Chawla, Mahesh Sent:

Monday, December 14, 2009 4:02 PM To:

Alan I Hassoun; johnsonrw@dteenergy.com Cc:

Pascarelli, Robert; Goel, Vijay; Kemper, William; Mazumdar, Subinoy; Wilson, George; Morris, R. Michael; Giessner, John; Jones, Robert

Subject:

Fermi 2 - LAR to Revise Degraded Voltage Function Requirements of TS Table 3.3.8.1-1 to Reflect Undervoltage Backfit Modification - ME1477 By letter dated June 10, 2009 (Agencywide Documents Access and Management System (ADAMS)

Accession No. ML091680379), Detroit Edition (the licensee) submitted a license amendment request (LAR) for Fermi 2 nuclear plant to revise the Degraded Voltage Function in the Technical Specifications (TS) Table 3.3.8.1-1. Specifically, the proposed amendment is to add new time delay logic associated with the degraded voltage function concurrent with a loss-of-coolant accident (LOCA).

By letter dated September 16, 2009 (ML093070294), the licensee provided supplemental information in response to the staffs request dated July 27, 2009. The NRC staff has reviewed the supplemental information provided by the licensee and has determined that additional information (follow-up) is required for the evaluation of the proposed change. Please let me know if you would like to have a teleconference to discuss the following information with the NRC staff.

Follow-up RAI #1: The licensee in its letter dated September 16, 2009, in response to RAI #1, stated that the minimum offsite voltage on the Division I, 120 kV system for which large motors can start and all safety related equipment can operate continuously with Load Tap Changer (LTC) operation on Transformer SS64 is 93.3%. The minimum offsite voltage on the Division II, 345 kV system for which large motors can start and safety related equipment can operate continuously is 98.4%.

Explain how the minimum post-contingency offsite voltages are related to the voltages stated above, i.e., 93.3% at 120 kV and 98.4% at 345 kV at switchyard buses. Provide supporting data or analysis to show that the degraded voltage relay settings are adequate when the grid voltage is just above the minimum post-contingency voltage, to protect all Class 1E equipment.

Follow-up RAI #2: The licensee in its letter dated September 16, 2009, in response to RAI #1, stated that the existing ABB 27D relays will be replaced with ABB 27N relays and additional time delay relays to achieve the LOCA degraded voltage time delay logic.

Confirm that new ABB 27N relays will provide Technical Specifications (TS) Table 3.3.8.1-1 Function 2a and Function 2b of the previous 27D relays, and that Function 2c will be provided by new time-delay (TD) relays. Also, provide catalog information for these relays, including AC and DC drawings showing connections of these new relays.

Follow-up RAI #3: The licensee in its letter dated September 16, 2009, in response to RAI #1, in the discussion under the heading Time Delay for Degraded Voltage (Without LOCA), has considered start of two Residual Heat Removal (RHR) pumps, with two Core Spray pumps starting five seconds later, in each Division.

Provide the basis of considering starting of two RHR pumps, and two Core Spray pumps in each division in a non-LOCA scenario.

Follow-up RAI #4: The licensee in its letter dated September 16, 2009, in response to RAI #1, stated that the time delay for a degraded voltage with LOCA is established in pending changes to calculation DC-0919, Volume I for the new degraded voltage time delay. The time delay is selected based on the following:

a) The maximum time delay which provides load shed and Emergency Diesel Generator (EDG) breaker closure (with RHR pump motor start) at or less than 10 seconds, consistent with the accident analysis.

b) The minimum time delay that allows sequential starting of LOCA loads without separating from the offsite power supply.

Provide summary/excerpts from the dynamic analysis, which provides the worst case voltage transient profile at the safety-related buses (those provided with degraded voltage relays) following LOCA.

Preferably superimpose the characteristics of degraded voltage relays on the bus voltage transient profile to confirm that degraded voltage relays can ride through the voltage dips experienced during starting of large LOCA loads.

Follow-up RAI #5: The licensee in its letter dated September 16, 2009, in response to RAI #3b, stated that in case of degraded voltage relay tripping with 7.6 seconds to 8.4 seconds of LOCA signal, the loads will be resequenced and the RHR pump motor can re-start a minimum of one second after tripping while the motor is running.

Confirm that one second is adequate for RHR pump motor to decrease its residual voltage to less than 25% of its rated voltage (typically considered safe for restarting purpose). Also, explain the function of degraded voltage and loss of voltage relaying after the safety-related loads are shifted from offsite source to EDG.

Follow-up RAI #6: Function 2.c, Time Delay with LOCA, has been added to TS Table 3.3.8.1-1 with allowable values between 7.6 seconds and 8.4 seconds. Furthermore, the licensee stated in the September 16, 2009, letter that existing ABB 27D relays have been replaced by ABB 27N relays.

Provide calculations including the uncertainties used in the selection of the nominal trip setpoint, allowable value, as-found tolerance, and as-left tolerance for all the functions in TS Table 3.3.8.1-1 affected by the replacement of the existing ABB 27D relays by ABB 27N relays and the addition of the new relay for Function 2.c.

Follow-up RAI #7: Describe the measures to be taken to ensure that the associated instrument channel is capable of performing its specified safety functions in accordance with applicable design requirements and associated analyses. Include in your discussion information on the controls you employ to ensure that the as-left trip setting after completion of periodic surveillance is consistent with your setpoint methodology. Also, discuss the plant corrective action processes (including plant procedures) for restoring channels to operable status when channels are determined to be "inoperable" or "operable but degraded". If the controls are located in a document other than the TS, e.g., plant test procedure, describe how it is ensured that the controls will be implemented.

Mahesh Chawla Phone: 301-415-8371

Fax: 301-415-1222 mahesh.chawla@nrc.gov E-mail Properties Mail Envelope Properties ()

Subject:

Fermi 2 - LAR to Revise Degraded Voltage Function Requirements of TS Table 3.3.8.1-1 to Reflect Undervoltage Backfit Modification - ME1477 Sent Date: 12/14/2009 3:36:33 PM Received Date: 12/14/2009 4:02:00 PM From: Chawla, Mahesh Created By: Mahesh.Chawla@nrc.gov Recipients:

hassouna@dteenergy.com (Alan I Hassoun)

Tracking Status: None johnsonrw@dteenergy.com (johnsonrw@dteenergy.com)

Tracking Status: None Robert.Pascarelli@nrc.gov (Pascarelli, Robert)

Tracking Status: None Vijay.Goel@nrc.gov (Goel, Vijay)

Tracking Status: None William.Kemper@nrc.gov (Kemper, William)

Tracking Status: None Subinoy.Mazumdar@nrc.gov (Mazumdar, Subinoy)

Tracking Status: None George.Wilson@nrc.gov (Wilson, George)

Tracking Status: None R.Michael.Morris@nrc.gov (Morris, R. Michael)

Tracking Status: None John.Giessner@nrc.gov (Giessner, John)

Tracking Status: None Robert.Jones@nrc.gov (Jones, Robert)

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 19947 12/14/2009 Options

Expiration Date:

Priority: olImportanceNormal ReplyRequested: False Return Notification: False Sensitivity: olNormal Recipients received: