Steps NOTE:
Diesel engine overspeed indication is NOT normal during starting of the Diesel Fire Pump. IF overspeed indication is present AND Diesel Fire Pump continues to run, THEN engine speed should be checked by observing local tachometer on engine panel.
- 4.
IOOP-41 IF diesel engine speed exceeds 2100 RPM AND the pump is NOT needed to support an actual emergency situation, THEN STOP Diesel Fire Pump in accordance with Section 8.2.
D Rev. 102 Page 16 of 272/
8.58 Transferring the Electric Fire Pump P2 Power Supply R
Reference Use 8.58.1 Initial Conditions 1.
All applicable prerequisites listed in Section 4.0 are met.
2.
The Unit SCO has determined the Electric Fire Pump power supply should be transferred.
8.58.2 Procedural Steps NOTE:
Switch position B is the normal power supply source from Bus E2, Compt AH7. Switch position A is the alternate power supply source from Bus E4, Compt AL3.
NOTE:
IF plant conditions require the transfer switch to remain in alternate power supply position A, THEN an EC tag should be used for tracking until the transfer switch is restored to normal power supply position B.
NOTE:
Steps in this section will be performed at the 2-FP-P2-XFER-SW cabinet unless otherwise noted.
NOTE:
Performance of the followings steps will mop the Electric Fire Pump.
1.
IF desired to transfer Electric Fire Pump power supply to the alternate source, THEN PERFORM the following:
a.
At Control Panel XU-69, MOMENTARILY PLACE the following switches to TRIP AND ENSURE the breaker indicates OFF:
ELECTRIC FIRE PUMP P2 ALTERNA TE LI FEED BREAKER CONTROL SWITCH (E4)
ELECTRIC FIRE PUMP P2 NORMAL FEED BREAKER CONTROL SWITCH (E2) b.
CONFIRM normal transfer switch operating oil level.
c.
REMOVE transfer switch locking device.
LI OOP-41 Rev. 102 Page 133 of 271 8.58 Transferring the Electric Fire Pump P2 Power Supply 8.58.1
- 1.
- 2.
8.58.2 Initial Conditions All applicable prerequisites listed in Section 4.0 are met.
The Unit SCO has determined the Electric Fire Pump power supply should be transferred.
Procedural Steps D
D NOTE:
Switch position B is the normal power supply source from Bus E2, Compt AH7. Switch position A is the alternate power supply source from Bus E4, Compt AL3.
NOTE:
IF plant conditions require the transfer switch to remain in alternate power supply position A, THEN an EC tag should be used for tracking until the transfer switch is restored to normal power supply position B.
NOTE:
Steps in this section will be performed at the 2-FP-P2-XFER-SW cabinet unless otherwise noted.
NOTE:
Performance of the followings steps will inop the Electric Fire Pump.
- 1.
IF desired to transfer Electric Fire Pump power supply to the alternate source, THEN PERFORM the following:
- a.
At Control Panel XU-69, MOMENTARILY PLACE the following switches to TRIP AND ENSURE the breaker indicates OFF:
ELECTRIC FIRE PUMP P2 AL TERNA TE D
FEED BREAKER CONTROL SWITCH (E4)
ELECTRIC FIRE PUMP P2 NORMAL FEED D
BREAKER CONTROL SWITCH (E2)
- b.
CONFIRM normal transfer switch operating oil D
level.
- c.
REMOVE transfer switch locking device.
D R
Reference Use IOOP-41 Rev. 102 Page 133 of 271 I
8.58.2 Procedural Steps d.
DISENGAGE position pin from position plate.
NOTE:
The position pin should be released prior to the switch reaching position A to allow the pin to engage automatically.
e.
PLACE transfer switch on front of cabinet in position A.
f.
ENSURE position pin engages position plate.
g.
INSTALL transfer switch locking device.
h.
At Control Panel XU-69, MOMENTARILY PLACE the following switches to CLOSE AND ENSURE breaker indicates ON:
ELECTRIC FIRE PUMP P2 ALTERNATE FEED BREAKER CONTROL SWITCH (E4)
ELECTRIC FIRE PUMP P2 NORMAL FEED BREAKER CONTROL SWITCH (E2) 2.
IF desired to transfer Electric Fire Pump power supply to the normal source, THEN PERFORM the following:
a.
