ML091280263
| ML091280263 | |
| Person / Time | |
|---|---|
| Site: | Browns Ferry |
| Issue date: | 04/30/2009 |
| From: | West R Tennessee Valley Authority |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| Download: ML091280263 (172) | |
Text
, Tennessee Valley Authority, Post Office Box 2000, Decatur, Alabama 35609-2000 April 30, 2009 10 CFR 50.36a(a)(2) 10 CFR 50, Appendix I,Section IV. B.1 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Mail Stop: OWFN, P1-35 Washington, D.C. 20555-0001 In the Matter of
)
Docket Nos. 50-259 Tennessee Valley Authority
)
50-260 50-296 BROWNS FERRY NUCLEAR PLANT (BFN) - UNITS 1, 2, AND 3 - ANNUAL RADIOACTIVE EFFLUENT RELEASE (ARER) REPORT - JANUARY THROUGH DECEMBER 2008 In accordance with 10 CFR 50.36a(a)(2); 10 CFR 50, Appendix I, Section IV.B; and BFN Technical Specification (TS) 5.6.3, TVA is submitting the BFN ARER report for January through December 2008. Also, in accordance with the BFN Offsite Dose Calculation Manual (ODCM) Section 1.1.1, Action (b), and Section 1.1.2, Action (c),
TVA is providing the BFN Inoperable Radioactive Effluent Instrumentation Report. provides the Radiological Impact Assessment Report. Enclosure 2 provides the Meteorological Data Tables. Enclosure 3 is the Effluent and Waste Disposal Annual Report, and Enclosure 4 is the Inoperable Radiological Effluent Instrumentation Report. TVA revised the Offsite Dose Calculation Manual (ODCM) during calendar year 2008, as such; Enclosure 5 provides a brief description of the changes and Revision 19 of the ODCM.
AJ-oo4
U.S. Nuclear Regulatory Commission Page 2 April 30, 2009 There are no commitments contained within this letter. If you have any questions concerning this submittal, please contact Paul Sawyer, BFN Radiation Protection Manager at (256) 729-2490.
- cerely, G. GWWest Site Vice President Browns Ferry Nuclear Plant Enclosures
- 1. Radiological Impact Assessment Report
- 2. Meteorological Data Tables
- 3. Effluent and Waste Disposal Annual report
- 4. Inoperable Radiological Effluent Instrumentation Report
- 5. Revision 19 to the Offsite Dose Calculation Manual
U.S. Nuclear Regulatory Commission Page 3 April 30, 2009 Enclosures cc (w/o Enclosures):
Ms. Eva A. Brown, Project Manager U.S. Nuclear Regulatory Commission (MS 08G9)
One White Flint, North 11555 Rockville Pike Rockville, Maryland 20852-2739 Ms. Heather J. Gepford, Acting Branch Chief U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW, Suite 23T85 Atlanta, Georgia 30303-8931 NRC Resident Inspector Browns Ferry Nuclear Plant 10833 Shaw Road Athens, Alabama 35611-6970 Mr. Ronald Sanacore (w/Enclosures)
American Nuclear Insurers 95 Glastonbury Blvd.
Glastonbury, Connecticut 06033
ENCLOSURE 1 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT (BFN)
UNITS 1, 2, AND 3 RADIOLOGICAL IMPACT ASSESSMENT REPORT JANUARY THROUGH DECEMBER 2008
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008
- 1. INTRODUCTION Potential doses to the "maximum exposed individual" and the population around Browns Ferry are calculated for each quarter as required in Section 5.2 of the Offsite Dose Calculation Manual (ODCM). The methodology for determining plant releases for the reporting period used to estimate dose is specified in Sections 6 and 7 of the ODCM. Dispersion of radioactive effluents in the environment is estimated using meteorological data and river flow measured during the period. In this report, the doses resulting from releases are described and compared to limits established for Browns Ferry.
II. DOSE LIMITS The ODCM specifies limits for the release of radioactive effluents, as well as limits for doses to the general public from the release of radioactive effluents. These limits are set well below the Technical Specification limits which govern the concentrations of radioactivity and doses permissible in unrestricted areas. This ensures that radioactive effluent releases are As Low As Reasonably Achievable.
The air dose limits in areas at and beyond the Site Boundary due to noble gases released in gaseous effluents per unit are:
< 5 mrad per quarter and
< 10 mrad per year for gamma radiation.
- and -
< 10 mrad per quarter and
< 20 mrad per year for beta radiation.
The dose limits to a Member of the Public in an unrestricted area from radioiodines, radioactive materials in particulate form, and radionuclides other than noble gases with half-lives > 8 days released in gaseous effluents for each unit are:
< 7.5 mrem per quarter and
< 15 mrem per year to any organ.
The dose or dose commitment to a Member of the Public from radioactive material in liquid effluents released to unrestricted areas are:
< 1.5 mrem per quarter and
< 3 mrem per year to the total body,
- and -
< 5 mrem per quarter and
< 10 mrem per year to any organ.
The limit for the total effective dose equivalent to an individual Member of the Public inside the site boundary is:
100 mrem per year.
The EPA limits for total dose to any Member of the Public in the vicinity of a nuclear power plant, established in the Environmental Dose Standard of 40 CFR 190, are:
< 25 mrem per year to the whole body,
< 75 mrem per year to the thyroid,
- and -
< 25 mrem per year to any other organ.
El-2
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Ill. DOSE CALCULATIONS Estimated doses to Members of the Public are determined using computer models (the Gaseous Effluent Licensing Code, GELC, and the Quarterly Water Dose Assessment Code, QWATA). These models are based on guidance provided by the NRC (in Regulatory Guides 1. 109, 1.111 and 1.113) for determining the potential dose to individuals and populations living in the vicinity of the plant. The area around the plant is analyzed to determine the pathways through which the public may receive a dose. The doses calculated are a representation of the dose to a "maximum exposed individual." Some of the factors used in these calculations (such as ingestion rates) are maximum values to ensure conservative reporting data. Many of these factors are obtained from NUREG/CR-1004. The values chosen will tend to overestimate the dose. The expected dose to actual individuals is lower. The calculated doses are presented in Tables 1, 2, 3, 4, 5, 6, 7, 8, and 9.
IV. DOSES FROM AIRBORNE EFFLUENTS For airborne effluents, Members of the Public can be exposed to radiation from several sources: direct radiation from the radioactivity in the air, direct radiation from radioactivity deposited on the ground, inhalation of airborne radioactivity, ingestion of vegetation which contains radioactivity deposited from the atmosphere, and ingestion of milk and beef which contains radioactivity deposited from the atmosphere onto vegetation and subsequently consumed by milk and beef animals.
Airborne Release Points There are four monitored release points from Browns Ferry Nuclear Plant: the turbine building, the radwaste building, the reactor building, and the stack.
Releases from the turbine building are considered ground-level releases. The ground-level Joint Frequency Distribution (JFD) is derived from windspeeds and directions measured 10 meters above ground and from the vertical temperature difference between 10 and 45 meters, and are presented for each quarter in Tables 10, 11, 12, and 13.
Releases from the radwaste and reactor buildings are considered split-level releases. Portions of the release are treated as ground-level while other portions are considered elevated depending on the ratio of the vertical exit velocity to the horizontal wind speed. The split-level dispersion approach is implemented using a model that requires two complete quarterly JFDs for each effluent vent, one for the ground-level releases and one for the elevated releases. The ground-level portion of the split-level JFD is based on wind speeds and directions measured 10 meters above ground-level and from the vertical temperature difference between 10 and 45 meters. The elevated portion of the split-level JFD is based on wind speeds and direction measurements at the 45 meter level and the vertical temperature difference between 45 and 91 meters. Both of these JFDs are given for each quarter in Tables 14, 15, 16, 17, 18, 19, 20, and 21.
Releases from the stack are considered to be elevated releases. The JFDs for elevated releases are based on wind directions and wind speeds measured at 91 meters and the vertical temperature difference between 45 and 91 meters, and are given for each quarter in Tables 22, 23, 24, and 25.
EI-3
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Meteorological Data Meteorological variables at BFN are measured continuously. Measurements collected include wind speed, wind direction, and temperature at heights of 10, 45, and 91 meters above the ground. Quarterly JFDs are calculated for each release point using the appropriate levels of meteorological data. A quarterly JFD gives the percentage of the time that the wind is blowing out of a particular upwind compass sector in a particular range of wind speeds for a given stability class A through G. The wind speeds are divided into nine wind speed ranges. Calms are distributed by direction in proportion to the distribution of noncalm wind directions less than 1.6 m/s (3.5 mph). Stability classes are determined from the vertical temperature difference between two measurement levels.
The generally open terrain around BFN does not cause any significant effects on the transport and dispersion of gaseous effluents from the plant. Within 30 kilometers of BFN, the terrain is mostly gently rolling hills (30-60 meters). Between 30 and 80 kilometers the hills become larger to the north and south, and mountainous to the east and northeast. The Tennessee River/Wheeler Lake may have a minor effect on transport and dispersion in the immediate vicinity of BFN during periods of winds with a southerly component, overcast skies, and relatively high wind speeds. Also, the lower layer (10-45 meters) stability class tends to be more stable. However, during this infrequent condition, dose estimates will be conservative.
External Exposure Dose Dose calculated for maximum external air dose (gamma-air and beta-air ) are made for points at and beyond the unrestricted area boundary as described in the BFN ODCM. The highest of these doses is then selected.
Submersion Dose External doses to the skin and total body, due to submersion in a cloud of noble gases, are calculated for the nearest residence in each sector. The residence with the highest dose is then selected from all sectors.
Organ Dose Dose to an organ due to releases of airborne effluents are estimated for the inhalation, ground contamination, and ingestion pathways. The ingestion pathway is further divided into three possible contributing pathways:
ingestion of cow/goat milk, ingestion of beef, and ingestion of vegetables. Doses from applicable pathways are calculated for each receptor location identified in the most recent land use survey. To determine the maximum organ dose, the doses from the pathways are summed for each receptor. For the ingestion dose, however, only those pathways that exist for each receptor are considered in the sum, e.g., milk ingestion doses are included only for locations where milk was consumed without commercial preparation and vegetable ingestion is included only for those locations where a garden was identified. To conservatively account for beef ingestion, a beef ingestion dose equal to that for the highest unrestricted area boundary location is added to each identified receptor. For ground contamination, the dose added to the organ dose being calculated is the total body dose calculated for that location, i.e., it is assumed that the dose to an individual organ is equal to the total body dose.
The maximum organ dose, thyroid dose, and total body dose from airborne effluents are presented in Tables 1, 2, 3, and 4.
El -4
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 V. DOSES FROM LIQUID EFFLUENTS For liquid effluents, the public can be exposed to radiation from three sources: the ingestion of water from the Tennessee River, the ingestion of fish caught in the Tennessee River, and direct exposure from radioactive material deposited on the river shoreline sediment (recreation).
The concentration of radionuclides in the Tennessee River are calculated by a computer model which uses measured hydraulic data downstream of BFN. Parameters used to determine the doses are based on guidance given by the NRC (in Regulatory Guides 1.109) for maximum ingestion rates, exposure times, etc. Wherever possible, parameters used in the dose calculation are site specific. The models that are used to estimate doses, as well as the parameters input to the models, are described in detail in the BFN ODCM.
Liquid Release Points and River Data Radionuclide concentrations in the Tennessee River are calculated assuming that releases in liquid effluents are continuous. When necessary, liquid releases from BFN, located at Tennessee River Mile 294, are made through diffusers which extend into the Tennessee River. It is assumed that releases to the river through these diffusers will initially be entrained in one-fifth of the water which flows past the plant. The QWATA code makes the assumption that this mixing condition holds true until the water is completely mixed at the first downstream dam (Wheeler Dam), at Tennessee River Mile 283.0.
Doses are calculated for locations within a 50 mile radius downstream of the plant site. The maximum potential recreation dose is calculated for a location immediately downstream from the plant's release point.
The maximum exposed individual dose from ingestion of fish is assumed to be that calculated for the consumption of fish caught anywhere between the plant and the first downstream dam. The maximum exposed individual dose from drinking water is assumed to be that calculated at the nearest downstream public water supply [West Morgan - East Lawrence (WMEL)].
This could be interpreted as indicating that the maximum exposed individual, as assumed for liquid releases from Browns Ferry, is an individual who obtains all of his drinking water at WMEL, consumes fish caught from the Tennessee River between BFN and Wheeler Dam, and spends 500 hours0.00579 days <br />0.139 hours <br />8.267196e-4 weeks <br />1.9025e-4 months <br /> per year on the shoreline just downstream of the plant's release point.
Doses calculated for the maximum exposed individual due to liquid effluents for each quarter in the period are presented in Tables 5, 6, 7, and 8, along with the average river flows past the plant site for the periods.
VI. POPULATION DOSES Population doses due to airborne effluents are calculated for an estimated 778,266 persons living within a 50-mile radius of the plant site. Doses from external pathways and inhalation are based on the 50-mile human population distribution. Ingestion population doses are calculated assuming that each individual consumed milk, vegetables, and meat produced within the sector in which the individual resides.
Population doses due to liquid effluents are calculated for the entire downstream Tennessee River population.
Water ingestion population doses are calculated using actual population figures for downstream public water supplies. Fish ingestion population doses are calculated assuming that all sport fish caught in the Tennessee River are consumed by the Tennessee River population. Recreation population doses are calculated using historical recreational data on the number of shoreline visits at downstream locations.
Population doses calculated for airborne and liquid effluents are presented in Tables 1, 2, 3, 4, 5, 6, 7, and 8.
El-5
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 VII. OFFSITE DIRECT RADIATION DOSE External gamma radiation levels were measured by environmental dosimeters deployed around BFN as part of the offsite Radiological Environmental Monitoring Program (REMP). The quarterly gamma radiation levels determined from these dosimeters during this reporting period averaged approximately 12.8 mrem/quarter at onsite (at or near the site boundary) stations and approximately 10.0 mrem/quarter at offsite stations or approximately 2.8 mrem/quarter higher onsite than at offsite stations. This difference is consistent with levels measured for pre-operation and construction phases of TVA nuclear plants where the average radiation levels onsite were generally 2-6 mrem!quarter higher than the levels offsite. This may be attributable to natural variations in environmental radiation levels, earth moving activities onsite, the mass of concrete employed in the construction of the plants, or other undetermined influences.
Fluctuations in natural background dose rates and in dosimeter readings tend to mask any small increments which may be due to plant operations. Thus, there was no identifiable increase in dose rate levels attributable to direct radiation from plant equipment and/or gaseous effluents.
VIII. DOSE TO A MEMBER OF THE PUBLIC INSIDE THE SITE BOUNDARY Pursuant to ODCM section 7.7.5, a review was performed to determine the highest dose to a member of the public in the site boundary. This review assumed that onsite TVA employees engaged in work activities not associated with nuclear power electric generation were considered as members of the public.
The dose to a member of the public consists of the sum of dose commitments from effluent releases as well as any direct radiation dose. The gaseous effluent dose commitment is negligible compared to the direct radiation dose.
The direct radiation dose was determined from area environmental dosimeters located onsite. It consisted of gamma dose from the plume, ground contamination and from equipment sources (i.e., tanks, turbine shine, radioactive material storage areas, etc.). The critical location was determined to a TLD near the Livewell Center (Training Center). The direct radiation dose accounting for background and occupancy was 1.4 mrem during 2008.
The total annual dose commitment to the member of the public for 2008 is 1.4 mrem; the direct radiation dose while in the site boundary. It can be concluded that the dose limit for a member of the public inside the site boundary as specified in 10 CFR 20.1301 was not exceeded.
- El-6
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 IX. TOTAL DOSE To determine compliance with 40 CFR 190, annual total dose contributions to the maximum exposed individual from BFN radioactive effluents and all other nearby uranium fuel cycle sources are considered.
The annual dose to any organ other than thyroid for the maximum exposed individual is conservatively calculated by summing the following doses: the total body air submersion dose for each quarter, the critical organ dose (for any organ other than the thyroid) from airborne effluents for each quarter from ground contamination, inhalation and ingestion, the total body dose from liquid effluents for each quarter, the maximum organ dose (for any organ other than the thyroid) from liquid effluents for each quarter, and any identifiable increase in direct radiation dose levels as measured by the REMP. This dose is compared to the 40 CFR 190 limit for total body or any organ dose (other than thyroid) to determine compliance.
The annual thyroid dose to the maximum exposed individual is conservatively estimated by summing the following doses: the total body air submersion dose for each quarter, the thyroid dose from airborne effluents for each quarter, the total body dose from liquid effluents for each quarter, the thyroid dose from liquid effluents for each quarter, and any identifiable increase in direct radiation dose levels as measured by the REMP. This dose is compared to the 40 CFR 190 limit for thyroid dose to determine compliance.
Total dose from the fuel cycle is presented in Table 9.
El-7
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table I Doses from Airborne Effluents First Quarter Individual Doses Pathway Dose Quarterly Limit Percent of Limit Location External Gamma Air 7.8E-1 1 mrad 5 mrad
< I %
NNW/1650 meters Beta Air 2.4E-10 mrad 10 mrad
< 1%
NNW/1650 meters Submersion Total Body 4.7E-04 mrem NA NA N/2000 meters Skin 5.5E-04 mrem NA NA N/2000 meters Organ Doses Child/Bone 6.6E-03 mrem 7.5 mrem
< I %
N/2000 meters Child/Thyroid 8.3E-03 mrem 7.5 mrem
< I %
N/2000 meters Child/Total Body 6.4E-03 mrem 7.5 mrem
< 1 %
N/2000 meters 9.80E-04 Population Doses Total Body Dose Maximum Organ Dose (organ) 1.2E-02 man-rem 1.8E-02 man-rem (thyroid)
Population doses can be compared to the natural background dose for the entire 50-mile population of about 70,044 man-rem/year (based on 90 mrem/yr for natural background).
El-8
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table 2 Doses from Airborne Effluents Second Quarter Individual Doses Pathway Dose Quarterly Limit Percent of Limit Location External Gamma Air 3.8E-11 mrad 5 mrad
< 1 %
SSE/2875 meters Beta Air 1.2E-10 mrad 10 mrad
< 1%
SSE/2875 meters Submersion Total Body 1.7E-04 mrem NA NA N/2000 meters Skin 2.1 E-04 mrem NA NA N/2000 meters Organ Doses Child/Bone 1.1E-02 mrem 7.5 mrem
< I %
N/2000 meters Child/Thyroid 1.2E-02 mrem 7.5 mrem
< 1 %
N/2000 meters Child/Total Body 1.OE-02 mrem 7.5 mrem
< 1 %
N/2000 meters Population Doses Total Body Dose 3.1 E-02 man-rem Maximum Organ Dose (organ) 3.7E-02 man-rem (thyroid)
Population doses can be compared to the natural background dose for the entire 50-mile population of about 70,044 man-rem/year (based on 90 mrem/yr for natural background).
El-9
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table 3 Doses from Airborne Effluents Third Quarter Individual Doses Pathway Dose Quarterly Limit Percent of Limit Location External Gamma Air 4.6E-I1 mrad 5 mrad
< I %
S/2250 meters Beta Air I.4E-10 mrad 10 mrad
< I %
S/2250 meters Submersion Total Body 1.2E-05 mrem NA NA E/1290 meters Skin 1.4E-05 mrem NA NA E/1290 meters Organ Doses Child/Bone 7.6E-03 mrem 7.5 mrem
< I %
NNW/1791 meters Child/Thyroid 8.6E-03 mrem 7.5 mrem
< I %
NNW/1 791 meters Child/Total Body 7.4E-03 mrem 7.5 mrem
< I %
NNW/1791 meters Population Doses Total Body Dose Maximum Organ Dose (organ) 5.OE-02 man-rem 5.7E-02 man-rem (thyroid)
Population doses can be compared to the natural background dose for the entire 50-mile population of about 70,044 man-rem/year (based on 90 mrem/yr for natural background).
