{{#Wiki_filter:Enclosure (9) CA06012 Atmospheric Dispersion Coefficient (X/Q) Calculation Calvert Cliffs Nuclear Power, Inc. November 3, 2005
E 0 A i EN-1-100 Forms Appendix Revision 3 ESP No.: I ES200100401 Supp No. I 000 Rev. No. 000 Page 1 of 1 FORM 19, CALCULATION COVER SHEET A. INITIATION (Control Doc Type - DCALC) Page 1 of 2m2j , DCALC No.: CA06012 RevisionNo.: 000 Vendor Calculation (Check one): El Yes z No Responsible Group: FOSU Responsible Engineer: Gerard E. Gryczkowski B. CALCULATION ENGINEERING El Civil a Instr &Controls ED Nuc Engrg DscIPLNE: El Electrical a Mechanical El Nuc Fuel Mngmt El Other: a Reliability Engrg
Title:
CONTROL RooM HABrIABILrIY ATMOSPHERIC DISPERSION COEFFICIENT CALCULATIONS Unit Efl 2 COMMON Proprietary or Safeguards Calculation a YES 0 NO Conminents: NA Vendor Calc No.: NA REVISION No.: NA Vendor Name: NA Safety Class (Check one): Z SR El AQ ° NSR There are assumptions that require Verification during walkdown: AIT#: NA This calculation SUPERSEDES: NA C. REVIEW AND APPROVAL: Responsible Engineer: Gerard E. Gryczkowski 2/05/2004 Printed 'ame and Sign t r J Date Independent Reviewer. Kim I. R. Knippel ORLI/l Printed Na ie and Si~Atje Date Approval: Phillip Wengloski / / /, Z / Printed Ifnme an&tignasre Date IF the results or conclusions of this calculation or revision might affect a procedure or the basis of a procedure, a Change Notification Form (Form 14) shall be forwarded to the Procedure Development Unit with a summary of the calculation's purpose and results.
-47 Ci06012 Rev.0 Page 2 of 283
- 2. LIST OF EFFECTIVE PAGES Page Latest Page Latest Page Latest Page Latest Page Latest Rev Rev Rev Rev Rev 001 0 002 0 003 0 004 0 *005 0 006 0 007 0 008 0 009 0 010 0 011 0 012 0 013 0 014 0 015 0 016 0 017 0 018 0 019 0 020 0 021 0 022 0 023 0 024 0 025 0 026 0 027 0 028 0 029 0 030 0 031 0 032 0 033 0 034 0 035 0 036 0 037 0 038 0 039 0 040 0 041 0 042 0 043 0 044 0 045 0 046 0 047 0 048 0 049 0 050 0 051 0 052 0 053 0 054 0 055 0 056 0 057 0 058 0 059 0 060 0 061 0 062 0 063 0 064 0 065 0 066 0 067 0 068 0 069 0 070 0 071 0 072 0 073 0 074 0 075 0 076 0 077 0 078 0 079 0 080 0 081 0 082 0 083 0 084 0 085 0 086 0 087 0 088 0 089 0 090 0 091 0 092 0 093 0 094 0 095 0 096 0 097 0 098 0 099 0 100 0 101 0. 102 0 103 0 104 0 105 0 106 0 107 0 108 0 109 0 110 0 111 0 112 0 113 0 114 0 115 0 116 0 117 0 118 0 119 0 120 0 121 0 122 0 123 0 124 0 125 0 126 0 127 0 128 0 129 0 130 0 131 0 132 0 133 0 134 0 135 0 136 0 137 0 138 0 139 0 140 0 141 0 142 0 143 0 144 0 145 0 146 0 147 0 148 0 149 0 150 0 151 0. 152 0 153 0 154 0 155 0 156 0 157 0 158 0 159 0 160 0 161 0 162 0 163 0 164 0 165 0 166 0 167 0 168 0 169 0 170 0 171 0 172 0 173 0 174 0 175 0 176 0 177 0 178 0 179 0 180 0 181 0 182 0 183 0 184 0 185 0 186 0 187 0 188 0 189 0 190 0 191 0 192 0 193 *0 194 0 195 0 196 0 197 0 198 0 199 0 200 0 201 0 202 0 203 0 204 0 205 0 206 0 207 0 208 0 209 0 210 0 211 0 212 0 213 0 214 0 215 0 216 0 217 0 218 0 219 0 220 0 221 0 222 0 223 0 224 0 225 0 226 0 227 0 228 0 229 0 230 0 231 0 232 0 233 0 234 0 235 0 236 0 237 0 238 0 239 0 240 0 241 0 242 0 243 0 244 0 245 0 246 0 247 0 248 0 249 0 250 0
CA 06012 Rev.0 Page 3 of 283 251 0 252 0 253 0 254 0 255 .0 256 0 257 0 258 0 259 0 260 0 261 0 262 0 263 0 264 0 265 0 266 0 267 0 268 0 269 0 270 0 271 0 272 0 273 0 274 0 275 0 276 0 277 0 278 0 279 0 280 0 281 0 282 0 283 0 4
CA 06012 Rev.0 Page 4 of 283
- 3. REVIEWER COMMENTS
CA06012 Rev.0 Page 5 of 283
- 4. TABLE OF CONTENTS
- 01. COVER SHEET .......................... 1
- 02. LIST OF EFFECTIVE PAGES ........................... 2
- 03. REVIEWER COMMENTS .4
- 04. TABLE OF CONTENTS .5
- 05. INTRODUCTION .6
- 06. INPUT DATA AND METHOD OF ANALYSIS .7
- 07. TECHNICAL ASSUMPTIONS ....................... 16
- 08. REFERENCES .......................... 17
- 09. DOCUMENTATION OF COMPUTER CODES .19
- 10. CALCULATIONS, RESULTS, AND CONCLUSIONS ....................... 20
- 11. AITTACHMENTS .............................. 24 ATTACHMENT A: ELEVATION MAP .24 ATTACHMENT B: AUXILIARY BUILDING ROOF WALKDOWN .26 ATTACHMENT C: SOURCE TO RECEPTOR DISTANCES .30 ATTACHMENT D: JOINT FREQUENCY TABLES .................................... 81 ATTACHMENT E: ARCON96 OUTPUT FILES .129 ATTACHMENT F: ANALYSIS OF JOINT FREQUENCY DATA BY YEAR AND VELOCITY . 281 ATTACHMENT G: ANALYSIS OF JOINT FREQUENCY DATA BY YEAR AND STABILITY CLASS..283 LAST PAGE OF REPORT .283
CA406012 Rev.0 Page 6 of 283
- 5. INTRODUCTION The Atmospheric Dispersion Coefficient (X/Q) denotes the degree of dispersion of activity as it is transported from the point of release to the receptor. It is defined as the ratio of the concentration at the receptor to the activity release rate.
The procedure for calculating X/Q consists of determining the 95th percentile X/Q (defined as the X/Q value exceeded 5% of the time based on site specific meteorological data). This value is used as the X/Q for the first post-accident time interval (0-8 hours). Then the value of X/Q is reduced on the basis of wind speed and wind direction averaging considerations for each subsequent time interval. The CCNPP design basis atmospheric dispersion coefficients are based on the Halitsky methodology, which consists of wind tunnel tests at New York University that modeled the EBRII reactor at the National Reactor Testing Station at Idaho Falls, Idaho (Ref.01). The model consisted of the reactor shell, the stack, and the auxiliary buildings constructed to scale. The reactor shell was modeled as a uniformly distributed source, while the vent stack was modeled as a point source. The measured X/Q results were compiled as a function of wind speed and direction. The results were combined with Calvert Cliffs Nuclear Power Plant (CCNPP) meteorological data also as a function of wind speed and direction to yield the 95th percentile X/Q values. While Regulatory Guide 1.194 (Rif.02) states that "holders of operating licenses may continue to use X/Q values determined with methodologies previously approved by the NRC staff', the required modeling of additional source and receptor points necessitated the calculation of additional atmospheric dispersion coefficients. Since it was not possible to deduce the additional atmospheric dispersion coefficients from the limited data of Ref0l, it was necessary to perform additional wind tunnel tests to determine the required atmospheric dispersion coefficients. CCNPP contracted with Cermak, Petreka, Peterson (CPP) to perform wind tunnel modeling of various source-receptor combinations at CCNPP (Ref.03). The model consisted of the entire site with all buildings constructed to scale. The measured X/Q results for each source-receptor pair were compiled as a function of wind speed and direction. The results were combined with CCNPP meteorological data. Joint Frequency Tables were constructed from hourly on site meteorological data, which tables list the frequency of occurrence of wind by wind speed and direction. From these, the 95th percentile X/Q were determined. The new wind tunnel results agreed well with results of identical source-receptor pairs from Ref.01. While wind tunnel testing per Halitsky (Ref.01) was the design basis methodology of CCNPP's design basis calculations, the NRC would not approve the updated wind tunnel generated atmospheric dispersion coefficient results and instead recommended the use of the conservative computer code ARCON96 (Ref.04) or the very conservative Murphy-Campe methodology of Ref.05 to generate the required atmospheric dispersion coefficient data. Note that while the Halitsky and wind tunnel methodologies produced similar results, the ARCON96 methodology is approximately three times more conservative, and the Murphy-Campe methodology six times more -conservative than CCNPP's design basis methodology (Ref.06). The Murphy-Campe methodology (Refs.2 and 5) for calculating X/Q is based on a number of wind tunnel and field tests of specific building configurations. 95th percentile velocities and horizontal and vertical standard deviations are input intQ the Murphy-Campe algorithms to yield 95th percentile atmospheric dispersion coefficients. The ARCON96 computer code (Ref.4) implements a computational model for calculating atmospheric dispersion coefficients in the vicinity of buildings. The model estimates impacts from ground level, vent, and elevated releases using a single year or multi-years of hourly meteorological data. This model also treats diffusion more realistically under low wind speed conditions than previous NRC-issued models. The ARCON96 methodology is used in this work. ARCON96 is verified and validated per 10 CFR 50 Appendix B. The inputs for these executions are in accordance with NRC guidance as outlined in Regulatory Guide 1.194 (Ref.2). The meteorological data includes eight years (1991-1998) of hourly wind speed, wind direction, and stability class readings from the CCNPP meteorological tower.
CA06012 Rev.0 Page 7 of 283
- 6. INPUT DATA AND METHOD OF ANALYSIS (1) The Auxiliary Building roof above the control room and above A512 was sealed tight via Mod ES 199702144.
(2) The control room regions defined by the control room envelope (CRE) are delineated in ES199901282 (Ref.7). The CRE encloses the following distinct regions:
- 69' CRHVAC Equipment Room (Room 512)
- 55' Shift Supervisors Office (Room 438)
- 55'Tech Support Center (Room 436)
- 55' Tech Support Center Annex (Room 437)
- 55' Central Alarm Station (Room 444)
- 45' Control Room (Room 405)
- 45' Ul DAS Room (Room 431)
- 45' U2 DAS Room (Room 406)
- 45' Control Room Annex and Stairway (Room 432)
- 45' Kitchen & Toilet Area (Rooms 402, 403, & 404)
- 27' Ul Cable Spreading Room (Room 306)
- 27' U2 Cable Spreading Room (Room 302)
- Ul Cable Chase IC
- U2 Cable Chase 2C (3) The volumes associated with the above regions are extracted from Ref.8, except for the 69' CRHVAC Equipment Room (A512) and the Units 1 and 2 Cable Chases (IC and 2C). The area of A512 (1227.4 ft2) was extracted from Ref.9, while the height (91.5'- 1.5' - 69') can be inferred from Ref.10. The volume of A512 is thus 25775.4 ft3 (1227.4
- 21). The area of each cable chase (22'
- 7') was'extracted from Ref.11, while the height (91.5' - 1.5' -
45') can be inferred from Refs.7 and 10. The volume of each cable chase is thus 6990 ft3 (22
- 7
- 45).
The component control room volumes are listed in the following table. The updated post-mod volume, which includes the cable chases and the control room hvac equipment room is 289194 ft3. This exceeds the pre-mod volume of 252195 ft3, as calculated in Ref.10, and the current design basis value of 166351 ft3 , as defined in Refs.12-13. Control Room Volume Calculations: Room Current Updated Updated DBA Pre-Mod Post-Mod Volume Volume Volume Re£12-13 Ref.11 Ref.7-11 ftA3 ftA3 ftA3 27' North CSR 306 47720 47720 27' South CSR 302 47364 47364 45' Shift Office Lower 402 954 45' Shift Office Upper 402 215 45' Kitchen Lower 403 4190 352 45' Kitchen Upper 403 902 80 45' Support Area Lower 404 600 45' Support Area Upper 404 135
CA 06012 Rev.0 Page 8 of 283 45'ControlRoomLower 405+438. 166351 66261 66261 45' Control Room Upper 405+438 46862 46862 45'S. DAS Lower 406 4318 4318 45' S. DAS Upper 406 6237 6237 45'N. DAS Lower 431 4318 4318 45'N. DAS Upper 431 6237 6237 45'TSC Lower 432 3686 3686 45'TSC Upper 432 477 477 55' TSC Lower 436 5082 5082 55' TSC Upper 436 2477 2477 55' CAS Lower 437+444 4356 4356 55' CAS Upper 437+444 1708 1708 69' CRHVAC Equipment Room 512 25775 Unit I Cable Chase IC 6990 Unit 2 Cable Chase 2C 6990 166351 252195 289194 (4) The radiological source points include the Units I and 2 containments, refueling water tanks (RWTs), atmospheric dump valves (ADVs), ventilation stacks (VSs), main steam goosenecks (MSGs), and equipment hatches or containment outage doors (CODs). (5) The site elevation map is documented in Attachment A, based on data extracted from Refs.14:21. (6) The control room inleakage points were deduced from PFT testing carried out by Brookhaven National Laboratory (BNL - Ref26, Attachment B). These included the Auxiliary Building West Road (WR) Inlet, the Turbine Building (TB) Inlet, the Units 1 and 2 Main Steam Isolation Valve Room (MSIV) Inlets, the Access Control 11 (ACI 1) Inlet, the Access Control 13 (AC13) Inlet, and the Units I and 2 Switch Gear Room (SWGR) Inlets. A walk down was performed on 06/03/2003 to determine the relative positions and elevations of the inlets. The results are documented in Attachment B. (7) Source to receptor distance calculations are documented in Attachment C, based on data extracted from Refs. 17-25 and from Attachment B. (8) Meteorology Per Ref.2, the meteorological data utilized for the X/Q calculations included wind speed, wind direction, and a measure of atmospheric stability. These data were obtained from an onsite meteorological measurement program based on the guidance of Safety Guide 23 (Ref.32), that include quality assurance provisions consistent with 'Appendix B to 10 CFR Part 50. The meteorological data set used in these assessments represents hourly averages as defined in Safety Guide 23. The data was representative of the overall site conditions and was free from local effects. To be representative of long-term meteorological trends, eight years of meteorological data (1991-1998) was used in the X/Q assessments. The met data files are designated as CC1991.MET, ..., CC1998.MET. JointFrequencyTables (JFTs) for the 8 years of meteorological data as a function of stability class and instrument height were generated via the JFDMET program and are included in Attachment D. The met data files were transformed into EXCEL files and then sorted by increasing velocity. The 10 m EXECL files are designated as CC1991.XLS, ..., CC1998.XLS. The 60 m EXCEL files are designated as CC1991a.XLS, ..., CC1998a.XLS. The average velocities were generated by summing the valid velocity values and dividing by the number of valid hours. The 95th percentile velocities were generated by multiplying the number of valid hours by 0.95 and using the velocity associated with that hourly
CA06012 Rev.0 Page 9 of 283 number. The following table lists the corresponding 10 m and 60 m average velocities (vave), the 95th percentile velocities (v95), the EXCEL and MET filenames, the data recovery statistics, and the ADV 17.22 m 95th percentile velocities. Safety Guide 23 requires that meteorological instruments should be inspected and serviced at a frequency which will assure at least a 90% data recovery. The overall data recovery exceeds 94% for both the 10 m and 60 m data sets by year, with an overall recovery level exceeding 98%. The maximum 10 m and 60 m vave standard deviations are 2.28 and 1.93, respectively. The maximum 10 m and 60 m v95 standard deviations are 1.51 and 1.50, respectively. Thus the data is well behaved. Average and 95th Percentile Wind Velocity as a Function of Elevation 10M 10m 60m 60m 17.22m lin 60m vave v95 vave v95 m95 v95 excel file excel file 1991 3.00 5.80 4.89 8.60 0.2198 6.54 ccl 991 ccl 991 a 1992 2.98 5.90 4.85 8.60 0.2103 6.61 ccl 992 ccl 992a 1993 3.01 6.20 4.91 9.20 0.2203 6.99 ccl 993 ccl 993a 1994 3.07 5.90 5.06 8.80 0.2231 6.66 ccl 994 ccl 994a 1995 3.02 5.80 4.85 8.50 0.2133 6.51 cc1995 cc1995a 1996 3.02 6.20 4.92 9.10 0.2142 .6.97 ccl 996 ccl 996a 1997 3.00 5.90 4.97 8.90 0.2294 6.68 ccl 997 ccl 997a 1998 2.84 5.70 4.81 8.90 0.2487 6.52 cc1998 cc11998a 2.99 5.92 4.91 8.82 0.2225 6.68 M95=ln(u6Olul 0)An(60/1 0) Ref.28
.v95(17.22m)=v95(1 Om)*(1 7.22/1 0)Am95 Ref.28 Hours 10m 10m 10m -60m 60m 60m MET Per Bad Good Bad Bad Good Bad File Year Hours Hours Percent Hours Hours Percent 1991 8760 53 8707 0.61 280 8480 3.20 ccl 991 1992 8784 55 8729 0.63 59 8725 0.67 ccl 992 1993 8760 88 8672 1.00 90 8670 1.03 ccl 993 1994 8760 210 8550 2.40 154 8606 1.76 ccl 994 1995 8760 97 8663 1.11 77 8683 0.88 ccl 995 1996 - 8784 464 8320 5.28 214 8570 2.44 ccl 996 1997 8760 47 8713 0.54 71 8689 0.81 cc1997 1998 8760 108 8652 1.23 244 8516 2.79 cc1998 70128 1122 69006 1.60 1189 68939 1.70 10m 1.0m 60m 60m 10m *vave 10m v95 60m vave 60m *v95 vave Deviation v95 Deviation vave Deviation v95 Deviation 1991 3.00 -0.12 5.80 0.67 4.89 0.22 8.60 0.90 1992 2.98 0.18 5.90 0.13 4.85 0.73 8.60 0.90 1993 3.01 -0.27 6.20 -1.51 4.91 -0.03 9.20 -1.50 1994 3.07 -1.16 5.90 0.13 5.06 -1.93 8.80 0.10 1995 3.02 -0.41 5.80 0.67 4.85 0.73 8.50 1.30 1996 3.02 -0.41 6.20 -1.51 4.92 -0.16 9.10 -1.10 1997 3.00 -0.12 5.90 0.13 4.97 -0.79 8.90 -0.30 1998 2.84 2.28 5.70 1.22 4.81 1.23 8.90 -0.30 2.99 5.92 4.91 8.82 Std Dev 0.07 0.18 0.08 0.25
CA06012 Rev.0 Page 10 of 283 Attachment F displays the joint frequency data in hours and percent by year and velocity at 1O and 60 m. The average and standard deviation for each velocity interval is also shown. Note that the results are well-be-haved with reasonable standard deviations, except at the low and high velocities where there are relatively few observations. Attachment G displays the joint frequency data in hours and percent by year and stability class. The average and standard deviation for each stability class is also shown. Note that the results are well-be-haved with reasonable standard deviations. The dispersion conditions are dominated by neutral or slightly stable weather (D and E stabilities: 69%) and neutral and stable weather together (D, E, F, and G stabilities) are found in 82% of observations. Note that the joint frequency data (%)by stability class for the years 1991-1998 is very similar to that listed in Ref.28 for the years 1970-1984 for Calvert Cliffs (A=7.4%, B=3.4%, C=4.8%, D=35.4%, E=33.8%, F=9.2%, G=6.0%). (9) The ARCON96 XIQ inputs were derived as follows: (a) Number of meteorological data files: 8 Refs.27,29 (b) Meteorological data file names: CC1991.MET Ref.27 CC1992.MET Ref.27 CC1993.MET Ref.27. CC1994.MET Ref.29 CC1995.MET Ref.29 CC1996.MET Ref.29 CC1997.MET Ref.29 CC1998.MET Ref.29 (c) Height of lower wind instrument (m): 10. Ref28 (d) Height of upper wind instrument (m): 60. Ref28 (e) Wind speed units type (lumls, 2=mph, 3=knots): I Refs.27,29 (f) Release type (1=ground, 2=vent, 3=elevated): I Ref,02 (g) Release height (in): (See Attachment A. All heights are in relation to ground level: 45') (i) Containment: Per Ref.2 Section 3.2.4.5, the release height is set at the center of the vertical plane. (193'5"-91'6")/2+91'6" - 45' = 97.4583' 29.7053 m (ii) RWT: 93.3203' - 45' = 48.3203' = 14.7280 m (iii) Yentilation Stack: 203'5'- 45' = 158.4167'= 48.2854 m (iv) ADV: 101'6" -45' = 56.5'= 17.2212 m (v) Main Steam Gooseneck: 101'3" - 45' = 56.25' = 17.1450 m (vi) Equipment Hatch: 53.3646' - 45' = 8.3646' = 2.5495 m (h) Building area (m2 ): 2000 Ref.02 Note that a sensitivity study was performed on this input parameter. The results are displayed in Results Section and indicate that the X/Q values are insensitive to this parameter. (i) Effluent vertical velocity (mis): 0.00 Ref.02
CA06012 Rev.0 Page 11 of 283 (i) Stack or vent flow (m3/s): 0.00 Ref.02 (k) Stack or vent radius (m): 0.00 Ref.02 (I)Direction to source (deg) and distance from source to receptor (i): (See Attachmnent C) Unit Source Receptor Distance (m) Direction (deg) 1 ADV AClI 50.22 294 2 ADV ACI I 17.99 224 1 ADV AC13 24.09 326 2 ADV AC13 24.09 123 1 ADV SWGRI 19.95 171 2 ADV SWGR1 64.30 145 1 ADV SWGR2 64.30 304 2 ADV SWGR2 19.95 278 1 ADV Turbine Building 37.46 264 2 ADV Turbine Building 37.46 186: 1 ADV West Road 62.94 23 2 ADV West Road 62.94 67 1 COD ACIl 92.58 290 2 COD ACIl 54.05 181 1 COD AC13 62.70 300 2 COD AC13 62.70 150 1 COD SWGR1 39.12 257 2 COD SWGR1 105.51 153 1 COD SWGR2 105.51 297 2 COD SWGR2 39.12 193 1 COD Turbine Building 78.73 275 2 COD Turbine Building 78.73 175 1 COD West Road 71.08 347 2 COD WestRoad 71.08 103 1 Containment AClI 53.17 283 2 Containment ACII 21.47 202 1 Containrnent AC13 21.85 292 2 Containment AC13 21.85 157 1 Containment SWGRI 12.09 225 2 Containment SWGRI 64.90 157 1 Containment SWGR2 64.90 292 2 Containment SWGR2 12.09 225 I Containment Tuibine Building 43.07 263 2 Containment Turbine Building 43.07 187 1 Containment West Road 33.38 358 2 Containment West Road 33.38 92 _ MSG ACI1 51.31 291 2 MSG ACI I 21.13 225 1 MSG AC13 23.50 319 2 MSG AC13 23.50 131 1 MSG SWGR1 22.07 178 2 MSG SWGRI 64.82 148 1 MSG SWGR2 64.82 302 2 MSG SWGR2 22.07 272 1 MSG Turbine Building 39.87 261
CA06012 Rev.0 Page 12 of 283 2 MSG Turbine Building 39.87 189 1 MSG West Road 59.98 22 2 MSG West Road 59.98 68 1 RWT AC11 97.95 270 2 RWT ACI .72.62 207 1 RWT AC13 65.23 270 2 RWT AC13 65.23 180 1 RWT SWGR1 63.12 231 2 RWT SWGR1 106.42 171 1 RWT SWGR2 106.42 279 2 RWT SWGR2 63.12 219 1 RWT West Road 46.92 324 2 RWT West Road 46.92 126 1 RWT Turbine Building 92.45 255 2 RWT Turbine Building 92.45 195 1 Ventilation Stack ACl 1 57.70 299 2 Ventilation Stack AC1l 18.16 195 1 Ventilation Stack AC13 32.93 327 2 Ventilation Stack AC13 32.93 122 1 Ventilation Stack SWGR1 12.27 187 2 Ventilation Stack SWGR1 72.44 142 1 Ventilation Stack SWGR2 72.44 307 2 Ventilation Stack SWGR2 12.27 262 1 Ventilation Stack Turbine Building 41.98 275 2 Ventilation Stack Turbine Building 41.98 175 1 Ventilation Stack West Road' 68.50 17 2 Ventilation Stack West Road 68.50 73 2 SWest Containment Road 36.6 358 2 Containment WVest Road 36.6 92 2 Containment West Road 33.4 358 1 Containment WVest Road 33.4 358 l Containment West Road 33.4 358 (m) Source window (deg): 90 Ref.02 (n) Intake height (m): (See Attachment A. All heights are in relation to ground level: 45') (i) West Road: The Auxiliary Building roof above the control room and above A512 was sealed tight. Most control room inleakage can then be assumed to originate at the Auxiliary Building inlet plenum on the west road side. The inlet plenumn is 54'xlO' with a bottom elevation of 70'. Ground level is at 45'. Thus the intake height is 75'-45'=30'=9.1440 m (ii) Turbine Building: The Turbine Building floor is at 45', while the door into the control room envelope is
-6'. Thus, the turbine building intake height is 48' - 45' = 3' = 0.9144 m.
(iii) ACi 1 86.6667' + 3.8333' - 45'= 45.5'= 13.8684 m (iv) AC13 91.5' + 6.3333' -45' =52.8333' =16.1036m (v) SWGR 69' + 7.0833' - 45' = 31.0833' = 9.4742 m (o) Grade elevation difference (m): 0 Ref.02
CA06012 Rev.0 Page 13 of 283 (P) Primary input, output, and joint frequency tabl file names: Unit Source Receptor Input Files Output File JFT File I ADV ACI I ADVIACII.INP ADVIACI I.OUT ADVIACII.JFD 2 ADV ACI I ADV2ACI L.INP ADV2ACI I.OUT ADV2ACI I.JFD I ADV AC13 ADVIAC13.INP ADVIAC13.OUT ADVIAC13.JFD 2 ADV AC13 ADV2AC13.TNP ADV2AC13.OUT ADV2AC13.JFD I ADV SWGRI ADVISWGI.INP ADVISWGI.OUT ADVISWGI.JFD 2 ADV SWGRI ADV2SWGI.TNP ADV2SWGI.OUT ADV2SWGI.JFD I ADV SWGR2 ADVISWG2.INP ADVISWG2.OUT ADVISWG2.JFD 2 ADV SWGR2 ADV2SWG2.INP ADV2SWG2.OUT ADV2SWG2.JFD I ADV Turbine Building ADVITB.TNP ADVITB.OUT ADVITB.JFD 2 ADV Turbine Building ADV2TB.INP ADV2TB.OUT ADV2TB.JFD I ADV West Road ADVIWR.INP ADVIWR.OUT ADVIWR.JFD 2 ADV West Road ADV2WR.INP ADV2WR.OUT ADV2WR.JFD I COD ACI I CODIACII.NP COD IAC I .OUT COD I AC I I.IFD 2 COD ACI I COD2ACI .INP COD2ACI l.OUT COD2ACI l.JFD I COD AC13 CODIAC13.INP CODIAC13.OUT CODIAC13.JFD 2 COD AC13 COD2AC13.TNP COD2AC13.OUT COD2AC13.JFD I COD SWGRI CODISWGNI.INP CODISWGI.OUT CODISWGI.JFD 2 COD SWGRI COD2SWGI.INP COD2SWGI.OUT COD2SWGl.JFD I COD SWGR2 CODISWG2.INP CODISWG2.OUT CODISWG2.JFD 2 COD SWGR2 COD2SWG2.INP COD2SWG2.OUT COD2SWG2.JFD I COD Turbine Building COD ITB.INP COD ITB.OUT COD 1TB.JFD 2 COD Turbine Building COD2TB.INP COD2TB.OUT COD2TB.JFD I COD West Road CODIWR.INP CODIWR.OUT CODIWRJFD 2 COD West Road COD2WRTNP COD2WR.OUT COD2WR.JFD I Containment ACI I CTMTIACII.INP CTMTIACI .OUT CTMTIACII.JFD 2 Containment ACI I CTMT2ACI l.INP CTMT2ACI I.OUT CTMT2ACI I .JFD I Containment AC13 CTMTIAC13.TNP CTMTIAC13.OUT CTMTIAC13.JFD 2 Containment AC13 CTMT2AC13.1NP CTMT2AC13.OUT CTMT2AC13.JFD 1 Containment SWGRI CTMTISWGl.INP CTMTISWGI.OUT CTMTISWGI.JFD 2 Containment SWGRI CTMT2SWGI.INP CTMT2SWGI.OUT CTMT2SWGI.JFD I Containment SWGR2 CTMTISWG2.INP CTMTISWG2.OUT CTMTISWG2.JFD 2 Containment SWGR2 CTMT2SWG2.INP CTMT2SWG2.OUT CTMT2SWG2.JFD I Containment Turbine Building CTMTITB.INP CTMTITB.OUT CTMTITB.JFD 2 Containment Turbine Building CTMT2TB.INP CTMT2TB.OUT CTMT2TB.JFD I Containment West Road CTMTIWR.INP CTMTIWROUT CTMTIWR.JFD 2 Containment West Road CTMT2WYR.INP CTMT2WR.OUT CTMT2WR.JFD I MSG ACI I MSGIACI I.INP MSGIACI I.OUT MSGIACII.JFD 2 MSG ACII MSG2ACI I.INP MSG2ACI .OUT MSG2ACII.JFD I MSG AC13 MSGIAC13.INP MSGIAC13.OUT MSGIAC13.JFD 2 MSG AC13 MSG2AC13.1NP MSG2AC13.OUT MSG2AC13.JFD I MSG SWGRI MSGISWG1.1NP MSGISWGI.OUT MSGISWGI.JFD 2 MSG SWGRI MSG2SWGI.INP MSG2SWGI.OUT MSG2SWGI.JFD I MSG SWGR2 MS.ISWG2JNP MSGISWG2.OUT MSGISWG2.JFD 2 MSG SWGR2 MSG2SWG2.INP MSG2SWG2.OUT MSG2SWG2.JFD 2 MSG Turbine Building MSGITB.INP MSGITB.OUT MSGITB.JFD 2 MSG Turbine Building MSG2TB.INP MSG2TB.OUT MSG2TB.JFD 2 MSG West Road MSGIWR.INP MSG2WR.OUT MSGIWR.JFD 2 MSG West Road MSG2WR.INP MSG2WR.OUT MSG2WR.JFD I RWT ACII RWTIACII.INP RWTIACII.OUT RWTIACII.JFD
CA406012 Rev.0 Page 14 of 283 2 RWT ACI I RWT2ACII.INP RWT2ACI .OUT RWT2ACI I.JFD 1 RWT AC13 RWTIACI3.INP RWTIAC13.OUT RWTIAC13.JFD 2 RWT AC13 RWT2ACI3.INP RWT2AC13.OUT RWT2AC13.JFD I RWT SWGRI RWTISWGI.INP RWTISWGI.OUT RWTISWGI.JFD 2 RWT SWGRI RWT2SWGI.INP RWT2SWGI.OUT RWT2SWGI.JFD I RWT SWGR2 RWTISWG2.INP .RWT1SWG2.OUT RWTISWG2.JFD 2 RWT SWGR2 RWT2SWG2.1NP RWT2SWG2.0UT RWT2SWG2.JFD 1 RWT Turbine Building RWTITB.INP RWTITB.OUT RWTITB.JFD 2 RWT Turbine Building RWT2TB.INP RWT2TB.OUT RWT2TB.JFD I RWT West Road RWTIiWR.INP RWTIWR.OUT RWTIWR.JFD 2 RWT West Road RWT2WR.INP RWT2WR.OUT RWT2WR.JFD I Ventilation Stack ACI I VSIAC1I.INP VSIACIl.OUT VSIAC1I.JFD 2 Ventilation Stack ACI I VS2ACI l.lNP VS2ACI l.OUT VS2ACI I.JFD 1 Ventilation Stack AC13 VSIAC13.INP VSIAC13.OUT VSIAC13.JFD 2 Ventilation Stack ACI3 VS2AC13.1NP VS2AC13.OUT VS2AC13.JFD I Ventilation Stack SWGRI VSISWGI.INP VSISWGI.OUT VSISWGI.JFD 2 Ventilation Stack SWGRI VS2SWGI.INP VS2SWGI.OUT VS2SWGI.JFD I Ventilation Stack SWGR2 VS I SWG2.1NP VSISWG2.OUT VSISWG2.JFD 2 Ventilation Stack SWGR2 VS2SWG2.INP VS2SWG2.OUT VS2SWG2.JFD I Ventilation Stack Turbine Building VSITB.INP VSITB.OUT VSITB.JFD 2 Ventilation Stack Turbine Building VS2TB.INP VS2TB.OUT VS2TB.JFD I Ventilation Stack West Road VSIWR.INP VSI WR.OUT VSIWR.JFD 2 Ventilation Stack West Road VS2WR.INP VS2WR.OUT VS2WR.JFD 1 Containment West Road CTMTIWRTS.INP CTMTINWRTS.OUT CTMTIWRTSJFD 2 Containment West Road CTMT2WRTS.INP CTMT2WRTS.OUT CTMT2WRTS.JFD I Containment West Road CTMTIWRA.INP CTMTIWRA.OUT CTMTIWRA.JFD. I Containment West Road CTMTIWRB.INP CTMTIWRB.OUT CTMTIWRB.JFD I Containment West Road CTMTIWRC.INP CTMTIWRC.OUT CTMTI WRC.JFD (q) Surface roughness length (m): 0.2 Ref.02 (r) Minimum wind speed (mis): 0.5 Ref.02 (s) Sector averaging constant: 4.30 Ref.02 (t) Hours in average: 1 2 4 8 12 24 96 168 360 720Ref.02 (u) Minimum number of hours: 1 2 4 8 11 22 87 152 324 648Ref.02 (v) Horizontal diffusion coefficient (m): (i) Containment: The horizontal diffusion coefficient is defined as the containment diameter divided by 6 (Ref.02) cy;137.5'/6=22.9l67'6.9850 m (ii) RWT, ADV, VS, MSG, COD ay~O (w) Vertical diffusion coefficient (m): (i) Containment: The vertical diffusion coefficient is defined as 1/6 of the height of the leakage area (Ref.02) c0z=(1 9 3 .4 16 7 ' - 91.5')/6 - 16.9861'=5.1774m (ii) RWT, ADV, VS, MSG, COD
'cz=O
CA06012 Rev.0 Page 15 of 283 (x) Flag for expanded output: n (I 0) Ref.2 allows an applicant to propose adjustments to the release height for plume rise that are due to buoyancy or mechanical'jet on a case-by-case basis. In order to credit these adjustments, the applicant must be able to demonstrate that the assumed buoyancy or vertical velocity of the effluent plumes will be maintained throughout the time intervals that plume rise is credited. In lieu of mechanistically addressing the amount of buoyant plume rise associated with energetic releases from steam relief valves or atmospheric dump valves, the ground level XIQ value calculated with ARCON96 (on the basis of the physical height of the release point) may be reduced by a factor of 5. This reduction may be taken only if (1) the release point is uncapped and vertically oriented and (2) the time-dependent vertical velocity exceeds the 95th percentile wind speed (at the release point height) by a factor of 5. The 95th percentile wind velocity at the ADV release point of 17.22 m is calculated above to be 6.68 m/sec using the 8 years of meteorological data and the height-to-velocity algorithm'of Ref.28 (u/u0 = (h/h,) m where m is determined from the 10 m to 60 m wind speed data). The ADV vertical velocity is calculated in an EXCEL spreadsheet as a function of steam generator temperature and pressure based on the methodology of Refs. 30-31. Since the discharge through the ADV will terminate when shutdown cooling is attained at 300TF (UFSAR 1.2.9.2), the minimum exit velocity from the ADV is 67.5 rn/sec. This is in excess of 10 times the 95th percentile wind speed at the ADV release point. Thus the factor of 5 decrease in the ADV X/Q values is justified for this work. Steam Flow Rate through the ADVs Atmospheric pressure (psia) 14.700 Ref. NEU-94-151 Resistance coefficient (K) 9.820 Ref. NEU-94-151 Maximum DP/PI 0.771 Ref. NEU-94-151 Crane P.A-22 Expansion Factor (Y) 0.704 Ref. NEU-94-151 Crane P.A-22 Limiting Diameterdl(in) 3.760 Ref. NEU-94-151 Exit Diameter de(in) 10.020 Ref. NEU-94-151 S.G S.G. S.G. Exit Exit Limiting Exit Exit Exit Exit Exit Soec Mass Mass Temp Pressure Vol Pressure Spec Vol Flow Flow Vol Flow Velocity Vol Flow Velocity TSG PSG SVSG PEX SVEX MFEX MFEX VFEX VEX VFEX VEX F psia ft3flbm psia fi3/lbm Ibm/sec Ibrr/sec cflsec ftl/sec m3/sec mrsec 300.000 67.000 6.466 15.343 25.742 4.713 4.713 121.320 221.548 3.435 67.528 344.343- 125.000 3.586 28.625 14.360 8.644 8.644 124.132 226.684 3.515 69.093 372.000 177.660 2.563 40.684 10.332 12.190 12.190 125.943 229.992 3.566 70.102 400.000 247.290 1.863 56.629 7.575 16.869 16.869 127.786 233.356 3.618 71.127 500.000 680.610 0.675 155.860 2.906 46.492 46.492 135.098 246.710 3.826 75.197 522.000 826.580 0.549 189.287 2.412 56.793 56.793 .136.974 250.137 3.879 76.242 545.000 1000.000 0.446 229.000 2.007. 69.331 69.331 139.154 254.116 3.940 77.455 PSG= From Steam Tables @TSG SVSG= From Steam Tables @ TSG PEX= (I-DPIPI)-PSG SVEX= From Steam Tables @ PEX MFEX= 0.525*Y*dlA2SQRT((PSG-PEX)/IUSVSG) Ref. Crane P.2-15 VFEX= MFEX*SVEX VEX= VFEX/(3.14159*(de/24)-2) VFEXP= VFEX*60 "Flow of Fluids through Valves, Fittings, and Pipes", Crane Technical Paper No. 410.
"ASME SteamTables Fifth Edition", 1983. "Fluid Velocities through the Main Steam Valve Room Stack and ADVs", NEU-94-151
CA06012 Rev.0 Page 16 of 283
- 7. TECHNICAL ASSUMPTIONS The following technical assumptions were utilized in this work:
(01) AC 1I and AC13 will be isolated on a SIAS signal, which will isolate this leakage path in case of an accident except for the fuel handling accident. The SWGRs are in continual recirculation mode and thus are also isolated from the environment. The MSIV rooms are also isolated from the environment, except for the Main Steam Line Break Accident which occurs in these rooms, due to the thermal buoyancy of the air in these rooms and due to the J-neck exhaust. For conservatism, all of the measured inleakage will be assumed to enter the control room from the most conservative pathway: either the West Road or Turbine Building inlets. (02) This work calculates the atmospheric dispersion coefficients from the source to the receptor assuming no thermal plume or momentum plume rise.
CA06012 Rev.0 Page 17 of 283
- 8. REFERENCES
- 01. J. Halitsky, J. Golden, P. Halpern, P. Wu, "Wind Tunnel Tests of Gas Diffusion from a Leak in the'Shell of a Nuclear Power Reactor and from a Nearby Stack,". Department of Meteorology and Oceanography Geophysical Sciences LaboratoryReport No. 63-2, New York University, 4/1163.
- 02. "Atmospheric Relative Concentrations for Control Room Radiological Habitability Assessments at Nuclear Power Plants", Regulatory Guide 1.194, 6/2003.
- 03. M.A. Ratcliff, B.C. Cochran, "Wind Tunnel Modeling of the Calvert Cliffs Nuclear Power Plant," Cermak Petreka Petersen Project94-1040, 10/94.
- 04. J.V. Ramsdell, C.A. Simonen, "Atmospheric Relative Concentrations in Building Wakes", NUREGICR-6331 Rev.], USNRC, 5/97.
- 05. K.G. Murphy, K.M. Campe, "Nuclear Power Plant Control Room Ventilation System Design for Meeting General Criterion 19," Proceedingsof 13th AEC Air Cleaning Conference, San Francisco, CONF 740807, USAEC, 8/74.
(06) "Dose Impact from Increased Control Room Inleakage at the Calvert Cliffs Nuclear Power Plant", ANS Summer Meeting, April 2002. (07) ES199901282 Supp.0 Rev.0, "Control Room Envelope Determination" (08) CA02725: "Modeling of the Control Room/Cable Spreading Room HVAC System Using GOTHIC Software" (09) M-90-207: "Maximum Flood Height Resulting from a Pipe Break in the Control Room HVAC Equipment Room" (10) BGE Drawing 63690SH0002 Rev/2: "AuxiliaryBuilding Sections and Details at El. 91'6" (11) BGE Drawing 62042SH0001 Rev.15: "Architectural Partial Floor Plan Auxiliary Building Control Room El. 45' 0" (12) Bechtel Calculation M-78-1: "Control Room LOCA Doses" (13) Letter BGE to NRC, Control Room Dose, 3/5/86. (14) BGE Drawing 62006SH0001 Rev.4: "General East and South Elevations" (15) BGE Drawing 12329B-03 Rev.8: "Refueling Water Storage Tank" (16) BGE Drawing 62043SH0003 Rev. 1: "Auxiliary Building Roof Plan" (17) BGE Drawing 62043SH0001 Rev.14: "Auxiliary Building Roof Plan" (18) , BGE Drawing 60330SH004 Rev.15. "Heating and Ventilation System, Auxiliary Building, El. 69'0", Sections and Details" (19) BGE Drawing 61612SH0001 Rev.2: "Turbine Building Cross Sections" (20) CA03750: "ARCON95 X/Q Analysis" (21) BGE Drawing 61740SH0001 Rev.22: "Containment Liner Plan, Elevation & Penetrations"
CA06012 Rev.0 Page 18 of 283 (22) BGE Drawing 62037SH0001 Rev.19: "Auxiliary Building and Containment Structure Floor Plan at El 45'0"" (23) BGE Drawing 60485SH0001 Rev.5: "Refueling Water Storage Tank Piping El 45'0" Unit I" (24) BGE Drawing 60486SH0001 Rev.7: "Refueling Water Storage Tank Piping El 45'0" Unit 2" (25) BGE Drawing 61685SH0001 Rev.29: "Auxiliary Building Unit I Floor Plan at El 69'0"" (26) ETP-01-035R: PFT Testing (27) CCMAIL from Mark Abrams at PLG to G.E.Gryczkowski, 3/5/97. (28) "Wind Flows and Dispersion Conditions at Calvert Cliffs", Maria Gavrilas and Melissa Wieland, BG&E-EPI, 9/85. (29) CCMAIL from Mark Abrarns at PLG to G.E.Gryczkowski, 6/26/02. (30) NEU-94-151: "NS-94-020 Fluid Velocities through the Main Steam Valve Room Stack and ADVs" (31) CRANE Technical Paper No. 410: "Flow of Fluids through Valves, Fittings,-and Pipe" (32) Safety Guide 23: "Onsite Meteorological Programs" (33) CA03940: "ARCON96: Atmospheric Relative Concentrations in Building Wakes" (34) CA04906: "ARCON96 Computer Code Installation Testing on PCB386" (35) NUREG/CR-6331 Rev. 1: "Atmospheric Relative Concentrations in Building Wakes"
CA 06012 Rev.0 Page 19 of 283
- 9. DOCUMENTATION OF COMPUTER CODES ARCON96 implements a computational model for calculating atmospheric dispersion coefficients (X/Q's) in the vicinity of buildings. An atmospheric dispersion coefficient is simply the ratio of the relative concentration at the receptor (gm/rnm 3) to the release rate at the release point (grnmsec). Thus atmospheric dispersion coefficients are in units of sec/rn3 . The model estimates impacts from ground-level, vent, and elevated releases using a single year or multi-years of hourly meteorological data. This model also treats diffusion more realistically under low wind speed conditions than previous NRC-issued models. ARCON96 is a revision of ARCON95. The differences between ARCON96 and ARCON95 are relatively modest. ARCON96 allows users to enter initial diffusion coefficients that may be used to approximate dimensions of diffuse area sources. The method of calculating average relative concentrations for periods longer than two hours was also changed. Centerline concentrations are now used for the first eight hours in each time period, while sector-average concentrations are used for the remaining hours.
The ARCQN96 computer code was documented and described in NUREG/CR-6331 Rev.l (Ref.35). The code was benchmarked and validated in Ref.33. The installation on the safety-related computer PCB386 is documented in Ref.34.
