Degraded Voltage Setpoint As-Found Values
ML102770115
Person / Time
Site: Fermi 
(NPF-043)
Issue date: 09/27/2010
From: Hassoun A
Detroit Edison
To: Mahesh Chawla
Plant Licensing Branch III
Chawla M, NRR/DORL, 415-8371
References
Download: ML102770115 (1)


Text

From:

Alan I Hassoun [hassouna@dteenergy.com]

Sent:

Monday, September 27, 2010 11:12 AM To:

Chawla, Mahesh

Subject:

Degraded Voltage Setpoint As-Found Values As stated in our response to NRC RAI (ML102140429) question 7, the Technical Specification degraded voltage allowable values are used for the as-found acceptable values.

As an more conservative measure, the Component Engineer evaluates as-found values for drift trends and determines when a relay should be prudently replaced.

Sam Hassoun Supervisor - Nuclear Licensing Fermi 2 Nuclear Power Plant Office: 734 586-4287 Email: hassouna@dteenergy.com

      • PROPRIETARY, CONFIDENTIAL OR PRIVILEGED COMMUNICATION ***

This communication may contain proprietary, privileged or confidential information protected by law. It is solely for the use of the intended recipient named above.

Any review, dissemination, distribution, forwarding, or copying of this communication by someone other than the intended recipient, or the individual responsible for delivering this communication to the intended recipient, is prohibited. If you have received this communication in error, please immediately notify the sender via email, then destroy the original message.