ML062480197
| ML062480197 | |
| Person / Time | |
|---|---|
| Site: | Oconee (DPR-055) |
| Issue date: | 08/31/2006 |
| From: | Brandi Hamilton Duke Energy Carolinas, Duke Power Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| Download: ML062480197 (170) | |
Text
Duke BRUCE H HAMILTON Vice President Potwer.
Oconee Nuclear Station Duke Power ONO1 VP / 7800 Rocherster Highway Seneca, SC 29672 864 885 3487 864 885 4208 fax August 31, 2006 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555
Subject:
Duke Power Company LLC d/b/a Duke Energy Carolinas, LLC (Duke)
Oconee Nuclear Station, Unit 3 Docket No. 50-287 Unit 3 EOC 22 Refueling Outage Inservice Inspection Report Fourth Ten-Year Inservice Inspection Interval Please find attached a copy of the Inservice Inspection Report for Oconee Unit 3 End of Cycle 22 Refueling Outage. This report is submitted pursuant to Section XI of the ASME Boiler and Pressure Vessel Code, 1998 Edition, with 2000 addenda, Subsubarticle IWA 6230.
Section 6 of the report provides a summary of pressure testing. One portion of Section 6 addresses the updated completion status of pressure tests conducted for the Third Interval. This includes an inspection performed on Unit 3 during the Fourth Interval for which credit is taken as meeting Third Interval requirements in accordance with Relief Request 04-ON-013, Rev 1. (approved by NRC 7/11/2006, see ADAMS Accession Number ML061650360). The remainder of Section 6 provides a summary of pressure testing for the first period of the Fourth Interval.
If there are any questions you may contact R. P. Todd at (864) 885-3418.
B. H. Hamilton, Site Vice-President Oconee Nuclear Station Attachment www.duke power. corn 1 J61
INSERVICE INSPECTION REPORT DUKE ENERGY OCONEE NUCLEAR STATION UNIT 3 TWENTY-SECOND REFUELING OUTAGE P Duke vEnergyo
Owner's Report For INSERVICE INSPECTIONS OCONEE UNIT 3 2006 REFUELING OUTAGE EOC22 (OUTAGE 1)
Plant Location: 7800 Rochester Highway, Seneca, South Carolina 29672 NRC Docket No. 50-287 Commercial Service Date: December 16, 1974 Document Completion Date f- ?-,- o G Owner: Duke Energy 526 South Church St.
Charlotte, N. C. 28201-1006 Revision 0
&J-Uý C. Ka4 Prepared By:
Reviewed By:
Approved By:
ZT Date C 0 (o Date 5-7-6 Date
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules
- 1.
Owner: Duke Energy, 526 S. Church St.. Charlotte, NC 28201-1006 (Name and Address of Owner)
- 2. Plant: Oconee Nuclear Station, 7800 Rochester Highway, Seneca, SC 29672 (Name and Address of Plant)
- 3. Plant Unit: 3
- 4.
Owner Certificate of Authorization (if required) N/A
- 5. Commercial Service Date: December 16, 1974
- 7.
Components Inspected:
- 6. National Board Number for Unit N/A Component or Appurtenance Manufacturer Installer Manufacturer Installer Serial No.
State or Province No.
National Board No.
ý-W)
See Section 1.1 in the Attached Report Note:
Supplemental sheets in the form of lists, sketches, or drawings may be used provided (1) size is 81/2 in. x 11 in., (2) information in items I through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
Total number of pages contained in this report 168.
FORM NIS-1 (Back)
- 8.
Examination Dates January 2, 2005 to June 2, 2006
- 9.
Inspection Period Identification:
- 10.
Inspection Interval Identification:
- 11.
Applicable Edition of Section XI
- 12.
Date/Revision of Inspection Plan:
First Period Fourth Interval 1998 Addenda 2000 November 18, 2004 / Revision 0
- 13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan.
See Sections 2.0. 3.0 and 6.0
- 14. Abstract of Results of Examination and Tests.
- 15. Abstract of Corrective Measures.
See Sections 4.0 and 6.0 See Subsection 4.3 We certify that a) the statements made in this report are correct b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.
Certificate of Authorization No. (if applicable)
NA Expiration Date NA Date 1/0 Signed Duke Energy Corp.
By Owner CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Al/ r/' *ýUozwo employed by *The HSBI&I Co. of Connecticut have inspected the components described in this Owner's Report during the period
/- Z -"0s to
- c;,&
, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in the Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, test, and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection Commissions
/*'Q/"
dC
'i-- 7nlspector's Signature Date c-/-o6 National Board, State, Province, and Endorsements
- The Hartford Steam Boiler Inspection & Insurance Company of Connecticut.
200 Ashford Center North Suite 205 Atlanta, GA. 30338-4860 (800) 417-3721 www.hsbc.com
DISTRIBUTION LIST
- 1.
Duke Energy Nuclear Quality Assurance and Oversight Division Quality Assurance Technical Services
- 2.
NRC Document Control Desk
- 3.
Hartford Steam Boiler Inspection and Insurance Company of Connecticut (AIA) c/o ANII at Oconee Note: The following personnel are to be notified via e-mail after the Inservice Inspection Report has been stored in the Nuclear Electronic Document Library:
GO Nuclear Assurance C/o Bruce Nardoci Inspection and Welding Services (ISI Coordinator)
TABLE OF CONTENTS Section Title Revision 1.0 General Information 0
2.0 Fourth Ten Year Interval Inspection Status 0
3.0 Final Inservice Inspection Plan 0
4.0 Results of Inspections Performed 0
5.0 Owners Report for Repair/Replacement Activities 0
6.0 Pressure Testing 0
1.0 General Information This report describes the Inservice Inspection of Duke Energy's Oconee Nuclear Station, Unit 3, during Outage 1/EOC 22. This is the first outage in the first inspection period of the Fourth Ten-Year Interval. ASME Section XI, 1998 Edition with the 2000 Addenda, was the governing Code for selection and performing of the ISI examinations.
In addition to the inservice inspections performed during EOC-22 as described in the above paragraph, Section 6.0 of this report contains an EOC-21 pressure test summary for tests that were performed to meet the requirements for the third inspection period of the Third Ten-Year Interval. Section 6.0 also contains a pressure test summary for EOC-22 which is for the first inspection period of the Fourth Ten-Year Interval. Relief Request 04-ON-013, Revision 1 was written and approved to allow performing third interval pressure test during the fourth interval.
Included in this report are: the inspection status for each examination category, the final inservice inspection plan, the inspection results for each item examined, and corrective actions taken when reportable conditions were found. In addition, there is an Owner's Report for Repair/Replacement Section included for completed NIS-2 documentation of repairs and replacements.
1.1 Identification Numbers Manufacturer Item Manufacturer or Installer State or National or Installer Serial No.
Province No.
Board No.
Reactor Vessel Babcock & Wilcox 620-0009-51-52 N/A N-1 25 Reactor Vessel Babcock & Wilcox 068S-03 N/A 200 Head (replaced head)
Steam Generator A Babcock & Wilcox 006K05 N/A 211 Steam Generator B Babcock & Wilcox 006K06 N/A 212 Pressurizer Babcock & Wilcox 620-0009-59 N/A N-126 Main Steam Duke Power NA NA NA System Auxiliary Steam Duke Power NA NA NA System Feedwater System Duke Power NA NA NA EOC 22 Refueling Outage Report Oconee Unit 3 Section 1 Page 1 of 4 Revision 0 August 3, 2006
Manufacturer Item Manufacturer or Installer State or National or Installer Serial No.
Province No.
Board No.
Emergency Duke Power NA NA NA Feedwater System Steam Generator Duke Power NA NA NA Flush System Condensate Duke Power NA NA NA System Vents and Exhaust Duke Power NA NA NA System Condenser Duke Power NA NA NA Circulating Water High Pressure Duke Power NA NA NA Service Water System Low Pressure Duke Power NA NA NA Service Water System Reactor Coolant Duke Power NA NA NA System High Pressure Duke Power NA NA NA Injection System Low Pressure Duke Power NA NA NA Injection System Reactor Building Duke Power NA NA NA Spray System Component Duke Power NA NA NA Cooling System Spent Fuel Cooling Duke Power NA NA NA System Vents - Reactor Duke Power NA NA NA Building Components Drains - Reactor Duke Power NA NA NA Building Components EOC 22 Refueling Outage Report Oconee Unit 3 Section 1 Page 2 of 4 Revision 0 August 3, 2006
1.2 Personnel, Equipment and Material Certifications All personnel who performed or evaluated the results of inservice inspections during the time frame bracketed by the examination dates shown on the NIS-1 Form were certified in accordance with the requirements of the 1998 Edition of ASME Section XI with the 2000 addenda including Appendix VII for ultrasonic inspections. In addition, ultrasonic examiners were qualified in accordance with ASME Section XI, Appendix VIII, and thel 998 Edition with the 2000 Addenda through the Performance Demonstration Initiative (PDI) for similar metal piping welds (Supplements 2 & 3) and bolting (Supplement 8). The reactor vessel flange to shell weld was examined in accordance with ASME Section V, Article 4 with Regulatory Guide 1.150.
The appropriate certification records for each inspector, calibration records for inspection equipment, and records of materials used (i.e., NDE consumables) are on file at Oconee Nuclear Station or copies can be obtained by contacting Duke Energy's Corporate Office in Charlotte, North Carolina.
The copies of the certification records for Washington Group International inspectors and Atlantic Group inspectors can be obtained by contacting Duke Energy's Corporate Office in Charlotte, North Carolina.
1.3 Reference Documents The following reference documents apply to the inservice inspections performed during this report period. A copy may be obtained by contacting the ISI Plan Manager at Duke Energy's Corporate Office in Charlotte, North Carolina.
Code Case N-460 (Applicable to items in this report where less than 100%
coverage of the required weld examination volume was achieved.) These items are identified on the Run D that is located in Section 4 of this report.
Duke Power Company Problem Investigation Process Report # 0-06-04344.
This PIP was written to track the Relief Request process for limited coverage on UT examinations of welds that were inspected during EOC-22 for Unit 3.
Duke Power Company Problem Investigation Process Report # 0-06-02812.
This PIP was written to track the correction of problems found with a support during an augmented inspection. (Support 3-03-0-2401A-H51, Item Number H04.001.005)
Request for Relief 03-006 (Allows Duke and Alternative for the Snubber Examinations required in IWF-5000 for the 4 th interval.)
EOC 22 Refueling Outage Report Page 3 of 4 Oconee Unit 3 Revision 0 Section 1 August 3, 2006
Request for Relief 04-ON-013, Revision 1 (Allows Duke to perform 3 rd interval pressure test during the 4 th interval.)
1.4 Augmented and Elective Examinations Augmented and elective examination information found within this Inservice Inspection Report is not required by the ASME Section XI Code; therefore, it is exempt from ANII review, verification, and/or record certification.
1.5 Responsible Inspection Aqencv The Hartford Steam Boiler Inspection and Insurance Company of Connecticut is responsible for the third party inspections required by ASME Section XI.
Authorized Nuclear Inservice Inspector(s)
Name:
Employer:
Business Address:
Gary Brouette, Nancy Slaughter, William Huber, and Mike Chapman The Hartford Steam Boiler Inspection & Insurance Company of Connecticut.
200 Ashford Center North Suite 205 Atlanta, GA 30338-4860 (800) 417-3721 www.hsbct.com EOC 22 Refueling Outage Report Oconee Unit 3 Section 1 Page 4 of 4 Revision 0 August 3, 2006
2.0 Fourth Ten Year Interval Inspection Status The completion status of inspections required by the 1998 ASME Code Section XI, with the 2000 Addenda, is summarized in this section. The requirements are listed by the ASME Section XI Examination Category as defined in Table IWB-2500-1 for Class 1 Inspections, Table IWC-2500-1 for Class 2 Inspections, and IWF-2500-1 for Class 1 and 2 Component Supports. Augmented inspections are also included.
Class 1 Inspections Examination Inspections Inspections Percentage
- Deferral Category Description Required Completed Completed Allowed B-A Pressure Retaining Welds 6 Welds
.5 Weld 8%
Yes in Reactor Vessel B-B Pressure Retaining Welds 10 Welds 0 Welds 0%
No in Vessels Other than Reactor Vessel B-D Full Penetration Welds of 54 0
0%
Partial Nozzles in Vessels Inspections Inspections Inspection Program B B-E Pressure Retaining Partial Penetration Welds in REFERENCE SECTION 6.0 OF THIS REPORT Vessels B-F Pressure Retaining 7 Welds 0 Welds 0%
No Dissimilar Metal Welds B-G-1 Pressure Retaining Bolting 128 Items 43.33 Items 34%
Yes Greater than 2 Inches in Diameter B-G-2 Pressure Retaining Bolting 16 Items 2 Items 13%
No 2 Inches and Less in Diameter B-J Pressure Retaining Welds 163 Welds 20 Welds 12%
No in Piping B-K Welded Attachments for 15 1
7%
No Vessels, Piping, Pumps and Valves Deferral of inspection to the end of the interval as allowed by ASME Section XI Tables IWB and IWC 2500-1.
EOC 22 Refueling Outage Report Oconee Unit 3 Section 2 Page 1 of 4 Revision 0 August 3, 2006
Class 1 Inspections (Continued)
Examination Inspections Inspections Percentage Deferral Category Description Required Completed Completed Allowed B-L-1 Pressure Retaining Welds 1 Weld 0 Weld 0%
Yes in Pump Casings B-L-2 Pump Casings 1 Casing 0 Casing 0%
Yes B-M-1 Pressure Retaining 1 Valve Body 0 Valve Body 0%
Yes Welds in Valve Bodies Weld Weld B-M-2 Valve Bodies 3 Valves 0 Valves 0%
Yes B-N-1 Interior of Reactor Vessel 3 Inspections 0 Inspection 0%
No B-N-2 Welded Core Support 1 Inspection 0 Inspections 0%
Yes Structures and Interior Attachments to Reactor Vessels B-N-3 Removable Core Support 1 Inspection 0 Inspections 0%
Yes Structures I
I I
B-0 Pressure Retaining Welds 12 Housing 4 Housing 33%
Yes in Control Rod Housings Welds Welds B-P All Pressure Retaining Components REFERENCE SECTION 6.0 OF THIS REPORT B-Q Steam Generator Tubing N/A N/A N/A N/A F-A Class 1 Component 36 Supports 6 Supports 17%
No F1.10& F1.040 Supports (Except items.
F-A Class 1 Component F1.050 items Supports, Snubbers I
- Deferral of inspection to the end of the interval as allowed by ASME Section XI Tables IWB and IWC 2500-1.
- Inspected under Selected License Commitment 16.9.18 per Relief Request 03-006 EOC 22 Refueling Outage Report Oconee Unit 3 Section 2 Page 2 of 4 Revision 0 August 3, 2006
Class 2 Inspections Examination Inspections Inspections Percentage
- Deferral Category Description Required Completed Completed Allowed C-A Pressure Retaining Welds 11 Welds 0 Welds 0%
No in Pressure Vessels C-B Pressure Retaining Nozzle 4 Welds 0 Welds 0%
No Welds in Vessels C-C Integral Attachments for 33 4
12%
No Vessels, Piping, Pumps Attachments Attachments and Valves C-D Pressure Retaining Bolting 2 Items 1 Items 50%
No Greater Than 2 Inches in Diameter C-F-1 Pressure Retaining Welds 166 Welds 13 Welds 8%
No in Austenitic Stainless Steel or High Alloy Piping C-F-2 Pressure Retaining Welds 67 Welds 8 Welds 12%
No in Carbon or Low Alloy Steel Piping C-G Pressure Retaining Welds N/A N/A N/A N/A in Pumps and Valves C-H All Pressure Retaining Components REFERENCE SECTION 6.0 OF THIS REPORT F-A Class 2 Component 138 Supports 16 Supports 12%
No F1.020 & F1.040 Supports (Except items.
F-A Class 2 Component F1.050 items Supports, Snubbers L
Deferral of inspection to the end of the interval as allowed by ASME Section XI Tables IWB and IWC 2500-1.
"* Inspected under Selected License Commitment 16.9.18 per Relief Request 03-006 EOC 22 Refueling Outage Report Oconee Unit 3 Section 2 Page 3 of 4 Revision 0 August 3, 2006
Augmented/Elective Inspections Augmented and elective examination information found within this Inservice Inspection Report is not required by the ASME Section XI Code; therefore, it is exempt from ANII review, verification, and/or record certification.
Item.
Number Description Percentage Complete GO1.001 Reactor Coolant Pump Flywheel None scheduled for EOC 22 G02.001 HPI Nozzle Safe End Examinations None scheduled for EOC 22 G03.001 Pressurizer Surge Line Examinations None scheduled for EOC 22 G04.001 Thermal Stress Piping (NRC Bulletin None scheduled for EOC 22 88-08)
G1i1.001.001 Reactor Pressure Vessel Head None scheduled for EOC 22 Penetration Nozzle by UT Examination per NRC Order EA-03-009.
G1i1.001.002 Bare Metal Visual Examination of the None scheduled for EOC 22 Reactor Pressure Vessel Head Surface per NRC Order EA-03-009.
G12.001 UT Examination per MRP-139 None scheduled for EOC 22 G12.002 UT Examination per MRP-139 None scheduled for EOC 22 G12.003 UT Examination per MRP-139 None scheduled for EOC 22 G13.001 VT-2 Bare Metal Visual per MRP-139 None scheduled for EOC 22 G13.002 VT-2 Bare Metal Visual per MRP-139 None scheduled for EOC 22 G14.001 VT-2 Bare Metal Visual per Oconee None scheduled for EOC 22 Response to BL-2004-01 H01.001 Pressurizer Sensing/ Sampling Nozzle None scheduled for EOC 22 Safe Ends H02.001 Class 1 RTE Mounting Bosses None scheduled for EOC 22 H03.001 Main Feedwater Piping in the East and 100% of EOC 22 Requirements West Penetration Rooms per QA-513J (ER-ONS-04-03)
H04.001 Main Feedwater and Main Steam Piping 100% of EOC 22 Requirements Supports and Attachment Welds per QA-513J (ER-ONS-04-05)
I EOC 22 Refueling Outage Report Oconee Unit 3 Section 2 Page 4 of 4 Revision 0 August 3, 2006
3.0 Final Inservice Inspection Plan The final Inservice Inspection Plan shown in this section lists all ASME Section XI Class 1, Class 2, Class 3, and Augmented examinations credited for this report period.
The information shown below is a field description for the reporting format included in this section of the report:
Item Number ID Number Sys Iso / Dwg. Numbers Proc Insp Req.
Mat / Sch.
Diam. / Thick Cal Blocks Comments
=
ASME Section XI Tables IWB-2500-1 (Class 1), IWC-2500-1 (Class 2), IWF-2500-1 (Class 1 and Class 2 ), Augmented Requirements
=
Unique Identification Number
=
Component System Identification
=
Location and/or Detail Drawings
=
Examination Procedures Examination Technique - Magnetic Particle, Dye Penetrant, etc.
General Description of Material
=
Diameter/Thickness Calibration Block Number General and/or Detail Description EOC 22 Refueling Outage Report Oconee Unit 3 Section 3 Page 1 of 1 Revision 0 August 3, 2006
EOC 22 CATEGORY B-A, Pressure Retaininq Welds In DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 C-Reactor Vessel Shell-to-Flan e Weld ITEM NUMBER ID NUMBER Plan Report Page 1 08/03/2006 SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS B01.030.001A 3-RPV-WR19 Circumferential Class A ISI-OCN3.001 50 OM-2201-227 NDE-650 UT CS 167.630 CB-08-99 Reactor Vessel Upper Shell Forging Pc. 86 to 12.000 Flange Pc. 7. Inspect from Flange Surface (manual Shell to scan).
Flange Total B01.030 Items:
Total B01 Items:
1 1
EOC 22 CATEGORY B-G-1, Pressure Retaining Bolting, DUKE ENERG CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 C
Greater Than 2 in. In Diameter Reactor Vessel ITEM NUMBER ID NUMBER Plan Report Page 2 08/0312006 SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Closure Head Nuts ****
B06.010.041 3-RPV-26-209-41 Class A B06.010.042 3-RPV-26-209-42 Class A B06.010.043 3-RPV-26-209-43 Class A B06.010.044 3-RPV-26-209-69 Class A OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OAL-13 VT-1 OAL-13 OAL-13 VT-1 OAL-13 VT-1 VT-1 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 Reactor Vessel Closure Head Nut.
Reactor Vessel Closure Head Nut.
Reactor Vessel Closure Head Nut.
Reactor Vessel Closure Head Nut.
B06.010.045 3-RPV-26-209-45 OAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A B06.010.046 3-RPV-26-209-46 QAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A B06.010.047 3-RPV-26-209-47 QAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A B06.010.048 3-RPV-26-209-48 OAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A
EOC 22 Y--
DUKE ENERGY CORPORATION CATEGORY B-G-I, Pressure Retaininq Bolting, INSERVICE INSPECTION PLAN MANAGEMENT C
Greater Than 2 in. In Diameter Reactor Vessel ITEM NUMBER ID NUMBER B06.010.049 3-RPV-26-209-49 Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 Plan Report Page 3 08/03/2006 SYS ISO/DWG NUMBERS OM 201-2271 50 B&W 149922 PROC INSP REQ MAT/SCH OAL-13 VT-1 CS DIA/THK CAL BLOCKS COMMENTS 9.250 Reactor Vessel Closure Head Nut.
1.300 Class A B06.010.050 3-RPV-26-209-50 Class A B06.010.051 3-RPV-26-209-51 Class A B06.010.052 3-RPV-26-209-52 Class A B06.010.053 3-RPV-26-209-53 Class A OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OAL-13 OAL-13 VT-1 VT-1 OAL-13 OAL-13 VT-1 VT-1 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 CS 9.250 1.300 Reactor Vessel Closure Head Nut.
Reactor Vessel Closure Head Nut.
Reactor Vessel Closure Head Nut.
Reactor Vessel Closure Head Nut.
B06.010.054 3-RPV-26-209-54 OAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A B06.010.055 3-RPV-26-209-55 QAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A B06.010.056 3-RPV-26-209-56 QAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A B06.010.057 3-RPV-26-209-57 QAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A
EOC 22 DUKE ENERCORPORATION CATEGORY B-G-1, Pressure Retaining Bolting, INSERVICE INSPECTION PLAN MANAGEMENT Greater Than 2 in. In Diameter Inservice Inspection Database Management System Reactor Vessel Oconee 3 N
Inservice Inspection Plan for Interval 4 Outag ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK C/
B06.010.058 3-RPV-26-209-58 OM 201-2271 OAL-13 VT-1 CS 9.250 50 B&W 149922 1.300 Class A 41 Plan Report Page 4 e 1 08/03/2006
,L BLOCKS COMMENTS Reactor Vessel Closure Head Nut.
B06.010.059 3-RPV-26-209-59 OM 201-2271 50 B&W 149922 OAL-13 VT-1 Class A CS 9.250 1.300 CS 9.250 1.300 Reactor Vessel Closure Head Nut.
B06.010.060 3-RPV-26-209-60 OM 201-2271 50 B&W 149922 OAL-13 VT-1 Reactor Vessel Closure Head Nut.