El-10
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table 4 Doses from Airborne Effluents Fourth Quarter Individual Doses Pathway Dose Quarterly Limit Percent of Limit Location External Gamma Air 1.5E-1 I mrad 5 mrad
< 1 %
SSW/2425 meters Beta Air 4.7E-I1 mrad 10 mrad
< I %
SSW/2425 meters Submersion Total Body 2.OE-04 mrem NA NA NNW/1639 meters Skin 2.4E-04 mrem NA NA NNW/1639 meters Organ Doses Child/ Liver 7.3E-03 mrem 7.5 mrem
< I %
NNW/1791 meters Child/Thyroid 7.8E-03 mrem 7.5 mrem
< I %
NNW/1791 meters Child /Total Body 6.4E-03 mrem 7.5 mrem
< I %
NNW/1791 meters Population Doses Total Body Dose 2.OE-02 man-rem Maximum Organ Dose (organ) 2.6E-02 man-rem (thyriod)
Population doses can be compared to the natural background dose for the entire 50-mile population of about 70,044 man-rem/year (based on 90 mrem/yr for natural background).
EI-II
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table 5 Doses from Liquid Effluents First Quarter*
Individual Doses (mrem)
Age Group Organ Dose Pathway Dose Quarterly Percent of Limit Limit Adult Total Body Fish Ingestion 1.2E-03 Recreation 1.3E-04 Water Ingestion 4.3E-05 Total 1.4E-03 1.5 mrem
< 1 %
Adult Liver Fish Ingestion 1.7E-03 Recreation 1.3E-04 Water Ingestion 5.2E-05 Total 1.9E-03 5 mrem
< I %
Child Thyroid Fish Ingestion 3.6E-07 Recreation 1.3E-04 Water Ingestion 2.9E-05 Total 1.6E-03 5 mrem
<1 %
Average Riverflow past BFN (cubic feet per second): 32513 Population Doses Total Body Dose Maximum Organ Dose (organ) 9.OE-03 man-rem 1.5E-02 man-rem (liver)
Population doses can be compared to the natural background dose for the entire 50-mile population of about 70,044 man-rem/year (based on 90 mrem/yr for natural background).
- Includes dose from abnormal releases.
EI-12
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table 6 Doses from Liquid Effluents Second Quarter*
Individual Doses (mrem)
Age Group Organ Dose Pathway Dose Quarterly Percent of Limit Limit Adult Total Body Fish Ingestion 1.1E-03 Recreation 1.7E-04 Water Ingestion 8.8E-05 Total 1.4E-03 1.5 mrem
<1 %
Teen Liver Fish Ingestion 1.7E-03 Recreation 1.7E-04 Water Ingestion 7.6E-05 Total 2.OE-03 5 mrem
< I %
Child Thyroid Fish Ingestion 1.1E-06 Recreation 1.7E-04 Water Ingestion 9.OE-05 Total 2.6E-04 5 mrem
< I %
Average Riverflow past BFN (cubic feet per second): 14255 Ponulation Doses Total Body Dose Maximum Organ Dose (organ) 1.3E-02 man-rem 1.8E-02 man-rem (liver)
Population doses can be compared to the natural background dose for the entire 50-mile population of about 70,044 man-rem/year (based on 90 mrem/yr for natural background).
- Includes dose from abnormal releases.
E1-13
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table 7 Doses from Liquid Effluents Third Quarter*
Individual Doses (mrem)
Age Group Organ Dose Pathway Dose Quarterly Percent of Limit Limit Adult Total Body Fish Ingestion 4.8E-05 Recreation 1.OE-05 Water Ingestion 2.OE-06 Total 6.OE-05 1.5 mrem
< 1 %
Teen Liver Fish Ingestion 7.3E-05 Recreation 1.OE-05 Water Ingestion 2.OE-06 Total 8.5E-05 5 mrem
< I %
Adult Thyroid Fish Ingestion 1.8E-08 Recreation I.OE-05 Water Ingestion 1.4E-06 Total 1.IE-05 5 mrem
< 1 %
Average Riverflow past BFN (cubic feet per second): 18029 Population Doses Total Body Dose Maximum Organ Dose (organ) 7.7E-04 man-rem 1.01E-03 man-rem (liver)
Population doses can be compared to the natural background dose for the entire 50-mile population of about 70,044 man-rem/year (based on 90 mrem/yr for natural background).
- Includes dose from abnormal releases.
E1-14
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table 8 Doses from Liquid Effluents Fourth Quarter*
Individual Doses (mrem)
Age Group Organ Dose Pathway Dose Quarterly Percent of Limit Limit Adult Total Body Fish Ingestion 8.5E-04 Recreation 1.OE-04 Water Ingestion 3.OE-05 Total 9.8E-04 1.5 mrem
< I %
Adult Liver Fish Ingestion 1.3E-03 Recreation 1.01E-04 Water Ingestion 3.7E-05 Total 1.4E-03 5 mrem
< I %
Adult Thyroid Fish Ingestion 3.8E-07 Recreation I.OE-04 Water Ingestion 1.4E-05 Total I.IE-04 5 mrem
< I %
Average Riverflow past BFN (cubic feet per second): 29719 Population Doses Total Body Dose 7.6E-03 man-rem Maximum Organ Dose (organ) 1.2E-02 man-rem (liver)
Population doses can be compared to the natural background dose for the entire 50-mile population of about 70,044 man-rem/year (based on 90 mrem/yr for natural background).
- Includes dose from abnormal releases.
El-15
Radiological Impact Assessment Browns Ferry Nuclear Plant January - December 2008 Table 9 Total Dose from Fuel Cycle First Second Third Fourth Dose Quarter Quarter Quarter Quarter Total Body or any Organ (except thyroid)
Total body air submersion 4.7E-04 1.7E-04 1.2E-05 2.OE-04 Critical organ dose (air) 6.6E-03 1.1E-02 7.6E-03 7.3E-03 Total body dose (liquid) 1.4E-03 1.4E-03 6.OE-05 9.8E-04 Maximum organ dose (liquid) 1.9E-03 2.OE-03 8.5E-05 1.4E-03 Direct Radiation Dose 0
0 0
0 Total 1.OE-02 1.5E-02 7.8E-03 9.9E-03 Cumulative Total Dose (mrem)
(Total body or any other organ) 4.3E-02 Annual Dose Limit (mrem) 2.5E+01 Percent of Limit
< 1%
Thyroid Dose (mrem)
Total body air submersion 4.7E-04 1.7E-04 1.2E-05 2.0E-04 Thyroid dose (airborne) 8.3E-03 1.2E-02 8.6E-03 7.8E-03 Total body dose (liquid) 1.4E-03 I.4E-03 6.OE-05 9.8E-04 Thyroid dose (liquid) 1.6E-03 2.6E-04 1.1 E-05 1.1 E-04 Direct Radiation Dose 0
0 0
0 Total 1.2E-02 1.4E-02 8.7E-03 9.1E-03 Cumulative Total Dose (Thyroid) mrem 4.3E-02 Annual Dose Limit (mrem) 7.5E+01 Percent of Limit
< 1%
El-16
ENCLOSURE 2 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT (BFN)
UNITS 1, 2, AND 3 METEOROLIGICAL DATA TABLES JANUARY THROUGH DECEMBER 2008 E2-1
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 10 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR GROUND LEVEL RELEASES FIRST QUARTER E2-2
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.094 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.614 0.236 0.567 0.142 0.047 0.000 0.000 0.000 0.000 0.000 1.606 0.047 0.047 0.000 0.000 0.000 0.000 0.283 0.000 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.520 0.189 0.236 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.047 0.142 0.236 0.945 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.094 0.047 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.236 0.283 0.047 0.000 0.000 0.000 0.897 0.283 0.803 0.142 0.047 0.047 0.000 0.047 0.236 0.283 3.354 TOTAL TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS HOURS OF VALID STABILITY OBSERVATIONS OF STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 72 71 2117 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED 6.61 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-3
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 01.000 0.000 0.000 0.000 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.094 0.047 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.189 0.047 0.000 0.000 0.000 0.000 0.000 0.236 0.189 0.094 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.614 0.189 0.047 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.283 0.142 0.047 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.047 0.094 0.425 0.472 1.323 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.236 0.094 0.094 0.425 0.000 0.000 0.000 0.000 01.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.378 0.094 0.047 0.000 0.000 0.047 0.236 0.283 0.142 0.094 0.000 0.047 0.047 0.331 0.520 0.567 2.834 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS B TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 62 60 21170 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/05/05 MEAN-WIND SPEED =
8.52 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-4
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.142 0.236 0.094 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.614 0.047 0.047 0.047 0.047 0.047 0.000 0.425 0.142 0.047 0.047 0.047 0.047 0.047 0.000 0.000 0.047 1.086 0.094 0.094 0.047 0.000 0.047 0.047 0.047 0.000 0.000 0.047 0.000 0.047 0.000 0.047 0.047 0.000 0.567 0.047 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.236 0.236 0.189 0.283 0.661 1.701 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.472 0.283 0.047 0.803 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.189 0.142 0.094 0.047 0.094 0.047 0.661 0.378 0.142 0.236 0.047 0.331 0.283 0.709 0.614 0.756 4.771 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS C TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 103 101 2117 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED =
8.16 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-5
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000
.0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.047 0.189 0.142 0.047 0.236 0.142 0.142 0.567 1.039 0.945 0.567 0.236 0.567 0.189 0.047 0.189 0.189 5.432 0.331 0.567 0.425 0.425 0.945 0.520 0.945 0.236 0.803 0.425 0.236 0.614 1.181 0.331 0.661 0.614 9.258 0.567 0.850 0.850 0.047 0.142 0.661 0.331 0.000 0.425
- 0. 142 0.189 0.094 0.897 0.897 1.134 0.425 7.652 0.189 0.425 0.378 0.000 0.000 0.189 0.000 0.000 0.047 0.094 0.000 0.094 1.086 1.559 2.976 1.559 8.597 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.661 1.039 2.692 0.803 5.243 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.283 0.472 0.000 0.756 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.047 0.000 1.275 1.984 1.701 0.709 1.228 1.559 1.842 1.275 2.220 1.228 0.709 1.370 4.015 4.204 8.172 3.590 0.094 37.081 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS D TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 803 785 2117 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL MEAN WIND SPEED =
7.69 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-6
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4.
1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.142 0.000 0.047 0.000 0.094 0.142 0.000 0.047 0.000 0.094 0.094 0.047 0.047 0.000 0.803 0.567 0.283 0.142 0.425 0.236 0.472 1.039 1.842 0.945 0.425 0.142 0.378 0.709 0.142 0.189 0.945.
8.880 0.567 0.331 0.756 0.236 0.520 0.661 0.378 0.520 2.409 0.520 0.094 0.142 0.283 0.094
- 0. 614 0.897 9.022 0.331 0.283 0.189 0.283 0.094 0.047 0.283 0.047 1.937 0.756 0.142 0.000 0.236 0.142 0.189 0 803 5.763 0.047 0.283 0.236 0.094 0.000 0.094 0.000 0.000 1.086 0.331 0.000 0.094 0.189 0.047 0.614 0.614 3.732 0.000 0.1000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.047 0.000 0.000 0.000 0.094 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.559 1.181 1.464 1.039 0.897 1.275 1.795 2.551 6.377 2.126 0.378 0.709 1.559 0.520 1.653 3.259 28.342 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS E TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS.E OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 610 600 2117 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED =
4.76 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-7
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.047 0.000 0.000 0.047 0.189 0.236 0.425 0.189 0.047 0.094 0.000 0.000 0.094 0.000 0.047 1.464 0.661 0.331 0.236 0.378 0.992 0.992 0.614 1.039 1.134 0.189 0.189 0.047 0.094 0.000 0.331 0.378 7.605 0.189 0.047 0.094 0.142 0.189 0.094 0.520 0.142 1.937 0.047 0.000 0.000 0.000 0.000 0.000 0.142 3.543 0.094 0.047 0.000 0.000 0.000 0.000 0.094 0.142 0.945 0.142 0.000 0.000 0.000 0.000 0.000 0.047 1.512 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.520 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.567 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.992 0.472 0.331 0.520 1.228 1.275 1.464 1.748 4.724 0.472 0.283 0.047 0.094 0.094 0.331 0.614 0.000 14.691 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS F TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 317 311 2117 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED =
3.37 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-8
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.094 0.000 0.094 0.331 0.283 0.142 0.000 0.047 0.047 0.000 0.047 0.094 0.094 1.323 0.236 0.047 0.283 0.189 0.094 0.000 0.425 2.598 1.512 0.000 0.047 0.000 0.000 0.094 0.047 0.094 5.668 0.047 0.000 0.047 0.047 0.000 0.047 0.142 0.236 1.086 0.000 0.000 0.000 0.000 0.000 0.000 0.047 1.701 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.236 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.236 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.283 0.047 0.378 0.331 0.094 0.142 0.897 3.118 2.976 0.000 0.094 0.047 0.000 0.142 0.142 0.236 8.928 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS G TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 195 189 2117 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED =
2.54 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-9
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 11 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR GROUND LEVEL RELEASES SECOND QUARTER E2-10
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0*.
000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.138 0.783 0.783 0.599 0.000 0.000 0.000 0.000 0.000 0.000 2.302 0.000 0.000 0.000 0.000 0.000 0.184 0.737 0.092 0.737 0.829
- 00.
322 0.276 0.046 0.000 0.000 0.000 3.223 0.138 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.230 0.046 0.046 0.092 0.737 0.230 0.092 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.230 0.184 0.138 0.737 1.703 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.322 0.184 0.184 0.783 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.368 0.184 0.046 0.000 0.000 0.184 0.875 0.875 1.519 1.427 0.322 0.414 0.599 0.645 0.368 1.013 8.840 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS A TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2172 192 192 2172 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED =
6.11 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-11
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.138 0.138 0.230 0.184 0.000 0.000 0.000 0.000 0.000 0.000 0.691 0.000 0.000 0.046 0.000 0.000 0.000 0.368 0.184 0.184 0.460 0.322
- 0. 368 0.046 0.000 0.000 0.000 1.980 0.092 0.138 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.276 0.276 0.092 0.046 0.092 1.151 0.092 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.230 0.691 0.276 0.138 1.565 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.184 0.046 0.000 0.276 0.000 0.000 0.000 0.000 0.000 0.000
- 01.
000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.184 0.184 0.138 0.000 0.000 0.000 0.506 0.322 0.414 0.737 0.322 0.691 0.599 1.013 0.368 0.230 5.709 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS B TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2172 124 124 2172 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED =
6.54 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-12
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
- NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.060 0.000 0.000 0.000 0.000 0.000 0.046 0.046 0.322 0.276 0.322 0.230 0.092 0.000 0.000 0.000 0.000 1.335 0.046 0.046 0.000 0.000 0.000 0.092 0.368 0.092 0.184 0.230 0.276 0.322 0.322 0.000 0.000 0.000 1.980 0.138 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.184 0.138 0.184 0.184 0.138 1.105-0.046 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0 000 0.000 0.000 0.000 0.092 0.414 0.230 0.230 1.105 0.000 0..000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.138 0.046 0.000 0.276 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 0 00 0.230 0.138 0.092 0.000 0.000 0.138 0.414 0.414 0.460 0.599 0.506 0.599 0.645 0.829 0.460 0.368 5.893.
TOTAL-HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS C TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2172 128 128 2172 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED =
6.03 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-13
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.046 0.000 0.000 0.000 0.000 0.322 0.276 0.276 0.276 0.322 0.506 1.473 1.335 1.703 1.519 0.875 1.335 0.552 0.276 0.092 0.276 0.460 0.506 0.460 0.276 0.368 0.599 0.691 0.322 0.737 0.967 0.276 1.105 1.427 0.599 0.460 0.184 9.438 0.460 0.322 0.092 0.000 0.046 0.046 0.046 0.000 0.046 0.092 0.000 0.414 0.921 0.645 0.322 0.276 3.729 0.276 0.599 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.783 0.691 1.151 0.829 4.512 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.276 0.368 0.092 0.829 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.138 0.000 0.000 0.138 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.519 1.703 0.875 0.599 0.737 1.151 2.210 1.657 2.486 2.624 1.151 2.993 3.775 2.624 2.394 1.657 0.092 11.418 0.000 30.157 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS D TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2172 655 655 2172 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED =
4.97 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-14
JOINT PERCENTAGE FREQUENCIES.OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.092 0.184 0.138 0.460 0.138 0.322 0.322 0.092 0.230 0.414 0.184 0.184 0.046 0.092 0.092 0.092 0.414 0.322 0.414 0.691 1.059 1.888 1.105 1.381 2.348 2.762 0.599 0.599 0.967 0.184 0.184 0.599 0.414 0.368 0.184 0.184 0.460 1.105 0.414 0.046 0.737 0.552 0.046 0.368 0.184 0.000 0.230 0.552 5.847 0.368 0.276 0.230 0.184 0". 000 0.322 0.046 0.000 0.645 0.230 0.000 0.138 0.000 0.092 0.322 0.276 3.131 0.046 0.092 0.046 0.000 0.000 0.000 0.046 0.000 0.138 0.046 0.000 0.092 0.138 0.184 0.322 0.322 1.473 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.335 1.243 1.013 1.519 1.657 3.637 1.934 1.519 4.098 4.006 0.829 1.381 1.335 0.552 1.151 1.842 3.085 15.5i6 0.000 29.052 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS E TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2172 631 631 2172 0
METEOROLOGICAL FACILITY:
Browns Ferry-Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT' 10.50 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED =
3.36 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-15
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.005 0.004 0.003 0.006 0.006 0.005 0.002 0.002 0.005 0.003 0.000 0.001 0.001 0.000 0.002 0.006 0.046 18.5-24.4
>=24.5 TOTAL 0.092 0.322 0.276 0.460 0.138 0.322 0.230 0.046 0.230 0.184 0.000 0.046 0.000 0.000 0.092 0.184 2.624 0.829 0.322 0.184 0.552 0.875 0.506 0.092 0.322 0.599 0.276 0.046 0.046 0.092 0.000 0.230 0.829 5.801 0.414 0.092 0.000 0.230 0.322 0.092 0.092 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.092 1.427 0.000 0.000
- 0. 092 0.000 0.046 0.000 0.000 0.000 0.230 0.000 0.000 0.000 0.000 0.000 0.046 0.046 0.460 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.340 0.740 0.555 1.249 1.387 0.925 0.416 0.370 1.110 0.509 0.046 0.093 0.093 0.092 0.370 1.157 10.451 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS F TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2172 227 227 2172 1
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED =
2.53 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-16
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 1. 013 0.460 0.092 0.276 0.184 0.092 0.138
- 0. 092 0.138 0.000 0.000 0.046 0.000 0.000 0.230 1.473 4.236 1.381 0.921 0.599 0.645 0.460 0.138 0.092 0.046 0.046 0.000 0.000 0.000 0.046 0.000 0.046 0.506 4.926 0.368 0.046 0.000 0.092
- 0. 138 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.737 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0. 000 2.762 1.427 0.691 1.013 0.783 0.230 0.230 0.138
- 0. 184 0.000 0.000 0.046 0.046 0.000 0.276 2.072 9.899 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS G TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2172 215 215 2172 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED =
1.86 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-17
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 12 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR GROUND LEVEL RELEASES THIRD QUARTER E2-18
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0'.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.097 0.872 0.727 0.097 0.145 0.000 0.000 0.000 0.000 0.000 2.035 0.048 0.048 0.000 0.000
- 0. 145 0.388 0.969 0.824 0.630 0.339 0.388 0.484 0.339 0.097 0.048
- 0. 145
- 4. 893 0.048 0.048 0.000 0.048 0.048 0.484 0.097 0.000 0.000 0.000 0.000 0.04-8 0.630 0.388 0.097 0.097 2.035 0.581 0.291 0.194 0.097 0.000 0.145 0.000 0.000 0.000 0.000 0.000 0.000 0.194 0.291 0.242 0.581 2.616 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0, 000 0.000 0.000 0.000 0.000 0.048 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000.