At Control Panel XU-69, MOMENTARILY PLACE the following switches to TRIP AND ENSURE the breaker indicates OFF:
ELECTRIC FIRE PUMP P2 NORMAL FEED BREAKER CONTROL SWITCH (E2)
ELECTRIC FIRE PUMP P2 ALTERNATE FEED BREAKER CONTROL SWITCH (E4) b.
CONFIRM normal transfer switch operating oil level.
c.
REMOVE transfer switch locking device.
OOP-41 Rev. 102 Page 134 of 271 8.58.2 Procedural Steps
- d.
DISENGAGE position pin from position plate.
D NOTE:
The position pin should be released prior to the switch reaching position A to allow the pin to engage automatically.
- e.
PLACE transfer switch on front of cabinet in D
position A.
- f.
ENSURE position pin engages position plate.
D
- g.
INSTALL transfer switch locking device.
D
- h.
At Control Panel XU-69, MOMENTARILY PLACE the following switches to CLOSE AND ENSURE breaker indicates ON:
ELECTRIC FIRE PUMP P2 AL TERNA TE D
FEED BREAKER CONTROL SWITCH (E4)
ELECTRIC FIRE PUMP P2 NORMAL FEED D
BREAKER CONTROL SWITCH (E2)
- 2.
IF desired to transfer Electric Fire Pump power supply to the normal source, THEN PERFORM the following:
- a.
At Control Panel XU-69, MOMENTARILY PLACE the following switches to TRIP AND ENSURE the breaker indicates OFF:
ELECTRIC FIRE PUMP P2 NORMAL FEED D
BREAKER CONTROL SWITCH (E2)
ELECTRIC FIRE PUMP P2 AL TERNA TE D
FEED BREAKER CONTROL SWITCH (E4)
- b.
CONFIRM normal transfer switch operating oil D
level.
- c.
REMOVE transfer switch locking device.
D IOOP-41 Rev. 102 Page 134 of 271 I
8.58.2 Procedural Steps d.
DISENGAGE position pin from position plate.
NOTE:
The position pin should be released prior to the switch reaching position B to allow the pin to engage automatically.
e.
PLACE transfer switch on front of cabinet in position B.
f.
ENSURE position pin engages position plate.
g.
INSTALL transfer switch locking device.
h.
At Control Panel XU-69, MOMENTARILY PLACE the following switches to CLOSE AND ENSURE the breaker indicates ON:
ELECTRIC FIRE PUMP P2 NORMAL FEED BREAKER CONTROL SWITCH (E2)
ELECTRIC FIRE PUMP P2 ALTERNATE FEED BREAKER CONTROL SWITCH (E4) 3.
COMPLETE Attachment 47.
OOP-41 Rev. 102 Page 135 of 271 8.58.2 Procedural Steps
- d.
DISENGAGE position pin from position plate.
D NOTE:
The position pin should be released prior to the switch reaching position B to allow the pin to engage automatically.
- e.
PLACE transfer switch on front of cabinet in D
position B.
- f.
ENSURE position pin engages position plate.
D
- g.
INSTALL transfer switch locking device.
D
- h.
At Control Panel XU-69, MOMENTARILY PLACE the following switches to CLOSE AND ENSURE the breaker indicates ON:
ELECTRIC FIRE PUMP P2 NORMAL FEED D
BREAKER CONTROL SWITCH (E2)
ELECTRIC FIRE PUMP P2 AL TERNA TE D
FEED BREAKER CONTROL SWITCH (E4)
- 3.
COMPLETE Attachment 47.
D IOOP-41 Rev. 102 Page 135 of 271 I
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE IN-PLANT NRC In-Plant K LESSON TITLE:
Dual Unit Station Blackout: Energizing 2B-112B-2 Battery Chargers with SAMA Diesels (Unit 2)
LESSON NUMBER:
AOT-OJT-JP-303-13 REVISION NO:
0
.1 J
LESSON TITLE:
PROGRESS ENERGY CAROLINAS BRUNSWICK TRAINING SECTION JOB PERFORMANCE MEASURE IN-PLANT NRC In-Plant K Dual Unit Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels (Unit 2)
LESSON NUMBER: AOT-OJT-JP-303-13 REVISION NO:
0
Station Blackout: Energizing 2B-112B-2 Battery Chargers with SAMA Diesels SAFETY CONSIDERATIONS:
- 1. Standard electrical precautions when working around energized electrical equipment.