Class A Total B06.010 Items:
20
EOC 22
"-, tDUKE ENERG(CORPORATION CATEGORY B-G-1 Pressure Retaining Bolting, INSERVICE INSPECTION PLAN MANAGEMENT Greater Than 2 in. In Diameter Inservice Inspection Database Management System C
M~tr Vessel Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 Plan Report Page 5 08/03/2006 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Closure Studs, when removed **
B06.030.041 3-RPV-25-209-41 Class A B06.030.042 3-RPV-25-209-42 Class A B06.030.043 3-RPV-25-209-43 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 Class A B06.030.044 3-RPV-25-209-44 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
40420 Reactor Closure Stud-Removed. Stud Length 63.250.
40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
40420 Reactor Closure Stud-Removed. Stud Length=
63.250.
40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
Class A B06.030.045 3-RPV-25-209-45 Class A B06.030.046 3-RPV-25-209-46 OM 201-2271 Class A 50 B&W 149922 OM 201-2271 50 B&W 149922 B06.030.047 3-RPV-25-209-47 Class A B06.030.048 3-RPV-25-209-48 OM 201-2271 50 B&W 149922 PDI-UT-5 UT CS 6.500 40420 0.000 Reactor Closure Stud-Removed. Stud Length =
63.250.
Class A
EOC 22 C
C/
DUKE ENERGY'CORPORATION CATEGORY B-G-1, Pressure Retaining Bolting, INSERVICE INSPECTION PLAN MANAGEMENT 4C Greater Than 2 in. In Diameter Reactor Vessel ITEM NUMBER ID NUMBER B06.030.049 3-RPV-25-209-49 Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 Plan Report Page 6 08/03/2006 SYS ISO/DWG NUMBERS OM 201-2271 50 B&W 149922 PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS PDI-UT-5 UT CS 6.500 40420 0.000 COMMENTS Reactor Closure Stud-Removed. Stud Length =
63.250.
Class A B06.030.050 3-RPV-25-209-50 Class A B06.030.051 3-RPV-25-209-51 Class A B06.030.052 3-RPV-25-209-52 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 Class A B06.030.053 3-RPV-25-209-53 Class A PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 PDI-UT-5 UT CS 6.500 0.000 40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
40420 Reactor Closure Stud-Removed. Stud Length=
63.250.
40420 Reactor Closure Stud-Removed. Stud Length 63.250.
40420 Reactor Closure Stud-Removed. Stud Length-_
63.250.
40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
B06.030.054 3-RPV-25-209-54 Class A B06.030.055 3-RPV-25-209-55 Class A B06.030.056 3-RPV-25-209-56 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 Class A B06.030.057 3-RPV-25-209-57 Class A
EOC 22 C
DUKE ENERGY CORPORATION CATEGORY B-G-I
- Pressure Retaining Bolting, INSERVICE INSPECTION PLAN MANAGEMENT Greater Than 2 in. In Diameter Inservice Inspection Database Management System Reactor Vessel Oconee 3 E
Inservice Inspection Plan for Interval 4 Outage 1 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIAITHK CAL BLOCKS B06.030.058 3-RPV-25-209-58 OM 201-2271 PDI-UT-5 UT CS 6.500 40420 50 B&W 149922 0.000 Class A C
Plan Report Page 7 08/03/2006 COMMENTS Reactor Closure Stud-Removed. Stud Length =
63.250.
Reactor Closure Stud-Removed. Stud Length =
63.250.
B06.030.059 3-RPV-25-209-59 Class A OM 201-2271 50 B&W 149922 OM 201-2271 50 B&W 149922 PDI-UT-5 UT CS 6.500 40420 0.000 B06.030.060 3-RPV-25-209-60 PDI-UT-5 UT CS 6.500 0.000 40420 Reactor Closure Stud-Removed. Stud Length =
63.250.
Class A Total B06.030 Items:
20
EOC 22 C
C DUKE ENERGY CORPORATION CATEGORY B-G-1* Pressure Retaining Bolting, INSERVICE INSPECTION PLAN MANAGEMENT Greater Than 2 in. In Diameter Inservice Inspection Database Management System Reactor Vessel Oconee 3 E
Inservice Inspection Plan for Interval 4 Outag ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CA (7
el
\\L BLOCKS COMMENTS Plan Report Page 8 08/03/2006
- Threads in Flange ****
B06.040.001 3-RPV-LIGAMENTS OM-2201-96 50 B&W 149904E NDE-640 UT CS 200.000 40387 12.500 Reactor Vessel Flange Threads. Stud Holes 1 - 60.
Class A Total B06.040 Items:
1
EOC 22 C7 C.
DUKE ENERGY CORPORATION CATEGORY B-G-1, Pressure Retaining Bolting.
INSERVICE INSPECTION PLAN MANAGEMENT Greater Than 2 in. In Diameter Inservice Inspection Database Management System Reactor Vessel Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIAITHK CAL BLOCKS COMMENTS Plan Report Page 9 08/0312006
Stud Holes 41-60.
Class A Total B06.050 Items:
1
EC22 C9 C,
DUKE ENERGY CORPORATION CATEGORY B-G-1. Pressure Retaining Boltinq.
INSERVICE INSPECTION PLAN MANAGEMENT Greater Than 2 in. In Diameter Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Bolts and Studs ****
B06.180.008 3-RCP-3B2-S OM 1201.D-0057 PDI-UT-5 UT CS 2.250 40359 Reactor Coola (7
Plan Report Page 10 0810312006 nt Pump 3B2 Seal Gland Bolts. 8 50 OM 1201.D-0059 0.000 Class A
- bolts, Bolt Length=1 1.750. Inspect seal gland bolting on one reactor coolant pump only.
Total B06.180 Items:
1
EOC 22 (7I DUKE ENERGY CORPORATION CATEGORY B-G-l, Pressure Retaining Bolting, INSERVICE INSPECTION PLAN MANAGEMENT Greater Than 2 in. In Diameter Inservice Inspection Database Management System 1
ITEM NUMBER ID NUMBER Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS Plan Report Page 11 08/03/2006
- Nuts, Bushings, and Washers ****
B06.200.008 3-RCP-3B2-WASHER OM 1201.D-0059 50 OM 1201.D-0057 Class A QAL-13 VT-1 NA 0.000 0.000 Reactor Coolant Pump 3B2 Seal Gland Nuts and Washers. 8 nuts and washers. Inspect seal gland nuts and washers on one reactor coolant pump only.
Total B06.200 Items:
Total B06 Items:
1 44
EOC 22 DUKE ENERGQCORPORATION CATEGORY B-G-2. Pressure Retaining Bolting, 2 INSERVICE INSPECTION PLAN MANAGEMENT in. And Less In Diameter Inservice Inspection Database Management System Steam Generators Oconee 3 Inservice Inspection Plan for Interval 4 Outag ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CA C
el kL BLOCKS COMMENTS Plan Report Page 12 08/03/2006
- Bolts, Studs, and Nuts ****
B07.030.001 3-SGA-UMW-STUDS Class A OM-201.S--0001 50 OM-201.S--0170 OM-201.S--0171 OM-201.S--0001 50 OM-201.S--0158 OM-201.S--0171 QAL-13 VT-1 CS 2.000 0.000 CS 2.000 0.000 Steam Generator 3A Upper Head Manway Studs and Nuts. (16 studs and nuts)
Stud length = 19.63". Examine all studs and nuts.
Steam Generator 3A Lower Head Manway Studs and Nuts. (16 studs and nuts) Stud length = 19.63".
Examine all studs and nuts.
B07.030.002 3-SGA-LMW-STUDS QAL-13 VT-1 Class A Total B07.030 Items:
Total B07 Items:
2 2
EOC 22 (C
CATEGORY B-J. Pressure Retaining Welds In Piping WNP 4 r Larger C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 Plan Report Page 13 08/03/2006 ITEM NUMBER ID NUMBER
- Circumferential Welds B09.011.005 3SGA-W2 Circumferential Class A Term end SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS ISI-OCN3-007 50 OM 201.S--0156.001 OM 201.S--0033.001 NDE-600 UT CS 33.500 Component 3.500 Nozzle to Pipe B09.011.005A 3SGA-W2 Circumferential Class A Term end ISI-OCN3-007 50 OM 201.S--0156.001 OM 201.S--0033.001 NDE-25 MT CS 33.500 3.500 Nozzle to Pipe Pump 3A1 Suction Piping. SG3A Outlet Nozzle to Pipe Pc. 67.
Weld W2 is listed on OM 201.S--0033.001 but drawing ISI-OCN3-007 is listed as the iso to show where the weld is located on the 3A1 Suction Piping Loop.
Pump 3A1 Suction Piping. SG3A Outlet Nozzle to Pipe Pc. 67.
Weld W2 is listed on OM 201.S--0033.001 but drawing ISI-OCN3-007 is listed as the iso to show where the weld is located on the 3A1 Suction Piping Loop.
Pump 3A1 Suction Piping. Safe End Pc. 55 to RCP 3A1 Suction Nozzle.
Pump 3A1 Suction Piping. Safe End Pc. 55 to RCP 3A1 Suction Nozzle.
B09.011.007 3-PIA1-8 Circumferential Class A Term end / Stress weld B09.011.007A 3-PIA1-8 Circumferential Class A Term end / Stress weld B09.011.009 3-PIA2-4 Circumferential Class A Stress weld B09.011.009A 3-PIA2-4 Circumferential Class A Stress weld B09.011.012 3-PIB1-4 Circumferential Class A Stress weld B09.011.012A 3-PIB1-4 Circumferential Class A Stress weld ISI-OCN3-007 50 O-ISIN4-100A-3.1 lSl-OCN3-007 50 O-ISIN4-100A-3.1 ISI.OCN3-008 50 O-ISIN4-100A-3.1 ISI-OCN3-008 50 O-ISIN4-100A-3.1 ISl-OCN3.009 50 O-ISIN4-100A-3.1 ISI-OCN3-009 50 O-ISIN4-100A-3.1 NDE-600 UT SS 33.500 Component 2.330 Safe End to Nozzle NDE-35 PT SS 33.500 2.330 Safe End to Nozzle NDE-600 UT CS 33.500 2.330 Pipe to Elbow Component Pump 3A2 Suction Piping. Pipe Pc. 63 to Elbow Pc.
62.
NDE-25 MT CS 33.500 2.330 Pipe to Elbow NDE-600 UT CS 33.500 Component 2.330 Pipe to Elbow Pump 3A2 Suction Piping. Pipe Pc. 63 to Elbow Pc.
62.
Pump 3B1 Suction Piping. Pipe Pc. 63 to Elbow Pc.
62.
Pump 3B1 Suction Piping. Pipe Pc. 63 to Elbow Pc.
62.
NDE-25 MT CS 33.500 2.330 Pipe to Elbow
EOC 22 (j
CATEGORY B-J. Pressure Retaining Welds In Piping NNP 4 r Larger C,
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 ITEM NUMBER ID NUMBER B09.011.015 3-PIB2-4 Circumferential Class A Stress weld B09.011.015A 3.PiB2-4 Circumferential Class A Stress weld B09.011.035 3HP-241-3 Circumferential Class A SYS ISO/DWG NUMBERS ISI-OCN3-010 50 O-lSIN4-100A-3.1 ISI-OCN3-010 50 O-ISIN4-100A-3.1 3HP-241 51A O-iSIN4-101A-3.4 PROC NDE-600 INSP REQ MAT/SCH UT CS DIA/THK CAL BLOCKS 33.500 Component 2.330 NDE-25 NDE-600 PDI-UT-2 Pipe to Elbow MT CS 33.500 2.330 Pipe to Elbow UT SS 4.000 Component 0.531 PDI-UT-2-O Valve 3HP-194 to Pipe PT SS 4.000 0.531 Valve 3HP-194 to Pipe UT SS 14.000 Component 1.250 PDI-UT-2-O Elbow to Pipe PT SS 14.000 1.250 Elbow to Pipe Plan Report Page 14 08/03/2006 COMMENTS Pump 3B2 Suction Piping. Pipe Pc. 63 to Elbow Pc.
62.
Pump 3B2 Suction Piping. Pipe Pc. 63 to Elbow Pc.
62.
This weld was listed previously as 3-51A-63-3 until iso 3-51A -63 was redrawn. Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
This weld was listed previously as 3-51A-63-3 until iso 3-51A -63 was redrawn.
Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
B09.011.035A 3HP-241-3 Circumferential Class A B09.011.037 3-53A-15-33 Circumferential Class A B09.011.037A 3-53A-15-33 Circumferential Class A B09.011.038 3-53A-15-34 Circumferential Class A B09.011.038A 3-53A-15-34 Circumferential Class A 3HP-241 51A O-ISIN4-101A-3.4 3-53A-15 (1) 53A O-ISIN4-102A-3.3 3-53A-15 (1) 53A O-ISIN4-102A-3.3 3-53A-15 (1) 53A O-ISIN4-102A-3.3 3-53A-15 (1) 53A O°ISIN4-102A-3.3 NDE-35 NDE-600 PDI-UT-2 NDE-35 NDE-600 PDI-UT-2 NDE-35 UT SS 14.000 Component Procedure NDE-600 uses the component for 1.250 PDI-UT-2-O calibration. Procedure PDI-UT-2 may be used in lieu Pipe to of procedure NDE-600. If PDI-UT-2 is used, then the Pipe calibration block listed shall be used.
PT SS 14.000 1.250 Pipe to Pipe
EOC 22 (C
CATEGORY B-J, Pressure Retaininq Welds In Piping NPS 4 or Larger ITEM NUMBER ID NUMBER SYS ISO/DWG NU B09.011.039 3-53A-1 5-35 3-53A-15 (1)
Circumferential 53A O-ISIN4-102A-Class A C,
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 IERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS NDE-600 UT SS 14.000 Component PDI-UT-2 1.250 PDI-UT-2-O Pipe to Elbow C
Plan Report Page 15 08/03/2006 COMMENTS Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
MB
-3.3' B09.011.039A 3-53A-15-35 Circumferential Class A 3-53A-15 (1) 53A O-ISIN4-102A-3.3 NDE-35 PT SS 14.000 1.250 Pipe to Elbow Total B09.011 Items:
18
EOC 22 C
CATEGORY B-J, Pressure Retaining Welds In Piping Less Than NPS 4 C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 C
Plan Report Page 16 08/03/2006 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Circumferential Welds ***
B09.021.010 3-PSP-14 Circumferential Class A Stress weld BO9.021.012 3-PIB1-10 Circumferential Class A Stress weld Dissimilar 9.021.038 3HP-241-12A Circumferential Class A BO B09.021.040 Class A B09.021.043 3HP-241-18A Circumferential 3HP-241-33 Circumferential 3LP-135-2 Circumferential ISI-OCN3-016 50 O-ISIN4-10OA-3.2 ISI-OCN3-009 50 O-ISIN4-100A-3.1 3HP-241 51A O-ISIN4-101A-3.4 3HP-241 51A O-ISIN4-101A-3.4 3HP-241 51A O-ISIN4-101A-3.4 3LP-135 53A O-ISIN4-102A-3.1 3RC-265 51A O-ISIN4-100A-3.1 NDE-35 NDE-35 NDE-35 PT SS 2.500 0.375 PT SS 2.500 0.375 Elbow to Tee PT CS-Inconel 3.500 0.672 Nozzle to Safe End PT SS 2,500 0.375 Tee to Pipe NDE-35 NDE-35 Class A Pressurizer Spray Piping. Elbow Pc. 98 to Tee Pc.
105.
Pump 3B1 Suction Piping. Drain Nozzle Pc. 87 to Safe End Pc. 88.
This weld was listed previously as 3-51A-63-12A until iso 3-51A -63 was redrawn.
This weld was listed previously as 3-51A-63-18A until iso 3-51A -63 was redrawn.
This weld was listed previously as 3-51A-63-33 until iso 3-51A -63 was redrawn.
This weld was listed previously as 3-53A-37-2 until iso 3-51 A-37 was redrawn.
This weld was listed previously as 3-51A-69-73 on iso 3-51A-69 until it was deleted and welded back as 3RC-265-79 on iso 3RC-265.
B09.021.059 NDE-35 Pipe to Elbow PT SS 2.500 0.375 Elbow to Pipe PT SS 3.000 0.438 Pipe to Valve 3LP-103 PT SS-Inconel 2.500 0.375 Elbow to Safe End Class A B09.021.064 3RC-265-79 Circumferential Class A Stress weld Dissimilar Total B09.021 Items:
7 NDE-35
EOC 22 C
CATEGORY B-J, Pressure Retaining Welds In IN Piping Inser Branch Pipe Connection Welds E
InUE ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS C
DUKE ENERGY CORPORATION SERVICE INSPECTION PLAN MANAGEMENT vice Inspection Database Management System Oconee 3 service Inspection Plan for Interval 4 Outage 1 PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS C'
Plan Report Page 17 08/0312006
- Less Than NPS 4 ****
B09.032.001 3-PIAI-10 Branch Class A Stress weld Dissimilar Total B09.032 Items:
ISI-OCN3.007 50 0-ISIN4-100A-3.1 NDE-35 PT CS-Inconel 12.000 2.250 Nozzle to Pipe Pump 3A1 Suction Piping. Drain Nozzle Pc. 64 to Pipe Pc. 63. The NPS of the branch line is 1.5 inches.
1
EOC 22 CATEGORY B-J. Pressure Retaining Welds In Piping Socket Welds ITEM NUMBER ID NUMBER SYS ISO/DWG NU DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 MBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS C,
Plan Report Page 18 08/03/2006 B09.040.001 3-50-152-10 Socket Class A B09.040.009 3RC-265-67 Socket Class A B09.040.01 0 3RC-265-76 Socket Class A 3-50-152 50 O-ISIN4-100A-3.2 3RC-265 51A O-ISIN4-100A-3.1 3RC-265 51A O-ISIN4-100A-3.1 NDE-35 NDE-35 PT SS 1.500 0.281 Pipe to Tee PT SS 1.500 0.281 Pipe to Elbow PT SS 1.500 0.281 Elbow to Pipe NDE-35 Total B09.040 Items:
3 Total B09 Items:
29
EOC 22 CATEGORY B-K, Welded Attaci Vessels, Piping, Pumps, And V; ITEM NUMBER ID NUMBER
- Welded Attachments ****
B1 0.020.012 3-51A-0-2478A-H5C Rigid Support Class A DUKE ENERGY CORPORATION iments For INSERVICE INSPECTION PLAN MANAGEMENT alves Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS C
Plan Report Page 19 08/03/2006 3-51-14/st 51A O-ISIN4-1
.It.1 01A-3.1 NDE-35 PT NA 2.500 0.500 Calculation No. OSC-1660-01. Inspect with F01.010.015.
Total B10.020 Items:
Total B10 Items:
1 1
EOC 22 (1
CATEGORY B-O,.Pressure Retaining Welds In Control Rod Housings Reactor Vessel ITEM NUMBER ID NUMBER SYS ISO/DWG NUME C'
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 lERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS Plan Report Page 20 08/03/2006 COMMENTS
B14.010.005 3-RPV-CRD-58WH9 B&W 149920E NDE-35 50 Class A B14.010.006 3-RPV-CRD-58WH60 B&W 43-53-032-12 NDE-35 50 Class A PT SS-Inconel 4.060 0.650 Housing Body to Adapter PT SS-CS 5.000 0.500 Base to Motor Tube PT SS-CS 4.300 0.400 Motor Tube to Extension PT SS 4.190 0.380 Extension to Cap CRDM #58 Housing Body to Adapter.
CRDM #58 Base to Motor Tube.
B14.010.007 3-RPV-CRD-58 B&W 43-53-033-09 NDE-35 CRDM #58 Motor Tube to Extension.
50 Class A B14.010.008 3-RPV-CRD-58W61 B&W 43-53-032-12 NDE-35 CRDM #58 Extension to Cap.
50 Class A Total B14.010 Items:
Total B14 Items:
4 4
EOC 22 CATEGORY C-C, Welded Attachments For Vessels, Piping, Pumps, And Valves C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System C-iEMpin ITEM NUMBER Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIAfTHK CAL BLOCKS Plan Report Page 21 08/03/2006 ID NUMBER COMMENTS
- Welded Attachments ****
C03.020.004 3-01A-0-24411-H12 Rigid Support Class B C03.020.042 3-51A-1-0-2437A-SR16 Rigid Restraint Class B C03.020.051 3-53-0-2478A-H5 Rigid Restraint Class B C03.020.062 3-54A-3-0-2435B-SR7 Hyd Snubber Class B Total C03.020 Items:
4 Total C03 Items:
4 3-01-01/sht.1 01A O-ISIN4-122A-3.1 3-51-05/sht.1 51A O-ISIN4-101A-3.3 3-56-03/sht.2 53 O-ISIN4-102A-3.1 3-54-02/sht. 1 54A O-ISIN4-103A-3.1 NDE-25 NDE-35 NDE-35 NDE-35 MT CS 36.000 0.750 PT NA 4.000 0.125 PT NA 12.000 0.375 PT NA 8.000 1.000 Calculation No. OSC-506.
Calculation No. OSC-542. Inspect with F01.021i.049.
Calculation No. OSC-1339-06.
Calculation No. OSC-555. Inspect with F(*1.022.043.
EOC 22 1
CATEGORY C-D, Pressure Retaining Bolting Greater Than 2 in. In Diameter ITEM NUMBER ID NUMBER SYS ISO/DWG NUME DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 3ERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS Plan Report Page 22 08/03/2006 COMMENTS
- Bolts and Studs ****
C04.030.002 3-HPI-PUMP-3B OM 201-1704 51A O-ISIN4-101A-3.3 PDI-UT-5 UT NA 2.500 40422 0.000 Class B High Pressure Injection Pump 3B (Casing bolts).
The bolting for these pumps can not be examined in place, therefore they will be scheduled for Outages 3,4,5,6. If one is disassembled for maintenance it will be examined and credit taken at that time. The remaining pumps will then be removed from the examination schedule. If the disassembly for maintenance does not happen by Outage 6 then the pump must be disassembled in order to perform the examination.
Total C04.030 Items:
Total C04 Items:
1 1
EOC 22 C
CATEGORY C-F-i, Pressure Retaining Welds In INSERVICE INSPECTION PLAN MANAGEMENT Austenitic SS Or High Alloy Piping Inservice Inspection Database Management System O
PiinnpWWeds
>= 3/8 in. Nominal Wall Thickness Oconee 3 or Pi in > NPS 4 Inservice Inspection Plan for Interval 4 Outag ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK C1 Plan Report Page 23 08/03/2006 el
- LBLOCKS COMMENTS
- Circumferential Weld C05.011.004 3LP-134-103 Circumferential Class B C05.011.004A 3LP-134-103 Circumferential Class B 3LP-134 53A O-ISIN4-102A-3.2 O-ISIN4-102A-3.3 3LP-134 53A O-ISIN4-102A-3.2 O-ISIN4-102A-3.3 NDE-600 PDl-UT-2 UT SS 10.000 Component 1.125 PDI-UT-2-O Reducer to Valve 3LP-1 8 NDE-35 PT SS 10.000 1.125 Reducer to Valve 3LP-18 This weld was listed previously as 3-53A-1 5-92 until iso 3-53A-15 (2) was redrawn.
This weld was listed previously as 3LP-134-92 until iso 3LP-134 was revised and deleted this weld.
Weld was remade as 3LP-134-103.
The ID of the 12" x 10" reducer has been machined to 10.413 (plus/minus.010"). Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
This weld was listed previously as 3-53A-15-92 until iso 3-53A-1 5 (2) was redrawn.
This weld was listed previously as 3LP-134-92 until iso 3LP-134 was revised and deleted this weld.
Weld was remade as 3LP-134-103.
The ID of the 12" x 10" reducer has been machined to 10.413 (plus/minus.010").
Reference Request for Relief 95-02 for calibration block.