CA06012 Rev.0 Page 20 of 283
- 10. CALCULATIONS, RESULTS, AND CONCLUSIONS The atmospheric dispersion coefficients resulting from the ARCON96 executions are as follows:
Unit I Unit 2 Unit I Unit 2 raw adv to ac1 raw adv to ac13 0-2 hr 2.33E-03 1.84E-02 9.48E-03 8.35E-03 2-8 hr 1.81 E-03 1.57E-02 7.58E-03 4.68E-03 8-24hr 7.52E-04 5.91 E-03 3.05E-03 1.74E-03 1-4 days 4.86E-04 4.92E-03 2.07E-03 1.28E-03 4-30 days 3.92E-04 3.86E-03 1.75E-03 9.10E-04 Unit 1 Unit 2 Unit 1 Unit 2 adjusted adv to ac 1 adjusted adv to ac13 0-2 hr 4.66E-04 3.68E-03 1.90E-03 1.67E-03 2-8 hr 3.62E-04 3.14E-03 1.52E-03 9.36E-04 8-24hr 1.50E-04 1.18E-03 6.1OE-04 3.48E-04 1-4 days 9.72E-05 9.84E-04 4.14E-04 2.56E-04 4-30 days 7.84E-05 7.72E-04 3.50E-04 1.82E-04 Unit I Unit 2 Unit 1 Unit 2 raw adv to swgl raw adv to swg2 0-2 hr 1.26E-02 1.36E-03 1.45E-03 1.24E-02 2-8 hr 1.00E-02 9.15E-04 1.15E-03 9.03E-03 8-24hr- 3.75E-03 2.96E-04 4.73E-04 3.71 E-03 1-4 days 2.66E-03 2.22E-04: 3.04E-04 - 2.49E-03 4-30 days 2.18E-03 1.68E-04 2.46E-04 2.05E-03 Unit 1 Unit 2. Unit 1 Unit 2 adjusted adv to swgl adjusted adv to swg2 0-2 hr 2.52E-03 2.72E-04 2.90E-04 2.48E-03 2-8 hr 2.OOE-03 1.83E-04 2.30E-04 1.81 E-03 8-24hr 7.50E-04 5.92E-05 9.46E-05 7.42E-04 1-4 days 5.32E-04 4.44E-05 6.08E-05 4.98E-04 4-30 days 4.36E-04 3.36E-05 4.92E-05 4.10E-04 Unit I Unit 2 Unit 1 Unit 2 raw adv to west road raw adv to turbine building 0-2 hr 1.40E-03
- 1.35E-03 3.70E-03 3.83E-03 2-8 hr 1.08E-03 9.39E-04 2.78E-03 3.25E-03 8-24hr 4.73E-04 3.78E-04 1.03E-03 1.32E-03 1-4 days 3.48E-04 2.52E-04 8.24E-04 9.92E-04 4-30 days 2.44E-04 1.66E-04 6.31 E-04 7.92E-04 Unit I Unit 2 Unit 1 Unit 2 adjusted adv to west road adjusted adv to turbine building 0-2 hr 2.80E-04 2.70E-04 7.40E-04 7.66E-04 2-8 hr 2.16E-04 1.88E-04 5.56E-04 6.50E-04 8-24hr 9.46E-05 7.56E-05 2.06E-04 2.64E-04 1-4 days 6.96E-05 5.04E-05 1.65E-04 1.98E-04 4-30 days 4.88E-05 3.32E-05 1.26E-04 1.58E-04
CA 06012 Rev.0 Page 21 of 283 Unit I Unit 2 Unit 1 Unit 2 cod to ac1 cod to ac13 0-2 hr 6.88E-04 2.01 E-03 1.41 E-03 1.36E-03 2-8 hr 5.56E-04 1.74E-03 1.1 5E-03 9.74E-04 8-24hr 2.35E-04 7.04E-04 4.81 E-04 3.17E-04 1-4 days 1.50E-04 5.03E-04 3.03E-04 2.28E-04 4-30 days 1.21 E-04 4.03E-04 2.46E-04 1.77E-04 Unit I Unit 2 Unit I Unit 2 cod to swgl cod to swg2 0-2 hr 3.74E-03 5.36E-04 5.51 E-04 3.82E-03 2-8 hr 2.98E-03 3.97E-04 4.48E-04 3.42E-03
- 8-24hr 1.11 E-03 1.30E-04 1.88E-04 1.42E-03 1-4 days 8.88E-04 9.31 E-05 1.19E-04 1.04E-03 4-30 days 6.77E-04 7.38E-05 9.73E-05 8.41 E-04 Unit 1 Unit 2 Unit 1 Unit 2 cod to west road cod to turbine building 0-2 hr 1.16E-03 9.90E-04 9.83E-04 1.02E-03 2-8 hr 9.49E-04 5.51 E-04 7.38E-04 8.48E-04 8-24hr 3.90E-04 2.20E-04 3.04E-04 3.34E-04 1-4 days 2.70E-04 1.53E-04 2.07E-04 2.31 E-04 4-30 days 2.36E-04 1.03E-04 1.67E-04 1.90E-04 Unit 1 Unit 2 Unit 1 Unit 2 containment to ac I containment to acI3 0-2 hr 9.19E-04 1.98E-03 1.93E-03 1.88E-03 2-8 hr 6.19E-04 1.39E-03 1.21 E-03 1.14E-03 8-24hr 2.44E-04 5.71 E-04 4.91 E-04 4.38E-04 1-4 days 1.80E-04 4.90E-04 3.61 E-04 3.22E-04 4-30 days 1.50E-04 4.13E-04 2.98E-04 2.67E-04 Unit 1 Unit 2 Unit 1 Unit 2 containment to swgl *containment to swg2 0-2 hr 2.21 E-03 6.89E-04 7.18E-04 2.21 E-03 2-8 hr 1.47E-03 4.62E-04 4.91 E-04 1.47E-03 8-24hr 5.79E-04 1.68E-04 2.05E-04 5.79E-04 1-4 days 5.23E-04 1.22E-04 1.42E-04 5.23E-04 4-30 days 4.46E-04 1.01 E-04 1.16E-04 4.46E-04 Unit I Unit 2 Unit 1 Unit 2 containment to west road containment to turbine building 0-2 hr 1.20E-03 1.12E-03 1.02E-03 1.02E-03 2-8 hr 7.78E-04 6.37E-04
- 7.1 OE-04 7.98E-04 8-24hr 3.38E-04 2.46E-04 2.57E-04 3.19E-04 1-4 days 2.53E-04 1.77E-04 2.19E-04 2.56E-04 4-30 days 2.11 E-04 1.22E-04 1.77E-04 2.14E-04
CA,06012 Rev.0 Page 22 of 283 Unit 1 Unit 2 containment to west road (taut string) 0-2 hr 1.11 E-03 1.04E-03 2-8 hr 7.29E-04 5.95E-04 8-24hr 3.19E-04 2.29E-04 1-4 days 2.36E-04 1.64E-04 4-30 days 1.98E-04 1.14E-04 Unit I Unit 2 Unit I Unit 2 msg to aclI msg to acl3 0-2 hr 2.25E-03 1.31 E-02 1.OOE-02 8.72E-03 2-8 hr 1.73E-03 1.17E-02 7.99E-03 5.32E-03 8-24hr 7.1 5E-04 44.33E-03 3.23E-03 1.83E-03 1-4 days 4.65E-04 *3.63E-03 2.15E-03 1.37E-03 4-30 days 3.78E-04 ;2.84E-03 1.78E-03 1.01 E-03 Unit I Unit 2 Unit I Unit 2 msg to swg1 msg to swg2 0-2 hr 1.07E-02 1.31 E-03 1.41 E-03 1.04E-02 2-8 hr 9.16E-03 9.52E-04 1.13E-03 7.84E-03 8-24hr 3.54E-03 3.05E-04 4.65E-04 3.1 OE-03 1-4 days 2.56E-03 2.22E-04 2.96E-04 2.20E-03 4-30 days 2.09E-03 1.72E-04 2.43E-04 1.75E-03 Unit 1 Unit 2 Unit 1 Unit 2 msg to west road msg to turbine building 0-2 hr 1.54E-03 1.48E-03 3.38E-03 3.48E-03 2-8 hr 1.19E-03 1.02E-03 2.56E-03 2.97E-03 8-24hr 5.15E-04 4.11E-04 9.45E-04 1.21 E-03 1-4 days 3.81 E-04 2.73E-04 7.73E-04 9.22E-04 4-30 days 2.67E-04 1.81 E-04 5.91 E-04 7.41 E-04 Unit 1 Unit 2 Unit 1 Unit 2 rwt to ac1 rwttoac13 0-2 hr 6.86E-04 1.27E-03 1.48E-03 1.51 E-03
- 2-8 hr 5.12E:04 1.12E-03 1.09E-03 1.28E-03 8-24hr 2.01 E-04 4.51 E-04 4.29E-04 5.17E-04 1-4 days 1.46E-04 3.53E-04 3.11 E-04 3.69E-04 4-30 days 1.17E-04 2.80E-04 2.48E-04 3.OOE-04 Unit 1 Unit 2 Unit I Unit 2 rwt to swg1 rwt to swg2 0-2 hr 1.66E-03 5.88E-04 5.74E-04 1.66E-03 2-8 hr 1.42E-03 4.72E-04 4.25E-04 1.44E-03 8-24hr 5.42E-04 1.79E-04 1.79E-04 5.63E-04 1-4 days 4.44E-04 1.26E-04 1.1 8E-04 4.52E-04 4-30 days 3.47E-04 I1.03E-04 9.78E-05 3.59E-04
CA06012 Rev.O Page 23 of 283 Unit ,1 Unit 2 Unit 1 Unit 2 rwt to west road rwt to turbine building 0-2 hr 2.57E- 03 2.30E-03 7.72E-04 7.90E-04 2-8 hr 2.13E- 03 1.32E-03 6.18E-04 6.92E-04 8-24hr 8.50E- 04 4.87E-04 2.26E-04 2.86E-04 1-4 days 5.71 E-04 3.64E-04 1.87E-04 2.21 E-04 4-30 days 4.85E-I04 2.55E-04 1.45E-04 1.76E-04 Unit 1I Unit 2 Unit 1 Unit 2 vent stack to acl I vent stack to ac 3 0-2 hr 1.42E-03 4.34E-03 2.89E-03 2.62E-03 2-8 hr 1.12E-03 3.51E-03 2.29E-03 1.72E-03 8-24hr 4.38E-04 1.41 E-03 9.15E-04 6.13E-04 1-4 days 3.03E-04 1.10E-03 6.32E-04 4.20E-04 4-30 days 2.45E-04 8.74E-04 5.33E-04 3.16E-04 Unit I Unit 2 Unit 1 Unit 2 vent stack to swg1 vent stack to swg2 0-2 hr 3.94E-03 9.33E-04 9.65E-04 3.82E-03 2-8 hr 3.21 E-03 6.78E-04 7.78E-04 2.72E-03 8-24hr 1.28E-03 2.21 E-04 3.06E-04 1.02E-03 1-4 days 9.74E-04 1.65E-04 2.07E-04 7.61 E-04 4-30 days 7.84E-04 1.25E-04 1.70E-04 5.95E-04 Unit 1 Unit 2 Unit I Unit 2 vent stack to west road vent stack to turbine building 0-2 hr 9.54E-04 8.73E-04 1.63E-03 1.68E-03 2-8 hr 6.86E-04 5.79E-04 1.19E-03 1.34E-03 8-24hr 2.95E-04 2.12E-04 4.61 E-04 5.14E-04 1-4 days 2.13E-04 1.49E-04 3.22E-04 3.84E-04 4-30 days 1.56E-04 1.03E-04 2.61 E-04 3.12E-04 Unit 1 containment to west road File Designation CTMTI WRA CTMT1WRC CTMT1WR CTMTI WRB IBldg Area (m2) ' 1 100 2000 10000 0-2 hr 1.22E-03 I1.20E-03 1.20E-03 1.20E-03 2-8 hr 7.98E-04 7.83E-04 7.78E-04 7.77E-04 8-24hr 3.52E-04 3.40E-04 3.38E-04 3.38E-04 1-4 days 2.61 E-04 2.55E-04 2.53E-04 2.53E-04 4-30 days 2.19E-04 2.13E-04 2.I1 E-04 2.11E-04 Note that atmospheric dispersion results were generated for all possible release and receptor points. This data verifies the importance of isolating ACI 1, AC13, the switchgear rooms, and the MSIV rooms post-accident. Also note that the adjusted ADV X/Q values assume full open ADV releases, which are reduced by a factor of 5 from the raw ADV values to incorporate the effects of thermal and momentum plume rise.
CA 06012 Rev.0 Page 24 of 283
- 11. ATTACHMENTS AITACHMENT A ELEVATION MAP
IeC D.) A~t--- *. (c)6ou5&401 tII. (64A
- 1. Control Room Ale Inlet I
- 2. Control RoomrXr Inlet f2
- 3. Control Room Xre Outlet..
(C) ol) woga.- 6r,
\
(Li/4i/I5#00/ A if. I (a 60t( 6CL /t N. N04'
- 4. Exhoust Vent VJ-54 ~,~ '
- 5. Smoke Removal Fan W-17 rR
- 6. Control Room HYAC Secondat ooeneck AC 112 C035f, ( I-OK If" A(e~'
- 7. Wqulpment Room Supply Fcn WU-28
- Points 13-17 and 20 are located on wells 10 bet - Ail ether points are lcocated on Auxillicy Eidg. roo._
- ~ ~ ~ (4)~ C 4 5B(o6( i~, 44iY; rh-)((7rQfoSHd2I 4g U (>,*
12)
CA06012 Rev.0 Page 26 of 283 ATTACHMENT B AUXILIARY BUILDING ROOF WALKDOWN
ATTACHEMENT A, RECORD OF WALKDOWN ESP No.: ES200100401 Supp. No.: 0 Rev. No. 0 Date: 06/30/2003
SUMMARY
OF WALUKDOWN: A walkdown of the Auxiliary Building Roof was performed by G.E.Gryczkowski and KI.RKnippel to determine the locations of the Control Room Inleakage points. The measured distances are detailed on the following diagram.
JUL 29 '02 03 37PM BNL DRS/ECD 426 P. 1/4 . 64o&1Z'AI/D
, 22c TRACERL iCHIVOOGY CENTERr BROOKHAVEN NATIONAL LABRABTQV... 't .
FACSiML * :..
- -.. . .ATX: XYu y29,20O2 1'A.
A W. .v-. Tnkn -. . Wzm-
.. J-Tr .1. ............ 1.
Aux Systems Engr Unit, Calvert Cliffs Nuclear Power Plant Lusby, MD 20657 FAX NO: (410) 495 -. 4727 MESSAGE: John, I'm on vacation this week but wanted to send you the Einal resu1ts but without my final assessment. Remarkably, total inleakage was 2930 4 185 cfm. Other flows, in cfmn; were: Zone Froinro CR 1nlealAke ., of totil -CR~C i.tkeiige Yo of ol 0 Outside . 275*185 . 9 .. 1866470 ... 64 2 AB 44$6#157. . 366:t248: 13 3 TTB 466*1.2 16 :r599i4i5: 20 4 MStVs 272i.134 .9 .3 44;; 2 5 ACI I 274* 33 9 . L .1-. 6 AC13 387* 38 13 11 .8 0 7 . SWGRs .81g* 114 28 . 2z1V 10 1 More next week. I'll put a copy in the mail also. Total no. of pages including this cover page: 4 From- Russell N. Dietz - Head Telephooe: (631)344-3059 Tracer Technology Center -Fax::(63I) 344.-2887 Atmospheric Sciences Division Catirinfition' (631)344-3275 Brookhaven National Laboratory : -ai:dietz@Vnl~gov Bldg 81SE Secretary: Barbara J. Roland Upton, NY 11973-5000 Secretary's email: rolandsbnl.gov
- Ale, I27 N
I
*C Sol . 00, 15. (t) 1 B -i, / : / 5 Om tOm 20m 30m Orm s5mn ' /i
- 1. Control Room A~r Inlet It (lf.)A'iI 4 4)/'J f 1Y)"L(4 7J
- 2. Control Room Air Inlet #22
- 3. Control Room Air OuUlet *) ",, 2
- 4. Exhaint Vent W-54 *D - J Ff ls,
- 5. Smoke Removal ran VWJ-17
- 6. Control Room HYAC Secondory Gooseneck AC 112
- 7. Equlpment Room Supply Fan VU-21
-Points 13-17 and 20 art located on wvans t below Auxiliory Bldg. roof. - Al ether paints are located on Auxiliary Bldg. roof.
47).54 9"ft I #,()ae~a ls(4
CA06012 Rev.0 Page 30of 283 ATTACHMENT C SOURCE TO RECEPTOR DISTANCES
CAO6O1 2 REV :0 PAE 3/ 0 em O')50/35'e CIoY3ca, avr/K I Om lOin 20m Om 40m 50m (I)S'o" tc35SiDvo/ At/Y .
- 1. Control Room hAr Inlet j11 ( t l. ( i
- 2. Control Room hir Inlet 12 O CJ 7SZ vD/ I 3: Control Room Ahr Outllt
- 6. Control Room WVAC Secondarycooseneck AC t r2
- 7. EquIpment Room Supply Fan _J-2A (t5 C A Yg5,9 4 Il 7v7 cd fS/t'Io/k rf*4)
-Ponts -A 13-17 and 20 are located cn wells 10' b Otlher points are located on Auxiliary Bldg. roo ) b/-IA, 5-(: ,)
6&jf (1 tbc/6rS*zl ov,7 t( / I, L' . vfv- V i/L}v &OS qL (Rs;4' z o# toI 6eJs.D frv)5J Aty tY (S-q) ' C~v) jrKvr o 60Csa)/
/lq- C-;WIWv Al"Y titf (.<4z)
CA060O12.RE V, PAGE 32
- 5, so
- too 150' 4-Om 1dm 20m ' .
46m m I. Control Room Xir Inlet 12 - 5 o 6
- 3. Centrol Roem. Air Outlet
- 4. Ezxhut Vent VU-54
#oao (wirl ts J C5 )
- 5. Smokeh Removal Fan WU-17
- 6. Control Room HVAC Secandoty Coaseneck AC I12
- 7. Equlpment Ream SupplyVfn W-26 'tal-; 1j/I
- Ponts 13-17 end 20 ere lcated on walls 10' below Auiary M5dg.roof. - An ether points ere,located on Auxfliory Pldg. roof.
CA06012 REV 0 PAGE'S
. 60VI TaJ. AC// * ... s //U9/'L 1 N
..4pV I'72 7 4-zV2-f ly-1 #0FCI/,' i9 . .LY. . . V/Z I a.
- CA060 1.2 REV 0 PAGE .3Y 00 a' 50' too, 150( 4 277.. v
'T T OrIV )
Cm m OC 3m 420 40m S5M (.4*( fCk)
- 1. Control Room AXrInet
- 2. Control Room Air InWet 12 t1 Z74
)
- 3. Control Room Xr OuUlet 4 Zhrl
- 4. Exhaoust Vent VJ-54 (j.~lf, oow?
- 5. Smoke Removal Fan W-17 C 64.-le C&41 Oo 6fl
- 6. Centrol Room HWAC Secondary Gooseneck 7.EquIpment Room Supply Fan VU-28 C: 11
)
- Pofnb 13-17 rnd 20 crr located on volbskf' hrowhuslary Bldg. roof. - Al other points ote,locoted on Auxiriory Bldg. roof.
CA060 12 REV 0 PAGE. 60.
- A'V/ .~ 0 505 Imcoe,5;r J -" 7* -A /- -,251,aoSgex-N 4 . os< 7 P, -&V;2Z e 324. 7%h7 a I-.,, is a-i 7 *SA ,y d--ce)/
*I 10 A@- 0 = /Ze 17g °2, o 73 0
CA0GO 1.2 REV 0 PAGE i ..
° 100' ISO',° 6m IOrm 2dm 3m 4Cm SOm C
- 1. Control Room Ar Inlet 1 '
- 2. Control Room Xr Inlet 2
- 3. Control Room Ar OuUzt
- 4. Exhoult Vent W-54
- 5. Smole Removel Fan W-17
- 6. Control Room HVAC Secondary Cooseneck AC '112
- 7. EquIpment Room Supply Fan VJ-2S
-Points 13-17 end 20 are located an wotls 10' below AuxrIiary Bldg. roof. - XI other points ore,locoted on Auxoilcy Eldg. roof.
CA060 12 REV 0 PAGE 37
/X'r..4Oe 40v/. *.1r IL'- 40/,Owrlaw: $41"&/ ~. - ~"ir.C/,z -/7. ~0 cI -Z~-53563-"= // /a Avi v c3 -- te, -L
.. ,.V "Ie
-- S2.L tn4 I 2 Scat . .. J . . . 2fY7 i .
- 262,.3
.'Av In -2 J, oT-- 2/c'1 * /=
6 zzs-~~'Y7/11ZY=lr 631
. .27,.,
CA060o12 REV 0 PAGE 30? a a' 50' too' I(4) SO,34i 150' I 0 2m m 540m n , C5 6 6?; ,= lf7Zg/ i)CW-31.- &WO° 1 Control Room Air Inlet IJ /Zt
- 2. Control Room Air Inlet 2
- 3. Control Room Air OuUe*
rn 1 oG
- 4. Exhaust Vent W-54
- 5. Smoke Removal Fan VU-17
- 6. Control Room HVAC Secondary Cooseneck AC 1I1
- 7. EquIpment Room Supply Fan WJ-28
-Polnts 13-17 and 20 ere located an walls 10' below Auxiliary Bldg. roof. -A other points are located on Auxiliary Bldg. roof.
CA06012 REV a PAGE.3'Mj ALI) v 17a p.. A
/r -o - .Y ...
_ !. XXd9 3/
. .* yf% pS / / ' *'
_ '* '~~~ , g-s*.**
'7 a, 4 ' (2F -o2 C Z, / 33 C t/~tW
('1 bYt
- 1; yt> I lt '2 gY;N~ /T D
CA060 1f2 REV O PAGE IcD
.El 50' tOO- 150' * /.
- I/* .
- 5 .6 131 C" . ;6/§/~v29S 6m 1dm Nbm am 40r *Om C , 9.OfS')
- 1. Control Foom AIr Inlet it
.2. Control Room Ar Inlet J. Control Room Air MuMeI t2 (~ 3o c.
- 4. Exhaust Vent WV-54
- 5. Smoke Removal Fan W-17 S. Control Room HVAC Secondory Coosemeck AC 112
- 7. EquIpment Room Suppl Fon WA-28
- PoInts 13-17 and 20 ere located on wogs 10' below Audliory Bldg. rool. - Xi other pornts ore locoled on Auxiiarfy Bldg. roof.
CAOBO 12 REV a PAGE -'/ dciev7bs
- ,rde/>-C.
C
-5o3.477 ~- 92 e -
5S3 e ,z r -5' ay,,vf7Y,5,, = zt-7. !~7yc1 Cc',p - -1 .. ')S P--- SC/I J- /77,23(A/ OR. % I A. 2Z*-a . S*zf - artYz7 C'OOL A{.._
CA06012.. REV 0 PAGE 9'1 0 J. -/ /, 0,, O 50' /J- li (OivcS m Idm Zbm 36m 40rn 50m 01a'scu fW#U6DvO
- 1. Control Room Air Inlet i1
- 2. Control Room Air Inlet 12
- 3. Central Room ^;r Outlet
- 4. Exhoust Vent W-54
- a. Smolke Remowol W-17 mon
- 8. Contiol Room HYAC Secondory Gociefmec AC 112
- 7. EquIpment Room Supply Fan WU-28
- Points 13-17 end 20 re [cmated on walts 10' below Auxtriary Bldg. roof.
- 1 other points are located on Auxlriary Eldg. roo(.
CA06012 REV 0 PAGE V-3
,-JD 4-CA OIk 7 Izk. £ CkJ1 -J J~ 3~. rank9 A9c1 A- 22f-75go237'~ -' /f 7 1
1. J I I
CA0 602 REV 0. PAGE 4y
- 0. 5O ,100 . ,So
(:iD i 5) L iF6omnm 30mm 4 6-S (41SavlfCKs) (cr71r O -
- 1. Control Room Air htet
- 2. Control Room Ar Wet 1Z
- 3. Control Room Ar OuMlet
- 4. Exhoust Vent W-54
- 5. Smoke Removal Fon W-17 S. Control Room HVAC Secondary Gooseneck AC 112
- 7. EquIpment Room Supply Fan W-28
-Points 13-17 and 20 are located on walgs 10' betow Ausxloty Bldg. roof. - Alother po3nts are located on Auxroary Bldg. roof.
CA060 12 REV 0 PAGE ff to. COO/ 1i20 Vwg-/ &rz, "-'Ie -6/zc 5
.I. , f,12 - g$Ce-4,I c-- 12X3773 '-3 /&4a-j z*fr-S.$57 77 = S7, 375 7 C7-C Omt / .-JD owr-L . 1 ci i3 A /
sZ l*gosh, VIj47 f ,A- 2&5`4 71/7L=2Y,'7-z 0SSR
- 'CDv/
3J;2c7 cODI**
.1 2) 5 ' / '54' cL- , AX -7 C/ ,$pfl)(07 I, .- Z,5 - /, IYOP--1 ,2,5"i cIAvt .a_ LIDz swo-G cl-./p 3773~ /l V0/- , a- 7,5- us -;w7 <':-~~,C 7z;0/ a 2v.
CA060 12 REV 0 PAGE ff
- o. 50 t0 0 917 bm n-rn 2dm )4dr 5d6m ,76'I*%-IvY
- 1. Control Room A Wel7et I I
- 2. Control Room Xr Inlet f2 3.
4. Control Room Air OuUet Exhoust Vent WU-5 V0 J{4 6
- 5. Smoke Removnol Fn W-17
- 6. Control Room VAC Secondary Cooseneck AC 112
- 7. Equlpment Room Supply Fan W-28
-Points 13-17 and 20 are located on walls 10 below Auxiliary Bldg. roof. -All other pints are located on Auxiliary Bldg. roof.
CAo60 12 REY 0 PAGE f7 (4141.J Ca .TO WW4/9010p9 ltif 2,tw- %e~> yw/f7
, ( AJ .. ' 19rt< 7S r.
I Jp~-, Isr 7/,
'u.
Adzw- YC} 2.335 2,c7 ^ /sw ins
..0 f ol :50 tfSljI aoo .Caer 6*o J -^s -:f /7? 7-4yy7'--
O 2 V114 2- AnO "l 1-00vZ da4-
--79 Ud Jms5 = 2{ gJy 1q, s 2?- -F0 .3"7 -r /, /, 4; 7 +ffi tfefi I0r 1i4fa 75-
CAo60.i 2 REV O PAGE. W 0
. 52' 100' ISO' (4) / 6ci, Om IOrm 20m S#m 40r dm .r J /!
O 7 Clszcs) K4S-2 Control Room Ar Intel 11 I of Control Room Oulletd or I 4, Exhaust Vent W-54 06 t m *4 / S Smc Removal Fan W-17 lW&( t 0A1,V) S. Control Room hVAC Secondary Gooseneck AC 12 t? /
- 7. Equlpment Room Supply Fen V-o28 (/ I 5O Z-. 3f: _ -SJoI
-PcFnbs 13-17 and 20 ore located on wvoll 10' below Auxliry Bldg. roof. / f 4- " 6 - All other points ore located on Auxiflary Bldg. roof.v-
CAOGO I 2 REY a PAGE f CA//fr 5 Cerr T2 -AC! 'V Yl cl- f3, 575 77<<ir.,w7 8,/7 Cm D4cl 0241 ._ 2J 3,1-6rce3 7 3 f2'.5- :2 ev?? AL- 22Z5 s-2,a S,- Y "'=2o,
/1 A~i~av "- ffI '
z
PAO. 12 RE.Y 0 PA6E-55a o __m (A) erf (k'4tvowN,) 6m mI 26m 3~m 40ni 50m g)227 'C Cs) " (lXcs
- 1. Control Room Air Inlet I CG /Sol w5> c s )
- 2. Control Room Xr Inlet $2
- 3. Control Room Air Outet
- 4. Exhaust Vent VU-54 *R J o
' 6 / J.5/ o
- 5. Smoke Removal Fon W-17
- 6. Control Room HVAC Secondary Gooseneck AC 112
- 7. Equlpment Room Supply Fan WU-2S
- Ponts 13-17 and 20 ore located on wells 10 below Aux~liory Bldg. roof. - A1 other points ore located on Auxiliory Eldg. roof.
CAO6012 REV 0 PAGE 57 talIWt t
- co 4Y
.. et ' /W z 7eX C.,H1. 5fa .JD#oq-11 C877"'- X,0i . aS 7, -7 7 - 272902?5 *xv .2<>cvr S341.9 :
D = /Ya,/7-ads7 ( - a/IX, 7.6 I?' 5-3t. ,/ - 2/. de95Y6 A".
,9 zZ-67,7st7 =/s22 0 , /sX~v7,X/- . TD IV A co / /= /I1-e I/ - /4i/1e3LO
CA060 12 REV 0 PAGE 5.Z
# A /O*fiWv) cm torn
- 1. Ccnlr 26m Room 36m .0 5CM 1I'm 1.e ID fo > g / I 4T - . Jf
- 1. control Room A~r.lnlde, I1..2C
- 2. Control Room Xk Ilet 2 / a
- 3. Control Room Air Outlat
- 4. Exhaust Vent W-S4
- 5. Smoke Removal Fon W-17
- 6. Control Room hVAC Secondary Gooseneck AC 112
- 7. Equtpment Room Supply Fan VU-25
-Points 13-17 and 20 ore located an vicls 10' below Auxiliory Bldg. roof. -All other points cre located on Auxilory Bldg. rooa.
CA060 i 2 REV 0 PAGE 53
'/ofir cui % eAf12 f/ 64 S_ A, it n aad P.. .
40j&.r , }X/ B ss,
- -Z 225 014/Ir J4 air Ad Avekr Z Ad" I I i - 2,, S5fc-7?/ ,-- If'-2-1Z ,S9$/
a- = $5 -ZZ,G33 292,34 Z
- 1 65e7 -To - 0#/O70 .2 wt-cl. -" /Z W/-
V
.1.Z22lc1~.
.UNT{} 2- ID ,>, W12> d; Sot L (2- c, OF7 {- Ce. 2/2,9/a7 / goa/0
- J 0 ,5-Wit tb o 'I'-I3 761i/.'ft If/ =
CA06012 REV 0 PAGE 5Y
. -d .o 5. -. . Y 03. -- - 35' . . q,9 0, Om Orn 2Ojn 36m 40m 50m 7, - vZ, YM,4, - -C
- 1. Control Room Mr InlTf
- 2. Control Room Air Inlet 12 3: Control Room Xr OuUet Ip 180(,
- 4. Exhoust Vent WT-54
- 5. Smoke Removal Fon VU-17
- c. Contrcl Room hVAC Secondary Cooseneckc AC 112.
- 7. Equipment Room Supply Fan W-28
- Points 13-17 end 20 are located an walls 10' below Auxary Bldg. roof. -Al ether paints are located on Auxioriy Bldg. roof.
UdSf j-al-r 110f3h .L 5v3-a 1110a <<v n azeI cJ -z),Zr - DJz{-If5 g / o<S h- r33 If I '4000,,4 Feg % 30la_ 40R~ A4 (mr2- ci4 wL~) f &OM
/ JI / /SjXcz 4 1Ct I
I ' f j ,1--f) "-I 2db7/47 cog t<46P, 2r/,g 21", i* T2 1'~y
/ cwct 7 -! /aU*K~(2<fA upsr~ 2 charN *0 J,4
- CA oCC 12. REV 0 PAGE 5%
0 S t00 150, W Cm 1Cm 2m 36m 40m 50m fl) 'JL7; 1 ) .
- 1. Control Room Air Inlet 1r
- 2. Control Room kr Inlet fi
- 3. Control Room Xkr Outlet ( p v (Jc,+a Rw .s)
- 4. Exhaust Vent W-S4
- 5. Smoke Removal Fan VU-17
- 6. Control Room tNAC Secondory Gooseneck AC 112 rIr1bJY Js L
L g ; o7 .
- 7. Equlpment Room Supply Fan WJ-28 7 1Lria L
-Points 13-17 and 20 cr located on woas 10 below Auxfllry Bldg. roof. - Al other pdints ore,locoted on Amillory Bldg. roof.
CA0601 2 REV o PAGE 57
- 1. Control Room PJr Inlet f1
- 2. Contral Roam Ajr Inlet Z
- 3. Control Room Mr Oultl
- 4. Exhaut Vent W-54
- 5. Smoke Removal Fon W-17
- 6. Control Room IWAC Secondary Cooseneck AC
- 7. Equlpment Room Supply Fan tJ-28
-Points 13-17 end 20 ern located an wells 10' below Auxiliary Bldg. roof. - All other poInts are located an Auxtlriry Eldg. root.
CA06012. REV 0 PAGE 5?
,; 1.yAle -
- 14. I
.I . ,tt . /vesIse ,/-l&.3Y7 s-< F/3/. fe Ftese G )I Its/ /'Ss .~ * -6 2G - 250,G~?
c - G7,3 V4 /Z/. /sf . '$F3a ea::, z 7's- Oj3 z~ g 2z Y, (.71 I
I CA06D12 6 REV1O
*. PAGE 5-- .5 I
ow~50 so 1R io . -7 1;7c 76; m lidmn 2m Jm 4m 5m It Z7 4rt (4/KC I. Control Room AJr Inlet jI (('44t4oue°oS )
- 2. Control Room Air Inlet 12 2,5 - 1
- 3. Contral Room Air Mv~et - r -! ~ 4r "6
- 4. CxhnotuVent W -54 .t. % O L)ISJ'T 51 5 Smone Remail ran W-17
=. Room WVAC Conlicl Secondary Coostnecie AC 112
- 7. EquIpment Room Supply Fen VU-28 c-f )772
- Pnts 13-17 and 20 are located on wols 10' below Auxtriary Bldg. roof. -/ elther paints are located on Auxsicry EMdg. roof.
*CA0601 REV 0 PAGE co 19*6/ . ' t6ca ,, ' 1 . / Zt iv -..ah-4 -fi 1 --vzo7 t 5@<,fI~v=/ #A5It
- . 5 i/ ,vf9 - /340,:SJc
- CA06012 REEV
*. ?AGE /. .5 I.
I. .1 . 1°;t,' ioo. . AC:H e/ 'p Om . 1dm 50' 2bm t0 3Cm 4Cmn I50t SO 'm (,566 -j- We) 5,1si *135)
- 1. Control Soom Ur Wet I1 ~ i, /? '
Ca) SCi
- 2. Control Room Ur Inlet 2
- 3. ConMMo Room Air Cutlet
- 4. Exhoast Vent W-54
- 5. Smoke Remaofl Fon W-17
- 6. Conticl Room HYAC Steondoar Gcoseneck AC f12
- 7. Equlpment Room Supply Fan NJ-28
-Polnts 13-17 and 20 onr located en wags 10' below Auxiliory BIdg. root. - A other points ore located on Auxiliary Bldg. roof.
4A066 A v REV 0 PAGE *C2t Aw -vz.swearc/
$S9^ (
4De6ivbr, 1JfxAe J V Z-Y~z-z s 22,a.07,47-p1. @ Ef~ & ,=Z'!-~~22.-
/77, cR .. 5zoF/ h~l b 5;L - s tJ2 / -^ Z ,Y so*'- 7 /leZZ o74 70o2,/ 0 Y?, es-7/1, . Ac_ 2z+Yf32,2,zw/yo b %.4iz .
ctI*-ZllzecL +agg f IV I ;ioZ. .0keS= -o/, o -%C
.I.._, -S y Y .t.go Ffts57/
I-,~e A J- 7 X,r 4>vrr-xlwj D
~gL-, 0.--E% S - I 1 A
I..
~A44I81" REV O PAGE '03 Cm lCr 2brn 3m 4C6m Sr (b ,L 1-,NfO 45. ' rC 3F7o77"- 2.9/b
- 1. Ccnlrot Room Ar InRl W1J t
- 2. Control Room Xr Inlet t2
- 3. Control Room Xr Outlet
- 4. Exhoust Vent W-54 I .i e-° 1
.5. 5moke Rennoyat Fan WU-17 l I
- 6. Control Room HWAC Secondary Gooseneck AC 112
- 7. EquIpment Room Supply Fan 'Al-28
-PoInts 13-17 and 20 are located an vols 10' below Auxlcry Bldg. roof. - other pdlnts ere located on Auxiliary Etdg. roof. ett
- I CA0601 - REV 0 PAGE CY
- I4 .
.0 AA \* .Q/ge .1 M \lo *. / (&a/3 rz 0 )yc . + ' *
- Y9-
>9 /ND75i f2
'- t 8o~472?M~ yLo2 _ tYL Tz,\&, I .~? /- Ap2 C.L Y-2Fo 1 -.
~/ ( yt2z
- M M, ~0sPQU-to gof,8'S
CAD60A 1 REV 0. PAGE 6S-I at oo* to too sco (4B) .1 o'.,o
,o (cb~1, Om 1d m 0m n rn- 40r 5 adm * */
- 1. control Room Alf Inle 1 10
- 2. Conlrel Room air IneW 12 t (D
t
- 3. Contra, zRoom ai ouutl r 11 a I9' 4.- Exhea Ven W- *
- 5. 5mkeh Removeal fein WU-17 S. Control Room hVAC Secondery GCosen ec 7._Eesulpmcnlt-ooam upply-FonnW-2S-v S 40t I
-X-; /
(II
-(/ - Poln.s 13-17 and 20 are located an wvis 10 below Auxtriry Bldg. roof. -All other points ore located on Auxinlary Bldg. roto.
- - CAD6v REV 0 PAGE 6C 4c./.
- 3 zs)7 7 - 72.s 2R--
,5-d(Z
- CA0601 v. REV 0 PAGE G7 I
mf so, too, 50h' 6m I dn 26m Z3~rn4M 36M
- 1. Control Room Air Inlet I1
- 2. Control Roorn Air IWlet 12
- 3. Control Ronm Air OuMth
- 4. Exhmust Vent W-54
- 5. Smoke Femoval Fon W-1 S. Control Room HWAC Secont
- -7.-Equtpmenl-Room-Suppiy-Fc
-PoInts 13-17 end 20 ore located on wollsI)0belD - Xi other points ereloctled on Auxiovry Wtdg.roof.
CA0.60.1 7 REV 0 PACE 6V'-: I I PAG
. .. .. I
- 6TJ -7 Act3 d,-
t/f + 7,'+2p= yt laD, 6zy
.(1otz,.</Apo I
J5-oR l -o,32 EJs rt A17
,6At14 sD,; /'w'~72 I 'j Zl 3,Z"=
art
,2zz-- /27f, 7 I
CAbI-7 0 REV 0 PAGE 679
- I II I AV Om 1Cm 20m 36m 40m Som 5J c i*
1.Control Room Air InWel I'D)
- 2. Control Room AXrInlet 2
/2J° (7
- 3. Control Room ir Outlel 4.. Exxhust Vent W-54
- A/i
/
6 I6 it
- 8. Control Room HYAC Secondary Goo0en f l2
- 7. Equlpment Room Supply Fan W-28 27 C ,hc
-Points 13-17 and 20 ore located an wolls 1o' blow AuxlOary Bldg. roof. - AJI other points crs,located on Aviliary Eldg. roof.
- M00:1 v REV 0 Lt . _
PAGE 70
- - - - I.
i: Sj /o/,-Y (n +cNK7*7'-S Vc47 - fX; .. .. 2........... 2s~v7,,, 'e43,/- v- 7a
,~k'r 72', SWCz.-
A5 AZ . It4 - &a7. -;2D0)la (
- I di 2zr-4 -=21f,Y90/2
.5 II
- d 47 1 * - I.
.4 7 S,5 - I.
crr53M, 178,P/ '-10, 4S Ae -, 5 3,, W 'o
,P. -:2 ?rj^4 lz ZvSe, 8,3c
- kiv.J,,L I-Ij -
jA- -:Sqj, A-dz, "=lowl, CEME P,A, =z z-,1- 4,y376o 1 . _ . .
DAD0812 REV 0 PAGE 71 I 0' 50 .100' I50' . (A) y.7,3/ . 3Z2 CIm Orn 201n jomn 4rn Sdm f7,3//(4wi / 4Y, .
- 2. Control Room Ar Inlet 12 (C) 7/,3S7 7,A* 2-f7 6
- 2. Control Aoom M~rInlet 72 3; Control Room Ar Outlet 4,
5. Exhaust Vent WV-54 Smoke Removal Fan W-17 2f 02. -~ l7 Y.a
- 6. Control Room IWAC Secondary cooseneck AC 112
- 7. EquIpment Room Supply Fon VU-28 NOTF
- PoInts 13-17 ond 20 ore located on walls 10' below Auxiliary Bldg. roof. - AR ether points ore located on Auxilicry Eldg. roof.
cAo.o /'6yt Ao
'7s a 14111r 11 A-IT Tra ux-sr @
lAe l(v 17-1,
- Nr 2,/ AL- p -{ AMP141 /,J
,,,- M."Ss ,6/z/-
2 4 /~3,%4%'~' 9c~97.-~- nobWT1 2 r 6t/'t's' 22-5 7: 2Y~2Z infi6 '^B&/7 2,Yn MaNr 2- fD s64/4/M/MSlw
. .7 ,- ,33~/X :
Dz6~2 t D~s STr
CA060.1 2 REV 0 PAGE 7.* a'N( S 12'4'IZ) 6m Idn 20m 3m 40m 50m * ) 1.Conlrol Room hr Inlel
- 2. Con" Room hr Inlet2 I
- 4. Exhaust Vent W-54 {O z (152AsV f)
- 5. Smoke Removal Fan W-17
- 6. Control Room HWAC Secondary Cooseneck AC fl2 IrI
- 7. Equlpment Room Supply Fan WU-25 f i,
W C COs1 htX s) -PoInts 13-17 and 20 ore located on wals 10' below Auxliory Bldg. roof. - MI other points are,located on Auxilory Bldg. roof.
CA060 12. REV 0 PAGE 7Y VS.4 if /1 L 7ZA -XL7 c/5 25 7 Vs5L 7 AC/I 2SX?9/f /;t Iq *1 J' zsi-o,? , /:6e -- /C,",e
.52.> . . . \5-rOx 'kli5 .~4oqsd 5t$7 *...2,0ZI"'
qf/._ vr,- - /g2b.0 6(1a/ .. 5r1W
..... /('1- .a.6. rl A
-CA060 1O REV 0 . .I .
PAGE 7* I O. tSG I (A"1rI 56.lea, MI 40 1 Om lOm 20m 3O6n 40m A rdm 5i cc88,Y (Vs 'O :,)
- 1. Control Room Air Ine 1W-2
- 2.Contro Room Xr Inlet' t2c
- t. Control Room hr outrlet
> (vs
- 5. Smoke Removol Fa5W-17 *oD ,Sg2/s (O qo v z
- 6. Control Room HVAC Secondary Gooseneck AC 112
- 7. Equlpment Room Supply ran W-28 liX
-Points 13-17 and 20 art loccted entwails 10 below Auxlary Bldg. root. -AnI othu polnts cre located an Ausflory Eldg. root.
CAO6012 REV 0 PAOE 76 Vs/1 46 L3 v/SI1 /O szls' I./ j cace6/ /2 - 92"S370.4-4 -, ~eoS -7 77,f35 3z97, s4 4c13 V5L clr354- 5S /Z2,- 0 .. ,44aNrl vlSKottlw *Asi 5W7-4
- g
CA060 1 .X REV 0 PAGE 77. a J&55ZI
. 50, 100- W4 i50 >
6-M a3zol<%* 54C bm I 'r 2dm ZOm -4m 506 * £ ) I.Cntrol Room Xe Inlet IIOi~f~II II
- 2. Control Room .r Inlet 2(D4
- 3. Control Room Xr Ouletl , it
- 5. Smoke Removal Fon W-17 (1IIv44
- 6. Control Room IWAG Secondary Gooseneck AC 112 ffe 5'(J~,l so, - 4v7
- 7. Equtpment Room Supply Fan VU-28 =
-Polnts 13-17 and 20 art located on wolls 10' below Auir Bldg. roof. -Xi other points cre,locoted on Auxilary E beo ldg.ui-3roof.' *D' 7C. 9So'
CA060o1 REV 0
'PAGE 78 %0 12,ON l7 d X 7-Mba/ IeZ &2- -yzb L44, cL 0.6 VJ-Z5aN+34 2,5 37W10:17,2f e3--
Z;az.:V(' Z. Y5 I
,/115-7
- -5.l 9-"6 13 ,9-1-7 3Lo -" 2Z582, z °-: .to t7,7 YS . .
1t -z 23,7;,- CP = 72 . Wea-7,
/
I.10 A aZ7 2? 2 =' ,Z. 7Z7 77 V"51-, 5w't- i45.,77Vp: ;3:
// // ~ ~ I
CADSO ? REV 0 PAGE 71 . o 50 too, 150' ) : ,2 OmIOm 20m 3Om 40nm 50m ' 1. 2. Control Room Air Inlet I Control Room Air Inlet t2l q1
- 3. Control Roomnir Outlet
- 4. Exhaust Vent W-54 S. Smoke Removal Fan W-17
- 6. Control Room HVAC Secondary Gooseneck AC 112
- 7. Equipment Room Supply Fan VW-28
-Points 13-17 cnd 20 ore locaed on wvcs 10' below Auxiliary Bldg. root. - Ail other polnts are located on Auxiliary Bldg..roao.
CA08012 I REY 0 PAGE (o -y
/~' .' D o 0 J.4 VS Y ; I ., -, aw ljok ..5/-Y5-2 5r7 t.V* ,, ' /2 LIZ V5s i 4/2 > W.9?9~. ft
CA06012 Rev.0 Page 81 of 283 ATTACHMENT D JOINT FREQUENCY TABLES CC1991.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 1
.MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 .15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 1 20 60 30 10 1 0 0 0 122 NNE 0 0 0 0 3 2 17 50 17 6 2 0 0 0 97 NE 0 0 1 0 2 7 20 20 11 5 3 0 0 0 69 ENE 0 0 0 5 5 8 21 19 0 0 0 0 0 0 S8 E 0 0 0 1 1 11 23 18 1 0 0 0 0 0 55 ESE 0 0 0 0 0 3 7 25 2 0 0 0 0 0 37 SE 0 0 0 0 0 1 10 37 6 1 0 0 0 0 55 SSE 0 0 0 1 0 1 4 28 26 3 0 0 0 0 63 S 0 0 0 0 1 1 3 6 4 1 0 0 0 0 16 SSW 0 0 0 0 0 1 1 31 20 5 0 0 0 0 58 SW 0 0 0 0 0 1 5 63 43 3 0 0 0 0 115 WSW 0 0 0 0 2 3 6 29 12 4 1 0 0 0 57 N 0 0 0 0 1 1 0 20 10 9 1 0 0 0 42 NNW 0 0 0 0 0 0 2 13 12 18 3 0 0 0 48 NW 0 0 0 1 1 2 8 18 19 25 0 0 0 0 74 NNW 0 0 0 0 3 2 15 18 13 5 0 0 0 0 56 999 0 0 1 0 0 3 2 0 0 0 1 0 0 0 7 0 0 2 8 19 48 164 455 226 95 12 0 0 0 1029 CC1991.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 1 10 26 11 10 1 0 0 0 .59 NNE 1 0 0 1 2 0 15 14 6 4 0 0 0 0 43 NE 0 1 1 0 3 3 6 4 6 3 1 0 0 0 28 ENE 0 0 0. 0 2 5 8 9 3 0 0 0 0 0 27 E 0 0 0 0 1 2 8 4 1 0 0 0 0 0 16.