2.
Hard Hat, safety glasses, gloves and ear protection where posted.
EVALUATOR NOTES: (Do not read to trainee)
- 1. The applicable procedure section WILL be provided to the trainee.
2.
If this is the first JPM of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the trainee.
Read the following to trainee.
TASK CONDITIONS:
1.
A complete Loss of Offsite Power has occurred in both Unit 1 and Unit 2.
2.
Diesel Generators 1, 2, 3 and 4 cannot be started.
3.
SAMG Diesel Toolbox is at MCC 2CB.
4.
OAOP-36.2 section 3.2.24 has been entered and performed up to step 5.
INITIATING CUE:
You are directed by the Control Operator to complete the actions associated with aligning 2-SAMA-DIESEL-2 to Battery Chargers 2B-1/2B-2 in accordance with Section 3.2.24 steps 5 through 12.
AOT-OJT-JP-303-01 2 Page 2 of 9 Rev.0 Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels SAF.ETY CONSIDERATIONS:
- 1. Standard electrical precautions when working around energized electrical equipment.
- 2. Hard Hat, safety glasses, gloves and ear protection where posted.
EVALUATOR NOTES: (Do not read to trainee)
- 1. The applicable procedure section WILL be provided to the trainee.
- 2. If this is the first JPM of the JPM set, read the JPM briefing contained in NUREG 1021, Appendix E, or similar to the trainee.
Read the following to trainee.
TASK CONDITIONS:
- 1.
A complete Loss of Offsite Power has occurred in both Unit 1 and Unit 2.
- 2.
Diesel Generators 1, 2, 3 and 4 cannot be started.
- 3.
SAMG Diesel Toolbox is at MCC 2CB.
- 4.
OAOP-36.2 section 3.2.24 has been entered and performed up to step 5.
INITIATING CUE:
You are directed by the Control Operator to complete the actions associated with aligning 2-SAMA-DIESEL-2 to Battery Chargers 2B-1/2B-2 in accordance with Section 3.2.24 steps 5 through 12.
AOT-OJT-JP-303-012 Page 2 of 9 Rev.O
Station Blackout: Energizing 2B-112B-2 Battery Chargers with SAMA Diesels PERFORMANCE CHECKLIST NOTE: Sequence is assumed unless denoted in the Comments.
Step 1
- Obtain marked up copy of OAOP-36.2 Section 3.2.24.
Current revision of OAOP-36.2 Section 3.2.24 obtained.
SAT/UNSAT TIME START Step 2
- Ensure TRANSFER SWITCH 2-SAMA-DG2-XFER-SW is in MCC 2CB.
2CB selected
- Critical Step** SAT I UNSAT PROMPT:
Perform the following at 2-SAMA-DIESEL-2.
If asked, inform examinee that oil level is in the STOP range of the dipstick.
Step 3 Check engine oil level is in the STOP range on the dip stick.
Oil level verified in the stop region.
SAT I UNSAT PROMPT:
Perform the following at 2-SAMA-DIESEL-2. Inform the examinee that 2-SAMA-DIESEL-2-52 is as you see it.
Step 4
- Ensure SAMA DIESEL GENERATOR 2 OUTPUT BREAKER, 2-SAMA-DIESEL-2-52, is OFF.
2-SAMA-DIESEL-2-52 Output breaker off SAT I UNSAT PROMPT:
Perform the following at 2-SAMA-DIESEL-2. Inform the examinee that you hear noise from the diesel after RUN is depressed.
Step 5
- Press RUN to start the engine.
Engine is running.
Step 1 - Obtain marked up copy of OAOP-36.2 Section 3.2.24.
Current revision of OAOP-36.2 Section 3.2.24 obtained.
SAT/UNSAT TIME START ____ _
Step 2 - Ensure TRANSFER SWITCH 2-SAMA-DG2-XFER-SW is in MCC 2CB.
2CB selected
- Critical Step** SAT / UNSAT PROMPT: Perform the following at 2-SAMA-DIESEL-2. If asked, inform examinee that oil level is in the STOP range of the dipstick.