This weld was listed previously as 3-53A-24-9 until iso 3-53A-24 was redrawn.
This weld was previously listed as 3LP-132-9; but due to an isometric revision deleted this weld. This weld is now 3LP-132-20.
Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
This weld was listed previously as 3-53A-24-9 until iso 3-53A-24 was redrawn.
This weld was previously listed as 3LP-132-9; but due to an isometric revision deleted this weld. This weld is now 3LP-132-20.
C05.01 1.011 3LP-132-20 Circumferential Class B 3LP-132 53A O-ISIN4-102A-3.2 NDE-600 PDl*UT-2 UT SS 10.000 Component 1.125 PDI-UT-2-O Elbow to Pipe PT SS 10.000 1.125 Elbow to Pipe C05.011.011lA 3LP-132-20 Circumferential Class B Total C05.011 Items:
4 3LP-132 53A O-ISIN4-102A-3.2 NDE-35
EOC 22 C
DUKE ENERGY CORPORATION CATEGORY C-F-i. Pressure Retaininq Welds In INSERVICE INSPECTION PLAN MANAGEMENT Austenitic SS Or Higqh Alloy Piping Inservice Inspection Database Management System PPiiinn Welds> 115 in. Nom Wall for Piping >=
Oconee 3 NPS 2 and <= NPS 4 Inservice Inspection Plan for Interval 4 Outage 1 Plan Report Page 24 08/03/2006 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Circumferential Weld C05.021.001 3-51A-101-1 Circumferential Class B C05.021.001A 3-51A-101-1 Circumferential Class B C05.021.010 3-51A-118-31 Circumferential Class B C05.021.010A 3-51A-118-31 Circumferential Class B C05.021.020 3-51A-120-8 Circumferential Class B C05.021.020A 3-51A-120-8 Circumferential Class B C05.021.028 3HP-501-20 Circumferential Class B 3-51A-101 51A O-ISIN4-101A-3.3 NDE-600 PDI-UT-2 3-51A-101 51A O-ISIN4-101A-3.3 3-51 A-1 18 51A O-ISIN4-101A-3.4 3-51A-118 51A O-ISIN4-101A-3.4 3-51A-120 51A O-ISIN4-IOIA-3.4 3-51A-120 51A O-ISIN4-101A-3.4 3HP-501 51A O-ISIN4-101A-3.1 NDE-35 NDE-600 PDI-UT-2 NDE-35 NDE-600 PDI-UT-2 NDE-35 UT SS 2.500 Component 0.375 PDI-UT-2-O Elbow to Pipe PT SS 2.500 0.375 Elbow to Pipe UT SS 4.000 Component 0.531 PDI-UT-2-O Elbow to Pipe PT SS 4.000 0.531 Elbow to Pipe UT SS 4.000 Component 0.531 PDI-UT-2-O Elbow to Pipe PT SS 4.000 0.531 Elbow to Pipe UT SS 2.500 Component 0.375 PDI-UT-2-O Elbow to Pipe PT SS 2.500 0.375 Elbow to Pipe Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
NDE-600 PDI-UT-2 Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
This weld was listed previously as 3-51A-141-20 on iso 3-51A-141 until it was transferred to iso 3HP-501.
This weld was listed previously as 3-51A-141-20 on iso 3-51A-141 until it was transferred to iso 3HP-501.
C05.021.028A 3HP-501-20 Circumferential Class B Term end 3HP-501 51A 0-ISIN4-1O1A-3.1 NDE-35
EOC 22 (7
C DUKE ENERGY-CORPORATION CATEGORY C-F-I, Pressure Retaining Welds Ini INSERVICE INSPECTION PLAN MANAGEMENT Austenitic SS Or High Alloy Piping Inservice Inspection Database Management System Piping Welds> 115 in. Nom Wall for Pping >=
Oconee 3 NPS2and <=NPS4 Inservice Inspection Plan for Interval 4 Outage 1 ITEM NUMBER ID NUMBER C05.021.037 3-51A-52-39 Circumferential Class B C05.021.037A 3-51A-52-39 Circumferential Class B C05.021.038 3-51 A-52-40 Circumferential Class B C05.021.038A 3-51A-52-40 Circumferential Class B C05.021.047 3-51 A-59-6 Circumferential Class B C05.021.047A 3-51A-59-6 Circumferential Class B C05.021.052 3HP-365-9C Circumferential Class B SYS ISO/DWG NUMBERS 3-51 A-52 51A O-ISIN4-101A-3.3 3-51 A-52 51A O-ISIN4-101A-3.3 3-51 A-52 51A O-ISIN4-101A-3.3 PROC NDE-600 PDI-UT-2 NDE-35 INSP REQ MAT/SCH DIAITHK CAL BLOCKS UT SS 4.000 Component 0.531 PDI-UT-2-O Tee to Reducer PT SS 4.000 0.531 Tee to Reducer UT SS 3.000 Component 0.438 PDI-UT-2-O Reducer to Pipe Plan Report Page 25 08/03/2006 COMMENTS Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
NDE-600 PDI-UT-2 Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
3-51A-52 51A O-ISIN4-101A-3.3 3-51 A-59 51A O-ISIN4-101A-3.4 NDE-35 PT SS 3.000 0.438 Reducer to Pipe UT SS 4.000 Component Procedure NDE-600 uses the component for 0.531 PDI-UT-2-O calibration. Procedure PDI-UT-2 may be used in lieu Elbow to of procedure NDE-600. If PDI-UT-2 is used, then the Pipe calibration block listed shall be used.
NDE-600 PDI.UT-2 3-51 A-59 51A O-ISIN4-101A-3.4 3HP-365 51A O-ISIN4-101A-3.4 NDE-35 PT SS 4.000 0.531 Elbow to Pipe UT SS 4.000 Component 0.674 PDI-UT-2-O Tee to Pipe NDE-600 PDI.UT-2 This weld was listed previously as 3-51A-66-9C on iso 3-51A-66 until it was transferred to iso 3HP-365.
Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
This weld was listed previously as 3-51A-66o9C on iso 3-51A-66 until it was transferred to iso 3HP-365.
C05.021.052A 3HP-365-9C Circumferential Class B 3HP-365 51A O-ISIN4-101A-3.4 NDE-35 PT SS 4.000 0.674 Tee to Pipe
EOC 22 C
CATEGORY C-F-I. Pressure Retaining Welds In Austenitic SS Or High Alloy Piping WPiing Welds > 1/5 in. Nom Wall for Piping >=
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 (I
ITEM NUMBER ID NUMBER C05.021.060 3-51 A-87-25 Circumferential Class B SYS ISO/DWG NUMBERS 3-51A-87 51A O-ISIN4-101A-3.4 PROC NDE-600 PDI.UT-2 INSP REQ MAT/SCH DINTHK CAL BLOCKS UT SS 4.000 Component 0.531 PDI-UT-2-O Pipe to Tee Plan Report Page 26 08/03/2006 COMMENTS Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-2 may be used in lieu of procedure NDE-600. If PDI-UT-2 is used, then the calibration block listed shall be used.
C05.021.060A 3-51A-87-25 Circumferential Class B C05.021.070 3-RCP-FTR3B-SH-1 Circumferential Class B Term end C05.021.070A 3-RCP-FTR3B-SH-1 Circumferential Class B Term end C05.021.071 3-RCP-FTR3B-SH-2 Circumferential Class B Term end C05.021.071A 3-RCP-FTR3B-SH-2 Circumferential Class B Term end Total C05.021 Items:
22 3-51 A-87 51A O-ISIN4-101A-3.4 3-51 A-87 51A O-ISIN4-101A-3.4 OM-201-0473-001 3-51 A-87 51A O-ISIN4-101A-3.4 OM-201-0473-001 3-51 A-87 51A O-ISIN4-101A-3.4 OM-201-0473-001 3-51 A-87 51A O-ISIN4-101A-3.4 OM-201-0473-001 NDE-35 PT SS 4.000 0.531 NDE-12 NDE-35 Pipe to Tee RT SS 4.000 0.531 Flange to RCP 3B Filter PT SS 4.000 0.531 Flange to RCP 3B Filter RT SS 4.000 0.531 RCP 3B Filter to Flange PT SS 4.000 0.531 RCP 3B Filter to Flange NDE-12 NDE-35
EOC 22 (7
- 7.
DUKE ENERGY CORPORATION CATEGORY C-F-2, Pressure Retaininq Welds In INSERVICE INSPECTION PLAN MANAGEMENT Carbon Or Low Alloy Steel Piping Inservice Inspection Database Management System ivina Welds >= 3/8 in. Nominal Wall Thickness Oconee 3 nor Piping > NPS 4 Inservice Inspection Plan for Interval 4 Outage 1 Plan Report Page 27 08/03/2006 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Circumferential Weld C05.051.010 3MS-138-19V Circumferential Class B Term end C05.051.010A 3MS-138-19V Circumferential Class B Term end C05.051.011 3MS-138-21V Circumferential Class B Term end C05.051.011A 3MS-138-21V Circumferential Class B Term end C05.051.021 3-03-31-16A Circumferential Class B C05.051.021A 3-03-31-16A Circumferential Class B C05.051.023 3SGB-W277 Circumferential Class B 3MS-138 01A O-ISIN4-122A-3.1 3MS-138 01A O-ISIN4-122A-3.1 3MS-138 01A O-ISIN4-122A-3.1 3MS-138 01A O-ISIN4-122A-3.1 3-03-31 03 O-ISIN4-121 B-3.3 3-03-31 03 O-ISIN4-121 B-3.3 OM 201.S--0155.001 03A O-ISIN4-121B-3.3 OM 201.S--0022.001 NDE-600 PDI-UT-1 NDE-25 NDE-600 PDI-UT-1 NDE-25 UT CS 24.000 Component 0.969 PDI-UT-1-O Reducer to Nozzle S/G 3A MT CS 24.000 0.969 Reducer to Nozzle S/G 3A UT CS 24.000 Component 0.969 PDI-UT-1-O Reducer to Nozzle S/G 3A MT CS 24.000 0.969 Reducer to Nozzle S/G 3A UT CS 24.000 Component 1.218 PDI-UT-1-O Valve 3FDW-37 to Pipe MT CS 24.000 1.218 Valve 3FDW-37 to Pipe Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used.
Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used.
NDE-600 PDI-UT-1 NDE-25 Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used.
NDE-600 UT CS 6.000 Component PDI-UT-1 0.432 PDI-UT-1-O Pipe to Pipe Cap Auxiliary Feedwater Header Ring on Steam Generator 3B (Vendor Weld). Procedure NDE-600 uses the component for calibration. Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used.
C05.051.023A 3SGB-W277 Circumferential Class B OM 201.3--0155.001 03A O-ISIN4-121B-3.3 OM 201.S--0022.001 NDE-25 MT CS 6.000 0.432 Pipe to Pipe Cap
EOC 22 CC DUKE ENERGY CORPORATION CATEGORY C-F-2. Pressure Retaining Welds In INSERVICE INSPECTION PLAN MANAGEMENT Carbon Or Low Alloy Steel Pipinq Inservice Inspection Database Management System OPiin Welds >= 3/8 in. Nominal Wall Thickness Oconee 3 orPipin >NPS4 Inservice Inspection Plan for Interval 4 Outage 1 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS C05.051.027 3LPS-509-5 3LPS-509 PDI-UT-10 UT SS-CS 8.000 Circumferential 14B O-ISIN4-124B-3.2 0.500 Plan Report Page 28 08/03/2006 COMMENTS Note:Weld 3-14B-1 16-16 was inspected in outage 1 for item # C05.051.027and since then has been deleted and weld 3LPS-509-5 took its place.
Note:Weld 3-144B-116-16 was inspected in outage 1 for item # C05.051.027A and since then has been deleted and weld 3LPS-509-5 took its place.
Class B C05.051.027A 3LPS-509-5 Circumferential Class B C05.051.041 3LPS-478-56 Circumferential Class B 3LPS-509 14B O-ISIN4-124B-3.2 3LPS-478 14B O-ISIN4-124B-3.2 NDE-35 Valve 3LPS-16 to Pipe PT SS-CS 8.000 0.500 Valve 3LPS-1 6 to Pipe NDE-600 PDI-UT-1 UT CS 8.000 Component This weld was listed previously as 3-14B-119-56 0.500 PDI-UT-1-O until iso 3-14B-119 was redrawn.
Pipe to Procedure NDE-600 uses the component for Flange calibration. Procedure PDI-UT-1 may be used in lieu of procedure NDE-600. If PDI-UT-1 is used, then the calibration block listed shall be used.
MT CS 8.000 This weld was listed previously as 3-14B-1 19-56 0.500 until iso 3-14B-119 was redrawn.
Pipe to Flange C05.051.041A 3LPS-478-56 Circumferential Class B Total C05.051 Items:
12 3LPS-478 14B O-ISIN4-124B-3.2 NDE-25
EOC 22
(
DUKE ENERGY CORPORATION CATEGORY C-F-2. Pressure Retaining Welds In INSERVICE INSPECTION PLAN MANAGEMENT Carbon Or Low Alloy Steel Piping Inservice Inspection Database Management System Socket Welds Oconee 3 B
Inservice Inspection Plan for Interval 4 Outag ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CA AC el
\\L BLOCKS COMMENTS Plan Report Page 29 08103/2006 C05.070.001 3-BWST-OUT-2 Socket Class B Term end 3-53B-46 53B O-ISIN4-102A-3.1 OM-2201-0839 NDE-35 PT CS 14.000 0.375 Flange to Nozzle Slip-On Flange to Borated Storage Tank Outlet Nozzle. Dwg-OM-1201-80.
Total C05.070 Items:
1
EOC22 Q
DUKE ENERGYCORPORATION CATEGORY C-F-2, Pressure Retaining Welds In INSERVICE INSPECTION PLAN MANAGEMENT Carbon Or Low Alloy Steel Piping Inservice Inspection Database Management System Wive Branch Connections of Branch Piping >=
Oconee 3 NPS2 Inservice Inspection Plan for Interval 4 Outage 1 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Circumferential Weld ****
C Plan Report Page 30 08/03/2006 C05.081.001 3MS-22A-E Branch Class B 3MS-1 17 01A O-ISIN4-122A-3.1 3MS-22A NDE-25 MT CS 8.000 0.500 Pipe to Pipe Grinnell Subassembly 3MS-22A. This subassembly weld was listed previously on iso 3-01 A-10 until it was transferred to iso 3MS-1 17.
Total C05.081 Items:
Total C05 Items:
1 40
EOC 22 c
CATEGORY D-A, Welded Attachments For C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System (C
Vessels, Piping, Pumps, And Valve ITEM NUMBER ID NUMBER SYS S
Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS Plan Report Page 31 08/03/2006 COMMENTS
- Welded Attachments ****
D01.020.001 3-01A-2403D-LC-1603 Rigid Restraint Class C D01.020.021 3-03-0-2439B-H54 Rigid Support Class C D01.020.024 3-03A-1-0-2401A-H52 Spring Hgr Class C D01.020.074 3-14B-2439B-DE043 Rigid Support Class C 3-01A-04/sht.1 01A O-ISIN4-122A-3.4 O-3TB-301 A04-01 3-03-01/sht.1 03 O-ISIN4-121 B-3.3 3-03A-02/sht.2 03A O-ISIN4-121 B-3.3 O-3TB-303A02-02 3-14-05/sht.2 14B O-ISIN4-124B-3.4 OAL-13 VT-1 NA 6.000 0.187 Calculation No. OSC-51 0. Inspect with F01.031.001.
QAL-13 OAL-13 OAL-13 VT-1 VT-1 VT-1 NA 24.000 2.000 NA 6.000 0.125 NA 10.000 0.280 Calculation No. OSC-512.
Inspect with H04.001.002 and F01.030.021.
Calculation No. OSC-513. Inspect with F01.032.023.
Calculation No. OSC-533. Inspect with F01.030.103.
Total D01.020 Items:
Total D01 Items:
4 4
EOC 22 C
CATEGORY F-A. Supports M~s1 PipinqSuports DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS 1C Plan Report Page 32 08/03/2006 ITEM NUMBER ID NUMBER COMMENTS
- Category A, One-Directional F01.010.014 3-51A-0-2479A-H5A Rigid Support Class A 3-53-1 0/sht.4 51A O-ISIN4-101A-3.4 O-3RB-35310-04 3-51-14/sht.1 51A O-ISIN4-101A-3.1 QAL-14 VT-3 NA 2.500 0.375 Calculation No. OSC-1343-06 Vol.B. H.P.I. East Coolant Loop.
Calculation No. OSC-1 660-01. Inspect with B10.020.012.
F01.010.015 Class A 3-51A-0-2478A-H5C Rigid Support QAL-14 VT-3 NA 2.500 0.500 Total F01.010 Items:
2
- Category B, Multi-Directional ****
F01.011.025 3-53A-0-2479A-H24C 3-53-09/sht.2 Rigid Restraint 53A O-ISIN4-10OA-3.2 Class A O-3RB-35309-02 QAL-14 VT-3 NA 1.500 0.250 Calculation No. OSC-1343-06 VoI.A.
Total F01.011 Items:
1
- Category C, Thermal Movement F01-.012.011 3-51A-0-2479A-H11A Spring Hgr 51A Class A 3-53-01/sht.3 O-ISIN4-101A-3.4 O-3RB-35301-03 QAL-14 VT-3 NA 2.500 0.000 Calculation No. OSC-1343-06 Vol.B. H.P.I. East Coolant Loop.
Total F01.012 Items:
1
EOC 22 CATEGORY F-A, Supports MC~s2 PipingSuports C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS 1C Plan Report Page 33 08/03/2006 ITEM NUMBER ID NUMBER COMMENTS
- Category A, One-Directional F01.020.004 3-01A-0-2441-H12 Rigid Support Class B F01.020.011 3-03-0-2479A-H5A Rigid Support Class B 3-01-01/sht.1 01A O-ISIN4-122A-3.1 3-03-07/sht. 1 03 O-ISIN4-121 B-3.3 O-2490B-4(S) 3-14-06/sht.2 14B O-ISIN4-124B-3.2 3-14B-08/sht.1 14B O-ISIN4-124B-3.2 OAL-14 OAL-14 VT-3 CS 36.000 0.750 VT-3 NA 24.000 0.365 Calculation No. OSC-506.
Inspect along with item number C03.020.004.
Calculation No. OSC-1335.
F01.020.022 Class B F01.020.023 Class B F01.020.035 Class B F01.020.036 Class B F01.020.037 Class B F01.020.038 3-14B-0-2439B-WM-1 001 Rigid Support 3-14B-0-2479A-H16A Rigid Support QAL-14 QAL-14 VT-3 VT-3 NA 8.000 0.000 NA 8.000 0.000 Calculation No. OSC-535.
Calculation No. OSC-1344-06.
3-51A-1-0-2439A-H240 Rigid Support 3-51A-1-0-2439A-H241 Rigid Support 3-51A-1-0-2439A-H314 Rigid Support 3-51A-0-2438C-DE030 Rigid Support 3-51-04/sht.1 51A O-ISIN4-101A-3.4 3-51-04/sht.1 51A O-ISIN4-101A-3.4 3-51-05/sht.7 51A O-ISIN4-101A-3.4 3-51-07/sht.1 51A O-ISIN4-101A-3.4 QAL-14 VT-3 NA 4.000 0.000 Calculation No. OSC-541.
QAL-14 QAL-14 VT-3 VT-3 NA 2.500 0.154 NA 4.000 0.000 NA 4.000 0.000 Calculation No. OSC-541.
Calculation No. OSC-541.
QAL-14 VT-3 Calculation No. OSC-544.
Class B
EOC 22 C
CATEGORY F-A, Supports WCa 2PipingSupports ITEM NUMBER ID NUMBER F01.020.039 3-51 A-0-2478A-RJ-1 000 Rigid Support Class B F01.020.040 3-51A-0-2479A-H17C Rigid Support Class B C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Plan Report Page 34 08103/2006 SYS ISO/DWG NUMBE 3-51-14/sht.5 51A O-ISIN4-101A-3.1 3-51-14/sht.5 51A O-ISIN4-101A-3.1 3-51-02/sht.2 53B O-ISIN4-102A-3.1 O-3AB-35102-02 3-54-01/sht.1 54A O-ISIN4-103A-3.1 Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 RS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS OAL-14 VT-3 NA 2.500 Calculation No. OSC-1660-01.
0.375 QAL-14 VT-3 F01.020.074 Class B 3-53B-2-0-2436C-H1143 Rigid Support OAL-14 VT-3 NA 2.500 0.145 NA 8.000 0.125 NA 8.000 0.125 Calculation No. OSC-539.
Calculation No. OSC-1660-01.
F01.020.083 3-54A-3-0-2436D-H46 Rigid Support Class B QAL-14 VT-3 Calculation No. OSC-554.
Total F01.020 Items:
12
- Category B, Multi-Directional F01.021.028 3-1 4B-0-2479A-H 11F 3-14B-13/sht.1 Rigid Restraint 14B 0-ISIN4-124B-3.2 Class B F01.021.049 3-51A-1-0-2437A-SR16 3-51-05/sht.1 Rigid Restraint 51A O-ISIN4-101A-3.3 Class B QAL-14 OAL-14 VT-3 VT-3 NA 8.000 0.000 NA 4.000 0.125 Calculation No. OSC-1344-06 Vol.7. This support can be found on hanger sketch 3-14B-0-2479A-H1 1.
Calculation No. OSC-542. Inspect with C03.020.042.
Total F01.021 Items:
2
- Category C, Thermal Movement F01.022.043 3-54A-3-0-2435B-SR7 Hyd Snubber 54A Class B 3-54-02/sht. 1 0-151N4-103A-3.1 QAL-14 VT-3 NA 8.000 1.000 Calculation No. OSC-555. Inspect with C03.020.062.
Total F01.022 Items:
1
EOC 22 C
CATEGORY F-A. Supports MCs3 PipirngSupports DUKE ENERG(CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1
'c Plan Report Page 35 08/03/2006 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Category A, One-Directional ****
F01.030.002 Class C F01o.030.021 Class C F01.030.024 Class C F01.030.027 Class C F01.030.030 Class C F01.030.040 Class C F01.030.052 Class C 3-01A-2403E-H4458 Rigid Support 3-03-0-2439B-H54 Rigid Support 3-03A-1-0-2439B-H 13 Rigid Support 3-03A-1-0-2437A-H137 Rigid Support 3-03A-2400A-H126 Rigid Support 3-03A-2401 B-DE024 Rigid Support 3-01 A-04/sht.2 01A O-ISIN4-122A-3.4 O-3TB-301 A04-02 3-03-01/sht.1 03 O-ISIN4-121B-3.3 3-03A-06/sht.2 03A O-ISIN4-121 D-3.1 3-03A-07/sht.2 03A O-ISIN4-121 D-3.1 3-03A-09/sht.1 03A O-ISIN4-121 D-3.1 3-03A-02/sht.1 03A O-ISIN4-121D-3.1 O-3TB-303A02-01 QAL-14 OAL-14 VT-3 NA 6.000 0.000 Calculation No. OSC-510.
Calculation No. OSC-512.
Inspect with H04.001.002 and D01.020.021.
VT-3 QAL-14 OAL-14
\\rr-3 VT-3 NA 24.000 2.000 NA 6.000 0.125 NA 6.000 0.125 NA 6.000 0.125 NA 6.000 0.000 Calculation No. OSC°519.
Calculation No. OSC-524.
QAL-14 OAL-14 VT-3 VT-3 Calculation No. OSC-526.
Calculation No. OSC-513.