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.678 0.388 0.242 0.145 0.194
- 1. 114 1.163 1.696 1.357 0.436 0.533 0.533 1.163 0.775 0.388 0.872 0.000 11.676 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS A TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 241 241 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
5.53 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-19
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.145 0.388 0.242 0.291 0.145 0.048 0.048 0.048 0.048 0.000 1.453 0.194 0.145 0.000 0.097 0.048 0.339 0.194 0.291 0.048 0.291 0.194 0.339 0.436 0.000 0.097 0.048 2.762 0.048 0.242 0.097 0.048 0.000 0.194 0.000 0.000 0.000 0.000 0.000 0.000 0.194 0.291 0.048 0.000 1.163 0.097 0.048 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.194 0.097 0.097 0.678 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.339 0.436 0.194 0.145 0.048 0.581 0.339 0.678 0.291 0.581 0.339 0.388 0.727 0.533 0.339 0.145 6.105 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS B TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 126 126 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
4.97 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-20
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY-WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.097 0.242 0.291 0.484 0.339 0.145 0.097 0.000 0.000 0.000 0.097 1.841 0.097
- 0. 194 0.145 0.048 0.000 0.388 0.000 0.000 0.048 0.048 0.291 0.339 0.484 0.242 0.048 0.097 2.471 0.242 0.097 0.048 0.097 0.097 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.291 0.145 0.000 0.097 1.211 0.097 0.048 0.000 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.145 0.145 0.048 0.581 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.0.00 0.000
.0.000*
0.000 0.436 0.339 0.194 0.291 0.097 0.581 0.242 0.291 0.533 0.388 0.436 0.436 0.775 0.533 0.194 0.388 6.153 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS C TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 127 127 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
4.77 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-21
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.000 0.048 0.097 0.000 0.048 0.000 0.048 0.000 0.048 0.339 0.291 0.145 0.388 0.194 0.436 1.163 0.727 1.114 1.114 1.114 1.647 1.114 0.145 0.194 0.145 0.533 0.436 0.339 0.581 0.727 1.550 0.048 0.145 0.048 0.436 0.194 0.678 1.308 0.436 0.242 0.436 8.140 0.533 0.145 0.727 0.339 0.242 1.260 0.000 0.000 0.000 0.145 0.000 0.000 0.727 0.727 0.484 1.066 6.395 0.048 0.097 0.145 0.194 0.000 0.097 0.000 0.000 0.000 0.048 0.000 0.000 0.145 0.242 0.388 0.291 1.696 0.000 0.000 0.242 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.291 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.453 0.969 1.599 1.550 1.163 3.343 1.308 0.872 1.211 1.841 1.308 2.374 3.295 1.599 1.308 1.986 27.180 0.388 10.271 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL.HOURS OF STABILITY CLASS D TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 561 561 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
4.47 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-22
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2009 -
SEP 30, 200B WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.145 0.097 0.097 0.145 0.145 0.097 0.242 0.000 0.097 0.097 0.048 0.048 0.000 0.194 0.533 0.727 0.242 0.678 1.793 1.211 0.678 0.533 0.581 0.824 0.678 1.017 0.872 0.242 0.194 0.388 0.630 0.484 0.242 0.581 2.132 1.502 0.048 0.000 0.048 0.000 0.000 0.194 0.872 0.000 0.242 0.727 7.703 0.194 0.242 0.242 0.291 0.242 0.921 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.048 0.048 0.339 2.665 0.000 0.000
- 0. 145 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048
- 0. 097 0.145 0.484 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0._000 0.000 0.000 0.000 1.357 1.550 1.017 1.696 4.264 3.779 0.872 0.630 0.872 0.824 0.775 1.308 1.890 0.388 0.581 1.841 SUBTOTAL 1.550 11.192 0.000 23.643 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS E TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 488 488 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
3.55 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-23
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.145 0.388 0.388 0.145 0.242 0.000 0.097 0.048 0.048 0.048 0.097 0.000 0.000 0.048 0.097 0.242 2.035 1.405 0.775 0.436 0.921 0.969 0.388 0.291 0.048 0.000 0.097 0.145 0.097 0.097 0.097 0.048 1.114 6.928 0.630 0.533 0.339 0.484 0.824 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.097 0.484 3.537 0.145 0.145 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.388 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.326 1.841 1.260 1.550 2.035 0.436 0.388 0.097 0.048 0.145 0.242 0.097 0.145 0.291 0.242 1.841 0.000 12.984 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS F TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 268 268 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
2.89 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-24
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 1.405 0.775 0.339 0.048 0.048 0.048 0.000 0.000 0.048 0.000 0.000 0.097 0.048 0.048 0.097 1.163 4.167 2.665 0.824 0.581 0.727 0.000 0.048 0.000 0.000 0.048 0.000 0.000 0.000 0.048 0.000 0.048 0.533 5.523 1.696 0.339 0.048 0.097 0.145 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.145 2.471 0.048 0.000 0.000 0.048 0.000 0.000 0.000 0.000.
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5.814 1.938 0.969 0.921 0.194 0.097 0.000 0.000 0.097 0.000 0.000 0.097 0.097 0.048 0.145 1.841 0.000 12.258 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS G TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 253 253 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
2.31 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-25
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 13 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR GROUND LEVEL RELEASES FOURTH QUARTER E2-26
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.273 0.409 0.364
- 0. 136 0.000 0.000 0.000 0.000 0.000 0.000 1.182 0.000 0.000 0.000 0.000 0.000 0.091 0.818 0.500 0.364 0.182 0.000 0.000 0.000 0.000 0.000 0.000 1.955 0.000 0.000 0.000 0.000 0.000 0.136 0.136 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.318
- 0. 682 0.091 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.045 0.000 0.318 1.227 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.045 0.045 0.182 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.727 0.091 0.000 0.000 0.000 0.273 1.227 0.909 0.773 0.318 0.000 0.000 0.045 0.091 0.045 0.364 4.864 TOTAL TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS HOURS OF VALID STABILITY OBSERVATIONS OF STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 107 107 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED =
5.84 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-27
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.045 0.000 0.136 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.227 0.000 0.000 0.000 0.045 0.136 0.091 0.227 0.227
- 0. 182 0.045 0.091 0.000 0.045 0.000 0.000 0.000 1.091 0.000 0.364 0.000 0.000 0.045 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.455 0.227 0.091 0.045 0.000 0.000 0.091 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.273 0.318 1.091 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.227 0.045 0.318 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.227 0.500 0.045 0.045
- 0. 182 0.227 0.273 0.227 0.364 0.045 0.091 0.000 0.045 0.045 0.500 0.364 3.182 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS B TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 70 70 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED =
7.33 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-28
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.091 0.409 0.227 0.045 0.045 0.000 0.000 0.000 0.000 0.000 0.818 0.182 0.045 0.000 0.000 0.000 0.136 0.500 0.000 0.136 0.045 0.000 0.045 0.045 0.000 0.000 0.000 1.136 0.091 0.182 0.045 0.000 0.000 0.136 0.000 0.000 0.000 0.000 0.000 0.045 0.091 0.045 0.045 0.045 0.727 0.182 0.364 0.045 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.045 0.045 0.227 0.273 0.364 1.591 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.182 0.000 0.182 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.455 0.591 0.091 0.000 0.000 0.318 0.591 0.409 0.364 0.091 0.045 0.136 0.182 0.273 0.500 0.409 4.455 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS C TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 98 98 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED =
6.56 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-29
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.091 0.045 0.091 0.091 0.000 0.000 0.000 0.000 0.000 0.000 0.318 0.182 0.136 0.182 0.091 0.227 0.727 1.136 1.091 1.091 0.409 0.455 0.455 0.227 0.136 0.182 0.091 6.818 0.455 0.455 0.455 0.364 0.455 0.545 0.409 0.636 0.273 0.091 0.091 0.636 0.636 0.318 0.409 0.364 6.591 0.818 0.545 0.409 0.091 0.000 1.409 0.227 0.000 0.136 0.000 0.000 0.500 0.955 0.409 0.273 0.318 6.091 0.955 0.364 0.136 0.000 0.000 0.455 0.045 0.000 0.045 0.000 0.000 0.000 0.591 1.136 1.773 1.636 7.136 0.227 0.091 0.091 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.500 0.773 0.409 2.091 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.182 0.000 0.182 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.636 1.591 1.273 0.545 0.682 3.136 1.909 1.773 1.636 0.591 0.545 1.591 2.409 2.500 3.591 2.818 0.000 29.227 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS D TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 643 643 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED =
6.45 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-30
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.091 0.045 0.182 0.091 0.182 0.455 0.545 0.409 0.091 0.091 0.318 0.045 0.045 0.000 0.000 0.045 0.409 0.364 0.591 0.500 0.955 1.545 1.091 1.227 0.955 0.409 0.500 0.682 0.364 0.182 0.136 0.273 0.500 0.500 0.500 0.364 0.727 1.545 0.455 0.545 0.500 0.136 0.045 0.182 0.455 0.227 0.273 0.318 7.273 0.500 0.273 0.409 0.136 0.000 1.409 0.045 0.045 0.227 0.136 0.000 0.136 0.364 0.182 0.273 0.727 4.864 0.045 0.000 0.182 0.000 0.000 0.273 0.000 0.000 0.182 0.091 0.000 0.000 0.091 0.136 0.545 1.273 2.818 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.182 0.045 0.318 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.591 1.182 1.864 1.091 1.864 5.227 2.136 2.227 1.955 0.864 0.864 1.045 1.318 0.773 1.409 2.682 2.636 10.182 0.000 28.091 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS E TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS TOTAL HOURS CALM METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL MEAN WIND SPEED =
4.28 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS 2200 618 618 2200 0
DATE PRINTED: 2009/03/04 E2-31
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 N
NNE NE ENE E
WNW NW NNW CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 12.5-18.4 18.5-24.4
>=24.5 TOTAL 0.045 0.091 0.182 0.227 0.182 0.227 0.273 0.182 0.273 0.045 0.000 0.000 0.045 0.000 0.000 0.045 1.818 0.727 0.636 0.591 0.545 1.045 0.409 1.000 1.227 0.545 0.227 0.136 0.091 0.045 0.000 0.045 0.500 7.773 0.636 1.182 0.136 0.318 0.773 0.136 0.136 0.545 0.273 0.000 0.000 0.000 0.000 0.000 0.000 0.682 4.818 0.000 0.045 0.000 0.045 0.000 0.000 0.045 0.000 0.455 0.000 0.000 0.000 0.000 0.000 0.045 0.182 0.818 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.227 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.273 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.409 1.955 0.909 1.136 2.000 0.773 1.455 1.955 1.773 0.318 0.136 0.091 0.091 0.000 0.091 1.409 SUBTOTAL 0.000 15.500 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS F TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 341 341 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED =
3.13 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-32
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION
- N NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.010 0.010 0.007 0.005 0.002 0.001 0.002 0.002 0.001 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.045 1.318 1.955 1.000 0.318 0.182 0.318 0.091 0.182 0.091 0.000 0.000 0.000 0.000 0.045 0.136 0.364 6.000 1.545 0.955 1.136 1.091 0.500 0.091 0.409 0.500 0.227 0.000 0.000 0.000 0.000 0.000 0.000 0.591 7.045 0.364 0.318 0.045 0.136 0.045 0.000 0.091 0.136 0.227 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.364 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.227 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.227 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.237 3.237 2.189 1.550 0.730 0.411 0.593 0.821 0.774 0.000 0.000 0.000 0.000 0.046 0.137 0.958 0.000 14.682 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS G TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 323 323 2200 1
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND SPEED AND DIRECTION MEASURED AT 10.50 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED =
1.98 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-33
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 14 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR SPLIT LEVEL RELEASES (GROUND LEVEL PORTION)
FIRST QUARTER E2-34
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JAN 1,
2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.011 0.002 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.014 0.000 0.000 0.000 0.000 0.000 0.000 0.109 0.030 0.076 0.011 0.007 0.000 0.000 0.000 0.000 0.000 0.233 0.004 0.003 0.000 0.000 0.000 0.000
- 0. 074 0.000 0.026 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.107 0.030 0.030 0.008 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.010 0.000 0.008
- 0. 024 0.040 0.152 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.036 0.009 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.035 0.033 0.008 0.000 0.000 0.000 0.182 0.041 0.105 0.011 0.007 0.010 0.000 0.008 0.060 0.049 0.550 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS A OF GROUND LEVEL STABILITY CLASS A 2134.000 390.980 13.470 11.740 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-35
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.044 0.000 0.001 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.010 0.008 0.000 0.004 0.000 0.000 0.000 0.000 0.000 0.000 0.022 0.015 0.005 0.000 0.000 0.000 0.008 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.000 0.000 0.000 0.029 0.021 0.006 0.005 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.010 0.008 0.016 0.074 0.078 0.218 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.054 0.017 0.018 0.090 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.037 0.011 0.005 0.000 0.000 0.008 0.010 0.052 0.000 0.005 0.000 0.010 0.008 0.070
.0. 091 0.097 0.403 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS B OF GROUND LEVEL STABILITY CLASS B 2134.000 390.980 12.090 8.600 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON. DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-36
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.-4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.015 0.005 0.011 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.031 0.000 0.000 0.000 0.000 0.000 0.000 0.028
- 0. 002 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 0.031 0.006 0.007 0.004 0.000 0.005 0.009 0.017 0.000 0.000 0.009 0.000 0.000 0.000 0.002 0.003 0.000 0.063 0.008 0.000 0.000 0.000 0.000 0.000 0.020 0.000 0.000 0.000 0.000 0.064 0.050 0.033 0.047 0.113 0.336 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.113 0.054 0.009 0.177 0.000 0.000 0..