ESE 0 0 0 0 1 1 12 3 0 0 0 0 0 0 17 SE. 0 0 0 0 2 1 1 9 3 0 0 0 0 0 16 SSE 0 0 0 0 0 1 3 17 9 3 0 0 0 0 33 S 0 0 0 0 2 0O 3 7 8 0 0 0 0 0 20 SSW 0 0 0 0 0 1 2 19 16 2 0 0 0 0 40 SW 0 0 0 0 1 1 8 34 20 6 0 0 0 0 70 WSW 0 0 0 0 0 2 5 15 12 2 2 0 0 0 38 W 0 0 0 0 1 1 3 17 4 3 0 0 0 0 29 WNW 0 0 0 0 0 1 2 6 13 11 4 0 0 0 37 NW 0 0 0 0 0 0 S 16 9 8 0 0 0 0 38 NNW 0 0 0 0 0 0 1 7 6 3 0 0 0 0 17 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1.15 20 92 207 127 55 8 0 0 0 528 CC1991.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 ' 3 6 14 16 6. 10 4 1 0 .0 60 NNE 0 0 0 1 2 2 14 10 7 4 0 0 0 1 41 NE 0 0 0 1 3 7 5 4 7 5 0 0 0 0 32 ENE 0 0 0 0 4 1 5 8 4 0 0 0 0 0 22 E 0 0 0 2 3 1 7 9 2 0 0 0 0 0 24 ESE 0 0 0 0 2 1 3 5 1 0 0 0 0 0 12 SE 0 0 0 0 0 1 8 14 4 0 0 0 0 0 27 SSE 0 0 0 0 0 0 4 23 6 3 0 0 0 0 36 S 0 0 0 0 1 1 3 11 3 3 0 0 0 0 22 SSW 0 1 0 0 0 3 13 13 19 8 2 0 0 0 59 SW 0 0 0 0 2 3 4 35 25 7 1 0 0 0 77 WSW 0 0 0 0 3 2 4 24 10 0 2 0 0 0 45 N 0 0 0 0 0 1 6 9 3 0 0 0 0 0 19 WNW 0 0 0 0 0 0 5 10 6 8 1 0 0 0. 30 NW 0 0 0 0 0 1 4 17 5 5 1 0 0 0 33 NNW 0 0 0 0 1 0 3 12 8 3 0 0 0 0 27 999 0 0 0 0 0 0 .1 0 1 0 0 0 0 0 2 0 1 0 4 24 30 103 220 117 56 11 1 0 1 568
CA06012 Rev.0 Page 82 of 283 CC1991.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 .5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 0 0 0 4 15 21 44 63 134 27 1 0 1 311 NNE 0 2 0 2 1 10 24 30 28 .55 42 6 0 3 203 NE 0 0 1 6 6 3 9 31 48 36 1 0 0 0 141 ENE 2 0 0 3 5 9 14 39 47 10 0 0 0 3 132 E 0 1 1 2 9 11 18 42 28 2 0 0 0 0 114 ESE 0 0 0 1 1 *8 8 16 8 2 0 0 0 1 45 SE 0 0 0 2 6 5 22 41 19 6 1 0 0 1 103 SSE 0 1 0 1 2 7 17 76 59 31 4 0 0 0 198 S 0 0 1 2 3 4 22 43 35 9 0 0 0 1 120 SSW 1 0 0 2 5 3 23 54 59 53 3 0 0 0 203 SW 1 1 0 1 7 8 21 74 82 48 2 0 0 1 246 WSW 0 0 1 1 11 5 28 54 28 4 0 0 0 0 132 W 0 0 1 2 1 8 12 34 13 10 1 0 0 0 82 WNW 0 1 0 2 2 5 21 25 55 39 10 0 0 0 160 NW 0 0 2 1 7 8 12 67 89 59 4 0 0 0 249 NNW 1 1 0 0 5 3 12 63 101 72 4 0 0 1 263 999 0 0 0 0 0 0 0 0 0 2 1 0 0 0 3 6 7 7 28 75 112 284 733 762 572 100 7 0 12 2705 CC1991.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS S MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 0 2 6 3 13 38 23 12 1 0 0 1 100 NNE 0 1 2 1 3 5 12 16 20 7 3 0 0 2 72 NE 0 2 3 3 4 6 7 9 4 0 0 0 0 1 39 ENE 0 0 0 2 2 5 8 .8 0 0 0 0 *0 0 25 E 1 1 1 1 1 6 7 10 2 0 0 0 0 0 30 ESE 0 1 1 1 1 2 7 23 6 1 0 0 0 0 43 SE 0 0 1 1 2 1 10 34 18 3 1 0 0 1 72 SSE 0 2 0 2 1 1 11- 48 62 18 1 0 0 2 148 S 1 .0 0 0 2 3 9 66 145 19 .0 0 0 O 245 SSW 0 0 0 2 1 1 9 62 201 86 3 0 0 0 365
- SW 2 2 1 1 7 2 14 53 157 78 1 0 0 1 319 WSW 1 0 2 4 3 S 4 48 66 3 1 0 0 0 137 W 3 1 0 2 2 3 9 47 29 3 0 0 0 1 100 WNW 1 3 0 0 5 4 11 50 57 11 0 0 0 0 142 NW 3 1 1 1 2 4 8 67 80 12 0 0 0 0 179 NNW 3 0 1 2 4 6 11 61 50 9 1 0 0 2 150 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 15 15 13 25 46 57 150 640 920 262 12 0 0 11 2166 CC1991.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 2 1 1 1 4 5 14 1 0 0 0 0 0 29 NNE 1 1 0 2 0 4 4 6 1 1 0 0 0 0 20 NE 0 1 2 2 1 2 6 2 1 0 0 0 0 1 18 ENE 0 0 0 0 4 2 6 5- 0 0 0 0 0 0 17 E 0 0 1 1 2 6 3 6 -0 0 0 0- 0 2 21 ESE 0 1 0 1 0 3 10 6 2 0 0 0 0 1 24 SE 0 0 0 1 2 1 3 14 4 0 0 0 0 1 26 SSE 0 0 0 0 3 2 6 19 16 0 0 0 0 0 46 S 1 0 0 1 1 7 5 38 84 4 0 0 0 1 142 SSW 0 0 0 3 1 1 8 52 81 25 0 0 0 0 171 SW 1 2 0 3 3 3 10 50 71 14 0 0 0 0 157 WSW 1 0 2 2 2 5 9 28 38 5 0 0 0 0 92 W 0 2 0 1 1 2 4 15 16 1 0 0 0 0 42 WNW 0 1 0 0 2 4 13 24 14 0 0 0 0 1 59 NW 1 1 0 0 6 1 5 14 26 2 0 0 0 1 57 NNW 1 2 0 2 3 0 8 32 14 0 0 0 0 1 63 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 13 6 20 32 47 105 325 369 52 0 0 0 9 984
CA06012 Rev.0 Page 83 of 283 CC1991 .MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 1 0 3 4 2 5 9 1 0 0 0 0 1 27 NNE 0 0 0 1 1 1 1 1 1 0 0 0 0 0 6 NE 1 1 0 1 0 1 2 1 0 0 0 0 0 0 .7 ENE 0 0 1 0 0 1 1 0 0 0 .0 0 0 1 4 E 0 1 2 1 1 2 6 0 0 0 0 0 0 3 16 ESE 0 1 0 0 3 *2 10 3 0 0 0 0 0 1 20 SE 0 2 0 1 4 4 11 5 0 0 0 0 0 0 27 SSE 0 0 1 3 1 3 7 11 5 1 0 0 0 1 33 S 1 1 0 1 2 4 4 27 38 4 0 0 0 0 82 SSW 0 0 0 0 1 6 4 24 24 6 0 0 0 3 68 SW 0 0 0 3. 1 0 7 20 17 11 0 0 0 0 59 WSW 0 0 1 2 0 1 5 20 9 2 0 0 0 0 40 W 0 0 0 0 4 2 6 9 8 3 0 0 0 0 32 WNW 0 0 0 1 0 5 8 20 11 1 0 0 0 1 47 NW 0 0 0 1 3 0 6 22 17 0 0 0 0 2 51 NNW 0 2 0 0 0 0 10 10 3 0 0 0 0 1 26 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 9 5 18 25 34 93 182 134 28 0 0 0 14 545 CC1991.MET JOINT FREQUENCY TABLE FOR 60M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ENE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 E 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ESE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SE 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 SSE 0 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 0 ' 0 .0 0 0 0 SSW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SW 0 0 0.0 0 0 0 0 0 0 0 0 0 0 0 WSW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNW 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 999 0.0 0 0 0 0 1 0 0 0 0 0 0 233 234 0 0 0 0 0 0 3 0 0 0 0 0 0233 236 CC1991.MET JOINT FREQUENCY TABLE FOR 60M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 2 4 1 6 18 32 88 207 135 176 34 2 0 3 708 NNE 2 4 2 8 12 24 87 127 80 77 47 6 0 6 482 NE 1 5 8 13 19 29 55 71 77 49 S 0 0 2 334 ENE 2 0 1 10 22 31 63 88 54 10 0 0 0 4 285 E 1 3 5 8 18 39 72 89 34 2 0 0 0 5 276 ESE 0 3 1 3 8 20 57 81 19 3 0 0 0 3 198 SE 0 2 1 5 16 14 66 154 54 10 2 0 0 3 327 SSE 0 3 1 7 7 15 52 222 183 59 5 0 0 3 557 S 3 1 1 4 12 20 49 198 317 40 0 0 0 2 647 SSW 1 1 0 7 8 16 60 255 :420 185 8 0 0 3 964 SW 4 5 1 8 21 18 69 329 415 167 4 0 0 2 1043 WSW 2 0 6 9 21 23 61 218 175 20 6 0 0 0 541 W 3 3 1 5 10 18 40 151 83 29 2 0 0 1 346 WNW 1 5 0 3 9 19 62 148 168 88 18 0 0 2 523 NW 4 2 3 4 19 16 48 221 245 111 5 0 0 3 681 NNW 5 5 1 4 16 11 61 203 195 92 5 0 0 5 603 999 0 0 1 0 0 3 4 0 1 2 2 0 0 233 246 31 46 34 104 236 348 994 2762 2655 1120 143 8 0 280 8761
CA06012 Rev.0 Page 84 of 283 CC1991.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 1 9 31 54 12 0 0 0 0 0 108 NNE 0 0 0 0 0 6 55 83 5 0 0 0 0 0 149 NE 0 0 0 3 0 4 18 41 9 0 0 0 0 0 75 ENE 0 0 0 0 8 17 24 7 1 0 0 0 0 0 57 E 0 0 1 1 6 10 34 2 0 0 0 0 0 0 54 ESE 0 0 0 1 2 8 25 6 0 0 0 0 0 0 42 SE 0 0 0 0 0 2 18 24 2 .0 0 0 0 0 46 SSE 0 0 0 0 1 5 10 45 10 0 0 0 0 0 71 S 0 1 0 0 0 0 4 4 2 1 0 0 0 0 12 SSW 0 0 0 0 0 1 8 27 6 0 0 0 0 0 42 SW 0 0 0 0 0 0 20 78 19 1 0 0 0 0 118 WSW 0 .0 0 0 1 4 13 40 9 1 0 0 0 0 68 W 0 0 0 0 4 0 7 18 5 1 0 0 0 0 *35 WNW 0 0 0 0 0 0 9 25 17 1 0 0 0 0 52 NW 0 0 0 2 0 1 7 19 23 4 0 0 0 0 56 NNW 0 0 0 1 0 4 10 18 10 0 0 0 0 0 43 999 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 0 1 1 9 24 71 293 491 130 9 0 0 0 0 1029 CC1991.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 2 9 19 12 1 0 0 0 0 43 NNE 0 0 0 0 2 4 19 19 2 0 0 0 0 0 46 NE 0 0 0 0 1 3 17 17 3 0 0 0 0 0 41 ENE 0 0 0 1 1 8 14 5 1 0 0 0 0 0 30 E 0 0 0. 0 3 10 5 2 0 0 0 0 0 0 20 ESE 0 0 0 0 1 4 10 1 0 0 0 0 0 0 16 SE 0 0 0 0 3 4 S 6 0 0 0 0 0 0 18 SSE .0 0 0 0 0 0 5 16 8 0 0 0 0 0 29 S 0 0 0 0 1 1 5 11 0 0 0 0 0 0 18 SSW 0 0 0 0 0 1 5 27 4 0 0 0 0 0 37 SW 0 0 0 0 0 1 21 35 10 0 0 0 0 0 67 WSW 0 0 0 0 1 2 9 26 3 1 0 0 0 0 42 W 0 0 0 0 0 3 5 14 4 1 0 0 0 0 27 WNW 0 0 0 0 1 1 7 14 7 1 0 0 .0 0 31 NW 0 0 0 0 0 1 7 16 13 3 0 0 0 0 40 NNW 0 0 0 0 0 1 9 11 2 0 0 0 0 0 23 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 14 46 152 239 69 7 0 0 0 0 528 CC1991.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 2 3 15 23 9 1 0 0 0 0 54 NNE 0 0 0 2 2 6 26 9 6 1 0.0 0 0 52 NE 0 0 .0 0 1 3 17 14 5 0 0 0 0 0 40 ENE 0 0 0 0 5 5 6 8 0 0 0 .0 0 0 24 E 0 0 0 1 4 7 6 4 1 0 0 0 0 0 23 ESE 0 0 0 0 4 2 8 1. 0 0 0 0 0 0 15 SE 0 0 0 0 1 3 7 -6 0 0 0 0 0 0 17 SSE 0 0 0 0 0 2 12 26 5 0 0 0 0 0 45 S 0 0 0 1 0 2 5 10 2 0 0 0 0 0 20 SSW 0 0 0 0 3 1 9 16 7 1 0 0 0 0 37 SW 0 0 0 0 2 3 14 47 18 2 0 0 0 0 86 WSW 0 0 0 0 1 3 17 23 2 2 0 0 0 0 48 W 0 0 0 0 3 4 10 10 1 1 0 0 0 0 29 W14 0 0 0 0 1 4 6 4 6 1 0 0 0 0 22 NW 0 0 0 0 0 2 8 12 8 0 0 0 0 0 30 NNW 0 0 1 0 1 1 9 9 4 0 0 0 0 0 25 999 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 0 0 1 5 30 51 176 222. 74 9 0 0 0 0 568
CA 06012 Rev.0 Page 85 of 283 CC1991.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 2 0 0 5 11 13 48 128 100 6 0 0 0 0 313 NNE 0 0 1 4 14 21 47 77 86 7. 0 0 0 0 257 NE 0 0 2 2 11 12 30 54 57 5 0 0 0. 0 173 ENE 0 1 2 0 8 16 33 78 7. 0 0 0 0 0 145 E 0 1 2 6 14 13 37 35 1. 0 0 0 0 0 109 ESE 0 0 2 4 13 10 21 16 0 0 0 0 0 0 66 SE 0 1 2 2 10 14 30 16 2 0 0 0 0 1 78 SSE 0 1 3 2 11 .21 43 77 24 4 0 0 0 0 186 S 0 0 1 2 12 15 40 53 11 0 0 0 0 0 134 SSW 0 1 1 5 8 10 30 76 35 3 0 0 0 1 170 SW 0 1 1 2 14 17 64 104 64 4 0 0 0 0 271 WSW 1 1 3 5 14 18 41 65 5 0 0 0 0 0 153 W 0 0 1 2 12 16 28 20 8 1 0 0 0 0 88 WNW 0 0 5 1 9 8 21 45 22 8 0 0 0 0 119 NW 0 1 0 5 11 18 34 108 35 7 0 0 0 0 219 NNW 0 2 2 3 8 10 53 121 24 0 0 0 0 0 223 999 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 3 10 28 50 181 232 600 1073 481 45 0 0 0 2 2705 CC1991.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS S MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100. 130 180 9998 9999 N 0 3 4 6 15 14 37 28 5 1 0 0 0 0 113 NNE 0 2 2 6 10 17 18 14 3 0 0 0 0 0 72 NE 0 0 2 2 7 10 9 9 2 0 0 0 0 0 41 ENE 0 2 4 7 5 9 4 1 0 0 0 0 0 0 32 E 1 1 1 5 7 0 7 2 0 0 0 0 0 0 24 ESE 0 3 2 3 8 9 9 0 0 0 0 0 0 0 34 SE 1 2 3 5 10 14 14 7 2 1 0 0 0 0 -59 SSE 0 4 2 8 18 12 29 24 3 0 0 0 0 1 101 S 3 4 4 8 17 20 77 85 2 0 0 0 0 0 220 SSW 1 8 6 8 22 29 87 148 25 1 0 0 0 0 335 SW 4 4 5 8 16 31 103 240 51 1 0 0 0 1 464 WSW 4 4 4 5 12 14 58 60 1 1 0 0 0 0 163 W 2 2 1 4 12 16 35 16 2 0 0 0 0 0 90 WNW 0 5 2 7 16 24 33 25 3 0 0 0 0 0 115 NW 0 4 4 7 21 18 76 46 2 0 0 0 0 0 178 NNW 1. 3 4 7 11 21 48 28 0 0 0 0 0 0 123 999 0 2 0 0 0 0 0 0. 0 0 0 0 0 0 2 17 53 50 96 207 258 644 733 101 5 0 0 0 2 2166 CC1991.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 160 9998 9999 N 1 4 2 4 5 7 2 0 0 0 0 0 0 0 25 NNE 0 1 2 1 5 5 4 0 0 0 0 0 0 0 18 NE 0 .0 4 2 2 3 2 0 0 0 0 0 0 0 13 ENE 0 2 2 0 3 8 0 0 0 0 0 0 0 0 15 E 1 1 5 1 1 2 0 0 0 0 0 0 0 0 11 ESE 0 5 4 0 3 0 0 0 0 0 0 0 0 0 12 SE 1 2 2 2 3 4 0 0 0 0 0 0 0 0 14 SSE 0 2 2 4 12 5 6 0 0 0 0 0 0 0 31 S 1 4 6 7 15 23 33 3 0 0 0 0 0 0 92 SSW 4 5 8 12 21 44 84 15 0 0 0 0 0 0 193 SW 1 6 3 14 34 44 107. 60 0 0 0 0 0 0 269 WSW 2 6 3 5 8 13 36 8 0 0 0 0 0 0 81 W 0 2 3 5 14 17 16 2 0 0 0 0 0 0 59 WNW 1 4 0 6 18 17 7 0 0 0 0 0 0 0 53 NW 0 4 2 4 14 18 16 3 0 0 0 0 0 0 61 NNW 3 3 3 5 5 8 6 1 0 0 0 0 0 0 34 999 0 0 0 0 1 0 2 0 0 0 0 0 0 0 3 15 S1 51 72 164 218 321 92 0 0 0 0 0 0 984
CA06012 Rev.0 Page 86 of 283 . CC1991.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 2 1 1 0 0 0 0 0 0 0 5 NNE 0 0 1 1 4 2 1 0 0 0 0 0 0 0 9 NE 0 0 2 2 9 2 1 0 0 0 0 0 0 0 16 ENE 0 2 2 0 2 1 1 0. 0 0 0 0 0 0 8 E 1 2 1 0 0 0 1 0 0 0 0 0 0 0 5 ESE 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 SE 1 1 2 1 2 0 1 0 0 0 0 0 0 0 8 SSE 0 2 2 0 2 0 0 0 0 0 0 0 0 0 6 S 2 5 1 7 11 16 12 0 0 0 0 0 0 0 54 SSW 0 2 2 2 36 25 25 2 0 0 0 0 0 0 94 SW 0 6 2 18 22 28 38 11 0 0 0 0 0 0 125 WSW 0 6 6 11 19 12 12 2 0 0 0 0 0 0 68 W 2 .3 9 13 16 12 6 1 0 0 0 0 0 0 62 WNW 0 0 1 3 24 13 4 0 0 0 0 0 0 0 45 rW 0 1 0 5 5 8 11 0 0 0 '0 0 0 0 30 NNW 0 1 1 3 3 1 0 0 0 0 0 0 0 0 9 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 32 32 67 157 121 114 16 0 0 0 0 0 0 545 CCl991.MET JOINT FREQUENCY TABLE FOR 10M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 2 1 2 3 7 3 0 0 0 0 0 0 19 NNE 0 0 0 3 2 3 5 8 0 0 0 0 0 0 21 NE 0 0 1 0 5 0 2 0 0 0 0 0 0 0 8 ENE 0 0 1 2 1 3 0 0 0- 0 0 0 0 0 7 E 0 0 0 1 1 8 1 0 0 0 0 0 0 0 11 ESE 0 0 1 5 2 0 0 0 0 0 0 0 0 0 8 SE 0 0 0 1 1 3 0 0 0 0 0 0 0 .0 5 SSE 0 1 1 0 1 2 7 0 0. 0 0 0 0 0 12 S 0 0 0 0 4 6 1 0. 0 0 0 0 0 0 11 SSW 0 0 1 1 3 3 1 0 0 0 0 0 0 0 9 SW 0 0 2 0 3 4 5 6 0 0 0 0 0 0 20 WSW 0 0 1 0 4 1 3 3 0 0 0 0 0 0 12 W 0 0 0 0 3 4 9 1 0 0 0 0 0 0 17 WNW 0 0 0 0 2 1 2 0 0 0 0 0 0 0 5 NW 0 1 0 2 5 2 1 0 0 0 0 0 0 0 11 NNW 0 0 0 2 5 2 1 0 0 0 0 0 0 0 10 999 0 0 0 0 0 1 0 0 0 0 0 0 0 49 50 0 3 10 18 44 46 45 21 0 0 0 0 0 49 236 CCl991.MET JOINT FREQUENCY TABLE FOR 10M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 .N 3 8 8 19 38 52 150 255 138 9 0 0 0 0 680 NNE 0 3 6 17 39 64 175 210 102 8 0 0 0 0 624 NE 0 0 11 11 36 37 96 135 76 5 0 0 0 .0 407 ENE 0 7 11 10 33 67 82 99 9 0 0 0 0 0 318 E 3 5 10 15 36 50 91 45 2 0 0 0 0 0 257 ESE 0 9 9 13 33 33 73 24 0 0 0 0 0 0 194 SE 3 6 9 11 30 44 75 59 6 1 0 0 0 1 245 SSE 0 10 10 14 45 47 112 188 50 4 0 0 0 1 481 S 6 14 12 25 60 83 177 166 17 1 0 0 0 0 561 SSW 5 16 18 28 93 114 249 311 77 5 0 0 0 1 917 SW 5 17 13 42 91 128 372 581 162 8 0 0 0 1 1420 WSW 7 17 17 26 60 67 189 227 20 5 0 0 0 0 635 W 4 7 14 24 64 72 116 82 20 4 0 0 0 0 407 WNW 1 9 8 17 71 68 89 113 55 11 0 0 0 0 442 NW 0 11 6 25 56 68 160 204 81 14 0 0 0 0 625 NNW 4 9 11 21 33 48 136 188 40 0. 0 0 0 0 490 999 0 2 0 0 3 1 3 0 0 0 0 0 0 49 58 41 150 173 318 821 1043 2345 2887 855 75 0 0 0 53 8761
CA06012 Rev.0 Page 87 of 283 CC1992.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 0 3 25 67 29 5 2 0 0 0 132 NNE 0 0 0 0 0 7 27 32 14 11 3 0 0 0 94 NE 0 1 0 0 0 3 13 8 1. 7 2 0 0 0 35 ENE 0 0 0 0 0 0 0 .3 1 0 0 0 0 0 4 E 0 0 0 0 0 1 4 5 2 0 0 0 0 0 12 ESE 0 0 0 0 0 0 0 4 0 0 0 0 0 0 4 SE 0 0 0 0 0 0 0 3 3. 0 0 0 0 0 6 SSE 0 0 0 0 0 1 0 1 7 3 0 0 0 0 12 S 0 0 0 0 0 0 0 0 2 0 0 0 0 0 2 SSW 0 0 1 0 0 0 1 1 3 1 0 0 0 0 7 SW 0 0 0 0 0 0 0 1 11 3 0 0 0 0 15 WSW 0 0 0 0 0 0 4 5 2 4 0 0 0 0 15 W 0 0 0 1 0 0 4 4 6 0 0 0 0 1 16 WNW 0 0 0 0 0 3 2 4 13 4 4 0 0 0 30 NW 0 0 0 0 0 0 0 10 5 6 5 0 0 0 26 NNW 0 0 0 0 0 1 1 8 9, 1 1 0 0 0 21 999 0 0 .0 0 1 2 5 2 0 0 0 0 0 1 11 0 1 1 2 1 21 86 158 108 45 17 0 0 2 442 CC1992.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 1 16 33 8 1 1 0 0 0 61 NNE 0 0 0 0 0 5 15 14 3 3 3 0 0 0 43 NE 0 0 0 0 1 1 6 4 1 1 2 0 0 0 16 ENE 0 0 0 0 1 3 8 3 1 0 0 0 0 0 16 E 0 0 0 0 0 0 10 14 0 0 0 0 0 0 24 ESE 0 0 0 0 0 0 1 3 1 0 0 0 0 0 5 SE 0 0 0 0 0 0 0 2 1 3 0 O 0 0 6 SSE 0 0 0 0 0 0 0 4 5 1 0 0 0 0 10 S 0 0 0 0 0 0 0 3- 2 0 0 0 0 0 5 SSW 0 0 0 0 0 0 0 1 3 0 0 0 0 0 4 SW 0 0 0 0 0 0 1 4 12 5 0 0 0 0 22 WSW 0 0 0 0 0 0 0 4 4 2 1 0 0 0 11 W 0 0 0 0 0 0 1 3 5 1 0 0 0 0 10 WNW 0 0 0 0 0 0 1 6 10 2 1 0 0 0 20 NW 0 0 0 0 1 0 0 2 11 .14 0 0 0 0 28 NNW 0 0 0 0 0 0 3 6 9 3 0 0 0 0 21 999 0 0 0 ,0 0 0 0 0 -0 0 0 0 0 0 0 0 0 0 0 4 10 62 106 76 36 8 0 0 0 302 CC1992.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 2 4 12 14 14 9 1 0 0 0 56 NNE 0 0 0 0 5 4 10 14 5' 4 1 0 . 0 0 43 NE. 0 0 0 0 0 3 11 7 3 3 5 0 0 0 32 ENE 0 0 0 0 0 4 3 4 2 1 0 0 0 0 14 E 0 0 0 0 2 2 9 6 0 0 0 0 0 1 20 ESE 0 0 0 0 1 2 4 6 0 0 0 0 0 0 13 SE 0 0 0 0 0 1 2 3 3 1 0 0 0 0 10 SSE 0 0 0 0 0 1 2 12 9 2 0 0 0 0 26 S 0 0 0 0 0 0 2 8 3 0. 0 0 0 0 13 SSW 0 0 0 0 0 0 0 9 5 1 0 0 0 0 15. SW 0 0 0 0 0 0 2 11 8 4 0 0 0 0 25 WSW 0 0 0 0 0 0 2 11 7 2 2 0 0 0 24 W 0 0 0 0 0 0 1 8 3 0 1 0 0 0 13 WNW 0 0 0 0 0 0 0 7 *8 12 2 0 0 0 29 NW 0 0 0 0 1 0 2 6 6 4 2 0 0 0 21 NNW 0 0 0 0 0 4 4 8 11 2 0 0 0 0 29 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 25 66 134 87 45 14 0 0 1 383
CA 06012 Rev.0 Page 88 of 283 CC1992.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 S 7 10 25 20 30 50 70 100 130 180 9998 9999 N 0 1 0 1 7 11 23 86 94 72 30 8 2 2 337 NNE 0 0 1 3 7 9 35 104 78 54 26 5 0 1 323 NE 0 2 0 2 6 13 33 .74 86 31 29 3 0 0 279 ENE 0 1 3 3 11 15 34 101 47 17 1 0 1 1 235 E 0 1 2 4 13 22 51 82 27 2 0 0 0 2 206 ESE 0 0 0 3 6 4 29 70 24 8 3 0 0 1 148 SE 0 0 0 1 7 9 17 68 23 18 0 0 0 0 143 SSE 0 0 0 4 3 7 26 110 65 49 5 0 0 1 270 S 0 0 0 0 0 5 18 41 23 12 S 0 0 0 104 SSW 0 0 0 1 4 5 28 72 47 31 1 1 0 0 190 SW 0 0 0 1 3 7 47 83 74 43 1 1 0 0 260 WSW 1 0 2 1 3 4 20 53 31 16 1 1 0 1 134 W 0 1 1 1 1 5 17 33 22 11 1 0 0 0 93 WNW 0 1 3 2 2 4 11 50 50 42 15 1 0 2 183 NW 0 0 0 2 9 4 10 70 63 39 9 0 0 0 206 NNW 0 0 . 5 2 5 10 75 97 47 3 0 0 2 246 999 1 0 0 0 1 0 4 0 0 0 0 0 0 1 7 2 7 13 34 85 129 413 1172 851 492 130 20 3 13 3364 CC1992.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 S 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 1 0 1 7 6 27 93 73 31 4 1 1 0 246 NNE 0 0 0 2 4 8 32 52 32 18 4 0 0 1 153 NE 0 0 2 3 4 7 11 25 10 2 4 0 0 0 68 ENE 0 0 0 2 1 4 25 25 5 3 1 0 0 0 66 E 0 1 1 0 6 13 26 42 9 1 1 0. 0 0100 ESE 0 0 0 2 6 6 12 35 I5 0 1 0 0 1 78 SE 0 0 0 1 2 4 12 59 11 3 I' O 0 0 93 SSE 0 0 0- 1 2 3 24 79 71 21 1 0 0 2 204 S 0 0 0 2 3 4 10 90 112 30 0 0 0 0 251 SSW 0 0 0 0 1 6 14 73 138 59 1 0 0 0 292 SW 0 1 1 1 4 3 25 69 134 98 3 0 0 0 339 WSW 0 1 0 0 4 2 20 62 62 25 0 0 0 0 176 W 0 0 1 1 3 5 15 60 20 2 0 0 0 1 108 WNW 2 0 0 0 2 S 14 79 71 19 3 1 0 0 195 NW 0 0 1 0 5 5 16 117 90 26 2 0 0 2 264 NNW 1 0 0 0 1 5 17 123 107 12 0 1 0 0 267 999 1 0 1 0 0 0 1 0 0 0 0 0 0 0 3 4 4 7 16 55 86 301 1083 960 350 26 3 1 7 2903 CC1992.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 1 1 1 3 5 10 16 8 0 0 0 0 0 46 NNE 0 0 0 2 1 3 12 2 3 3 0 0 0 0 26 NE 1 0 0 2 3 4 8 14 2 0 0 0. 0 0 34 ENE 0 0 0 0 2 2 3 6 2 0 0 0 0 0. 15 E 0 0 0 0 1 4 5 3 0 0 0 0 0 0 13 ESE 0 1 0 1 1 2 11 7 1 0 0 0 0 0 24 SE 0 0 0 0 1 4 4 14 3 0 0 0 0 0 26 SSE 1 0 0 0 1- 1 4 18 9 l 0 0 0 2 37 S 0 0 0 1 1 1 5 37 61 6 0 0 0 0 112 SSW 0 0 0 0 1 3 6 27 52 6 0 0 0 0 95 SW 0 .0 0 1 2 3 6 27 28 10 0 0 0 0 77 WSW 0 0 0 0 0 3 4 27 29 5 0 0 0 0 68 W 0 0 0 2 4 3 4 29 14 0 0 0 0 0 56 WNW 1 0 0 0 1 2 6 15 13 0 0 0 0 0 38 NW 0 0 0 1 1 3 6 25 28 3 0 0 0 2 69 NNW 0 1 0 1 1 3 9 24 24 0 0 0 0 0 63 999 0 1 0 0 0 1 1 6 2 0 0 0 0 5 15 4 4 1 12 24 47 104 297 278 34 0 0 0 9 814
CA 06012 Rev.0 Page 89 of 283 CC1992.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 3 1 7 4 10 5 0 0 0 0 0 1 32 NNE 0 0 1 1 2 1 7 4 1 0 0 0 0 0 17 NE 0 0 1 0 3 2 1 0 1. 0 0 0 0 0 8 ENE 1 0 1 1 2 1 6 1 0 0 0 0 0 0 13 E 0 3 2 0 1 2 2 0 0 0 0 0 0 0 10 ESE 0 1 0 1 *2 3 2 3. 1 0 0 0 0 2 15 SE 1 0 0 0 2 1 6 2 0 0 0 0 0 0 12 SSE 0 1 0 0 3 3 5 8 6 0 0 0 0 0 26 S 0 0 1 2 1 3 5 18 35 5 0 0 0 0 70 SSW 0 1 0 0 2 4 10 30 37 5 0 0 0 0 89 SW .0 0 0 0 3 3 4 29 9 0 0 0 0 0 48 WSW 1 0 0 1 3 4 4 26 6 3 0 0 0 0 48 W 1 0 1 2 3 2 4 19 22 2 0 0 0 1 57 WNW 0 1 0 1 0 2 4 13 8 5 0 0 0 0 34 NW 0 0 0 2 3 2 7 8 4 0 0 0 0 0 26 NNW 0 1 0 0 1 4 8 12 7 0 0 0 0 0 33 999 0 0 0 0 0 0 0 0 1 0 0 0 0 1 2 4 9 10 12 38 41 85 178 138 20 0 0 0 5 540 CC19924.MET JOINT FREQUENCY TABLE FOR 60M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 .50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 1 0 0 0 0 0 0 I NNE 0 0 1 0 0 0 0 0 0 0 0 0 0 0 1 NE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ENE 0 0 0 0 0 0 1 2 0 0 0 0 0 .0 3 E 0 0 0 0 0 1 1 0 0 0 0 0 0 0 2 ESE 0 0 0 0 0 0 0 0 -0 0 0 0 0 0 0 SE 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 SSE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSW . 0 0 0 0 0 1 0 0 0 0 0 0 0 1 SW 0 0 0 0 2 0 0 0 0 0 0 0 0 0 2 WSW 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 W 0 0 0 0 0 0 0 0 0 1 0 0 0 0 1 WNW 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 NW 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 NNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 999 0 0 0 0 0 0 0 0 0 0 0 0 0 22 22 0 0 1 2 2 2 3 4 0 1 0 0 0 22 37 CC1992.MET JOINT FREQUENCY TABLE FOR 60M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 2 4 4 5 27 34 123 315 226 118 38 9 3 3 911 NNE 0 0 3 8 19 37 138 222 136 93 37 5 0 2 700 NE 1 3 3 7 17 33 83 132 104 44 42 3 0 0 472 ENE 1 1 4 6 17 29 80 145 58 21 2 0 1 1 366 E 0 5 5 4 23 45 108 152 38 3 1 0 0 3 387 ESE 0 2 0 7 16 17 59 128 42 8 4 0 0 4 287 SE 1 0 0 3 12 19 41 151 44 25 1 0 0 0 297 SSE 1 1 0 5 9 16 61 232 172 77 6 0 0 5 585 S 0 0 1 5 5 13 40 197 238 53 5 0 0 0 557 SSW 0 1 1 1 8 18 60 213 285 103 2 1 0 0 693 SW 0 1 1 3 14 16 85 224 276 163 4 1 0 0 788 WSW 2 1 2 2 10 14 54 188 141 57 4 1 0 1 477 W 1 1 3 7 11 15 46 156 92 17 2 0 0 3 354 WNW 2 2 3 3 5 16 38 175 173 84 25 2 0. 2 530 NW 0 0 1 6 20 14 41 238 207 92 18 0 0 4 641 NNW 1 2 1 6 5 22 52 256 -264 65 4 1 0 1 680 999 2 1 1 0 2 3 11 8 2 0 0 0 0 30 60 14 25 33 78 220 361 1120 3132 2498 1023 195 23 4 59 8785
CA06012 Rev.0 Page 90 of 283 CC1992.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 2 6 31 57 8 1 0 0 0 0 105 NNE 0 0 0 0 2 12 41 46 7 0 0 0 0 0 108 NE 0 0 0 0 1 5 26 8 13 1 0 0 0 0 54 ENE 0 0 0 0 1 1 4 0 2 0 0 0 0 0 8 E 0 0 0 0 0 0 8 2 0 0 0 0 0 0 10 ESE 0 0 0 0 0 1 4 2 0 .0 0 0 0 0 7 SE 0 0 0 0. 0 0 1 4 0 0 0 0 0 0 5 SSE 0 0 0 0 0 0 1 8 3 0 0 0 0 0 12 S 0 0 0 0 1 1 0 2 1 0 0 0 0 0 5 SSW 0 0 0 0 1 0 0 3 .0 0 0 0 0 0 4 SW 1 0 0 0 0 0 0 3 9 0 0 0 0 0 13 WSW 0 0 0 1 0 1 6 5 6 0 0 0 0 0 19 W 0 0 0 0 2 1 5 7 1 0 0 0 0 0 16 WNW 0 0 .0 0 1 0 3 10 5 3 0 0 0 0 22 NW 0 0 0 0 0 1 4 13 4 7 0 0 0 0 29 NNW 0 0 0 1 0 0 2 9 5 1 0 0 0 0 18 999 0 0 0 0 1 0 2 0 0 0 0 0 0 4 7 1 0 0 2 12 29 138 179 64 13 0 0 0 4 442 CC1992.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 1 20 27 2 1 0 0 0 0 Si NNE 0 0 0 0 0 3 27 .12 2 0 0 0 0 0 44 NE 0. 0 0 0 3 3 15 9 4 1 0 0 0 0 35 ENE 0 0 0 0 1 4 11 2 0 0 0 0 0 0 18 E 0 0 0 0 1 4 14 1 0 0 0 0 0 0 20 ESE 0 0 0 0 0 1 3 3 0 0 0 0 0 0 7 SE 0 0 0 0 0 0 1 3 1 0 0 0 0 0 5 SSE 0 0 0 0 0 0 0 7. 4 0 0 0 0 0 11 S 0 0 0 0 0 0 0 5 0 *0 0 0 0 0 S SSW 0 0 0 0 0 0 0 3 2 0 0 0 0 0 5
- SW 0 0 0 0 0 0 1 5 14 1 0 0 0 0 21 WSW 0 0 0 0 0 1 2 5 2 2 0 0 0 0 12 W 0 0 0 0 0 1 2 4 3 0 0 0 0 0 10 WNW 0 0 0 0 0 0 3 8 1 1 0 0 0. 0 13 NW 0 0 0 0 1 0 0 15 16 0 0 0 0 0 32 NNW 0 0 0 0 0 1 2 7 3 0 0 0 0 0 13 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 19 101 116 54 6 0 0 0 0 302 CC1992.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 2 5 14 30 9 1 0 0 0 0 61 NNE 0 0 0 0 5 5 15 8 2 0 0 0 0 0 35 NE 0 0 0 0 2 2 18 13 5 4 0 0 0 0 44 ENE 0 0 0 0 1 4 8 7 1 0 0 0 0. 0 21 E 0 0 0 0 3 4 10 1 0 0 0 0 0 0 18 ESE 0 0 0 0 0 2 6 1 0 0 0 0 0 0 9 SE 0 0 0 0 0 2 3 6 0 0 0 0 0 0 11 SSE 0 0 0 0 0 1 2 17 4 0 0 0 0 0 24 S -0 0 0 0 0 1 2 11 0 0 0 0 0 0 14 SSW 0 0 0 0 0 0 2 8 3 0 0 0 0 0 13 SW 0 0 0 0 0 1 2 23 5 0 0 0 0 0 31 WSW 0 0 0 0 0 0 1 13 3 3 0 0 0 0 20 W 0 0 0 0 0 1 3 9 0 0 0 0 0 0 13 WNW 0 0 0 0 0 0 4 9 6 3 0 0 0 0 22 NW 0 0 0 0 0 3 1 10 9 0 0 0 0 0 23 NNW 0 0 1 0 2 0 6 11 1 2 0 0 0 1 24 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 15 31 97 177 48 13 0 0 0 1 383
CA 06012 Rev. 0 Page 91 of 283 CC1992.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 1 6 12 16 68 149 65 25 4 0 0 0 347 NNE 1 0 0 3 18 40 93 108 27 7 0 0 0 0 297 NE 0 0 1 6 9 18 79 128 45 24 0 0 0 1 311 ENE 0 1 0 4 24 47 104 88 8 0 1 0 0 0 277 E 1 0 4 8 27 38 68 18 1 0 0 0 0 2 167 ESE 0 2 1 4 16 32 59 41 .5 1 0 0 0 0 161 SE 1 0 1 7 6 21 48 44 12 0 0 0 0 0 140 SSE 0 0 1 1 13 8 66 122 42 5 0 0 0 0 258 S 2 1 2 0 11 15 32 49 18 3 0 0 0 0 133 SSW 0 0 1 4 5 13 41 76 24 4 0 0 0 0 168 SW 0 2 1 3 13 20 63 118 57 3 1 0 0 0 281 WSW 0 1 2 4 4 9 38 75 17 1 1 0 0 0 152 W 1 3 1 3 11 12 28 34 12 1 1 0 0 0 107 WNW 0 0 2 3 9 8 30 52 31 11 0 0 0 1 147 NW 0 1 0 6 11 10 51 81 35 10 0 0 0 0 205 NNW 0 0 1 3 8 12 53 107 17 5 0 0 0 1 207 999 0 0 0 0 0 1 1 1 0 0 0 0 0 3 6 6 12 19 65 197 320 922 1291 416 100 8 0 0 8 3364 CC1992.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS S MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 3 6 20 20 75 76 12 3 0 0 0 0 216 NNE 0 1 3 9 20 25 58 39 4 0 1 0 0 0 160 NE 1 1 1 5 7 12 20 20 3 1 0 0 0 0 71 ENE 0 0 2 4 11 13 19 6 3 1 0 0 0 0 59 E 1 0 3 7 14 15 23 2 2 0 0 0 0 0 67 ESE 2 3 6 7 24 19 16 11 1 0 0 0 0 0 89 SE 0 4 0 5 15 17 23 7 1 1 0 0 0 1 74 SSE 2 1 3 5 27 20 48 49 9 0 0 0 0 1 165 S 6 3 5 8 28 39 92 90 5 1 0 0 0 0 277 SSW 2 2 3 4 19 37 81 134 20 2 0 0 0 0 304 SW 2 3 5 5 20 34 79 187 55 4 0 0 0 1 395 WSW 2 5 8 13 16 25 58 70 8 0 0 0 0 0 205 W 1 6 1 10 23 27 38 21 3 0 0 0 0 0 130 WNW 1 0 3 11 32 43 44 33 8 2 1 0 0 0 178 NW 0 3 4 9 28 51 82 92 21 3 0 0 0 0 293 NNW 0 3 2 3 28 30 91 59 0 0 0 0 0 0 216 999 0 0 0 0 1 0 0 0 0 0 0 0 0 3 4 20 36 52 111 333 427 847 896 155 18 2 0 0 6 2903 CC1992.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 1 2 4 9 1 5 5 0 0 0 0 0 0 28 NNE 0 0 0 2 5 2 10 4 0 0 0 0 0 0 23 NE 0 *2 0. 3 4 2 4 00 0 0 0 0 0 15 ENE 0 1 1 1 5 2 1 0 .0 0 0 0 0 0 11 E 1 1 3 2 1 3 3 0 0 0 0 0 0 0 14 ESE 1 3 0 2 2 1 0 0 0 0 0 0 0 0 9 SE 1 1 1 6 5 3 1 0 0 0 0 0 0 0 18 SSE 1 2 2 3 13 9 2 0 0 0 0 0 0 0 32 S 3 3 4 5 15 19 30 1 0 0 0 0 0 0 80 SSW 7 4 4 4 25 33 59 14 0 0 0 0 0 0 150 SW 3 2 2 2- 14 27 46 33 0 0 0 0 0 0 129 WSW 1 3 8 1 21 23 20 10 0 0 0 0 0 1 88 W 2 4 4 9 13 13 11 1 0 0 0 0 0 0 57 WNW 0 3 4 7 19 21 9 0 0 0 0 0 0 0 63 NW 0 4 1 3 9 15 25 3 1 0 0 0 0 0 61 NNW 1 2 1 4 7 6 5 1 0 0 0 0 0 0 27 999 0 0 0 0 0 0 0 0 0 0 0 0 0 9 9 22 36 37 58 167 180 231 72 1 0 0 0 0 10 814
CA06012 Rev.0 Page 92 of 283 CC1992.MET JOINT FREQUENCY TABLE FOR 1OM AND STABILITY-CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 0 1 0 3 0 1 2 0 0 0 0 0 0 8 NNE 0 1 0 1 1 1 0 1 0 0 0 0 0 0 5 NE 0 0 1 0 0 0 0 0 0 0 0 0 0 .0 1 ENE 0 0 2 0 1 0 1 0 0 .0 0 0 0 0 4 E 1 0 0 0 1 1 1 0 0 0 0 0 0 0 4 ESE 0 0 0 1 1 1 0 0 0 0 0 0 0 0 3 SE 1 1 0 2 0 0 0 0 0 0 0 0 0 0 4 SSE 0 1 1 0 4 3 1 0 0 0 0 0 0 0 10 S 1 2. 3 6 17 15 7 1 0 0 0 0 0 2 54 SSW 3 7 3 11 23 19 41 1 0 0 0 0 0 0 108 SW 2 4 3 15 19 46 17 0 0 0 0 0 0 0 106 WSW 1 8 8 18 28 17 16 3 0 0 0 0 0 1 100 W 1 10 2 16 14 18 17 0 0 0 0 0 0 0 78 WNW 0 6 7 5 11 2 3 0 0 0 0 0 0 0 34 NW 0 0 1 0 1 6 8 0 0 0 0 0 0 0 16 NNW 1 0 2 1 0 0 0 0 0 0 0 0 0 0 4 999 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 12 40 34 76 124 129 113 8 0 0 0 0 0 4 540 CC1992.MET JOINT FREQUENCY TABLE FOR IOM AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNE 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 NE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ENE 0 0 0 0 0 0 4 0 0 0 0 0 0 0 4 E 0 0 0 3 0 1 0 0 0 0 0 0 0 .0 4 ESE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SE 0. 0 0 0 0 0 0 0 0 0 0 0 0 0 0-SSE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 O' 0 O 0 0 O O 0 SSW 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1, SW 0 0 0 0 1 1 0 0 0 0 0 0 0 0 2 WSW 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 W 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 WNW 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 NW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNW 0 0 0 *0 0 0 0 0 0 0 0 0 0 0 0 999 0 0 0 0 0 0 0 0 0 0 0 0 0 22 22 0 0 0 3 2 2 7 1 0 0 0 0 0 22 37 CC1992.MET JOINT FREQUENCY TABLE FOR IOM AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 2 3 7 16 48 49 214 346 96 31 4 0 0 0 816 NNE 1 2 3 15 51 88 245 218 42 7 1 0 0 0 .673 NE 1 3. 3 14 26 42. 162 178 70 31 0 0 0 1 531 ENE 0 2 5 9 44 71 152 103 14 1 1 0 0 0 402 E 4 1 10 20 47 66 127 24 3 0 0 0 0 2 304 ESE 3 8 7 14 43 57 88 58 6 1 0 0 0 0 285 SE 3 6 2 20 26 43 77 64 14 1 0 0 0 1 257 SSE 3 4 7 9 57 41 120 203 62 5 0 0 0 1 512 S 12 9 14 19 72 90 163 159 24 4 0 0 0 2 568 SSW 12 13 11 23 73 102 225 239 49 6 0 0 0 0 753 SW 8 11 11 25 67 129 208 369 140 8 1 0 0 1 978 WSW 4 17 26 37 70 76 141 181 36 6 1 0 0 2 597 W 5 23 8 38 63 73 105 76 19 1 1 0 0 0 412 WNW 1 9 16 26 72 74 96 113 51 20 1 0 0 1 480 NW 0 8 6 18 50 86 171 214 86 20 0 0 0 0 659 NNW 2 5 7 12 45 49 159 194 26 8 0 0 0 2 509 999 0 0 0 0 2 1 3 1 0 0 0 0 0 42 49 61 124 143 315 856 1137 2456 2740 738 150 10 0 0 55 8785
CA 06012 Rev.0 Page 93 of 283 CC1993.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 11 33 24 20 1 0 0 0 89 NNE 0 0 0 0 0 4 22 47 18 8 2 0 0 0 101 NE 0 0 0 0 0 3 16 8. 4 1 0 3 0 0 35 ENE 0 0 0 0 2 6 16 3 0 0 0 0 0 0 27 E 0 0 0 0 0 7 21 9 0 0 0 0 0 0 37 ESE 0 0 0 1 0 1 9 14 2 0 0 0 0 0 27 SE 0 0 0 0 0 1 7 19 11 1 0 0 0 0 39 SSE 0 0 0 0 0 0 3 25 13 3 0 0 0 0 44 S 0 0 0 0 0 0 2 7 4 1 0 0 0 0 14 SSW 0 0 0 0 0 1 4 9 6 2 0 0 0 0 22 SW 0 0 0 0 0 0 2 11 19 11 0 0 0 0 43 WSW 0 0 0 0 0 0 0 15 1 2 0 0 0 0 18 W 0 0 0 0 0 0 0 7 2 0 1 0 0 0 10 WNW 0 0 0 0 0 0 0 8 7 2 2 0 0 0 19 NW 0 0 0 0 0 0 0 7 20 6 1 0 0 0 34 NNW 0 0 0 0 0 1 1 7 7 0 0 0 0 0 16 999 0 0 0 0 0 0 0 0 0 0 2 0 0 0 2 0 0 0 1 2 24 114 229 138 57 9 3 0 0 577 CC1993.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 2 11 19 18 5 3 0 0 0 58 NNE 0 0 1 0 3 5 20 16 5 1 1 0 0 0 52 NE 0 0 0 0 0 2 8 5 2 0 0 1 0 0 18 ENE 0 0 0 0 2 1 6 1 0 0 2 1 0 0 13 E 0 0 0 1 1 3 11 2 0 0 0 0 0 0 18 ESE 0 0 0 0 2 1 5 7 0 0. 0 0 0 0 15 SE .0 0 0 0 0 1 5 6 1 1 1 0 0 01s SSE 0 0 0 2 0 .0 3 10 6 1 0 0 0 0 22 S 0 0 0 0 0 0 2 2 1 0 0 0 0 0 5 SSW 0 0 0 0 0 0 2 7 4 1 1 0 0 0 15 SW 0 0 0 0 0 0 2 11 7 4 0 0 0 0 24 WSW 0 0 0 0 0 1 1 14 6 2 0 0 0 0 24 W 0 0 0 0 0 0 0 3 0 0 0 0 0 0 3 WNW 0 0 0 0 . 0 0 0 6 6 5 0 0 0 0 17 NW 0 0 0 0 0 0 0 2 9 8 3 0 0 0 22 NNW 0 0 0 0 0 1 1 2 5 1 1 0 0 0 11 999 0 0 0 0 0 0 0 0 0 0 0 0 .0 0 0 0 0 1 3 8 17 77 113 70 29 12 2 0 0 332 CC1993.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 1 14 21 11 8 1 0 0 0 57 NNE 0 0 0 0 2 6 14 18 6 3 7 0 0 0 56 NE 0 0 0 0 1 1 4 6 1 0 7 0 0 0. 20 ENE 0 0 0 0 1 3 0 2 0 0. 1 1 0 0 8 E 0 0 0 0 0 7 5 3 0 0 0 0 0 0 15 ESE 0 0 0 0 0 1 3. 1 0 0 0 0 0 0 5 SE 0 0 0 1 1 0 5 10 5 0 0 0 0 0 22 SSE 0 0 0 0 0 0 2 12 9 1 0 0 0 0 24 S 0 0 0 0 0 0 1 3 1 0 0 0 0 0 5 SSW 0 0 0 0 1 0 3 4 5 1 0 0 0 0 14 SW 0 0 0 0 0 1 4 11 10 6 0 0 0 0 32 WSW 0 0 0 0 0 0 3 9 5 3 0 0 0 0 20 W 0 0 0 0 0 2 2 6 0 1 0 0 0 0 11 WNW 0 0 0 0 0 0 0 6 5 7 3 0 0 0 21 NW 0 0 0 0 0 0 0 8 9 13 5 0 0 0 35 NNW 0 0 0 0 0 0 2 7 9 5 0 0 0 0 23 999 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 1 7 22 62 128 76 48 24 1 0 0 369