3-04A-2-0-2439B-SR4 3-04A-01 Rigid Support 04A O-ISIN4-121B-3.5 OAL-14 VT-3 NA 6.000 1.000 Calculation No. OSC-520.
F01.030.081 3-08-2400A-H10 Rigid Support Class C 3-08-01/sht.1 08 O-ISIN4-122A-3.4 QAL-14 VT-3 NA 10.000 0.000 Calculation No. OSC-1808.
EOC 22 C
CATEGORY F-A, Supports MC~as 3 PpingSupprts ITEM NUMBER ID NUMBER F01.030.103 3-14B-2439B-DE043 Rigid Support Class C DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 Plan Report Page 36 08/03/2006 COMMENTS Calculation No. OSC-533. Inspect with D01.020.074.
F01.030.104 Class C F01.030.105 Class C F01.030.106 Class C F01.030.107 Class C F01.030.112 Class C F01.030.113 Class C F01.030.114 Class C 3-14B-2439B-DE033 Rigid Support 3-14B-2439B-DE044 Rigid Restraint 3-14B-2437B-DE007 Rigid Support 3-14B-2437A-DE019 Rigid Support 3-56-5-0-2437A-H2 Rigid Support 3-56-1-0-2437A-SR110 Rigid Support 3-56-1-0-2437A-SR102 Rigid Support SYS ISO/DWG NUMBERS 3-14-05/sht.2 14B O-ISIN4-124B-3.4 3-14-06/sht.2 14B O-ISIN4-124B-3.2 3-14-06/sht.3 14B O-ISIN4-124B-3.2 3-14B-03/sht.1 14B O-ISIN4-124B-3.1 3-14B-07/sht.1 14B O-ISIN4-124B-3.1 3-56-0 1/sht..1 56 O-ISIN4-104A-3.1 3-56-O2/sht..1 56 O-ISIN4-104A-3.1 O-3AB-35602-01 3-56-02/sht.2 56 O-ISIN4-104A-3.1 O-3AB-35602-02 OAL-14 OAL-14 Vr-3 VT-3 NA 8.000 0.237 NA 8.000 0.280 PROC INSP REQ MAT/SCH QAL-14 VT-3 NA Calculation No. OSC-535.
Calculation No. OSC-535.
OAL-14 OAL-14 VT-3 NA 16.000 0.187 Calculation No. OSC-531.
Calculation No. OSC-1357.
DIA/THK CAL BLOCKS 10.000 0.280 VT-3 QAL-14 OAL-14
\\rr-3 VT-3 NA 12.000 0.187 NA 8.000 0.125 NA 8.000 0.125 NA 8.000 0.125 Calculation No. OSC-567.
Calculation No. OSC-563.
OAL-14 VT-3 Calculation No. OSC-563.
Total Category BMut i-ircisa**
16
- Category B, Multi-Directional **
EOC 22 4-CATEGORY F-A. Supports ITEM NUMBER ID NUMBER F01.031.001 3-01A-2403D-LC-1603 Rigid Restraint Class C F01.031.028 3-03A-2439F-H5618 Rigid Restraint Class C DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System SYS ISO/DWG NUMBE 3-01A-04/sht.1 01A O-ISIN4-122A-3.4 O-3TB-301 A04-01 3°03A-13/sht.1 03A O-ISIN4-121 D-3.1 0-3AB-303A13-01 Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 RS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS QAL-14 VT-3 NA 6.000 0.187 Plan Report Page 37 08/03/2006 COMMENTS Calculation No. OSC-510. Inspect with D01.020.001.
Calculation No. OSC-1224-23.
QAL-14 VT-3 NA 10.000 0.000 Total F01.031 Items:
2
- Category C, Thermal Movement F01.032.023 3-03A-1-0-2401A-H52 Spring Hgr 03A Class C 3-03A-02/sht.2 O-lSlN4-121 B-3.3 O-3TB-303A02-02 OAL-14 VT-3 NA 6.000 0.125 Calculation No. OSC-513. Inspect with 001.020.024.
Total F01.032 Items:
1
EOC 22 C
CATEGORY F-A, Supports C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 C,
ESupports Other Than Piping Supports Plan Report Page 38 08/03/2006 ITEM NUMBER ID NUMBER SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS COMMENTS
- Class 1, 2, and 3
- F01.040.004 3-LDC-A Class A F01.040.005 3-DHRC-A Class C F01.040.006 3-50-RCPM-H6625 Constant Support Class A OM 201-3107 51A O-ISIN4-101A-3.1 OM 201-0286 53 O-ISIN4-102A-3.2 OM 2201-227 OM 201.D-003 50 O-ISIN4-100A-3.1 O-ISIN4-10OA-3.3 OM 201-3142 14B O-ISIN4-124B-3.2 OM 235-0513 OM 208-0027 14B O-ISIN4-124A-3.1 OM 240-0002 14B O-ISIN4-124A-3.1 QAL-14 VT-3 OAL-14 OAL-1 4 VT-3 VT-3 NA 0.000 0.000 NA 0.000 0.000 NA 6.000 0.000 NA 0.000 0.000 NA 0.000 0.000 NA 0.000 0.000 Letdown Cooler 3A Support.
F01.040.007 3-RB-CC-C OAL-14 VT-3 Decay Heat Removal 3A Support. Equipment support located on Class C side.
Reactor Coolant Pump 3B2 Motor Constant Support.
Reactor Building Cooling Coils 3C. Also reference OM 201-0514.
Low Pressure Service Water Pump 3A Support Legs & Pad.
Low Pressure Service Water Strainer 3A Support Legs.
Class B F01.040.011 3-LPSW-PU-A OAL-14 VT-3 Class C F01.040.012 3-LPSW-STR-A OAL-14 VT-3 Class C Total F01.040 Items:
Total F01 Items:
6 44
EOC 22 CATEGORY ELC. Elective Inspections DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 I
ITEM NUMBER Plan Report Page 39 08/03/2006 Inservice Inspection Plan for Interval 4 Outage 1 SYS ISO/DWG NUMBERS PROC INSP REQ MAT/SCH DINTHK CAL BLOCKS ID NUMBER COMMENTS H03.001.006 3-03-31-10 Circumferential 3-03-31 03 O-ISIN4-121B-3.3 NDE-600 NDE-640 Class C UT CS 24.000 Component 1.218 Pipe to Elbow UT CS 24.000 Component 1.218 Pipe to Elbow H03.001.007 3-03-31-1 OG Circumferential 3-03-31 03 O-ISIN4-121B-3.3 NDE-600 NDE-640 Class C H03.001.008 3-03-31-8 Circumferential 3-03-31 03 O-ISIN4-121B-3.3 NDE-600 NDE-640 UT CS 24.000 Component 1.218 Pipe to Elbow Class C Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-640 should be used for thickness measurements on this weld.
Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.
Weld 3-03-31 -10 is a Elbow to Pipe weld located on iso 3-03-31.Weld 3-03-31-10G is a Grinnell Subassembly (pipe to elbow) weld located on the opposite end of the elbow from weld 3-03-31-10.
Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-640 should be used for thickness measurements on this weld.
Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.
Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-640 should be used for thickness measurements on this weld.
Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.
Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-640 should be used for thickness measurements on this weld.
Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.
Weld 3-03-31-3 is a Elbow to Pipe weld located on iso 3-03-31.Weld 3-03-31-3G is a Grinnell Subassembly (pipe to elbow) weld located on the opposite end of the elbow from weld 3-03-31-3.
Procedure NDE-600 should be used for angle beam inspection and Procedure NDE-640 should be used for thickness measurements on this weld.
Inspection results should be forwarded to Timothy D. Brown of the Oconee Design Basis Group.
H03.001.012 Class C 3-03-31-3 Circumferential 3-03-31 03 O-ISIN4-121B-3.3 3-03-31 03 O-ISIN4-121B-3.3 NDE-600 UT CS 24.000 Component NDE-640 1.218 Elbow to Pipe H03.001.013 3-03-31-3G Circumferential Class C NDE-600 NDE-640 UT CS 24.000 Component 1.218 Elbow to Pipe Total H03.001 Items:
5 Total H03 Items:
5
EOC 22 CATEGORY ELC, Elective Inspections C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 BERS PROC INSP REQ MAT/SCH DIANTHK CAL BLOCKS C
Plan Report Page 40 08/03/2006 ITEM NUMBER ID NUMBER SYS ISO/DWG NUME COMMENTS H04.001.001 3-03-2439B-H5041 Spring Hgr Class B H04.001.002 3-03-0-2439B-H54 Rigid Support Class C H04.001.002A 3-03-0-2439B-H54 Rigid Support Class C H04.001.003 Class C H04.001.004 Class C H04.001.005 Class C H04.001.006 Class C H04.001.007 3-03-0-2439A-H53 Spring Hgr 3-03-0-2439A-H52 Spring Hgr 3-03-0-2401A-H51 Rigid Support 3-03-0-2401A-DE001 Mech Snubber 3-03-0-2401A-H50 Spring Hgr 3-03-01/sht.1 03 O-1SIN4-121B-3.3 3-03-01/sht.1 03 O-ISIN4-121B-3.3 3-03o01/sht.1 03 O-ISIN4-121 B-3.3 3-03-01/sht.1 03 O°ISIN4-121 B-3.3 3-03-01/sht.1 03 O-ISIN4-121B-3.3 3-03-01/sht.1 03 O-ISIN4-121B-3.3 3-03-01/sht. 1 03 O-ISIN4-121B-3.3 3-03-01/sht.1 03 O-ISIN4-121B-3.3 OAL-14 VT-3 OAL-14 VT-3 NA 24.000 0.000 NA 24.000 2.000 NDE-25 MT NA 24.000 2.000 OAL-14 QAL-14 VT-3 VT-3 OAL-14 OAL-14 VT-3 VT-3 Calculation No. OSC-512.
Calculation No. OSC-512.
Inspect with item numbers F01.030.021 and H04.001.002A.
Calculation No. OSC-512.
Inspect with H04.001.002 Perform a Surface exam on the attachment welds.
NA 24.000 0.000 NA 24.000 0.000 NA 24.000 0.000 NA 24.000 0.000 NA 24.000 0.625 Calculation No. OSC-512.
Calculation No. OSC-512.
Calculation No. OSC-512.
Calculation No. OSC-512.
OAL-14 VT-3 Calculation No. OSC-512.
Inspect with item number H04.001.007A.
Class C
EOC 22
'C CATEGORY ELC, Elective Inspections I
ITEM NUMBER ID NUMBER H04.001.007A 3-03-0-2401A-H50 Spring Hgr Class C C
DUKE ENERGY CORPORATION INSERVICE INSPECTION PLAN MANAGEMENT Inservice Inspection Database Management System Oconee 3 Inservice Inspection Plan for Interval 4 Outage 1 IERS PROC INSP REQ MAT/SCH DIA/THK CAL BLOCKS NDE-35 PT NA 24.000 0.625 SYS ISO/DWG NUME 3-03-01/sht.1 03 O-ISIN4-121B-3.3 H04.001.022 3-FPA-27 OAL-14 VT-3 NA 0.000 0.000 03 O-60M Plan Report Page 41 08/03/2006 COMMENTS Calculation No. OSC-512.
Inspect along with item number H04.001.007.
Perform a Surface exam on the attachment welds.
Rupture Restraint Inspect along with item number H04.001.022A.
Rupture Restraint Inspect along with item number H04.001.022.
Perform a Surface exam on the attachment welds.
Rupture Restraint Inspect along with item number H04.001.023A.
Rupture Restraint Inspect along with item number H04.001.023.
Perform a Surface exam on the attachment welds.
Class C H04.001.022A 3-FPA-27 NDE-25 MT NA 0.000 0.000 03 0-60M Class C H04.001.023 3-FPA-25 QAL-14 VT-3 03 O-60M Class C H04.001.023A 3-FPA-25 NDE-25 MT 03 0-60M Class C NA 0.000 0.000 NA 0.000 0.000 NA 36.000 0.250 NA 36.000 0.000 H04.001.042 Class B 3-01A-0-24011B-H19 Rigid Support 3-01-01/sht.2 01A O-ISIN4-122A-3.1 3-01-01/sht.2 01A O-ISlN4-122A-3.1 OAL-14 VT-3 Calculation No. OSC-506.
H04.001.045 3-01 A-0-2401 B-H22 Rigid Support Class B QAL-14 VT-3 Calculation No. OSC-506.
Total H04.001 Items:
Total H04 Items:
15 15
4.0 Results Of Inspections Performed The results of each examination shown in the final Inservice Inspection Plan (Section 3 of this report) are included in this section. The completion date and status for each examination are shown. All examinations revealing reportable indications and any corrective action required as a result are described in further detail in Subsections 4.1 and 4.2. Corrective measures performed and limited examinations are described in further detail in Subsections 4.3 and 4.4.
The information shown below is a field description for the reporting format included in this section of the report:
Item Number ID Number Sys Insp Date Insp Status Insp Limited Geo. Ref.
(Geometric Reflector applies only to UT)
RFR (Relief Request)
Comments
=
ASME Section XI Tables IWB-2500-1 (Class 1), IWC-2500-1 (Class 2), IWF-2500-1 (Class 1 and Class 2),
Augmented Requirements
=
Unique Identification Number
=
Component System Identification
=
Date of Examination
=
CLR Clear REC Recordable REP Reportable
=
Indicates inspection was limited.
Coverage obtained is listed
=
Y Yes NNo
=
Y Yes N No
=
General and/or Detail Description EOC 22 Refueling Outage Report Oconee Unit 3 Section 4 Page 1 of 2 Revision 0 August 3, 2006
4.1 Reportable Indications EOC 22 (Outage 1) did not have any reportable indications during this report period.
4.2 Corrective Action Corrective action is action taken to resolve flaws and relevant conditions, including supplemental examinations, analytical evaluations, repair/ replacement activities, and corrective measures. There were no problems that required corrective action during this report period.
4.3 Corrective Measures Corrective measures are actions (such as maintenance) taken to resolve relevant conditions, but not including supplemental examinations, analytical evaluations, and repair/ replacement activities. Any corrective measures performed for examinations associated with this report period will be shown on the examination data sheets which are on file at the Duke Energy Corporate Office in Charlotte, North Carolina.
4.4 Limited Examinations Limited examinations (i.e., less than or equal to 90% of the required examination coverage obtained) identified during EOC 22 (Outage 1) are shown in the table below.
A Request for Relief will be submitted to seek NRC acceptance of the limited coverage for the items listed in the table below.
Item Number Description of Limitation B09.011.007 Coverage limitation (50.00%)
B09.011.035 Coverage limitation (37.50%)
C05.011.004 Coverage limitation (37.50%)
C05.021.052 Coverage limitation (89.40%)
EOC 22 Refueling Outage Report Oconee Unit 3 Section 4 Page 2 of 2 Revision 0 August 3, 2006
EOC 22 Plant: Oconee 3 DUKE ENERGY C PORATION QUALITY ASSURANCE T-CHNICAL SERVICES In-Service Inspection Database Management System Oconee 3 Inservice Inspection Listing Interval 4 Outage 1 SYSTEM INSP DATE INSP STATUS INSP LIMITED GEO REF RFR COMMENTS C
Run D Page 1 08/03/2006 ITEM NUMBER B01.030.001A B06.010.041 B06.010.042 B06.010.043 B06.010.044 B06.010.045 B06.010.046 B06.010.047 B06.010.048 B06.010.049 B06.010.050 B06.010.051 B06.010.052 B06.010.053 B06.010.054 B06.010.055 B06.010.056 B06.010.057 B06.010.058 B06.010.059 B06.010.060 B06.030.041 B06.030.042 B06.030.043 B06.030.044 B06.030.045 B06.030.046 B06.030.047 B06.030.048 B06.030.049 B06.030.050 B06.030.051 B06.030.052 B06.030.053 B06.030.054 B06.030.055 ID NUMBER 3-RPV-WR19 3-RPV-26-209-41 3-RPV-26-209-42 3-RPV-26-209-43 3-RPV-26-209-69 3-RPV-26-209-45 3-RPV-26-209-46 3-RPV-26-209-47 3-RPV-26-209-48 3-RPV-26-209-49 3-RPV-26-209-50 3-RPV-26-209-51 3-RPV-26-209-52 3-RPV-26-209-53 3-RPV-26-209-54 3-RPV-26-209-55 3-RPV-26-209-56 3-RPV-26-209-57 3-RPV-26-209-58 3-RPV-26-209-59 3-RPV-26-209-60 3-RPV-25-209o41 3-RPV-25-209-42 3-RPV-25-209-43 3-RPV-25-209-44 3°RPV-25-209-45 3-RPV-25-209-46 3-RPV-25-209-47 3-RPV-25-209-48 3-RPV-25-209-49 3-RPV-25-209-50 3-RPV-25-209-51 3-RPV-25-209-52 3-RPV-25-209-53 3-RPV-25-209-54 3-RPV-25-209-55 50 05/18/2006 REC N
N Indications 1 and 2, 7 degree were 25% DAC and are metallurgical interface signals from the weld fusion zones.
50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/13/2006 05/13/2006 05/13/2006 05/13/2006 05/13/2006 05/13/2006 05/13/2006 05/13/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/10/2006 05/12/2006 05/12/2006 05/12/2006 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N N
EOC 22 Plant: Oconee 3 ITEM NUMBER B06.030.056 B06.030.057 B06.030.058 B06.030.059 B06.030.060 B06.040.001 B06.050.003 B06.180.008 B06.200.008 B07.030.001 B07.030.002 B09.011.005 B09.011.005A B09.011.007 B09.0i 1.007A B09.011.009 B09.011.009A B09.011.012 B09.011.012A B09.011.015 B09.011.015A B09.011.035 B09.011.035A B09.011.037 B09.011.037A B09.011.038 B09.011.038A B09.01 1.039 B09.011.039A B09.021.010 B09.021.012 B09.021.038 B09.021.040 ID NUMBER 3-RPV-25-209-56 3-RPV-25-209-57 3-RPV-25-209-58 3-RPV-25-209-59 3-RPV-25-209-60 3-RPV-LIGAMENTS 3-RPV-WASH-BUSH 3°RCP-3B2-S 3-RCP-3B2-WASHER 3-SGA-UMW-STUDS 3-SGA-LMW-STUDS 3SGA-W2 3SGA-W2 3-PIA1-8 3-PIA1-8 3-PIA2-4 3-PIA2-4 3-PIB1-4 3-PIB1-4 3-PIB2-4 3-PIB2-4 3HP-241-3 3HP-241-3 3-53A-15-33 3-53A-15-33 3-53A-15-34 3-53A-15-34 3-53A-1 5-35 3-53A-15-35 3-PSP-14 3-PIB1-10 3HP-241-12A 3HP-241-18A SYSTEM 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 51A 51A 53A 53A 53A 53A 53A 53A 50 50 51A 51A INSP DA 05/12/2(
05/12/2(
05/12/2(
05/12/2(
05/1 2/2(
05/17/2(
05/13/2(
DUKE ENERGYC,PORATION QUALITY ASSURANCE T-CHNICAL SERVICES In-Service Inspection Database Management System Oconee 3 Inservice Inspection Listing Interval 4 Outage 1 TE INSP STATUS INSP LIMITED GEO REF RFR
)06 CLR N
N
)06 CLR N
N
)06 CLR N
N
)06 CLR N
N 06 CLR N
N 006 CLR N
N
)06 CLR N
N C
Run D Page 2 08/03/2006 COMMENTS 05/06/2006 05/04/2006 05/06/2006 05/06/2006 05/08/2006 05/08/2006 05/03/2006 05/03/2006 05/08/2006 05/08/2006 05/08/2006 05/08/2006 05/10/2006 05/10/2006 05/09/2006 05/09/2006 05/11/2006 05/09/2006 05/11/2006 05/09/2006 05/11/2006 05/09/2006 05/05/2006 05/08/2006 05/09/2006 05/09/2006 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR 50.00%
37.50%
Washers on stud holes 41 thru 52 showed rust and pitts on the side that contacts head flange. The rust and pitts were reviewed by the reactor systems engineer and found to be acceptable. QC inspection activities and Engineering disposition was documented on WO number 98732915-01 and WO number 98747902.
Relief Request will be filed for the limitation.
Relief Request will be filed for the limitation.
C DUKE ENERGYC 'PORATION QUALITY ASSURANCE 1"tCHNICAL SERVICES In-Service Inspection Database Management System C
EOC 22 Plant: Oconee 3 Run D Page 3 08/03/2006 ITIRA Nil lMP~fl Ifl Nil IMRFP
!~Y5~TFM IN~P DATE ITPRA Kl""RPP in N"MBER SYSTEM INSP DATE B09.021.043 B09.021.059 B09.021.064 B09.032.001 B09.040.001 B09.040.009 B09.040.010 B10.020.012 B14.010.005 B14.010.006 B14.010.007 B14.010.008 C03.020.004 C03.020.042 C03.020.051 C03.020.062 C04.030.002 C05.011.004 C05.011.004A C05.011.011 C05.011.011A C05.021.001 C05.021.001A C05.021.010 C05.021.010A C05.021.020 C05.021.020A C05.021.028 C05.021.028A C05.021.037 C05.021.037A C05.021.038 C05.021.038A C05.021.047 C05.021.047A C05.021.052 C05.021.052A 3HP-241-33 3LP-135-2 3RC-265-79 3-PiAl-10 3-50-152-10 3RC-265-67 3RC-265-76 3-51 A-0-2478A-H5C 3-RPV-CRD-58WH9 3-RPV-CRD-58WH60 3-RPV-CRD-58 3-RPV-CRD-58W61 3-01A-0-2441-Hi2 3-51A-1-0-2437A-SR16 3-53-0-2478A-H5 3-54A-3-0-2435B-SR7 3-HPI-PUMP-3B 3LP-134-103 3LP-134-103 3LP-132-20 3LP-132-20 3-51A-101-1 3-51A-101-1 3-51A-1 18-31 3-51 A-1 18-31 3-51 A-1 20-8 3-51 A-1 20-8 3HP-501-20 3HP-501-20 3-51 A-52-39 3-51 A-52-39 3-51 A-52-40 3-51 A-52-40 3-51 A-59-6 3-51 A-59-6 3HP-365-9C 3HP-365-9C 51A 53A 51A 50 50 51A 51A 51A 50 50 50 50 01A 51A 53 54A 51A 53A 53A 53A 53A 51A 51A 51A 51A 51A 51A 51A 51A 51A 51 A 51 A 51A 51A 51A 51A 51A 05/09/2006 05/08/2006 05/08/2006 05/08/2006 05/04/2006 05/09/2006 05/09/2006 05/14/2006 05/06/2006 05/05/2006 05/05/2006 05/05/2006 05/16/2006 02/02/2006 05/10/2006 04/24/2006 02/17/2005 02/02/2006 02/01/2006 02/01/2006 01/30/2006 02/03/2006 02/01/2006 01/31/2006 01/30/2006 01/31/2006 01/30/2006 05/14/2006 05/14/2006 02/03/2006 02/01/2006 02/06/2006 02/06/2006 01/31/2006 01/30/2006 02/02/2006 02/01/2006 Oconee 3 Inservice Inspection Listing Interval 4 Outage 1 INSP STATUS INSP LIMITED GEO REF CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR 37.50%
N CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR N
CLR 89.40%
N CLR N
COMMENTS RFR N
N N
N N
N N
N N
N N
N N
N N
N N
Y N
N N
N N
N N
N N
N N
N N
N N
N N
Y N
COMMENTS Relief Request will be filed for the limitation.
Relief Request will be filed for the limitation.