000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.014 0.007 0.004 0.000 0.005 0.009 0.081 0.007 0.011 0.009 0.000 0.065 0.050 0.149 0.105 0.123 0.638 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS C OF GROUND LEVEL STABILITY CLASS C 2134.000 390.980 23.710 13.620 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-37
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.002 0.000 0.000 0.000 0.002 0.027 0.071 0.026 0.024 0.000 0.001 0.000 0.000 0.000 0.000 0.154 0.015 0.024 0.013 0.007 0.052 0.031 0.203 0.005 0.090 0.053 0.007 0.019 0.045 0.000 0.008 0.023 0.598 0.073 0.089 0.081 0.004 0.021 0.155 0.154 0.000 0.092 0.028 0.032 0.007 0.091 0.075 0.101 0.040 1.043 0.032 0.072 0.054 0.000 0.000 0.038 0.000 0.000 0.038 0.058 0.000 0.024 0.207 0.252 0.500 0.261 1.536 0.000 0.000 0.000 0.000 0.000 0.044 0.000 0.000 0.000 0.000 0.000 0.000 0.229 0.280 1.036 0.249 1.838 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.240 0.395 0.000 0.635
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.047 0.000 0.094 TOTAL 0.120 0.187 0.147 0.012 0.074 0.270 0.384 0.076 0.246 0.163 0.039 0.052 0.572 0.894 2.087 0.573 5.897 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS D OF GROUND LEVEL STABILITY CLASS D 2134.000 390.980 1157.440 125.840 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-38
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JAN 1,
2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.009 0.025 0.007 0.007 0.019 0.009 0.029 0.116 0.343 0.118 0.017 0.007 0.007 0.014 0.001 0.001 0.027 0.747 0.057 0.028 0.055 0.027 0.069 0.094 0.090 0.299 0.522 0.076 0.013 0.019 0.031 0.006 0.041 0.090 1.518 0.051 0.044 0.025 0.040 0.016 0.007 0.076 0.047 0.944 0.175 0.027 0.000 0.034 0.017 0.025 0.114 1.643 0.008 0.054 0.038 0.014 0.000 0.060 0.000 0.000 0.999 0.169 0.000 0.074 0.037 0.008 0.107 0.106 1.673 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.017 0.000 0.000 0.000 0.064 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.047
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.142 0.132 0.126
- 0. 100 0.095 0.190 0.283 0.697 2.582 0.485 0.047 0.100 0.134 0.079 0.175 0.336 5.701 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS E OF GROUND LEVEL STABILITY CLASS E 2134.000 390.980 715.440 121.670 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-39
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.009 0.012 0.031 0.017 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.0,79 0.018 0.017 0.015 0.022 0.069 0.080 0.075 0.235 0.164 0.025 0.010 0.006 0.006 0.000 0.007 0.019 0.768 0.016 0.004 0.011 0.018 0.022 0.015 0.149 0.096 0.529 0.007 0.000 0.000 0.000 0.000 0.000 0.022 0.888 0.017 0.009 0.000 0.000 0.000 0.000 0.066 0.141 0.654 0.028 0.000 0.000 0.000 0.000 0.000 0.007 0.922 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.493 0.039 0.000 0.000 0.000 0.000 0.000 0.000 0.532 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.052 0.030 0.026 0.039 0.097 0.104 0.301 0.503 1.857 0.102 0.010 0.'006 0.006 0.000 0.007 0.048 3.189 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS F OF GROUND LEVEL STABILITY CLASS F 2134.000 390.980 152.410 68.050 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-40
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/l00 m)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.013 0.000 0.017 0.058 0.045 0.021 0.000 0.000 0.002 0.000 0.000 0.002 0.000 0.157 0.005 0.005 0.001 0.007 0.007 0.000 0 *.097 0.634 0.280 0.000 0.001 0.000 0.000 0.005 0.002 0.000 1.044 0.000 0.000 0.002 0.003 0.000 0.006 0.061 0.122 0.388 0.000 0.000 0.000 0.000
.0.000 0.000 0.005 0.588 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.155 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0.155 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000a 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.005 0.005 0.004
- 0. 022 0.007 0.023 0.216 0.801 0.843 0.000 0.001 0.002 0.000 0.005 0.004 0.005 1.943 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS G OF GROUND LEVEL STABILITY CLASS G 2134.000 390.980 59.440 41.460 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBER DATE PRINTED: 2008/05/05 E2-41
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 15 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR SPLIT LEVEL RELEASES (GROUND LEVEL PORTION)
SECOND QUARTER E2-42
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.011 0.065 0.090 0.098 0.000 0.000 0.000 0.000 0.000 0.000 0.264 0.000 0.000 0.000 0.000 0.000 0.020 0.053 0.011 0.109 0.109 0.037 0.023 0.003 0.000 0.000 0.000 0.365 0.014 0.010 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.011 0.025 0.004 0.005 0.010 0.079 0.030 0.011 0.007 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.041 0.030 0.021 0.112 0.260 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.018 0.103 0.054 0.037 0.212 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.075 0.000 0.000 0.075
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.045 0.020 0.007 0.000 0.000 0.020 0.064 0.076 0.199 0.206 0.037 0.042 0.087 0.212 0.080 0.159 1.255 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS A OF GROUND LEVEL STABILITY CLASS A 2172.000 241.280 30.760 27.250 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-43
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.000 0.000 0.001 0.000 0.000 0.000 0.000 0.000 0.000 0.005 0.000 0.000 0.001 0.000 0.000 0.000 0.024 0.008 0.006 0.050 0.023 0.026 0.003 0.000 0.000 0.000 0.141 0.012 0.012 0.003 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 067 0.000 0.040 0.029 0.010 0.004 0.006 0.181 0.015 0.005 0.006 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.007 0.043 0.098 0.041 0.024 0.238 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.037 0.056 0.009 0.000 0.102 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.040 0.000 0.000 0.040
>=2 4. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.027 0.017 0.011 0.000 0.000 0.000 0.028 0.008 0.006 0.118 0.023
- 0. 073 0.112 0.203 0.054 0.030 0.708 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS B OF GROUND LEVEL STABILITY CLASS B 2172.000
.241.280 34.160 15.370 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY: = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-44
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE APR 1,
2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL TOTAL TOTAL TOTAL TOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 004 0.021 0.005 0.017 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.010 0.030 0.000 0.027 0.025 0.011 0.024 0.012 0.000 0.000 0.000 0.139 0.012 0.004 0.003 0.000 0.000 0.000 0.000 0.000 0.000 0.039 0.000 0.023 0.012 0.015 0.014 0.012 0.134 0.006 0.006 0.007 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.015 0.060 0.038 0.037 0.170 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.042 0.045 0.020 0.000 0.106 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.076 0.000 0.000 0.076
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.018 0.010 0.011 0.000 0.000 0.010 0.034 0.021 0.032 0.081 0.011 0.047 0.081 0.197 0.072 0.049 0.674 HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS C OF GROUND LEVEL STABILITY CLASS C 2172.000 241.280 88.020 14.630 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-45
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant PART I OF 2 GROUND LEVEL RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.011 0.043 0.103 0.054 0.092 0.099 0.026 0.017 0.004 0.000 0.002 0.000 0.451 0.017 0.022 0.005 0.003 0.016 0.072 0.104 0.042 0.296 0.224 0.029 0.068 0.081 0.010 0.003 0.003 0.994 0.061 0.043 0.010 0.000 0.007 0.006 0.011 0.000 0.035 0.079 0.000 0.066 0.112 0.041 0.026 0.036 0.535 0.048 0.099 0.006 0.006 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.017 0.133 0.120 0.188 0.144 0.760 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.026 0.069 0.114 0.023 0.233 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 o.0oo 0.000 0.000 0.000 0.000 0.110 0.000 0.000 0.110
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.127 0.164 0.020 0.010 0.034
- 0. 122 0.218 0.096 0.422 0.402 0.055 0.168 0.355 0.350 0.333 0.207 3.082 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS D OF GROUND LEVEL STABILITY CLASS D 2172.000 241.280 1174.160 66.940 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-46
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE APR 1,
2008 JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WSW W
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.000 0.000 0.001 0.003 0.001 0.020 0.023 0.020 0.003 0.000 0.000 0.003 0.000 0.081 0.005
- 0. 004 0.013 0.045 0.075 0.175 0.073 0.195 0.292 0.369 0.053 0.029 0.023 0.006 0.000 0.017 1.373 0.043 0.038 0.013 0.011 0.053 0.173 0.090 0.011 0.346 0.186 0.008 0.035 0.015 0.000 0.018 0.048 1.088 0.054 0.044 0.034 0.022 0.000 0.066 0.015 0.000 0.467 0.104 0.000 0.024 0.000 0.013 0.047 0.040 0.930 0.008 0.017 0.007 0.000 0.000 0.000*
0.025 0.000 0.132 0.035 0.000 0.017 0.036 0.031 0.053 0.057 0.418 0.000 0.000 0.000 0.000 0.000-0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.110 0.103 0.073 0.079 0.128 0.416 0.206 0.207 1.257 0.716 0.081 0.107 0.074 0.050 0.122 0.162 3.890 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS E OF GROUND LEVEL STABILITY CLASS E 2172.000 241.280 638.100 84.490 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-47
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE APR 1, 2008 JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.010 0.007 0.025 0.011 0.012 0.012 0.008 0.029 0.023 0.000 0.007 0.000 0.000 0.002 0.001 0.147 0.064 0.00 7 0.006 0.031 0.036 0.038 0.004 0.031 0.101 0.049 0.000 0.001 0.000 0.000 0.004 0.084 0.455 0.064 0.015 0.000 0.030 0.038 0.014 0.010 0.000 0.034 0.009 0.000 0.000 0.000 0.000 0.000 0.014 0.227 0.000 0.000 0.014 0.000 0.008 0.000 0.000 0.000 0.216 0.000 0.000 0.000 0.000 0.000 0.005 0.007 0.250 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 017 0.000 0.000 0.017 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.128 0.032 0.027 0.087 0.092 0.064 0.025 0.040 0.379 0.081 0.000 0.008 0.000 0.017 0.010 0.106 1.095 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS F OF GROUND LEVEL STABILITY CLASS F 2172.000 241.280 160.550 23.790 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-48
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.000 0.020 0.019 0.009 0.005 0.012 0.023 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.093 0.116 0.029 0.008 0.033 0.018 0.001 0.002 0.006 0.008 0.000 0.000 0.000 0.001 0.000 0.001 0.002 0.226 0.050 0.004 0.000 0.006 0.015 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.011 0.086 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.167 0.035 0.008 0.058 0.052 0.010 0.007 0.019 0.031 0.000 0.000 0.000 0.001 0.000 0.004 0.013 0.406 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS G OF GROUND LEVEL STABILITY CLASS G 2172.000 241.280 46.250 8.810 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-49
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY -,DECEMBER 2008 TABLE 16 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR SPLIT LEVEL RELEASES (GROUND LEVEL PORTION)
THIRD QUARTER E2-50
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.003 0.051 0.028 0.015 0.014 0.000 0.000 0.000 0.000 0.000 0.113 0.000 0.000 0.000 0.000 0.002 0.049 0.049 0.082 0.035 0.037 0.006 0.006 0.002 0.000 0.000 0.001 0.270 0.005 0.003 0.000 0.004 0.009 0.084 0.016 0.000 0.000 0.000 0.000 0.003 0.058 0.040 0.003 0.008 0.233
- 0. 092 0.046 0.031 0.015 0.000 0.030 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 024 0.037 0.031 0.095 0.399 0.000 0.000 0.009 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.023 0.032 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.097 0.048 0.041 0.019 0.011 0.164 0.069 0.133 0.063 0.052 0.020 0.009 0.084 0.077 0.034
- 0. 127 1.047 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS A OF GROUND LEVEL STABILITY CLASS A 2064.000 153.760 21.620 21.620 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-51
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant PART I OF 2 GROUND LEVEL RELEASE MODE JUL 1,
2008 SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.001 0.000 0.000 0.001 0.000 0.054 0.012 0.000 0.000 0.000 0.000 0.010 0.003 0.000 0.000 0.001 0.083 0.002 0.024 0.010 0.003 0.000 0.036 0.000 0.000 0.000 0.000 0.000 0.000 0.009 0.018 0.004 0.000 0.108 0*.015 0.007 0.016 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.029 0.014 0.014 0.098 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.010 0.000 0.010 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0.000 0.000 0.000 0.000 0.000 TOTAL 0.019 0.031 0.026 0.004 0.000 0.090 0.012 0.000 0.008 0.000 0.000 0.010 0.017 0.047 0.028 0.015 0.306 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS B OF GROUND LEVEL STABILITY CLASS B 2064. 000 153.760 17.980 6.310 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-52
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JUL 1,
2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.002 0.029 0.016 0.001 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.063 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.000 0.000 0.004 0.072 0.023 0.004 0.003 0.009 0.007 0.013 0.000 0.000 0.000 0.000 0.000 0.000 0.019 0.014 0.000 0.004 0.096 0.015 0.008 0.000 0.016 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.018 0.023 0.008 0.089 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.035 0.035 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.038 0.013 0.003 0.025 0.007 0.077 0.002 0.029 0.016 0.001 0.000 0.000 0.024 0.031 0.023 0.051 0.340 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS C OF GROUND LEVEL STABILITY CLASS C 2064.000 153.760 49.270 7.020 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-53
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.001 0.003 0.001 0.000 0.000 0.003 0.019 0.075 0.043 0.048 0.026 0.022 0.003 0.001 0.000 0.000 0.000 0.245 0.015 0.014 0.009 0.020 0.049 0.236 0.008 0.016 0.020 0.150 0.002 0.018 0.058 0.004 0.003 0.019 0.642 0.070 0.018 0.075 0.041 0.030 0.214 0.000 0.000 0.000 0.092 0.000 0.000 0.081 0.071 0.062 0.123 0.876 0.009 0.015 0.026 0.031 0.000 0.019 0.000 0.000 0.000 0.042 0.000 0.000 0.021 0.032 0.061 0.045 0.300 0.000 0.000 0.082 0.010 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.096 0.047 0.192 0.101 0.082 0.489 0.083 0.059 0.069 0.310 0.025 0.021 0.161 0.108 0.125 0.188 2.156 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS D OF GROUND LEVEL STABILITY CLASS D 2064.000 153.760 1055.720 44.500 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-54
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.003 0.000 0.000 0.000 0.000 0.008 0.007 0.000 0.000 0.000 0.019 0.023 0.016 0.000 0.024 0.090 0.101 0.052 0.052 0.032 0.028 0.028 0.018 0.006 0.006 0.004 0.019 0.500 0.079 0.049 0.024 0.064 0.262 0.234 0.010 0.000 0.010 0.000 0.000 0.017 0.086 0.000 0.021 0.069 0.925 0.031 0.035 0.036 0.044 0.039 0.159 0.000 0.000 0.000 0.000 0.000 0.000 0.014 0.004 0.007 0.051 0.420 0.000 0.000 0.025 0.008 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.007 0.017 0.027 0.084 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.026 0.026 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.133 0.100 0.085 0.140 0.391 0.495 0.064 0.052 0.042 0.028 0.028 0.044 0.113 0.017 0.049 0.192 1.974 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS E OF GROUND LEVEL STABILITY CLASS E 2064.000 153.760 621.420 40.740 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-55
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/lao M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JUL 1,
2008 SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.001 0.010 0.000 0.000 0.008 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.019 0.084 0.032 0.024 0.047 0.049 0.021 0.006 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.003 0.089 0.358 0.093 0.077 0.048 0.063 0.091 0.007 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.010 0.011 0.058 0.457 0.025 0.027 0.008 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.000 0.000 0.000 0.068 0.000 0.000 0.005 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.000 0.000 0.013 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.203 0.146 0.086 0.109 0.148 0.029 0.006 0.000 0..000 0.000 0.001 0.000 0.009 0.017 0.014 0.147 0.915 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS F OF GROUND LEVEL STABILITY CLASS F 2064.000 153.760 217.760 18.890 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-56
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE JUL 1,
2008 SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.012 0.001 0.008 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.027 0.187 0.037 0.031 0.041 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.031 0.328 0.258 0.043 0.007 0.007 0.012 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.015 0.341 0.009 0.000 0.000 0.007 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.016 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.466 0.082 0.046 0.055
- 0. 012 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.051 0.711 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS G OF GROUND LEVEL STABILITY CLASS G 2064.000 153.760 80.230
- 14. 680 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 MIS NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-57
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 17 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR SPLIT LEVEL RELEASES (GROUND LEVEL PORTION)
FOURTH QUARTER E2-58
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE OCT 1, 2008 DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 *000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.033 0.038 0.017 0.006 0.000 0.000 0.000 0.000 0.000 0.000 0.094 0.000 0.000 0.000 0.000 0.000
- 0. 012 0.090 0.083 0.044 0.021 0.000 0.000 0.000 0.000 0.000 0.000 0.250 0.000 0.000 0.000 0.000 0.000 0.023 0.022 0.000 0.025 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.070 0.127 0.016
~0.000 0.000 0.000 0.023 0.000 0.000 0.000 0.000 0.000 0.000 0.007 0.006 0.000 0.051 0.231 0.010 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.009 0.015 0.009 0.043 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.136 0.016 0.000 0.000 0.000 0.058 0.145 0.121 0.085 0.028 0.000 0.000 0.007 0.015 0.015 0.060 0.688 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS A OF GROUND LEVEL STABILITY CLASS A 2200.000 292.740 25.660 15.130 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30. METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL' EFFLUENT VELOCITY =12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-59
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND-SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0;000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.002 0.000 0.006 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.000 0.000 0.000 0.002 0.005 0.004 0.052 0.017 0.023 0.005 0.004 0.000 0.004 0.000 0.000 0.000 0.117 0.000 0.029 0.000 0.000
.0.005 0.006 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.040 0.038 0.015 0.007 0.000 0.000 0.070 0.000 0.000 0.031 0.000 0.000 0.000 0.000 0.000 0.046 0.048 0.255 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.012 0.061 0.009 0.082 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0
. 000 0.000 0.600 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.038 0.044 0.007 0.002 0.010 0.080 0.054 0.017 0.060 0.005 0.004 0.000
- 0. 004 0.012 0.107 0.057 0.502 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS B OF GROUND LEVEL STABILITY CLASS B 2200.000 292.740 20.430 11.050 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-60
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE OCT 1,
2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.013 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.021 0.000 0.000 0.000 0.000 0.000 0.013
- 0. 054 0.000 0.000 0.000 0.000 0.003 0.005 0.000 0.000 0.000 0.075 0.009 0.009 0.004 0.000 0.000 0.065 0.000 0.000 0.000 0.000 0.000 0.007 0.011 0.004 0.005 0.005 0.119 0.041 0.061 0.005 0.000 0.000 0.024 0.000 0.000 0.000 0.000 0.000 0.008 0.009 0.038 0.039 0.052 0.277 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.035 0.000 0.035 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.050 0.070 0.010 0.000 0.000 0.102 0.054 0.008
- 0. 013 0.000 0.000 0.019 0.025 0.041 0.080 0.057 0.527 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS C OF GROUND LEVEL STABILITY CLASS C 2200.000 292.740 47.850 11.600 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-61
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE OCT 1,
2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.000 0.000 0.000 0.000 0.000 0.020 0.037 0.012 0.039 0.018 0.002 0.002 0.000 0.000 0.000 0.000 0.130 0.015 0.017 0.004 0.005 0.011 0.055 0.082 0.055 0.017 0.006 0.000 0.035 0.048 0.006 0.007 0.016 0.380 0.112 0.056 0.032 0.002 0.000 0.446 0.121 0.000 0.080 0.000 0.000 0.075 0.125 0.030 0.033 0.035 1.147 0.172 0.060 0.021 0.000 0.000 0.265 0.030 0.000 0.038 0.000 0.000 0.000 0.105 0.182 0.303 0.283 1.460 0.111 0.060 0.036 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.170 0.255 0.135 0.768 0.000 0-.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.146 0.000 0.146
>=24.5 0.000 0.000 0.000
.0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.409 0.194 0.093 0.007 0.011 0.785 0.271 0.071 0.175 0.025 0.002 0.112 0.278 0.389 0.745 0.469 4.035 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS D OF GROUND LEVEL STABILITY CLASS D 2200.000 292.740 1059.170 88.760 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-62
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE OCT 1,
2008 DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.000 0.000 0.025
- 0. 017 0.011 0.000 0.000 0.005 0.000 0.000 0.000 0.000 0.000 0.062 0.006 0.003 0.003 0.018 0.047 0.128 0.061 0.156 0.107 0.019 0.018 0.017 0.018 0.001 0.003 0.002 0.608 0.054 0.046 0.041 0.024 0.085 0.240 0.111 0.318 0.104 0.026 0.009 0.021 0.040 0.021 0.024 0.030 1.196 0.078 0.042 0.054 0.019 0.000 0.278 0.017 0.044 0.180 0.049 0.000 0.025 0.051 0.025 0.035 0.114 1.011 0.008 0.000 0.031 0.000 0.000 0.116 0.000 0.000 0.175 0.062 0.000 0.000 0.017 0.025 0.100 0.240 0.775 0.017 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.025 0.047 0.023 0.112 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.
.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.163 0.091 0.133 0.061 0.132 0.788 0.207 0.530 0.566 0.157 0.032 0.063 0.125 0.098 0.210 0.410 3.764 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS E OF GROUND LEVEL STABILITY CLASS E 2200.000 292.740 670.230
- 82. 810 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-63
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.008 0.007 0.004 0.006 0.012 0.006 0.030 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.079 0.059 0.027 0.020 0.028 0.063 0.036 0.125 0.411 0.059 0.006 0.006 0.005 0.000 0.000 0.005 0.041 0.892 0.085 0.158 0.018 0.038 0.082 0.022 0.059 0.434 0.160 0.000 0.000 0.000 0.000 0.000 0.000 0.095 1.152 0.000 0.007 0.000 0.008 0.000 0.000 0.010 0.000 0.410 0.000 0.000 0.000 0.000 0.000 0.007 0.030 0.471 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.221 0.022 0.000 0.000 0.000 0.000 0.000 0.200 0.243 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL
- 0. 144 0.192 0.047 0.081 0.149 0.064 0.206 0.852 0.880 0.028 0.006 0.005 0.000 0.000 0.011 0.170 2.837 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS F OF GROUND LEVEL STABILITY CLASS F 2200.000 292.740 257.170 62.410 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-64
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 1 OF 2 GROUND LEVEL RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.007 0.000 0.007 0.006 0.010 0.006 0.007 0.009 0.000 0.000 0.000 0.000 0.000 0.000 0.002 0.055 0.087 0.024 0.020 0.035 0.016 0.000 0.056 0.105 0.041 0.000 0.000 0.000 0.000 0.000 0.000 0.004 0.389 0.036 0.047 0.006 0.016 0.005 0.000 0.026 0.067 0.119 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.321 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.190 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.190 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.123 0.077 0.027 0.059 0.027 0.010 0.088 0.179 0.359 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.954 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF GROUND LEVEL RELEASE OF STABILITY CLASS G OF GROUND LEVEL STABILITY CLASS G 2200.000 292.740 119.490 20.980 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 10.03 AND 45.30 METERS WIND DIRECTION MEASURED AT 10.50 METER LEVEL WIND SPEED MEASURED AT 10.50 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-65
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 18 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR SPLIT LEVEL RELEASES (ELEVATED PORTION)
FIRST QUARTER.
E2-66
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
~0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.028 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.028
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.000 0.006 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.075 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.000 0.081 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS A OF ELEVATED STABILITY CLASS A 2134.000 1743.020 13.470 1.730 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-67
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.043 0.000 0.000 0.040 0.000 0.000 0.000 0.083 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.021 0.013 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.034
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.021 0.013 0.000 0.043 0.047 0.000 0.040 0.000 0.000 0.000 0.164 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS B OF ELEVATED STABILITY CLASS B 2134.000 1743.020 12.090 3.490 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-68
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
SSW.
SW WSW
-W WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0.
000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.ooo 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.094 0.000 0.000 0.000 0.000 0.000 0.187 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.044 0.000 0.046 0.000 0;000 0.000 0.000 0.090 0.000 0.000 0.042 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.040 0.082 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.038 0.000 0.000 0.038 0.076 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.037 0.000.