Step 3 - Check engine oil level is in the STOP range on the dip stick.
Oil level verified in the stop region.
SAT/UNSAT PROMPT: Perform the following at 2-SAMA-DIESEL-2. Inform the examinee that 2-SAMA-DIESEL-2-52 is "as you see it".
Step 4 - Ensure SAMA DIESEL GENERATOR 2 OUTPUT BREAKER, 2-SAMA-DIESEL-2-52, is OFF.
2-SAMA-DIESEL-2-52 Output breaker off SAT/UNSAT PROMPT:
Perform the following at 2-SAMA-DIESEL-2. Inform the examinee that you hear noise from the diesel after "RUN" is depressed.
Step 5 - Press RUN to start the engine.
Engine is running.
- Critical Step** SAT / UNSAT AOT-OJT-JP-303-012 Page 3 of 9 Rev.O
Station Blackout: Energizing 2B-112B-2 Battery Chargers with SAMA Diesels Step 6
- Close SAMA DIESEL GENERATOR 2 OUTPUT BREAKER, 2-SAMA-DIESEL-2-52.
2-SAMA-DIESEL-2-52 Output breaker closed (up position).
MCC 2CB, Compt. C60 closed.
C57.
MCC 2CB, compt C57 closed
C56.
MCC 2CB, compt C56 closed
- Critical Step** SAT I UNSAT NOTE:
Ensure that examinee adheres to all rules regarding fire doors when performing next step. Battery room to cable spread room door 2-CTB-DR-EL023-1 13 should be simulated tied open. Materials are located in SAMG Diesel Toolbox. Initial conditions state that the toolbox is at MCC 2CB. The SAMG Diesel Toolbox original location is in the equipment gangbox in the stairwell to the Unit I Control Room.
Step 10
- Tie open the door between 2B Battery Room and Cable Spread, 2-CTB-DR-EL023-113.
2-CTB-DR-EL023-1 13 simulated tied open.
SAT I UNSAT AOT-OJT-JP-303-012 Page 4 of 9 Rev.0 Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels Step 6 - Close SAMA DIESEL GENERATOR 2 OUTPUT BREAKER, 2-SAMA-DIESEL-2-52.
2-SAMA-DIESEL-2-52 Output breaker closed (up position).
MGG 2GB, Gompt. G60 closed.
C57.
MGG 2GB, compt G57 closed
C56.
MGG 2GB, compt G56 closed
- Critical Step** SAT I UNSAT NOTE:
Ensure that examinee adheres to all rules regarding fire doors when performing next step. Battery room to cable spread room door 2-CTB-DR-EL023-113 should be simulated tied open. Materials are located in SAMGDieselToolbox..Initial conditions state that the toolbox is at MCC 2CB. The SAMG Diesel Toolbox original location is in the equipment gang box in the stairwell to the Unit 1 Control Room.
Step 10 - Tie open the door between 2B Battery Room and Cable Spread, 2-CTB-DR-EL023-113.
2-GTB-DR-EL023-113 simulated tied open.
SAT/UNSAT AOT -OJT -J P-303-0 12 Page 4 of 9 Rev.O
Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels PROMPT:
The following steps are performed in the battery rooms (28-1). Inform the examinee that the D.C. amperes on BAT-AM-6002 indicate 30 amps.
Step 11
- Confirm the following for Battery Chargers 2B-1, D.C. AMPERES, BAT-AM-6002, indicates between 10 and 50 amps Verified to be between 10- 50 amps.
SAT I UNSAT PROMPT:
The following steps are performed in the battery rooms (2B-2). Inform the examine that the D.C. amperes on BAT-AM-6003 indicate 20 amps.
I Step 12
- Confirm the following for Battery Chargers (28-2), D.C. AMPERES, BAT-AM-6003, indicates between 10 and 50 amps Verified to be between 10- 50 amps SAT I UNSAT PROMPT: The following steps are performed in the battery rooms (28-1). Inform the examinee that the D.C. VOLTS, BAT-VM-601 1, indicates 135 volts.
Step 13
- Confirm the following for Battery Chargers 2B-1, D.C. VOLTS, BAT-VM-601 1, indicates between 130 and 140 volts Verified to be between 130
- 140 volts SAT I UNSAT PROMPT: The following steps are performed in the battery rooms (2B-2). Inform the examinee that the D.C. VOLTS, BAT-VM-6012, indicates 135 volts.