EOC 22 Plant: Oconee 3 DUKE ENERGY PORATION QUALITY ASSURANCE ECHNICAL SERVICES In-Service Inspection Database Management System Oconee 3 Inservice Inspection Listing Interval 4 Outage 1 TE INSP STATUS INSP LIMITED GEO REF RFR Run D Page 4 08/03/2006 COMMENTS ITEM NUMBER C05.021.060 C05.021.060A C05.021.070 C05.021.070A C05.021.071 C05.021.071 A C05.051.010 C05.051.01 OA C05.051.011 C05.051.011 A C05.051.021 C05.051.021 A C05.051.023 C05.051.023A C05.051.027 C05.051.027A C05.051.041 C05.051.041 A C05.070.001 C05.081.001 D01.020.001 D01.020.021 D01.020.024 D01.020.074 F01.010.014 F01.010.015 F01.011.025 F01.012.011 F01.020.004 ID NUMBER SYSTEM INSP DA 3-51 A-87-25 3-51 A-87-25 3-RCP-FTR3B-SH-1 3-RCP-FTR3B-SH-1 3-RCP-FTR3B-SH-2 3-RCP-FTR3B-SH-2 3MS-138-19V 3MS-138-19V 3MS-138-21V 3MS-138-21V 3-03-31-16A 3-03-31-16A 3SGB-W277 3SGB-W277 3LPS-509-5 3LPS-509-5 3LPS-478-56 3LPS-478-56 3-BWST-OUT-2 3MS-22A-E 3-01A-2403D-LC-1603 3-03-0-2439B-H54 3-03A-1-0-2401A-H52 3-14B-2439B-DE043 3-51A-0-2479A-H5A 3-51A-0-2478A-H5C 3-53A-0-2479A-H24C 3-51A-0-2479A-H11A 3-01A-0-2441-H12 51A 05/16/2006 51A 05/16/2006 51A 05/06/2006 CLR CLR REC N
N N
N N
N N
N N
N 51A 05/16/2006 CLR 51A 05/06/2006 REC All indication (porosity) sizes are < 12.5 surface flaw a/t% per Appendix A, figure B of NDE-12.
All indication (porosity) sizes are < 12.5 surface flaw a/t% per Appendix A, figure B of NDE-12.
51A 01A 01A 01A 01A 03 03 03A 03A 14B 14B 14B 14B 53B 01A 01A 03 03A 14B 51 A 51 A 05/16/2006 05/03/2006 05/03/2006 05/03/2006 05/03/2006 05/05/2006 05/05/2006 05/14/2006 05/14/2006 01/31/2006 01/31/2006 01/31/2006 01/30/2006 01/31/2006 05/16/2006 04/30/2006 05/06/2006 01/05/2006 01/31/2006 05/05/2006 05/13/2006 CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR CLR REC N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
N N
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. Work Order 98375661 was written to correct problems.
53A 05/03/2006 REC 51A 05/05/2006 CLR 01A 05/03/2006 REC N
N N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
C DUKE ENERGY PORATION QUALITY ASSURANCE TECHNICAL SERVICES In-Service Inspection Database Management System Oconee 3 Inservice Inspection Listing Interval 4 Outage 1 C
EOC 22 Plant: Oconee 3 Run D Page 5 08/03/2006 ITEM NUMB F01.020.011 F01.020.022 ER F01.020.023 FO1.020.035 F01.020.036 F01.020.037 F01.020.038 F01.020.039 F01.020.040 F01.020.074 F01.020.083 F01.021.028 F01.021.049 F01.022.043 F01.030.002 F01.030.021 F01.030.024 F01.030.027 F01.030.030 F01.030.040 ID NUMBER 3-03-0-2479A-H5A 3-14B-0-2439B-WM-1 00 3-1 4B-0-2479A-H1 6A 3-51 A-1 2439A-H240 3-51A-1-0-2439A-H241 3-51A-1-0-2439A-H314 3-51A-0-2438C-DE030 3-51A-0-2478A-RJ-100 3-51A-0-2479A-H17C 3-53B-2-0-2436C-H1143 3-54A-3-0-2436D-H46 3-14B-0-2479A-H1 1 F 3-51A-1-0-2437A-SR16 3-54A-3-0-2435B-SR7 3-01 A-2403E-H4458 3-03-0-2439B-H54 3-03A-1-0-2439B-Hi3 3-03A-1-0-2437A-H137 3-03A-2400A-H126 3-03A-2401 B-DE024 SYSTEM 03 14B 05/03/2006 01/31/2006 INSP DATE INSP STATUS CLR REC INSP LIMITED GEO REF RFR COMMENTS INSP LIMITED GEO REF RFR 14B 05/05/2006 CLR 51A 01/31/2006 REC 51A 01/31/2006 CLR 51A 01/31/2006 REC 51A 01/23/2006 CLR 51A 05/13/2006 REC 51A 05/05/2006 REC N
N N
N N
N N
N N
N COMMENTS N
N N
N N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. Work Order 98375655 was written to correct problems.
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. Work Order 98371273 was written to correct problems.
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
53B 01/23/2006 54A 01/23/2006 14B 05/05/2006 51A 01/23/2006 REC CLR CLR REC N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
N N
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
N N
N N
N N
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
N N
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
54A 04/17/2006 REC 01A 01/23/2006 CLR 03 05/06/2006 REC N
N N
N N
N N
N N
N N
N 03A 03A 03A 03A 0113112006 01/23/2006 03/07/2006 03/02/2006 CLR CLR CLR REC The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. Work Order 98377084 was written to correct problems.
The discrepancies that were found were reviewed by civil
C DUKE ENERGY(
PORATION QUALITY ASSURANCE TECHNICAL SERVICES In-Service Inspection Database Management System C
EOC 22 Plant: Oconee 3 ITEM NUMBER Oconee 3 Inservice Inspection Listing Interval 4 Outage 1 INSP STATUS INSP LIMITED GEO REF Run D Page 6 08/03/2006 ID NUMBER SYSTEM INSP DATE RFR COMMENTS F01.030.052 F01.030.081 F01.030.103 F01.030.104 F01.030.105 F01.030.106 F01.030.107 F01.030.112 F01.030.113 F01.030.114 F01.031.001 F01.031.028 F01.032.023 F01.040.004 F01.040.005 F01.040.006 F01.040.007 F01.040.011 F01.040.012 H03.001.006 H03.001.007 H03.001.008 H03.001.012 3-04A-2-0-2439B-SR4 3-08-2400A-H10 3-14B-2439B-DE043 3-14B-2439B-DE033 3-14B-2439B-DE044 3-14B-2437B-DE007 3-14B-2437A-DE019 3-56-5-0-2437A-H2 3-56-1-0-2437A-SR1 10 3-56-1-0-2437A-SR102 3-01 A-2403D-LC-1 603 3-03A-2439F-H5618 3-03A-1-0-2401A-H52 3-LDC-A 3-DHRC-A 3-50-RCPM-H6625 3-RB-CC-C 3-LPSW-PU-A 3-LPSW-STR-A 04A 02/16/2006 REC engineering and the support was found to be acceptable for service.
N N
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
08 14B 14B 14B 14B 14B 56 56 56 01A 01/23/2006 01/31/2006 02/14/2006 02/14/2006 02107/2006 01/23/2006 01/23/2006 01/23/2006 01/23/2006 04/30/2006 CLR CLR CLR CLR REC CLR CLR CLR CLR REC N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
03A 01/31/2006 REC 03A 01/05/2006 REC N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
N N
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
51 A 53 50 14B 14B 14B 05/03/2006 01/23/2006 05/03/2006 05/03/2006 01/23/2006 04/19/2006 05/12/2006 05/12/2006 05/12/2006 05/13/2006 CLR CLR CLR CLR CLR REC CLR CLR CLR CLR N
N N
N N
N N
N N
N N
N N
N N
N N
N N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
3-03-31-10 3-03-31-1 OG 3-03-31-8 3-03-31-3 03 03 03 03
C EOC 22 Plant: Oconee 3 DUKE ENERGY r PORATION QUALITY ASSURANCE TECHNICAL SERVICES In-Service Inspection Database Management System Oconee 3 Inservice Inspection Listing Interval 4 Outage 1 INSP DATE INSP STATUS INSP LIMITED GEO REF RFR Run D Page 7 08/03/2006 COMMENTS ITEM NUMBER H03.001.013 H04.001.001 H04.001.002 H04.001.002A H04.001.003 H04.001.004 H04.001.005 H04.001.006 H04.001.007 H04.001.007A H04.001.022 H04.001.022A H04.001.023 H04.001.023A H04.001.042 H04.001.045 ID NUMBER SYSTEM 3-03-31-3G 3-03-2439B-H5041 3-03-0-2439B-H54 3-03-0-2439B-H54 3-03-0-2439A-H53 3-03-0-2439A-H52 3-03-0-2401 A-H51 3-03-0-2401A-DE001 3-03-0-2401A-H50 3-03-0-2401A-H50 3-FPA-27 3-FPA-27 3-FPA-25 3-FPA-25 3-01A-0-24011B-H-19 3-01 A-0-2401 B-H22 03 03 05/13/2006 CLR 01/31/2006 REC N
N N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
N N
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. Work Order 98377084 was written to correct problems.
03 05/06/2006 REC 03 03 03 03 03 03 03 03 03 03 05/11/2006 CLR 01/31/2006 REC 01/25/2006 CLR 01/18/2006 REC N
N N
N N
N N
N 01/18/2006 CLR 04/29/2006 REC 05/15/2006 CLR 05/22/2006 REC N
N N
N N
N N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. Work Order 98372891 was written to correct problems.
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. OE300823 was written to perform the required modifications. PIP 0-06-02812 was written to document and track the correction of this problem.
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. Work Order 98376317 and 98376944 were written to correct problems.
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service. Work Order 98376317 and 98376944 were written to correct problems.
05/10/2006 CLR 05/22/2006 REC N
N N
N 03 05/10/2006 CLR 01A 01/18/2006 REC 01A 01/18/2006 REC N
N N
N The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
N N
The discrepancies that were found were reviewed by civil engineering and the support was found to be acceptable for service.
5.0 Owner's Report for Repair and Replacement Activities As required by the applicable code, records of Class 1 and Class 2 Repair and Replacement work is included on NIS-2 forms in this section.
Due to station processing and approval time frames, three categories of repair and replacement documentation exist for: 1) work performed during a prior refueling cycle; 2) work performed during the current refueling cycle; and 3) work completed but documentation not yet reviewed and approved.
There were 10 work orders for Category 1 repair and replacement documentation for this reporting period. Work Orders 98477769, 98477773, 98359458, 98477774, 98382634, 98564758, 98661506-02, 98698904-01, 98661506-01, and 98688463 had work completed prior to 1-2-2005 and copies of the NIS-2 forms are included in this report. PIP 0-05-01326 was written at the end of the Unit 3 EOC-21 refueling outage to document the late submittal for the NIS-2 forms.
Category 2 had 46 NIS-2 forms for work orders completed during this reporting period. Copies of the NIS-2 forms are included in this section of the report.
There were no Category 3 items during this reporting period.
The individual work order documents and manufacturers' data reports are on file at Oconee Nuclear Station.
5.1 Class 1 and 2 Preservice Examinations As required by the applicable code, Preservice Inspection (PSI) Examinations were performed on ISI Class 1 and ISI Class 2 items during this report period.
There is a list for PSI exams that were performed and the list is located behind the NIS-2 forms in this section. The list has one page and is entitled "Preservice Examinations of Class 1 & 2 Welds". PSI examination data for items on the list previously mentioned is on file in the Oconee Nuclear Station QA Vault.
EOC 22 Refueling Outage Report Oconee Unit 3 Section 5 Page 1 of 1 Revision 0 August 3, 2006
t°
'Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions ofthe'ASME Code Section XI Work Order Number98477769 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company
-Oconee Nuclear Station ONS -
526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 11/24/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class High Pressure Injection System, ASME Class 2 5.
(a) Applicable USAS 1331.7 19 69
- Edition, No
- Addenda, No Code Case Construction Code:
(b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section Xl Code Case(s)
N-556
- 6. Identification of Components Name of Component Name of Manufacturer Manufacturer Serial Number National Board No.
Other Identification Year Built Corrected,
- 7. Description of Work Replace the old wedge on 3HP-25with a new wedge that has hardfacing added to the guides to eliminate a performance concern that is detailed in PIP 0-01-2188. The body/bonnet nuts were not marked and assumed to be the original nut material. Dawing OM 201 -186 shows that the B/B nuts should be replaced with SA194, grade 2H material. The replacement material is superior in quality and strength when compared to the original material.
- 8. Test Conducteo H" lydrostatic F-1 Pneumatic Ri Nominal Operating Pressure E-] Exempt
[
F/V Leak Check Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number I
98477769 Sheet 2,of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached)
Wedge w/ Hardfacing on the guides, Stock Code H 530427, Serial # B8042-4 Body/Bonnet Nuts, Stock Code # 293556, ASME SA194, Gr 2H, HT # 7307732 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Date
_'/-__-_
W
"'~vnerjr/Owner's Dd-ignee, Tittle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and th.e State or Province of (1v/oez-x Z'*A*,,
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 9_'?-_e-5/
to
//-Z/'-C) 5"
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing th~s certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
-hspector's Signature Date
__-/7-_
Commissions 4/
$/*'A/i'c National Board, State, Province, and Endorsements
Form NIS-2 Owner's Report for Repair/Replacement Activiiy As required by the provisions of the ASME Code Section XI Work Order Number 1
98477773 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS -
526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 11/24/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class High Pressure Injection System, ASME Class 2 5.
(a) Applicable USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case Construction Code:
(b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section XI Code Case(s)
N-556
- 6. Identification of Components Name of Name of Manufacturer National Other Year Built Corrected, ASME Code Component Manufacturer Serial Number Board No.
Identification
- Removed, Stamped or Installed (Yes / No) 3HP-24 Powell UNK LUNK NONE LJNK Corrected NO I
- 7. Description of Work Replace the old wedge on 3HP-24 with a new wedge that has hardfacing added to the guides to eliminate a performance concern that is detailed in PIP 0-01-2188. The body/bonnet studs and nuts were not marked and assumed to be the original fastener material. Outline drawing OM 201 -186 shows that the B/B studs and nuts should be replaced with SA-193, Grade B7 and SA-194, grade 2H respectively. The replacement material is superior in quality and strength when compared to the original material.
- 8. Test Conducteal II Hydrostatic
-- Pneumatic '
-- Nominal Operating Pressure
["] Exempt 19 F/V Leak Check OF Pressure PSI Test Temperature
Form NIS:-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98477773.
I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached)
Wedge w/ Hardfacing on the guides, Stock Code # 530427,'Serial # B8042-4 Body/Bonnet Threaded Rod (Studs), Stock Code # 297412, ASME A 193, GR B7, HT # 622817 Body/Bonnet Nuts. Stock Code # 293556, ASME SA194. Gr 2H, HT # 7307732 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed xv/,/
Date ly/- e'f-Oef tOhner r wner's Degnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of..44VazrI.'
e., o.,
and employed by HSB CT of Hartford, Connecticut have inspected the components describecd in this Owner's Report during the period Y-218 -
- V to
//-.Z
,-o V
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date Commissions,
/J'S
',./,)
National Board, State, Province, and Endorsements Inspector's Signature J/
7-c..x"
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98359458 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company.
Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC.29672 11/23/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Ghurch Street Not Applicable Charlotte, NC 2820 1-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Feedwater, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 68
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
Valve 3FDW-334 Pacific 289232 N/A N/A UNK Corrected NO N/A N/A N/A N/A N/A N/A N/A NA/
- 7. Description of Work Body to Bonnet bolting was replaced.
t JJt
. Test Conducted H-"
lydrostatic E]- Pneumatic Pressure L--Nominal Operating Pressure r-] Exempt PSI Test Temperature Other IrZ/"*.et Ch/ti, OF "I 0
-oCF?
I A4
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section Xl Work Order Number 98359458 I
Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Studs for 3FDW-334, UTC No. 0001062615 and Nuts UTC No. 0001062844 Were installed.
0 0
O O
M.
0 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Engineer Date 11/23/2004 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Alo.,,-,v and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
//-,/z -e V to
//- 2,
ý-/
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions
'/c-
-"-'--Tnspector's Signature National Board, State, Province, and Endorsements Date
Form 'NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI V
Work Order Number 98477774 Sheet I of 3
- 1. Owner 2." Plant Unit Duke Power Company Oconee Nuclear Station ONS -
526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 11/18/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class 3LP-21, 3A BWST Suction Isol. (Low Pressure Injection System), ASME Class 2 5.
(a) Applicable USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case Construction Code:
(b) Applicable Edition Section Xl Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Code Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Stamped or Installed (Yes I No)
Removed existing wedge Powell N/A N/A N/A N/A Removed NO on 3LP-21 Installed new wedge on Pratt SN#7 N/A N/A 2002 Installed NO 3LP-21 Removed body/bonnet UNK N/A N/A N/A N/A Removed NO studs on 3LP-21 Installed new UTC#'s body/bonnet Mackson A518 N/A
.,01008151 &
99 & 04 Installed NO studs on 3LP-21
- 7. Description of Work Replace the old wedge on 3LP-21 with a new wedge that has hardfacing added to the guides to eliminate a performance concern that is detailed in PIP 0-01-2188. The body/bonnet studs and nuts were not marked and assumed to be the original fastener material. Outline drawing OM 2201 -453 shows that the 13/B studs and nuts should be replaced with ASME SA 193, Grade 137 and SA;1 94, grade 2H respectively. The replacement material is superior in quality and strength when compared to the original material.
- 8. Test Conducted F-Hydrostatic E] Pneumatic 1"' Nominal Operating Pressure 1L Exempt
[*
F/V Leak Check OF Pressure PSI Test Temperature MEN
Form 'NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U
Work Order Number 98477774 Sheet 2 of 3
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 11/11/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201- 006 Expiration Date I
Not Applicable
- 4. Identification of System, ASME Class 3LP-21, 3A RX BLDG (Pen #36) Emerg Sump Isol. (Low Pressure Injection System), ASME Class 2 5.
(a) Applicable Construction Code:
USAS B331.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
Removed old Body/Bonnet Unk N/A N/A N/A N/A Removed NO nuts on 3LP-21.
Install new Body/Bonnet Mackson N/A UTC#'s 2003 Installed NO nuts on 3LP-0001060162 21.
¶form'NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section Xl Work Order Number Sheet 0w1 98477774 3 of 3
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 Wedge w/ Hardfacing on the guides, Stock Code # 496900, Serial # 7 A a o S4 _25 O a O Body/Bonnet Threaded Rod (Studs), Stock Code # 297415, ASME SA193, GR B7 Class A O Body/Bonnet Nuts, Stock Code # 131738, ASME SA 194, Gr 2H O
0 0
0 0
O CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of thoriz ion urn Not Applicable
.Expiration Date Not Applicable Signed
_DI ate 1,
Ownr r'/ein
- Title, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commrn~ssionp]s,ed by he National Board of Boiler and Pressure Vessel Inspectors and the State or Province of A) t
.Zi z
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
_____-__/
V/
to
/
,,and state that to the best of my knowledge and belief, the Owner has performed exarrnihations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind an ing from or connected with this inspection.
~~~ ~Commissions
/(/O j Date Inspector's Signature National Board, State, Province, and Endorsements Date
/a--tS
Forln NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section Xi V
Work Order Number 1
98 Sheet I of 3 382634.
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS -3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 11/11/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class 3LP-1 9, 3A RX BLDG (Pen #36) Emerg Sump Isol. (Low Pressure Injection System), ASME Class 2 5.
(a) Applicable USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case Construction Code:
(b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Built Corrected, ASME Code I-.- mtonct-
-anu~cure-4 -erti umner-4 -boa4rd-No-1=wenI~ftmtcitIof-I i -Remover'e
-j-tammoe or Installed (Yes / No)
Removed existing wedge on Powell N/A N/A N/A N/A Removed NO 3LP-19 Installed new wedge on Pratt SN#6 N/A N/A 2002 Installed NO 3LP-19 Removed body/bonnet studs UNK N/A N/A N/A N/A Removed NO on 3LP-19 Installed new body/bonnet Mackson A518 N/A Heat # 9303 1993 Installed NO studs on 3LP-19 7.. Description of Work Replace the old wedge on 3LP-19 with a new wedge that has hardfacing added to the guides to eliminate a performance concern that is detailed in PIP 0-01-2188. The body/bonnet studs and nuts were not marked and assumed to be the original fastener material. Outline drawing OM 2201 -454 shows that the B/B studs and nuts should be replaced with SA 453, Grade 660 and SA-194, grade 6 respectively. The replacement material is superior in quality and strength when compared to the original material. *
- 8. Test Conducted liii Hydrostatic r-1 Pneumatic L Nominal Operating Pressure 1-"] Exempt F/V Leak Check OF Pressure PSI Test Temperature I.
Fortn NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98382634 Sheet 2 of 3
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 1 1/11/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class 3LP-19, 3A RX BLDG (Pen #36) Emerg Sump Isol. (Low Pressure Injection System), ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
Removed old Body/Bonnet Unk N/A N/A N/A N/A Removed NO nuts on 3LP-19.
Install new Body/Bonnet Mackson N/A Heat Treat #
2004 Installed NO nuts on 3LP-52387 19.
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 98382634 3.of 3
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Wedge w/ Hardfacing on thý guides, Stock Code # 496900, Serial # 6 0 Body/Bonnet Threaded Rod (Studs), Stock Code # 297448, ASME SA453, GR 660 Class A, UTC # 0001059497, HT # HX6 O Body/Bonnet Nuts, Stock Code # 131738, ASME SA194, Gr 6, UTC # 0001073599, HT # 52387 O
0 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of A oriz*brjj'4u llr Not Applicable Expiration Date Not Applicable Signed WAi*
/A//q ys! A-Date // L, Owner & Owp(r's Designee, Title "
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of,Ac-,z
' V* Z,U.t.,
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 57-2&c-C) V to
/2-/-o Y
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
(~) _____________________Commissions
,/6/%'/-
/.
Inspector's Signature National Board, State, Province, and Endorsements Date S-2$-'0 0*
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME. Code Section XI
'I I
Work Order Number 98564758 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Chadlotte, NC 2820 1-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class High Pressure Injection, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 68
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, 1992 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 3HP-0058 Velan Valve Unknown N/A N/A 1968 Corrected NO N/A N/A N/A N/A N/A N/A N/A N/A
- 7. Description of Work Body to bonnet bolting was replaced.
J
- 8. Test Conducted
[] Hydrostatic
[] Pneumatic Pressure L-]Nominal Operating Pressure E] Exempt
[P Other
'/jzs d-PSI Test Temperature OF "
Z
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98564758 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Bolting for 3HP-0058 UTC No. 0001062084 and Nuts for bolting UTC No. 0001071271 were installed.
) N/A O N/A O N/A O N/A
( N/A O N/A O N/A 0 N/A CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Auth ~zation Number Not Applicable Expiration Date Not Applicable Signed Engineer Date 11/23/2004 D
nT CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
,-7' and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Rejort during the period
//-/.o -o V to
,-Z 9'
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Inspector's Signature mDate
.'4 Commissions
.JC/$
'/
,,d'c...
National Board, State, Province, and Endorsements
.orm NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI S
Work Order Number 98661506-02 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 11/26/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Spent Fuel Cooling, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section Xl Code Case(s)
N-556
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
"nubber on S/R 3-56-0-2478A-Grinnell 30200 None None UNK Removed NO HI-0 Snubber on S/R 3-56-0-2478A-Grinnell 35759 None None 2004 Installed NO HI0
- 7. Description of Work Snubber removed, rebuilt and converted to Config. A, tested and reinstalled.