0.000 0.037
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- o. o0o 0.000 TOTAL 0.047 0.000 0.042 0.000 0.000 0.000 0.047 0.000 0.000 0.044 0.094
- 0. 046 0.038 0.037 0.000 0.078 0.473 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS C OF ELEVATED STABILITY CLASS C 2134.000 1743.020 23.710 10.090 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 MIS NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-69
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 N
NNE NE ENE E
WNW NW NNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.094 0.094 0.000 0.047 0.094 0.000 0.187 0.094 0.281 0.094 0.328 0.094 0.047 0.047 0.094 0.000 0.047 1.546 0.515 0.281 0.328 0.187 0.422 0.328 0.562 0.422 0.375 0.234 0.469 0.656 0.515 0.375 0.328 0.141 6.139 0.318 0.671 0.489
- 0. 137 0.406 0.047 0.134 0.272 0.363 0.181 0.183 0.498 0.536 0.629 0.721 0.856 1.728 1.325 0.916 0.205 0.209 0.656 0.369 0.653 0.654 1.023 0.246 0.209 1.323 1.354 1.999 2.192 0.650 0.614 0.000 0.000 0.039 0.380 0.831 0.877 2.352 1.060 0.306 0.225 0.948 1.709 2.860 1.793 14.646 0.000 0.000 0.000 0.000 0.000 0.036 0.657 0.267 0.717 0.306 0.000 0..143 0.313 0.469 1.124 0.211 4.242
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.038 0.063 0.000 0.000 0.000 0.000 0.025 0.044 0.000 TOTAL 3.305 2.939 1.780 0.671 1.076 1.634 2.647 2.811 4.618 3.132 1.298 1.777 3.683 4.656 7.076 5.239 SUBTOTAL 6.442 15.061 0.171 48.341 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS D OF ELEVATED STABILITY CLASS D 2134.000 1743.020 1157.440 1031.600 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05
-E2-70
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.094 0.094 0.047 0.047 0.000 0.094 0.141 0.234 0.141 0.281 0.094 0.094 0.187 0.047 0.141 0.141 0.000 1.781 0.047 0.047 0.141 0.187 0.047 0.234 0.609 0.187 0.422 0.234 0.328 0.281 0.187 0.141 0.375 0.187 3.655 0.408 0.224 0.454 0.315 0.222 0.225 0.403 0.365 0.181 0.407 0.088 0.181 0.230 0.180 0.224 0.184 4.290 0.295 0.290 0.616 0.531 0.291 0.820 1.110 1.147 1.211 0.700 0.576 0.248 0.294 0.365 0.403 0.493 9.391 0.076 0.000 0.117 0.000 0.039
- 0. 151 0.948
- 1. 822 2.190 0.264 0.000 0.037 0.115 0.078 0.115 0.268 6.219 0.000 0.000 0.000 0.000 0.000 0.037 0.463 0.524 0.846 0.323 0.027 0.043 0.000 0.000 0.000 0.000 2.264
>=24.5 0.000 0.000 0.000 0.000 0.000 0.007 0.009 0.048 0.040 0.023 0.004 0.000 0.000 0.000 0.000 0.000 TOTAL 0.919 0.608 1.421 1.034 0.693 1.615 3.776 4.234 5.171 2.045 1.164 0.978 0.873 0.904 1.257 1.133 0.132 27.824 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS E OF ELEVATED STABILITY CLASS E 2134.000 1743.020 715.440 593.770 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-71
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JAN 1,
2008 MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000.
0.000 0.047 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.187 0.047 0.047 0.094 0.000 0.047 0.047 0.141 0.047 0.000 0.000 0.094 0.000 0.094 0.047 0.000 0.000 0.703 0.088 0.000 0.000 0.088 0.133 0.136 0.314 0.045 0.000 0.000 0.090 0.090 0.136 0.000 0.045 1.165 0.041 0.085 0.212 0.247 0.206 0.324
- 0. 503*
0.084 0.000 0.000 0.000 0.043 0.000 0.000 0.000 0.000
- 1. 744 0.000 0.000 0.000 0.000 0.000 0.039 0.000 0.038 0.038 0.039 0.000 0.000 0.000 0.000 0.000 0.000 0.154 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.223 0.179 0.306 0.335 0.386 0.546 0.957 0.214 0.085 0.039 0.184 0.133 0.276 0.047 0.000 0.045 3.953 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS F OF ELEVATED STABILITY CLASS F 2134.000 1743.020 152.410 84.360 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-72
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.094 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.094 0.047 0.000 0.047 0.000 0.000 0.000 0.094 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.234 0.000 0.045 0.000 0.000 0.000 0.000 0.176 0.000 0000 0.000 0.000 0.000 0.044 0.000 0.000 0.000 0.265 0.000 0~.000 0.000 0.084 0.000 0.039 0.126 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.250 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000*
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.047 0.045 0.047 0.084 0.000 0.039 0.396 0.094 0.000 0.047 0.000 0.000 0.044 0.000 0.000 0.000 0.843 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS G OF ELEVATED STABILITY CLASS G 2134.000 1743.020 59.440
- 17. 980 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY
= 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-73
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 19 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR SPLIT LEVEL RELEASES (ELEVATED PORTION)
SECOND QUARTER E2-74
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE APR 1, 2008 - JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 o ooo 0.000 0.000 0.000 0.000 0.000 o.oo0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.043 0.000 0.000 0.000 0.000 0.000 0.043 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.041 0.000 0.000 0.000 0.039 0.000 0.000 0.000 0.000 0.080 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.038 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.038 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.080 0.000
-0.000 0.043 0.039 0.000 0.000 0.000 0.000 0.162 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS A OF ELEVATED STABILITY CLASS A 2172.000 1930.720 30.760 3.510 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-75
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE APR 1, 2008 - JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.134 0.000 0.000 0.000 0.000 0.180 0.000 0.000 0.000 0.000, 0.000 0.000 0.000 0,000 0.000 0.083 0.042 0.203 0.043 0.000 0.000 0.000 0.372 0.000 0.000 0.000 0.000 0.000 0.000 0.037 0.000 0.000 0.000 0.000 0.038 0.112 0.000 0.000 0.000 0.187 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.017 0.000 0.000 0.000 0.017
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.009 0.009 0.000 0.000 0.017 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.037 0.000 0.000 0.083 0.134 0.421 0.181 0.009 0.000 0.000 0.865 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS B OF ELEVATED STABILITY CLASS B 2172.000 1930.720 34.160 18.790 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-76
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.138 0.322 0.138 0.046 0.000 0.000 0.000 0.645 0.000.
0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.045 0.045 0.221 0.087-0.000 0.000 0.000 0.443 0.039 0.000 0.000 0.000 0.000 0.000 0.042 0.041 0.000 0.000 0.448 0.737 0.166 0.078 0.040 0.000 1.592 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.076 0.038 0.112 0.111 0.187 0.000 0.036 0.561 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.050 0.072 0.000 0.000 0.122
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0l. 000 0.000 0.000 0.000 0.015 0.000 0.000 0.015 TOTAL 0.039 0.000 0.000 0.000 0.000 0.000 0.087 0.041 0.000 0.259 0.853 1.209 0.461 0.353 0.040 0.036 3.379 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS C OF ELEVATED STABILITY CLASS C 2172.000 1930.720 88.020 73.390 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-77
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.046 0.000 0.046
.0. 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.184 0.230 0.138 0.092 0.138 0.138 0.138 0.322 0.691 0.829 0.599
- 0. 184 0.138 0.046 0.138 0.092 0.092 4.006 0.460 0.460 0.276 0.230 0.230 0.322 0.552 0.783 1.151 0.967 0.875 0.691 0.921 0.460 0.414 0.230 9.024 0.360 0.400 0.402 0.045 0.136 0.529 0.673
- 0. 849 1.018 0.617 1.119 0.621 0.616 0.578 0.402 0.308 8.673 1.649 1.139 0.165 0.040 0.000 0.570 1.573 1.890 2.362 1.372 0.734 0.901 1.298 1.326 1.396 1.282 17.695 0.416 0.418 0.000 0.000 0.000 0.075 0.679 0.855 1.835 0.865 0.076 0.455 0.446 1.279 0.865
- 0. 828 9.092 0.000 0.000 0.000 0.000 0.000 0~.000 0.197 0.304 1.090 0.131 0.000 0.000 0.056 0.251 0.090 0.069 2.187
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.026 0.058 0.012 0.000 0.000 0.000 0.021 0.000 0.000 TOTAL 3.115 2.601 0.936 0.499 0.504 1.680 3.995 5.396 8.342 4.563 2.988 2.806 3.383 4.053 3.260 2.855 0.117 50.977 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS D OF ELEVATED STABILITY CLASS D 2172.000 1930.720 1174.160 1107.220 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-78
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.092 0.184 0.000 0.138 0.230 0.092 0.414 0.506 0.322 0.322 0.184 0.092 0.276 0.230 0.276 0.138 0.092 3.499 0.138 0.138 0.092 0.184 0.322 0.783 0.599 0.276 0.552 0.599 0.230 0.138 0.138 0.368 0.276 5.157 0.354
- 0. 179 0.265 0.088
- 0. 176 0.313 0.528 0.264 0.264 0.755 0.490 0.308 0.271 0.088 0.352 0.265 4.961 0.881 0.282 0.281 0.322 0.409 0.765 0.802 0.923 1.079 1.023 0.084 0.250 0.203 0.081 0.239 0.930 8.554 0.038 0.000 0.000 0.038 0.000 0.152 0.339 0.792 0.906 0.189 0.075 0.113 0.000 0.000 0.189 0.114 2.945 0.000 0.000 0.000 0.000 0.000 0.000
.0.119 0.108 0.000 0.036 0.000 0.000 0.000 0.000 0.000 0.000 0.263
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.018 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 1.595 0.599 0.776 0.863 1.046 1.967 3.077 3.025 2.848 2.740 1.339 1.177 0.842 0.629 1.286 1..678 0.018 25.488 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS E OF ELEVATED STABILITY CLASS E 2172.000 1930.720 638.100 553.610 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-79
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0.092 0.000 0.138 0.046 0.092 0.000 0.230 0.046 0.046 0.092 0.046 0.184 0.046 0.000 0.000 0.000 0.000 0.967 0.138 0.046 0.046 0.046 0.138 0.138 0.092 0.046 0.092 0.230 0.000 0.046 0.092 0.046 0.092 0.046 1.335 0.092 0.000 0.043 0.311 0.134 0.177 0.308 0.221 0.088 0.221 0.000 0.000 0.000 0.000 0.046 0.043 1.684 0.317 0.244
- 0. 122 0.283 0.121 0.249 0.082 0.081 0.164 0.120 0.000 0.042 0.000 0.000 0.000 0.279 2.104 0.038 0.000 0.038 0.000 0.038 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.115 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.585 0.428 0.295 0.732 0.430 0.794 0.529 0.395 0.437 0.617 0.230 0.180 0.092 0.046 0.138 0.368 6.297 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS F OF ELEVATED STABILITY CLASS F 2172.000 1930.720 160.550 136.760 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-80
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.046 0.046 0.092 0.092 0.046 0.046 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.552 0.043 0.046 0.000 0.000 0.044 0.000 0.270 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.447 0.476 0.080 0.000 0.000 0.000 0.000 0.000b 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.556 0.038 0.038 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.076 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.603 0.210 0.184 0.092 0.090 0.046 0.362 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.137 1.724 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS G OF ELEVATED STABILITY CLASS G 2172.000 1930.720 46.250 37.440 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/08/04 E2-81
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT' JANUARY - DECEMBER 2008 TABLE 20 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR SPLIT LEVEL RELEASES (ELEVATED PORTION)
THIRD QUARTER E2-82
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS A OF ELEVATED STABILITY CLASS A 2064.000 1910.240 21.620 0.000 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-83
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.048 0.000 0.097 0.000 0.000 0.000 0.000 0.000 0.194 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.048 0.048 0.094 0.046 0.000 0.000 0.000 0.284 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.043 0.000 0.000 0.000 0.000 0.088 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0:000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.048 0.048 0.048 0.189 0.137 0.046 0.000 0.000 0.000 0.565 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS B OF ELEVATED STABILITY CLASS B 2064.000 1910.240 17.980 11.670 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY =12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-84
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.048 0.000 0.000 0.145 0.339 0.291 0.048 0.000 0.000 0.000 0.921 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.185 0.000 0.000 0.048 0.093 0.047 0.000 0.000 0.000 0.418 0.085 0.124 0.000 0.000 0.000 0.043 0.126 0.000 0.000 0.000 0.000 0.045 0.127 0.000 0.000 0.000 0.549 0.079 0.000 0.000 0.000 0.000 0.000 0.040 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.040 0.159 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
-0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.164 0.124 0.000 0.000 0.048 0.043 0.260 0.185 0.000 0.145 0.388 0.428 0.222 0.000 0.000 0.040 2.047 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS C OF ELEVATED STABILITY CLASS C 2064.000 1910.240 49.270 42.250 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-85
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 N
NNE NE ENE E
WNW NW NNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.194 0.145 0.145 0.242 0.145 0.339 0.145 0.533 0.727 0.678 0.872 0.921 0.581 0.242 0.097 0.194 0.339 0.484 0.630 0.194 0.339 0.339 0.194 0.824 1.260 0.969 1.114 1.938 1.550 1.647 0.436 0.484 0.145 0.653 0.604 0.331 0.417 0.558 0.279 0.753 0.935 0.851 0.421 0.142 0.896 1.497 0.514 0.283 0.562 1.171 0.678 0.645 0.259 0.515 1.724 1.594 0.681 0.417 0.343 0.130 0.131 1.775 1.713
- 1. 013 1.317 0.241 0.121 0.196 0.118 0.040 0.554 2.364 0.944 0.311 0.040 0.000 0.000 0.000 0.040 0.238 0.319 5.524 0.000 0.000 0.000 0.000 0.000 0.000 0.074 0.356 0.049 0.047 0.000 0.000 0.000 0.000 0.000 0.025 0.551
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.029 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 2.743 2.177 1.608 1.279 1.790 2.896 6.141 4.950 3.400 2.838 3.131 3.158 5.161 2.800 2.212 2.708 SUBTOTAL 6.347 12.548 9.695 14.105 0.029 48.993 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS D OF ELEVATED STABILITY CLASS D 2064.000 1910.240 1055.720 1011.220 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89..59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-86
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 N
NNE NE ENE E
WNW NW NNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.048 0.000 0.000 0.048 0.048 0.000 0.097 0.000 0.000 0.048 0.048 0.000 0.000 0.000 0.000 0.388 0.145 0.242 0.048 0.242 0.048 0.388 0.339 0.242 0.291 0.194 0.194 0.388 0.194 0.097 0.048 0.242 3.343 0.291 0.581 0.291 0.533 0.388 0.194 0.388 0.581 0.727 0.630 0.581 0.581 0.630 0.000 0.194 0.484 7.074 0.604 0.235 0.325 0.231
- 0. 604 0.659 0.569 0.142 0.094 0.284 0.045 0.383 0.374 0.094 0.329 0.231 1.525 0.385 0.852 1.107 1.249 1.966 0.600 0.130 0.171 0.133 0.000 0.044 0.772 0.215 0.511 1.113 0.239 0.080 0.198 0.119 0.000 0.080 0.078 0.199 0.040 0.039 0.000 0.000 0.000 0.000 0.120 0.079 1.272 0.000 0.000 0.044 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.036 0.080
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 2.853 1.572 1.759 2.233 2.337 3.336 1.974 1.392 1.322 1.280 0.869 1.444 1.969 0.406 1.203 2.186 SUBTOTAL 5.203 10.774 0.000 28.134 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS E OF ELEVATED STABILITY CLASS E 2064.000 1910.240 621.420 580.680 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-87
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JUL 1,
2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.048 0.000 0.097 0.000 0.000 0.097 0.048 0.048 0.048 0.000 0.242 0.145 0.145 0.097 0.145 0.145 0.048 0.097 0.145 1.453 0.097 0.097 0.145 0.048 0.097 0.000 0.048 0.242 0.194 0.000 0.291 0.097 0.194 0.097 0.000 0.048 1.696 0.046 0.277 0.236 0.276 0.319 0.000 0.047 0.097 0.000 0.000 0.000 0.048 0.046 0.000 0.046 0.186 1.623 0.899 0.634 0.774 0.551 0.470 0.515 0.044 0.000 0.000 0.000 0.000 0.085 0.000 0.041 0.000 0.435 4.449 0.040 0.237 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.040 0.000 0.000 0.000 0.000 0.318 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 1.081 1.246 1.252 0.924 0.935 0.563 0.139 0.581 0.339 0.145 0.388 0.416 0.385 0.234 0.191 0.814 9.635 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS F OF ELEVATED STABILITY CLASS F 2064.000 1910.240 217.760 198.870 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-88
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.048 0.000 0.000 0.048 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.145
- 0. 048
- 0. 145 0.242 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.533
- 0.141 0.141 0.141 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.373 0.701 0.299 0.342 0.130 0.087 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.558 0.359 0.160 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.519 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 1.108 0.745 0.773 0.273 0.087 0.000 0.048 0.048 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.045 3.176 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS G OF ELEVATED STABILITY CLASS G 2064.000 1910.240 80.230 65.550 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AN~.D 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY
= 12.60 MIS NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-89
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 21 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR SPLIT LEVEL RELEASES (ELEVATED PORTION)
FOURTH QUARTER E2-90
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.040 0.000 0.039 0.038 0.040 0.000 0.158 0.000 0.000 0.000 0.000 0.000 0.000 0.037 0.037 0.000 0.000 0.000 0.000 0.000
- 0. 112 0.037 0.000 0.223 0.000 0.000 0.000 0.000 0.000 0.000 0.052 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.052
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.089 0.037 0.000 0.000 0.040 0.000 0.085 0.150 0.077 0.000 0.479 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS A OF ELEVATED STABILITY CLASS A 2200.000 1907.260 25.660 10.530 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-91
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.6000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.044 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.044 0.077 0.041 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.040 0.038 0.000 0.000 0.000 0.000 0.000 0.197 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.036
- 0. 074 0.000 0.110 0.000 0.000 0.000 0.000 0.000 0.000 0.030 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.030
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.077 0.041 0.000 0.000 0.000 0.000 0.075 0.044 0.000 0.040 0.038 0.000 0.000 0.036 0.074 0.000 0.426 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS B OF ELEVATED STABILITY CLASS B 2200.000 1907.260 20.430 9.380 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 ANDl 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-92
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.091 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.136 0.000.
0.043 0.000 0.000 0.044 0.132 0.000 0.085 0.132 0.000 0.000 0.043 0.000 0.000 0.000 0.000 0.480 0.080 0.000 0.000 0.000 0.000 0.121 0.000 0.042 0.000 0.080 0.000 0.156 0.119 0.000 0.040 0.116 0.753 0.038 0.000 0.000 0.000 0.000 0.000 0.038 0.000 0.000 0.000 0.000 0.037 0.000 0.036 0.000 0.000 0.149 0.000 0.000 0.000 0.000 0.000 0.000 0.049 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.036 0.000 0.085
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.117 0.043 0.000 0.000 0.044 0.253 0.132 0.218 0.132 0.080 0.000 0.282 0.119 0.036 0.075 0.116 1.648 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS C OF ELEVATED STABILITY CLASS C 2200.000 1907.2 60 47.850 36.250 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-93
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 N
NNE NE ENE E
WNW NW NNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.091 0.000 0.000 0.000 0.000 0.045 0.000 0.091 0.000 0.000 0.045 0.045 0.000 0.000 0.000 0.000 0.318 0.136 0.091 0.045 0.136 0.182 0.182 0.455 0.455 0.227 0.273 0.318 0.318 0.273 0.091 0.136 0.136 3.455 0.455 0.182 0.409 0.136 0.227 0.409 1.227 0.818 0.545 0.636 0.455 0.273 0.273
- 0. 182 0.227 0.273 6.727 0.354 0.785 0.566 0.221 0.090 0.397 0.518 0.565 0.747 0.219 0,.174 0.394 0.262 0,265 0.087 0,.175 1.845 1.193 0.320 0.041 0.082 0.824 1.377 1.260 0.877.