Step 14
- Confirm the following for Battery Chargers 2B-2, D.C. VOLTS, BAT-VM-6012, indicates between 130 and 140 volts Verified to be between 130
- 140 volts SAT IUNSAT AOT-OJT-JP-303-012 Page 5 of 9 Rev.0 Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels PROMPT:
The following steps are performed in the battery rooms (28~1). Inform the examinee that the D.C. amperes on BAT-AM-6002 indicate 30 amps.
Step 11 - Confirm the following for Battery Chargers 2B-1, D.C. AMPERES, BAT-AM-6002, indicates between 10 and 50 amps Verified to be between 10 - 50 amps.
SAT/UNSAT PROMPT:
The following steps are performed in the battery rooms (28-2). Inform the examinee that the D.C. amperes on BAT-AM-6003 indicate 20 amps.
Step 12 - Confirm the following for Battery Chargers (28-2), D.C. AMPERES, BAT-AM-6003, indicates between 10 and 50 amps Verified to be between 10 - 50 amps SAT/UNSAT PROMPT: The following steps are performed in the battery rooms (28-1). Inform the examinee that the D. C. VOLTS, BAT-VM-6011, indicates 135 volts.
Step 13 - Confirm the following for Battery Chargers 2B-1, D.C. VOLTS, BAT-VM-6011, indicates between 130 and 140 volts Verified to be between 130 - 140 volts SAT/UNSAT PROMPT: The following steps are performed in the battery rooms (28-2). Inform the examinee that the D.C. VOLTS, BAT-VM-6012, indicates 135 volts.
Step 14 - Confirm the following for Battery Chargers 2B-2, D.C. VOLTS, BAT-VM-6012, indicates between 130 and 140 volts Verified to be between 130 - 140 volts SAT/UNSAT AOT -OJT -JP-303-012 Page 5 of 9 Rev.O
Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels Step 15-Notify the TSC station batteries are charging using Battery Chargers 2B-1/2B-2 without battery room ventilation.
TSC notified (control room acceptable with comments)
SAT I UNSAT Termination Cue When the TSC has been notified that the battery chargers have been enerqized from the SAMA Diesels this JPM may be terminated Time completed:
- Comments required for any step evaluated as UNSAT.
AOT-OJT-JP-303-012 Page 6 of 9 Rev.O Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels Step 15 - Notify the TSC station batteries are charging using Battery Chargers 2B-1/2B-2 without battery room ventilation.
TSC notified (control room acceptable with comments)
SAT/UNSAT Termination Cue:
When the TSC has been notified that the battery chargers have been enerQized from the SAMA Diesels this JPM may be terminated.
Time completed: _____ _
- Comments required for any step evaluated as UNSAT.
AOT -OJT -J P-303-0 12 Page 6 of 9 Rev.O
Station Blackout: Energizing 2B-112B-2 Battery Chargers with SAMA Diesels LIST OF REFERENCES RELATED TASKS:
200104B404 Perform AO actions to align diesel power to the battery chargers per OAOP-36.2.
KIA REFERENCE AND IMPORTANCE RATING:
295003 AA1.02 4.2/4.3 Ability to Operate and/or Monitor Emergency Generators as it applies to a Station Blackout
REFERENCES:
OAOP-36.2, Section 3.2.21 TOOLS AND EQUIPMENT:
1.
Plant page (or) 2.
Radio 3.
SAMG tool box SAFETY FUNCTION (from NUREG 1123, Rev 2):
6 (Electrical Distribution)
REASON FOR REVISION:
New for SAMA Diesels.
AOT-OJT-JP-303-012 Page 7 of 9 Rev.0 Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels LIST OF REFERENCES RELATED TASKS:
200104B404 Perform AO actions to align diesel power to the battery chargers per OAOP-36.2.
KIA REFERENCE AND IMPORTANCE RATING:
295003 AA1.02 4.2/4.3 Ability to Operate and/or Monitor Emergency Generators as it applies to a Station Blackout
REFERENCES:
OAOP-36.2, Section 3.2.21 TOOLS AND EQUIPMENT:
- 1. Plant page (or)
- 2. Radio
- 3. SAMG tool box SAFETY FUNCTION (from NUREG 1123, Rev 2):
6 (Electrical Distribution)
REASON FOR REVISION:
New for SAMA Diesels.