CA06012 Rev.0 Page 94 of 283 CC1993.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 8 12 46 91 70 75 39 2 0 1 345. NNE 0 0 0 1 5 15 57 107 79 95 27 2 0 0 388 NE 0 0 1 3 2 18 35 91 68. 59 21 3 0 0.301 ENE 1 0 0 1 12 15 40 69 26 18 2 2 0 0 185 E 0 0 1 1 7 21 47 48 18 0 0 1 0 0 144 ESE 0 0 1 1 6 16 27 36 10 10 0 0 0 0 107 SE 0 1 1 1 6 4 13 58 28 12 5 0 0 0 129 SSE 0 0 0 1 3 4 21 102 69 30 5 1 0 0 236 S 0 0 1 1 4 4 7 36 36 9 0 0 0 0 98 SSW 0 0 0 1 2 2 13 51 55 40 4 0 0 0 168 SW 0 0 0 1 2 5 24 80 54 49 7 1 0 0 223 WSW 0 0 0 0 2 4 20 68 44 3 0 0 0 0 141 W 0 0 0 0 4 6. 18 43 13 14 2 0 0 0 100 WNW 0 0 0 1 5 6 6 30 44 33 11 0 0 0 136 NW 0 1 2 0 1 3 10 48 55 60 16 1 0 0 197 NNW 0 0 1 1 4 4 9 62 49 47 7 1 0 0 185 999 0 0 0 0 0 0 0 0 0 1 9 2 0 1 13 1 2 8 15 73 139 393 1019 718 555 155 16 0 2 3096 CC1993.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS S MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 1 2 4 1 18 63 58 18 0 0 0 0 165 NNE 0 0 1 1 3 2 24 57 21 14 2 0 0 0 125 NE 0 0 2 2 3 9 22 37 13 18 0 0 0 0 106 ENE 0 0 0 1 4 8 12 36 7 2 1 0 0 0 71 E 0 1 2 1 4 9 28 32 5 1 1 0 0 0 84 ESE 0 4 0 5 2 3 19 37 8 .1 0 0 0 0 79 SE 0 0 1 2 4 4 11 58 19 4 0 0 0 0 103 SSE 0 0 0 1 1 1 22 93 80 26 7 0 0 0 231 S 0 0 1 4 2 *6 18 60 "128 39 0 0 0 0 258 SSW 0 0 0 1 3 6 9 53 128 92 3 0 0. 0 295 SW 0 0 0 1 2 3 14 78 122 75 2 0 0 0 297 WSW '0 0 0 2 3 1 11 81 66 15 0 0 0 0 179 W 0 0 3 1 3 3 13 38 20 12 0 0 0 0 93 WNW 0 0 0 0 1 7 11 66 58 20 2 0 0 0 165 NW 0 0 0 2 4 4 17 95 97 36 1 0 0 0 256 NNW 0 0 1 1 2 1 14 124 93 16 0 0 0 0 252 999 0 0 1 0 0 1 0 0 0 0 0 0 0 0 2 0 5 13 27 45 69 263 1008 923 389 19 0 0 02761 CC1993.MET JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 1 2 2 4 4 9 12 1 1 0 0 0 0 37 NNE 0 0 1 1 2 2 4 5 4 0 0 0. 0 0 19 NE .0 1 0 0 2. 3 12 5 3 1 0 0 0 0 27 ENE 0 0 0 1 1 2 6 6 1 .0 0 0 0 0 17-E 0 0 1 3 4 3 6 2 0 0 0 0 0 0 19 ESE 0 0 0 1 3 4 7 14 1 0 0 0 0 0 30 SE 0 0 1 2 1 5 8 18 4 0 0 0 0 0 39 SSE 1 0 0 0 1 4 7 30 21 1 0 0 0 0 65 S 0 1 0 0 2 4 6 26 81 2 0 0 0 0 122 SSW 0 0 1 1 1 1 12 38 73 5 0 0 0 0 132 SW 0 1 0 1 3 3 4 33 62 4 0 0 0 0 111 WSW 0 0 0 2 2 3 9 35 15 5 0 0 0 0 71 W 0 0 0 1 3 4 9 14 26 1 0 0 0 0 58 WNW 1 0 1 2 0 1 8 19 15 0 0 0 0 0 47 NW 0 0 0 0 0 1 4 17 22 4 0 0 0 0 48 NNW 0 0 0 0 1 0 4 20 9 . 0. 0 0 0 0 34 999 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 3 4 7 18 30 44 115 294 338 24 0 0 0 0 877
CA06012 Rev.0 Page 95 of 283 CC1993.MET - JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 2 2 2 1 5 9 9 0 0 0 0 0 0 30 NNE .1 0 0 1 2 2 3 1 0 0 0 0 0 0 10 NE 0 0 1 1 1 3 1 1 1 0 0 0 0 0 9 ENE 0 0 0 2 2 3 4 1 0 0 0 0 0 0 12 E 0 1 0 3 5 6. 4 0 0 0 0 0 0 0 19 ESE 0 2 0 2 5 3 6- 3 0 0 0 0 0 0 21 SE 0 0 1 1 8 2 9 15 2 0 0 0 0 0 38 SSE 0 0 1 1 4 3 10 11 5 0 0 0 0 0 35 S 0 1 0 0 0 5 13 26 28 2 0 0 0 0 75 SSW 0 1 1 2 2 2 7 34 35 2 0 0 0 0 86 SW. 0 0 1 3 5 2 10 40 19 4 0 0 0 0 84 WSW 1 1 2 1 2 3 4 26 13 2 0 0 0 0 55 W 0 0 0 1 4 7 7 28 23 0 0 0 0 0 70 WNW 0 0 1 1 1 0 11 9 9 4 0 0 0 0 36 NW 0 1 1 2 1 3 3 10 .11 4 0 0 0 0 36 NNW 0 2 0 1 2 8 7 13 3 0 0 0 0 0 36 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 11 11 24 45 57 108 227 149 18 0 0 0 0 652 CC1993.MET JOINT FREQUENCY TABLE FOR 60M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 5 5 NNE 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 NE 0 0 0 0 0 1 1 0 1 0 0 0 0 2 5 ENE 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 E 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 ESE 0 0 0 0 0 0 0 0 .0 0 0. 0 0 0 0 SE 0 0 0 0 0 0 0 0 0 0 0 0 0 4 4 SSE 0 0 0 0 0 0 0 0 1 0. 0 0 0 3 4 S 0 0 0 0 0 0 0 0 0 0 0 0 0 11 11 SSW 0 0 0 0 1 0 0 0 0 0 0 0 .0 0 1 SW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WSW 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 W 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NW 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 NNW 0 0 0 1 0 0 .0 0 0 0 0 0 0 0 1 999 0 0 0 0 0 0 0 0 0 0 0 0 0 59 59 0 .0 0 2 2 1 2 0 2 0, 0 0 0 88 97 CC1993.MET JOINT FREQUENCY TABLE FOR 60M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 3 5 7 18 25 118 248 182 127 44 2 0 6 786 NNE 1 0 3 4 17 36 144 251 133 121 39 .2 0 2 753 NE 0 1 4 6 .9 40 99 153 93 79 28 7 0 2 521 ENE 1 0 0 6 24 38 84 117 34 20 6 4 0 0- 334 E 0 2 4 9 21 56 123 96 23 1 1 1 0 0 337 ESE 0 6 1 10 18 29 76 112 21 11 0 0 0 0 284 SE 0 1 4 7 20 17 58 184 70 18 6 0 0 4 389 SSE 1 0 1 5 9 12 68 283 204 62 12 1 0 3 661 S 0 2 2 5 8 19 49 160 279 53 0 0 0 11 5s8 SSW 0 1 2 5 10 12 50 196 306 143 8 0 0 0 733 SW 0 1 1 6 12 14 60 264 293 153 9 1 0 0 814 WSW 1 1 2 5 9 12 48 248 150 32 0 0 0 2 510 W 0 0 3 3 14 22 49 139 84 28 3 0 0 0 345 WNW 1 0 2 4 7 14 36 144. 144 71 18 0 0 0 441 NW 0 2 3 4 7 11 34 187 223 131 26 1 0 0 629 NNW 0 2 2 4 9 15 38 235 175 69 8 1 0 0 558 999 0 0 1 1 0 1 0 1 0 1 11 2 0 60 78 6 22 40 91 212 373 1134 3018 2414 1120 219 22 0 90 8761
CA06012 Rev.0 Page 96 of 283 CC1993.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 2 14 31 10 2 0 0 0 0 60 NNE 0 0 -0 0 0 5 36 55 14 0 0 0 0 0 110 NE 0 0 0 0 0 11 28 13 2 3 0 0 0 0 57 ENE 0 0 0 0 4 6 19 1 0 0 0 0 0 0 30 E 0 0 0 0 1 9 19 4 . 1 0 0 0 0 0 34 ESE 0 0 0 0 0 4 19 6 0 0 0 0 0 0 29 SE 0 0 0 0 0 2 9 16 0 0 0 0 0 0 27 SSE 0 0 0 0 0 0 13 34 7 0 0 0 0 0 54 S 0 0 0 0 0 0 2 7 1 0 0 0 0 0 10 SSW 0 0 0 0 1 1 8 9 3 0 0 0 0 0 22 SW. 0 0 0 0 0 1 4 26 15 0 0 0 0 0 46 WSW 0 0 0 0 0 0 5 14 3 0 0 0 0 0 22 W 0 0 0 0 0 0 1 7 0 1 0 0 0 0 9 WNW 0 0 0 0 0 0 1 11 2 4 0 0 0 0 18 NW 0 0 0 0 0 0 0 24 7 1 0 0 0 0 32 VN`W 0 0 0 0 0 0 3 12 2 0 0 0 0 0 17 999 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 0 0 7 41 181 270 67 11 0 0 0 0 577 CC1993.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 2 3 12 25 4 2 0 0 0 0 48 NNE 0 0 0 0 1 9 23 17 2 1 0 0 0 0 53 NE 0 0 1 0 2 6 11 10 .0 0 1 0 0 0 31 ENE 0 0 0 0 4 1 6 2 1 2 0 0 0 0 16 E 0 0 0 0 1 4 11 1 0 0 0 0 0 0 .17 ESE 0 0 0 0 1 .1 4 3 0 0. 0 0 0 0 9 SE 0 0 0 0 0 4 5 2 1 1 0 0 0 0 13 SSE 0 0 0 1 0 1 11 12 2 0 0 0 0 0 27 S 0 0 0 1 1 0 2 1 0 0 0 0 0 0 5 SSW 0 0 0 0 0 0 3 12 1 1 0 .0 0 0 17 SW 0 0 0 0 0 0 2 11 5 0 0 0 0 0 18 WSW 0 0 0 0 0 1 8 15 1 0 0 0 0 0 25 W 0 0 0 0 0 0 1 2 3 0 0 0 0 0 6 WNW 0 0 0 0 1 0 3 7 5 0 0 0 0 0 16 NW 0 0 0 0 1 0 0 9 10 4 0 0 0 0 24 NNW 0 0 0 0 0 0 0 5 1 1 0 0 0 0 7 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0. 1 2 14 30 102 134 36 12 1 0 0 0 332 CC1993.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 3 12 25 5 1 0 0 0 0 46 NNE 0 0 0 1 0 10 26 12 6 0 .0 0 0 0 55 NE 0 0 0 . 0 2 5 4 14. 11 1 0 0 0 0 37 ENE 0 0 0 0 1 4 5 1 0 3 0 0 0 - 0 14 E 0 0 0 0 2 2 9 0 0 0 0 0 0 0 13 ESE 0 0 0 0 1 1 0 1 0 0 0 0 0 0 3 SE 0 0 0 0 1 1 8 6 .0 0 0 0 0 0 16 SSE 0 0 1 0 0 3 3 20 4 0 0 0 0 0 31 S 0 0 0 0 0 1 1 2 0 0 0 0 0 0 4 SSW 0 0 0 0 0 1 3 7 1 0 0 0 0 0 12 SW 0 0 0 0 2 0 5 16 5 1 0 0 0 0 29 WSW 0 0 0 0 0 2 5 13 3 1 0 0 0 0 24 W 0 0 0 0 1 1 6 3 2 0 0 0 0 0 13 WNW 0 0 0 0 0 1 2 . 6 3 2 0 0 0 0 14 NW 0 0 0 0 0 0 4 10 20 4 0 0 0 0 38 NNW 0 0 0 0 0 0 3 12 4 1 0 0 0 0 20 999 0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 .1 1 10 35 96 148 64 14 0 0 0 0 369
CA 06012 Rev.0 Page 97 of 283 CC1993.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 0 3 15 21 68 120 65 24 0 0 0 0 317 NNE 0 0 0 4 11 44 104 113 41 4 0 0 0 0 321 NE 0 1 2 5 12 28 104 134 87 14 1 0 0 0 388 ENE 0 0 2 3 10 42 82 69 25 6 1 0 0 0 240 E 0 0 3 7 26 40 49 19 0 1 0 0 0 0 145 .ESE 0 1 0 5 16 19 30 13 4 0 0 0 0 0 88 SE 0 3 2 5 10 16 30 41 12 3 0 0 0 0 122 SSE 0 1 1 2 6 12 56 93 22 5 1 0 0 0 199 S 0 1 0 2 5 14 30 65 13 1 0 0 0 0 131 SSW 0 2 0 2 6 11 22 79 33 9 0 0 0 0 164 SW 0 0 2 0 6 12 58 98 51 14 1 0 0 0 242 WSW 0 0 1 2 6 13 58 65 5 1 0 0 0 0 151 W 0 0 1 0 13 9 37 27 15 1 0 0 0 0 103 WNW 0 2 2 2 7 6 21 53 27. 22 0 0 0 0 142 NW 0 0 0 2 6 5 36 66 48 16 0 0 0 0 179 NNW 0 0 1 1 5. 10 43 54 42 6 0 0 0 0 162 999 0 0 1 0 0 0 0 0 0 0 0 0 0 1 2 0 12 18 45 160 302 828 1109 490 127 4 0 0 1 3096 CC1993.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 1 3 12 17 55 67 3 0 0 0 0 0 159 NNE 0 1 0 8 17 36 49 26 3 0 0 0 0 0 140 NE 0 2 1 3 16 16 21 20 10 0 0 0 0 0 89 ENE 0 3 1 4 14 10 27 12 2 0 0 0 0 0 73 E 0 2 4 4 17 23 16 8 0 1 0 0 0 0 75 ESE 0 2 6 9 15 19 13 5 0 0 0 0 0 0 69 SE 1 1 4 6 21 22 19 15 1 0 0 0 0 0 90 SSE 3 0 4 5 *25 25 42 38 24 3 0 0 0 0 169 S 1 2 0 9 24 29 77 95 *22 1 0 0 0 0 260 SSW 2 2 4 8 14 30 83 110 59 3 0 0 0 .0 315 SW 3 2 2 5 16 26 101 179 42 2 0 0 0 0 378 WSW 0 7 4 8 19 25 59 56 8 0 0 0 0 0 186 W 1 5 3 6 18 19 37 18 6. 0 0 0 0 0 113 WNW 1 5 3 17 25 23 39 37 6 2 0 0 0 0 158 NW 1 3 2 4 28 49 74 77 18 2 0. 0 0 0 258 NNW 2 2 3 7 30 48 74 54 8 0 0 0 0 0 228 999 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 15 40 42 107 311 417 786 817 212 14 0 0 0 0 2761 CC19934.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 2 5 3 1 2 3 1 0 1 0 0 0 0 0 18 NNE 0 1 3 6 6 4 6 0 0 0 0 0 .0 0 26 NE .1 1 2 0 1 . 1 3 2 0 0. 0 0 0 0 11 ENE 0 2 0 4 7 2 1 0 0 0 0 0 0 0 16 E 2 0 0 2 5 1 0 0 0 0 0 0 0 0 10 ESE 2 0 2 4 4. 1 0 0 0 0 0 0 0 0 13 SE 2 3 1 2 11 4 3 0 0 0 0 0 0 0 26 SSE 1 5 1 4 8 11 2 1 0 0 0 0 0 0 33 S 0 5 4 8 19 21 24 8 0 0 0 0 0 0 89 SSW 4 5 4 17 30 35 54 14 1 0 0 0 0 0 164 SW 3 4 4 10 24 35 86 24 1 0 0 0 0 0 191 WSW 6 3 4 6 14 20 23 9 0 0 0 0 0 0 85 W 1 2 6 7 13 17 18 1 0 0 0 0 0 0 65 WNW 1 3 3 1 22 14 6 0 0. 0 0 0 0 0 50 NW 0 2 5 6 10 22 17 2 0 0 0 0 0 0 64 NNW 1 1 0 4 1 8 0 0 0 .0 0 0 0 0 15 999 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 26 42 42 82 177 200 244 61 3 0 0 0 0 0 877
CA06012 Rev.0 Page 98 of 283 CC1993.MET JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 1 0 0 0 0 0 0 0 0 0 2 NNE 0 1 1 1 2 0 1 0 0 0 0 0' 0 0 6 NE 0 0 0 0 2 2 0 0 0 0 0 0 0 0 4 ENE 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1 E 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 ESE 0 1 2 0 1 0 0 0 0 0 0 0 0 0 4 SE 0 1 2 2 0 0 2 0 0 0 0 0 0 0 7 SSE 1 6 3 0 6 3 0 0 0 0 0 0 0 0 19 S 1 5 6 2 17 7 6 0 0 0 0 0 0 0 44 SSW 2 5 9 17 26 35 18 1 0 0 0 0 0 0 113 SW 3 3 7 22 49 54 32 7 0 0 0 0 0 0 177 WSW 2 5 12 23 32 21 17 3 0 0 0 0 0 0 115 W 2 4 13 15 16 14 6 0 0 0 0 0 0 0 70 WNW 4 5 4 7 19 13 3 0 0 0 0 0 0 0 55 NW 2 7 3 5 5 3 5 0 0 0 0 0 0 0 30 NNW 0 2 0 1 0 1 0 0 0 0 0 0 0 0 4 999 0.0 0 0 0 0 0 0 0 0 0 0 0 0 0 17 46 62 97 176 153 90 11 0. 0 0 0. 0 0 652 CC1993.MET JOINT FREQUENCY TABLE FOR 10M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 . 7 10 15 20 .30 SO 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 7 7 NNE 0 0 0 1 0 0 0 0 0 0 0 0 0 13 14 NE 0 0 0 0 1 0 1 0 0 0 0 0 0 4 6 ENE 0 0 0 0 0 0 1 1 0 0 0 0 0 2 4 E 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 ESE 0 0 0 0 0 0 0 0 .0 0 0 0 0 1 1 SE 0 0 0 0 0 0 0 0 0 0 0 0 0 7 7 .SSE 0 0 0 0 0 0 0 2 0 0 0 0 0 7 9 S 0 0 0 0 0 0 0 0 0 0 0 0 0 9 .9 SSW 0 0 0 0 1 0 0 0 0 0 0 0 0 3 4 SW 0 0 0 0 1 0 0 0 0 0 0 0 0 2 3 WSW 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 W 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 WNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNW 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 999 0 0 0 1 0 0 0 0 0 0 0 0 0 25 26 0 0 0 2 3 0 2 3 0 0 0 0 0
- 87 97 CC1993.MET JOINT FREQUENCY TABLE FOR 10M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 2 7 4 8 33 49 162 268 58 29 0 0 0 7 657 NNE 0 3 4 21 37 108 245 223 66 5 0 0 0 13 725 NE. 1 4 6 8 36 69 172 193 110 18 2 0 0 4 623 ENE 0 6 3 11 40 65 141 86 28. 11 1 0 0 2 394 E 2 2 7 14 52 79 104 32 1 2 0 0 0 2 297 ESE 2 4 10 18 38 45 66 28 4 0 0 0 0 1 216 SE 3 8 9 15 43 49 76 80 14 4 0 0 0 7 308 SSE 5 12 10 12 45 55 127 200 59 8 1 0 0 7 541 S 2 13 10 22 66 72 142 178 36 2 0 0 0 9 552 SSW 8 14 17 44 78 113 191 232 98 13 0 0 0 3 811 SW 9 9 15 37 98 128 288 361 119 17 1 0 0 2 1084 WSW 8 15 21 39 71 82 175 175 20 2 0 0 0. 2 610 W 4 11 23 28 61 60 106 58 26 2 0 0 0 2 381 WNW 6 15 12 27 74 57 75 114 .43 30 0 0 0 0 453 NW 3 12 10 17 50 79 136 188 103 27 0 0 0 0 625 NNW 3 5 4 13 36 67 123 137 57 8 0 0 0 1 454 999 0 0 1 2 0 1 0 0 0 0 0 0 0 26 30 58 140 166 336 858 1178 2329 2553 872 178 5 0 0 , 88 8761
CA06012 Rev.0 Page 99 of 283 cc1994.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 7 44 19 2 0 0 0 0 72 NNE 0 0 0 1 0 0 17 44 17 5 1 0 0 0 8S NE 0 0 0 0 1 2 5 10 4 1 0 0 0 0 23 ENE 0 0 0 0 0 4 13 5 0 0 0 0 0 0 22 E 0 0 0 0 1 6 20 9 0 0 0 0 0 0 36 ESE 0 0 0 0 0 2 13 24 1 0 0 0 0 0 40 SE 0 0 0 0 1 1 16 34 19 1 0 0 0 0 72 SSE 0 0 0 0 0 1 6 28 22 13 1 0 0 0 71 S 0 0 0 0 0 1 11 12 6 3 0 0 0 0 33 SSW 0 0 0 0 1 2 7 30 22 10 1 0 0 0 73 SW 0 0 0 0 0 1 9 38 25 8 0 0 0 0 81 WSW 0 0 0 0 0 1 4 16 8 2 0 0 0 0 31 W 0 0 0 0 0 1 0 2 3 0 0 0 0 0 6 WNW 0 0 0 0 0 1 1 0 5 12 1 0 0 0 20 NW 0 0 0 0 0 0 1 2 4 6 3 0 0 0 16 NNW 0 0 0 0 0 0 1 1 3 2 0 0 0 0 7 999 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 1 4 23 131 299 158 65 7 0 0 1 689 cc1994.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 7 39 14 0 0 0 0 0 60 NNE 0 0 0 0 0 3 22 23 8 4 0 0 0 0 60 NE 0 0 0 0 0 3 4 7 2 1 0 0 0 0 17 ENE 0 0 0 0 2 5 5 3 0 0 0 0 0 0 15 E 0 0 0 0 0 5 11 3 0 0 0 0 0 0 19 ESE 0 0 0 0 1 3 5 4 0 0 0 0 0 0 13 SE 0 0 0 0 0 2 4 7 5 1 0 d 0 0 19 SSE 0 0 B 0 0 1 3 12 11 5 0 0 0 0 32 S - 0 0 0 0 0 3 1. 3 2 2 0 0 0 0 11 SSW 0 0 0 0 0 0 S 17 16 7 0 0. 0 0 45 SW 0 0 0 0 2 1 5 20 23 17 0 0 0 0 68 WSW 0 0 0 0 0 0 5 14 2 3 0 0 0 0 24 W 0 0 0 0 0 1 4 8 7 3 0 0 0 0 23 WNW 0 0 0 0 0 0 0 2 5 3 2 0 0 0 12 NW 0 0 0 0 0 0 0 0 4 5 3 0 0 0 12 NNW 0 0 0 0 0 0 0 6 8 5 0 0 0 0 19 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 27 81'168 107 56 5 0 0 0 449 cc1994.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 1 0 0 2 9 2S 17 4 10 0 0 0 58 NNE 0 0 0 0 2 3 17 18 8 4 2. 0 0 1 55 NE 0 0 0 0 4 3 7 5 4 0 0 0 0 0 23 ENE 0 0 0 0 2 2 8 6 0 0 0 0 0 .0 .18 E 0 0 0 0 1 4 4 1 0 0 0 0 0 0 10 ESE 0 0 0 1 1 2 6 2 0 0 0 0 0 0 12 SE 0 0 0 0 0 0 3 12 4 0 0 0 0 0 19 SSE 0 0- 0 0 0 1 6 7 6 2 0. 0 0 0 22 S 0 0 0 0 1 0 2 8 1 1 0 0 0 0 13 SSW 0 0 0 0 1 1 7 8 15 3 2 0 0 0 37 SW 0 0 0 0 .0 3 3 24 16 10 0 0 0 0 56 WSW 0 0 0 0 0 1 4 16 4 6 0 0 0 0 31 W 0 0 0 0 0 1 1 7 6 2 0 0 0 0 17 WNW 0 0 0 1 0 0 2 7 11 8 1. 0 0 0 30 NW 0 0 0 0 0 0 1 3 10 14 3 0 0 0 31 NNW 0 0 0 0 0 0 1 10 12 4 0 0 0 0 27 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 2 12 23 81 159 114 58 8 0 0 1 459
CA06012 Rev.0 Page 100 of 283 cc1994.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 2 1 2 3 12 22 86 93 106 17 2 0 11 357 NNE 0 1 1 1 8 14 36 53 81 110 31 4 0 10 350 NE 0 0 1 2 8 7 16 39 57 49 21 3 3 4 210 ENE 0 0 0 0 5 10 16 62 50 7 4 1 0 0 155 E 0 0 0 2 9 11 16 30 7 1 0 0 0 0 76 ESE 0 0 1 0 3 6 13 34 6 1 0 0 0 0 64 SE 0 0 0 2 4 10 16 43 14 8 1 0 0 0 98 SSE 0 0 0 2 1 3 21 66 63 29 1 0 0 0 186 S 1 2 1 3 9 3 14 37 35 11 1 0 0 0 117 SSW 0 0 .0 3 6 4 22 56 70 52 2 0 0 0 215 SW 0 0 0 0 6 7 29 66 74 49 5 0 0 0 236 WSW 0 1 1 1 4 9 20 60 29 10 0 0 0 1 136 W 0 1 1 0 6 7 12 24 22 9 1 1 0 0 84 WNW 0 1 0 4 1 2 13 28 52 32 9 0 0 2 144 NW 0 1 0 2 5 3 11 54 93 87 12 0 0 1 269 NNW 0 0 0 1 7 6 11 64 101 82 12 0 0 4 288 999 0 0 0 0 1 0 0 2 2 3 3 0 0 87 98 1 9 7 25 86 114 288 804 849 646 120 11 3 120 3083 cc1994.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS S 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 4 2 22 41 59 38 11 2 1 0 180 NNE 1 0 0 0 4 4 13 39 27 16 1 0 0 0 105 NE 0 0 0 3 1 1 11 41 5. 2 2 1 1 0 68 ENE 0 0 0 3 4 5 18 16 7 0 0 0 0 0 53 E 0 0 1 3 4 5 19 23 6 0 0 0 0 0 61 ESE 0 1 0 0 5 4 14 21 2 2 0 0 0 0 49 SE 0 0 1 0 3 2 12 38 14 5 0 1. 0 0 76 SSE 0 0 O 1 3 2 11 65 65 19 2 0 0 0 168 S 0 1 1 1 2 5 13 47 154 32 0 0 0 0 256 SSW 1 0 0 1 3 1 10 84 149 113 0 1 0 0 363 SW 0 0 0 0 2 3 20 76 139 88 0 0 0 0 328 WSW 0 1 0 0 4 4 16 54 58 13 0 0 0 0 150 W 0 0 0 1 1 3 15 46 20 3 0 0 0 1 90 WNW 0 0 0 0 3 7 13 45 48 11 2 0 0 3 132 NW 0 1 0 2 2 1 14 67 105 23 1 0 0 0 216 NWe 0. 1 0 0 1 2 14 91 108 17 1 1 0 0 236 999 0 0 0 0 0 1 0 0 0 0 0 0 0 15 16 2 5 3 15 46 52 235 794 966 382 20 6 2 19 2547 cc1994.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 0 0 1 1 5 17 3 2 0 0 0 0 30 NNE 1 0 0 1 0 1 6 8 4 0 0 0 0 0 21 NE 0 0 2 1 1 2 7 5 2 1 0 .0 0 0 21 ENE 0 0 0 0 2 4 8 1 1 0 0 0 0 .0 16 E 0 1 0 2 3 6 3 6 0 0 0 0 0 0 21 ESE 0 0 1 1 2 6 4 7 0 0 0 0 0 0 21 SE 0 1 0 0 1 4 12 16 7 0 0 0 0 0 41 SSE 0 0 1 0 0 3 9 28 30 2 1 0 0 0 74 S 0 0 0 0 2 3 9 26 66 13 0 0 0 0 119 SSW 0 0 0 2 2 2 3 27 105 25 0 0 0 0 166 SW 1 0 0 0 0 1 5 31 37 9 0 0 0 0 84 WSW 0 0 0 2 3 1 S 29 21 2 0 0 0 1 64 W 0 0 0 0 1 1 2 17 13 1 0 0 0 0 35 WNW 0 0 0 0 1 0 3 16 9 1 0 0 0 0 30 NW 1 0 0 0 2 0 5 22 28 5 0 0 0 0 63 NNW 0 0 1 0 4 1 3 19 20 0 0 0 0 0 48 999 0 0 0 0 0 0 0 0 0 . 0 0 0 0 5 5 3 3 5 9 25 36 89 275 346 61 1 0 0 6 859
CA06012 Rev.0 Page 101 of 283 cc1994.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 2 2 1 1 5 11 10 2 0 0 0 0 0 34 NNE 1 1 0 1 0 5 1 4 1 1 0 0 0 0 15 NE 0 0 0 1 3 0 2 2 2 2 0 0 0 0 12 ENE 0 2 1 0 1 1 8 2 0 0 0 0 0 0 15 E 0 0 1 1 1 0 4 1 0 0 0 0 0 0 8 ESE 0 0 0 4 1 3 2 0 0 0 0 0 0 0 10 SE 0 0 0 0 2 4 3 2 2 0 0 0 0 0 13 SSE 1 2 1 0 6 2 4 8 2 1 0 0 0 0 27 S 0 0 0 1 3 4. 13 32 36 5 0 0 0 0 94 SSW 0 0 1 1 2 4 7 35 30 14 0 0 0 0 94 SW 0 1 0 1 3 2 10 27 28 15 0 0 0 0 87 WSW .0 0 1 0 2 5 5 30 18 2 0 0 0 0 63 W 0 0 0 1 2 5 6 25 10 0 0 0 0 0 49 WNW 0 0 0 1 3 4 8 22 8 1 0 0 0 0 47 NW 0 1 0 0 2 4 7 13 11 .1 0 0 0 0 39 NNW 0 0 1 0 2 2 13 15 9 0 0 0 0 0 42 999 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 2 9 8 13 34 50 104 228 159 42 0 0 0 0 649 cc1994.met JOINT.FREQUENCY TABLE FOR 60M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNE 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 NE 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 ENE 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 E 0 0 0 0 0 0 3 0 0 0 0 0 0 0 3 ESE 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 SE 0 0 0 0 1 0 0 0 0 0 0 0 0 1 SSE 0 *0 0 0 0 0 0 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 O. 0 0 0 0 0 0 0 SSW 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 SW 0 0 0 0 0 0 1 1 0 0 0 0 0 0 2 WSW 0 0 0 2 0 0 1 0 0 0 0 0 0 0 3 W 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 WNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NW 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 NNW 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 999 0 0 0 0 1 0 0 0 0 0 0 0 0 7 B 0 0 0 4 2 2 9 1 0 0 0 0 0 7 25 cc1994.met JOINT FREQUENCY TABLE FOR 60M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 5 4 3 9 22 83 262 207 152 28 4 1 11 791 NNE 3 2 1 4 14 30 113 189 146 140. 35 4 0 11 692 NE 0 0 .3 7 18 18 53 109 76 56 23 4 4 4 375 ENE 0 2 1 3 16 31 77. 95 *58 7 4 1 *0 0 295 E 0 1 2 8 19 37 80 73 13 1 0 0 0 0 234 ESE 0 1 2 7 13 26 57 92 9 3 0 0 0 0 210 SE 0 1 1 2 12 23 66 152 . 65 15 1 1 0 0 339 SSE 1 2 2 3 10 13 60 214 199 71 5 0 0 0 580 S 1 3 2 5 17 19 63 165 300 67 1 0 0 0 643 SSW 1 0 1 7 15 14 62 257 407 224. 5 1 0 0 994 SW 1 1 0 1 13 18 82 283 342 196 5 0 0 0 942 WSW 0 2 2 5 13 21 60 219 140 38 0 0 0 2 502 W 0 1 1 2 10 20 40 129 81 18 1 1 0 1 305 WNW 0 1 0 6 8 14 40 120 138 68 15 0 0 5 415 NW 1 3 0 5 11 8 39 161 255 141 22 0 0 1 647 NNW 0 1 2 1 14 12 43 206 261 110 13 1 0 4 668 999 0 0 0 0 2 1 0 2 2 3 3 0 0 115 128 8 26 24 69 214 327 1018 2728 2699 1310 161 17 5 154 8760
CA 06012 Rev.0 Page 102 of 283 cc1994.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 10 9998 9999 N 0 0 0 0 0 0 13 27 3 0 0 0 0 0 43 NNE 0 0 0 0 2 0 33 41 0 0 0 0 0 0 76 NE 0 0 0 0 0 3 18 28- 6 0 0 0 0 0 55 ENE 0 0 0 0 0 7 21 2 0 0 0 0 0 0 30 E 0 0 0 0 0 6 22 3 0 0 0 0 0 0 31 ESE 0 0 0 0 1 2 19 5 0 0 0 0 0 0 27 SE 0 0 0 0 1 2 36 24 3 0 0 0 0 0 66 SSE 0 0 0 0 2 0 18 41 21 1 0 0 0 0 83 S 0 0 0 0 1 0 9 5 6 0 0 0 0 0 21 SSW 0 0 0 0 2 3 13 30 13 1 0 0 0 0 62 SW 0 0 0 0 1 4 23 49 13 2 0 0 0 0 92 WSW 0 0 0 0 0 1 9 16 3 0 0 0 0 0 29 W 0 0 0 0 1 0 1 5 0 0 0 0 0 0 7 WNW 0 0 0 0 0 1 0 3 6 2 0 0 0 0 12 NW 0 0 0 0 0 1 1 5 10 5 0 0 0 0 22 NNW 0 0 0 0 0 0 0 2 3 1 0 0 0 0. 6 999 0 0 0 0 0 1 1 0 0 0 0 0 0 25 27 0 0 0 0 11 31 237 286 87 12 0 0 0 25 689 cc1994.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 13 42 3 0 0 0 0 0 58 .NNE 0 0 0 0 0 6 21 22 0 .0 0 0 0 0 49 NE 0 0 0 0 1 3 15 15 3 0 0 0 0 0 37 ENE 0 0 0 0 1 8 10 1 0 0 0 0 0 0 20 E 0 0 0 0 1 7 10 1 0 0 0 0 0 0 19 ESE 0 0 0 0 3 3 1 1 0 0 0 0 0 0 8 SE 0 0 0 0 0 2 4 6 0 0 0 0 0 0 12 SSE 0 0 0 0 2 2 4 22 6 1 0 0 0 0 37 S 0 0 0 0 1 2 4 3 1 0 0 0 0 0 11 SSW 0 0 0 0 1 2 7 15 15 0 0 0 0 0 40 SW 0 0 0 0 0 2 12 36 16 1 0 0 0 1 68 WSW 0 0 0 0 2 3 11 7 7 1 0 0 0 0 31 W 0 0 0 0 1 2 4 13 3 0 0 0 0 0 23 WNW 0 0 0 0 0 0 0 5 3 1 0 0 0 0 9 NW 0 0 0 0 0 0 0 4 3 4 0 0 0 0 11 NNW 0 0 0 0 0 0 0 4 7 0 0 0 0 . 0 11 999 0 0 0 0 0 0 0 0 0 0 0 0 0 5 5 0 0 0 0 13 42 116 197 67 8 0 0 0 6 449 cc1994.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 1 12 33 5
- 0 0 0 0 0 51 NNE 0 0 .0 0 2 5 28 18 2 0 0 0 0 0 55 NE 0 .0 0 0 4 4 .17 11 3 *0 0 0 0 .0 39 ENE 0 0 0 0 1 1. 14 5 0 0 0 *0 0 0 21 E 0 0 0 1 3 2 7 0 0 *0 0 0 0 0 13 ESE 0 0 1 0 1 1 4 0 0 0 0 0 0 0 7 SE 0 0 0 0 2 0 6 5 0 0 0 0 0 0 13 SSE 0 0 0 0 1 3 7 15 3 0 0 0 0 0 29 S 0 0 0 0 2 2 4 5 0 0 0 0 0 0 13 SSW 0 0 0 0 0 1 6 14 5 1 0 0 0 0 27 SW 0 0 0 0 2 3 14 34 14 1 0 0 0 0 68 WSW 0 0 0 0 0 2 9 13 3 0 0 0 0 0 27 W 0 0 0 0 0 2 1 11 5 0 0 0 0 0 19 WNW 0 0 0 0 0 .0 4 15 5 0 0 0. 0 0 24 NW 0 0 0 0 0 0 0 14 16 3 0 0 0 0 33 NNW 0 0 1 0 0 1 2 7 2 1 .0 0 0 0 14 999 0 0 0 0 0 0 0 0 0 0 0 0 0 6 6 0 0 .2 1 18 28 135 200 63 6 0 0 0 6 459
CA06012 Rev.0 Page 103 of 283 cc1994 .met JOINT FREQUENCY TABLE FOR 1OM AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 5 12 15 57 166 76 8 1 0 0 1 341 NNE 0 0 1 3 12 28 68 135 49 3 0 0 0 6 305 NE 0 0 1 1 9 20 48 118 85 14 3 1 0 4 304 ENE 0 0 0 .2 9 12 57 99 18 7 1 0 0 0 205 E 0 1 1 10 17 15 27 14 0 0 0 0 0 0 85 ESE 0 1 1 3 6 14 20 11 0 0 0 0 0 0 56 SE 0 0 0 6 7 16 25 10 2 0 0 0 0 1 67 SSE 0 2 3 5 14 6 54 80 26 0 0 0 0 0 190 S 0 2 2 2 6 13 30 45 8 1 0 0 0 0 109 SSW 0 3 2 5 9 13 43 95 43 2 0 0 0 2 217 SW 1 2 2 7 15 21 57 113 56 8 0 0 0 0 282 WSW 0 1 1 5 9 18 36 51 11 1 0 0 0 1 134 W 0 0 0 4 8 7 31 24 5 2 0 0 0 0 81 WNW 0 0 1 7 5 14 25 57 22 9 0 0 0 0 140 NW 1 0 2 8 10 7 29 106 63 12 0 0 0 0 238 NNW 0 1 1 4 9 8 60 126 61 3 0 0 0 0 273 999 0 1 0 0 1 0 1 5 5 0 0 0 0 43 56 2 14 18 77 158 227 668 1255 530 70 5 1 0 58 3083 cc1994.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 1 4 12 19 57 68 20 5 1 0 0 0 188 NNE 1 0 2 4 16 21 44 22 1 0 0 0 0 0 111 NE 0 5 2 2 7 7 20 13 3 1 0 0 0 0 60 ENE 0 1 1 4 10 10 20 3 0 1 0 1 0 0 51 E 0 4 0 3 14 11 10 5 0 0 0 0 0 0 47 ESE 1 5 2 9 16 9 8 1 0 0 0 0 0 0 51 SE 2 4 2 9 12 13 12 5 0 1 0 0 0 0 60 SSE' 1 4 3 4 19 24 30 24 5 2 0 0 0 1 117 S 1 1 4 9 11 24 77 88 10 0 0 0 0 0 225 SSW 1 4 4 10 20 34 115 145 44 3 0 0 0 0 380 SW 1 2 4 9 19 43 118 185 50 1 0 0 0 0 432 WSW 3 4 5 8 13 18 52 58 4 0 0 0 0 0 165 W 1 4 5 11 16 22 22 8 1 0 0 0 0 0 90 WNW 0 2 4 6 16 22 24 35 5 2 0 0 0 0 116 NW 0 1 0 5 24 33 90 71 9 1 0 0 0 0 234 NNW 0 2 3 6 19 26 63 44 0 0 0 0 0 0 163 999 0 0 0 0 0 1 0 0 0 0 0 0 0 56 57 12 44 42 103 244 337 762 775 152 17 1 1 0. 57 2547 cc1994.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 1 5 6 4 5 2 0 0 0 0 0 0 23 NNE 2 0 2 4 8 4 3 2 0 0 0 0 0 0 25 NE 0 1 0 1 5 2 1 1 0. 0 0 0 0 0 11 ENE 0 1 1 1 6 5 1 0 0 0 0 0 0 0 15 E 0 1 1 4 4 2 1 0 0 0 0 0 0 0 13 ESE 0 2 2 2 2 0 0 0 0 0 0 0 0 0 8 SE 2 2 0 6 5 3 1 0 0 0 0 0 0 0 19 SSE 1 5 1 9 14 9 10 0 1 0 0 0 0 0 50 S 1 3 6 7 13 20 26 6 0 0 0 0 0 0 82 SSW 0 4 3 9 28 39 91 37 0 0 0 0 0 0 211 SW 0 3 3 7 14 33 66 27 0 0 0 0 0 0 153 WSW 1 2 3 4 12 18 19 5 0 0 0 0 0 0 64 W 3 3 4 4 10 12 6 0 0 0 0 0 0 0 42 WNW 1 1 2 6 16 15 10 0 0 0 0 0 0 0 51 NW 1 0 0 5 8 12 32 5 0 0 0 0 0 0 63 NNW 2 2 0 0 3 5 1 0 0 0 0 0 0 0 13 999 0 0 1 0 0 0 0 0 0 0 0 0 0 15 16 14 30 30 74 154 183 273 8s 1 0 0 0 0 15 859
CA06012 Rev.0 Page 104 of 283 cc1994.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 0 0 1 1 1 0 0 0 0 0 0 0 4 NNE 0 0 1 4 0 4 6 1 0 0 0 0 0 0 16 NE 0 0 0 1 1 2 0 0 0 0 0 0 0 0 4 ENE 0 0 2 2 0 1 0 0 0 0 0 0 0 0 5 E 1 2 0 2 2 0 0 0 0 0 0 0 0 0 7 ESE 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 SE 1 1 0 0 0 1 1 0 0 0 0 0 0 0 4 SSE 0 2 4 2 2 3 2 0 0 0 0 0 0 0 15 S 1 1 4 2 15 7 14 0 0 0 0 0 0 0 44 SSW 1 2 2 14 31 27 31 6 0 0 .0 0 0 0 114 SW 2 6 7 16 47 35 45 21 0 0 0 0 0 0 179 WSW 0 2 8 25 24 13 14 0 0 0 0 0 0 0 86 W 3 4 6 15 32 14 4 0 0. 0 0 0 0 0 78 WNW 1 2 4 7 15 14 6 0 0 0 0 0 0 0 49 NW 1 0 0 0 3 6 7 0 0 0 0 0 0 0 17 NNW 0 0 1 0 2 0 0 0 0 0 0 0 0 0 3 999 0 0 0 0 0 0 0 0 0 0 0 0 0 23 23 11 23 39 90 175 129 131 28 0 0 0 0 0 23 649 cc1994.met JOINT FREQUENCY TABLE FOR 10M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNE 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 NE 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 ENE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 '0 E 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ESE 0 0 0 0 0 0 0, 0 0 0 0 0 0 0 0 SE 0 0 1 0 0 0 0 0 0 0 0 0 0 0 1 'SSE 0 0 0 0 0 0. 0 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSW 0 0 0 0 0 0 0 0.0 0 0 0 0 0 0 SW 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 WSW 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 W 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNW. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 999 0 0 0 0 0 0 0 0 0 0 0 0 0 20 20 0 0 1 1 2 0 1 0 0 0 0 0 0 20 25 cc1994.met JOINT FREQUENCY TABLE FOR 10M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 2 2 14 31 40 158 338 107 13 2 0 0 1 708 NNE 3 0 6. 15 40 68 204 241 .52 3 0 0 0 6 638 NE 0 6 3 6 27 41 119 186 100 15 3 1 0 4 511 ENE 0 2 4 9 27 44 123 110 18 8- .1 1 0 0 347 E 1 8 2 20 41 43 77 23 0 0 *0 0 0 0 215 ESE 1 8 6 14 29 30 52 18 0 0 0 0 0 0 158 SE 5 7 3 21 27 37 85 50 5 1 0 0 0 1 242 SSE 2 13 11 20 54 47 125 182 62 4 0 0 0 1 521 S 3 7 16 20 49 68 164 152 25 1 0 0 0 0 505 SSW 2 13 11 38 91 119 306 342 120 7 0 0 0 2 1051 SW 4 13 16 39 99 141 335 465 149 13 0 0 0 1 1275 WSW 4 9 17 42 61 73 150 150 28 2 0 0 0 1 537 W 7 11 15 34 68 59 69 61 14 2 0 0 0 0 340 WNW 2 5 11 26 52 66 69 115 41 14 0 0 0 0 401 NW 3 1 2 18 45 59 159 205 101 25 0 0 0 0618 NNW 2 5 6 10 33 40 126 183 73 5 0 0 0 0 483 999 0 1 1 0 1 2 2 5 S 0 0 0 0 193 210 39 111 132 346 775 977 2323 2826 900 113 6 2 0 210 8760
CA06012 Rev.0 Page 105 of 283 ccl995.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 3 33 18 9 0 0 0 0 63 NNE 0 0 0 0 0 2 5 34 26 4 0 0 0 0 71 NE 0 0 0 0 1 1 3 8 5 5 0 0 0 0 23 ENE 0 0 0 1 0 2 6 1 0 0 0 0 0 0 10 E 0 0 0 0 1 5 19 9 0 .0 0 0 0 0 34 ESE 0 0 0 0 1 4 12 11 0 0 0 0 0 0 28 SE 0 0 0 0 1 1 8 34 6 5 0 0 0 0 55 SSE 0 0 0 0 0 1 6 41 16 3 0 0 0 0 67 S 0 0 0 0 1 0 6 10 3 0 0 0 0 0 20 SSW 0 0 0 0 0 2 5 21 11 1 0 0 0 0 40 SW 0 0 0 0 0 2 8 32 24 4 0 0 0 0 70 WSW 0 0 0 0 0 1 1 11 14 3 0 0 0 0 30 W 0 0 0 0 0 0 4 ' 8 5 5 0 0 0 0 22 WNW 0 0 0 0 0 1 1 8 24 12 3 0 0 0 49 NW 0 0 0 0 0 0 1 0 13 10 0 0 0 0 24 NNW 0 0 0 0 0 0 0 1 1 2 0 0 0 0 4 999 0 0 0 0 2 0 2 4 5 0 0 0 0 2 15 0 0 0 1 7 22 90 266 171 63 3 0 0 2 625 cc1995.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 0 0 0 0 0 5 29 17 4 0 0 0 0 56 NNE 0 0 0 1 0 1 14 33 5 4 0 0 0 0 58 NE 0 0 0 0 0 2 14 6 7 0 0 0 0 0 29 ENE 0 0 0 0 0 1 3 2 0 0 0 0 0 0 6 E 0 0 0 0 1 3 9 3 0 0 0 0 0 0 16 ESE 0 0 0 0 0 0 2 2 1 0 0 0 0 0 5 SE 0 0 0 0 0 2 3 3 1 1 0 0 0 0 10 SSE 0 0 0 0 0 1 5 22 5 2 1 0 0 0 36 S 0 0 0 0 2 0 2 5 1 0 0 0 0 0 10 SSW 0 0 0 0 0 1 3 .8 7 10 0 0. 0 0 29 SW 0 0 0 0 0 1 9 20 9 5 2 0 0 0 46 WSW 0 0 0 0 1 0 1 7 10 4 1 0 0 0 24 W 0 0 0 0 0 1 0 7 3 2 0 0 0 0 13 WNW 0 0 0 0 0 0 1 13 11 9 5 0 0 0 39 NW 0 0 0 0 0 0 2 12 6 8 2 0 0 0 30 NNW 0 0 0 0 0 0 2 5 6 3 0 0 0 0 16 999 0 0 0 0 0 1 2 2 2 1 0 0 0 1 9 1 0 0 1 4 14 77 179 91 53 11 0 0 1 432 ccl995.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 1 10 34 13 3 0 0 0 0 61 NNE 0 0 0 0 0 3 10 30 7 5 2 0 0 0 57 NE 0 0 0 .0 1 4 11 11 3 3 0 0 0 0 33 ENE 0 0 0 0 0 5 11 2 0 0 0 0 0 0 18 E 0 0 0 0 2 2 7 4 1 0 0 0 0 0 16 ESE 0 0 0 0 1 3 9 4 0 0 0 0 0 0 17 SE 0 0 0 0 0 0 4 6 0 2 0 0 0 0 12 SSE 0 0 0 0 0 2 3 19 8 6 0 0 0 0 38 S 0 0 0 0 0 3 1 9 2 0 0 0 0 0 15 SSW 0 0 0 0 0 2 5 11 12 4 0 0 0 0 34 SW 0 0 0 0 0 3 8 17 8 3 1 0 0 0 40 WSW 0 0 0 1 0 1 4 9 9 4 1 0 0 0 29. W 0 0 0 0 0 1 1 4 6 2 1 0 0 0 15 WNW 0 0 0 0 0 2 2 10 8 5 0 0 0 0 27 NW 0 0 0 0 0 0 2 11 9 12 3 0 0 0 37 NNW 0 0 0 0 0 0 1 8. 6 0 0 0 0 0 is 999 0 0 0 0 1 1 2 3 0 0 0 0 0 0 7 0 0 0 1 5 33 91 192 92 49 8 0 0 0 471
CA06012 Rev.0 Page 106 of 283 ccl995.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 1 3 10 21 44 104 92 83 6 0 0 0 365 NNE 0 1 0 0 6 16 59 84 80 75 21 0 0 0 342 NE 1 0 1 2 7 15 31 60 86 54 8 0 0 0 265 ENE 0 0 2 0 12 15 44 83 46 15 0. 0 0 0 217 E 0 0 0 7 8 15 33 53 28 3 0 0 0 0 147 ESE 0 0 1 3 1 5 23 45 14 0 0 0 0 0 92 SE 0 0 0 2 6 5 25 38 13 7 0 0 0 0 96 SSE 0 1 0 2 0 2 34 88 71 52 8 2 0 0 260 S 0 0 0 1 3 2 19 46 23 9 0 0 0 0 103 SSW 0 0 0 1 1 4 5 42 47 48 4 0 0 0 152 SW 0 0 1 0 6 8 19 58 52 32 4 0 0 0 180 WSW 0 0 0 2 8 7 20 43 32 15 1 0 0 0 128 W 0 0 0 4 9 7 14 33 24 13 1 0 0 0 105 WNW 0 0 0 2 6 9 17 64 70 61 18 1 0 0 248 NW 0 0 0 0 5 7 10 79 130 94 6 0 0 0 331 NNW 0 a 0 4 2 4 20 87 100 52 6 0 0 0 276 999 0 0 2 0 2 4 7 14 12 11 5 0 0 12 69 1 4 8 33 92 146 424 1021 920 624 88 3 0 12 3376 ccl995.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 4 9 12 51 46 26 5 0 0 0 154 NNE 0 2 1 1 0 4 13 35 15 16 2 0 0 0 89 NE 0 0 1 1 3 4 8 18 10 2 0 0 0 0 47 ENE 0 1 1 2 4 3 18 21 5 0 0 0 0 0 55 E 0 1 0 0 8 12 28 28 2 0 0 0 0 0 79 ESE 0 3 1 4 5 3 20 40 1 1 0 0 0 0 78 SE 0 0 0 1 6 4 18 58 12 2 0 0 0 0 101 SSE 0 0 0 1 6 4 8 59 *56 19 4 0 0 0 157 S 0 .0 0 1 2 2 9 81 114 50 0 0 0 0 259 SSW 1 0 0 1 3 4 8 46 113 66 2 0 0 0 244 SW 0 1 1 1 1 7 18 *61 129 65 3 0 0 1 288 WSW 0 0 0 0 2 4 9 28 44 11. 0 0 0 0 98 W 0 2 1 0 7 5 15 37 35 2 1 0 0 0 105 WNW 0 0 0 0 3 2 14 65 72 8 0 0 0 0 164 ITel 0 0 1 1 0 3 11 105 .83 12 0 0 0 0 216 NNW 0 0 0 0 2 6 9 76 67 13 0 0 0 0 173 999 0 0 0 2 1 1 6 38 14 0 0 0 0 8 70 1 10 7 17 57 77 224 847 818 293 17 0 0 9 2377 ccl995.net JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 0 0 0 4 7 16 8 6 0 0 0 0 42 NNE 1 1 0 0 1 3 2 13 2 0 0 0 0 0 23 NE 0 1 0 0 0 2 7 7 1 0 0 0 0 0 18