0.440 0.281 1.034 1.357 1.613 0.711 1.262 1.596 0.411
- 0. 110 0.000 0.000 0.517
- 1. 104 0.845 0.520 0.293 0.147 0.149 0.408
- 0. 627 2.036 1.442 0.201 0.077 0.000 0.000 0.000 0.036 0.785 0.495 0.180 0.045 0.000 0.000 0.020 0.317 0.575 0.110 2.842
>=24.5 0.000 0.005 0.000 0.000 0.000 0.000 0.046 0.073 0.051 0.012 0.000 0.000 0.000 0.000 0.036 0.000 TOTAL 4.679 2.743 1.451 0.535 0.581 2.410 5.512 4.601 3.148 1.919 1.420 2.213 2.593 3.096 3.810 3.399 SUBTOTAL 5.819 14.518 10.208 0.223 44.110 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS D OF ELEVATED STABILITY CLASS D 2200.000 1907.260 1059.170 970.410 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-94
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE OCT 1, 2008 -
DEC 31, 2008
-WIND DIRECTION N
NNE NE ENE E
WNW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 045 0.000
- 0. 045
- 0. 045 0.000
- 0. 045 0.000
- 0. 045 0.136 0.000 0.000 0.091 0.000 0.045 0.000 0.000 0.500 0.000 0.136 0.136 0.000 0.318 0.273 0.591 0.227 0.409 0.273 0.318 0.227 0.091 0.227 0.136 0.091 3.455 0.227 0.136 0.273
- 0. 182 0.409 0.364 0.818 0.318 0.409 0.273 0.545 0.364
- 0. 136 0.182 0.091 0.091 4.818 0.089 0.220 0.219 0.312 0.526 0.435 0.916 0.746 0.128 0.089 0.265 0.350 0.393 0.132 0.131 0.131 5.081 0.563 0.760 0.675 0.360 0.655 1.504 1.044 0.760 0.479 0.323 0.120 0.165 0.280 0.201 0.750 0.870 9.507 0.150 0.000 0.075 0.075 0.000 0.413 0.739 0.256 0.037 0.037 0.036 0.036 0.000 0.000 0.519 0.298 2.672 0.000 0.000 0.000 0.000 0.000 0.000 0.270 0.259 0.069 0.025 0.000 0.000 0.000 0.000 0.000 0.000 0.623
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.011 0.004
- 0. 023 0.007 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 1.075 1.252 1.423 0.975 1.908 3.034 4.390 2.616 1.690 1.025 1.285 1.232 0.901 0.787
- 1. 627 1.482 0.045 26.701 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS E OF ELEVATED STABILITY CLASS E 2200.000 1907.260 670.230 587.420 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-95
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.091 0.000 0.045 0.045 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.273 0.045 0.045 0.091 0.182 0.136 0.273 0.273 0.045 0.318 0.227 0.000 0.136 0.182 0.045 0.000 0.000 2.000 0.000 0.045 0.000 0.045 0.045 0.227 0.455 0.273 0.182 0.182 0.227 0.091 0.045 0.045 0.000 0.000 1.864 0.000 0.000 0.086 0.000 0.180 0.349 0.313 0.000 0.091 0.131 0.090 0.045 0.045 0.000 0.000 0.090 1.419 0.322 0.476 0.565 0.355 0.245 0.570 0.320 0.084 0.000 0.000 0.000 0.000 0.042 0.000 0.000 0.283 3.261 0.000 0.000 0.000 0.000 0.000 0.000 0.036 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.036 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.368 0.613 0.833 0.582 0.651 1.464 1.396 0.402 0.636 0.540 0.318 0.273 0.314 0.091 0.000 0.372 8.853 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS F OF ELEVATED STABILITY CLASS F 2200.000 1907.260 257.170 194.760 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY = 12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-96
SPLIT JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/l00 M)
Browns Ferry Nuclear Plant PART 2 OF 2 ELEVATED RELEASE MODE OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE ENE E
WNW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.136 0.000 0.000 0.000 0.000 0.045 0.227 0.091 0.091 0.045 0.000 0.045 0.045 0.045 0.045 0.091 0.909 0.000 0.000 0.045 0.000 0.091 0.182 0.409
- 0. 182 0.045 0.000 0.000 0.000 0.000 0.000 0.091 0.045 1.091 0.000 0.000
- 0. 177 0.043 0.042 0.308 0.487 0.130 0.043 0.000 0.000 0.000 0.000 0.000 0.000 0.043 1.273 0.197 0.000 0.286 0.000 0.042 0.163 0.205 0.122 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.039 1.054 0.000 0.150 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.150 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24. 5 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.334 0.150 0.509 0.043 0.175 0.698 1.329 0.525 0.180 0.045 0.000 0.045 0.045 0.045 0.136 0.218 4.478 TOTAL TOTAL TOTAL TOTAL HOURS HOURS HOURS HOURS OF VALID OBSERVATIONS OF ELEVATED RELEASES OF STABILITY CLASS G OF ELEVATED STABILITY CLASS G 2200.000 1907.260 119.490 98.510 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND DIRECTION MEASURED AT 45.74 METER LEVEL WIND SPEED MEASURED AT 45.74 METER LEVEL EFFLUENT VELOCITY
=12.60 M/S NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-97
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 22 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR ELEVATED RELEASES FIRST QUARTER E2-98
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.093 0.000 0.000 0.000 0.000 0.000 0.000 0.093 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.185 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS A TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 4
4 2162 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED = 22.15 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-99
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000.
0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000
ý0.046 0.046 0.000 0.000 0.046 0.046 0.046 0.000 0.000 0.000 0.231 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS B TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 5
5 2162 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED = 15.86 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-100
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0.000 0.046 0.000 0.000
-0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.093 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.093 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.046 0.139 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.046 0.139 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.093 0.000 0.046 0.000 0.000 0.000 0.046 0.000 0.000 0.046 0.046 0.093 0.046 0.046 0.000 0.093 0.555 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS C TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 12 12 2162 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED = 10.73 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-101
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.139 0.000 0.139 0.046 0.046 0.000 0.093 0.370 0.046 0.139 0.231 0.278 0.093 0.046 0.000 0.000 0.139 1.665 0.416 0.185 0.139 0.046 0.231 0.463 0.278 0.139 0.139 0.231 0.278 0.324 0.463 0.370 0.185 0.046 3.932 0.231 0.278 0.185 0.139 0.139 0.370 0.046 0.139 0.370 0.324 0.139 0.463 0.463 0.509 0.463 0.324 1.804 1.711 1.295 0.278 0.555 0.324 0.324 0.509 0.786 0.555 0.278 0.324 1.203 1.665 1.295 1.665 1.110 1.156 0.324 0.046 0.093 0.740 0.786 1.110 2.359 1.295 0.370 0.093 1.295 1.711 3.469 3.053 0.093 0.231 0.046 0.000 0.000 0.278 1.434 0.509 1.804 0.925 0.139 0.324 0.971 1.295
- 2. 174 0.648 0.000 0.000 0.046 0.000 0.000 0.000 0.416 0.879 0.740 0.093 0.000 0.185 0.601 0.463 1.110 0.046 3.654 3.700 2.081 0.601 1.064 2.266 3.654 3.330 6.337 3.654 1.480 1.804 5.042 6.013 8.742 5.920 4.579 14.570 19.010 10.870 4.579 59.343 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS D TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 1283 1283 2162 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED = 14.24 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-102
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.046 0.000 0.093 0.000 0.000 0.000 0.000 0.046 0.093 0.000 0.231 0.000 0.093 0.093 0.046 0.046 0.093 0.046 0.046 0.833 0.046 0.139 0.093 0.046 0.185 0.231 0.509 0.000 0.139 0.139 0.093 0.185 0.139 0.231 0.278 0.046 2.498 0.000 0.046 0.231 0.000 0.093 0.000 0.231 0.093 0.185 0.093 0.231 0.046 0.046 0.324 0.000 0.139 1.758 0.601 0.509 0.601 0.370 0.786 0.416 0.694 1.018 0.971 0.648 0.648 0.185 0.416 0.185 0.509 0.231 0.139 0.093 0.463 0.463 0.093 0.463 0.694 1.989 2.313 0.786 0.694 0.231 0.555 0.416 0.370 0.648 0.046 0.139 0.093 0.000 0.000 0.185 0.740 1.665 2.960 0.786 0.000 0.046 0.093 0.000 0.046 0.046 6.846 0.000 0.000 0.000 0.000 0.000 0.185 0.370 1.110 1.156 0.231 0.093 0.093 0.000 0.000 0.000 0.000 0.833 0.925 1.480 0.879 1.203 1.573 3.238 6.105 7.724 2.775 1.896 0.833 1.295 1.249 1.295 1.156 8.788 10.407 3.238 34.459 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS E TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 745 745 2162 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL MEAN WIND SPEED = 14.85 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/05/05 E2-103
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F (1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0'.
000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.093 0.000 0.046 0.093 0.000 0.000 0.000 0.046 0.000 0.046 0.000 0.000 0.000 0.324 0.046 0.000 0.000 0.000 0.046 0.046 0.046 0.093 0.000 0.000 0.000 0.000 0.046 0.000 0.093 0.000 0.416 0.093 0.046 0.093 0.046 0.231 0.278 0.231 0.463 0.046 0.000 0.046 0.093 0.139 0.046 0.000 0.046 1.896 0.093 0.046 0.046 0.139 0.139 0.139 0.324 0.231 0.046 0.000 0.046 0.093 0.046 0.000 0.000 0.000 1.388 0.000 0.000 0.000 0.000 0.046 0.046 0.000 0.046 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.231 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.046 0.231 0.093 0.139 0.278 0.463 0.601 0.694 0.833 0.139 0.046 0.185 0.185 0.278 0.046 0.093 0.046 4.348 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS F TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 94 94 2162 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED =11.40 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-104
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant JAN 1, 2008 -
MAR 31, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.093 0.000 0.000 0.000 0.093 0.000 0.000 0.000 0.000 0.185 0.000 0.046 0.000 0.000 0.000 0.000 0.139 0.093 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.278 0.000 0.046 0.046 0.000 0.093 0.000 0.231 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.416 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.093 0.046 0.000 0.093 0.000 0.370 0.185 0.000 0.000 0.000 0.093 0.000 0.000 0.000 0.000 0.879 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS G TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2162 19 19 2162 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/05/05 MEAN WIND SPEED = 11.38 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-105
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 23 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR ELEVATED RELEASES SECOND QUARTER E2-106
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 046 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0.184 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS A TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2177 4
4 2177 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED = 11.82 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-107
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.092 0.276 0.000 0.000 0.000 0.000 0.413 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.138 0.092 0.000 0.000 0.000 0.276 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.092 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.138 0.000 0.000 0.000 0.138 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.092 0.184 0.505 0.230 0.000 0.000 0.000 1.056 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS B TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2177 23 23 2177 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED = 14.27 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-108
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4,"
1.5-3.4 3.5-5.4 5.5-7.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.138 0.138 0.046 0.000 0.000 0.000 0.000 0.322 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.046 0.230 0.230 0.046 0.000 0.000 0.000 0.597 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.046 0.000 0.000 0.230
- 0. 827 0.138 0.092 0.046 0.000 1.424 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.322 0.230 0.000 0.184 0.000 0.000 0.827 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.138 0.138 0.092 0.000 0.046 0.459 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.184 0.000 0.000 0.276 0.046 0.000 0.000 0.000 0.000 0.046 0.046 0.046 0.000 0.230 0.965 1.470 0.413 0.551 0.046 0.046 3.904 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS C TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2177 85 85 2177 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED = 12.70 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-109
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.138 0.092 0.046 0.230 0.138 0.092 0.138 0.413 0.551 0.597 0.230 0.138 0.092 0.046 0.138 0.046 0.138 3.124 0.367 0.413 0.184 0.276 0.138 0.184 0.413 0.551 0.689
- 0. 873 0.551 0.735 0.505 0.413 0.367 0.184 6.844 0.413 0.367 0.322
- 0. 184 0.230 0.459 0.689 0.413 0.873 0.413 0.551 0.322
- 0. 597 0.597 0.367 0.230 1.332 1.194 0.413 0.046 0.046 1.194 1.148 1.975 1.791 1.470 1.562 1.194 1.240 1.516 0.781 1.194 0.965 0.873 0.184 0.000 0.092 0.230 1.102 1.240 2.756 1.470 0.597 0.735 0.597 1.516 1.148 1.516 0.046 0.000 0.000 0.000 0.000 0.046 0.413 0.919 2.067 0.459 0.138 0.276 0.505 0.689 0.276 0.184 6.017 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.413 1.148 0.230 0.000 0.000 0.092 0.276 0.000 0.000 3.261 2.894 1.332 0.643 0.597 2.251 4.272 6.063 9.922 5.145 3.537 3.353 3.583 5.145 2.986 3.491 SUBTOTAL 7.028 18.098 15.021 2.205 58.475 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS D TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2177 1273 1273 2177 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED = 11.57 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-110
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 o.o0o 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.046 0.000 0.000 0.000 0.046 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.138 0.000 0.092 0.000 0.046 0.046 0.138 0.184 0.322 0.138 0.000 0.000 0.092 0.092 0.138
- 0. 092 0.138 1.516 0.046 0.046 0.092 0.184 0.138 0.184 0.413 0.322 0.367 0.230 0.138 0.184 0.276 0.046 0.138 0.046 2.848 0.230 0.184 0.138 0.046 0.092 0.413 0.643 0.459 0.230 0.092 0.184 0.092 0.276 0.230 0.276
- 0. 184 3.767 0.643 0.413 0.276 0.413 0.276 0.597 0.643 0.643 0.735 0.919 0.873 0.322 0.230 0.092 0.413 0.322 0.965 0.276 0.184 0.276 0.138 0.597 1.102 1.056 1.929 1.286 0.643 0.322 0.230 0.046 0.184 0.781 0.000 0.000 0.000 0.000 0.000 0.138 0.322 0.413 0.367 0.046
- 0. 092 0.000 0.000 0.000 0.046 0.000 1.424 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.322 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.883 1.056 0.689 0.965 0.689 2.113 3.353 3.537 3.813 2.572 1.929 1.011 1.102 0.551 1.148 1.470 7.809 10.014 0.367 27.882 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS E TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2177 607 607 2177 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED = 11.02 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-1 11
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 - JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.046 0.046 0.138 0.000 0.092 0.000 0.000 0.046 0..000 0.046 0.046 0.000 0.000 0.459 0.000 0.000 0.000 0.046 0.046 0.138 0.184 0.046 0.000 0.046 0.000 0.000 0.046 0.000 0.000 0.000 0.551 0.092 0.092 0.092 0.046 0.138 0.230 0.138 0.092 0.046 0.046 0.092 0.000 0.000 0.000 0.000 0.046 1.148 0.046 0.276 0.046 0.184 0.184 0.184 0.322 0.276 0.138 0.184 0.230 0.000 0.046 0.000 0.000 0.092 2.205 0.413 0.138 0.092 0.230
- 0. 092 0.138 0.000 0.000 0.322 0.322 0.000 0.046 0.000 0.000 0.000 0.184 1.975 0.092 0.000 0.046 0.092 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.276 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.643 0.505 0.276 0.643 0.505 0.873 0.643 0.505 0.505 0.643 0.367 0.046 0.138 0.046 0.000 0.322 6.661 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS F TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2177 145 145 2177 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED = 10.36 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-112
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant APR 1, 2008 -
JUN 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.092 0.092 0.230 0.092 0.046 0.046 0.000 0.000 0.367 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.873 0.184 0.322 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.551 0.046 0.230 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.276 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.600 0.322 0.781 0.092 0.092 0.184 0.000 0.000 0.367 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.837 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS G TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2177 40 40 2177 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/08/04 MEAN WIND SPEED = 12.84 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-113
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 24 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR ELEVATED RELEASES THIRD QUARTER E2-114
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS A TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 0
0 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL MEAN WIND SPEED =
0.00 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2008/11/19 E2-115
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.048 0.097 0.048 0.000 0.000 0.000 0.000 0.242 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.097 0.048 0.000 0.000 0.000 0.242 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.097 0.000 0.048 0.194 0.145 0.048 0.000 0.000 0.000 0.581 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS B TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 12 12 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND.