AOT-OJT-JP-303-012 Page 7 of 9 Rev.O
Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels Time Required for Completion:
18 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual Unit:
2 Setting:
Control Room Simulator____ (Not applicable to In-Plant JPMs)
Time Critical:
Yes No X
Time Limit Alternate Path:
Yes No X
EVALUATION Trainee:________________________________________
JPM:
Pass Fail Remedial Training Required: Yes No Did Trainee Verify Procedure Revision?:
Yes No (Each Student should yerify one JPM per evaluation set)
Comments:
Comments reviewed with Student Evaluator Signature:
Date:______________
AOT-OJT-JP-303-012 Page 8 of 9 Rev.O Station Blackout: Energizing 2B-1/2B-2 Battery Chargers with SAMA Diesels Time Required for Completion:
18 Minutes (approximate).
APPLICABLE METHOD OF TESTING Performance:
Simulate Actual Unit:
2 Setting:
Control Room Simulator __ (Not applicable to In-Plant JPMs)
Time Critical:
Yes No L Time Limit Alternate Path:
Yes No X
EVALUATION Trainee:, ________________ _
JPM:
Pass __
Fail __
Remedial Training Required: Yes No __
Did Trainee Verify Procedure Revision?: Yes No __ _
(Each Student should verify one JPM per evaluation set.)
Comments:
Comments reviewed with Student Evaluator Signature:
Date: _____ _
AOT-OJT-JP-303-012 Page 8 of 9 Rev.O
TASK CONDITIONS:
1.
A complete Loss of Offsite Power has occurred in both Unit 1 and Unit 2.
2.
Diesel Generators 1, 2, 3 and 4 cannot be started.
3.
SAMG Diesel Toolbox is at MCC 2CB.
4.
OAOP-36.2 section 3.2.24 has been entered and performed up to step 5.
INITIATING CUE:
You are directed by the Control Operator to complete the actions associated with aligning 2-SAMA-DIESEL-2 to Battery Chargers 2B-112B-2 in accordance with Section 3.2.24 steps 5 through 12.
TASK CONDITIONS:
- 1.
A complete Loss of Offsite Power has occurred in both Unit 1 and Unit 2.
- 2.
Diesel Generators 1, 2, 3 and 4 cannot be started.
- 3.
SAMG Diesel Toolbox is at MCC 2CB.
- 4.
OAOP-36.2 section 3.2.24 has been entered and performed up to step 5.
INITIATING CUE:
You are directed by the Control Operator to complete the actions associated with aligning 2-SAMA-DIESEL-2 to Battery Chargers 2B-1/2B-2 in accordance with Section 3.2.24 steps 5 through 12.
3.2.24 Alignment of 2-SAMA-Diesel-2 to Battery Chargers 2B-112B-2 1.
OBTAIN the SAMG Diesel Toolbox from the equipment gangbox located 23 Control Building stairwell, Unit 1.
NOTE:
Cross-tying E buses is the preferred method to energize battery chargers. If cross-tying E buses is NOT possible, this section aligns the SAMA diesels to L
energize the battery chargers.
2.
CONTACT the Control Room to determine if continuing with this section is desirable.
3.
OPEN MCC 2CB, Compt A09, located on 480V Sub E8.
4.
ENSURE all breakers on MCC 2CB are off.
5.
ENSURE TRANSFER SWITCH 2-SAMA-DG2-XFER-SW is in MCC 2CB.
6.
PERFORM the following at 2-SAMA-DIESEL-2:
a.
CHECK engine oil level is in the STOP range on the dip stick.
b.
ENSURE SAMA DIESEL GENERATOR 2 OUTPUT BREAKER, 2-SAMA-DIESEL-2-52, is OFF.
c.
PRESS RUN to start the engine.
LI d.
CLOSE SAMA DIESEL GENERA TOR 2 OUTPUT BREAKER, 2-SAMA-DIESEL-2-52.
7.
CLOSE SAMA DIESEL GENERA TOR #2 SUPPLY, located on MCC 2CB, Compt. C60.
8.