- ENE 0 0 1 .1 2 3 5 2 0 0 0 0 0 0 14 E 1 0 0 1 4 4 3 3 -0 0 0 0 0 0 16 ESE 0 2 1 0 0 2 5 4 0 1 0 0 0 0 15 SE 0 0 0 1 3 2 6 16 2 0 0 0 0 0 30 SSE 0 0 1 0 4 1 11 24 16 1 0 0 0 0 58 S 0 0 0 1 4 2 7 35 55 4 0 0 0 0 108 SSW 0 0 2 2 1 3 10 29 58 2 0 0 0 0 107 SW 0 0 0 0 2 2 5 43 65 8 0 0 0 0 125 WSW 0 0 1 0 2 2 5 24 20 4 0 0 0 0 58 W 0 0 2 2 2 1 9 24 21 0 0 0 0 0 61 WNW 0 4 0 0 0 2 7 22 19 2 0 0 0 0 56 NW 1 1 0 2 0 0 6 27 27 4 0 0 0 0 68 NNW 0 0 0 0 3 2 10 34 8 0 0 0 0 0 57 999 0 0 0 1 0 0 6 8 3 0 0 0 0 1 19 3 10 8 11 28 35 111 331 305 32 0 0 0 1 875
CA06012 Rev.0 Page 107 of 283 cc1995.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 0 2 2 *2 3 4 0 0 0 0 0 0 14 NNE 0 0 0 0 2 1 1 1 1 0 0 0 0 0 6 NE 0 0. 0 1 5 1. 0 2 1 0 0 0 0 0 10 ENE 0 0 1 2 1 2 5 0 0 0 0 0 0 0 11 E 1 0 2 1 6 4 2 0 0 0 0 0 0 0 16 ESE 0 0 0 1 3 2 4 0 0 0 0 0 0 0 10 SE 0 0 0 0 4 6 2 5 0 0 0 0 0 0 17 SSE 0 0 1 3 3 3 7 9 14 0 0 0 0 0 40 S 0 0 0 0 1 2 7 27 ,34 0 0 0 0 0 71 SSW 0 1 0 1 2 1 5 33 51 6 0 0 0 0 100 SW 0 0 0 2 1 1 12 29 19' 4 0 0 0 0 68 WSW 0 0 0 0 0 0 6 27 17 1 0 0 0 0 51 W 0 1 0 0 1 1 4 13 14 2 0 0 0 1 37 WNW 0 0 1 2 1 0 9 15 12 0 0 0 0 0 40 NW 0 1 0 0 1 0 8 12 10 1 0 0 0 0 33 NNW 0 0 0 0 1 1 5 9 3 0 0 0 0 0 19 999 0 0 0 1 0 0 1 4 0 0 0 0 0 3 9 1 4 5 16 34 27 81 190 176 14 0 0 0 4 552 ccl995.met JOINT FREQUENCY TABLE FOR 60M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ENE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 E 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ESE 0 0 0 0 0 0 0 0 0- 0 0 0 0 0 0 SE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 SW 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 WSW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 WNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NW 0 0 0 0 0 0 0 2 0 .0 0 0 0 0 2 NNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 999 0 0 0 0 0 0 0 0 0 0 0 0 0 48 48 0 0 0 0 1 . 0 1 2 0 0 0 0 0 48 52 ccl995.met JOINT FREQUENCY TABLE FOR 60M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 3 1 6 16 37 84 271 194 131 11 0 0 0 755 NNE 1 4 1 2 9 30 104 230 136 104 25 0 0 0 646 NE 1. 1 2 4 17 29 74 112 113 64 8 0 0 0 425 ENE 0 1 5 6 19 31 92 111 51 .15 0 0 0 0 331 E 2 1 2 9 30 45 101 100 31 3 0 0 0 0 324 ESE 0 5 3 8 11 19 75 106 16 2 0 0 0 0 245 SE 0 0 0 4 20 20 66 160 34 17 0 0 0 0 321 SSE 0 1 2 6 13 14 74 262 186 83. 13 2 0 0 656 S 0 0 0 3 13 11 51 213 232 63 0 0 0 0 586 SSW 1 1 2 5 7 17 41 190 299 137 6 0 0 0 706 SW 0 1 2 3 11 .24 79 260 306 121 10 0 0 1 818 WSW 0 0 1 3 13 15 46 149 146 42 3 0 0 0 418 W 0 3 3 6 19 16 48 126 108 26 3 0 0 1 359 WNW 0 4 1 4 10 16 51 197 216 97 26 1 0 0 623 N' 1 2 1 3 6 10 40 248 278 141 11 0 0 0 741 NNW 0 1 0 4 8 13 47 220 191 70 6 0 0 0 560 999 0 0 2 4 6 7 26 73 36 12 5 0 0 75 246 7 28 28 80 228 354 1099 3028 2573 1128 127 3 0 77 8760
CA 06012 Rev.0 Page 108 of 283 ccl995.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 1 2 32 6 0 0 0 0 0 41 NNE 0 0 0 0 0 1 17 47 5 0 0 0 0 0 70 NE 0 0 0 0 0. 3 9 17 8 0 0 0 0 0 .37 ENE 0 0 0 0 0 2 12 3 0 0 0 0 *0 0 17 E 0 0 0 0 0 5 18 6 0 0 0 0 0 0 29 ESE 0 0 0 0 2 5 17 1 0 0 0 0 0 0 25 SE 0 0 0 0 0 3 19 40 5 0 0 0 0 0 67 SSE 0 0 0 0 1 1 13 42 6 0 0 0 0 0 63 S 0 0 0 0 2 0 7 10 1 0 0. 0 0 0 20 SSW 0 0 0 0 3 4 12 25 2 0 0 0 0 0 46 SW 0 0 0 0 1 3 14 35 12 0 0 0 0 0 65 WSW 0 0 0 0 0 1 9 16 5 0 0 0 0 0 31 W 0 0 0 0 0 2 4 13 6 0 0 0 0 0 25 WNW 0 0 1 0 0 0 3 24 12 2 0 0 0 0 42 NW 0 0 0 0. 0 1 1 12 16 1 0 0 0 0 31 NNW 0 0 0 0 1 0 0 4 .1 0 0 0 0 0 6 999 0 0 0 0 2 0 0 0 0 0 0 0 0 8 10 0 0 1 0 12 32 157 327 85 3 0 0 0 8 625 cc1995.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 l 11 36 6 0 0 0 0 0 54 NNE 0 0 0 0 0 3 22 17 3 0 0 0 0 0 45 NE 0 0 0 0 1 2 25 20 0 0 0 0 0 0 48 ENE 0 0 0 0 0 2 8 3 1 0 0 0 0 0 14 E 0 0 0 0 0 4 9 0 0 0 0 0 0 0 13 ESE 0 0 0 0 1 2 2 1 0 0 0 0 0 0 6 SE 0 0 0 0 0 2 8 5 1 0 0 0 0 0 16 SSE 0 0 0 0 0 2 14 12 7 0 0 0 0 0 35 S 0 0 0 0 1 0 4 4 0 0 0 .0 0 0 9 SSW 0 0 0 0 1 4 6 7 11 0 0 0 0 .0 29 SW 0 0 0 1 0 2 17 18 8 2 0 0 0 0 48 WSW 0 0 0 0 0 0 6 9 3 3 0 0 0 0 21 W 0 0 0 0 0 0 2 9 .4 0 0 0 0 0 15 WNW 0 0 0 0 0 0 5 14 8 3 0 0 0 0 30 NW 0 0 0 0 0 1 2 17 9 6 0 0 0 0 35 NNW 0 0 0 0 0 0 2 5 4 0 0 0 0 0 11 999 0 0 0 0 0 0 0 0 0 0 0 0 0 3 .3 0 0 0 1 4 25 143 177 65 14 0 0 0 3 432 cc1995.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 14 39 3 0 0 0 0 0 56 NNE 0 0 0 0 1 3 19 19 4 0 0 0 0 0 46 NEZ 0 0 0 0 2 5 16 17 3 0 0 0 0 0 43 ENE 0 0 0. 0 3 4 i5 5 0 0 0 0 0 0 27 E 0 0 0 0 2 6 8 2 0 0 0 0 0 0 i8 ESE 0 0 0 0 1 4 9 1 1 0 0 0 0 .0 16 SE 0 0 0 0 1 3 4 6 1 0 0 0 0 *0 15. SSE 0 0 0 0 0 1 8 18 5 1 0 0 0 0 33 S 0 0 0 0 2 1 4 09 1 0 0 0 0 0 17 SSW 0 0 0 0 0 2 8 18 5 0.0 0 0 0 33 SW 0 0 0 1 1 3 16 19 3 1 0 0 0 0 44 WSW 0 0 0 0 1 1 6 15 5 1 0 0 0 0 29 W 0 0 0 0 1 1 4 3 3 1 0 0 0 0 13 WNW 0 0 0 0 1 1 4 12 4 0 0 0 0 0 22 NW 0 0 0 0 0 1 6 13.14 3 0 0 0 0 37 NNW 0 0 0 0 0 2 3 13 2 0 0 0 0 0 20 999 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 0 0 0 1 16 38 144 209 54 7 0 0 0 2 471
CA 06012 Rev.0 Page 109 of 283 cc1995.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 2 3 3 7 26 105 173 65 5 0 0 0 0 389 NNE 0 0 0 3 16 31 90 112 25 1 0 0 0 1 279 NE 0 0 0 2 10 19 69 157 63 1 0 0 0 0 321 ENE 0 0 1 3 14 35 100 103 11 0 0 0 0 0 267 E 0 0 2 7 17 30 50 34 1 0 0 0 0 0 141 ESE 0 0 3 4 18 22 37 14 0 0 0 0 0 0 98 SE 0 0 1 3 10 22. 24 21 3 0 0 0 0 0 84 SSE 0 1 0 5 9 19 67 88 55 8 1 0 0 0 253 S 1 1 0 2 8 15 47 47. .9 0 0 0 0 0 130 SSW 0 1 3 3 6 6 32 52 41 6 0 0 0 1 151 SW 0 0 2 1 6 22 49 83 34 4 0 0 0 1 202 WSW 0 1 1 3 12 11 33 56 12 2 0 0 0 0 131 W 0 0 2 6 10 20 18 49 9 1 0 0 0 1 116 WNW 0 0 1 1 20 14 31 94 41 18 0 0 0 0 220 NW 0 1 1 1 9 12 59 135 77 10 0 0 0 0 305 NNW 0 0 2 3 9 14 60 141 22 2 0 0 0 0 253 999 0 0 0 1 1 0 1 8 10 5 0 0 0 10 36 1 7 22 51 182 318 872 1367 478 63 1 0 0 14 3376 cc1995.met JOINT FREQUENCY TABLE FOR IOM AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N. 0 1 1 8 17 15 35 64 8 1 0 0 0 0 150 NNE 0 2 0 2 12 16 30 25 3 0 0 0 0 0 90 NE 0 2 1 4 5 3 14 9 2. 0 0 0 0 0 40 ENE 0 0 1 3 7 13 19 8 0 0 0 0 0 0 51 E 1 0 2 11 30 13 16 2 0 0 0 0 0 0 75 ESE 0 0 8 9 13 16 15 3 1 0 0 0 0 0 65 SE 0 3 5 6 25 21 13 6 0 0 0 0 0 0 79 SSE 0 2 2 12 26 25 31 41 11 2 0 0 0 0 152 S 1 1 7 14 18 23 91 103 12 0 0 0 0 0 270 SSW 0 3 5 12 22 26 76 110 31 3 0 0 0 0 288 SW 0 2 3 5 15 26 82 169 30 0 0 0 0 0 332 WSW 1 3 4 8 18 20 48 26 2 0 0 0 0. 0 130 W 0 3 3 10 20 23 35 25 3 0 0 0 0 0 122 WNW 1 3 3 8 21 22 56 44 2 1 0 0 0 0 161 NW 1 1 4 9 18 29 91 58 3 0 0 0 0 0 214 NNW 1 2 2 6 11 19 68 36 0 0 0 0 0 0 145 999 0 0 0 1 0 0 0 1 0 0 0 0 0 11 13 6 28 51 128 278 310 720 730 108 7 0 0 0 11 2377 ccl995.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 2 6 4 3 9 0 0 0 0 0 0 24 NNE 0 3 1 1 4 11 7 1 1 0 0 0 0 0 29 .NE 1 0 2 7 3 3 2 0 0 0 0 0 0 0 18 ENE 0 0 2 2 0 4 7 0 0 0 0 0 0 0 15 E 0 2 0 2 1 2 0 0 0 0 0 0 0 0 7 ESE 0 3 4 3 4 1 1 0. 0 0 0 0 0 0 16 SE 0 3 4 1 7 4 0 0 0 0 0 0 0 0 19 SSE 0 0 0 6 11 10 7 1 0. 0 0 0 0 0 35 S 0 3 5 11 31 28 28 1 0 0 0 0 0 0 107 SSW 1 5 9 8 18 34 69 6 0 0 0 0 0 0 150 SW 2 3 2 9 16 31 85 18 0 0 0 0 0 0 166 WSW 2 2 3 5 17 21 26 5 0 0 0 0 0 0 81 W 0 1 2 6 11 11 11 0 0 .0 0 0 0 0 42 WNW 1 6 2 7 21 26 16- 2 0 0 0 0 0 0 81 NW 0 1 2 2 13 16 21 2 0 0 0 0 0 0 57 NNW 0 2 3 3 5 3 1 0 0 0 0 0 0 0 17 999 0 0 0 0 0 0 0 0 0 0 0 0 0 11 11 7 34 41 75 168 209 284 45 1 0 0 0 0 11 875
CA 06012 Rev.0 Page 110 of 283 cc1995.tmet JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 2 0 0 1 2 0 0 1 0 0 0 0 0 0 6 NNE 0 1 0 0 0 1 1 0 0 0 0 0 0 0 3 NE 0 1 0 .0 2 0 0 0 0 0 0 0 .0 0 3 ENE 0 2 1 0 1 0 0 0 0 0 0 0 0 0 4 E 1 0 0 1 0 0 0 0 0 0 0 0 0 0 2 ESE 0 0 0 1 1 0 0 0 0 0 0 0 0 0 2 SE 1 0 1 0 2 0 1 0 0 0 0 .0 0 0 5 SSE 0 2 1 8 5 5 0 0 0 0 0 0 0 0 21 S 0 2 2 9 15 24 15 0 0 0 0 0 0 0 67 SSW 1 5 2 10 26 42 40 1 0 0 0 0 0 0 127 SW 2 4 5 12 20 44 45 2 0 0 0 0 0 0 134 WSW 1 3 5 10 13 28 16 0 0 0 0 0 0 0 76 W 0 3 3 13 17 19 6 1 0 0 0 0 0 0 62 WNW 0 3 0 1 8 10 6 0 0 0 0 0 0 0 28 NW 0 0 0 0 3 1 3 0 0 0 0 0 0 0 7 NNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 999 0 1 0 0 0 0 0 0 0 0 0 0 0 4 5 8 27 20 66 115 174 133 5 0 0 0 0 0 4 552 ccl99S.m~et JOINT FREQUENCY TABLE FOR 10M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ENE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 E 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ESE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSW 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 SW 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 WSW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 WNW 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 NW 0 0 0 0 1 1. 1 0 0 0 0 0 0 0 3 NNW 0 0 0 1 1 0 0 0 0 0 0 0 0 0 2 999 0 0 0 0 0 0 0 0 0 0 0 0 0 44 44 0 0 0 1 4 2 1 0 0 0 0 0 0 44 52 ccl995.met JOINT FREQUENCY TABLE FOR 10M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 2 3 4 14 32 47 170 354 88 6 0 0 . 0 0 720 NNE 0 6 1 6 33 66 186 221 41 1 0 0 0 1 562 NE 1 3 3 13 23 35 135 220 76 1 0 0 0 0 510 ENE 0 . 2 5 8 25 60 161 122 12 0 0 0 0 0 395 E 2 2 4 21 50 60 101 44 1 0 0 0 0 0 285 ESE 0 3 15 17 40 50 81 -20 2 0 0 0 0 0 228 SE 1 6 11 10 45 55 69 78 10 0 0 0 0 0 285 SSE 0 5 3 31 52 63 140 202 84 11 1 0 0 0 592 S 2 7 14 36 77 91 196 174 23 0 0 0 0 0 620 SSW 2 14 19 33 77 118 243 219 90 9 0 0 0 1 825 SW 4 9 12 29 59 131 308 344 87 7 0 0 0 1 991 WSW 4 9 13 26 61 82 144 127 27 6 0 0 0 0 499 W 0 7 10 35 60 76 80 100 25 2 0 0 0 1 396 WNW 2 12 7 17 71 74 121 190 67 24 0 0 0 0 585 NW 1 3 7 12 44 62 184 237 119 20 0 0 0 0 689 NNW 1 4 7 13 27 38 134 199 29 2 0 0 0 0 454 999 0 1 0 2 3 0 1 9 10 5 0 0 0 93 124 22 96 135 323 779 1108 2454 2860 791 94 1 0 0 97 8760
CA06012 Rev.0 Page 111 of 283 cc1996.met JOINT FREQUENCY TABLE FOR 60M AND STAB3ILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 S 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 3 20 14 1 1 0 0 0 39 NNE 0 0 0 0 1 0 6 24 16 4 1 0 0 0 52 NE 0 0 .0 0 2 2 5 14 0 1 0 0 0 0 24 ENE 0 0 0 0 0 2 5 0 0 0 0 0 0 0 7 E 0 0 0 0 0 2 .5 2 0 0 0 0 0 3 12 ESE 0 0 0 0 0 0 1 10 0 0 0 0 0 0 11 SE 0 0 0 0 1 0 0 21 10 1 0 0 0 0 33 SSE 0 0 0 0 0 1 5 15 17 9 0 0 0 0 47 S 0 0 0 0 0 2 3 9 2 2 1 0 0 0 19 SSW 0 0 0 0 0 2 5 28 13 11 3 0 0 0 62 SW 0 0 0 0 0 6 6 45 8 7 2 0 0 0 74 WSW 0 0 0 0 0 .1 7 27 12 1 0 0 0 0 48 W 0 0 0 0 0 0 3 21 9 1 0 0 0 0 34 WNW 0 0 0 0 0 1 1 4 18 14 5 0 0 0 43 NW 0 0 0 0 0 0 0 3 10 10 2 0 0 0 25 NNW 0 0 0 0 0 1 0 0 1 7 0 0 0 0 9 999 0 0 0 0 0 0 2 0 0 0 0 0 0 0 2 0 0 0 0 4 20 57 243 130 69 15 0 0 3 541 cc1996.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 S 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 1 3 26 9 4 0 0 0 0 43 NNE 0 0 0 1 0 2 7 12 2 0 0 0 0 0 24 NE 0 0 0 0 0 1 3 5 2 1 1 0 0 0 13 ENE 0 0 0 0 0 2 4 0 0 1 0 0 0 0 7 E 0 0 0 0 0 2 6 0 0 0 0 0 0 1 9 ESE 0 0 0 0 0 0 1 5 1 1 0 0 0 0 8 SE 0 0 0 0 1 0 1 9 2 1 0 0 0 0 *.14 SSE 0 0 0 0 0 0 0 9 15 3 0 0 0 0 27 S 0 0 0 0 1 1 4 6 4 0 0 0 0 0 16 SSW 0 0 0 0 1 3 4 9 8 4 1 0 0 0 30 SW 0 0 0 0 2 1 0 21 6 3 1 0 0 0 34 WSW 0 0 0 0 0 0 5 12 3 0 1 0 0 0 21 W 0 0 0 0 0 0 4 10 13 2 2 0 0 0 31 WNW 0 0 0 0 0 0 1 15 17 8 3 0 0 0 44 NW 0 0 0 0 0 1 0 5 19 10 2 0 0 0 37 NNW 0 0 0 0 1 0 1 6 4 0 0 0 0 0 12 999 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 1 6 14 44 150 105 38 11 0 0 2 371 cc1996.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 3 15 40 8 5 1 0 0 0 73 NNE 0 0 0 0 4 5 8 16 .5 2 0 0 0 0 40 NE 0 0 0 0 4 4 11 3 2 2 0 0 0 0 26 ENE 0 0 0 0 1 3 4 3 0 0 0 0 0 0 11 E 0 0 0 0 1 8 7 1 0 0 0 0 0 1 18 ESE 0 0 0. 0 0 3. 4 2 0 0 0 0 0 0 9 SE 0 0 0 0 0 3 5 4 3 2 0 0 0 0 17 SSE 0 0 0 0 1 1 6 23 14 6 0 0 0 0 51 S 0 0 0 0 2 1 5 5 3 0 0 0 0 0 16 SSW 0 0 0 0 0 3 2 15 3 8 3 0 0 0 34 SW 0 0 0 0 2 1 4 17 3 6 2 0 0 0 35 WSW 0 0 0 0 2 0 8 15 6 0 0 0 0 0 31 W 0 0 0 0 0 0 4 8 2 1 0 0 0 0 1s WNW 0 .0 0 0 0 1 3 10 10 10 2 0 0 0 36 NW 0 0 0 1 0 0 2 8 8 13 2 0 0 0 34 NNW 0 0 0 1 0 0 1 9 6 5 0 0 0 0 22 999 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 2 18 36 89 179 73 60 10 0 0 2 469
CA06012 Rev.0 Page 112 of 283 ccl996.mnet JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 1 0 6 5 14 59 107 78 99 32 8 0 2 412 NNE 0 0 2 0 7 17 S6 82 52 39 19 18 2 0 294 NE 0 1 2 6 4 9 19 47. 31 15 11 1 0 1 147 ENE 0 0 0 4 16 22 32 68 31 16 1 0 0 1 191 E 0 0 0 3 14 20 27 68 20 4 2 0 0 2 160 ESE 0 1 1 1 7 12 30 32 7 1 0 1 0 0 93 SE 0 0 0 0 5 6 25 55 30 9 10 0 .0 0 140 SSE 0 0 0 2 4 11 46 109 101 49 10 1 0 0 333 S 0 2 1 3 2 4 23 58 24 31 6 0 0 0 154 SSW 0 0 1 3 6 8 14 49 45 67 7 0 0 1 201 SW 0 1 0 1 2 6 18 52 45 34 7 0 0 0 166 WSW 0 0 1 0 2 6 16 51' 24 8 1 0 0 0 109 W 0 0 0 4 3 4 14 45 14 17 1 0 0 7 109 WNW 0 0 0 0 2 10 16 57 60 49 9 2 0 2 207 NW 0 1 2 2 4 5 11 62 94 86 15 0 0 2 284 NNW 0 1 2 2 8 5 22 84 83 67 3 1 0 1 279 999 0 0 0 0 0 0 0 3 0 0 0 0 0 3. 6
*1 8 12 . 37 91 159 428 1029 739 591 134 32 2 22 3285 cc1996.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10. 15 20 30 50 70 100 130 180 9998 9999 N 0 2 0 2 4 8 13 53 41 8 0 0 0 0 131 NNE 1 0 0 3 6 5 14 35 38 13 0 0 0 0 115 NE 0 0 1 3 4 4 .13 36 23 2 0 0 0 0 86 ENE 0 1 0 1 1 7 12 21 4 0 0 0 0 5 52 E 0 0 1 3 5 11 21 29 4 2 0 0 0 6 82 ESE 0 2 0 3 6 5 13 34 11 0 2 1 0 10 87 SE 0 0 0 0 4 5 14 62 22 . 4 4 0 0 1 116 SSE 0 1 0 1 2 4 16 102 88 23 18 3 0 0 258 S 1 1 0 1 4 8 17 78 103 34 1 0 0 1 249 SSW 0 0 2 2 0 5 13 71 135 100. 6 0 0 2 336 SW 1 3 3 3 6 2 14 57 85 66 .2 0 0 0 242 WSW 1 1 0 2 3 3 12 45 54 8 0 0 0 1 130 W 0 3 1 1 3 3 13 50 41 6 0 0 0 2 123 WNW 0 1 0 2 1 3 14 69 91: 13 0 0 0 5 199 NW 0 0 2 0 1 3 19 66 106 10 1 0 0 5 213 NNW 0 0 1 0 0 3 9 76 45 7 0 0 0 0 141 999 0 0 0 0 0 0 0 1 0 0 0 0 0 3 4 4 15 11 27 50 79 227 885 891 296 34 4 0 41 2564 cc1996.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 2 2 3 10 30 3 0 0 0 0 0 50 NNE 0 3 1 1 2 3 1 8 .0 1 0 0 0 0 20 NE 0 0 0 0 2 1 3 3 5 1 0 0 0 0 *15 ENE 1 0 0 1 3 3 5 2 0 0 0 0 0 0 15 E 0 0 0 1 1 2 6 0 0 0 0 0 0 0 10 ESE 0 1 0 0 4 .6 6 5 0- 0 0 0 0 0 22 SE 0 0 1 0 2 8 9 17 1 0 0 0 0 0 38 SSE 0 0 0 1 2 3 9 24 11 0 0 0 0 0 50 S 0 0 0 0 3 1 8 43 80 7 0 0 0 0 142 SSW 0 0 0 0 3 1 5 43 69 10 0. 0 0 0 131 SW 1 1 0 1 1 1 7 47 39 3 1 0 0 0 102 WSW 0 0 1 0 3 3 1 24 17 5 0 0 0 0 54 W 0 0 0 0 0 7 5 15 .21 1 0 0 0 0 49 WNW 0 1 0 0 1 0 5 29 18 0 0 0 0 0 54 NW 0 0 0 0 3 2 2 16 21 5 0 0 0 0 49 NNW 0 0 0 1 1 1 8 26 10 0 0 0 0 0 47 999 0 0 0 0 0 0 0 0 0 -0 0 0 0 0 0 2 6 3 8 33 45 90 332 295 33 1 0 0 0 848
CA 06012 Rev.0 Page 113 of 283 cc1996.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 1 1 .1 4 12 8 0 0 0 0 0 0 28 NNE 0 0 0 1 4 2 2 2 0 0 0 0 0 0 11 NE 0 0 0 1 0 4 0 0 0 0 0 0 0 0 5 ENE 0 2 0 1 4 0 2 0 0 0 0 0 0 0 9 E 1 0 2 3 1 5 0 0 0 0 0 0 0 0 12 ESE 0 0 1 2 1 1 4 2 0 0 0 0 0 0 11 SE 0 0 0 0 4 0 6 4 0 0 0 0 0 0 14 SSE 0 0 1 0 3 4 5 9 7 2 0 0 0 0 31 S 0 0 0 0 2 3 2 23 39 10 0 0 0 0 79 SSW 0 1 1 0 2 2 9 40 34 6 0 0 0 0 95 SW 0 0 0 1 2 1 8 37 14 5 0 0 0 0 68 WSW 0 0 0 1 4 1 8 13 13 2 0 0 0 0 42 W 0 0 0 2 2 3 3 15 14 1 0 0 0 0 40 WNW 0 1 0 1 3 2 10 14 6 2 0 0 0 0 39 NW 0 1 0 0 6 0 3 6 13 1 0 0 0 0 30 NNW 0 0 0 2 4 5 7 9 6 0 0 0 0 0 33 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 6 .6 16 43 37 81 182 146 29 0 0 0 0 547 cc1996.met JOINT FREQUENCY TABLE FOR 60M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ENE 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 E 0 0 0 0 0 1 1 0 0 0 0 0 0 0 2 ESE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SE 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 SSE 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 S 0 0 0 0 1 0 0 1 0 -1 0 0 0 0 3 SSW 0 a 0 0 0 0 0 1 0 0 0 0 0 0 1 SW 0 0 0 0 0 0 0 2 0 1 0 0 0 0 3 WSW 0 0 0 0 0 1 1 0 0 0 0 0 0 0 2 W 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 WNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 999 0 0 0 0 0 0 1 0 0 0 0 0 0 144 145 0 0 0 0 1 3 3 5 1 2 0 0 0 144 159 cc1996.met JOINT FREQUENCY TABLE FOR 60M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 4 1 11 13 33 115 284 153 117 34 8 0 2 776 NNE 1 3 3 6 24 34 94 179 113 59 20 18 2 0 556 NE 0 1 3 10 16 25 54 108 63 22 12 1 0 *1 316 ENE 1 3 0 7 25 39 64 95 35 17 1 0 0 6 293 E 1 0 3 10 22 51 73 100 24 6 2 0 0 13 305 ESE 0 4 2 6 18 27 59 90 19. 2 2 2 0 10 241 SE 0 0 1 0 17 22 60 172 68 17 14 0 0 1 372 SSE 0 1 1 4 12 25 87 291 253 92 28 4 0 0 798 S 1 3 1 4 15 20 62 223 255 85 8 0 0 1 678 SSW 0 1 4 5 12 24 52 256 307 206. 20 0 0 3 890 SW 2 5 3 6 15 18 57 278 200 125 15 0 0 0 724 WSW 1 1 2 3 14 15 58 187 129 24 2 0 0 1 437 W 0 3 1 7 8 17 46 164 115 29 3 0 0 9 402 WNW 0 3 0 3 7 17 50 198 220 96 19 2 0 7 622 NW 0 2 4 3 14 11 37 166 271 135 22 0 0 7 672 NNW 0 1 3 6 14 15 48 210 155 86 3 1 0 1 543 999 0 0 0 0 0 0 3 4 0 0 0 0 0 152 159 8 35 32 91 246 393 1019 3005 2380 1118 205 36 2 214 8784
CA 06012 Rev.0 Page 114 of 283 cc1996.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 8 19 4 1 0 0 0 1 33 NNE 0 0 0 0 1 1 10 27 1 0 0 0 0 2 42 NE. 0 0 0 0 3 1 13 21 3 0 0 0 0 0 41 ENE 0 0 0 0 0 2 6. 1 0 0 0 0 0 0 9 E 0 0 0 0 0 4 4 1 0 0 0 0 0 2 11 ESE 0 0 0 0 0 1 5 7 0 0 0 0 0 1 14 SE 0 0 0 0 0 1 2 22 1 0 0 0 0 0 26 SSE 0 0 0 0 1 1 3 33 13 0 0 0 0 0 51 S 0 0 0 0 2 2 7 11 2 0 0 0 0 0 24 SSW 0 0 0 0 1 0 12 22 7 8 0 0 0 0 50 SW 0 0 0 0 0 8 26 31 9 3 0 0 0 0 77 WSW 0 0 0 1 3 3 14 22 2 0 0 0 0 4 49 W 0 0 0 0 0 0 13 16 4 0 0 0 0 1 34 WNW 0 0 0 0 1 0 2 15 19 6 0 0 0 0 43 NW 0 0 0 0 0 0 1 15. 10 3 0 0 0 1 30 NNW 0 0 0 0 0 0 0 0 5 0 0 0 0 0 5 999 0 0 0 0 1 1 0 0 0 0 0 0 0 0 2 0 0 0 1 13 25 126 263 80 21 0 0 0 12 541 cc1996.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 12 23 3 0 0 0 0 0 38 NNE 0 0 0 0 2 1 10 11 0 0 0 0 0 2 26 NE 0 0 0 0 0 1 10 4 2 0 0 0 0 0 17 ENE 0 0 0 0 0 1 8 2 1 0 0 0 0 1 13 E 0 0 0 0 0 2 4 0 0 0 0 0 0 1 7 ESE 0 0 0 0 1 1 1 2 0 0 0 0 0 0 5 SE 0 0 0 0 0 0 .4 10 1 0 0 0 0 0 15 SSE 0 0 0 0 0 2 2 17 8 0 0 0 0 0 29 S 0 0 0 0 1 1 1 9 0 0 0 0 0 0 12 SSW 0 0 0 0 3 2 7 15 .4 2 0 0 0 0 33 SW 0 0 0 0 0 1 12 13 6 1 0 0 0 0 33 WSW 0 0 0 0 1 0 7 12 0 .1 0 0 0 0 21 W 0 0 0 0 0 0 5 15 3 1 0 0 0 4 28 WNW 0 0 0 0 0 0 8 24 7 5 0 0 0 0 44 NW 0 0 0 0 1 0 1 15 17 2 0 0 0 4 40 NNW 0 0 0 0 0 0 2 7 0 0 0 0 0 0 9 999 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 9 12 94 179 52 12 0 0 0 13 371 cc1996.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 1 0 0 3 21 29 7 1 0 0 0 1 63 NNE 0 0 0 0 6 4 21 10 1 0 0 0 0 5 47 NE 0 0 0 0 1 8 14 9 1 0 0 0 0 3 36 ENE 0 0 0 0 3 3 13 1 0 0 0 0 0 1 .21 E 0 0 0 0 1 6 6 0 0 0 0 0 0 0 13 ESE 0 0 0 0 1 1 4 0 0 0 0 0 0 1 7 SE 0 0 0 0 2 1 11 4 1 0 0 0 0 0 19 SSE. 0 0 0 1 0 5 11 19 11 1 0 0 0 0 48 S 0 0 0 0 1 1 6 7 2. 0 0 0 0 0 17 SSW 0 0 0 0 3 0 7 8 3 4 0 0 0 1 26 SW 0 0 0 0 2 3 8 17 9 3 0 0 0 1 43 WSW 0 0 0 0 2 1 8 12 . 0 0 0 0 0 1 *24 W 0 0 0 0 0 3 10 8 1 0 0 0 0 0 22 WNW 0 0 0 0 1 1 5 14 10 2 0 0 0 0 33 NW 0 0 0 0 0 0 6 11 16 2 0 0 0 0 35 NNW 0 0 0 0 0 0 6 3 3 0 0 0 0 0 12 999 0 0 0 0 2 0 0 0 0 0 0 0 0 1 3 0 0 1 1 25 40 157 152 65 13 0 0 0 15 469
CA06012Rev.0 Page 115 of 283 cc1996.met JOINT FREQUENCY TABLE FOR 1OM AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 SO 70 100 130 180 9998 9999 N 0 0 0 4 13 32 102 134 94 29 3 0 0 6 417 NNE 0 0 4 6 18 39 106 60 29 19 0 0 0 9 290 NE 0 1 3 5 11 16 41 61 18 12 0 0 0 10 178 ENE 0 0 1 3 20 33 56 63 12 0 0 0 0 13 201 E 0 .0 0 4 28 25 68 25 3 0 0 0 0 13 166 ESE 0 1 2 5 12 23 18 8 1 0 0 0 0 8 78 SE 0 1 3 4 11 25 29 35 9 8 0 0 0 21 146 SSE 1 1 0 3 7 29 78 111 43 7 0 0 0 15 295 S 0 0 1 6 12 15 49 55 31 5 0 0 0 3 177 SSW 0 1 0 6 10 10 31 69 56 15 0 0 0 6 204 SW 0 0 0 7 10 16 47 56 31 9 0 0 0 4 180 WSW 1 1 1 2 6 12 42 41 5 1 0 0 0 4 116 W 0 1 1 7 8 13 24 37 16 1 0 0 0 8 116 WNW 0 1 0 1 10 15 32 60 41 9 1 0 0 9 179 NW 0 0 2 11 5 15 50 136 73 17 0 0 0 4 313 NNW 0 1 2 1 17 11 48 96 36 3 0 0 0 7 222 999 0 0 1 0 0 0 0 0 0 0 0 0 0 6 7 2 9 21 75 198 329 821 1047 498 135 4 0 0 146 3285 cc1996.met JOINT FREQUENCY TABLE FOR 1OM AND STABILITY CLASS S MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 5 9 21 13 39 42 3 0 0 0 0 5 138 NNE 1 3 0 5 15 17 38 31 0 0 0 0 0 0 110 NE 0 1 2 3 8 13 19 20 0 0 0 0 0 0 66 ENE 0 2 2 3 9 9 17 8 0 0 0 0 0 2 52 E 0 1 5 9 .12 15 18 1 2 0 0 0 0 5 68 ESE 0 1 2 9 17 14 13 7 1 2 0 0 0 8 74 SE 0 2 4 6 18 21 30 14 0 3 0 0 0 5 103 SSE 0 3 5 10 32 35 51 57 9 20. 0 0 0 2 224 S 0 12 4 5 33 33 70 92 13 1 0 0 0 7 270 SSW 0 3 5 9 26 30 100 106 35 4 0 0 0 14 332 SW 3 5 5 6 15 31 82 118 32 2 0 0 0 16 315 WSW 2 5 1 7 17 22 45 43 1 0 0 0 0 5 148 W 3 3 5 6 27 15 42 33 1 0 0 0 0 5 140 WNW 0 1 3 11 16 31 53 49 8 0 0 0 0 16 188 NW 0 6 3 9 20 30 77 52 6 0 0 0 0 9 212 NNW 3 1 6 2 12 18 53 18 0 0 0 0 0 3 116 999 0 0 0 0 0 2 0 0 0 0 0 0 0 6 8 12 50 57 109 298 349 747 691 111 32 0 0 0 108 2564 cc1996.met JOINT FREQUENCY TABLE FOR 1OM AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 4 3 7 3 3 0 0 0 0 0 0 0 20 NNE 1 0 0 3 6 3 5 1 0 0 0 0 0 0 19 NE 0 1 1 1 5 4 3 0 0 0 0 0. 0 0 15 ENE 0 0 1 4 4 4 1 0 0 0 0 0 0 0 14 E 0 1 2 5 3 1 3 0 0 0 0 0 0 0 15 ESE 0 0 1 2 4 3 0 0 0 0 0 0 0 0 10 SE 0 2 1 1 8 5 1 0 0 0 0 0 0 0 18 SSE 1 1 4 5 13 7 4 0 0 0 0 0 0 0 35 S 2 4 2 3 28 28 32 6 0 0 0 0 0 1 106 SSW 3 3 1 4 24 52 72 13 1. 0 0 0 0 1 174 SW 2 4 5 2 20 31 66 16 0 0 0 0 0 0 146 WSW 2 3 3 6 14 25 24 4 0 0 0 0 0 2 83 W 1 1 4 4 12 21 14 1 0 0 0 0 0 3 61 WNW 0 1 0 S 16 12 9 0 0 0 0 0 0 2 45 NW 2 3 1 4 11 16 17 4 .0 0 0 0 0 2 60 NNW 1 2 2 3 13 3 1 0 0 0 0 0 0 0 25 999 0 1 1 0 0 0 0 0 0 0 0 0 .0 0 2 15 27 33 55 188 218 255 45 1 0 0 0 0 11 848
CA 06012 Rev.0 Page 116 of 283 cc1996.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 6 0 1 0 0 0 0 0 0 0 0 0 7 NNE 0 0 0 2 1 1 0 0 0 0. 0 0 0 0 4 NE 0 1 1 0 3 0 0 0 0 0 0 0 0 0 5 ENE 0 0 0 3 5 .2 2 0 0 0 0 0 0 0 12 E 0 1 0 0 2 1 0 0 0 0 0 0 0 . 0 4 ESE 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 SE 0 0 1 0 0 0 0 0 0 0 0 0 0 0 1 SSE 0 1 1 4 5 2 0 0 0 0 0 0 0 0 13 S 0 5 0 1 10 13 7 0 0 0 0 0 0 2 38 SSW 1 6 6 5 19 37 42 3 0 0 0 0 0 3 122 SW 0 7 9 8 32 52 31 2 0 0 0 0 0 6 147 WSW 1 2 5 13 21 18 6 2 0 0 0. 0 0 1 69 W 2 6 5 9 16 13 8 0 0 0 0 0 0 1 60 WNW 1 3 2 5 14 10 6 0 0 0 0 0 0 0 41 NW 0 0 0 1 3 7 8 0 0 0 0 0 0 0 19 NNW 0 0 2 0 1 1 0 0 0 0 0 0 0 0 4 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 32 38 52 133 157 110 7 0 0 0 0 0 13 547 cc1996.met JOINT FREQUENCY TABLE FOR 10M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 0 0 0 0 0 0 0 0 .0 1 NNE 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 NE 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 ENE 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 E 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 ESE 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 SE 0 0 0 0 0 0 0 0 0 0-. 0 0 0 0 0 SSE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 S 0 0 0 0 1 1 0 0 0 0 0 0 0 0 2 SSW 0 0 0 0 0 0 .0 *2 0 0 0 0 0 0 2 SW 0 0 0 0 0 1 0O 0 0 0 0 0 0 0 1 WSW 0 0 0 0 1 0 0. 0 0 0 0 0 0 0 1 W 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WNW 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 NW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNW 0 0 0 0 0 0 0 0 0 0 0 ,0 0 0 0 999 0 0 1 0 0 0 0 0 0 0 0 0 0 144 145 0 0 1 0 4 4 1 3 0 0 0 0 0 146 159 cc1996.met JOINT FREQUENCY TABLE FOR 10M AND ALL STABI3LITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 16 16 43 51 185 247 111 31 3 0 0 13 717 NNE 2 3 4 16 49 66 190 140 31 19 0 0 0 20 540 NE 0 4 7 9 31 44 100 115 24 12 0 0 0 13 359 ENE 0 2 4 13 41 54 103 76 13 0 0 0 0 17 323 E 0 3 7 18 46 55 103 27 5 0 0 0 0 21 285 ESE 0 2 5 17 36 43 41 24 2 2 0 0 0 18 190 SE 0 5 9 11 39 53 77 85 12 11 0 0 0 26 328 SSE 2 6 10 23 58 81 149 237 84 28 0 0 0 17 695 S 2 21 7 15 88 94 172 180 48 6 0 0 0 13 646 SSW 4 13 12 24 86 131 271 238 106 33 0 0 0 25 943 SW 5 16 19 23 79 143 272 253 87 18 0 0 0 27 942 WSW 6 11 10 29 65 81 146 136 8 2 0 0 0 17 511 W 6 11 15 26 63 65 116. 110 25 2 0 0 0 22 461 WNW 1 6 5 22 58 69 116 162 85 22 1 0 0 27 574 NW. 2 9 6 25 40 68 160 233 122 24 0 0 0 20 709 NNW 4 4 12 6 43 33 110 124 44 3 0 0 0 10 393 999 0 1 3 0 3 3 0 0 0 0 0 0 0 158 168 34 118 151 293 868 1134 2311 2387 807. 213 4 0 0 464 8784
CA 06012 Rev.0 Page 117 of 283 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 6 33 107 33 8 7 0 0 0 194 NNE 0 0 0 0 2 8 38 82 19 6 5 0 0 0 160 NE 0 0 0 0 4 7 27 .14 6 1 2 0 0 0 61 ENE 0 1 0 1 2 7 12 3 0 0 0 0 0 0 26 E 0 0 0 0 2 10 16 2 1 0 0 0 0 0 31 ESE 0 0 0 0 1 4 15 19 1 0 0 0 0 0 40 SE 0 0 1 1 1 3 13 32 6 2 0 0 0 0 59 SSE 0 0 0 0 0 0 9 45 25 6 0 0 0 0 85 S 0 0 0 0 1 0 7 19 4 2 0 0 0 0 33 SSW 0 0 0 0 1 2 17 36 18 11 1 0 0 0 86 SW 0 0 0 0 1 2 21 53 41 30 3 0 0 0 151 WSW 0 0 0 0 1 3 16 42 17 11 2 0 0 0 92 W 0 0 1 0 0 2 9 22 18 7 2 0 0 0 61 WNW 0 0 0 1 0 0 4 19 40 38 3 0 0 0 105 NW 0 0 1 0 1 0 3 11 32 49 6 1 0 0 104 NNW 0 0 0 0 0 1 5 12 15 8 0 0 0 0 41 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 3 3 17 55 245 518 276 179 31 1 0 0 1329 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 3 13 20 13 4. 0 1 0 0 55 NNE 0 0 0 0 1 2 18 11 3 3 5 0 0 0 43 NE 0 0 0 1 3 5 10 5 2 3 1 0 0 0 30 ENE 0 0 0 0 0 7 7 2 0 0 0 0 0 0 16 E 0 0 0 0 3 7 6 1 0 1 0 0 0 0 18 ESE 0 0 0 0 0 2 4 4 0 0. 0 0 0 0 10 SE 0 0 0 0 0 0 5 6 1 .1 0 0 0 0 13 SSE 0 0 0 0 1 3 4 12 5 1 0 0 0 0 26 S 0 0 0 0 0 0 2 7 1 1 1 0 0 0 12 SSW 0 0 0 0 0 1 0 7 5 5 0 0 0 0 18 SW 0 0 1 0 2 *3 3 11 4 8 1 0 0 0 33 WSW 0 0 0 0 0 2 1 .12 10 5 0 0 0 0 30 W 0 0 0 0 0 3 6 7 4 0 0 0 0 0 20 WNW 0 0 0 0 0 0 2 13 10 4 3 0 0 0 32 NW 0 0 0 0 1 0 3 8 9 10 2 3 0 0 36 NNW 0 0 0 0 1 0 3 7 4 1 1 0 0 0 17 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 13 38 87 133 71 47 14 4 0 0 409 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N a 0 0 0 3 3 6 18 5 4 3 0 0 0 42 NNE 0 0 0 0 0 4 7 6 9 6 2 0 0 0 34 NE 0 0 0 1 3 6 9 9 4 3 .- 5. 0 0 0 40. ENE 0 0 0 0 3 2 8 3 0 1 0 0 0 0 17 E 0 0 0 1 4 6 4 4 1 0 0 0 0 0 20 ESE 0 0 0 0 2 2 2 0 0 0 0 0 0 0 6 SE 0 0 0 0 1 1 4 5 2 0 1 0 0 0 14 SSE 0 0 0 0 0 2 4 11 11 2 0 0 0 0 30 S 0 0 0 0 0 0 2 2 2 0 0 0 0 0 6 SSW 0 0 0 0 0 1 9 9 8 5 0 0 0 0 32 SW 0 0 0 0 1 2 9 16- 11 8 2 0 0 0 49 WSW 0 0 0 0 1 0 8 15 7 8 0 0 0 0 39 W 0 0 0 0 0 2 4 6 8 2 1 0 0 0 23 WNW 0 0 0 0 1 0 4 12 4 3 3 0 0 0 27 NW 0 0 0 0 0 0 2 6 9 9 1 0 .0 0 27 NNW 0 0 0 1 0 3 3 12 5 4 0 0 0 0 28 999 0 0 0 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 3 19 34 85 134 87 55 18 0 0 0 435
CA06012 Rev.0 Page 118 of 283 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 1 2 6 10 22 50 58 78 13 0 0 0 241 NNE 0 1 0 2 10 8 30 49 75 94 19 0 0 0 288 NE 0 1 1 4 2 8 20 40 54 75 28 0 0 1 234 ENE 0 0 2 5 7 7 23 71 44 16 2 0 0 3 180 E 0 1 1 1 14 11 23 67 20 2 0 0 0 1 141 ESE 0 1 4 0 2 6 14 27 6 0 0 0 0 0 60 SE 0 0 3 2 3 6 10 46 23 5 1 0 0 0 99 SSE 0 1 0 0 S 12 16 71 68 28 3 0 0 0 204 S 0 1 1 1 6 0 13 33 27 16 2 0 0 0 100 SSW 0 0 0 1 1 3 9 41 46 45 7 0 0 0 153 SW 0 0 0 0 2 4 14 50 63 59 6 0 0 0 198 WSW 0 0 2 0 1 4 15 36 33 20 1 0 0 0 112 W 0 1 0 1 1 7 21 30 21 5 1 0 0 0 88 WNW 0 1 1 2 3 5 16 49 39 28 7 1 0 1 153 NW 0 0 0 4 2 1 18 68 95 59 27 0 0 0 274 NNW 0 1 0 2 3 3 11 89 94 .41 3 0 0 0 247 999 0 0 0 0 0 0 0 1 0 0 0 0 0 7 8 0 10 16 27 68 95 275 818 766 571 120 1 0 13 2780 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 ,50 70 100 130 180 9998 9999 N 0 0 0 0 1 1 10 51 38 12 3 0 0 0 116 NNE 0 1 0 1 3 5 10 28 17 16 0 0 0 0 81 NE 0 0 0 2 4 5 16 23 7 4 0 0 0 0 61 ENE 0 1 0 1 2 1 9 23 2 0 0 0 0 1 40 E 0 0 0 0 2 7 22 20 0 0 0 0 0 4 55 ESE 0 1 1 0 2 5 15 16 6 1 0 0 0 10 57 SE 0 0 0 0 2 2 5 26. 10 4 0 0 0 0 49 SSE 0 0 0 1 3 1 5 55 55 5 0 0 a 0 125 S 1 1 0 2 1 3 7 55. 99 23 0 0 0 0 192 SSW 0 1 2 1 0 2 8 45 132 73 4 0 0 0 268 SW 0 0 0 3 '3 4 4 42 122 100 0 0 0 0 278 WSW 0 0 0 1 4 0 9 43 58 13. 0 0 0 0 128 W 0 0 0 1 1 2 5 56 48 5 0 0 0 0 118 WNW 0 0 0 1 0 2 14 76 70 16 1 0 0 0 180 NW 0 0 0 1 1 3 5 91 100 27 0 0 0 0 228 NNW 0 1 0 2 1 3 16 76 96 14 0 0 0 0 209 999 0 0 0 0 0 0 0 0 0 0 0 0 0 17 17 1 6 3 17 30 46 160 726 860 313 8 0 0 32 2202 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 1 0 4 1 9 10 6 0 0 0 0 0 31 NNE 0 3 0 1 4 1 4 4 2 1 0 0 0 0 20 NE 0 0 0 0 2 2 8 .6 5 .0 0 0 0 0 23 ENE 0 0 0 0 1 4 3 4 1 0 0 0 0 0 13 E 0 0 0 1 5 2 3' 3 2 ,0 0 0 0 0 16 ESE 0 0 1 1 2 6 6 5 1 0 0 0 0 0 22 SE 0 1 0 1 2 2 3 22 4 0 0 0 0 0 35 SSE 1 0 0 1 3 .3 6 22 25 0 0 0 0 0 61 S 0 0 1 1 0 2 3 27 54 5 0 0 0 0 93 SSW 0 1 0 0 0 4 9 34 76 5 0 0 0 0 129 SW 0 0 0 0 2 b 6 35 65 9 0 0 0 0 117 WSW 0 0 0 0 1 2 8 20 31 0 0 0 0 0 62 W 0 0 0 0 0 1 9 21 21 0 0 0 0 0 52 WNW 0 0 0 0 0 1 2 30 20 2 0 0 0 0 55 NW 0 0 0 1 2 1 3 25 38 2 0 0 0 0 72 NNW 0 0 0 1 1 4 4 34 12 0 0 0 0 0 56 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 5 3 8 29 36 86 302 363 24 0 0 0 0 857
CA06012 Rev.0 Page 119 of 283 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 *7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 2 4 13 2 0 0 0 0 0 0 22 NNE 0 0 0 1 4 5 3 3 0 0 0 0 0 0 16 NE 0 0 0 2 3 3 1 0 0 0 0 0 0 0 9 ENE 0 2 0 1 3 0 0 1 0 0 0 0 0 0 7 E 0 0 1 2 4 1 0 0 0 0 0 0 0 0 8 ESE 0 0 0 1 3 1 3 0 0 0 0 0 0 0 8 SE 0 1 0 0 0 4 2 7 1 0 0 -0 0 0 15 SSE 0 0 1 3 1 3 2 20 5 0 0 0 0 0 35 S 0 0 0 1 2 5 4 29 22 1 0 0 0 0 64 SSW 0 0 0 1 3 7 9 45 48 7 0 0 0 0 120 SW 0 0 0 1 4 2 10 41 36 5 0 0 0 0 99 WSW 0 0 0 2 1 4 10 40 24 3 0 0 0 0 84 W 0 0 0 2 3 1 14 38 15 2 0 0 0 0 75 WNW 0 0 0 0 1 0 12 26 13 0 0 0 0 0 52 NW 0 0 1 1 3 2 4 17 9 1 0 0 0 0 38 NNW 0 1 1 0 1 1 4 12 9 0 0 0 0 0 29 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 4 19 38 43. 91 281 182 19 0 0 0 0 681 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50