89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
7.19 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-116
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant JUL 1,
2008 SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.145 0.242 0.194 0.048 0.000 0.000 0.000 0.630 0.000 0.000 0.000 0.000 0.048 0.000 0.048 0.048 0.000 0.000 0.145 0.097 0.097 0.000 0.000 0.000 0.484 0.097 0.000 0.000 0.000 0.000 0.097 0.097 0.097 0.000 0.000 0.000 0.097 0.097 0.000 0.000 0.000 0.581 0.194 0.097 0.000 0.000 0.000 0.097 0.048 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.484 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
.0.000 0.000 0.000 0.000 0.000 0.291 0.097 0.000 0.000 0.048 0.194 0.194 0.145 0.000 0.145 0.388 0.388 0.291 0.000 0.000 0.000 2.180 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS C TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 45 45 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
8.53 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-117
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant
- JUL 1, 2008 -
SEP 30, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW CALM 0.002 0.001 0.002 0.001 0.001 0.002 0.004 0.008 0.003 0.006 0.005 0.004 0.003 0.001 0.001 0.002 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.242 0.097 0.194 0.097 0.145 0.242 0.436 0.678 0.339 0.581 0.484 0.436 0.291 0.097 0.097 0.194 0.339 0.388 0.291 0.291 0.242 0.291 0.775 0.678 0.581 0.969 1.357 1.599 1.599 0.339 0.339 0.097 0.630 0.484 0.194 0.291 0.145 0.388 0.630 0.824 0.678 0.630 0.533 0.630 1.308 0.630 0.339 0.436 0.969 0.872 0.824 0.678 0.581 1.017 1.211 0.775 0.484 0.484 0.484 0.533 2.277 2.035 0.727 1.211 1.211 0.484 0.242 0.097 0.436 2.229 2.519 0.727 0.291 0.242 0.097 0.048 0.291 0.291 0.533 0.678 0.000 0.000
- 0. 145
- 0. 145 0.000 0.581 1.114 0.775 0.242 0.048 0.000 0.000 0.000 0.000 0.000 0.097 3.149 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.339 0.291 0.048 0.000 0.000 0.000 0.000 0.000 0.000 3.394 2.327
- 1. 892 1.600 1.552 4.751 6.739 4.901 2.910 3.010 2.960 3.251 5.768 3.392 2.036 2.715 SUBTOTAL 4.651 10.174 8.769 15.165 10.417 0.727 53.198 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS D TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 1098 1098 2064 1
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED =
9.37 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-118
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30,.2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 02,000 0.000 0.000 0.048 0.000 0.048 0.000 0.000 0.000 0.048 0.000 0.000 0.194 0.000 0.097 0.145 0.097 0.097 0.291 0.242 0.048 0.097 0.000 0.097 0.242 0.048 0.097 0.048 0.000 1.647 0.194 0.145 0.242 0.145 0.048 0.242 0.291 0.388 0.242 0.339 0.339 0.242 0.291 0.339 0.097 0.145 3.731 0.145 0.436 0.388 0.291 0.242 0.291 0.678 0.678 0.291 0.242 0.484 0.436 0.339 0.291 0.145 0.048 5.426 0.727 0.775 0.727 1.066 0.388 1.066 1.163 0.097 0.194 0.533 0.145 0.581 0.727 0.630 0.339 0.581 9.738 1.696 0.291 0.630 0.533 0.678 1.841 0.630 0.242 0.145 0.048 0.048 0.000 0.242 0.242 0.242 0.436 7.946 0.145 0.145 0.242 0.194 0.000 0.145 0.097 0.048 0.000 0.048 0.000 0.000 0.000 0.000 0.097 0.145 1.308 0.000 0.000 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 2.955 1.890 2.471 2.326 1.453 3.876 3.101 1.550 0.969 1.260 1.114 1.502 1.647 1.647 0.969 1.405 0.145 30.136 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS E TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 622 622 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED = 10.00 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-119
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 N
NNE NE ENE E
WNW NW NNW CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.5-12.4 12.5-18.4 18.5-24.4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.097 0.097 0.000 0.000 0.097 0.048 0.097 0.533 0.097 0.048 0.000
- 0. 000' 0.048 0.097 0.048 0.145 0.194 0.000 0.145 0.000 0.097 0.194 0.097 0.097 1.308 0.000 0.000 0.048 0.097 0.242 0.000 0.048 0.048 0.097 0.000 0.048 0.048 0.194 0.194 0.097 0.048 1.211 0.339 0.242 0.581 0.242 0.388 0.484 0.145 0.048 0.145 0.000 0.048 0.097 0.048 0.048 0.048 0.048 2.955 0.678 0.775 0.436 0.291 0.533 0.484 0.145 0.000 0.000 0.000 0.000 0.097 0.097 0.000 0.000 0.097 3.634 0.048 0.291 0.291 0.000 0.048 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.727 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.211 1.357 1.357 0.630 1.260 1.114 0.436 0.242 0.436 0.097 0.339 0.242 0.436 0.533 0.291 0.388
>=24.5 TOTAL SUBTOTAL 0.000 10.368 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS F TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 214 214 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED = 11.02 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-120
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant JUL 1, 2008 -
SEP 30, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18.5-24.4
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.097 0.000 0.048 0.000 0.000 0.097 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.242 0.000 0.145 0.242 0.242 0.291 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.969 0.194 0.194 0.388 0.242 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.066 0.242 0.824 0.097 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.163 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.436 1.211 0.727 0.533 0.436 0.048 0.000 0.048 0.048 0.000 0.000 0.000 0.048 0.000 0.000 0.000 3.537 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS G TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2064 73 73 2064 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2008/11/19 MEAN WIND SPEED = 14.68 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-121
METEOROLOGICAL DATA TABLES BROWNS FERRY NUCLEAR PLANT JANUARY - DECEMBER 2008 TABLE 25 JOINT FREQUENCY DISTRIBUTION IN PERCENT FOR ELEVATED RELEASES FOURTH QUARTER E2-122
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.136 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.227 0.000 0.000 0.000 0.000 0.000 0.045 0.591
- 0. 182 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.864 0.045 0.000 0.000 0.000 0.000 0.045 0.455 0.000 0.091 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.636 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.045 0.000 0.000 0.000 0.000 0.091 1.136 0.318 0.182 0.045 0.000 0.000 0.000 0.045 0.000 0.000 1.864 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS A TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 41 41 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED:
2009/03/04 MEAN WIND SPEED = 11.54 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-123
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B
(-1.9< DELTA T<=-1.7 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.000 0.000 o.0oo 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045
- 0. 045 0.000 0.000 0.000
- 0. 000 0.000 0.000 0.000 0.091 0.000 0.000 0.000 0.000 0.000 0.000 0.091 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.136 0.000 0.000 0.000 0.000 0.000 0.091 0.045 0.045 0.045 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.273 0.227 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.091 0.045 0.000 0.045 0.000 0.000 0.045 0.500 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.091 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.273 0.045 0.000 0.000 0.000 0.091 0.136 0.136 0.136 0.091 0.091 0.000 0.045 0.000 0.000 0.045 1.091 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS B TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 24 24 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED = 12.38 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-124
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C
(-1.7< DELTA T<=-1.5 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW
- NNW SUBTOTAL WIND SPEED (MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.045 0.045 0.045 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.182 0.091 0.000 0.000 0.000 0.000 0.182 0.182 0.000 0.000 0.136 0.000 0.000 0.000
- 0. 045 0.000
- 0. 045 0.682 0.500 0.000 0.000 0.000 0.000 0.045 0.182 0.091 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.091 0.909 0.045 0.000 0.000 0.000 0.000 0.000 0.045 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.045 0.227 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.636 0.000 0.000 0.000 0.000 0.273 0.455 0.273 0.045 0.136 0.000 0.000 0.000 0.045 0.045 0.182 2.091 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS C TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 46 46 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED = 13.48 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-125
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D
(-1.5< DELTA T<=-0.5 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NTW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.045 0.000 0.045 0.045 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.182 0.045 0.045 0.091 0.136 0.182 0.091 0.409 0.182 0.273 0.273 0.136 0.318 0.000 0.136 0.091 0.000 2.409 0.227 0.227 0.273 0.091
- 0. 136 0.500 0.682 0.364 0.136 0.455 0.409 0.227 0.091 0.227 0.136 0.182 4.364 0.091 0.500 0.409 0.318 0.045 0.455 0.273 0.182 0.227 0.227 0.182 0.318 0.182 0.091 0.136 0.136 3.773 0.955 1.045 0.500 0.182 0.182 0.773 0.273 0.364 0.591 0.091 0.227 0.682 0.773 0.955 0.545 0.909 9.045 1.273 0.727 0.000 0.000 0.136 0.136 0.455 0.273 0.045 0.091 0.091 0.818 0.773 1.045 1.318 1.136 8.318 0.500 0.091 0.045 0.000 0.000
- 0. 182 0.864 0.091 0.091 0.000 0.000 0.091 0.318 0.591 1.045 0.318 4.227 0.045 0.136 0.000 0.000 0.000 0.045 0.818 0.000 0.000 0.136 0.000 0.000 0.000 0.182 0.091 0.045 3.136 2.773 1.364 0.727 0.727 2.227 3.818 1.455 1.364 1.273 1.045 2.455 2.136 3.227 3.364 2.727 1.500 33.818 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS D TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 744 744 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED.AT 90.29 METER LEVEL MEAN WIND SPEED = 11.83 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-126
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E
(-0.5< DELTA T<= 1.5 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
>=24.5 TOTAL 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.045 0.045 0.182 0.045 0.000 0.091 0.091 0.273 0.091 0.091 0.045 0.045 0.136 0.091 0.273 0.045 0.000 0.045 0.091 1.455 0.091 0.045 0.045 0.045 0.000 0.227 0.409 0.000 0.182 0.136 0.136 0.045 0.045 0.045 0.091 0.045 1.591 0.091 0.182 0.045 0.045 0.091 0.409 0.227 0.182 0.455 0.136 0.273 0.136 0.273 0.136 0.091 0.091 2.864 0 318 0.636 0.500 0.227 0.273 0.727 1.273 1.227 0.955 0.273 0.636 0.818 0.864 0.500 0.136 0.409 9.773 0.955 0.455 0.727 0.455 0.273 1.818 1.727 0.909 0.500 0.273 0.273 0.500 0.409 0.545.
0.864 1.091 11.773 0.136 0.000 0.091 0.000 0.000 0.409 1.136 0.364 0.136 0.182 0.182 0.045 0.045 0.045 0.909 0.500 4.182 0.000 0.000 0.000 0.000 0.000 0.045 0.591 0.818 0.455 0.182 0.000 0.000 0.045 0.000 0.045 0.045 1.636 1.318 1.500 0.864 0.955 3.727 5.455 3.545 2.727 1.318 1.591 1.864 1.727 1.273 2.227 2.318 2.227 34.045 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS E TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 749 749 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED = 13.42 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-127
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F
( 1.5< DELTA T<= 4.0 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.000 0.000 0.045 0.000 0.000 0.045 0.045 0.000 0.136 0.091 0.045 0.045 0.045 0.000 0.045 0.091 0.000 0.045 0.091 0.727 0.000 0.000 0.045 0.000 0.045 0.000 0.136 0.182 0.045 0.091 0.045 0.182 0.136 0.045 0.000 0.000 0.955 0.000 0.091 0.000 0.000 0.000 0.091 0.182 0.045 0.136 0.091 0.182 0.045 0.091 0.045 0.000 0.000 1.000 0.273 0.045 0.091 0.318 0.227 0.455 0.727 1.091 0.773 0.136 0.182 0.273 0.136 0.091 0.136 0.136 5.091 0.864 0.864 0.500 0.364 0.136 0.273 0.364 0.591 0.273 0.364 0.045 0.000 0.000 0.000 0.182 0.409 5.227 0.000 0.091 0.136 0.000 0.000 0.000 0.091 0.682 0.045 0.091 0.000 0.000 0.000 0.000 0.091 0.000 1.227 0.000 0.000 0.000 0.000 0.000 0.000 0.182 0.864 0.545 0.091 0.000 0.000 0.000 0.000 0.000 0.000 1.136 1.091 0.818 0.727 0.409 0.955 1.773 3.500 1.864 0.909 0.455 0.591 0.455 0.182 0.455 0.636 1.682 15.955 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS F TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 351 351 2200
.0 METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL MEAN WIND SPEED = 13.44 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS DATE PRINTED: 2009/03/04 E2-128
JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)
Browns Ferry Nuclear Plant OCT 1, 2008 -
DEC 31, 2008 WIND DIRECTION N
NNE NE ENE E
WNW NW NNW SUBTOTAL WIND SPEED(MPH) 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4
>=24.5 TOTAL CALM 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.045 0.045 0.045 0.000 0.000 0.045 0.000 0.045 0.091 0.000 0.091 0.000 0.000 0.045 0.455 0.091 0.000 0.136 0.045 0.000 0.091 0.182 0.091 0.091
- 0. 045 0.000 0.136 0.227 0.318 0.091 0.182 1.727 0.136 0.045 0.000 0.364 0.273 0.455 0.318 0.318 0.136 0.136 0.045 0.091 0.182
- 0. 182 0.045 0.182 2.909 0.045 0.000 0.182 0.000 0.091 0.364 0.409 0.227 0.091 0.000 0.000 0.091 0.273 0.091 0.045 0.045 1.955 0.091 0.091 0.273 0.045 0.000 0.273 0.545 0.591 0.364 0.091 0.136 0.000 0.091 0.136 0.045 0.000 2.773 0.091 0.000 0.045 0.091 0.000 0.045 0.045 0.227 0.273 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.818 0.000 0.000 0.091 0.000 0.000 0.000 0.000 0.182 0.045 0.045 0.000 0.000 0.000 0.000 0.000 0.000 0.364 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.136 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.455 0.136 0.773 0.591 0.409 1.227 1.500 1.682 1.136 0.364 0.273 0.318 0.864 0.727 0.227 0.455 0.136 11.136 TOTAL HOURS OF VALID STABILITY OBSERVATIONS TOTAL HOURS OF STABILITY CLASS G TOTAL TOTAL TOTAL HOURS HOURS HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS CALM 2200 245 245 2200 0
METEOROLOGICAL FACILITY:
Browns Ferry Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 45.30 AND 89.59 METERS WIND SPEED AND DIRECTION MEASURED AT 90.29 METER LEVEL DATE PRINTED: 2009/03/04 MEAN WIND SPEED =
7.24 NOTE:
TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS E2-129
ENCLOSURE 3 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT (BFN)
UNITS 1, 2, AND 3 EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT JANUARY THROUGH DECEMBER 2008 E3-1
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 Regulatory and BFN ODCM Limits A.
Fission and Activation Gases in Gaseous Effluent:
The release of fission and activation gases is regulated by the dose limits of 10 CFR 50 Appendix I and BFN Offsite Dose Calculation Manual (ODCM). The air dose to areas at and beyond the site boundary due to noble gases released in gaseous effluents per unit, shall be limited during any calendar quarter to < 5 millirad (mrad) for gamma radiation and < 10 mrad for beta radiation; and during any calendar year to < 10 mrad for gamma radiation and
< 20 mrad for beta radiation.
B.
lodines and Particulates with Half-Lives Greater than Eight Days in Gaseous Effluents.
The release of iodines and particulates in gaseous effluent is regulated by the dose limits of 10 CFR 50 Appendix I and the BFN ODCM. The dose to a member of the public from radioiodines, radioactive materials in particulate form, and radionuclides other than noble gases with half-lives greater than eight days in gaseous effluent released per unit to areas at and beyond the site boundary shall be limited to any organ during any calendar quarter to < 7.5 millirem (mrem), and during any calendar year to < 15 mrem.
C.
Liquid Effluents The release of radioactive liquid effluents is regulated by the dose limits of 10 CFR 50 Appendix I and the BFN ODCM. The doses or dose commitment to a member of the public from radioactive materials in liquid effluents released from each unit to unrestricted areas shall be limited during any calendar quarter to < 1.5 mrem to the total body and <5 mrem to any organ and during any calendar year to < 3 mrem to the total body and < 10 mrem to any organ.
II.
Limitation on Dose Rate A.
Fission and Activation Gases in Gaseous Effluent:
I. The instantaneous release rate of fission and activation gases is based on the dose rate limits of 10 CFR 20.1301 and the BFN ODCM. The dose rate at any time to areas at and beyond the site boundary due to noble gases released in gaseous effluents from the site shall be limited to
< 500 mrem per year to the total body and < 3000 mrem per year to the skin.
E3-2
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 II.
Limitations on Dose Rate (Continued)
B.
lodines and Particulates with Half-Lives Greater than Eight Days in gaseous effluents.
- 1.
The instantaneous release rate of particulates and iodines is regulated by the dose rate limits of the BFN ODCM. The dose rate at any time to areas at and beyond the site boundary, due to 1-131, 1-133, H-3 and particulates with greater than eight days half-lives released in gaseous effluents from the site, shall be limited to < 1500 mrem per year to any organ.
- 2.
The BFN ODCM Section 7.3 determines the maximum particulate and iodine dose rates.
C.
Liquid Effluents
- 1. The concentration of radionuclides in liquid effluents released at any time from the site to unrestricted areas shall be limited to the concentrations specified in 10 CFR 20.1001 -
20.2402, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases.
- 2. For dissolved or entrained noble gases, the concentration shall be limited to 2E-4 pCi per milliliter (ml) total activity.
Ill.
Measurements and Approximations of Total Radioactivity A.
Fission and Activation Gases:
I. Noble gases in the building vent and stack (elevated) gaseous effluents are continuously monitored. The flow rate of the stack is continuously monitored and the building vent effluent flow rates are calculated once a shift based on the configuration of operating exhaust fans. The vent flow is calculated for each release. Gas grab samples of the stack are taken and analyzed weekly. Gas grab samples of in-service vents are taken and analyzed monthly. The specific noble gas activity concentrations and total volume of the gases are used to calculate the total Curies of noble gases released.
- 2. The tritium concentration is determined by the analysis of a monthly grab sample for each release point.
E3-3
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 Ill.
Measurements and Approximations of Total Radioactivity (continued)
B.
lodines and Particulates I.
lodines and particulates are continuously sampled on impregnated charcoal filters and particulate filters, respectively. The charcoal and particulate samples are replaced at least weekly and analyzed to determine specific activity concentrations. The specific activity concentrations and vent flow rate data are used weekly to verify that release rate limits were not exceeded. The specific activity concentrations and total volume of gaseous effluent are used on a monthly basis to determine the total Curies of each particulate and iodine released during the month.
- 2.
The gross alpha concentration is determined by analysis of a monthly particulate filter composite sample and strontium -89 and -90 are determined by analysis of a quarterly particulate filter composite sample for each release point.
C.
Liquid Effluents I.
The gamma ray emitting radionuclide concentrations are determined for each batch by gamma ray spectroscopy analysis of a grab sample. The allowable release rate is calculated for each batch based upon the known dilution flow. The flow rate of the liquid effluent is continuously monitored and the total volume released in each batch is determined. The total gamma activity released in each batch is determined by multiplying the radionuclide concentrations by the total volume discharged. The total gamma activity released during the month is then determined by summing the gamma activity content of each batch discharged during the month.
- 2.
The gross alpha and tritium concentrations are measured on a monthly composite sample. The strontium -89 and -90 and iron -55 are measured on a quarterly composite sample.
D.
The Radioactive Gaseous and Liquid Waste Monitoring Sampling and Analysis Program is specified in ODCM Sections 1/2.2.1 and 1/2.2.2.
E3-4
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT SUPPLEMENTAL INFORMATION 2008 IV.
Batch A. Liquid Quarer Quater Ouarer Quarter 1
2 3
4 Units 1.
2.
3.
4.
5.
6.
Number of batches released Each Total time for batches released Minutes Maximum time period for a batch release Minutes Average time period for a batch release Minutes Minimum time period for a batch release Minutes Average stream flow during period of release into a flowing stream Cubic feet per second 14 3399 300 243 200 15 3864 300 258 165 1
238 238 238 238 8
1925 340 241 135 32513 14255 18029 29719 B. Gaseous None C. Abnormal/Unplanned Releases*
Type Number of Releases Total Activity Releases (Curies)
Liquid Two Groundwater Leak 1.1 E-02 Ci/year (groundwater H-3) 5.5E-03 Curies H-3 4th Qtr to river 4.7 E-04 Curies F-I18 4th Qtr to river
- An explanation of any liquid or gaseous abnormal/unexplained release shall be documented in the summary.
E3-5
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT LIQUID EFFLUENTS - SUMMATION OF ALL RELEASES YEAR 2008 Units Quarter Quarter
)uarter 3
Quarter Error 4
A. Fission and Activation Products (Does not include tritium, gases, Alpha)
- 1.
Total Release
- 2.
Average Diluted Concentration Released During Period
- 3.
Percent of Applicable Limit B. Tritium
- 1.
Total Releases
- 2.
Average Diluted Concentration Released During Period
- 3.
Percent of Applicable Limit C. Dissolved and Entrained Noble Gases
- 1.
Total Releases
- 2.
Average Diluted Concentration Released During Period
- 3.
Percent of Applicable Limit D. Gross Alpha Radioactivity I.
Total Releases
- 2.
Average Diluted Concentration Released During Period E. Volume of Liquid Waste to Discharge Canal (Prior to dilution)
F.
Volume of Dilution Water for Period G. Total CCW 1
2 Curies 4.48E-03 2.50E-03 1.74E-04 4.23E-03**
9 g~Ci/ml 2.59E-10 2.31E-10 3.22E-10 4.09E-10 Curies 2.45E+00** 3.32E+00** 7.OOE-02**
1.51E+00**
6 PCi/mI 1.42E-07 3.07E-07 Curies 8.25E-05 3.57E-05 gCi/ml 4.77E-12 Curies ND*
3.31E-12 ND ND 1.77E+06 1.08 E+ 10 1.29E-08 ND ND ND ND 3.14E+04 5.41 E+08 1.45E-07 1.74E-05 8
1.68E-12 ND ND 48 jtCi/ml Liters Liters ND 1.71E+06 1.73E+10 6.86E+05 1.04E+I0 3
10 Gigagal. 2.43E+02 2.23E+02 2.78E+02 2.50E+02
- ND -- Not Detected. Dilution flow was not determined for the abnormal release.
- Includes activity from abnormal release.
- The applicable limit is expressed in terms of dose. See Enclosure 1, Tables 5 through 8.
E3-6
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT LIQUID RELEASES FOR YEAR 2008 - BATCH MODE CURIES Isotope Quarter Quarter Quarter Quarter (Required by Regulatory (REG) Guide 1.21) 1 2
3 4
I.
Ba-140 ND*
ND ND ND
- 2.
Ce-141 ND ND ND ND
- 3.
Co-58 ND 9.42E-06 ND 3.60E-05
- 4.
Co-60 1.21E-03 9.25E-04 8.28E-05 8.81E-04
- 5.
Cr-51 ND ND ND ND
- 6.
Cs-134 4.86E-04 1.80E-04 9.37E-06 2.28E-04
- 7.
Cs-137 2.70E-03 1.17E-03 6.45E-05 1.92E-03
- 8.
Fe-59 ND ND ND ND
- 9.
1-131 ND ND ND ND
- 10.
La-140 ND ND ND ND
- 11.
Mn-54 7.01E-05 1.23E-04 5.75E-06 7.34E-05
- 12.
Mo-99 ND ND ND ND
- 13.
Nb-95 ND ND ND ND
- 14.
Sr-89 ND ND ND ND
- 15.
Sr-90 ND ND ND ND
- 16.
Tc-99m ND ND ND ND
- 17.
Xe-133 3.97E-05 1.23E-05 ND 7.22E-06
- 18.
Xe-135 4.28E-05 2.34E-05 ND 1.02E-05
- 19.
Zn-65 ND 3.69E-06 ND 3.51E-04
- 20.
Zr-95 ND ND ND ND
- - Not Detected E3-7
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT LIQUID RELEASES FOR YEAR 2008 - BATCH MODE CURIES Isotope Others (Not Required by REG Guide 1.21)
Quarter Quarter 2
Quarter 3
Quarter 4
I.
F-18
- 2.
- 3.