CLOSE BATT CHARGER 2B-1 AC INPUT NORM FEED, located on MCC 2CB, Compt. 057.
9.
CLOSE BATT CHARGER 2B-2 AC INPUT NORM FEED, LI located on MCC 2CB, Compt. C56.
10.
TIE OPEN the door between 2B Battery Room and Cable El Spread, 2-CTB-DR-EL023-1 13.
OAOP-36.2 Rev. 41 Page 128 of 196 3.2.24
- 1.
Alignment of 2-SAMA-Diesel-2 to Battery Chargers 2B-1/2B-2 OBTAIN the SAMG Diesel Toolbox from the equipment gangbox located 23' Control Building stairwell, Unit 1.
NOTE:
Cross-tying E buses is the preferred method to energize battery chargers. If cross-tying E buses is NOT possible, this section aligns the SAMA diesels to energize the battery chargers.
- 2.
CONTACT the Control Room to determine if continuing with this section is desirable.
- 3.
OPEN MCC 2CB, Compt A09, located on 480V Sub E8.
W
- 4.
ENSURE all breakers on MCC 2CB are off.
W
- 5.
ENSURE TRANSFER SWITCH 2-SAMA-DG2-XFER-SW D
is in MCC 2CB.
- 6.
PERFORM the following at 2-SAMA-DIESEL-2:
- a.
CHECK engine oil level is in the STOP range on the D
dip stick.
- b.
ENSURE SAMA DIESEL GENERA TOR 2 OUTPUT D
BREAKER, 2-SAMA-DIESEL-2-52, is OFF.
- c.
PRESS RUN to start the engine.
D
- d.
CLOSE SAMA DIESEL GENERA TOR 2 OUTPUT D
BREAKER,2-SAMA-DIESEL-2-52.
- 7.
CLOSE SAMA DIESEL GENERA TOR #2 SUPPL Y, D
located on MCC 2CB, Compt. C60.
- 8.
CLOSE BATT CHARGER 2B-1 AC INPUT NORM FEED, D
located on MCC 2CB, Compt. C57.
- 9.
CLOSE BA TT CHARGER 2B-2 AC INPUT NORM FEED, D
located on MCC 2CB, Compt. C56.
- 10.
TIE OPEN the door between 2B Battery Room and Cable D
Spread, 2-CTB-DR-EL023-113.
IOAOP-36.2 Rev. 41 Page 128 of 1961
3.2.24 Alignment of 2-SAMA-Diesel-2 to Battery Chargers 2B-112B-2 11.
CONFIRM the following for BATTERY CHARGERS 2B-I (2B-2):
a.
D.C. AMPERES, BAT-AM-6002, indicates between 10 and 50 amps b.
D.C. AMPERES, BAT-AM-6003, indicates between 10 and 50 amps c.
D.C. VOLTS, BAT-VM-60I I, indicates between 130 and 140 volts d.
D.C. VOLTS, BAT-VM-6012, indicates between 130 and 140 volts CAUTION Batteries generate hydrogen gas when being charged.
12.
NOTIFY the TSC station batteries are charging using Battery Chargers 2B-I/2B-2 without battery room ventilation.
13.
MONITOR SAMA diesel fuel level AND REQUEST Maintenance to refuel as necessary.
END OF SECTION OAOP-36.2 Rev. 41 Page 129 of 196 3.2.24 Alignment of 2-SAMA-Diesel-2 to Battery Chargers 2B-1/2B-2
- 11.
CONFIRM the following for BA TTERY CHARGERS 2B-1 (2B-2):
- a.
O. C. AMPERES, BA T-AM-6002, indicates between D
10 and 50 amps
- b.
O. C. AMPERES, BA T-AM-6003, indicates between D
10 and 50 amps
- c.
O. C. VOL TS, BA T-VM-60 11, ind icates between 130 D
and 140 volts
- d.
O. C. VOL TS, BA T-VM-60 12, ind icates between 130 D
and 140 volts CAUTION Batteries generate hydrogen gas when being charged.
IOAOP-36.2
- 12.
NOTIFY the TSC station batteries are charging using D
Battery Chargers 2B-112B-2 without battery room ventilation.
- 13.
MONITOR SAMA diesel fuel level AND REQUEST D
Maintenance to refuel as necessary.