- 70 100 130 180 9998 9999 N 0 0 1 0 0 0 0 1 0 0 0 0 0 0 2 NNE 0 0 0 0 1 0 3 1 0 0 0 0 0 0 5 NE 0 0 0 0 0 0 1 0 0 0 0 0 0 1 2 ENE 0 0 0 0 1 1 0 0 0 0 0 0 0 1 3 E 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 ESE 0 0 0 0 0 1 0 0. 0 0 0 0 0 0 1 SE 0 0 0 .0 2 0 0 0 0 0 0 0 0 0 2 SSE 0 0 0 0 0 0 .0 1 0 0 0 0 0 0 1 S 0 0 0 1 0 0 1 0 0 0 0 0 0 0 2 SSW 0 0 0 Q 1 0 1 1 0 0 0 0 0 0 3 SW 0 0 0 D 1 2 5 1 0 0 0 0 0 0 9 WSW 0 0 0 0 0 0 1 1 0 0 0 0 0 0 2 W 0 0 0 1 0 0 1 0 0 0 0 0 0 0 2 WNW 0 0 0 0 0 1 1 1 0 0 0 0 0 0 3 NW 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 NNW 0 0 0 0 0 0 2 0 0 0 0 0 0 0 2 999 0 0 0 0 0 0 1 1 0 0 0 0 0 24 26 0 0 1 2 6 6 17 9 0 0 0 0 0 26 67 cc1997.met JOINT FREQUENCY TABLE FOR 60M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 3 3 17 28 106 259. 153 106 26 1 0 0 703 NNE 0 5 0 5 25 33 113 184 125 126 31 0 0 0 647 NE 0 1 1 10 21 36 92 97 .78 86 36 0 0. 2 460 ENE 0 4 2 8 19 29 62 107 47 17 2 0 0 5 302 E 0 1 2 5 34 45 74 97 24 3 0 0 0 5 290 ESE 0 2 6 2 12 27 59 71 14 1 0 0 0 10 204 SE 0 2 4 4 11 18 42 144 47 12 2 0 0 0 286 SSE 1 1 1 5 13 24 46 237 194 42 3 0 0 0 567 S 1 2 2 6 10 10 39 172 209 48 3 0 0 0 502 SSW 0 2 2 3 6 20 62 218 333 151 12 0 0 0 809 SW 0 0 1 4 16 19 72 249 342 219 12 0 0 0 934 WSW 0 0 2 3 9 is 68 209 180 60 3 0 0 0 549 W 0 1 1 5 5 18 69 180 135 21 *4 0 0 0 439 WNW 0 1 1 4 5 9 55 226 196 91 17 1 0 1 607 NW 0 0 2 7 10 7 38 227 292 157 36 4 0 0 780 NNW 0 3 1 6 7 15 48 242 235 68 4 0 0 0 629 999 0 0 0 0 0 0 1 2 1 0 0 0 0 48 52 2 26 31 80 220 353 1046 2921 2605 1208 191 6 0 71 8760
CA 06012 Rev.0 Page 120 of 283 cc1997.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 2 4 49 85 14 4 0 0 0 0 158 NNE 0 0 0 1 2 16 74 71 8 0 0 0 0 0 172 NE 0 0 0 0 1 7 53 29 3 1 0 0 0 0 94 ENE 0 0. 0 0 1 12 16 3 0 1 0 0 0 0 33 E 1 0 0 1 1 12 19 2 0 0 0 0 0 0 36 ESE 0 0 0 0 2 7 19 6 0 0 0. 0 0 0 34 SE 1 0 0 0 1 3 18 23 1 0 0 0 0 0 47 SSE 0 1 0 0 0 1 24 56 13 0 0 0 0 0 95 S 0 0 0 0 1 5 15 13 2 0 0 0 0 0 36 SSW 0 0 0 0 1 7 28 27 10 1 0 0 0 0 74 SW 0 0 0 0 2 13 36 63 36 4 0 0 0 0 154 WSW 0 0 0 1 1 4 30 42 11 2 0 0 0 0 91 W 0 1 0 0 1 9 15 31 6 2 0 0 0 0 65 WNW 0 0 0 1 0 2 15 42 39 4 0 0 0 0 103 NW 0 0 0 0 0 0 9 38 58 6 1 0 0 0 112 NNW 0 0 0 0 1 2 .7 11 4 0 0 0 0 0 25 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
* . 2 2 0 4 17 104 427 542 205 25 1 0 0 0 1329 cc1997.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY 'LASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 4 16 23 5. 2 0 0 0 . 0 51 NNE 0 0 0 0 0 9 17 10 6 0 0 0 0 0 42 NE 0 0 0 1 2 6 15 9 4 0 0 0 0 0 37 ENE 0 0 0 0 5 2 11 2 0 0 0 0 0 0 20 E 0 0 0 1 2 6 8 1 0 0 0 0 .0 0 18 ESE 0 0 0 0 0 3 7 0 *0 0 0 0 0 0 10 SE 0 0 0 0 2 0 .6 1 0 ,0 0 0 0 0 9
-SSE 0 0 0 0 1 2 13 10 2 0 0 0 0 0 28 S 0 0 0 0 0 1 5 2 1 1 0 0 0 0 10 SSW 0 0 0. 0 1 2 3 6 4 0 0 0 0 0 16 SW 0 0 0 0 1 1 10 13 9 2 0 0 0 0 36 WSW 0 0 1 0 3 3 5 16 4 1 0 0 0 0 33 W 0 0 0 0 1 1 6 9 1 0 0 0 0 0 18 WNW 0 0 0 0 0 2 5 11 8 2 0 0 0 0 28 NW 0 0 0 0 1 2 5 17 6 5 2 0- 0 0 38 NNW 0 0 0 0 0 2 5 7 1 0 0 0 0 0 15 999 0 0 0 0 0 0 0 0 C 0 0 0 0 0 0 0 0 1 2 20 46 137 137 51 13 2 0 0 0 409 cc1997.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS . 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 5 2 20 12 *7 2 0 0 0 0 49 NNE 0 0 0 1 2 4 12 10 2 0 0 0 0 0 31 NE 0 0 0 0 3 8 9 .13 8 *0 0 0 0 0 41 ENE 0 0 0 0 1 4 15 2 2 1 0 0 0 0 25 E 0 0 1 0 2 6 7 1 0 0 0 0 0 0 17 ESE 0 0 0 1 0 4 0 0 0 0 0 0 0 0 5 SE 0 0 0 0 3 3 5 3 0 0 0 0 0 0 14 SSE 0 0 0 1 0 1 8 14 5 0 0 0 0 0 29 S 0 0 0 0 1 3- 4 4 1 0 0 0 0 0 13 SSW 0 0 0 0 1 4 4 10 0 1 0 0 0 0 20 SW 0 0 0 0. 3 5 12 20 6 3 0 0 0 0 49 WSW 0 0 0 0 0 8 15 11 9 1 0 0 0 0 44 W 0 0 0 1 0 2 6 12 3 1 0 0 0 0 25 WNW 0 0 0 0 1 1 8 11 2 2 0 0 0 0 25 NW 0 0 0 0 1 3 6 13 5 3 0 0 0 0 31 NNW 0 0 0 0 0 3 1 9 4 0 0 0 0 0 17 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 5 23 61 132 145 54 14 0 0 0 0 435
CA 06012 Rev.0 Page 121 of 283 cc1997.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 .70 100 130 180 9998 9999 N 0 0 3 1 13 21 41 118 58 8 0 0 0 0 263 NNE 1 2 2 4 24 26 39 96 33 2 0 0 0 1 230 NE 2 0 0 5 12 12 31 128 63 10 0 0 0 4 267 ENE 0. 0 2 4 11 22 65 81 27 5 0 0 0 1 218 E 0 2 1 1 14 20 50 29 0 0 0 0 0 0 117 ESE 0 2 0 8 16 17 29 8 0 0 0 0 0 0 80 SE 0 0 3 2 3 14 30 25 5 0 0 0 0 0 82 SSE 0 0 0 1 9 17 51 85 21 2 0 0 0 0 186 S 0 2 1 8 10 11 34 35 11 1 0 0 0 0 113 SSW 1 2 1 0 8 11 29 52 24 6 0 0 0 0 134 SW 0 2 2 3 6 18 47 96 49 5 0 0 0 0 228 WSW 0 2 3 4 6 11 26 55 20 1 0 0 0 0 128 W 0 0 0 4 8 18 24 33 5 1 0 0 0 0 93 WNW 0 2 1 4 11 14 33 51 24 6 1 0 0 0 147 NW 2 2 1 6 11 21 53 119 56 21 0 0 0 0 292 NNW 0 1 1 4 8 18 55 94 16 2 0 0 0 0 199 999 0 0 0 0 0 0 1 0 0 0 0 0 0 2 3 6 19 21 59 170 271 638 1105 412 70 1 0 0 8 2780 cc1997.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 3 17 17 34 42 6 1 0 0 0 0 120 NNE 2 0 3 5 22 17 21 19 0 0 0 0 0 0 89 NE 1 1 2 1 9 6 13 18 0 0 0 0 0 0 51 ENE 0 1 0 4 6 5 16 4 0 0 0 0 0 1 37 E 0 1 2 6 13 10. 12 0 0 0 0 0 0 4 48 ESE 0 1 5 9 12 9 7 1 0 0 0 0 0 9 53 SE 0 5 2 7 13 .7 13 4 1 0 0 0 0 1 53 SSE 1 0 2 4 8 25 29 18 1 0 0 0 0 0 88 S 1 0 4 5 13 29 87 54 0. 0 0 0 0 0 193 SSW 0 4 2 1 19 26 84 92 21 0 0 0 0 0 249 SW 2 0 3 9 21 19 94 166 40 0 0 0 0 0 354 WSW 1 3 4 8 16 24 51 40 14 0 0 0 0 0 161 W 0 4 5 10 21 18 41 38 0 0 0 0 0 0 137 WNW 1 5 1 9 21 34 49 60 4 1 0 0 0 0 185 NW 1 0 2 11 18 44 68 89 9 0 0 0 0 0 242 NNW 0 0 3 6 11 32 55 35 0 0 0 0 0 0 142 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 10 25 40 98 240 322 674 680 96 2 0 0 0 15 2202 ccl997.met JOINT FREQUENCY TABLE FOR IOM AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 1 1 9 1 6 0 0 0 0 0 0 0 19 NNE 0 0 0 2 5 6 1 0 0 0 0 0 0 0 14 NE 0 0 0 3 2 2 .2 4 0 0 0 0 0 0 13 ENE 0 1 0 0 0 4 0 0 .0 0 0 0 0 0 5 E 0 0 2 2 0 1 2 2 0 0 0 .0 0 0 9 ESE 1 1 0 3 2 0 0 0 0 0 0 0 0 0 7 SE 0 3 5 2 7 5 1 0 0 0 0 0 0 0 23 SSE 0 4 4 5 20 10 5 0 0 0 0 0 0 0 48 S 0 4 5. 5 7 21 27 3 0 0 0 0 0 0 72 SSW 3 5 2 6 27 51 58 8 0 0 0 0 0 0 160 SW 4 0 5 4 30 31 101 17 0 0 0 0 0 1 193 WSW 2 3 0 2 15 25 28 1 0 0 0 0 0 0 76 W 1 3 5 7 13 18 12 1 0 0 0 0 0 0 60 WNW 0 4 3 5 11 14 24 0 0 0 0 0 0 0 61 NW 0 2 4 5 14 24 25 6. 0 0 0 0 0 0 80 NNW 1 1 1 1 7 6 0 0 0 0 0 0 0 0 17 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 12 32 37 53 169 219 292 42 0 0 0 0 0 1 857
CA 06012 Rev.0 Page 122 of 283 ccl997 .met JOINT FREQUENCY TABLE FOR IOM AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 2 0 0 0 0 0 0 0 0 '0 2 NNE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NE 1 0 1 0 2 0 0 0 0 0 0 0 0 0 4 ENE 0 0 0 1 1 0 .0 0 0 0 0 0 0 0 2 E 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 ESE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SE 0 1 0 1 1 0 0 0 0 0 0 0 0 0 3 SSE 1 1 1 2 6 1 1 0 0 0 0 0 0 0 13 S 1 2 2 12 15 16 1 0 0 0 0 0 0 0 49 SSW 1 1 2 9 3S 36 39 2 0 0 0 0 0 0 125 SW 2 2 6 12 41 71 71 4' 0 0 0 0 0 0 -209 WSW 1 3 4 16 38 28 31 1 0 0 0 0 0 0 122 W 1 4 6 14 24 14 6 0 0 0 0 0 0 0 69 WNW 2 3 2 7 17 15 6 0 0 0 0 0 0 0 52 NW 1 2 1 0 2 10 12 0 0 0 0 0 0 0 28 NNW 0 0 0 3 0 0 0 0 0 0 0 0 0 0 3 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 19 25 77 184 191 167 7 0 0 0 0 0 0 681 ccl997.met JOINT FREQUENCY TABLE FOR IOM AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES'10 DIR 2 5 7 10 1S 20 30 50 70 100 130 .180 9998 9999 N 0 0 0 0 1 0 0 0 0 0 0 0 0 0 1 NNE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NE 0 0 1 0 1 4 2 0 0 0 0 0 0 1 9 ENE 0 0 0 0 1 1 2 0 0 0 0 0 0 1 5 E 0 0 0 0 0 0 2 0 0 0 0 0 0 3 5 ESE 0 0 0 1 1 0 0 0 0 0 0 0 0 0 2 SE 0 0 0 0 1 0 0 0 0 0 0 0 0 1 2 SSE 0 0 0 2 0 0 1 0 0 *0 0 0 0 0 3 S 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 SSW 0 0 0 1 1 2 0 0 0 0 0 0 0 0 4 SW 0 0 0 0 0 5 2 0 0 0 0 0 0 0 7 WSW 0 0 0 0 0 0 2 0 0 0 0 0 0 0 2 W 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 WNW 0 0 0 0 1 1 1 0 0' 0 0 0 0 0 .3 NW 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 NNX 0 0 0 0 0 1 1 0 0 0 0 0 0 0 2 999 0 0 0 0 0 0 0 2 0 0 0 0 0 17 19 0 0 1 4 7 14 14 4 0 0 0 0 0 23 67 cc1997.met JOINT FREQUENCY TABLE FOR iOM AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 - DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 4 6 50 49 166 280 90 17 0 0 0 0 663 NNE 3 2 5 13 55 78 164 206 49 2 0 0 0 1 578 NE 4 1 4 10 32 45 125 201 78 11 0 0 0 5 516 ENE 0 2 2 9 26 50 125 92 29 7 0 0 0 3 345 E 1 3 6 11 32 55 100 35 0 0 0 0 0 7 250 ESE 1 4 5 22 33 40 62 15 0 0 0 0 0 9 191 SE 1 9 10 12 31 32 73 56 7 0 0 0 0 2 233 SSE 2 6 7 15 44 57 132 183 42 2 0 0 0 0 490 S 2 8 12 30 47 86 173 112 15 2 0 0 0 0 467 SSW 5 12 7 17 93 139 245 197 59 8 0 0 0 0 782 SW 8 4 16 28 104 163 373 379 140 -14 0 0 0 1 1230 WSW 4 11 12 31 79 103 188 166 58 5 0 0 0 0 657 W 2 12 16 36 68 80 111 124 15 4 0 0 0 0 468 WNW 3 14 7 26 62 83 141 175 77 15 1 0 0 0 604 NW 4 6 8 22 47 104 178 283 134 35 3 0 0 0 824 NNW 1 2 5 14 27 64 124 156 25 2 0 0 0 0 420 999 0 0 0 0 0 0 1 2 0 0 0 0 0 19 22 41 97 126 302 830 1228 2481 2662 818 124 4 0 0 47 8760
CA 06012 Rev.0 Page 123 of 283 cc1998.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 5 33 85 37 5 2 0 0 3 171 NNE 0 0 0 0 4 16 56 85 18 7 1 0 0 4 191 NE 0 0 0 2 4 11 36 17 1 0 0 0 0 0 71 ENE 0 0 0 1 2 8 25 7 0 0 0 0 0 0 43 E 0 0 1 1 4 12 45 11 1 0 0 0 0 0 75 ESE 0 0 0 0 1 2 14 14 0 0 0 0 0 2 33 SE 0 0 0 0 0 0 6 21 11 1 0 0 0 1 40 SSE 0 0 0 0 0 0 3 22 18 3 0 0 0 4 50 S 0 0 0 0 0 1 1 9 3 2 0 0 0 0 16 SSW 0 0 0 0 0 1 0 12 11 3 0 0 0 3 30 SW 0 0 0 0 1 0 0 25 18 8 1 0 0 0 53 WSW 0 0 0 0 0 1 1 21 7 1 2 0 0 3 36 W 0 0 0 0 0 0 1 4 9 2 0 0 0 2 18 WNW 0 0 0 0 0 0 0 0 7 1 0 0 0 0 8 NW 0 0 0 0 1 0 0 3 7 3 0 0 0 1 15 NNW 0 0 0 0 0 0 2 12 15 5 0 0 0 2 36 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 4 18 57 223 348 163 41 6 0 0 25 886 cc1998.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 2 3 17 22 10 3 0 0 0 0 57 NNE 0 0 0 0 1 3 9 18 4 4 1 0 0 0 40 NE 0 0 1 0 1 2 9 8 0 0 0 0 0 0 21 ENE 0 0 0 0 0 3 2 2 0 0 0 0 0 0 7 E 0 0 0 0 1 2 9 2 0 0 0 0 0 0 14 ESE 0 0 0 1 2 2 8 8 .0 0 0 0 0 1 22 SE 0 0 0 0. 1 1 2 13 2 0 0 0 0 0 19 SSE 0 0 0 0 0 0 1 16 8. 1 0 0 0 1 27 S 0 0 0 0 0 0 1 3 2 1 0 0 0 1 8 SSW 0 1 0 0 0 0 2 6 4 8 0 0 0 0 21 SW 0 0 0 0 0 0 4 8 10 5 0 0 0 1 28 WSW 0 0 0 0 0 1 0 5 5 0 0 0 0 1 12 W 0 0 0 0 0 0 0 3 2 0 0 0 0 0 5 WNW 0 0' 0 0 0 0 0 3 6 8 0 0 0 2 19 NW 0 0 0 0 0 0 0 4 10 0 0 0 0 0 14 NNW 0 0 0 0 0 0 3 4 12 1 0 0 0 1 21 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 8 17 67 125 75 31 1 0 0 8 335 ccl998.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 3 6 18 6 7 0 0 0 1 42 NNE 0 0 0 0 1 5 9 7 4 4 0 0 0 2 32 NE 0 0 0 1 1. 4 7 7 2 2 0 0 0 0 24 ENE 0 0 0 0 0 2 10 4 0 0 0 0 0 0 16 E 0 1 0 0 1 4 6 4 1 0 0 0 0 0 17 ESE 0 0 0 1 0 1 4 2 0 0 0 0 0 0 8 SE 0 0 0 0 0 1 8 8 2 0 0 0 0 0 19 SSE 0 0 0 1 0 0 4 15 8 1 0 0 0 1 30 S 0 0 0 0 0 0 5 7 0 0 0 0 0 1 13 SSW 0 0 0 0 0 0 2 8 8 4 0 0 0 0 22 SW .0 0 0 0 0 2 4 16 20 3 0 0 0 1 46 WSW 0 0 0 0 1 0 4 19 3 1 0 0 0 0 28 W 0 0 0 0 0 0 0 6 8 1 0 0 0 1 16 WNW 0 0 0 0 0 0 1 3 10 4 0 0 0 1 19 NW 0 0 0 0 0 0 3 5 16 1 1 0 0 2 28 NNW 0 0 0 0 1 1 3 11 4 4 0 0 0 1 25 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 3 6 23 76 140 92 32 1 0 0 11 385
CA06012 Rev.0 Page 124 of 283 cc1998.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 4 11 30 50 57 67 28 7 0 1 256 NNE 0 0 0 1 10 10 22 51 69 96 38 6 0 1 304 NE 0 0 1 2 8 8 20 49 50 36 8 1 0 0 183 ENE 0 1 1 1 8 12 21 55 9 1 0 .0 0 0 109 E 0 0 1 2 9 13 22 59 7 1 0 0 0 0 114 ESE 0 1 0 2 2 9 21 64 13 2 2 0 0 0 116 SE 0 0 0 1 8 7 22 72 22 6 0 0 0 0 138 SSE 0 1 0 1 3 3 27 76 45 15 0 0 0 6 177 S 0 0 1 0 7 8 16 43 19 7 2 0 0 0 103 SSW 0 0 0 0 1 6 22 36 41 26 5 0 0 0 137 SW 0 0 2 1 3 9 33 71 32 29 1 0 0 1 182 WSW 0 0 0 0 3 10 29 69 25 4 0 0 0 5 145 W 0 0 0 2 7 7 24 58 30 7 1 0 0 0 136 WNW 1 0 1 2 6 5 16 56 58 28 2 0 0 1 176 NW 0 0 0 1 3 7 14 64 62 22 5 2 0 3 183 NNW 0 1 1 2 3 4 18 64 59 36 1 0 0 0 189 999 0 0 0 0 0 0 0 0 0 0 0 0 0 15 15 1 4 8 19 85 129 357 937 598 383 93 16 0 33 2663 ccl998.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 5 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 1 2 4 17 47 30 7 4 0 0 1 113 NNE 0 0 0 0 2 7 5 39 46 16 3 4 0 1 123 NE 0 0 1 3 2 3 12 43 18 5 1 2 0 1 91 ENE 0 0 0 0 2 4 16 52 17 2 0 0 0 0 93 E 0 0 1 1 5 5 20 41 7 2 1 0 0 0 83 ESE 0 0 0 1 0 2 15 35 1 2 0 0 0 0 56 SE 0 0 0 0 2 .2 14 59 13 -6 3 0 0 0 99 SSE 0 0 0 1 4 8 14 90 .71 22 2 0 0 2 214 S . 0 0 1 0 5 2 23 81 88 22 1 0 0 12 235 SSW 0 0 2 3 0 0 7 60 138 77 4 0 0 5 296 SW 0 0 1 1 2 7 14 .53 110 74 3 0 0 1 266 WSW 0 0 0 0 3 4 18 37 61 9 0 0 0 2 134 W 0 0 1 0 1 0 10 51 42 3 0 0 0 4 112 WNW 0 1 0 2 2 .5 7 68 86 21 0 0 0 0 192 NW 0 0 0 1 4 4 17 108 89 27 6 0 0 3 259 NNW 0 0 1 0 4 2 15 102 90 20 1 0 0 3 238 999 0 0 0 1 0 1 1 0 0 0 0 0 0 27 30 0 1 8 15 40 60 225 966 907 315 29 6 0 62 2634 ccl998.met JOINT FREQUENCY TABLE FOR 6CM AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 2 6 1 13 22 2 1 0 0 0 1 48 NNE 0 0 0 1 1 2 2 7 3 0 0 1 0 0 17 NE 0 0 1 0. 1. 5 5 4 3 11 9 14 3 0 56 ENE 0 0 0 3 1 3 4 4 2 4 0 0 0 0 21 E 0 0 0 2 5 7 6 2 3 3 2 0 0 0 30 ESE 0 0 0 2 4 1 6 10 0 0 0 0 0 0 23 SE 0 0 0 2 3 0 7 16 3 0 0 0 0 1 32 SSE 0 0 0 1 1 4 9 20 29 3 0 0 0 3 70 S 0 0 0 2 1 4 17 43 42 5 0 0 0 3 117 SSW 0 0 0 1 3 0 6 36 75 14 2 0 0 1 138 SW 0 0 1 3 1 3 10 26 46 34 12 0 0 1 137 WSW 0 1 1 0 0 3 5 24 27 4 0 0 0 0 65 W 0 0 1 3 1 3 5 29 23 0 0 0 0 0 65 WNW 0 0 0 2 1 2 9 46 36 9 2 0 0 1 108 NW 0 0 0 1 3 1 5 38 53 32 19 0 0 8 160 NNW 0 0 0 1 3 2 4 36 18 1 0 0 0 3 68 999 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 1 4 26 35 41 113 363 365 121 46 15 3 23 1156
CA06012 Rev.0 Page 125 of 283 cc1998.met JOINT FREQUENCY TABLE FOR 60M AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 5 10 10 2 0 0 0 0 0 28 NNE 0 1 1 0 2 3 4 2 0. 0 0 0 0 0 13 NE 0 1 1 0 3 2 2 0 0 1 0 0 0 0 10 ENE 0 0 1 0 2 5 3 3 0 0 .0 0 0 0 14 E 0 0 0 0 4 5 2 0 1 0 0 0 0 0 12 ESE 0 0 0 0 4 *2 2 1 0. 0 0 0 0 0 9 SE 0 1 0 0 3 4 8 7 0 0 0 0 0 0 23 SSE 0 1 0 0 1 2 9 5 6 1 0 0 0 0 25 S 0 0 0 0 1 1 3 20 23 1 0 .0 0 0 49 SSW 0 0 1 0 2 1 4 22 43 3 0 0 0 3 79 SW 0 0 0 3 2 6 10 38 19 3 0 0 0 4 85 WSW 0 0 0 1 3 5 10 31 16 1 0 0 0 2 69 W 0 1 0 1 3 3 7 26 11 1 0 0 0 3 56 WNW 0 0 0 1 1 2 7 18 17 1 0 0 0 8 55 NW 0 0 1 0 1 2 5 26 23 3 0 0 0 3 64 NNW 0 1 0 0 0 2 7 15 5 0 0 0 0 0 30 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 6 5 6 33 50 93 224 166 15 0 0 0 23 621 cc1998.met JOINT FREQUENCY TABLE FOR 60M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 NNE 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 NE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ENE 0 0 0 0 0 0 0. 1 0 0 0 0 0 0 1
- E 0 0 0 0 0 0 0 1 0 0 0 0 0 2 3 ESE 0 0 0 0 0 1 0 1 0 0 0 0 0 3 5 SE 0 0 0 0 0 1 0 0 0 0 0 0 0 0 I SSE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 0.0 0 .0 0 0 0 0 SSW 0 0 0 0 0 1 3 0 0 0 0 0 0 1 5 SW 0 0 0 0 0 2 2 0 0 0 0 0 0 0 4 WSW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 999 0 0 0 0 1 1 3 1 0 0 0 0 0 53 59 0 0 0 0 1 7 8 5 0 0 0 0 0 59 80 cc1998.met I JOINT FREQUENCY TABLE FOR 60M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 4 17 32 126 255 144 90 34 7 0 7 716 NNE 0 1 1 2 21 47 107 209 144 127 43 11 0 8 721 NE 0 1 5 8 20 35 91 128 74 55 18 17 3 1 456 ENE 0 1 2 5 15 37 81 128 28 7 0 0 0 0 304 E 0- 1 3 6 29 48 110 120 20 6 3 0 0 2 348 ESE 0 1 0 7 13 20 .70 135 14 4 2 0 0 6 272 SE 0 1 0 3 17 16 67 196 53 13 3 0 0 2 371 SSE 0 2 0 4 9 17 67 244 185 46 2 0 0 17 593 S 0 0 2 2 14 16 66 206 177 38 3 0 0 17 541 SSW 0 1 3 4 6 9 46 190 320 135 11 0 0 .13 728 SW 0 0 4 8 9 29 77 237 255 156 17 0 0 9 801 WSW 0 1 1 1 10 24 67 206 144 20 2 0 0 13 489 W 0 1 2 6 12 13 47 177 125 14 1 0 0 10 408 WNW 1 1 1 7 10 14 40 194 220 72 4 0 0 13 577 NW 0 0 1 3 12 14 44 248 260 88 31 2 0 20 723 NNW 0 2 2 3 11 11 52 244 203 67 2 0 0 10 607 999 0 0 0 1 1 2 4 1 0 0 0 0 0 96 105 1 14 27 74 226 384 1162 3108 2366 938 176 37 3 244 8760
(
CA06012 Rev.0 Page 126 of 283 ccl998.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 1 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 1 4 47 81 7 3 0 0 0 2 145 NNE 0 1 0 0 6 18 73 55 4 0 0.0 0 1 158 NE 0 0 0 0 2 25 68 38 0 0 0 0 0 0 133 ENE 0 0 0 0 5 11 44 4 0 0 0 0 0 0 64 E 0 0 0 1 3 12 43 8 0 0 0 0 0 0 67 ESE 0 0 0 0 1 8 16 1 0 0 0 0 0 2 28 SE 0 0 0 0 0 4 15 29 1 0 0 0 0 0 49 SSE 0 0 0 0 0 1 8 27 6 0 0 0 0 0 42 S 0 0 0 0 0 0 5 12- 1 0 0 0 0 0 18 SSW 0 0 0 0 2 2 6 22 1 0 0 0 0 0 33 SW 0 0 0 1 1 0 8 27 9 0 0 0 0 0 46 WSW 0 0 0 0 0 2 7 26 3 3 0 0 0 0 41 W 0 0 0 0 0 1 2 12 3 .0 0 0 0 0 18 WNW 0 0 0 0 0 0 0 7 3 0 0 0 0 0 10 NW 0 0 0 0 0 0 1 8 1 0 0 0 0 0 10 NNW 0 0 0 2 0 1 5 15 1 0 0 0 0 0 24 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 4 21 89 348 372 40 6 0 0 0 5 886 cc1998.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 2 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 0 0 1 1 3 21 21 2 0 0 0 0 0 50 NNE 0 0 0 0 2 2 24 9 3 0 0 .0 0 0 40 NE 0 0 0 0 0 5 16 10 0 0 0 0 0 0 31 ENE 0 0 0 0 1 3 9 1 0 0 0 0 0 0 14 E 0 0 0 0 1 3 8 1. 0 0 0 0 0 0 13 ESE 0 0 0 0 3 5 5 5 0 0 0 0 0 0 18 SE 0 0 0 0 2 2 6 10 0 0 0 0 0 0 20 SSE 0 0 0 0 0 0. 7 19 2 0 0 0 0 0 28 S 0 0 0 0 0 1 2 4 .1 0 0 0 0. 0 8 SSW 0 0 0 0 0 1 6 3 5 0 0 0 0 0 15 SW 0 0 0 0 0 2 S 15 *6 0 0 0 0 0 28 WSW 0 1 0 0 0 0 5 8 1 0 0 0 0 0 15 W 0 0 0 0 1 0 2 4 0 0 0 0 0 0 7 WNW 0 0 0 0 0 0 3 7 6 0 0 0 0 0 16 NW 0 0 0 0 0 1 1 16 1 0 0 0 0 0 19 NNW 0 0 0 0 0 1 3 9 0 0 0 0 0 0 13 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 1 11 29 123 142 27 0 0 0 0 0 335 cc1998.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 3 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 0 0 2 5 12 21 7 0 0 0 0 0 47 NNE 0 0 0 0 2 5 11 5 1 0 0 0 0 0 24 NE 0 0 0 0 0 5 11 8 1 0 0 0 0 0 25 ENE 0 0 0 0 5 7 12- 4 0 0 0 0 0 0 28 E .0 0 0 0 2 4 7 2 0 0 0 0 0 0 15 ESE 0 0 0 0 1 4 2 0 0 0 0 0 0 0 7 SE 0 0 0 0 2 3 9 7 0 0 0 0 0 0 21 SSE 0 0 0 1 0 2 9 18 1 0 0 0 0 0 31 S 0 0 0 0 0 2 6 3 0 0 0 0 0 0 11 SSW 0 0 0 0 0 1 7 11 3 0 0 0 0 0 22 SW 0 0 0 0 2 3 11 22 4 0 0 0 0 0 42 WSW 0 0 0 0 1 1 10 18 1 0 0 0 0 0 31 W 0 0 0 0 0 1 3 12 1 0 0 0 0 0 17 WNW 0 0 0 0 0 0 3 11 4 0 0 0 0 0 18 NW 0 0 0 0 0 0 5 17 3 . 1 0 0 0 0 26 NNW 0 0 0 0 1 3 4 8 4 0 0 0 0 0 20 999 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 18 46 122 167 30 1 0 0 0 0 385
CA 06012 Rev.0 Page 127 of 283 ccl998.met JOINT FREQUENCY TABLE FOR l0M AND STABILITY CLASS 4 MAXIMUM VELOCITY TIMES 10 DIR 2 S 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 1 2 11 27 60 96 54 16 2 0 0 2 271 NNE 0 0 1 9 13 16 52 91 50 4 1 0 0 0 237 NE 0 0 2 3 15 15 44 109 49 4 0 0 0 0 241 ENE 0 1 1 1 9 20 57 43 3 0 0 0 0 0 135 E 1 3 3 5 18 19 43 11 0 0 0 0 0 0 103 ESE 0 2 1 4' 19 27 44 16 2 0 0 0 0 0 115 SE 0 2 3 5 8 17 67 29 2 1 0 0 0 0 134 SSE 1 1 0 3 9 25 52 85 14 0 0 0 0 0 190 S 0 1 1 6 9 19 32 38 3 0 0 0 0 0 109 SSW 0 2 0 1 16 10 25 37 20 5 0 0 0 0 116 SW 0 0 0 3 10 25 62 69 25 4 0 0 0 0 198 WSW 1 1 0 5 13 20 55 55 3 0 0 0 0 0 153 W 0 1 1 2 10 25 43 51 7 1 0 0 0 0 141 WNW 0 1 2 3 14 16 42 63 30 0 0 0 0 0 171 NW 0 1 2 2 10 12 48 86 17 4 0 0 0 0 182 NNW 0 0 0 1 4 12 38 78 17 3 0 0 0 1 154 999 0 0 0 0 0 0 0 0 0 0 0 0 0 13 13 3 16 18 55 188 305 764 957 296 42 3 0 0 16 2663 ccl998.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS S MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 2 10 18 12 29 20 8 3 0 0 0 0 103 NNE 1 0 1 4 9 15 36 26 1 1 0 0 0 0 94 NE 0 2 2 5 4 6 28 .36 10 6 1 0 0 0 100 ENE 0 1 2 2 12 12 36 32 2 0 0 0 0 0 99 E 0 2 3 5 19 20 21, 12 1 0 0 0 0 0 83 ESE 1 2 3 4 7 18 13 1 2 0 0 0 0 0 51 SE 1 5 2 9 18 27 17 8 2 0O 0 0 0 *90 SSE 0 3 4 5 31 .20 45 35 10 2 0 0 0 0 155 S 2 5 4 9 28 40 85 65 10 0 0 0 0 0 248 SSW 0 9 3 12 24 46 81 110 24 0 0 0 0 0 309 SW 0 2 0 13 35 32 79 137 31 4 0 0 0 0 333 WSW 0 1 4 11 14 22 66 47 2 1 0 0 0 0 168 W 0 4 4 8 23 26 45 32 1 0 0 0 0 0 143 WNW 0 1 3 10 17 30 60 40 8 1 0 0 0 0 170 NW 0 0 2 7 25 52 99 63 16 7 0 0 0 2 273 NNW 0 l 2 0 22 31 64 61 6 0 0 0 0 0 187 999 0 0 0 1 0 1 1 0 0 0 0 0 0 25 28 5 39 41 115 306 410 805 725 134 26 1 0 0 27 2634 cc1998.met JOINT FREQUENCY TABLE FOR 10M AND STABILITY CLASS 6 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 1 1 1 10 5 3 2 1 0 0 0 0 0 24 NNE 0 0 0 3 1 2 5 0 0 0 0 0 0 0 11 NE 0 0 1 5 1 0 2 S 8 15 8 0 0 0 45 ENE 0 1 0 5 2 1 1 5 5 2 0 0 0 0 22 E 0 1 2 2 2 1 1 5 3 0 0 0 0 0 17 ESE 1 1 1 1 4 2 1 0 0 0 0 0 0 0 11 SE 1 2 3 9 12 4 0 1 0 0 0 0 0 0 32 SSE 3 3 4 2 18 12 5 0 0 0 0 0 0 0 47 S 1 5 6 18 16 23 25 4 1 0 0 0 0 0 99 SSW 2 5 3 13 34 44 50 11 2 0 0 0 0 0 164 SW 3 8 5 10 30 36 66 32 15 12 0 0 0 1 218 WSW 4 1 5 4 22 26 28 1 0 0 0 0 0 0 91 W 2 2 6 9 28 22 26 0 0 0 0 0 0 1 96 WNW 0 2 2 3 30 31 30 7 2 1 0 0 0 0 108 NW 0 2 3 2 20 26 23 32 24 19 0 0 0 0 151 NNW 0 0 1 4 6 6 2 0 0 0 0 0 0 0 19 999 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 17 34 43 91 236 241 268 105 61 49 8 0 0 3 1156
CA06012 Rev.0 Page 128 of 283 ccl998.met JOINT FREQUENCY TABLE FOR 1OM AND STABILITY CLASS 7 MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 0 0 1 0 1 1 0 0 0 0 0 0 0 0 3 NNE 0 0 1 1 0 1 0 0 0 0 0 0 0 0 3 NE 0 0 0 0 1 0 0 0 1 0 0 0 0 0 2 ENE 0 0 0 1 0 0 0 0. 0 0 0 0 0 0 1 E 0 3 0 0 0 1 0 1 0 0 0 0 0 0 5 ESE 0 2 0 0 0 0 0 0 0 0 0 0 0 0 2 SE 0 4 0 2 1 0 0 0 0 0 0 0 0 0 7 SSE 1 1 0 1 6 2 0 0 0. 0 0 0 0 0 11 S 0 0 2 9- 20 9 7 0 0 0 0 0 0 0 47 SSW 0 0 2 6 19 39 28 1 0 0 0 0 0 0 95 SW 2 4 4 9 54 58 43 0 0 0 0 0 0 0 174 WSW 1 3 6 11 30 31 11 0 0 0 0 0 0 0 93 W 0 2 4 10 38 31 9 0 0 0 0 0 0 0 94 WNW 1 2 1 4 19 16 3 0 0 0 0 0 0 0 46 NW 0 0 3 0 7 3 14 3 0 0 -0 0 0 0 30 NNW 0 1 1 0 3 1 0 0 0 0 0 0 0 0 6 999 0 1 1 0 0 0 0 0 0 0 0 0 0 0 2 5 23 26 54 199 193 115 5 1 0 0 0 0 0 621 cc1998.met JOINT FREQUENCY TABLE FOR 10M AND NO STABILITY CLASS MAXIMUM VELOCITY TIMES 10 DIR 2 5 7 10 15 20 .30 50 .70 100 130 180 9998 9999 N 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNE 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 NE 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ENE 0 0 0 0 0 0 0 2 0 0 0 0 0 0 2 E 0 0 0 0 0 0 1 1 0 0 0 0 0 2 4 ESE 0 0 0 0 1 0 0 0 0 0 0 0 0 3 4 SE 0 0 0 0 0 1 0 0 0 0 0 0 0 .0 1 SSE' 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 S 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SSW 0 0 0 0 0 2 1 0 0 0 0 0 0 0 3 SW 0 0 0 0 2 1 1 0 0 0 0 0 0 0 4 WSW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 WNW 0 0 0 0 0 0 1 0 0 0 0 0 0 0 1 NW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 NNW 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 999 0 0 0 0 1 2 4 1 0 0 0 0 0 52 60 0 0 0 0 4 7 8 4 0 0 0 0 .0 57 80 cc1998.met JOINT FREQUENCY TABLE FOR 10M AND ALL STABILITY CLASSES MAXIMUM VELOCITY TIMES 10 . DIR 2 5 7 10 15 20 30 50 70 100 130 180 9998 9999 N 1 2 5 14 44 57 172 241 79 22 2 0 0 4 643 NNE 1 1 3 17 33 60 201 186 59 5 1 0 0 1 568 NE 0 2 5 13 23 56 169 206 69 25 9 0 0 .0 577 ENE 0 3 3 9 34 54 159 91 10 2 0 0 0 0 365 E 1 9 8 13 45 60 124 41 4 0 0 0 0 2 307 ESE 2 7 5 9 36 64 81 23 4 0 0 0 0 5 236 SE 2 13 8 25 43 58 114 84 5 2 0 0 0 0 354 SSE 5 8 8 12 64 62 126 184 33 2 0 0 0 0 504 S 3 11 13 42 73 94 162 126 . 16 0 0 0 0 0 540 SSW 2 16 8 32 95 145 204 195 55 5 0 0 0 0 757 SW 5 14 9 36 134 157 275 302 90 20 0 0 0 1 1043 WSW 6 7 15 31 80 102 182 155 10 4 0 0 0 0 592 W 2 9 15 29 100 106 130 111 12 1 0 0 0 1 516 WNW 1 6 8 20 80 93 142 135 53 2 0 0 0 0 540 NW 0 3 10 11 62 94 191 225 62 31 0 0 0 2 691 NNW 0 2 4 7 36 55 116 171 28 3 0 0 0 1 423 999 0 1 1 1 1 3 5 1 0 0 0 0 0 91 104 31 114 128 321 983 1320 2553 2477 589 124 12 0 0 108 8760
CA06012 Rev.0 Page 129 of 283 ATTACHMENT E ARCON96 OUTPUT FILES ADVIACI l.OUr Program
Title:
ARCON96. Developed For U.S.-Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov LA Brown Phone:(301)415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jjamsdellgpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/19/2003 at 09:43:30
**'* ARCON INPUT *******
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 17.2 Building Area (mA2) 2000.0 Effluent vertical velocity (mls) .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (in) .00 Direction .. intake to source (deg) = 294 Wind direction sector width (deg) 90 Wind direction window (deg) 249 - 339 Distance to intake (in) = 50.2 Intake height (m) = 13.9 Terrain elevation difference (m) = .0 Output file names
CA06012 Rev.0 Page 130 of 283 ADVIACI I.out ADVIACIl.jtd Minimum Wind Speed (mfs) .5 Surface roughness length (m) = .20 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in window = 16550 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 863 Hours direction not in windoworcalm = 51634 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER UM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.OOE-02 1.00E-02 1.OOE-02 1.OOE-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.OE-06 1.00E-06 1.00E-06 1.0OE-06 1.00E-06 1.0OE-06 l.OOE-06 ABOVE RANGE 0. . 0. 0. 0. 0. 0. 0. 0. 0. 0. INRANGE 17413. 21199. 26270. 33346. 39246. 50556. 66266. 66553. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 51634. 47673. 42282. 34611. 29164. 17457. 739. 60. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 25.22 30.78 38.32 49.07 . 57.37 74.33 98.90 99.91 100.00 100.00 95th PERCENTILE X/Q VALUES 2.33E-03 2.25E-03 2.12E-03 1.94E-03 1.57E-03 1.15E-03 6.51E-04 5.56E-04 4.71E-04 4.27E-04 95% X/Q for standard.averaging intervals 0 to 2 hours 2.33E-03 2 to 8 hours 1.81 E-03 8 to 24 hours 7.52E-04 I to 4 days 4.86E-04 4 to 30 days 3.92E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 3.13E-03 2.17E-04 SECTOR-AVERAGE 1.83E-03 1.26E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 13) of 283 ADV2AC I I -OUT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 41 5 I1080 e-mail: jyll~nrc.gov J.J.Hayes Phone: (301) 415 3167 e-mail: jjh(~nrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2~nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:jramsdell~pnl.gov Code Documentation: NUREG/CR-6331I Rev. I The program was prepared for an agency of the United States Government. Neither the United States Governmentf nor any agency thereof, nor any of their, employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/19/2003 at 09:44:05 ARCON INPUT ***** Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CCI1992.MET CCI993.MET CCI1994.MET CC1995.MET CCI1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (in) 10.0 Height of upper wind instrument (in) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (in) = 17.2 Building Area (mrA2) 2000.0 Effluent vertical velocity (miVs) - .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (in) - .00 Direction ., intake to source (deg) - 224 Wind direction sector width (deg) 90 Wind direction window (deg) =179 -269 Distance to intake (in) 18.0 Intake height (in) = 13.9 Terrain elevatioti difference (in) - .0 Output file names ADV2ACllI.out ADV2ACI I.jf'd Minimum Wind Speed (mls) = .5 Surface roughness length (in) = .20
CA06012 Rev.0 Page 132 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084
'Hours direction in window - 24257 Hours elevated plume w/ dir. in window - 0 Hours of calm winds - 863 Hours direction not in window or calm - 43927 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPERLIM. 1.OOE-01 1.00E-01 1.00E-01 1.00E-01 1.00E-01 1.OOE-01 1.OOE-01 1.00E-01 1.00E-01 1.00E-01 LOW LIM. 1.00E-OS 1.00E-05 1.00E-05 1.00E-05 1.00E-05 1.00E-05 1.00E-05 1.OOE-05 1.OOE-05 1.00E-05 ABOVE RANGE 0. 0. 0. 0. 0. 0.. 0. 0. 0. 0. IN RANGE 25120. 28860. 33733. 40464. 45882. 54876. 66077. 66570. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 43927. 40012. 34819. 27493. 22528. 13137. 928. 43. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 36.38 41.90 49.21 59.54 67.07 80.68 98.62 99.94 100.00 100.00 95th PERCENTILE X/Q VALUES 1.84E-02 1.78E-02 1.72E-02 1.64E-02 1.32E-02 9.39E-03 6.04E-03 5.22E-03 4.51E-03 4.15E-03 95% X/Q for standard averaging intervals 0 to 2 hours 1.84E-02 2 to 8 hours 1.57E-02 8 to 24 hours 5.91E-03 I to 4 days 4.92E-03 4 to 30 days 3.86E-03 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.26E.02 1.69E-03 SECTOR-AVERAGE 1.32E-02 9.85E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 133 of 283 ADVIAC13.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRCContacts: J.Y.Lee Phone: (301)415 1080 e-rnail: jyll inrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhhnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J.V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/19/2003 at 09:43:40
**++ARCON INPUT *****
Number of Meteorological Data Files - 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1 994.MET CC1995.MET CC1 996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 17.2 Building Area (m^2) - 2000.0 Efuent vertical velocity (m/s) - .00 Vent or stack flow (m^3/s) .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) - 326 Wind direction sector width (deg) 90 Wind direction window (deg) = 281 -011 Distance to intake (m) 24.1 Intake height (m) 16.1 Terrain elevation difference (m) - .0 Output file names ADVIAC13.out ADVIAC13.jfd Minimum Wind Speed (m/s) - .5 Surface roughness length (m) = .20
.CA06012Rev.0 Page 134 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number ofhours of data processed - 70131 Hours of missing data 1084 Hours direction in window - 18670 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 863 Hours direction not in window or calm = 49514 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E.0I I.OOE-01 1.00E-01 1..00I-01 1.OOE-OI .00E-01 l.OOE-0l 1.OOE-01I.LOE-l0 l.00E-O0 LOW LIM. 1.00E-05 1.00E-05 1.00E-05 1.00E-05 1.GOE-05 1.00E-05 1.OOE-05 1.00E-05 1.00E-05 l.00E-05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19533. 23316. 28424. 35287. 40868. 51362. 66190. 66502. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 56. 0. 0. ZERO 49514. 45556. 40128. 32670. 27542. 16651. 815. 55. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 28.29 33.85 41.46 51.93 59.74 75.52 98.78 99.92 100.00 100.00 95th PERCENTILE X/Q VALUES 9.48E-03 9.11E-03 8.73E-03 8.06E-03 6.56E-03 4.72E-03 2.73E-03 2AOE-03 2.07E-03 1.88E-03 95% X/Q for standard averaging intervals 0 to 2 hours 9.48E-03 2 to 8 hours 7.58E-03 8 to 24 hours 3.05E-03 1 to 4 days 2.07E-03 4 to 30 days 1.75E-03.