Nb-97 4
Ag-10m ND*
ND 2.61 E-06 7.29E-05 ND 1.26E-05 9.27E-07 4.74E-04**
1.45E-05 1.08E-05 ND ND 6.63E-05 5.52E-06 2.16E-04 ND
- - Not Detected
- Activity from abnormal release.
E3-8
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES YEAR 2008 Units Quarter I
A. Fission and Activation Gases
- 1. Total Releases Curies
- 2. Average Release Rate for Period gCi/sec
- 3.
Percent of Applicable Limit B. lodines I. Total Iodine-131 Curies
- 2. Average Release Rate for Period ptCi/sec
- 3. Percent of Applicable Limit C. Particulates
- 1. Particulates with half-lives
> eight days Curies
- 2. Average Release Rate for Period ptCi/sec
- 3.
Percent of Applicable Limit
- 4. Gross Alpha Radioactivity Curies D. Tritium
- 1. Total Release Curies
- 2. Average Release Rate for Period jiCi/sec
- 3. Percent of Applicable Limit ND**
ND 4.15E-04 5.28E-05 1.62E-04 2.06E-05 ND 2.14E+01 2.73E+00 Quarter 2
ND ND 4.79E-04 6.09E-05 7.29E-05 9.27E-06 ND 5.60E+01 7.12E+00 Quarter 3
Quarter Error 4
ND ND ND ND 45 6.31E-04 5.51E-04 36 7.94E-05 6.93E-05 3.08E-05 3.87E-06 ND 7.63E+01 9.60E+00 1.35E-04 35 1.70E-05 ND 3.02E+01 21 3.80E+00
- Applicable Limits are expressed in terms of dose. See Enclosure 1, Tables I through 4.
- ND - Not Detected.
E3-9
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 GASEOUS EFFLUENTS - ELEVATED RELEASE Quarter Quarter Quarter Quarter 1
2 3
4 CURIES
- 1.
Fission Gases Kr-85m Kr-85 Kr-87 Kr-88 Xe-133 ND*
ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND Xe-135m Xe-135 Xe-138 Others (specify)
Total for Period
- 2.
lodines ND 1-131 1-133 Total for Period
- ND - Not Detected.
2.07E-04 6.07E-04 8.14E-04 1.85E-04 4.54E-04 6.39E-04 2.46E-04 4.05E-04 6.5 1E-04 2.17E-04 1.97E-04 4.14E-04 E3-10
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 GASEOUS EFFLUENTS - ELEVATED RELEASE Quarter Quarter Quarter 1
2 3
CURIES
- 3.
Particulates*
Sr-89 Sr-90 Cs-134 Cs-137 Ba-140 La-140 Others (specify)
Y-91m Cs-138 Ba-139 Total for Period*
- 4.
Tritium Quarter 4
2.09E-05 ND**
ND ND 4.15E-06 2.43E-06 1.03E-04 5.54E-03 1.16E-02 1.73E-02 1.02E+00 1.73E-05 ND ND ND ND ND 4.40E-05 3.41 E-03 2.52E-03 5.99E-03 2.64E+00 2.09E-05 ND ND 2.08E-06 2.32E-06 ND 1.1OE-04 ND 1.28E-02 1.30E-02 5.90E+00
- 1. 11E-05 ND ND ND ND ND 1.07E-05 ND 2.14E-03 2.16E-03 5.63E+00
- Includes all nuclides, even those with less than an eight day half-life.
- ND - Not Detected.
E3-11
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 GASEOUS EFFLUENTS - GROUND RELEASE CURIES Quarter Quarter Quarter Quarter 2
3 4
- 1.
Fission Gases Kr-85m ND*
ND ND ND Kr-85 ND ND ND ND Kr-87 ND ND ND ND Kr-88 ND ND ND ND Xe-133 ND ND ND ND Xe-135m ND ND ND ND Xe-135 ND ND ND ND Xe-138 ND ND ND ND Others(specify)
NONE Total for Period ND ND ND ND
- 2.
lodines 1-131 8.02E-05 5.72E-05 6.75E-05 9.96E-05 1-133 4.41E-04 2.58E-04 2.25E-04 7.67E-05 Total for Period 5.21E-04 3.15E-04 2.92E-04 1.76E-04
- ND - Not Detected.
E3-12
CURIES
- 3.
Particulates*
Sr-89 Sr-90 Cs-134 Cs-137 Ba-140 La-140 EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 GASEOUS EFFLUENTS - GROUND RELEASE Quarter Quarter Quarter 1
2 3
ND**
ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND ND Quarter 4
ND ND ND ND ND ND Others (specify)
Y-91m Cs-138 Ba-139 2.05E-05 5.97E-04 3.91 E-03 ND 8.68E-04 4.02E-03 ND ND 1.28E-03 1.28E-03 7.77E+00 ND ND 2.92E-04 2.92E-04 5.29E+00 Total for Period*
4.52E-03 4.89E-03
- 4.
Tritium 2.29E+00 4.44E+00
- Include all nuclides even those with less than an eight day half-life.
- ND - Not Detected.
E3-13
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 GASEOUS EFFLUENTS - MIXED MODE RELEASE*
CURIES Quarter Quarter Quarter Quarter 1
2 3
4 1
Fission Gases Kr-85m ND**
ND ND ND Kr-85 ND ND ND ND Kr-87 ND ND ND ND Kr-88 ND ND ND ND Xe-133 ND ND ND ND Xe-135m ND ND ND ND Xe-135 ND ND ND ND Xe-138 ND ND ND ND Others(specify)
NONE Total for Period ND ND ND ND
- 2.
lodines 1-131 1.28E-04 2.37E-04 3.18E-04 2.34E-04 1-133 8.51E-04 1.07E-03 9.96E-04 4.70E-04 Total for Period 9.80E-04 1.31 E-03 1.31 E-03 7.04E-04
- The Reactor Building and Radwaste Building are treated as split-level releases.
- ND - Not Detected.
E3-14
CURIES
- 3.
Particulates**
Sr-89 Sr-90 Cs-134 Cs-137 Ba-140 La-140 Others (specify)
Na-24 Mn-54 Co-58 Co-60 Zn-65 Y-91m EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 GASEOUS EFFLUENTS - MIXED MODE RELEASE*
Quarter Quarter Quarter 1
2 3
Quarter 4
ND***
ND ND 9.78E-06 ND ND 5.31E-07 1.39E-05 5.23E-06 1.08E-04 5.24E-08 ND ND ND ND 1.43E-05 ND ND ND ND ND 4.13E-05 ND ND ND ND ND 5.16E-06 ND ND ND ND ND 3.41 E-07 ND 7.05E-05 ND ND 8.06E-06 5.29E-05 ND ND ND 6.88E-06 1.25E-05 2.79E-05 ND 1.65E-04
- The Reactor Building and Radwaste Building are treated as split-level releases.
- Includes all nuclides, even those with less than an eight day half-life.
- N D - Not Detected.
E3-15
EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT YEAR 2008 GASEOUS EFFLUENTS - MIXED MODE RELEASE*
CURIES Quarter Quarter 2
Particulates**
(Continued)
Others (specify) 1 Mo-99 Tc-99m Ag-110m Ba-139 ND ND ND 1.06E-03 ND ND 1.05E-03 Quarter 3
ND ND ND 2.63E-03 2.70E-03 6.26E+0 1 7.54E-07 7.36E-07 1.59E-05 1.95E-04 4.85E-04 1.93E+01 Quarter 4
Total for Period**
1.20E-03
- 1. 1E-03 1.81E+01 4.89E+01
- 4.
- The Reactor Building and Radwaste Building are treated as split-level releases.
- Includes all nuclides, even those with less than an eight day half-life.
- ND - Not Detected.
E3-16
BROWNS FERRY NUCLEAR PLANT ANNUAL EFFLUENT AND WASTE DISPOSAL REPORT 2008 SOLID WASTE AND IRRADIATED FUEL A.
Solid Waste Shipped Off-site for Burial or Disposal (Not Irradiated Fuel)
- 1.
Type of Waste Units Amount Error %
- a.
Spent resins, filters, filter sludge m3 6.08E+01 evaporator bottoms, etc.
Ci 1.09E+03
+/-25.0
- b.
Dry compressible waste, contaminated equipment, etc.
- 1.
Shipped from site m3 2.55E+03 to processor Ci 2.70E+00
+/-25.0
- 2.
Estimated volume sent to m3 6.62E+02 burial by waste processor Ci 5.48E+01
+/-25.0
- c.
Irradiated components, control rod m3 0.OOE+00 blades & LPRMs with fission chambers Ci 0.OOE+00
+/-25.0
- d.
Other - Combined packages, fuel pool m3 1.28E+02 Components.
Ci 9.79E+02
+/-25.0
- 2.
Estimate of Maior Nuclide Composition by Waste Type
- a.
Spent resins, filters, filter sludge, evaporator bottoms, etc.
Nuclide Percentage Curies
- 1)
CO-60 4.36E+01 4.74E+02
- 2)
FE-55 2.60E+01 2.82E+02
- 3)
CS-137 1.04E+01 1.13E+02
- 4)
MN-54 8.83E+00 9.59E+01
- 5)
ZN-65 3.33E+00 3.62E+01
- 6)
CO-58 2.59E+00 2.81E+01
- 7)
CS-134 2.55E+00 2.77E+01
- 8)
CR-51 8.06E-0I 8.76E+00
- 9)
AG-110M 6.84E-01 7.43E+00
- 10)
NI-63 5.31E-01 5.77E+00
- 11)
FE-59 2.46E-01 2.67E+00
- 12)
CE-144 1.21E-01 1.31E+00
- 13)
CU-64 1.06E-01 1.15E+00
- 14)
PU-241 5.34E-02 5.80E-01
- 15)
ZR-95 4.60E-02 5.OOE-01
- 16)
NB-95 3.77E-02 4.09E-01 E3-17
Nuclide Percentage Curies
- 17)
SR-90 3.04E-02 3.30E-01
- 18)
C-14 1.91E-02 2.08E-01
- 19)
TC-99 1.54E-02 1.67E-01
- 20)
H-3 5.17E-03 5.62E-02
- 21)
CO-57 9.94E-04 1.08E-02
- 22)
NI-59 4.16E-04 4.52E-03
- 23) 1-131 3.77E-04 4.09E-03
- 24)
CE-141 2.43E-04 2.64E-03
- 25)
BA-140 2.28E-04 2.48E-03
- 26)
AM-241 1.33E-04 1.45E-03
- 27)
PU-238 1.11E-04 1.21E-03
- 28)
SR-89 7.55E-05 8.20E-04
- 29)
CM-242 6.OOE-05 6.52E-04
- 30)
CM-243 5.15E-05 5.59E-04
- 31)
CM-244 5.14E-05 5.58E-04
- 32)
PU-239 2.27E-05 2.47E-04
- 33)
PU-240 2.27E-05 2.47E-04
- 34)
LA-140 1.59E-07 1.73E-06
- 35) 1-133 3.74E-27 4.06E-26
- b.
Dry compressible waste, contaminated equipment, etc.
I)
CO-60 5.62E+01 1.52E+00
- 2)
FE-55 2.19E+01 5.93E-01
- 3)
MN-54 1.01E+01 2.72E-01
- 4)
CS-137 6.21E+00 1.68E-01
- 5)
ZN-65 2.92E+00 7.90E-02
- 6)
CS-134 1.65E+00 4.45E-02
- 7)
NI-63 5.55E-01 1.50E-02
- 8)
H-3 2.07E-01 5.60E-03
- 9)
CO-58 1.01E-01 2.73E-03
- 10)
NI-59 5.07E-02 1.37E-03
- 11)
CR-51 5.03E-02 1.36E-03
- 12)
PU-241 1.92E-02 5.20E-04
- 13)
C-14 4.40E-03 1.19E-04
- 14)
SR-90 3.77E-03 1.02E-04
- 15)
AM-241 2.72E-04 7.36E-06
- 16)
CM-243 1.09E-04 2.96E-06
- 17)
CM-244 1.09E-04 2.96E-06
- 18)
PU-238 1.05E-04 2.84E-06
- 19)
CM-242 9.17E-05 2.48E-06
- 20)
PU-239 2.56E-05 6.91E-07
- 21)
PU-240 2.56E-05 6.91E-07
- 22)
TC-99 1.96E-05 5.29E-07 E3-18
- c.
Irradiated components, Control Rod Blades & LPRMs with fission chambers None
- d. Other. Combined packages, non-irradiated fuel pool components.
Nuclide Percentage Curies
- 1)
CO-60 4.28E+01 4.19E+02
- 2)
FE-55 2.86E+01 2.80E+02
- 3)
MN-54 1.02E+01 9.98E+01
- 4)
CS-137 7.64E+00 7.48E+01
- 5)
CO-58 3.44E+00 3.37E+01
- 6)
ZN-65 3.12E+00 3.06E+01
- 7)
CS-134 1.67E+00 1.64E+01
- 8)
CR-51 9.20E-01 9.01E+00
- 9)
AG-I 10M 6.17E-01 6.04E+00
- 10)
NI-63 4.16E-01 4.07E+00 1I)
FE-59 2.71E-01 2.65E+00
- 12)
CE-144 1.06E-01 1.04E+00
- 13)
ZR-95 7.73E-02 7.57E-01
- 14)
NB-95 6.11E-02 5.98E-01
- 15)
PU-241 5.18E-02 5.07E-01
- 16)
SR-90 2.81E-02 2.75E-01
- 17)
C-14 1.63E-03 1.60E-02
- 18)
H-3 1.18E-03 1.16E-02
- 19)
TC-99 4.19E-04 4.1OE-03
- 20)
MO-99 2.53E-04 2.48E-03
- 21)
NI-59 2.01E-04 1.97E-03
- 22)
AM-241 9.53E-05 9.33E704
- 23)
PU-238 8.07E-05 7.90E-04
- 24)
CM-242 4.95E-05 4.85E-04
- 25)
SR-89 4.73E-05 4.63E-04
- 26)
CM-243 3.31E-05 3.24E-04
- 27)
CM-244 3.3 1E-05 3.24E-04
- 28)
CO-57 2.89E-05 2.83E-04
- 29)
P1-239 1.70E-05 1.66E-04
- 30)
PU-240 1.70E-05 1.66E-04
- 31)
NA-24 6.33E-09 6.20E-08
- 32)
TC-99M 2.03E-17 1.99E-16 E3-19
- 3.
Solid Waste Disposition Number of Shipments 12 Mode of Transportation HIC/Cask, Sole Use Truck Destination Barnwell Waste Management Barnwell, SC 59 19 Sole Use Truck Non-Sole Use Truck Duratek Services Oak Ridge, TN Duratek, Inc.
Kingston, TN B.
Irradiated Fuel Disposition Number of Shipments None Mode of Transportation N/A Destination N/A E3-20
BROWNS FERRY NUCLEAR PLANT EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT
SUMMARY
OF ABNORMAL/UNPLANNED RELEASES 2008 The release of radioactive material to the environment from Browns Ferry has been a small fraction of the 10 CFR 20 Appendix B and 10 CFR 50 Appendix I limits. There were no limits exceeded as specified in 10 CFR 20 Appendix B and 10 CFR 50 Appendix I.
No abnormal gaseous releases occurred in 2008. Two abnormal liquid releases occurred in 2008. One based on tritium identified in groundwater samples and a second due to a leak that was detected January 8, 2009 (Problem Evaluation Reports 160665 and 162203).
Onsite groundwater monitoring locations were sampled during the year. These locations were not part of BFN Radiological Environmental Monitoring Program (REMP). The purpose of these shallow wells was to monitor for potential leaks from plant equipment. Trace levels of tritium were detected in two of these monitoring locations. BFN initiated a groundwater study to identify the source of the tritium. Results from a groundwater study completed in June 2006 suggest the source of the tritiated groundwater is associated with the Radwaste/Condensate Transfer tunnel. Water that may leak into the tunnel could egress via expansion joints and/or cracks through the tunnel wall. The highest concentration identified in the groundwater for the year was 11,500 pCi/L. Groundwater and surface water level measurements during the study indicated the return channel and subsequently the Tennessee River will ultimately be recipient to tritiated groundwater discharge from the site. The estimated groundwater/channel water dilution ratio is 1:20,000 at a rate of approximately 0.5 gpm. Using the highest measured tritium concentration in groundwater, (11,500 pCi/L at the source of the plume) the aqueous tritium concentration in the channel would be 0.58 pCi/L. Assuming this concentration and release rate for the entire year results in a release of approximately 1.1E-02 Ci/year. This is a small fraction of the liquid radwaste and gaseous releases for 2008 and would result in a small fraction of the reported dose.
Samples of Units 1, 2, and 3 station sumps are analyzed monthly for contamination. No samples showed activity in 2008; however, the Unit I sample collected in January 2009, showed traces of both F-I 8 (1.3E-07 ýtCi/ml) and H-3 (1.5E-06 [tCi/ml). The total release for 2008 is estimated at F-18 (4.7E-04 Ci) and H-3 (5.5E-03 Ci). The sumps empty into the river. This is a small fraction of the liquid radwaste releases for 2008 and would result in a small fraction of the reported dose (<lE-07 mrem).
Investigation of the source of this release is ongoing and the contribution to the 2009 report will be reported.
Missed Compensatory Samples During the reporting period, January 1 through December 31, 2008, there was one missed compensatory sample. During a maintenance procedure, on July 10, 2008 at 10:08, a jumper was installed rendering the unit 2 Off-Gas Post Treatment Radiation Monitors 2-RM-090-265 and -266 inoperable. The ODCM requires a compensatory sample once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> when both monitors are inoperable. Inadequate communications resulted in exceeding the 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> sampling requirement. The sample was taken at 18:48.
The sample was 40 minutes late. No activity was found in the sample. (PER 148128)
E3-21
Changes to the Radwaste System and Changes to the Process Control Program (PCP)
In calendar year 2008, Browns Ferry had one change to the radwaste system and no changes to the Process Control Program (PCP).
A design change (Design Change Notice (DCN) 67609A) was completed to retire in place a flow element, and remove from service a flow modifier, flow switch, and flow indicator associated with the Cooling Tower Blow-down flow. Cooling Tower Blow-down flow is used for dilution for Liquid Radwaste releases when all units are operating in Helper Mode. The interlock and alarm associated with the flow switch were removed.
A conservative dilution flow rate is used for determining the set points for the Liquid Radwaste monitor while in helper mode. In addition, flow through the Cooling Tower line must be verified during Radwaste discharge while in Helper Mode, by visual observation. Radwaste Discharge while in Helper Mode is rare.
E3-22
ENCLOSURE 4 TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT (BFN)
UNITS 1, 2, AND 3 INOPERABLE RADIOLOGICAL EFFLUENT INSTRUMENTATION REPORT JANUARY THROUGH DECEMBER 2008 E4-1
INOPERABLE RADIOLOGICAL EFFLUENT INSTRUMENTATION REPORT 2008 This report is to comply with Browns Ferry Nuclear Plant Offsite Dose Calculation Manual (Offsite Dose Calculation Manual (ODCM)) Sections 1/2.1.1 and 1/2.1.2. The ODCM requires the exertion of best efforts to return inoperable instruments to operable status within 30 days. Failure to return such instruments to an operable status within the prescribed interval requires a description in the Annual Radioactive Effluent Release Report.
During the reporting period, January 1 through December 31, 2008, there were no radioactive gaseous effluent monitoring instruments out of service for greater than 30 days.
One Residual Heat Removal Service Water (RHR SW) monitor (2-RM-90-133D) was inoperable from March 17, 2008, to May 09, 2008 due to the sample pump tripping on low flow (PER 142731). A PER action establishing an expectation in an BFN Operations Daily Instruction (ODI) dated September 05, 2008 for unplanned Limiting Condition of Operations (LCO) that exceed 50% of the LCO time will be escalated in priority and consideration of twenty-four support will be made to ensure timely resolution.
All compensatory measures were followed.
E4-2