- 9. Test Conducted F] Hydrostatic 1
Pneumatic LI Nominal Operating Pressure 0
Exempt Pressure PSI Test Temperature
"-'Other OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98661506-02 I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 Installed new modifier kit UTC 0001057222. and seal kit UTC 0001056635.
0 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Z.
°4sretv Repair/Replacement Engineer Date 11/26/04 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
,,e 4,,0,4 and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 0_-o__0 to
.//-,z. -C, -1
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
--4aspector's Signature Date Commissions
,J/
.Y-*,O/..'_
National Board, State, Province. and Endorsements
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98698904-01 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 11/26/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Chartotte, N7C 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Low Pressure Injection, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section XI Code Case(s)
N-556
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
Inubber on S/R 3-53B-2 Grinnell 10344 None None UNK Corrected NO 2435B-SR22
- 7. Description of Work Snubber rebuilt and converted to Config. A, and tested. New serial number after conversion is 35766. Snubber to be reinstalled by W.O. 98656247.
- 8. Test Conducted
[-I Hydrostatic
-]Pneumatic E" Nominal Operating Pressure Exempt Other I
Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98698904-01 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Installed new modifier kit UTC 0001057730, seal kit UTC 0001042786, and bushing stock 0044241.
0 Q
o CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
~R..o4ACRepair/Replacement Engineer Date 11/26/04 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of k,,,,
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
.-,Z,.r--,,v" to C>
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the ex5minations and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions National Board, State, Province, and Endorsements Inspector's Signature IDate 3
2/o
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 98661506-01 Sheet.
I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 11/26/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlptte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Low Pressure Injection, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section XI Code Case(s)
N-556
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) nubber on S/R 3-53A-0-2479A-Lynair Unknown None None UNK Removed NO HIC OSnubber on S/R 3-53A-0-2479A-Grinnell 35541 None None 2004 Installed NO HIC
Test Conducted lydrostatic 1:1 Pneumatic
[-1 Nominal Operating Pressure 0
Exempt Pressure PSI Test Temperature LI Other OF h
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98661506-01 I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Installed new. snubber UTC 0001051561, and replaced piston rod eye, UTC 1053974 0
0 o
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
11 Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed SAIAA..C Repair/Replacement Engineer Date 11/26/04 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of e,-,7,v and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
/0 - a6,V '5" to
,/ /-
e- -. 5/
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions
.Jc'
.-- z.J/ '
National Board, State, Province, and Endorsements DateIi ector's Signature I
Date
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI
'U Work Order Number 98688463 Sheet I of 2 (ml
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672.
12/16/2004
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Main Steam, ASME Class 2 5..
(a) Applicable Construction Code:
USAS B31.1 19 67
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section XI Code Case(s)
N-416-1
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 4ipe DPCo.
None None None 2004 Installed NO
- 7. Description of Work OE-18489, Installed a 3" capped branch, 2" plugged half coupling and plugged an existing 1-1/2" half coupling.
i Test Conducted
-" Hlydrostatic
'- Pneumatic 1K Nominal Operating Pressure
['
Exempt r
Pressure PSI Test Temperature
- ] Other
9.
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number ExpirationDateNot Applicable Signed Date Owner or Owner's Designee, Titr e, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of.4.=,7' 4,.oc,,
and employed.by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
/Z-V*'-o to iZ-//..
1'
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date Commissions 4 i /VA
,I4ldc National Board, State, Province, and Endorsements
- pector's Signature
FormrNIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 98777029 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/28/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NQ 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Reactor Coolant, ASME Class 1 5.
(a) Applicable Construction Code:
USAS B31.7
- 19.
69
- Edition, 06/68
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification
.Built
- Removed, Code.
or Installed Stamped (Yes I No) alve 3RC-2 KSB 0146061/6 1103 DMV-789 2000 Removed YES Valve 3RC-2 Flowserve 91AWZ 1320 UTC 1091352 2004 Installed YES Piping DPCo None None None 2006 Installed NO liiiI~~II_
- 7. Description of Work Removed existing stainless steel valve and replaced with stainless steel valve because the existing valve had not been flow tested. Therefore, the differential pressure versus flow rate when the valve was fully open could not be precisely L-Mnown.
- 8. Test Conducted H
Hydrostatic E] Pneumatic 1-- Nominal Operating Pressure I"' Exempt Other Visual Pressure PSI Test Temperature OF
Foim NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98777029 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 Removed existine valve 3RC-2 and reolaced with a stainless steel valve (serial#91AWZ).
0 Q
0o 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed rL P-l-t-"
Date
.1oSIO*6 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period to 7-'/p*.,
, and state that t6 the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions,-
,,v'/,e..-
I U)
Date
-nspecscr's Signature "7--/
Y,-oe*.
National Board, State, Province, and Endorsements I
Form NIS-2 Owner's Report for Repair/Replac ement Activity As required by the provisions of the ASME Code Section XI Work Order Number
.98771071-01 Sheet 1 of2
- 1. Owner I
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 2820 1-1006 Seneca, SC 29672 5/24/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class High Pressure Injection system, Letdown Cooler, ASME Class 1 5.
(a) Applicable Construction Code:
B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Component Name of Manufacturer Manufacturer Serial Number National Board No.
Other Identification Year Built Corrected,
- Removed, or Installed ASME Code Stamped (Yes / No) 3A Letdown Graham Cooler-old 0 Manufacturing 44773-3 12769 None 1983 Removed YES Corp.
3A Letdown Graham Cooler - new 0 Manufacturing 44773-1 12767 None 1983 Installed YES Corp._____
- 7. Description of Work Replacement of 3A Letdown Cooler with used spare cooler of same design.
- 8. Test Conducted H-Hydrostatic r-1 Pneumatic Nominal Operating Pressure
[:] Exempt Pressure PSI Test Temperature Other functional leak check OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98771071-01 I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 Form N-i (2 pages) attached for S/N 44773-3, the Letdown Cooler removed from the 3A position. This cooler was constructed to ASME Section III, Class 3, 1980 edition, summer 1980 addenda.
@ Form N-I (2 pages) attached for S/N 44773-I, the used spare Letdown Cooler to be installed in the 3A position. This cooler was also constructed to ASME Section III, Class 3, 1980 edition, summer 1980 addenda. To make this a useable spare, this Letdown Cooler had one tube plugged with mechanical plugs (two Pop-A-Plugs installed) under WO # 98763544.
0
.F E
C I
CERIFIAT CoFe COMPLIANCE.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
?.'yV~
~/ h~Engineer Date 5/24/2006 P~wner or Owner's 15esignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of /o, ry.1 and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 3,z.?5'/0 e.
to 7c,,.ý//,
and state that to the best of my knowledge and belief, thd Owrer has performed exa rinatibns and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions /jc i?
'vdl National Board, State, Province, and Endorsements I "fi"pector's Signature Date
- I-/ 4/'-.*.
Form NIS-2 Owner's Report for. Repair/Replacement Activity As required by the provisions of the ASME Code Section Xl I
Work Order Number 98741772-06 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NIC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Reactor Coolant, ASME Class I 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/13 Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 3RC-68 Consolidated BL-08896 none none UNK Removed YES 3RC-68 Consolidated BL-08895 none none UNK Installed YES
- 7. Description of Work Installed valve, serial number BL-08896, was removed for section XI testing. Replaced with previously tested spare, 4 serial number BL-08895, from stock. Valve, serial number BL-08895 was removed from unit 2 and repaired on work order number 98719296-01.
- 8. Test Conducted j ] Hydrostatic
["-] Pneumatic 1:1 Nominal Operating Pressure 1-- Exempt 0
Other RCS visual Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity ks required by the provisions of the ASME Code Section XI Work Order Number Sheet 98741772-06 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Replaced existing valve with tested valve form stock. Serial number BL-08895.
0o 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
"*/,4 __ /ý',k.
ýve, Date f
Owner or Owner's Vesignee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the. State or Province of x)oerw and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period el-to 7-/1-. ee-
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions
_____'_/__/____'__-"
Spector's Signature National Board, State, Province, and Endorsements Date ___
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98719296-01 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South CGiurch Street Not Applicable Charfotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Reactor Coolant, ASME Class I 5.
(a) Applicable Construction Code:
ASME Section III 19 65
- Edition, 67
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
Pressurizer Code Safety Valve Dresser BL-08895 n/a none UNK Corrected YES (spare)
- 7. Description of Work L 1]qeplaced disc and nozzle.
I
- 8. Test Conducted i Hlydrostatic F1 Pneumatic 1:1 Nominal Operating Pressure
[
Exempt
[
Other Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replac'ement Activity
's required by the provisions of the ASME Code Section XI I
Work Order Number Sheet 98719296-01 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Disc is stock code 423063, UTC: 1068295.
O Nozzle is stock code 582128, UTC: 1087884.
0 Z
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Nbt Applicable Certificate of Authorization Numye)
Not Applicable Expiration Date Not Applicable Signed
-- iAýi IA I (/R-
/
Date S
Owner or O(vner's De~gnee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of liogi7w 1
and employed by HSI3 CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 7-zg-oci-to 7-/ -'e -0 6
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this O~wner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
________________________Commissions_______________
Inspector's Signature National Board, State, Province, and Endorsements Date 7 -____
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98697785-01 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/17/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company' Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
(a) Applicable Construction Code:
ASME Section III 19 g
- Edition, 0
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 qrv
- Edition,
ýZ&e5'0 Addenda.
(c) Applicable Section XI Code.Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped-(Yes I No) 3HP-VA-334 Yarway Unknown None None 1992 NO
.*f-K
- 7. Description of Work Replaced stem and disc asembly due to valve leakage.
M. I
- 8. Test Conducted H
lHydrostatic El Pneumatic to Nominal Operating Pressure E1 Exempt Pressure PSI Test Temperature El Other OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98697785-01 I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Disc and stem assembly, UTC1074791, SC 279949 0
0 0
0 0
0 c0 CERTIFICATE OF COMPLIANCE..
I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable SignedQ.-
t A
- -r, -
-/t/9(
Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of.,(,6crw. -
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
-9' a.
to 7-./,'-6 6
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date Commissions National Board, State, Province, and Endorsements a
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98741777-07 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy 4
Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration'Date Not Applicable
- 4. Identification of System, ASME Class Reactor Coolant System, ASME Class 1 5.
(a) Applicable Construction Code:
USAS 1331.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 3RC-66 Consolidated BL-08903 none none 1969 Removed NO O3RC-66 Consolidated BW-08706 none none 1980 Installed NO 0 Inlet Flange LINK none none none LUNK Corrected NO Bolting
- 7. Description of Work Valve serial number BL-08903, was removed for ASME section XI testing. Replaced with tested spare valve, serial L
number BW-08706 from stock. Installed new inlet bolting material to facilitate through studded base.
- 8. Test Conducted
-] Hydrostatic Ed Pneumatic
-] Nominal Operating Pressure
[:] Exempt Z Other RCS Visual Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section X!
I Work Order Number 98741777-07 I
Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Replaced existing valve with tested spare from stock. Serial number: BW-08706 0 Inlet Stud material - stock code # 297388, UTC # 1073084, Inlet Nut Material - stock code # 131853, UTC # 1067856 0
G 0
0 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed 5/rSr.
Engineer Date 5/16/2006
-Owner or Owner's'Designee, Title CERTIFICATE OF INSERVICE INSPECTION
- r I, the undersigned, holding a valid commission issued by the National Board of Boiler and PresTs-ure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
/_Y._"--o 0_r, to 7-*,. o
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date 5:;Z
__4eýg Commissions iQC,4
/
/,,
National Board, State, Province, and Endorsements
~'~~pector's Signature
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI
- 1 Work Order Number 98719299-01 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy 4 Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Reactor Coolant System, ASME Class I 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
PORV (RC-66)
Consolidated BW-08706 none none 1980 Corrected NO Spare
- 7. Description of Work Replaced pilot disc and spindle as part of preventive maintenance and corrective action from PIP 05-3015.
nilot disc, stock code: 77535, UTC #: 972816
- 4'*pilot spindle, stock code: 590121, UTC #: 1087901
- 8. Test Conducted H
Hydrostatic F1 Pneumatic 1:1 Nominal Operating Pressure 0
Exempt
[:] Other Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98719299-01 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Pilot disc, stock code: 77535, UTC #: 972816, pilot spindle, stock code: 590121, UTC #: 1087901 0
CO 0
0 0
0 0
§ CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
.-£5
/ Sr. Engineer Date 5/16/2006 Owner or OW'her's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Presure Vessel Inspectors and the State or Province of
,,and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 7-46-'s.-
to 7-.,y-e1..
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Dat Commissions 9_vA.,-s8 -.
-"1Zisiector's Signature National Board, State, Province, and Endorsements I.
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98745256-01 Sheet I of 2
- 1. Owner
- 2. Plant Unit 3
Duke Power Company Oconee Nuclear Station 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/06
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, I'TC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Reactor Coolant, ASME Class 1 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes /No)
Size 2-1/2 X 5 Grinnell 16817 N/A N/A N/A Removed No Snubber Rod Eye Grinnell N/A N/A N/A N/A Removed No Size 2-1/2 X5 Snbe Anvil 36156 N/A UTC 1082297 N/A Installed No Snubber Rod Eye Anvil N/A N/A UTC 1087503 N/A Installed No
- 8. Test Conducted H
Pneumatic I Nominal Operating Pressure D Exempt
[
Other Visual Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Remwas (
W ork Order Number Sheet i
98745256-01 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 0
G O
O C CERIFIAT OFde COMPLIANCE.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed A6!0__
Date V4~9.
Owner or Owner's Designee, TitlE CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
<1oe~rwLi.eL, and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 3-.r-~to
- 7. V-O!e-
, and state that to the best of my knowledge and belief, the Owner has pe~rformed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.
By signing thig' certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
7J~*1 Commissions nspector's Sign~ature National -Board, State, Province, and Endorsements Dat 7
"/"l 0
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98764437-01, -50 Sheet I of2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/24/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 2820 1-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class High Pressure Injection system, Letdown Cooler, ASME Class 1 5.
(a) Applicable Construction Code:
B331.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes / No) 3A Letdown Graham Cooler - old O Manufacturing 97347-1" 21523 None 1994 Removed YES Corp.
Chemical Anchor-Darling ET561-I-x (as Connector 0 (supplied by part of Letdown None None 1993 Installed NO (aka pressure Cooler S/N seal)
Graham Mfg.)
97347-1) 3A Letdown Energy Steel &
None None 2006 Installed YES Cooler - new 0 Supply Co.
N32389-2
- 7. Description of Work Replacement of 3A Letdown Cooler with new spare cooler of same design. The new spare cooler (S/N N32389-2) required the installation of one chemical connector. The chemical connector that was installed was removed from the used Letdown Cooler, S/N 97347-1, which had been in service in the 3A location. *
- 8. Test Conducted 1"j Hydrostatic
[] Pneumatic
[:1 Nominal Operating Pressure
'- Exempt Other functional leak check Pressure PSI Test Temperature
- _OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section Xl Work Order Number 98764437-01, -50 Sheet 2( )f 2
~*1
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Form N-I (2 pages) attached for S/N 97347-I, the Letdown Cooler removed from the 3A position. This is also the cooler that was the "donor" of the chemical connector later installed on the S/N N32389-2 cooler. This cooler was constrtted to ASME Section III, Class 3, 1986 edition, 1988 addenda.
O Certificate of Compliance (1 page) - Anchor/Darling - Chemical Connectors ET56 1-1 and ET561 originally installed on Letdown Cooler S/N 97347-I.
One of these connectors was removed from cooler S/N 97347-1 and installed on S/N N32389-2.
The chemical connector was constructed to ASME Section III, Class 3, 1986 edition, 1988 addenda.
OForm N-I (3 pages) attached for S/N N32389-2, the new Letdown Cooler installed in the 3A position. This cooler was constructed to ASME Section 111. Class 3. 1989 edition, no addenda.
0 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed r-Owner o Engineer Date 5/24/2006 p
q CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of,
and employed by
-HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period J..-
Z c
to P-/1,'.-ol
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date
~-~¶~specorsS-ignature Commissions A4 W3___.dc),A'4 National Board, State, Province, and Endorsements U
L Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI S
Work Order Number 98738734 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/8/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NIS 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class RCS (Pressurizer), ASME Class 1
- 5.
~
(a) Applicable Construction Code:
ASME Section III 19 65
- Edition,
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
N-638-1 (for Vent Weld Pad)
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) rv Pzr Vent Nozzle B&W Unknown N/A Unknown Unkn Removed NO Pzr Vent Nozzle AREVA 5066928-01-04 N/A UTC 1082137 2005 Installed NO 1"6000# Full Cplg Unknown None None UTC 1090071 2006 Installed NO 1"600# Full Cplg Unknown None None UTC 1090071 2006 Installed NO
- 7. Description of Work The single Pzr Alloy 600 Vent Nozzle replaced with stainless steel Vent Nozzle welded to an external weld pad. New SS L
Nozzlewelded to removed N2 & Vent piping; piping reinstalled with 1", 6000# Full Coupling (two places), not BWs.
6
- 8. Test Conducted Hydrostatic 1 PneumaticrN Pressure 2250 Nominal Operating Pressure
[:] Exempt
[: Other PSI Test Temperature 650 OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XM I
Work Order Number 98738734 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Removed Vent Nozzle - SB 166 (Inconel).
O Replaced Vent Nozzle - SA 479, Type 316 stainless steel, UTC #0001084962, Manufacturer's Serial #5066928-001-04.
0 Reinstalled N2 piping (attached to Vent piping at tee) with new, 1", 6000#, SA182, F316 SW Full Coupling, UTC#000109007.
0 Reinstalled Vent ninJia2 (attached to N2 riding, at tee) with new. 1". 6000#. SA182. F316 SW Full Couolinm. UTC#000109007.
0 o
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable, Certificate kAuthorization Number Not Applicable Expiration Date Not Applicable Signed CA 4~ 4 1Aj[cIM poP~dJpk-pL CGkKS I Date
ýrIV I )a.oo(a Owner or Owner's Ibcsignee, Title 9
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of A/o,lay7",
Z.4'
.oo and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period J- -.3 - oe, to 4 -./Z -o0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this. certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
-*,4,ýector's Signature Commissions Al/e-
/',,),
,dc_
National Board, State, Province, and Endorsements Date
t J;
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 98738734 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/8/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, Ne 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class RCS (Pressurizer), ASME Class 1 5.
(a) Applicable Construction Code:
ASME Section III 19 65
- Edition, Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
,'ýzrvel Tap B&W Unknown N/A Unknown Unkn Removed NO Safe End Pzr Level Tap AREVA 5066926-01-01 N/A UTC 1082137 2005 Installed NO Safe End Pzr Level Tap B&W Unknown N/A N/A Unkn Removed NO Safe End Pzr Level Tap AREVA 5066926-01-02 N/A UTC 1082137 2005 Installed NO Safe End Pzr Level Tap B&W Unknown N/A N/A Unkn Removed NO Safe End Pzr Level Tap AREVA 5066926-01-03 N/A UTC 1082137 2005 Installed NO Safe End
- 7. Description of Work All 3 Pzr Alloy 600 steam space level safe ends and butt welds replaced with stainless steel safe ends and butt welds.
\\ *. Test Conducted
[H Hydrostatic El Pneumatic
] Nominal Operating Pressure
[-] Exempt
[:] Other Pressure 2250 PSI Test Temperature 650 OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number Sheet 98738734 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Removed Steam Space Level Tap Safe End - SB 166. No identifying information other than component material, 3RCIV-166.
0 Replaced Steam Space Level Tap Safe End - SA 479, Type 316, UTC # 0001082137, Mfg Serial #5066926-001-01, 3RCIV-166.
@ Removed Steam Space Level Tap Safe End - SB166. No identifying information other than component material, 3RCIV-167.
o Replaced Steam Spate Level Tap Safe End - SA 479, Type 316, UTC # 0001082137, Mfg Serial #5066926-001-02, 3RCIV-167.
0 Removed Steam Space Level Tap Safe End - SB1166. No identifying information other than component material, 3RCIV-165.
O Replaced Steam Snace Level TaD Safe End - SA 479. Tvoe 316. UTC # 0001082137. Mfa Serial #5066926-001-03.3RCIV-165.
Q)
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorizaion Number Not Applicable Expiration Date Not Applicable Signed C&W r).o f45W r0
.q, Date 5iiz7I2,W3I Owvner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of U/o~erw *a*za*
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
.T--3 -o0 to
- -/Ž -o,/
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this'.certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
J~~~_Commissions
,'/"/,'</,
Inspector's Signature National Board, State, Province, and Endorsements Date
,/ -/2.-O-
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98710661 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 1 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/19/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlptte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Low Pressure Injection, ASME Class 1 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 1LP-173 Flow Serve 2375-AT-680 1
2003 Removed YES 1LP-173 Flow Serve 69AYL 1289 LINK 2004 Installed YES Pipe Duke Energy None None None 2006 Installed NO Corporation None None None_00 IntaleN
- 7. Description of Work Replace valve 1LP-173, valve has packing leak.
W' 8. Test CConducted Hydrostatic
[-1 Pneumatic 0 Nominal Operating Pressure 1-- Exempt Pressure PSI Test Temperature
[-1 Other
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.
Type Code Symbol Stamp Not Applicable Expiration Date Not Applicable Date 611912006 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of,f},*e,-r,'
z
, 4 _.A and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period Z
___to 7-...,v'-4.
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing thisý certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Inspector's Signature
[Date Commissions,4).
/'.O'd'~l
'C-National Board, State, Province, and Endorsements
)'orm'NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI V
I Work Order Number 98733423 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/8/2006
- 3. Work Performed by Type Code Symbol Stamp Nolt Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
(a) Applicable Construction Code:
ASME Section III 19 74
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stampe(
(Yes / No CRDM #58 Diamond Power 1755 LINK LINK IUNK Removed YES CRDM #58 Diamond Power 1755 UNK LINK UNK Installed YES
- 7. Description of Work Remove CRDM #58 for internals repair and re-install. Replace CRDM hold down bolts and nut ring with new ones per station practice for this component.
- 8. Test Conducted HI Iydrostatic
[:] Pneumatic 0
Nominal Operating Pressure
[-] Exempt
[-] Other Pressure 2155 PSI Test Temperature
-532 OF
°,
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98733423 Sheet 2of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 CRDM # 58 was removed and the same one re-installed.
§ 8 new CRDM hold down bolts installed, old ones discarded per standard practice. Material SA-453, Gr. 660. UTC 1087309, SIN's GN-7904,-7908,-7914,-7919,-7923,-7938,-7941,-7894 O 1 new (2 piece) nut ring installed, old one discarded per standard practice. Material SA-320, Gr. L-43. f0TC 1075364, S/N GN-83 (both) 0 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
_5,s "it r
Date5/8/2006 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Al and employed by HSB CT of Hartford, Connecticut have inspected the compon'ents described in this Owner's Report during the period to
/Y-.0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Inspector's Signature Commissions National Board, State, Province, and Endorsements Date
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98660909 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station
..ONS - 3 526 South Church Street 7800 Rochester.Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672
- 3. Work.Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, !'C 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Core Flood, ASME Class 1 5.
(a) Applicable Construction Code:
USAS B31.7 19 68
- Edition, No r
- nda, No Code Case (b) Applicable Edition Section XI Utilized For RIR Activity 19 89
- Edition, W
j A.:epda.