HOURLY VALUE RANGE MAX XIQ MINX/Q CENTERLINE 1.31E-02 8.58E-04 SECTOR-AVERAGE 7.66E-03 5.OOE-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 135 of 283 ADV2AC13.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyllInrc.gov J.l. Hayes Phone: (301)415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/19/2003 at 09:44:11
**** ARCON INPUT *********
Number of Meteorological Data Files = 8
. Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET . CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0.
Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) e 17.2 Building Area (mr2) 2000.0 Effluent vertical velocity (mns) - .00 Vent or stack flow (mW31s) . = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 123 Wind direction sector width (deg) = 90 Wind direction window (deg) 078 - 168 Distance to intake (m) - 24.1 Intake height (in) 16.1 Terrain elevation difference (m) - .0 Output file names ADV2AC13.out ADV2AC13.jrd Minimum Wind Speed (mis) Surface roughness length (m) .20
CA 06012 Rev.0 Page 136 of 283 Sector averaging constant 4.3 Initial value of sigma y - .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window = 10327 Hours elevated plume w/ dir. in window - 0 Hours of calm winds - 863 Hours direction not in window or calm - 57857 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-0I 1.OOE-01 1.00E-01 t.00E.OI 1.00E-1 I.OOE-01 1.00E-01 1.00E-0 1.OOE-1 1.00E-01 LOW LIM. 1.00E-05 l.OOE-05 1.DOE-05 1.OOE-05 1.00E-05 1.005-05 1.005-05 1.00L-05 1.OOE-05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 11190. 14363. 18795. 25640. 31533. 43744. 64440. 66178. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 56. 0. 0. ZERO 57857. 54509. 49757. 42317. 36877. 24269. 2565. 379. - 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 16.21 20.85 27.42 37.73 46.09 64.32 96.17 99.43 100.00 100.00 95th PERCENTILE X/Q VALUES 8.35E-03 7.54E-03 6.48E-03 5.60E-03 4.44E-03 3.03E403 1.72E-03 1.43E-03 1.18E-03 1.02E-03 95% XIQ for standard averaging intervals 0 to 2 hours 8.35E-03 2 to 8 hours 4.68E-03 8 to 24 hours 1.74E-03 I to 4 days 1.28E-03 4 to 30 days 9.10E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.304-02 1.30E-03 SECTOR-AVERAGE 7.57E-03 7.57E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 137 of 283 ADVISWGI .OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyll1nrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jamsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third partys use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/19/2003 at 09:44:19
**' ARCON INPUT ********
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) I10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 172 Building Area (mA2) 2000.0 Effluent vertical velocity (mtfs) = .00 Vent or stack flow (m"3/s) = .00 Vent or stack radius (in) = .00 Direction .. intake to source (deg) 171 Wind direction sector width (deg) 90 Wind direction window (deg) 126 - 216 Distance to intake (in) 20.0 Intake height (m) = 9.5 Terrain elevation difference (m) - .0 Output file names ADVISWGI.out ADVISWGI .jfd Minimum Wind Speed (mns) = .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 138 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z - .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window - 18583 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm = 49601 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. I 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-01 1.00E-01. 1.00E-01 L.OOE-01 1.00E-01 l.00E-01 1.OOE.0l 1.0E-01 1.00E-01 1.00E-01 LOW LIM. 1.00E-05 1.00E-05 L.OOE-05 I.OOE-05 1.OOE-05 1.00E-05 I.OOE-05 .OOE-05 1.OOE-05 1.OOE-05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19446. 23350. 28328. 34842. 40144. 50300. 65533. 66441. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 49601. 45522. 40224. 33115. . 28266. 17713. 1472. 172. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 28.16 33.90 41.32 51.27 58.68- 73.96 97.80 99.74 100.00 100.00 95th PERCENTILE XIQ VALUES 1.26E-02 1.22E-02 1.16E-02 1.06E-02 8.58E-03 6.05E-03 3.51E-03 3.OOE-03 2.58E-03 2.35E-03 95% X/Q for standard averaging intervals 0 to 2 hours 1.26E-02 2 to 8 hours 1.00E-02 8 to 24 hours 3.75E-03 I to 4 days 2.66E-03 4 to 30 days 2.18E-03 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.66E-02 1.26E-03 SECTOR-AVERAGE 9.68E-03 7.35E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 139 of 283 ADV2SWGI .OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jylII3nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail:jjhQnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/19/2003 at 09:48:46
^" . ARCON INPUT * **
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CCI997.MET CC1998.MET Height of lower wind instrument (in) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (in) - 17.2 Building Area (mr2) - 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mA3is) e .00 Vent or stack radius (m) - .00 Direction.. intake to source (deg) 145 Wind direction sector width (deg) = 90 Wind direction windowv(deg) = 100- 190 Distance to intake (in) = 64.3 Intake height (in) 9.5 Terrain elevation difference (in) = .0 Output file names ADV2SWGI .out ADV2SWGI.jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 140 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z - .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window - 12396 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 863 Hours direction not in window or calm = 55788 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. I 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.GOE-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.OOE-06 1.OE-06 1.00E-06 1.00E-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 13259. 16467. 21011. 27884. 33776. 45575. 64853. 66396. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. O0 0. 0. ZERO 55788. 52405. 47541. 40073. 34634. 22438. 2152. 217. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 19.20 23.91 30.65 41.03 49.37 67.01 96.79 99.67 100.00 100.00 95th PERCENTILE XJQ VALUES 1.36E-03 1.29E-03 1.18E-03 1.03E-03 8.08E-04 5.39E-04 3.01E-04 2.57E-04 2.10E-04 1.86E-04 95% X/Q for standard averaging intervals 0 to 2 hours . 1.36E-03 2 to 8 hours 9.15E-04 8 to 24 hours 2.96E-04 I to 4 days 2.22E-04 4 to 30 days 1.68E-04 HOURLY VALUE RANGE MAX X/Q MINX/Q CENTERLINE 1.93E-03 2.04E-04 SECTOR-AVERAGE 1.12E-03 1.19E-04 NORMAL PROGRAM COMPLETION.
CA06012 Rev.0 Page 141 of 283 ADVI SWG2.OUT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301)415 1080 e-mail: jyllenrc.gov J. J.Hayes Phone: (301) 415 3167 e-mail: jjhbnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/19/2003 at 09:44:24
' ARCON INPUT *******.*
Number of-Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 17.2 Building Area (m^2) 2000.0 Effluent vertical velocity (mrs) = .00 Vent or stack flow (mn3/s) - .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) = 304 Wind direction sector width (deg) 90 Wind direction window (deg) 259 - 349 Distance to intake (m) 64.3 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names ADVISWG2.out ADVISWG2.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 142 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in window' - 16461 Hours elevated plume w/ dir. in window - 0 Hours of calm winds - 863 Hours direction not in window or calm - 51723 DISTRIBUTEON
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 I.OOE-02 1.00E-02 1.001E-02 1.00E-02 1.00E-02 1.00E-02 1.OOE-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 I.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0:. 0. 0. IN RANGE 17324. 20947. 25849. 32822. 38635. 49878. 66191. 66545. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 51723. 47925. 42703. 35135. 29775. 18135. 814. 68. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 25.09 30.41 37.71 48.30 56A8 73.34 98.79 99.90 100.00 100.00 95th PERCENTILE X/Q VALUES 1.45E-03 1.39E-03 1.32E-03 1.22E-03 9.95E-04 7.23E-04 4.09E-04 3.48E-04 2.96E-04 2.68E-04 95% XIQ for standard averaging intervals 0 to 2 hours 1.45E-03 2 to 8 hours 1.15E-03 8 to 24 hours 4.73E-04 I to 4 days 3.04E-04 4 to 30 days 2.46E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.92E-03 1.36E-04 SECTOR-AVERAGE 1.12E-03 7.95E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 143 of 283 ADV2SWG2.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyll nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhgnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2inrc.gov Code Developer. J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdell3pnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/19/2003 at 09:48:51
' ARCON INPUT********
Number of Meteorological Data Files - 8 Meteorological Data File Names CC1991.MET. CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) ' 17.2 Building Area (m^2) - 2000.0 Effluent vertical velocity (rnls) = .00 Verit or stack flow (m^A3s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 278 Wind direction sector width (deg) 90 Wind direction window (deg) = 233 - 323 Distance to intake (m) - 20.0 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names ADV2SWG2.out ADV2SWG2.jfd Minimum Wind Speed (mis) Surface roughness length (m) .20
CA06012 Rev.0 Page 144 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z e .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window = 17839 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 863 Hours direction not in window or calm = 50345 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPERLIM. I.00E-01 L.OOE-01 1.00E-0 1.OOE-01 1.00E-01 I.OOE-0I 1.OOE-0I I.00E-01 1.00E-0! 1.OOE-01 LOW LIM. l.OOE-05 1.OOE-05 1.00E-05 1.OOE-05 I.OOE-05 1.00E-05 I.OOE-05 1.00E-05 1.00E-05 I.OOE-05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 18702. 23250. 29012. 36755. 42920. 53832. 66476. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 50345. 45622. 39540. 31202. 25490. 14181. 529. 0. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 27.09 33.76 42.32 54.09 62.74 79.15 99.21 100.00 100.00 100.00 95th PERCENTILE X/Q VALUES 1.24E.02 1.18E-02 1.09E.02 9.86E-03 7.97E-03 S.76E-03 3.31E-03 2.81E-03 2.43E-03 2.22E-03 95% X/Q for standard averaging intervals 0 to 2 hours 1.24E-02 2 to 8 hours 9.03E-03 8 to 24 hours 3.71 E-03 1 to 4 days 2.49E-03 4 to 30 days 2.05E-03 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.66E.02 1.07E-03 SECTOR-AVERAGE 9.68E.03 6.25E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 145 of 283 ADVITB.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11.00 a.m. NRCContacts: J.Y.Lee Phone: (301)415 1080 e-mail: jyll nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhbnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer. J. V. Ramsdell Phone: (509) 372 6316 e-mail:j_ramsdel1@pnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 16.07:02
- ARCON INPUT *********
.Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC199S.MET CC1996.MET CC1997.MET CCI 998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 17.2 Building Area (mA2) 2000.0 Effluent vertical velocity (mrs) = .00 Vent or stack flow (mA3/s) e .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 264 Wind direction sector width (deg) 90 Wind direction window (deg) 219 - 309 Distance to intake (m) .37.5 Intake height (in) = .9 Terrain elevation difference (m) - .0 Output file names ADVITB.out ADVITB.jfd Minimum Wind Speed (mls) = .5 Surface roughness length (in) = .20
CA 06012 Rev.0 Page 146 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window 19977 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm 48207 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.00E-02 I.OOE-02 1.OOE-02 1.OOE-02 .00E-02 L.OOE-02 I.OOE-02 1.OOE-02 1.00E-02 I.OOE-02 LOW LIM. 1.00E-06 1.OOE-06 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.OOE-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 20840. 25825. 31948. 40035. 46268. 56472. 66453. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 48207. 43047. 36604. 27922. 22142. 11541. 552. 0. 0. 0. TOTALXlQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 30.18 37.50 46.60 58.91 67.63 83.03 99.18 100.00 100.00 100.00 95th PERCENTILE X1Q VALUES 3.70E-03 3.55E-03 3.34E-03 3.01E-03 2.41E-03 1.69E-03 1.04E-03 8.75E-04 7.52E-04 6.85E-04 95% X/Q for standard averaging intervals 0 to 2 hours 3.70E-03 2 to 8 hours 2.78E-03 8 to 24 hours 1.03E-03 I to 4 days 8.24E-04 4 to 30 days 6.31 E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 4.70E-03 3.49E-04 SECTOR-AVERAGE 2.74E-03 2.03E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 147 of 283 ADV2TB.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyllnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:j_rarnsdellepn1.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/VI12003 at 16:07:07
*******ARCON INPUT ********
Number of Meteorological Data Files -- 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) _ 17.2 Building Area (mA2) 2000.0 Effuent vertical velocity (mis) - .00 Vent or stack flow (m'3/s) .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) - 186 Wind direction sector width (deg) 90 Wind direction window (deg) 141 - 231 Distance to intake (m) 37.5 Intake height (m) - .9 Terrain elevation difference (m) .0 Output file names ADV2TB.out ADV2TB.jfd Minimum Wind Speed (m/s) .5 Surface roughness length (m) .20
CA06012 Rev.0 Page 148 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in window = 23334 Hours elevated plume wi dir. in window - 0 Hours of calmwinds - 863 Hours direction not in window or calm 44850 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. l.OOE-02 1.00E-02 1.OOE.02 1.00E-02 1.00E-02 I.OOE-02 1.00E.02 I.OOE-02 1.OOE-02 l.00E-02 LOW LIM. l.OOE.06 1.00E-06 1.OOE.06 1.00E-06 1.00E-06 I.OOE-06 I.OOE-06 1.OOE-06 1.OE-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 24197. 28050. 32670. 38614. 43421. 52501. 65559. 66443. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0.. 0. 0. 0. 0.
- ZERO 44850. 40822. 35882. 29343. 24989. 15512. 1446. 170. 0. 0.
TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013.. 67005. 66613. 67247. 67747.
% NON ZERO 35.04 40.73 47.66 56.82 63.47 77.19 97.84 99.74 100.00 100.00 95th PERCENTILE X/Q VALUES 3.83E-03 3.72E-03 3.59E-03 3.39E-03 2.77E-03 2.01E-03 1.25E.03 1.07E-03 9.27E04' 8.53E-04 95% X/Q for standard averaging intervals 0 to 2 hours 3.83E-03 2 to 8 hours 3.25E-03 8 to 24 hours 1.32E-03 I to 4 days 9.92E-04 4 to 30 days 7.92 E-04 HOURLY VALUE RANGE, MAX XIQ MIN X/Q CENTERLINE 4.70E-03 3.76E.04 SECTOR-AVERAGE 2.74E.03 2.19E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 149 of 283 ADVIWR.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J.Y. Lee Phone: (301) 415 1080 e-mail: jyll nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. ProgramRun 8/11/2003 at 16:06:50
***' ARCON INPUT '
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC 1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 17.2 Building Area (m'2) 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mA3/s) - .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) = 023 Wind direction sector width (deg) = 90 Wind direction window (deg) - 338 -068 Distance to intake (m) = 62.9 Intake height (m) 9.1 Terrain elevation difference (m) = .0 Output file names ADVI WR.out ADVI WR.jfd Minimum Wind Speed (m/s) e .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 150 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window - 17720 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm - 50464 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. I 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-02 1.OOE-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.OOE-02 1.OOE-02 1.00E-02 l.00E-02 LOW LIM. 1.OOE-06 I.OOE-06 1.OOE-06 1.OOE-06 1.O0E-06 I.OOE-06 1.O0E-06 1.00E-06 1.OOE-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. '0. 0. 0. 0. 0. 0. IN RANGE 18583. 21774. 26240. 32641. 38145. 48434. 65369. 66454. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 50464. 47098. 42312. 35316.. 30265. 19579. 1636. 159. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 26.91 31.62 38.28 48.03 55.76 71.21 97.56 99.76 100.00 100.00 95th PERCENTILE X/Q VALUES 1.40E-03 1.36E-03 1.28E-03 1.16E-03 9.56E-04 7.03E-04 4.37E-04 3.74E-04 3.05E-04 2.70E-04.
95% X/Q for standard averaging intervals 0 to 2 hours 1.40E-03 2 to 8 hours I.08E-03 8 to 24 hours 4.73E-04 I to 4 days . 3.48E-04 4 to 30 days 2.44E-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 2.00E-03 1.41 E-04 SECTOR-AVERAGE 1.17E-03 8.21E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 151 of 283 ADV2WROUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, i 997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl1enrc.gov I. J. Hayes Phone: (301) 415 3167 e-mail: jjhsnrc.gov LA Brown Phone:(301)415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jjramsdellpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 16:06:55
'a** ARCON INPUT "
Number-of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 17.2 Building Area (mA2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mn3/s) e .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) - 067 Wind direction sector width (deg) 90 Wind direction window (deg) - 022 - 112 Distance to intake (m) 62.9 Intake height (m) = 9.1 Terrain elevation difference (m) .0 Output file names ADV2WRout ADV2WR.jfd Minimum Wind Speed (mis) - .5 Surface roughness length (m) - .20
CA 06012 Rev.0 Page 152 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total nuniber of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window - 12158 Hours elevated plume wI dir. in window - 0 Hours of calm winds 863 Hours direction not in window or calm = 56026 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.OOE02 1.00E-02 E .02E 2 1.00E-02 1.00E-02 1.0011.O2E-. 1.OEE-0 0E22 2 1.00E402 1..E-02 LOW LIM. 1.00E-06 1.000 I.OOEE06 E6 1.OOE-06 I.00E06 l.0LE-06 I.OOE-06 I.OOE 6E01.0 1.0E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 13021. 16242. 20742. 27253. 32734. 43448. 63914. 66009. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 56026. 52630. 47810. 40704. 35676. 24565. 3091. 604. 0. 0. TOTAL XQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 18.86 23.58 30.26 40.10 47.85 63.88 95.39 99.09 100.00 100.00 95th PERCENTILE X/Q VALUES 1.35E-03 1.28E-03 1.17E-03 1.04E-03 8.38E-04 5.99E-04 3.39E-04 2.84E-04 2.23E.04 1.89E-04 95% XJQ for standard averaging intervals 0 to 2 hours 1.35E-03 2 to 8 hours 9.39E-04 8 to 24 hours 3.78E-04 I to 4 days 2.52E-04 4 to 30 days 1.66E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.00E-03 1.41E-04 SECTOR-AVERAGE 1.17E-03 8.21 E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 153 of 283 CODIACI I.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 am. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllsnrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhbnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: j_ramsdellspnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/2112003 at 10:44:47
*+** ARCON INPUT ********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 2.5 Building Area (mW2) - 2000.0 Effluent vertical velocity (mrs) .00 Vent or stack flow (mA3/s) .00 Vent or stack radius (m) .00 Direction.. intake to source (deg) 290 Wind direction sector width (deg) 90 Wind direction window (deg) = 245 -335 Distance to intake (m) 92.6 Intake height (m) 13.9 Terrain elevation difference (m) - .0 Output file names CODIACI l.out CODIACI I.jfd Minimum Wind Speed (mis) .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 154 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data - 1084 Hours direction in window - 16700 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 1000 Hoursdirectionnotinwindoworcalm - 51347 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 LOW LIM. 1.OOE-07 1.OOE-07 1.OOE-07 1.00E-07 1.OOE-07 1.00E-07 1.00E-07 1.00E-07 1.00E-07 1.OOE-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 17700. 21716. 27008. 34310. 40353. 51627. 66455. 66583. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 51347. 47156. 41544. 33647. 28057. 16386. 550. 30. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 25.63 31.53 39.40 50.49 58.99 75.91 99.18 99.95 100.00 100.00 95th PERCENTILE X/Q VALUES 6.88E-04 6.73E-04 6.42E-04 5.89E-04 4.81E-04 3.53E-04 2.01E-04 1.72E-04 1.47E-04 1.32E-04 95% X/Q for standard averaging intervals 0 to 2 hours 6.88E-04 2 to 8 hours 5.56E-04 8 to 24 hours 2.35E-04 I to 4 days 1.50E-04 4 to 30 days 1.21 E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 9.56E-04 7.84E-05 SECTOR-AVERAGE 5.57E-04 4.57E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 155 of 283 COD2ACI I.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: ijhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:j_ramsdellpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/2112003 at 10:45:13
' ARCON INPUT**********
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CCI998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 2.5 Building Area (m^2) = 2000.0 Effluent vertical velocity (m.s) = .00 Vent or stack flow (mW3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) - 181 Wind direction sector width (deg) = 90 Wind direction window (deg) = 136 - 226 Distance to intake (m) 54.0 Intake height (m) - 13.9 Terrain elevation difference (m) = .0 Output file names COD2ACl l.out COD2AC1 I jfd Minimum Wind Speed (m/s) Surface roughness length (m) fi .20
CA06012 Rev.0 Page 156 of 283 Sector averaging constant = 43 Initial value of sigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window - 21981 Hours elevated plume wI dir. in window = 0 Hours of calm winds = 1000 Hours direction not in window or calm - 46066 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 I .OOE-02 1.GOE-02 1.00E-02 1.00E-02 i.OOE-02 1.00E-02 1.001E-02 1.00E-02 1.OOE-02 LOW LIM. I.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 22981. 26854. 31581. 37668. 42642. 52044. 65690. 66453. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. . 0. 0. 0. ZERO 46066. 42018. 36971. 30289. 25768. 15969. 1315. 160. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 33.28 38.99 46.07 55.43 62.33 76.52 98.04 99.76 100.00 100.00 95th PERCENTILE X/Q VALUES 2.01E-03 1.97E-03 1.92E-03 1.81E-03 IA8E-03 1.07E-03 6.45E-04 5.57E-04 4.78E-04 4.35E-04 95% X/Q for standard averaging intervals 0 to 2 hours 2.01 E-03 2 to 8 hours 1.74E-03 8 to 24 hours 7.04E-04 I to 4 days 5.03E-04 4 to 30 days 4.03E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.62E-03 2.41 E-04 SECTOR-AVERAGE 1.53E-03 1.40E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 157 of 283 CODIACI3.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl l enrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhbnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer. J. V. Ramsdell Phone: (509) 372 6316 e-mail:j.ramsdel1epn1.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:45:01
***+ ARCON INPUT *******
Number of Meteorological Data Files B Meteorological Data File Names CC1991.MET CCI992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 2.5 Building Area (mW2) - 2000.0 Effluent vertical velocity (m/s) = .00 Vent or stack flow (m"3/s) - .00 Vent or stack radius (m) = .00 Direction.. intake to source (deg) e 300 Wind direction sector width (deg) = 90 Wind direction window (deg) = 255 -345 Distance to intake (m) = 62.7 Intakeheight (m) 16.1 Terrain elevation difference (m) - .0 Output file names CODIAC13.out CODIAC13.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 158 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed= 70131 Hours of missing data = 1084 Hours direction in window - 16446 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 1000 Hours direction not in windoworcalm - 51601 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-02 1.O0-2 I.00E.02 I.OOE.02 I.00E2 1.OOE.02 1.00E42 1.OOE2 1 .00E-02 .OOE-02 LOW LIM. 1.OOE-06 1.00E-06 1.00E-06 1.00E.06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. INRANGE 17446. 21164. 26121. 33102. 38935. 50173. 66311. 66578. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 51601. 47708. 42431. 34855. 29475. 17840. 694. 35. 0. 0. TOTAL XQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 25.27 30.73 . 38.10 48.71 56.91 73.77 98.96 99.95 100.00 100.00 95th PERCENTILE XIQ VALUES .41E403 1.37E-03 1.31E403 1.21E-03 9.88E-04 7.24E-04 4.08E-04 3.49E-04 2.96E-04 2.67E.04 95% X/Q for standard averaging intervals 0 to 2 hours 1.41 E-03 2 to 8 hours 1.15E-03 8 to24 hours 4.81E-04 I to 4 days 3.03E-04 4 to 30 days 2.46E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE .1.96E-03 1.56E-04 SECTOR-AVERAGE 1.14E-03 9.07E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 159 of 283 COD2AC13.0UT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllInrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jhsnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results ofsuch use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:45:08
**+*** ARCON INPUT *********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 2.5 Building Area (m^2) = 2000.0 Effluent vertical velocity (mrs) - .00 Vent or stack flow (mA3/s) - .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) = 150 Wind direction sector width (deg) - 90 Wind direction window (deg) 105- 195 Distance to intake (m) = 62.7 Intake height (m) 16.1 Terrain elevation difference (m) - .0 Output file names COD2AC 13.out COD2AC13.jfd Minimum Wind Speed (mls) = .5 Surface roughness length (m) .20
CA06012 Rev.0 Page 160 of 283 Sector averaging constant 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data - 1084 Hours direction in window = 13143 Hours elevated plume w/ dir. in window 0O Hours of calm winds = 1000 Hours direction not in window or calm = 54904 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER 1 2 4 8 12 .24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E402 1.00E-02 .OOE-02 1.OOE-02 1.00E-02 LOW LLM. L.OOE-06 1.OOE-06 .OOE-06 L.00E-06 1.0 6 1.OOE-06 1. 6 1.00E-06 1.00E-06 1.00E406 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. INRANGE 14143. 17482. 22144. 29095. 34963. 46505. 65190. 66462. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 54904. 51390. 46408. 38862. 33447. 21508. 1815. 151. 0. 0. TOTALXlQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 20.48 25.38 32.30 42.81 51.11 68.38 97.29 99.77 100.00 100.00 95th PERCENTILE X/Q VALUES 1.36E-03 1.30E-03 1.21E-03 1.07E-03 8.45E404 5.68E-04 3.13E-04 2.72E404 2.21E-04 1.95E-04 95% XIQ for standard averaging intervals 0 to 2 hours 1.36E-03 2 to 8 hours 9.74E-04 8 to 24 hours 3.17E-04 I to 4 days 2.28E-04 4 to 30 days 1.77E-04 HOURLY VALUE RANGE MAX X/Q MIN XIQ CENTERLINE 1.94E-03 2.14E-04 SECTOR-AVERAGE 1.13E403 1.25E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 161 of 283 CODISWGL.OUT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J.J.Hayes Phone:(301)4153167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jamsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third partys use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:45:22
**** ARCON INPUT *********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 2.5 Building Area (mW2) - 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mA3/s) - .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) = 257 Wind direction sector width (deg) = 90 Wind direction window (deg) 212 - 302 Distance to intake (m) = 39.1 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names CODISWGI.out CODISWGIjfd Minimum Wind Speed (m/s) .5 Surface roughness length (m) .20
CA406012 Rev.0 Page 162 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window = 21165 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 1000 Hours direction not in window or calm = 46882 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.OOE-02 I.OOE2 1.00E-02 1.OOEL 2 1.002E02 1.00E-02 1.00E-02 1.OOE-02 1.00E-02 1.00E-02 LOW LIM. 1.00E-06 1.OOE-06 1.OOE-06 1.OOE-06 l.00E-06 1.OOE-06 1.OOE-06 1.002-06 1.002-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 22165. 26989. 32971. 40791. 46921. 56597. 66304. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 46882. 41883. 35581. 27166. 21489. 11416. 701. 0. 0. 0. TOTALXIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 32.10 39.19 48.10 60.02 68.59 83.21 98.95 100.00 100.00 100.00 95th PERCENTILE XIQ VALUES 3.74E-03 3.65E-03 3.48E-03 3.17E-03 2.54E-03 1.79E-03 1.IE-03 9.42E-04 8.09E-04 7.36E-04 95% X/Q for standard averaging intervals 0 to 2 hours 3.74E-03 2 to 8 hours 2.982-03 8 to 24 hours 1.11E-03 I to 4 days 8.88E-04 4 to 30 days 6.77E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 4.96E-03 4.14E-04 SECTOR-AVERAGE 2.89E-03 2.41E-04 NORMALPROGRAM COMPLETION
CA 06012 Rev.0 Page 163 of 283 COD2SWGI .OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhlnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 c-mail: j_ramsdellepnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:45:38
***+*+* ARCON INPUT *****
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) e 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 2.5 Building Area (m^'2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (m"31s) - .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) - 153 Wind direction sector width (deg) - 90 Wind direction window (deg) 108 - 198 Distance to intake (m) t 105.5 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names COD2SWGI .out COD2SWGI.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) .20
CA06012 Rev.0 Page 164 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window = 13726 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 1000 Hours direction not in window or calm = 54321 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 .96 168 360 720 UPPER LIM. 1.OOE-03 1.00E-03 1.OOE-03 l.00E-03 1.00E-03 1.OOEE03 1.00E-03 I.OOE-03 1.OOE-03 1.00E-03 LOW LIM. l.GOE-07 1.002-07 1.00E-07 1.00E-07 1.00E-07 1.00E-07 i.00E-0 07 1.00E-07 1.00E-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 14726. 18163. 22905. 29865. 35678. 47066. 65243. 66466. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. . 0. ZERO 54321. 50709. 45647. 38092. 32732. 20947. 1762. 147. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 21.33 26.37 33.41 43.95 52.15 69.20 97.37 99.78 100.00 100.00 95th PERCENTILE X/Q VALUES 5.36E-04 5.15E-04 4.85E-04 4.32E-04 3.43E-04 2.31E-04 1.27E-04 1.1IE-04 9.05E-05 8.09E-05 95% X/Q for standard averaging intervals 0 to 2 hours 5.36E-04 2 to 8 hours 3.97E-04 8 to 24 hours 1.30E-04 I to 4 days
- 9.31 E-05 4 to 30 days 7.38E-05 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 7.48E-04 8.60E-05 SECTOR-AVERAGE 4.36E-04 5.01E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 16S of 283 CODI SWG2.OUT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl lnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhsnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2inrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:45:27
*** ARCON INPUTf"**"* ""***
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1 996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 2.5 Building Area (mA2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (rnA3/s) . .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 297 Wind direction sector width (deg) 90 Wind direction window (deg) 252 - 342 Distance to intake (m) 105.5 Intake height (m) 9.5 Terrain elevation difference (m) .0 Output file names CODI SWG2.out CODISWG2.jfd Minimum Wind Speed (m/s) - .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 166 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window - 16435 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 1000 Hours direction not in window or calm = 51612 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-03 1.00E-03 1.00E-03 l.OOE-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 LOW LIM. 1.OOE-07 1.OOE-07 1.OOE-07 1.00E-07 1.00E-07 1.OOE-07 1.OE-07 1.OOE-07 l.OOE-07 1.00E-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 17435. 21203. 26232. 33257. 39130. 50425. 66262. 66553. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 35. 0. 0. ZERO 51612. 47669. 42320. 34700. 29280. 17588. 743. 25. 0. 0. TOTALXIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 25.25 30.79 38.27 48.94 57.20 74.14 98.89 99.96 100.00 100.00 95th PERCENTILE X/Q VALUES 5.SIE-04 5.31E-04 5.09E-04 4.73E-04 3.86E-04 2.83E-04 1.60E-04 1.38E-04 1.17E-04 1.06E-04 95% X/Q for standard averaging intervals 0 to 2 hours 5.51E-04 2 to 8 hours 4.48E-04 8 to 24 hours 1.88E-04 I to 4 days 1.19E-04 4 to 30 days 9.73E-05 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 7.53E-04 6.23E-05 SECTOR-AVERAGE 4.39E-04 3.63E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 167 of 283 COD2SWG2.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyll nrc.gov J..J. Hayes Phone:(301)4153167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jyamsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run .8/21/2003 at 10:45:33
' ARCON INPUT *********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 2.5 Building Area (m12) = 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mA3Is) .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 192 Wind direction sector width (deg) 90 Wind direction window (deg) e147 -237 Distance to intake (m) = 39.1 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names COD2SWG2.out COD2SWG2 jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 168 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window = 24472 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 1000 Hours direction not in window or calm = 43575 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24
- 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 I .OOE-02 1.OOE-02 I .OOE02 1.00E-02 1.00E-02 .E-02 .OOEI -02 1.00E-02 LOW LIM. 1.OOE-06 1.00E-06 I .OOE-06 1.OOE-06 I.00E.06 1.00E-06 I.00E-06 I.OOE-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0, 0. 0. 0.
IN RANGE 25472. 29370. 33879. 39626. 44321. 53183. 65681. 66456. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 43575. 39502. 34673. 28331. 24089. 14830. 1324. 157. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247.. 67747.
%NONZERO *36.89 .42.64 49.42 58.31 64.79 78.20 98.02 99.76 100.00 100.00 95th PERCENTILE X/Q VALUES 3.82E-03 3.77E-03 3.70E-03 3.52E-03 2.90E-03 2.12E.03 1.31E-03 1.14E-03 9.91E-04 9.04E-04 95% X/Q for standard averaging intervals 0 to 2 hours 3.82E-03 2 to 8 hours 3.42E03 8 to 24 hours 1.42E-03 I to 4 days 1.04E-03 4 to 30 days 8.41E.04 HOURLY VALUE RANGE MAX X(Q MIN XIQ CENTERLINE 4.96E-03 4.44E-04 SECTOR-AVERAGE 2.89E-03 2.59E04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 169 of 283 CODITB.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11.00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J. J. Hayes Phone: (301) 415 3167 c-mail: jjhhnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:j ramsdellspnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their. employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11(2003 at 16:25:33
"""' ARCON INPUT ""*"
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC) 997.MET CC1998.MET Height of lower wind instrument (in) 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 2.5 Building Area (mA2) - 2000.0 Effluent vertical velocity (m/s) = . 00 Vent or stack flow (mrn3Is) .00 Vent or stack radius (mi) .00 Direction .. intake to source (deg) 275 Wind direction sector width (deg) 90 Wind direction window (deg) 230 - 320 Distance to intake (m) - 78.7 Intake height (m) - .9 Terrain elevation difference (m) - .0 Output file names CODITB.out CODITB.jfd Minimum Wind Speed (m/s) - .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 170 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z e .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data - 1084 Hours direction in window = 18115 Hours elevated plume w/dir. in windowi = 0 Hours of calm winds = 1000 Hours direction not in window or calm - 49932 D[STRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE.02 1.OOE-02 I.00E-02 I.OOE-02 1.00E-02 1.OOE-02 1.OOE-02 1.OOE-02 1.00E-02 1.OOE-02 LOW LIM. l.OOE-06 1.OOE-06 1.00E.06 1.00E.06 l.OOE-06 1.00E-06 l.OOE-06 l.OOE-06 1.OOE-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19115. 23776. 29711. 37664. 43958. 54776. 66470. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 49932. 45096. 38841. 30293. 24452. 13237. 535. 0. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 27.68 34.52 43.34 55.42 64.26 80.54 99.20 I60.00 100.00 100.00 95th PERCENTILE X/Q VALUES 9.83E-04 9.37E-04 8.78E-04 7.99E-04 6.48E-04 4.69E-04 2.72E-04 2.31E.04 2.OOE-04 1.81E-04 95% X/Q for standard averaging intervals 0 to 2 hours 9.83E-04 2 to 8 hours 7.38E-04 8 to 24 hours 3.04E-04 I to 4 days 2.07E-04 4 to 30 days 1.67E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.32E-03 1.06E-04 SECTOR-AVERAGE 7.71E-04 6.20E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 171 of 283 COD2TB.OUT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J.J.Hayes Phone:(301)4153167 e-mail:jjhsnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdell1pnl.gov Code Documentation: NUREGICR-6331.Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 16:25:38
*'***** ARCON INPUT *********
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC 1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (in) = 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (in) - 2.5 Building Area (mW2) - 2000.0 Effluent vertical velocity (mls) = .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) * .00 Direction .. intake to source (deg) - 175 Wind direction sector width (deg) e 90 Wind direction window (deg) 130 - 220 Distance to intake (m) 78.7 Intake height (m) .9 Terrain elevation difference (in) = .0 Output file names COD2TB.out COD2TB.jfd Minimum Wind Speed (mis) - .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 172 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in window - 20007 Hours elevated plume w/ dir. in window = 0 Hours of calm winds =1000 Hours direction not in window or calm = 48040 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. I 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 I.OOE-02 1.00E-02 1.OOE-02 1.00E-02 1.00E-02 I.OOE-02 L.OOE-02 1.OOE-02 L.OOE-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E46 1.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 21007. 24954. 29881. 36229. 41393. 51237. 65766. 66524. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 48040. 43918. 38671. 31728. 27017. 16776. 1239. 89. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 30.42 36.23 43.59 53.31 60.51 75.33 98.15 99.87 100.00 100.00 95th PERCENTILE X/Q VALUES 1.02E-03 9.87E-04 9.53E-04 8.90E-04 7.26E-04 5.20E.04 3.03E-04 2.61E-04 2.26E-04 2.05E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.02E-03 2 to 8 hours 8.48E-04 8 to 24 hours 3.34E-04 I to 4 days 2.31 E-04 4 to 30 days 1.90E-04 HOURLY VALUE RANGE MAX XIQ *MINX/Q CENTERLINE 1.32E-03 1.24E-04 SECTOR-AVERAGE 7.70E-04 7.25E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 173 of 283 CODIWR.OUT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office ofNuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRCContacts: J.Y.Lee Phone: (301)415 1080 e-mail: jyll nrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail:jjhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:j ramsdellcpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 16:25:21
*++* ARCON INPUT *
- Number of Meteorological Data Files .= 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) . 2.5 Building Area (mA2) = 2000.0 Effluent vertical velocity (m's) .00 Vent or stack flow (mW3/s) .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 347 Wind direction sector width (deg) 90 Wind direction window (deg) - 302 - 032 Distance to intake (m) 71.1 Intake height (m) 9.1 Terrain elevation difference (m) - .0 Output file names CODIWR-out CODI WR.jfd Minimum Wind Speed (Wis) .5 Surface roughness length (m) - .20
CA 06012 Rev.0 Page 174 of 283 Sector averaging constant = 4.3 Initial value of sigma y - .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window . = 19574 Hours eevated plume w/ dir. in window 0 Hours of calm winds - 1000 Hours direction not in window or calm = 48473 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER.' 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1 OOE42 1.00E-02 .. 1.OOE-02 1.00 .OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 LOW LIM. 1.00E-06 1.00E-06 L.OOE-06 1.00E-06 1.O0E-06 1.00E406 1.00E-06 1.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 20574. 24582. 29712. 36479. 42063. 52206. 66245. 66580. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 48473. 44290. 38840. 31478. 26347. 15807. 760. 33. 0. 0. TOTAL XlQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 29.80 35.69 43.34 53.68 61.A9, 76.76 98.87 99.95 100.00 100.00 95th PERCENTILE X/Q VALUES 1.16E-03 1.12E-03 1.07E-03 1.00E-03 8.16E-04 5.94E-04 3.51E-04 3.14E-04 2.71E-04 2.SIE-04 95% XIQ for standard averaging intervals 0 to 2 hours 1.16E-03 2 to 8 hours 9.49E-04 8 to 24 hours 3.90E-04 I to 4 days 2.70E-04 4 to 30 days 2.36E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE. 1.59E-03 1.28E-04 SECTOR-AVERAGE 9.29E-04 7.48E-05 NORMAL PROGRAM COMPLETION
CAO06012Rev.0 Page 175 of 283 COD2WR.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyll nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhhnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 16:25:26
*+** ARCON INPUT ********
Number of Meteorological Data Files - 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) ^ 2.5 Building Area (mW2) 2000.0
. Effluent vertical velocity (mis) .00 Vent or stack flow (mW3Is) .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) - 103 Wind direction sector width (deg) 90 Wind direction window (deg) 058 - 148 Distance to intake (m) 71.1 Intake height (m) 9.1 Terrain elevation difference (m) - .0 Output file names COD2WR.out COD2WR.jfd Minimum Wind Speed (mls) = .5 Surface roughness length (m) e .20
CA 06012 Rev.0 Page 176 of 283 Sector averaging constant 4.3 Initial value of sigma y - .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window - 8956 Hours elevated plume w/ dir. in window - 0 Hours of calm winds 1000 Hours direction not in window or calm - 59091 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.OOE-02 1.OOE-02 I.OOE-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 L.OOE-06 1.00E-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. INRANGE 9956. 13074. 17536. 24277. 30012. 42110. 63909. 66092. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 13. 0. 0. ZERO 59091. 55798. 51016. 43680. 38398. 25903. 3096. 508. 0. 0. TOTAL XtQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 14.42 18.98 25.58 35.72 43.87 61.91 95.38 99.24 100.00 100.00 95th PERCENTILE X/Q VALUES 9.90E-04 8.83E-04 7.73E-04 6.61E-04 5.27E-04 3.67E-04 2.06E-04 1.73E-04 1.36E-04 1.17E-04 95% X/Q for standard averaging intervals 0 to 2 hours 9.90E-04 2 to 8 hours 5.51 E-04 8 to 24 hours 2.20E-04 I to 4 days 1.53E-04 4 to 30 days 1.03E-04 HOURLY VALUE RANGE MAX XIQ MIN JXQ CENTERLINE l.52E-03 1.80E-04 SECTOR-AVERAGE 8.89E-04 1.05E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 177 of 283 CTMTIACI L.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jylllnrc.gov J.J. Hayes Phone: (301)415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: j.ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/15/2003 at 08:50:28
*** ARCON INPUT
- Number of Meteorological Data Files - 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) I10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 29.7 Building Area (m12) 2000.0 Effluent vertical velocity (mls) = .00 Vent or stack flow (rn31s) .00-Vent or stack radius (m) .00 Direction .. intake to source (deg) - 283 Wind direction sector width (deg) 90 Wind direction window (deg) 238 - 328 Distance to intake (m) 53.2 Intake height (m) 13.9 Terrain elevation difference (m) - .0 Output file names CTMTIACI L.out CTMTIACI I.jfd Minimum Wind Speed (mrs) .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 178 of 283 Sector averaging constant 4.3 Initial value of sigma y 6.99 Initial value of sigma z 5.18 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window = 17292 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm = 50892 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 I.00E-02 L.OOE-02 I.OOE-02 1.OOE-03 1.00E-03 L.OOE-03 L.OOE-03 L.OOE-03 I.00E-03 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-07 1.00E-07 1.00E-07 1.OOE-07 1.00E-07 I.OOE-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 18155. 22535. 28126. 35749. 41910. 53005. 66497. 66583. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 50892. 46337. 40426. 32208. 26500. 15008. 508. 30. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. . 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 26.29 32.72 41.03 52.61 61.26 77.93 99.24 99.95 100.00 100.00 95th PERCENTILE X/Q VALUES 9.19E-04 8.67E-04 7.83E-04 6.94E-04 5.56E-04 3.94E-04 2.33E-04 2.01E-04 1.73E-04 1.61E-04 95% X/Q for standard averaging intervals 0 to 2 hours 9.19E-04 2 to 8 hours 6.19E-04 8 to 24 hours 2.44E-04 I to 4 days 1.80E-04 4 to 30 days 1.50E-04 HOURLY VALUE RANGE MAX XIQ MIN XIQ CENTERLINE 1.08E-03 8.84E-05 SECTOR-AVERAGE 6.32E-04 5.15E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 179 of 283 CTMT2ACI I.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyll nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhhnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/1512003 at 08:50:40
" ARCON INPUT **"""
Number of Meteorological Data Files = 8 Meteorological Data File Names CCI99l.MET CC1992.MET CC1993.MET CCI994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 29.7 Building Area (m^2) 2000.0 Effluent vertical velocity (m/s) - .00 Vent or stack flow (mA3/s) - .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) = 202 Wind direction sector width (deg) 90 Wind direction window (deg) = 157-247 Distance to intake (m) = 21.5 Intake height (m) = 13.9 Terrain elevation difference (m) - .0 Output file names CTMT2ACI l.out CTMT2ACI I jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 180 of 283 Sector averaging constant 4.3 Initial value of sigma y = 6.99 Initial value of sigma z = 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window - 25057 Hours elevated plume wI dir. in window - 0 Hours of calm winds - 863 Hours direction not in windoworcalm - 43127 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.OOE-02 l.OOE-02 1.OOE-02 1.00E-02 1.OOE-02 1.00E-02 1.02E-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 25920. 29826. 34518. 40372. 45098. 53784. 65641. 66445. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 43127. 39046. 34034. 27585. 23312. 14229. 1364. 168. 0. 0. TOTALXIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 37.54 43.31 50.35 59.41 65.92 79.08 97.96 99.75 100.00 100.00 95th PERCENTILE X/Q VALUES 1.98E-03 1.84E-03 1.68E-03 1.S4E-03 1.24E-03 8.93E-04 5.90E-04 5.223-04 4.70E-04 4.37E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.98E-03 2 to 8 hours 1.39E-03 8 to 24 hours 5.71E-04 I to 4 days 4.90E-04 4 to 30 days 4.13E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.41E-03 2.36E-04 SECTOR-AVERAGE 1.41E-03 1.37E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 181 of 283 CTMTIAC13.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jjransdel1epnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/15/2003 at 08:50:50
*+** ARCON INPUT ******.
