ECCS Instrumentation 3.3.5.1 Table 3.3.5.1-1 (page 3 of 6)

Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES REQUIRED REFERENCED OR OTHER CHANNELS FROM SPECIFIED PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION A.1 REQUIREMENTS VALUE

2.

LPCI System

e.

Reactor Steam Dome Pressure Permissive - Bypass Timer (Pump Permissive) 1,2,3 4 (a) 5 (a) 2 2

C SR 3.3.5.1.7 SR 3.3.5.1.8 B

SR 3.3.5.1.7 SR 3.3.5.1.8

> 18 minutes and

_ 22 minutes

> 18 minutes and

< 22 minutes

f.

Low Pressure Coolant Injection Pump Start - Time Delay Relay 1,2,3, 4 (a) 5 (a) 4 per pump B

SR 3.3.5.1.7 SR 3.3.5.1.8 Pumps A, B Pumps C, D

g.

Low Pressure Coolant Injection Pump Discharge Flow - Low (Bypass)

h.

Reactor Steam Dome Pressure -

Low (Break Detection)

Recirculation Pump Differential Pressure

- High (Break Detection)

j.

Recirculation Riser Differential Pressure

- High (Break Detection)

k.

Reactor Steam Dome Pressure -

Time Delay Relay (Break Detection) 1,2,3, 4(a), 5 (a) 1,2,3, 1 per pump 4

1,2,3 4 per pump E

SR SR SR B

SR SR SR C

SR SR SR C

SR SR SR B

SR SR SR 3.3.5.1.2 3.3.5.1.7 3.3.5.1.8 3.3.5.1.2 3.3.5.1.7 3.3.5.1.8 3.3.5.1.2 3.3.5.1.7 3.3.5.1.8 3.3.5.1.2 3.3.5.1.6 3.3.5.1.8 3.3.5.1.2 3.3.5.1.4 3.3.5.1.8

< 5.33 seconds

_< 10.59 seconds

>_ 360 gpm and 5 745 gpm

>_ 873.6 psig and

9 923.4 psig

_ 63.5 inches wc

< 24.0 inches wc

  • 2.79 seconds 1,2,3 4

1,2,3 2

(a)

When associated ECCS subsystem(s) are required to be OPERABLE per LCO 3.5.2.

Monticello 3.3.5.1-8

-A^erncm-nt Ne. 44 G Correction letter of 10/12/06