(c) Applicable Section XI Code Case(s)
None 7V l
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 3CF-0012 Crane Nuclear Unknown N/A N/A 1968 Corrected NO N/A N/A N/A N/A N/A N/A N/A N/A
- 7. Description of Work Retaining ring was damaged during removal. New retaining ring installed.
- 8. Test Conducted L] Hydrostatic
[] Pneumatic 4 Nominal Operating Pressure
[] Exempt I"] Other Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 98660909 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 Retainingring for 3CF-0012, UTC No. 994992,.installed.
O N/A O N/A O N/A O N/A O N/A O N/A O N/A ON/A 0 N/A CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section X.
Type Code Symbol Stamp Not Applicable Certificate of Auth ation Number Not Applicable Expiration Date Not Applicable Signed Engineer Date 11/10/2004 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid cormmission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
- o ]
] t/
to
,and state that to the best of my knowledge and belief, thd Owner 'has performed examirti-ong and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing tills certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
O A/*l*i~#*C6*J/2T/Lu_
4e-* ZACommissions U Inspector's SignatureL_
National Board, State, Province, and Endorsements Date
-7/L2-1 / C
FormNIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U
I Work Order Number 98660911 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NU 28201-1006 Expiration Date I
Not Applicable
(a) Applicable Construction Code:
USAS B31.7 19 68
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89 Edition,./'e-,J92* Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed
-Stamped (Yes / No) 3CF-0014 Crane Nuclear Unknown N/A N/A 1968 Corrected NO N/A N/A N/A N/A N/A N/A N/A N/A
- 7. Description of Work Retaining ring was damaged during removal. New retaining ring installed.
- 8. Test Conducted
[]Hydrostatic
[-] Pneumatic VN Nominal Operating Pressure
["] Exempt Other Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 1
98660911 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached)
O Retaining ring for 3CF-0014, UTC.No. 9949992, installed.
0 N/A 09 NIA O9N/A O N/A ON/A
( N/AI O N/A O N/A 0 N/A CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section AI.
Type Code Symbol Stamp Not Applicable Certificate of Autho rzation Number Not Applicable Expiration Date Not Applicable Signed Engineer Date 11/10/2004
+/-I.rsDsine il CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comrissionisi ued by he National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
/0 /,"7,/n4-to
/-
0'r_____,
, and state that to the best of my knowledge and belief, the Owner' has performed examinfions and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
6I~f(
rWt*./LA7A Commissions V
Inspector's Signature '.-'
Date National Board, State, Province, and Endorsements
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98789762-01 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class High Pressure Injection, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19
-98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped
)
(Yes I No)
Anderson N98671 3HP-404 Greenwood 0003n/a none 2001 Removed YES Crosby Anderson N98671 3HP-404 Greenwood 0004n/a none 2002 Installed YES Crosby
- 7. Description of Work Install spare valve, serial number N98671-00-0004 from warehouse.
- 8. Test Conducted
]"H lydrostatic
[:] Pneumatic El Nominal Operating Pressure L Exempt
['] Other HPI leakage, Visual Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98789762-01 I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 Replaced with new tested valve from stock. Stock code 491821. UTC number 1051756.
0 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
-t..*;7
/,A
/ Sr. Engineer Date 5/19/2006
- '-Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of o_-L.6eA' L5
.4a and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 6--/7o,04 to 7-Z.-o4,
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date Commissions
/z/4'U/o-*-
National Board, State, Province, and Endorsements
- "'snspector's Signature
?7-Z. -oL.
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U
I Work Order Number 98787483 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/12/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, N-28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Low Pressure Injection, ASME Class 2
- 5.
/3I1.7 w4..
(a) Applicable Construction Code:
USAS 13;I,1P 0
1wý 9 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Component Name of Manufacturer Manufacturer Serial Number National Board No.
Other Identification Year Built Corrected,
- Removed, or Installed ASME Code Stamped (Yes I No) 4 I
9
- 4.
4 Body to Bonnet bolting to 3LP-32 UNK none none none UNK Corrected NO
- 7. Description of Work Installed new body to bonnet nuts.
U
- 8. Test Conducted
[]Hydrostatic E] Pneumatic Pressure
-- Nominal Operating Pressure ER Exempt PSI Test Temperature Z Other Visual leakage OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASMýE Code Section MI Work Order Number 98787483 I
Sheet '
2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached)
O Nut material - stock code # 131716 1, UTC # 1057527.
e 0
o CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Al.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable SindSr.
Engineer Date 6/12/2006
.D-T CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
,q and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 7-/1.e.&.
to -
-7.
-.e-*
o
,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XA.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions tC/-'c1
/,,jc._
D t r/
s,,
National Board, State. Province, and Endorsenents I Date
/'-c*
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98706523 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/25/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Reactor Building Spray, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
Hanger 3-54B-O-DPC none none none 1975 Corrected NO 2477-HI2A (I)
- 7. Description of Work Install shim between hanger and pipe to bring gap within specification.
- 8. Test Conducted H'
[-] Pneumatic Pressure E-Nominal Operating Pressure 0
Exempt PSI Test Temperature E-]Other OF
I ý Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI
,)Work Order Number Sheet 98706523 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o 1/16 inch shim, A240 Grade 304, stock code 191133 0
0 o(
0m 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
-Senior Engineer Date 5/25/2006 0winer or On s
sgnee, Title OI CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of,
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
/ - e O,T-to
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_____________________________Commissions,
~Inspector's Signature National Board, State, Province, and Endorsements Date 7e--
h
C_-
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98788172-01 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy
-Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/26/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Low Pressure Service Water, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
Pipe DPC none none none 2006 Installed NO
- 7. Description of Work Replace 4 flanges, rotate flanges to two hole position to match mating flanges.
- 8. Test Conducted HIydrostatic
[] Pneumatic
-I Nominal Operating Pressure
-I Exempt Other Leak Inspection Pressure PSI Test Temperature
°_OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98788172-01 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 3 inch weld neck pipe flange, SA182 Grade 304, 150#, Sch. 40, SIC 87823, UTC 1087201 & 1088327 3 inch schedule 40 pipe, SA312 Grade TP304, SIC 149539, UTC 1036883 Q
0 o
C 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Authori ation Number Not Applicable Expiration Date Not Applicable Signed 7/Senior Engineer Date 5/26/2006 Owner or 0 eLr;.esignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of
_,___,___,_____,_,_/__,
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period to 7-//-oC
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions o,41-/e1W,,
y Date
~~-~1as~ctor's Signature National Board, State, Province, and Endorsements
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI IWork Order Number 98738842,QWOO Sheet I of 2
- 1. Owner 1
- 2. Plant Unit 3 Duke Power Company Oconee Nuclear Station 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/06
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charjotte, N-C 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class t --
e,'. t-'#.
Main Steam, ASME Class,
?
%'/,
5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Buiit
- Removed, Code or Installed Stamped (Yes I No)
Pivot Pin Grinnell N/A N/A N/A N/A Removed No Pivot Pin Anvil N/A N/A UTC 1085365 N/A Installed No
- 7. Description of Work Replaced worn pivot pin
- 8. Test Conducted H'--
lydrostatic 1] Pneumatic Pressure
-Nominal Operating Pressure
[
Exempt PSI Test Temperature Other Visual
- F
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number I Sheet 98738842-Or 0a, 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 0
0 o
e S
0 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Au horization Number Not Applicable Expiration Date Not Applicable Signed Date Owner or Owner's Designet Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of i/N and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 5-r-1-7.
b to 7-/ V - 6 (-
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Inspect Date 7-1/-,K0 (
Commissions 191KA lox / Ile tv*1 or's Signature NationalBoard(State, Province, and Endorsements
A Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98745256-02 Sheet I of 2
- 1. Owner
- 2. Plant Unit 3
Duke Power Company Oconee Nuclear Station 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/06
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Cburch Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Main Steam, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
New Miller Hydraulic New Miller 18611 N/A N/A N/A Removed No Reservoir Config A Hydraulic Anvil 36312 N/A UTC 1081182 N/A Installed No Reservoir
- 7. Description of Work Replace the existing New Miller cylinder witrh a Anvil Config. A
- 8. Test Conducted LI Hydrostatic D Pneumatic 1:1 Nominal Operating Pressure E]Exempt v7 Other Visual Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI (I)
Work Order Number Sheet 98745256-02 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 0
O Piovot pin was worn oo 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
__Date Owner or Owner's Designee, Tide CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of A.tAr' rvxoLZ.,.AJA and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
.=-,s-a4 to 7-/V-*-4
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Qwner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- '~'
~~tor'si~a r
Commissions National Board, State, Province, and Endorsements Date 7-__
Form NIS-2 Owner's Report for, Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98745256-04 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit 3
Duke Power Company Oconee Nuclear Station 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/06
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Main Steam, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer.
Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
Snubber Grinnell 16345 N/A N/A N/A
- 8. Test Conducted ri Hydrostatic n
Pneumatic E] Nominal Operating Pressure Exempt Other Visual Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report forRepair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98745256-04 I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o A'
0 0
CO 0
0 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Date
'Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of.,.A/e-,e..O,'
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 3 -,-
to 7-/1,1-o6
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Inspector's Signature Date 7-'-1 Commissions 4/*95 -iJ$*-
National Board, State, Province, and Endorsements
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI q
Work Order Number 98745256-05 Sheet I of 2
- 1. Owner
- 2. Plant Unit 3
Duke Power Company Oconee Nuclear Station 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/19/06
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, IZC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Main Steam, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Component Name of Manufacturer Manufacturer Serial Number National Board No.
Other Identification Year Built Corrected,
- Removed, or Installed ASME Code Stamped (Yes I No)
New Miller Hydraulic Reservoir &
Valve New Miller 18874 N/A N/A N/A Removed No Config A Hydraulic Anvil 36325 N/A UTC 1090765 N/A Installed No Reservoir &
Valve
- 7. Description of Work Replace the existing New Miller cylinder witrh a Anvil Config. A
- 8. Test Conducted E] Hydrostatic 1--
Pneumatic L-I Nominal Operating Pressure 11 Exempt Z Other Visual Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code'Section XI I
Work Order Number 98745256-05 I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 0
0 o
0 Q)
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
/*
Date
/9f9O Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of,/e,,-
4'.J.,,
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period J,-/,.
to 7-l/*/.o 6&
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions _____
___.____/___
v -T nspector's Signature National Board, State, Province, and Endorsements Date
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI U
I Work Order Number 98704954 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/13/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date INot Applicable
- 4. Identification of System, ASME Class Unit 3 Reactor Coolant Make-up Pump, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 24inches of ON3HPIPU0005 UNK UNK UNK Treaded Rod UNK Removed EDB# 297412 (8 each)
ON3HPIPU0005 LINK UNK UNK Heavy Hex Nuts UNK Removed EDB# 293556 (8 each)
ON3HPIPU0005 UNK UNK UNK Hard Washers LINK Removed EDB# 233023 Hex Nut ON3HPIPU0005 UNK UNK UNK Hee R
at UNK Installed See Remark #1 ON3HPIPU0005 LINK LINK UNK Washer UNK Installed See Remark #2 LN ntle Threaded Rod ON3HPIPU0005 LINK UNK SeNK reark #3 LINK Installed See Remark #3
- 7. Description of Work
,The 2asket material located in the Unit 3 SSF Reactor Coolant Makeup Pumn Accumulator Flanges will be renlaced.
All other parts involved in work scope will be inspected and replaced as necessary.
- 8. Test Conducted["]
Hydrostatic 0- Pneumatic 0-"
Nominal Operating Pressure E] Exempt Z Other PT/3/0400/008 Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98704954 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 NUT, HEX, HEAVY HEX, 5/8", 11 UNC-2B, Carbon STL. ASME SA194 GR 2H, ANSI B 18.2.2, A (UTC#1088212) (S/C#
293556) (QTY: 8)
O WASHER, HARDENED STEEL, CIRCULAR, 5/8", CARBON STL, ASTM F436 Type 1, ASTM F436 (UTC#1088215)
(S/C#233023) (QTY: 8)
O ROD, THREADED, 5/8", 1 1-UNC-2A, ALLOY STL, ASME SA 193 GR B7, 1007B1AR1COA005,A,AS (UTC#188217)
(S/C#297412) (24 inches) o 0
0 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorizatio Numb r t Applicable Expiration Date Not Applicable Signed O
OTitl Assistant Engineer Date
/( /3'-
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of.Jor-.,'
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period z"-
.-C.
to 7-eoe-
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this, certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- m*
- Commissions I--pector's Signature National Board, State, Province, and Endorsements Date 7-'-.
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98787482 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Stree 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/12/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Low Pressure Injection, ASME Class 2
- 5.
031--7 (a) Applicable Construction Code:
USASJt-13 A9 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section X1 Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification
- Removed, Code or Installed Stamped
_(Yes I No)
I Body to Bonnet bolting to 3LP-11 UNK none none none UNK Corrected NO
- 7. Description of Work Installed new body to bonnet bolting.
- 8. Test Conducted I '-]Hydrostatic
[]Pneumatic E] Nominal Operating Pressure
[-]Exempt
[
Other Vistualleakage Pressure PSI Test Temperature
- F_
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number Sheet 98787482 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Stud material - stock code # 297414, UTC # 1074201, Nut material -stock code # 131716 1, UTC # 1057527.
S 0
o Se 0
0 B
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Sr. Engineer Date 6/12/2006
,er's Desige, Tte CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of W,,-, e*
nz-"
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 7-4-o _
to 7',1'-O 6,.
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions t
iNational Board, State, Province, and Endorsements Date
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI W
o k O d rNIb 44 Sheet I of 2
- 1. Owner
- 12. Plant
ý4/s/.r Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/22/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 2820 1-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Low Pressure Service Water System, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 3LPSW-16 BNL Industries DMV-1040 unk unk unk Corrected NO
- 7. Description of Work Repair seat leak and replaced P/B bolting see OE# 300849 also I
- 8. Test Conducted o
F] Hydrostatic E]Pneumatic k[Nominal Operating Pressure 1-" Exempt I
Pressure PSI Test Temperature Other FN Leak Check OF I
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 1
98697247 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Threaded rod bolting s/c # 297414 7/8 inch 9 UNC-2A ASME SA-193 B-7 UTC# 0001081616 0
o 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorizatign Number Not Applicable Expiration Date Not Applicable Signed/A&"
4K Date 5 Z*-O2 Owner or Owner's Desig'nee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler'and Pressure Vessel Inspectors and the State or Province of
_A and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
&--.0 6 to 7--
6&-d s
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
/...*/J*/*
Commissions It/J*ec-I I
Inspei*o Date
- -/k-Or; r's Signature National Board,/Xate, Province, and Endorsements h
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98585413 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 6/7/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, Nf 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Reactor Building Spray, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) anger 3-54A O-2439B-SR19 DPC none none none 1975 Corrected NO (1)
- 7. Description of Work Installed 1/8 inch siim to reduce gap between hanger and pipe 8& Test OnnrI,uetpe H[
Iydrostatic
[E] Pneumatic
["] Nominal Operating Pressure
[
Exempt El 0 Pressure PSI Test Temperature ther OF
I I
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98585413 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o 1/8 inch shim, ASTM A240 Grade 304, stock code 191130.
0 0
O CO CERIFIAT OFde COMPLIANCE.
Type Code Symbol Stamp Not Applicable Certificate of Authoriz,~ ion Number Not Applicable Expiration Date Not Applicable Signed I 1 '9 1
Senior Engineer Date 6n172006 OZwner or O=n(s PVIignee, Title' 1p CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel
- Inspectors and the State or Province of
"._J,
'A' and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 7--
to 7-<6C-o-
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this,, certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report.. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
0 Commissions,,,'*,//,//<J,
- l T-iý spector's Signature Date 7 -?.-
c, National Board, State, Province, and Endorsements
Form NIS-2 Owner's Report fol Repair/ReplacementActivity As required by the provisions of the ASME Code Section XI I Work Order Number 98773365 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit 3 Duke Power Company Oconee Nuclear Station 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 05/24/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class Main Steam, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 3-OIA-244I-DPC NA NA NA 2006 Installed No H4484 (1) 3-OIA-2441-DPC NA NA NA 2006 Installed No H4485 (1)
- 7. Description of Work In order to eliminate the excessive forces on the 1" diameter piping, two new tie-back supports were added to the l"piping system.
The tie-back supports will transfer the excessive loads to the near-by 12" diameter header pipes, which are capable of taking the loads and the resulting moments.
- 8. Test Conducted H lydrostatic
-- Pneumatic L
Nominal Operating Pressure 0
Exempt
[--
Other Pressure PSI Test Temperature OF
I
° Form NIS-2 Owner's.Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI
- iWork Order Number Sheet I F.27 3 3 (*S 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0
.X 0
o-o
/0323X I*9,3z 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Date
-'1
-Cv O
ivnOer's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comriissir issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Aa);
W-yed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period L/-/
6/
- o to
/,and state that to the best of my knowledge and belief, thne r has performed examihations an aken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this in pection.
Y 2~*4(2(2L4 ZK Commissions 1/69 frfm U Inspector's Signature National Board, State, Province, and Endorsements Date _
._-__/___
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98657237 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672
- 3* -
o,
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class LPI, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 89
- Edition, No Addenda.
(c) Applicable Section Xl Code Case(s)
N-416-I
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes / No)
Piping DPCo None None None 2004 Installed NO
- 7. Description of Work ONOE-18226 removed piping with a hot spot and replaced the piping with new pipe. The piping configuration was the same except the purge port was place on top portion of the pipe.
r8. Test Conducted E-"] Hydrostatic
[-' Pneumatic Nominal Operating Pressure Exempt Pressure PSI Test Temperature I-] Other
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 9A5 Tz3 "7I Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached)
Z 0
0 0
o o
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applic~tble7t--'7E-x. -,.Eration Date Not Applicable Signed Age*, E"s,,-,0r..
Date
__r__"
O~vi-r or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commiss~o isued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period W2 /'/-.
to
/V_____-/__.
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions
/IC-//* 9
/s'
,V"*'-
U Inspector's Signature National Board, State, Province, and Endorsements Date 10Z2_1_/
f--"
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98629418-01 Sheet I of 3
- 1. Owner
- 2. Plant Unit Duke Power Company1 Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/24/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, hLC 28201-1006 Expiration Date
.,-.I-Not Applicable
- 4. Identification of System, ASME Class LPSW, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section Xl Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification
- Removed, Code or Installed Stamped (Yes I No) 31f3LPSW-565 BNL Ind.
UNKNOWN UNK UNK UNK Removed NO 3LPSW-566 BNL Ind.
A95030H UNK UNK 1999 Removed YES 3LPSW-1054 Velan 042041 N/A UTC 1074112 2004 Installed YES 3LPSW-1055 Velan 052003 N/A UTC 1078883 2004 Installed YES 3LPSW-1058 Flowserve AV-912 1264 UTC 1069165 2003 Installed YES 3LPSW-1059 Flowserve AV-915 1265 UTC 1065849 2003 Installed YES 3LPSW-1061 Velan 052002 N/A UTC 1078571 2004 Installed YES 3LPSW-1062 Velan 042012 N/A UTC 1072429 2004 Installed YES
- 7. Description of Work NSM ON-33107 Part BM I modified LPSW piping to disconnect RB Aux Coolers from 3B RBCU LPSW headers and establish supply & return lines to main LPSW headers.
Test Conducted Hydrostatic E--] Pneumatic Nominal Operating Pressure M Exempt
[:] Other Pressure
/290 PSI Test Temperature "2 k,.5" 'F I
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 98629418-01 Sheet 2 of 3
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/24/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NE 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class LPSW, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes / No) 6" Pipe Caps DPCo.
NONE NONE NONE UNK Removed NO
- 1) Piping DPCo.
NONE NONE NONE 2006 Installed NO 3 -2439 H574 4
4
- 4.
4-4 I I I
T
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98629418-01 I Sheet 3 of 3
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 6" - Pipe, Elbows, Flanges, (48) 3/4"nuts, 3/4"threaded Rod, 3/4"washers 0
Q O
0 0
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable--
Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
"/.
t/A Technical Specialist I1 Date
. 0 4/Owner or Mvner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of z,"e,,,,
,zo' and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period 2 o4 to
-'-Z_.-odV
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report.
Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Inspecto Date L
r's Signature Commissions National Board, State, Province, and Endorsements
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section X-I Work Order Number 98748276-01 Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/10/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Char'otte, NTC 28201-1006 Expirtion Date Not Applicable
- 4. Identification of System, ASME Class High Pressure Injection, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section Xl Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No) 3HP-16 Crane Aloyco LUNK N/A N/A 1968 Corrected NO
- 7. Description of Work Bonnet to body studs and nuts were replaced due to slight corrosion.
'wi. 8. Test Conducted 11 Hydrostatic
[-' Pneumatic
[-n Nominal Operating Pressure E-" Exempt Pressure PSI Test Temperature Other Visual OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number Sheet 98748276-01 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o Bonnet/body studs, 3HP-16, UTC # 0001086587, stock code 467112, HT# 8098536 O Bonnet/body nuts, 3HP-16, UTC # 0001079370, stock code 313135, HT # Y67408 0
O
(
0 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed
ý4,a.
v,*,,or,;.(Adc,
,*D--ate 5/10/2006 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Xlae,,
,a&*_.*4, and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
"-__ -__._to
__-/_-_,"o
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing tils certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
______ Commissions nseor's Signature National Board, State, Province, and Endorsements Date Z- " ot-
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI 9
Work Order Number 98787721 Sheet 1 of 2 L
4 i= w 1. Owner Duke Power Company 526 South Church Street Charlotte, NC 28201-1006
- 2. Plant Oconee Nuclear Station 7800 Rochester Hwy Seneca, SC 29672 Unit ONS-3 Date 5/31/2006 4
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class HPI (Charging), ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- 7. Description of Work Removed existing Socket Weld and portions of existing 1.5" Sch 160 pipe adjacent to valve 3HP-248. Replaced with new Pipe stub, 1.5" Sch 160, SA376 TP304, UTC# 1077294 socket welded to the valve and to a 1.5" 6000# Full Socket Welded Coupling, SA186 F304, UTC# 0976235. Coupling welded to remnant of existing pipe.
Test Conducted Hydrostatic
[:] Pneumatic Nominal Operating Pressure n
Exempt r-] Other Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98787721 Sheet 2 of 2 F9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 1.5", Sch 160 Pipe, SA376, TP304, Seamless, UTC No. 1077294 andl.5" #6000 Coupling, SA182, F304, UIC No. 0976235.
0 0
0) 0 o
o CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization N; ber Not Applicable Expiration Date Not Applicable Signed Q
J C
1 Jb.
, Senior Engineer Date 5/31/2006 Owner or Owner's DIesignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Presure Vessel Inspectors and the State or Province of,
and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period Z5"-,-%--o, to
,7.-.--0
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
~~Zdii~~i~+v Commissions
/'A/1 I
'1~D~
"4nsectrF's Signature National Board, State, Province, and Endorsements
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 98771071-36 Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 7/18/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, N?ý 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class High Pressure Injection, ASME Class 1 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Component Name of Manufacturer Manufacturer Serial Number National Board No.
Other Identification Year Built Corrected,
- Removed, or Installed ASME Code Stamped (Yes I No)
Inger 3-51A-
-2478A-H[6384 DPC None None None 1970 Removed NO Hanger 3-51 A-DPC None None None 2006 Installed NO 2478A-H6384 (1)
- 7. Description of Work Hanger was removed to faciliate removal and installation of 3B Letdown Cooler. Hanger was removed and re-installed using new nuts and washers.
- 3. Test Conducted
[] lydrostatic
["- Pneumatic
[-' Nominal Operating Pressure 0
Exempt
['] Other Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98771071-36 Sheet 2 of 2 r".Oemarks (Applicable Manufacturer's Data Reports to be attached) o 3/8 inch x 16tpi galvanized nut were used, ASTM A563 Grade A with coating of ASTM B633 Type I Class FE/ZN, S/C 368739, UTC 1079655 and 3/8 inch harden washers, ASTM F436 type 1 with ASTM A153 Class C coating, SIC 332114, UTC 1079879.
4 0
oD 0
CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the' ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed B.k
ý
ýSenior Engineer Date 7/18/2006 1
Owe.r-y sDsgne il CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the.State or Province of,4/,r-.,
J, and employed by HSB CT of Hartford, Connecticut have Inspected the components described In this Owner's Report during the period 7.U. -04 to 7-zo e
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Ovner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing thiscertificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.
)
Commissions
.dJ/*-V..O/k4,cL
. '.---nspetor's Signature Date 7-"4-"oe National Board, State, Province, and Endorsements I
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI
'I I
Work Order Number 987311100-o Sheet I of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy 4
Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/25/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class LPSW, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
- 1) (2) 3B R3CU Aerofin None None None 1993 Corrected YES Coils# 1, 2, 3, 4
- 7. Description of Work PM on the 3B RBCU Coils (tube cleaning and eddy current testing) required disassembly/reassembly of the cooler channel head. This involved disassembling the Low Pressure Service Water (LPSW) piping from the coils. The 5/8-inch diameter LPSW piping bolting material for the piping-to-coil flanges required replacement due to surface degradation.
- Additionally due to coil tube inlet erosion, protective stiffener sleeves were installed in the tube ends of selected tubes.
- Tubes that show signs of significant degradation in the form of ID corrosion pitting were removed from service by mechanical tube plugging.
- 8. Test Conducted H1 lydrostatic
["] Pneumatic 1:1 Nominal Operating Pressure 1:1 Exempt Pressure PSI Test Temperature Other pressure test OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI Work Order Number 98731110-o6 Sheet 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 Replaced 5/8-inch diameter nuts (SA194 Gr 2H) and studs (SA193 B7 threaded rod) on the 3B RBCU Coil flanges (Stock Code
O - Installed stiffener sleeves (0.500-inch ID x 0.556-inch OD, SA213 type 316L stainless steel) in selected tube ends of 3B coils (approximately 100 sleeves in each of 4 coils). AREVA part number 9009920-002, Stock Code # 593541.
- Installed mechanical tube plugs (52 plugs total for all 4 coils) in degraded tubes. Stock Code #s 476892, 5.91018, 438772.
0 0
0 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed orOw sEngineer Date 5/25/06 O~ er r Ownr's Dsignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
/-.',
to g.- Z"-*e
,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
./***4 j*,,*,*;*
Commissions
______/_
inspa-or s ignare National boaro, State, Provlnce, and Endorsements I Date K___z__
____Ole
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 98731111-O0, Sheet 1 of 2
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy 4 Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/25/200"6
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class LPSW, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
VI()
(2) 3C RBCU Coils# 1, 2, 3, 4 Aerofin None None None 1993 Corrected YES
- 7. Description of Work PM on the 3C RBTCU Coils (tube cleaning and eddy current testing) required disassembly/reassembly of the cooler channel head. This involved disassembling the Low Pressure Service Water (LPSW) piping from the coils. The 5/8-inch diameter LPSW piping bolting material for the piping-to-coil flanges required replacement due to surface degradation.
Additionally due to coil tube inlet erosion, protective stiffener sleeves were installed in the tube ends of selected tubes.
Tubes that show signs of significant degradation in the form of ID corrosion pitting were removed from service by mechanical tube plugging.
- 8. Test Conducted E" Hydrostatic
[] Pneumatic E] Nominal Operating Pressure r1-Exempt Z Other pressure test Pressure PSI Test Temperature OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI W
Work Order Number Sheet K
98731111-0(0 2 of 2
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) 0 Replaced 5/8-inch diameter nuts (SA 194 Gr 2H) and studs (SA 193 B7 threaded rod) on the 3C RBCU Coil flanges (Stock Code
4 0 Installed stiffener sleeves (0.500-inch ID x 0.556-inch OD, SA213 type 316L stainless steel) in selected tube ends of 3C coils (approximately 100 sleeves in each of 4 coils). AREVA part number 9009920-002, Stock Code # 593541.
Installed mechanical tube plugs (100 plugs total for all 4 coils) in degraded tubes. Stock Code #s 476892, 5916'18, 438772.
0 0
0 0
0 0
CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed OX eýW/.,*O7 ME/ z Engineer Date 5/25/06
/Owier or Owner's ltesignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period
___-_C to
__-/______.
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
._______Commissions GA2.3o At'td
[nspcior's Signature National Board, State, Province, and Endorsements Date
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I
Work Order Number 98731109 Sheet I of 3
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/25/06
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class LPSW, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B331.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
RBCU Coil 3A Aerofin None None None 1993 Removed YES RB3CU Coil # I (2) (4) 3A (1C Ci Aerofin 050904 1894 None 2005 Installed YES RB3CU Coil # 2 (2) 3A Aerofin None None None 1993 Corrected YES RBCU Coil # 2 (2) (4) 3A RBUCi 2Aerofin 050903 1 893 None 2005 Installed YES (1) 3A RBCU Coil # 4 Aerofin None None None 1993 Removed YES (2) (4) 3A RBC Coi #
Aerofin 050902 1892 None 2005 Installed YES RBCU Coil # 4 1
11.
- 7. Description of Work PM on the 3A RBCU Coils (tube cleaning and eddy current testing) required disassembly/reassembly of the cooler channel head. This involved disassembling the Low Pressure Service Water (LPSW) piping from the coils. The 5/8-inch dia. LPSW piping bolting material for the piping-to-coil flanges required replacement due to surface degradation.
- Additionally due to coil tube inlet erosion, protective stiffener sleeves were installed in the tube ends of selected tubes.
- Tubes that showed signs of significant degradation in the form of ID corrosion pitting were removed from service by mechanical tube plugging.
In the case of the three of the four 3A coils, the extent of tube degradation was such that the coils were replaced with new spares of identical design.
L 0 rl Hydrostatic 1:1 Pneumatic 1
Nominal Operating Pressure 1n Exempt Pressure PSI Test Temperature Z Other pressure test OF
Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I Work Order Number 987311-0 Sheet 2 of 3 9-"0.
- 1. Owner
- 2. Plant Unit Duke Power Company Oconee Nuclear Station ONS - 3 526 South Church Street 7800 Rochester Hwy Date Charlotte, NC 28201-1006 Seneca, SC 29672 5/25/2006
- 3. Work Performed by Type Code Symbol Stamp Not Applicable Duke Power Company Authorization Number 526 South Church Street Not Applicable Charlotte, NC 28201-1006 Expiration Date Not Applicable
- 4. Identification of System, ASME Class LPSW, ASME Class 2 5.
(a) Applicable Construction Code:
USAS B31.7 19 69
- Edition, No
- Addenda, No Code Case (b) Applicable Edition Section XI Utilized For R/R Activity 19 98
- Edition, 2000 Addenda.
(c) Applicable Section XI Code Case(s)
None
- 6. Identification of Components Name of Name of Manufacturer National Other Year Corrected, ASME Component Manufacturer Serial Number Board No.
Identification Built
- Removed, Code or Installed Stamped (Yes I No)
. 3)(4) 3A RBCU Coi 32 Aerofin None None None 1993 Corrected YES RBCUJ Coil #2 (3) 3A RBC Ci Aerofin 050902 1892 None 2005 Corrected YES RB3CU Coil #44 I_
I-I
I Form NIS-2 Owner's Report for Repair/Replacement Activity As required by the provisions of the ASME Code Section XI I V Vork Or*der Number Sheet 987311109-04 1
3 of 3
- 9. Remarks (Applicable Manufacturer's Data Reports to be attached) o 3A RBCU Coils # 1, 2, & 4 had the tube bundles replaced (due to extensive tube degradation) with new tube bundles from spare coils. The waterboxes to the coils were not replaced, only the tube bundles. The waterboxes from the 3 old cQils were reused.
Note the waterbox is the subcomponent of the coil that has the N-stamp nameplate attached to it.
@ 3A RBCU Coils # 1, 2, & 4 - new tube bundles were installed. The tube bundle is a subcomponent of a RBCU coil. The coils are N-stamped components, Stock Code 377897, UTC #'s 000;090045, 0001083088, & 0001090046. (Form N-I's attached). The waterboxes to the coils were not replaced, only the tube bundles. The waterboxes from the 3 old coils were reused and were bolted up to the new bundles. Note the waterbox is the subcomponent of the coil that has the N-stamp nameplate attached to it.
O Installed stiffener sleeves (0.500-inch ID x 0.556-inch OD, SA213 type 316L stainless steel) in selected tube ends of 3A RBCU Coil # 2 (approximately 100 sleeves). AREVA part number 9009920-002, Stock Code#._, 5.93541.
Installed mechanical tube plugs; Pop-A-Plugs (26 plugs in the old Coil #3, and 2 plugs in the new Coil #4) in degraded tubes.
Stock Code #,s 476892, 591018, 438772.
o Replaced 5/8-ýic-hdiameter nift (SAT194 Gr 2H and studs (SA 193 B7 threaded rod) on the 3A RBCU Coil flanges (Stock Code
- 293"56, UTC # 00010882-I, and Stock Code #t297412,*UTC #'s 0001082122 and 0001088217).
0 0
0 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.
Type Code Symbol Stamp Not Applicable Certificate of Authorization Number Not Applicable Expiration Date Not Applicable Signed Ut jt//
j Engineer Date 5/25/06
\\...
Owner or OFwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of and employed by HSB CT of Hartford, Connecticut have inspected the components described in this Owner's Report during the period I, /_,=.,0 to 1,T"-g.
, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
____*_-,_.0___
,0_
Commissions GA Xo_
A I/t4 lnslctors Signature National Board, State, Province, and Endorsements Date
,Z___-s__.
Date: 07/13/06 Sheet: 1 of 1 TO:
ONS ISIM Plan Manager FROM:
ONS QA Tech. Support PRESERVICE EXAMINATIONS OF CLASS 1 & 2 WELDS RE:
As required by ASME Section XI 1998 Edition with 2000 addenda. Pre-service examinations were performed on ISI Class 1 & 2 welds made during the U3EOC22 outage timeframe. The following is a list of the welds that received pre-service examinations during this outage timeframe.
WORK ORDER WELD NUMBER ISI CLASS INSPECTION TYPE NUMBER MT PT RT UT 3LPS-0736 - 1, 2, 98629418 3, 8, 9, 10 11, 15, &
2 X
X 16 3LPS-0762 - 1,2, 2
X X
3, 4, 5, 6, 7, & 12 3LPS-0765-1, 2, 2
X X
3,7, & 8 98764437 1 -N32389-2-1 1
X X
98784220 1-44773-1-8 1
X X
98764437 3HP-0501 - 28 1
X 3HP-0502 - 30 1
X 98771071 3HP-0503 - 31 1
X 3HP-0504 - 30 1
X Prepared By: at.&
6.0 Pressure Testinq This is a two-part summary showing a compilation of Class 1 and Class 2 pressure tests conducted from refueling outage EOC-21 through refueling outage EOC-22. The first part of this summary, titled "Third Period / Third hIterval Summary," is a completion status for the third period of the third 10-year interval. The second part, titled "First Period / Fourth Interval Summary," is a completion status for the first period of the fourth 10-year interval.
Third Period/ Third Interval Summary Table 6-1 shows the number of Class 1 pressure tests conducted to fulfill the requirements of the third inspection period of the third 10-year interval. There was no through-wall leakage observed during this pressure test.
Table 6-1 Total Examinations Examination Test Requirement Credited Since Refueling Category Outage 21 B-P System Hydrostatic Test (IWB-5222) 11 Table 6-2 shows a completion status of pressure tests conducted during the third period of the third ten-year interval Table 6-2 Total Total
(%)
Examination Test Requirement Examinations Examinations Examinations Category Required For Credited For Complete For This Period This Period This Period B-E System Hydrostatic Test 1
1 100%
(IWB-5222)
B-P System Leakage Test 1
1 100%
(IWB-5221)
B-P System Hydrostatic Test 6
61 100%
(IWB-5222)
C-H System 10 10 100%
Inservice/Functional Test (IWC-5221) 1 Reference Relief Request Serial No. 04-ON-013, revision 1 to perform the 3 rd interval test in the 41h interval.
EOC 22 Refueling Outage Report Oconee Unit 3 Section 6 Page 1 of 6 Revision 0 June 28, 2006
Table 6-2 (Continued)
Total Total
(%)
Examination Test Requirement Examinations Examinations Examinations Category Required For Credited For Complete For This Period This Period This Period C-H System Hydrostatic Test 79 79 100%
(IWC-5222)
The Class 1 (Category B-P) hydrostatic test is required once during each 10-year interval. Table 6-3 shows the completion data of the Class 1 (Category B-P) hydrostatic test conducted during refueling cycle EOC22. This test was for the isolated area between two closed valves and was not part of the Class 1 Leakage Test boundary that is required each refueling outage. Therefore, one test was not conducted to satisfy two different interval requirements.
I First Period / Fourth Interval Summary This summary is a pressure test completion status for the first period of the fourth ten-year interval. Table 6-4 shows the pressure tests completed from refueling outage EOC-21 through refueling outage EOC-22. There was no through-wall leakage observed during these pressure tests.
Table 6-4 Total Examinations Credited Examination Test Requirement For This Outage Category B-P System Leakage Test (IWB-5220) 1 C-H System Leakage Test (IWC-5220) 43 EOC 22 Refueling Outage Report Oconee Unit 3 Section 6 Page 2 of 6 Revision 0 June 28, 2006
Table 6-5 shows a completion status of pressure tests conducted during the first period of the fourth ten-year interval Table 6-5 Total Total
(%)
Examination Test Requirement Examinations Examinations Examinations Category Required For Credited For Complete For This Period This Period This Period B-P System Leakage Test 2
1 50%
(IWB-5220)
C-H System Leakage Test 52 43 82.69%
(IWC-5220)
The Class 1 (Category B-P) leakage test is required each refueling outage. Table 6-6 shows the completion data of the Class 1 (Category B-P) leakage test conducted during refueling cycle EOC22.
Table 6-6 Detailed Class 1 Listing E0C22 Zone Completion E0C22 VT-2 Code Case(s)
Number Boundary Dwg Status Examination Date Used OZ3L-1A O-ISIL4-100A-3.1 Complete 05/30/06 None O-ISIL4-100A-3.2 Complete 05/30/06 None O-ISIL4-100A-3.3 Complete 05/30/06 None O-ISIL4-101A-3.1 Complete 05/30/06 None O-ISIL4-101A-3.4 Complete 05/30/06 None O-ISIL4-102A-3.1 Complete 05/30/06 None O-ISIL4-102A-3.3 Complete 05/30/06 None O-ISIL4-11 OA-3.1 Complete 05/30/06 None O-ISIL4-11OA-3.4 Complete 05/30/06 None The Class 2 (Category C-H) leakage tests are required each period. Table 6-7 shows the completion data of the Class 2 (Category C-H) leakage tests conducted during refueling cycle EOC22.
Table 6-7 Detailed Class 2 Listina E0C22 E0C22 VT-2 Zone Completion Examination Code Case(s)
Number Boundary Dwg Status Date Used 1
IZ3L-10 O-ISIL4-101A-3.3 Complete 04/29/06 None 2
IZ3L-11 O-ISIL4-101A-3.3 Complete 04/29/06 None 3
IZ3L-12 O-ISIL4-101A-3.4 Not Yet Tested N/A N/A O-ISIL4-101A-3.3 Not Yet Tested N/A N/A 4
IZ3L-13 O-ISIL4-101A-3.3 Complete 04/10/06 None 5
IZ3L-14A O-ISIL4-101A-3.3 Complete 05/21/06 None EOC 22 Refueling Outage Report Oconee Unit 3 Section 6 Page 3 of 6 Revision 0 June 28, 2006
Table 6-7 Detailed Class 2 Listing (Continued)
EOC22 EOC22 VT-2 Zone Completion Examination Code Case(s)
Number Boundary Dwg Status Date Used 6
IZ3L-20 O-ISIL4-101A-3.3 Complete 04/19/06 None 7
IZ3L-22 O-ISIL4-102A-3.1 Not Yet Tested N/A N/A O-ISIL4-101 A-3.3 Not Yet Tested N/A N/A O-ISIL4-102A-3.2 Not Yet Tested N/A N/A O-ISIL4-104A-3.1 Not Yet Tested N/A N/A 8
IZ3L-24 O-ISIL4-102A-3.1 Complete 03/29/06 None O-ISIL4-103A-3.1 Complete 03/29/06 None 9
IZ3L-25 O-ISIL4-102A-3.1 Complete 03/31/06 None O-ISIL4-103A-3.1 Complete 03/31/06 None 10 IZ3L-27 O-ISIL4-102A-3.2 Complete 03/27/06 None 11 IZ3L-4 O-ISIL4-101A-3.1 Complete 04/03/06 None 12 IZ3L-40 O-ISIL4-109A-3.1 Complete 10/19/05 None 13 IZ3L-41 O-ISIL4-109A-3.1 Complete 03/08/06 None 14 IZ3L-48 O-ISIL4-122A-3.4 Complete 02/27/06 None O-ISIL4-122A-3.1 Complete 02/27/06 None O-ISIL4-122A-3.2 Complete 02/27/06 None O-ISIL4-122A-3.3 Complete 02/27/06 None O-ISIL4-122B-3.1 Complete 02/27/06 None 15 IZ3L-5 O-ISIL4-101A-3.1 Not Yet Tested N/A N/A O-ISIL4-1 01 A-3.3 Not Yet Tested N/A N/A 16 IZ3L-60 O-ISIL4-124B-3.2 Complete 03/07/06 None O-ISIL4-124B-3.4 Complete 03/07/06 None 17 OZ3L-1 4B O-ISIL4-101A-3.3 Complete 05/21/06 None O-ISIL4-101A-3.4 Complete 05/21/06 None 18 OZ3L-15 O-ISIL4-101A-3.4 Complete 05/30/06 None 19 OZ3L-1 6 O-ISIL4-101A-3.4 Complete 05/29/06 None 20 OZ3L-17 O-ISIL4-101A-3.2 Complete 05/28/06 None 21 OZ3L-17B O-ISIL4-101A-3.2 Complete 05/19/06 None 22 OZ3L-1 8 O-ISIL4-101A-3.2 Complete 05/27/06 None 23 OZ3L-19A O-ISIL4-101A-3.5 Complete 05/21/06 None O-ISIL4-104A-3.1 Complete 05/21/06 None 24 OZ3L-19B O-ISIL4-101A-3.5 Complete 05/21/06 None 25 OZ3L-1A O-ISIL4-101A-3.1 Complete 05/30/06 None O-ISIL4-101A-3.5 Complete 05/30/06 None 26 OZ3L-2 O-ISIL4-101A-3.1 Complete 05/30/06 None O-ISIL4-101A-3.4 Complete 05/30/06 None O-ISIL4-101A-3.5 Complete 05/30/06 None 27 OZ3L-21 O-ISIL4-102A-3.1 Complete 05/27/06 None 28 OZ3L-23 O-ISIL4-101A-3.2 Complete 05/27/06 None O-ISIL4-102A-3.1 Complete 05/27/06 None O-ISIL4-102A-3.2 Complete 05/27/06 None SO-ISIL4-104A-3.2 Complete 05/27/06 None EOC 22 Refueling Outage Report Oconee Unit 3 Section 6 Page 4 of 6 Revision 0 June 28, 2006
Table 6-7 Detailed Class 2 Listing (Continued)
EOC22 EOC22 VT-2 Zone Completion Examination Code Case(s)
Number Boundary Dwg Status Date Used 29 OZ3L-26 O-ISIL4-102A-3.2 Partial 05/27/06 None 30 OZ3L-28 O-ISIL4-102A-3.2 Complete 05/27/06 None 31 OZ3L-29 O-ISIL4-102A-3.2 Complete 05/27/06 None 32 OZ3L-29A O-ISIL4-102A-3.2 Complete 05/27/06 None O-ISIL4-102A-3.3 Complete 05/27/06 None 33 OZ3L-3 O-ISIL4-101A-3.1 Complete 05/30/06 None 34 OZ3L-30 O-ISIL4-102A-3.2 Complete 05/27/06 None 35 OZ3L-30A O-ISIL4-102A-3.2 Complete 05/27/06 None O-ISIL4-102A-3.3 Complete 05/27/06 None 36 OZ3L-31 A O-ISIL4-102A-3.3 Complete 04/29/06 None 37 OZ3L-31B O-ISIL4-102A-3.3 Complete 04/29/06 None 38 OZ3L-31C O-ISIL4-102A-3.3 Complete 04/29/06 None 39 OZ3L-39 0-ISIL4-104A-3.1 Not Yet Tested N/A N/A 40 OZ3L-42A O-ISIL4-1 1 OA-3.1 Complete 05/30/06 None 41 OZ3L-42B O-ISIL4-11OA-3.1 Complete 05/30/06 None 42 OZ3L-44 O-ISIL4-121 B-3.3 Not Yet Tested N/A N/A O-ISIL4-121 B-3.5 Partial 05/27/06 None O-ISIL4-121D-3.1 Partial 05/27/06 None O-ISIL4-121 D-1.2 Not Yet Tested N/A N/A 0-ISIL4-11OA-3.1 Not Yet Tested N/A N/A 0-ISIL4-122A-3.1 Not Yet Tested N/A N/A 43 OZ3L-6 O-ISIL4-101A-3.2 Complete 05/27/06 None 0-ISIL4-101A-3.1 Complete 05/27/06 None O-ISIL4-109A-3.1 Complete 05/27/06 None 44 OZ3L-64 O-ISIL4-124B-3.2 Complete 05/30/06 None 45 OZ3L-65 0-ISIL4-124B-3.4 Not Yet Tested N/A N/A 46 OZ3L-6B 0-ISIL4-101A-3.2 Not Yet Tested N/A N/A 47 OZ3L-7 O-ISIL4-101A-3.2 Complete 05/19/06 None 0-ISIL4-1O1A-3.3 Complete 05/19/06 None 48 OZ3L-7B O-ISIL4-101A-3.3 Complete 05/19/06 None 0-ISIL4-102A-3.2 Complete 05/19/06 None 49 OZ3L-89 O-ISIL4-116C-3.1 Not Yet Tested N/A N/A 0-ISIL4-137B-1.3 Not Yet Tested N/A N/A 50 OZ3L-9 O-ISIL4-101A-3.3 Complete 05/27/06 None O-ISIL4-102A-3.2 Complete 05/27/06 None 51 OZ3L-90 0-ISIL4-116C-3.1 Complete 05/16/06 None 52 OZ3L-91 O-ISIL4-116C-3.1 Complete 05/16/06 None EOC 22 Refueling Outage Report Oconee Unit 3 Section 6 Page 5 of 6 Revision 0 June 28, 2006
Section 6 Prepared By:
Date:
Section 6 Reviewed By:
Date:
EOC 22 Refueling Outage Report Oconee Unit 3 Section 6 Page 6 of 6 Revision 0 June 28, 2006