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CCI 995.MET CC1996.MET CC1997.MET CCI998.MET Height of lower wind instrument (m) I 1Q.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 29.7 Building Area (mW2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (rmA3/s) .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) 292 Wind direction sector width (deg) = 90 Wind direction window (deg) 247 - 337 Distance to intake (m) 21.9 Intake height (m) = 16.1 Terrain elevation difference (m) e .0 Output file names CTMTIACI 3.out CTMTI AC13jfd Minimum Wind Speed (rmns) .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 182 of 283 Sector averaging constant 4.3 Initial value of sigma y 6.99 Initial value of sigma z 5.18 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window - 16638 Hours elevated plume w/ dir. in window - 0 Hours of calm winds - 863 Hours direction not in window or calm = 51546 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. I - 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.OOE-02 1.OOE-02 1.00E-02 1.OOE-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.00E.06 l.00E-06 1.00E-06 1.OOE-06 1.00E-06 L.OOE-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 17501. 21355. 26486. 33630. 39572. 50859. 66400. 66583. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 51546. 47517. 42066. 34327. 28838. 17154. 605. 30. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 25.35 31.01 38.64 49.49 57.85 74.78 99.10 99.95 100.00 100.00 95th PERCENTILE X/Q VALUES 1.93E-03 1.78E-03 1.57E-03 1.39E-03 I.IIE-03 7.90E-04 4.68E-04 4.05E-04 3.46E-04 3.21E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.93E-03 2 to 8 hours 1.21E-03 8 to 24 hours 4.91 E-04 I to 4 days 3.61 E-04 4 to 30 days 2.98E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.51E-03 2.13E-04 SECTOR-AVERAGE 1.46E.03 1.24E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 183 of 283 CTMT2AC]3.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl1Inrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhgnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/15/2003 at 08:50:59
***' ARCON INPUT *********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 29.7 Building Area (mA2) e 2000.0 Efuent vertical velocity (mis) .00 Vent or stack flow (mA3/s) - .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) e 157 Wind direction sector width (deg) 90 Wind direction window (deg) = 112 - 202 Distance to intake (m) 21.9 Intake height (m) e 16.1 Terrain elevation difference (m) e .0 Output file names CTMT2AC13.out CTMT2AC13.jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 184 of 283 Sector averaging constant 4.3 Initial value of sigma y e 6.99 Initial value ofsigma z - 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in window = 14619 Hours elevated plume w/dir. in window - 0 Hours of calm winds 863 Hours direction not in window or calm = 53565 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 l.OOE-02 1.00E-02 1.00E-02 t.OOE-02 1.00E-02 l.OOE-02 1.OOE-02 1.00E-02 LOW LIM. l.OOE-06 1.OOE-06 l.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 l.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 15482. 19014. 23837. 30803. 36572. 47841. 65256. 66458. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 53565. 49858. 44715. 37154. 31838. 20172. 1749. 155. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 22.42 27.61 34.77 45.33 53.46 70.34 97.39 99.77 100.00 100.00 95th PERCENTILE X/Q VALUES 1.88E403 1.72E-03 1.52E-03 1.32E-03 1.05E-03 7.33E-04 4.25E-04 3.67E-04 3.07E-04 2.88E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.88E-03 2 to 8 hours 1.14E-03 8 to 24 hours 4.38E-04 I to 4 days 3.22E-04 4 to 30 days 2.67E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.51 E-03 2.82E-04 SECTOR-AVERAGE 1.46E-03 1.64E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 185 of 283 CTMTI SWGl .OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhbnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: j_ramsdellepn1.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use.-or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8115/2003 at 08:51:12
**** ARCON INPUT ***..**
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 29.7 Building Area (mW2) 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mA3/s) = .09 Vent or stack radius (m) - * .00 Direction .. intake to source (deg) 225 Wind direction sector width (deg) = 90 Wind direction window (deg) = 180 - 270 Distance to intake (m) = 12.1 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names CTMTISWGI .out CTMTISWGI .jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 186 of 283 Sector averaging constant 4.3 Initial value of sigma y 6.99 Initial value of sigma z = 5.18 Expanded output for code testing not selected Total number of hours of dita processed = 70131 Hours of missing data - 1084 Hours direction in window = 24200 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 863 Hours direction not in window or calm = 43984 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.OOE-02 1.00E-02 1.OOE-02 1.00E-02 1.OOE-02 1.OOE-02 1.OOE-02 1.00E-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 AB3OVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 25063. 28796. 33670. 40423. 45902. 54962. 66078. 66570. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 43984. 40076. 34882. 27534. 22508. 13051. 927. 43. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 36.30 41.81 49.12 59.48 67.10 80.81 98.62 99.94 100.00 100.00 95th PERCENTILE X/Q VALUES 2.21E-03 2.04E-03 1.83E-03 1.66E-03 1.33E-03 9.39E-04 6.27E-04 5.63E-04 5.07E-04 4.70E-04 95% XtQ for standard averaging intervals 0 to 2 hours 2.21E-03 2 to 8 hours 1.47E-03 8 to 24 hours 5.79E-04 l to 4 days 5.23E-04 4 to 30 days 4.46E-04 HOURLY VALUE RANGE MAX XIQ MIN XIQ CENTERLINE 2.76E-03 2.64E-04 SECTOR-AVERAGE 1.61 E-03 1.54E-04 NORMAL PROGRAMS COMPLETION
CA06012 Rev.0 Page 187 of 283 CTMT2SWGI .OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date:- June25,1997 11:00a.m. NRCContacts: J.Y.Lee Phone: (301)415 1080 e-mail: jyllInrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J.V. Ramsdell Phone: (509) 372 6316 e-mail: j_ramsdellepnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results ofsuch use, of any portion of this program or represents that its use by such third party wvould not infringe privately owned rights. Program Run 8/15/2003 at 08:51:27
*'*+ ARCON INPUT ********
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) = 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 29.7 Building Area (mA2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mW31s) - .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) e 157 Wind direction sector width (deg) = 90 Wind direction window (deg) 112-202 Distance to intake (m) = 64.9 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names CTMT2SWGI .out CTMT2SWGI .jfd Minimum Wind Speed (mts) .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 188 of 283 Sector averaging constant 4.3 Initial value of sigma y = 6.99 Initial value of sigma z - 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in window - 14619 Hours elevated plume w/dir. in window = 0 Hours of calm winds = 863 Hours direction not in window or calm = 53565 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 I.OOE-03 I.00E-03 1.OOE-03 I.OOE.03 t.OOE-03 LOW LIM. 1.001E07 1.00E-07 l.OOE-07 1.OOE-07 1.OOE-07 1.00E-07 1.OOE-07 t.00E-07 1.00E-07 1.OOE-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 15482. 19014. 23837. 30803. 36572. 47841. 65256. 66458. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 53. 0. 0. ZERO 53565. 49858. 44715. 37154. 31838. 20172. 1749. 102. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 22.42 27.61 34.77 45.33 53.46 70.34 97.39 99.85 100.00 100.00 95th PERCENTILE X/Q VALUES 6.89E-04 6.42E-04 S.85E404 5.19E-04 4.13E-04 2.85E404 1.63E-04 1.41E-04 1.18E404 1.10E-04 95% X/Q for standard averaging intervals 0 to 2 hours 6.89E-04 2 to 8 hours 4.62E-04 8 to 24 hours 1.68E-04 I to 4 days 1.22E-04 4to30days L.OIE-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 8.53E-04 1.14E-04 SECTOR-AVERAGE 4.97E-04 6.66E405 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 189 of 283 CTMTISWG2.0UT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee , Phone: (301) 415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail:jjhenrc.gov LA Brown Phone:(301)415 1232 e-mail: lab2tnrc.gov Code Developer: J.V. Ramsdell Phone: (509) 372 6316 e-mail: j_ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/15/2003 at 08:51:18
**** ARCON INPUT *******
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (i) 10.0 Height of upper wind instrument (m) 660.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 29.7 Building Area (mA2) = 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 292 Wind direction sector width (deg) = 90 Wind direction window (deg) 247 - 337 Distance to intake (m) 64.9 Intake height (m) - 9.5 Terrain elevation difference (m) - .0 Output file names CTMTISWG2.out CTMTISWG2.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 190 of 283 Sector averaging constant 4.3 Initial value of sigma y = 6.99 Initial value of sigma z = 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window - 16638 Hours elevated plume w/ dir. in window - 0 . Hours of calm winds 863 Hours direction not in windoworcalm - 51546 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-03 1.OOE.03 1.00E-03 1.OOE.03 I.OE.03 1.OOE-03 1.00E-03 1.OOE-03 1.00E-03 1.OOE-03 LOW LIM. 1.00E-07 1.00E-07 1.00E-07 1.00E-07 I.OOE-07 1.00E-07 1.00E-07 1.00E-07 l.OOE-07 l.OOE-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 17501. 21355. 26486. 33630. 39572. 50859. 66400. 66583. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 51546. 47517. 42066. 34327. 28838. 17154. 605. 30. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 25.35 31.01 38.64 49.49 57.85 74.78 99.10 99.95 100.00 100.00 95th PERCENTILE X/Q VALUES 7.18E-04 6.73E-04 6.13E-04 5.48E-D4 4.38E-04 3.19E-04 1.86E-04 1.59E-04 1.37E-04 1.26E-04 95% X/Q for standard averaging intervals 0 to 2 hours 7.18E-04 2 to 8 hours 4.91 E-04 8 to 24 hours 2.05E-04 I to 4 days 1.42E-04 4 to 30 days 1.16E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 8.53E-04 8.21E-05 SECTOR-AVERAGE 4.97E404 4.79E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 191 of 283 CTMT2SWG2.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00a.m. NRC Contacts: J.Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: ijhenrc.gov LA Brown Phone:(301)415 1232 e-mail: lab2inrc.gov Code Developer: J.V. Ramsdell Phone: (509) 372 6316 e-mail: jamsdellspnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/15/2003 at 08:51:35
,*** ARCON INPUT *.******
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 29.7 Building Area (m'2) - 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) - 225 Wind direction sector width (deg) = 90 Wind direction window (deg) 180-270 Distance to intake (m) = 12.1 Intake height (m) 9.5 Terrain elevation difference (m) = .0 Output file names CTMT2SWG2.out CTMT2SWG2.jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) =.20
CA 06012 Rev. 0 Page 192 of 283 Sector averaging constant 4.3 Initial value of sigma y G 6.99 Initial value of sigma z = 5.18 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window = 24200 Hours elevated plume wl dir. in window - 0 Hours of calm winds - 863 Hours direction not in window or calm = 43984 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 I.OOE-02 1.00E-02 I.OOE-02 1.OOE-02 1.OOE-02 .OOE-02 LOW LIM. .OOE-06 1.00E-06 1.00E-06 .OOE-06 I.OOE-06 1.OE-06 .OOE06 I .OOE06 .OOE-06 L.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 25063. 28796. 33670. 40423. 45902. 54962. 66078. 66570. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 43984. 40076. 34882. 27534. 22508. 13051. 927. 43. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 36.30 41.81 49.12 59.48 67.10 80.81 98.62 99.94 100.00 100.00 95th PERCENTILE X/Q VALUES 2.21E-03 2.04E403 1.83E-03 1.66E-03 1.33E403 9.39E-04 6.27E-04 5.63E-04 5.07E-04 4.70E.04 95% X/Q for standard averaging intervals 0 to 2 hours 2.21 E-03 2 to 8 hours 1.47E-03 8 to 24 hours 5.79E-04 1 to 4 days 5.23E-04 4 to 30 days 4.46E-04 HOURLY VALUE RANGE MAX X/Q MEN X/Q CENTERLlNE 2.76E-03 2.64E-04 SECTOR-AVERAGE 1.61 E-03 1.54E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 193 of 283 CTMTITB.OUT Program Titde: ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office ofNuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J.Y. Lee Phone: (301) 415 10S0 e-mail: jyllenrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail:jjhinrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: j_ramsdellspnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 14:13:53
*+** ARCON INPUT *********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1 995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 29.7 Building Area (mA2) = 2000.0 Effluent vertical velocity (mis) . = .00
. Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 263 Wind direction sector width (deg) 90 Wind direction window (deg) 218 - 308 Distance to intake (m) = 43.1 Intake height (m) .9 Terrain elevation difference (m) - .0 Output file names CTMTITB.out CTMTITB.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) a .20
CA06012 Rev.0 Page 194 of 283 Sector averaging constant e 4.3 Initial value of sigma y 6.99 Initial value of sigma z 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window - 20196 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm = 47988 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.001E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 I.00E-02 1.00E-02 1.00E-02 LOW LIM. 1.00E-06 1.001E-06 I.00E-06 I.00E-06 I.OOE-06 I.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 21059. 26031. 32123. 40171. 46365. 56455. 66444. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 47988. 42841. 36429. 27786. 22045. 11558. 561. 0. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 30.50 37.80 46.86 59.11 67.78 83.01 99.16 100.00 100.00 100.00 95th PERCENTILE XIQ VALUES 1.02E-03 9.71E-04 8.84E-04 7.87E-04 6.25E-04 4.34E-04 2.72E-04 2.39E-04 2.09E-04 1.90E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.02E-03 2 to 8 hours 7.1OE-04 8 to 24 hours 2.57E-04 I to 4 days 2.19E-04 4 to 30 days 1.77E-04 HOURLY VALUE RANGE MAX X/Q MIN XIQ CENTERLINE 1.17E-03 1.05E-04 SECTOR-AVERAGE 6.84E-04 6.09E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 195 of 283 CTMT2TB.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyllenrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 811 1/2003 at 14:14:01
"*"* ARCON INPUT .**
Number of Meteorological Data Files - 8 Meteorological Data File Names CC1991.MET CC1992.MET CCI 993.MET CC1994.MET CC1995.MET CC1996.MET
*CC1 997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 29.7 Building Area (m^2) 2000.0 Effluent vertical velocity (rnis) .00 Vent or stack flow .(mA3/s) - .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 187 Wind direction sector width (deg) - 90 Wind direction window (deg) 142 - 232 Distance to intake (m) = 43.1 Intake height (m) .9 Terrain elevation difference (m) - .0 Output file names CTMT2TB.out CTMT2TB.jfd Minimum Wind Speed (m/s) .5 Surface roughness length (m) .20
CA06012Rev.0 Page 196 of 283 Sector averaging constant = 4.3 Initial value of sigma y = 6.99 Initial value of sigma z = 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window = 23558 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 863 Hours direction not in window or calm - 44626 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. .1 2 . 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.DOE-02 1.00E-02 1.00E-02 L.OOE-02 1.00E-02 LOW UM. 1.00E-06 1.00E-06 1.00E-06 1.GOE-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 24421. 28287. 32921. 38849. 43630. 52637. 65558. 66443. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. - 0. 0. ZERO 44626. 40585. 35631. 29108. 24780. 15376. 1447. 170. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 35.37 41.07 48.02 57.17 63.78 77.39 97.84 99.74 100.00 100.00 95th PERCENTILE X/Q VALUES 1.02E-03 9.82E-04 9.31E-04 8.53E-04 6.87E-04 4.97E-04 3.17E-04 2.74E-04 2.43E-04 2.28E-04 95% XIQ for standard averaging intervals 0 to 2 hours 1.02E-03 2 to 8 hours 7.98E-04 8 to 24 hours . 3.19E-04 I to 4 days 2.56E-04 4 to 30 days 2.14E-04 HOURLY VALUE RANGE MAX XIQ MN XIQ CENTERLINE 1.17E-03 1.12E-04 SECTOR-AVERAGE 6.84E-04 6.52E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 197 of 283 CTMTI WR.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRCContacts: J.Y. Lee Phone: (301)415 1080 e-mail: jyl l nrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: I. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdelllpnl.gov Code Documentation: NUREG/CR-633I Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results ofsuch use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 14:13:02
*"'*' ARCON INPUT ** * '
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1 998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 29.7 Building Area (m^2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (m"3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 358 Wind direction sector width (deg) = 90 Wind direction window (deg) = 313 -043 Distance to intake (m) 33.4 Intake height (m) 9.1 Terrain elevation difference (m) - .0 Output file names CTMTI WR.out CTMTIWRjfd Minimum Wind Speed (rns) .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 198 of 283 Sector averaging constant 4.3 Initial value of sigma y 6.99 Initial value of sigma z 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window = 19377 Hours elevated plurne w/ dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm - 48807 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 t.OOE-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.OOE-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 I.00E-06 I.OOE.06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. INRANGE 20240. 24125. 29070. 35744. 41353. 51447. 66031. 66557. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 48807. 44747. 39482. 32213. 27057. 16566. 974. 56. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 29.31 35.03 42.41 52.60 60.45 75.64 98.55 99.92 100.00 100.00 95th PERCENTILE X/Q VALUES 1.20E-03 1.09E-03 9.80E-04 8.83E-04 7.19E-04 5.20E-04 3.20E-04 2.85E-04 2.48E-04 2.26E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.20E.03 2 to 8 hours 7.78E-04 8 to 24 hours 3.38E-04 I to 4 days 2.53E-04 4 to 30 days 2.1 E-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE I.60E-03 1.51 E-04 SECTOR-AVERAGE 9.34E404 8.79E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 199 of 283 CTMT2WR.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 14:13:43
*** ARCON INPUT
- Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC]996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) = 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 29.7 Building Area (m^2) - 2000.0 Effluent vertical velocity (m's) - .00 Vent or stack flow (rn3Is) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 092 Wind direction sector width (deg) 90 Wind direction window (deg) = 047 - 137 Distance to intake (m) = 33.4 Intake height (m) = 9.1 Terrain elevation difference (m) - .0 Output file names CTMT2WRout CTMT2WR.jfd Minimum Wind Speed (mls) = .5 Surface roughness length (m) .20
CA06012 Rev.0 Page 200 of 283 Sector averaging constant = 4.3 Initial value of sigma y 6.99 Initial value of sigma z = 5.18 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window - 9011 Hours elevated plume w/ dir. in window - 0 Hours of calm winds 863 Hours direction not in window or calm = 59173 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE.02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOEE02 I.00EE02 I .OOE-02 1.OOE-02 I .OOE-02 1.OOE-02 LOW LIM. 1.00E-06 I.OOE-06 1.OOE-06 1.00E-06 I.OOE-06 1.00E-06 I.OOE-06 I.OOE-06 I.OOE-06 I.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 9874. 12872. 17255. 23861. 29420. 41034. 63371. 65772. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 59173. 56000. 51297. 44096. 38990. 26979. 3634. 841. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 14.30 18.69 25.17 35.11 43.01 60.33 94.58 98.74 100.00 100.00 95th PERCENTILE X/Q VALUES 1.12E-03 9.86E-04 8.80E-04 7.57E-04 5.97E-04 4.16E-04 2.37E-04 1.97E-04 1.57E-04 1.37E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.12E-03 2 to 8 hours 6.37E-04 8 to 24 hours 2.46E-04 I to 4 days 1.77E-04 4 to 30 days 1.22E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERIUNE 1.60E-03 1.33E-04 SECTOR-AVERAGE 9.34E-04 7.73E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 201 of 283 MSGIACI I.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25. 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1030 e-mail: jyll nrc.gov J.J. Hayes Phone:(301)415 3167 e-mail: jjhbnrc.gov LA Brown Phone:(301)415 1232 e-mail: lab2@nrc.gov Code Developer; J.V. Ramsdell Phone: (509) 372 6316 e-mail: jjamsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:46:01
***+ARCON INPUT *+***
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 17.1 Building Area (mr2) = 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) = 291 Wind direction sector width (deg) = 90 Wind direction window (deg) 246 - 336 Distance to intake (m) - 51.3 Intake height (m) 13.9 Terrain elevation difference (m) = .0 Output file names MSGIACI 1.out MSGIACI Ijfd Minimum Wind Speed (mis) - .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 202 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window = 16687 Hours elevated plume wI dir. in window = 0 Hours of calm winds - 863 Hours direction not in windoworcalm = 51497 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.OOE-02 1.00E-02 I .OOE-02 1.00E-02 I.OOE-02 1.00E-02 1.OOE-02 L.OOE-02 L.00E-02 LOW LIM. 1.00E-06 L.OOE-06 1.00E-06 1.OOE-06 1.OOE-06 I.00E06 l .OOE06 1..OEE06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. INRANGE 17550. 21538. 26647. 33867. 39866. 51145. 66411. 66583. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 52581. 48593. 41905. 34090. 28544. 16868. 594. 30. 0. 0. TOTALX/Qs 70131. 70131. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 25.02 30.71 38.87 49.84 58.28 75.20 99.11 99.95 100.00 100.00 95th PERCENTILE X/Q VALUES 2.25E-03 2.15E-03 2.03E.03 1.86E-03 1.51E-03 I.JOE-03 6.22E-04 5.32E-04 4.53E-04 4.11E-04 95% X/Q for standard averaging intervals 0 to 2 hours 2.25E-03 2 to 8 hours 1.73E-03 8 to 24 hours 7.15E-04 I to 4 days 4.65E-04 4 to 30 days 3.78E-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 3.OOE-03 2.08E-04 SECTOR-AVERAGE 1.75E-03 1.22E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 203 of 283 MSG2AC l l.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J.Y. Lee Phone: (301) 415 1080 e-mail:jyll nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail:jjhgnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jyamsdellcpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:46:22
*'*" ARCON INPUT *""""'
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Releaseheight(m) 17.1 Building Area (m-2) = 2000.0 Effluent vertical velocity (mIs) - .00 Vent or stack flow (mr3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 225 Wind direction sector width (deg) 90 Wind direction window (deg) 180-270 Distance to intake (m) = 21.1 Intake height (m) - 13.9 Terrain elevation difference (m) .0 Output file names MSG2ACI l.out MSG2ACI I jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) .20
CA06012 Rev.0 Page 204 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigmar = .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window - 24200 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 863 Hours direction not in window or calm = 43984 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPERLIM. 1.OOE-01 L.OOE.01 L.OOE-01 L I.OOE-01 .OOE-01 1.OOE-01 1.OOE-01 LOOE-01 1.00E-01 1OOE-01 LOW LIM. 1.OOE-05 1.00E.O5 1.OOE-05 L.OOE-05 1.00E.05 L.OOE-O5 1.00E-05 1.00E-05 1.00E-05 1.00E05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 25063. 28901. 33670. 40423. 45902. 54962. 66078. 66570. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 45068. 41230. 34882. 27534. 22508. 13051. 927. 43. 0. 0. TOTALX/Qs 70131. 70131. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 35.74 41.21 49.12 59.48 67.10 80.81 98.62 99.94 100.00 100.00 95th PERCENTILE XJQ VALUES 1.31E-02 1.30E-02 1.28E-02 1.21E-02 9.79E-03 6.92E-03 4.45E-03 3.87E-03 3.30E-03 3.05E-03 95% X/Q for standard averaging intervals 0 to 2 hours 1.31 E-02 2 to 8 hours 1.17E-02 8 to 24 hours 4.33E-03 I to 4 days 3.63E-03 4 to 30 days 2.84E-03 HOURLY VALUE RANGE MAX X/Q MINXIQ CENTERLINE 1.66E-02 1.26E-03 SECTOR-AVERAGE 9.70E.03 7.37E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 205 of 283 MSGIACl3.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jihhnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:46:12
**** ARCON INPUT *****.***
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 17.1 Building Area (mW2) = 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mA3s) . - .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) - 319 Wind direction sector width (deg) - 90 Wind direction window (deg) - 274 - 004 Distance to intake (m) - 23.5 Intake height (m) = 16.1 Terrain elevation difference (m) - .0 Output file names MSGIAC13.out MSGIAC13.jfd Minimum Wind Speed (m/s) e.5 Surface roughness length (m) - .20
CA06012 Rev.0 Page 206 of 283 Sector averaging constant = 4.3 Initial value of sigma y - .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed 70131 Hours of missing data 1084 Hours direction in window - 17843 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm - 50341 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPERLIM. I.OOE-01 1.OOE-01 1.00E-01 L.OOE-01 L.OOE-01 1.00E-01 1.00E-01 1.OOE-01 1.OOE-01 1.OOE-01 LOW LIM. 1.00E-05 1.00E-05 1.00E-05 1.OOE-05 I.OOE-05 1.00E-05 1.00E-05 I.00E-05 1.00E-05 1.00E-05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 18706. 22500. 27420. 34399. 40070. 50856. 66280. 66530. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 29. 0. 0. ZERO 51425. 47631. 41132. 33558. 28340. 17157. 725. 54. 0. 0. TOTALX/Qs 70131. 70131. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 26.67 32.08 40.00 50.62 58.57 74.77 98.92 99.92 100.00 100.00 95th PERCENTILE X/Q VALUES I.OOE-02 9.53E-03 9.10E-03 8.50E-03 6.89E.03 4.99E-03 2.86E-03 2.47E.03 2.13E-03 1.92E-03 95% XIQ for standard averaging intervals 0 to 2 hours I.00E-02 2 to 8 hours 7.99E-03 8 to 24 hours 3.23 E-03 I to 4 days 2.15E-03 4 to 30 days 1.78E-03 HOURLY VALUE RANGE MAX X/Q MINYXQ CENTERLINE 1.38E-02 9.OOE-04 SECTOR-AVERAGE 8.04E-03 5.25E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 207 of 283 MSG2AC13.OUT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllInrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail:jjhgnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail:jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. 1 The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/2112003 at 10:46:33
**** ARCON INPUT ******
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 17.1 Building Area (mA2) - 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mA3/s) - .00 Vent or stack radius (m) ' .00 Direction.. intake to source (deg) = 131 Wind direction sector width (deg) 90 Wind direction window (deg) 086 - 176 Distance to intake (m) _ 23.5 Intake height (m) - 16.1 Terrain elevation difference (m) - .0 Output file names MSG2AC13.out MSG2AC13.jfd Minimum Wind Speed (m/s) .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 208 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window - 10913 Hours elevated plume w/ dir. in window - 0 Hours of calm winds - 863 Hours direction not in window or calm 57271 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. I 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-01 1.00E-0 1.O LOE-0 1.OE-01 1.00E-01 1.00E-01 1.00E-0I L.OOE-01 1.00E-01 1.00E-01 LOW LIM. 1.00E-05 1.00E-05 1.00E-05 l.OOE-05 1.OE-05 1.OOE-05 1.00E-105 1.OOE-05 1.00E.05 1.OOE-05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 11776. 14978. 19414. 26274. 32158. 44260. 64238. 66115. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 151. 0. 0. ZERO 58355. 55153. 49138. 41683. 36252. 23753. 2767. 347: 0. 0. TOTAL X/Qs 70131. 70131. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 16.79 21.36 28.32 38.66 47.01 65.08 95.87 99.48 100.00 100.00 95th PERCENTILE X/Q VALUES 8.72E-03 8.26E-03 7.21E-03 6.17E-03 4.87E-03 3.27E.03 1.85E-03 1.55E-03 1.27E-03 1.12E-03 95% X/Q for standard averaging intervals 0 to 2 hours 8.72E-03 2 to 8 hours 5.32E-03 8 to 24 hours 1.83E-03 I1to 4 days 1.37E-03 4 to 30 days 1.0IE-03 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.38E-02 1.34E-03 SECTOR-AVERAGE 8.04E-03 7.81 E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 209 of 283 MSGISWGI .OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyll nrc.gov
*. J. Hayes Phone: (301) 415 3167 e-mail: jjhgnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jjramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights.
Program Run 8/21/2003 at 10:46:42
**** ARCON INPUT *S*******
- Number ofMeteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) = 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 17.1 Building Area (mA2) - 2000.0 Efmuent vertical velocity (mis) - .00 Vent or stack flow (m"3/s) .00 Vent or stack radius (m) - .00 Direction.. intake to source (deg) - 178 Wind direction sector width (deg) 90 Wind direction window (deg) 133 - 223 Distance to intake (m) = 22.1 Intake height (i) 9.5 Terrain elevation difference (m) .0 Output file names MSGISWGI.out MSGISWGljfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 210 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window 21060 Hours elevated plume w/ dir. in window = 0 Hours of calm winds 863 Hours direction not in window or calm - 47124 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-01 1.00E-01 1.00E-01 1.00E-01 1.00E-01 1.00E-01 1.00E-01 1.00E-01 1.0OE-01 1.00E-01 LOW LIM. 1.00E-05 1.00E-05 I.OOE-05 I.OOE-05 I.OOE-05 1.00E-05 1.OOE-05 1.OE-05 1.00E-05 1.00E-05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 21923. 25871. 30605. 36807. 41886. 51500. 65698. 66513. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0
- 0. 3. 0. 0.
ZERO 48208. 44260. 37947. 31150. 26524. 16513. 1307. 97. 0. 0. TOTALX/Qs 70131. 70131. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 31.26 36.89 44.64 54.16 61.23 75.72 98.05 99.85 100.00 100.00 95th PERCENTILE X/Q VALUES 1.07E402 1.05E-02 1.02E-02 9.53E-03 7.72E-03 5.54E-03 3.30E-03 2.83E-03 2.46E-03 2.25E-03 95% X/Q for standard averaging intervals 0 to 2 hours 1.07E-02 2 to 8 hours 9.16E-03 8 to 24 hours 3.54E-03 I to 4 days 2.56E403 4 to 30 days 2.09E-03 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 1.40E-02 1.07E-03 SECTOR-AVERAGE 8.15E-03 6.24E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 211 of 283 MSG2SWGl.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 c-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. ProgramRun 8/21/2003 at 10:47:03
******* ARCON INPUT ********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 17.1 Building Area (mA2) 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mW3/s) - .00 Vent or stack radius (m) .00 r Direction .. intake to source (deg) = 148 Wind direction sector width (deg) = 90 Wind direction window (deg) e 103 - 193 Distance to intake (m) 64.8 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names MSG2SWGI .out MSG2SWGI jfd Minimum Wind Speed (mls) .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 212 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z - .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window 12850 Hours elevated plume w/ dir. in window - 0 Hours of calm winds 863 Hours direction not in windoworcalm - 55334 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.OOE-02 1.00E-02 1.OE-02 1.00E.02 .OOE-02 l.OOE-02 1.OOE-02 l.OOE-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 L.OOE-06 l.OOE-06 1.00E-06 1.00E.06 l.OOE-06 l.00E-06 1.00E-06 l.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 13713. 17031. 21559. 28447. 34316. 45967. 65133. 66435. 67247. 67747. BELOW RANGE O. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 56418. 53100. 46993. 39510. 34094. 22046. 1872. 178. 0. 0. TOTALXIQs 70131. 70131. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 19.55 24.28 31.45 41.86 50.16 67.59 97.21 99.73 100.00 100.00 95th PERCENTILE X/Q VALUES 1.31E-03 1.27E-03 1.19E-03 1.04E-03 8.21E-04 5.51E.04 3.04E.04 2.63E.04 2.15E-04 1.90E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.31 E-03 2 to 8 hours 9.52E-04 8 to 24 hours 3.05E-04 I to 4 days 2.22E-04 4 to 30 days 1.72E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE I .90E-03 2.01 E-04 SECTOR-AVERAGE 1.IIE-03 1.17E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 213 of 283 MSGISWG2.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J.Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J.J.Hayes Phone:(301)4153167 e-mail: jjhsnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, ofany portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8121/2003 at 10:46:48 ARCON INPUT ****** Number of Meteorological Data Files = 8 Meteorological Data File Names CCI991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 17.1 Building Area (mA2) 2000.0 Effluent vertical velocity (mls) - .00 Vent or stack flow (mA31s) - .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 302 Wind direction sector width (deg) = 90 Wind direction window (deg) = 257 - 347 Distance to intake (m) = 64.8 Intake height (m) - 9.5 Terrain elevation difference (m) - .0 Output file names MSGISWG2.out MSGISWG2.jfd Minimum Wind Speed (mrs) .5 Surface roughness length (m) e .20
CA 06012 Rev.0 Page 214 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data - 1084 Hours direction in window = 16442 Hours elevated plume w/ dir. in window 0 Hours of calm winds = 863 Hours direction notin windoworcalm = 51742 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.OOE-02 I.OOE-02 I .OOE-02 1.OOE-02 1.001E-02 .I .OOE-02 I.OOE-02 I .OOE-02 I .OOE-02 I .OOE-02 LOW LIM. I.OOE-06 I.OOE-06 I.OOE-06 1.00E-06 I.OOE-06 I.OOE-06 I.OOE-06 I.00E-06 I.OOE-06 1.OOE-06 ABOVE RANGE. 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 17305. 21046. 25867. 32817. 38623. 49841. 66196. 66551. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 52826. 49085. 42685. 35140. 29787. 18172. 809. 62. 0. 0. TOTALX/Qs 70131. 70131. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 24.68 30.01 37.73 48.29 56.46 73.28 98.79 99.91 100.00 100.00 95th PERCENTILE X/Q VALUES 1.41E-03 1.36E-03 1.30E-03 1.20E-03 9.76E-04 7.I1E-04 4.OOE-04 3.43E-04 2.91E-04 2.64E-04 95% X/Q for standard averaging intervals O to 2 hours I.41E-03 2 to 8 hours 1.13E-03 8 to 24 hours 4.65E-04 I to 4 days 2.96E-04 4 to 30 days 2.43E-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 1.90E-03 1.34E-04 SECTOR-AVERAGE 1.11 E-03 7.84E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 215 of 283 MSG2SWG2.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl l nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jjamsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Govenment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/21/2003 at 10:47:07
***1* ARCON INPUT **********
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 17.1 Building Area (mA2) e 2000.0
.Efuent vertical velocity (mls) = .00 Vent or stack flow (mA3/s) e .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) e 272 Wind direction sector width (deg) 90 Wind direction window (deg) 227-317 Distance to intake (m) 22.1 Intake height (m) = 9.5 Terrain elevation difference (m) = .0 Output file names MSG2SWG2.out MSG2SWG2.jfd Minimum Wind Speed (mrs) - .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 216 of 283 Sector averaging constant 4.3 Initial value of sigma y = .00 Initial value ofsigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window 18586 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 863 Hours direction not in window or calm - 49598 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-01 L.OOE-01 1.00E-0l 1.00E-0I 1.00E-01 L.OOE-01 1.00E-01 1.00E-0I 1.00E-01 1.00E-01 LOW LIM. 1.00E-05 1.OOE-05 1.00E-05 L.OOE.05 1.DOE-05 1.00E-05 1.OOE-05 1.OOE-05 1.OOE-05 L.OOE-05 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19449. 24289. 30278. 38337. 44662. 55376. 66593. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 50682. 45842. 38274. 29620. 23748. 12637. 412. 0. 0. 0. TOTALX/Qs 70131. 70131. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 27.73 34.63 44.17 56.41 65.29 81.42 99.39 100.00 100.00 100.00 95th PERCENTILE X/Q VALUES 1.04E-02 1.01E-02 9.46E-03 8.48E-03 6.84E-03 4.89E-03 2.87E-03 2.43E-03 2.1OE-03 1.90E-03 95% X/Q for standard averaging intervals 0 to 2 hours 1.04E-02 2 to 8 hours 7.84E-03 8 to 24 hours 3.10E-03 I to 4 days 2.20E-03 4 to 30 days 1.75E-03 HOURLY VALUE RANGE MAX X/Q M1NX/Q CENTERLINE I4AOE-02 9.10E-04 SECTOR-AVERAGE 8.1SE-03 5.31E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 217 of 283 MSGITB.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jylltnrc.gov J. J.Hayes Phone: (301) 415 3167 e-mail: jhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer. J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellspnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 16:18:01
..*.*** ARCON INPUT **,****
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) e 17.1 Building Area (mA2) . 2000.0 Effluent vertical velocity (mns) = .00 Vent or stack flow (mW3/s) e .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 261 Wind direction sector width (deg) - 90 Wind direction window (deg) - 216 - 306 Distance to intake (m) 39.9 Intake height (m) = .9 Terrain elevation difference (m) = .0 Output file names MSGITB.out MSGITB jfd Minimum Wind Speed (mrs) .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 218 of 283 Sector averaging constant 4.3 Initial value of sigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window - 20577 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 863 Hours direction not in window or calm = 47607 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 *8 12 24 96 168 360 720 UPPER LIM. 1.OOE-02 1.OE-02 1.00E.02 1.00E-02 1.00E-02 1.00E-02 t.OOE-02 1.00E-02. 1.00E-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 21440. 26360. 32431. 40384. 46549. 56447. 66387. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 47607. 42512. 36121. 27573. 21861. 11566. 618. 0. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 31.05 38.27 47.31 59.43 68.04 82.99 99.08 100.00 100.00 100.00 95th PERCENTILE X/Q VALUES 3.38E-03 3.24E-03 3.07E-03 2.76E-03 2.22E-03 1.55E-03 9.67E.04 8.15E-04 7.01E-04 6.41E-04 95% X/Q for standard averaging intervals 0 to 2 hours 3.38E-03 2 to 8 hours 2.56E-03 8 to 24 hours 9.45E-04 I to 4 days 7.73E.04 4 to30days S.91E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 4.24E-03 3.17E-04 SECTOR-AVERAGE 2.47E-03 1.85E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 219 of 283 MSG2TB.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: 1.Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhQnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results ofsuch use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/1112003 at 16:18:06
*.**'** ARCON INPUT ***.*
Number of Meteorological Data Files - 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 17.1 Building Area (m^2) - 2000.0 Effluent vertical velocity (rnms) = .00 Vent or stack flow (m^3/s) e .00 Vent or stack radius (m) = .00 Direction.. intake to source (deg) 189 Wind direction sector width (deg) 90 Wind direction window (deg) - 144 - 234 Distance to intake (m) 39.9 Intake height (m) - .9 Terrain elevation difference (m) = .0 Output file names MSG2TB.out MSG2TB.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 220 of 283 Sector averaging constant - 4.3 Initial value of sigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data - 1084 Hours direction in window = 23986 Hours elevated plume w/dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm - 44198 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-02 1.00E-02 1.00E-02 1.00E-02 1.OOE-02 I.OOE-02 1.00E-02 1.OOE-02 1.OOE-02 1.00E-02 LOW LIM. L.OOE-06 .OOE-06 1.OOE-06 1.OOE-06 1.OOE-06 1.OOE-06 L.OOE-06 I.OOE-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 24849. 28709. 33297. 39105. 43804. 52725. 65572. 66443. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 44198. 40163. 35255. 28852. 24606. 15288. 1433. 170. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 35.99 41.68 48.57 57.54 64.03 77.52 97.86 99.74 100.00 100.00 95th PERCENTILE X/Q VALUES 3.48E-03 3.38E-03 3.26E-03 3.10E-03 2.53E-03 1.84E-03 1.15E-03 9.92E-04 8.68E-04 7.96E-04 95% X/Q for standard averaging intervals 0 to 2 hours 3.48E-03 2 to 8 hours 2.97E-03 8 to 24 hours 1.21 E-03 I to 4 days 9.22E-04 4 to 30 days 7.41 E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 4.24E-03 3.42E-04 SECTOR-AVERAGE 2.47E-03 1.99E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 221 of 283 MSGIWROUT Program
Title:
ARCON96. Developed For: US. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone:(301)415 1080 e-mail: jyll nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhsnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail:Lj_ramsdelltpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8111/2003 at 16:17:48
**** ARCON INPUT *******
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) = 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 17.1 Building Area (rnY2) - 2000.0 Effluent vertical velocity (rn's) - .00 Vent or stack flow (mA3/s) . .00 Vent or stack rad ius (m) = .00 Direction .. intake to source (deg) 022 Wind direction sector width (deg) 90 Wind direction window (deg) ' 337 - 067 Distance to intake (m) - 60.0 Intake height (m) - 9.1 Terrain elevation difference (m) = .0 Output file names MSGI WR.out MSGI WR.jfd Minimum Wind Speed (mis) Surface roughness length (m) =.20
CA06012 Rev.0 Page 222 of 283 Sector averaging constant 4.3 Initial value of sigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window = 17743 Hours elevated plume wI dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm - 50441 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.00E-02 1.00E-02 I.00E-02 1.GOE-02 I.OOE-02 1.00E-02 1.00E-02 1.00E-02 1.OOE-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 l.OOE-06 1.00E-06 1.00E-06 l.O6E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 18606. 21816. 26323. 32743. 38243. 48545. 65396. 66454. 67247. 67747. BELOW RANGE 0.. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 50441. 47056. 42229. 35214. 30167. 19468. 1609. 159. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 26.95 31.68 38.40 48.18 55.90 71.38 97.60 99.76 100.00 100.00 95th PERCENTILE X/Q VALUES l.54E-03 1.49E-03 1.40E-03 1.27E-03 1.04E-03 7.68E-04 4.78E-04 4.08E-04 3.32E-04 2.95E-04 95% XIQ for standard averaging intervals 0 to 2 hours 1.54E-03 2 to 8 hours 1.19E-03 8 to 24 hours 5.1SE-04 I to4days 3.81E-04 4 to 30 days 2.67E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.20E-03 1.55E-04 SECTOR-AVERAGE 1.28E-03 9.01 E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 223 of 283 MSG2WR.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division ofReactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-633 I Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 16:17:54
**** ARCON INPUT **********
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) v 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 17.1 Building Area (mA2) 2000.0 Effluent vertical velocity (mIs) - .00. Vent or stack flow (rn63/s) - .00 Ventlor stack radius (m) " .00 Direction .. intake to source (deg) - 068 Wind direction sector width (deg) 90 Wind direction window (deg) 023 - 113 Distance to intake (m) = 60.0 Intake height (m) = 9.1 Terrain elevation difference (m) = .0 Output file names MSG2WR.out MSG2WR.jfd Minimum Wind Speed (mis) =.5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 224 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window - 12035 Hours elevated plume w/ dir. in window = 0 Hours of calm winds 863 Hours direction not in window or calm = 56149 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 I.OOE-02 1.00E-02 I.OOE-02 1.00E-02 I.OOE-02 1.00E-02 I.00E-02 1.OOE-02 LOW LIM. 1.OOE-06 I.OOE-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 12898. 16084. 20584. 27095. 32581. 43342. 63818. 65970. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 56149. 52788. 47968. 40862. 35829. 24671. 3187. 643. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 18.68 23.35 30.03 39.87 47.63 63.73 95.24 99.03 100.00 100.00 95th PERCENTILE X/Q VALUES 1.48E-03 1.40E-03 1.28E-03 1.13E-03 9.14E-04 6.52E-04 3.68E-04 3.09E-04 2.44E-04 2.06E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.48E-03 2 to 8 hours 1.02E-03 8 to 24 hours 4.11 E-04 I to 4 days 2.73E-04 4 to 30 days 1.81E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.19E-03 1.55E-04 SECTOR-AVERAGE 1.28E-03 9.01E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 225 of 283 RWTIACI I.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 c-mail:j_ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 912/2003 at 08:24:51 ARCON INPUT " Number of Meteorological Data Files - 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 14.7 Building Area (mA2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mW3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) = 270 Wind direction sector width (deg) = 90 Wind direction window (deg) 225 - 315 Distance to intake (m) = 97.9 Intake height (m) 13.9 Terrain elevation difference (m) = .0 Output file names RWTIACI l.out RWTI ACI Ijfd Minimum Wind Speed (m/s) .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 226 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z e .00 Expanded output for code testing not selected Total number of hours ofdata processed = 70131 Hours of missing data = 1084 Hours direction in window e 18925 Hours elevated plume w/ dir. in window = 0 Hours ofcalm winds = 863 Hours direction not in window or calm - 49259 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.DOE-03 1.00E-03 1.00E-03 1.00E-03 1.00E-03 l.OOE-03 l.OOE-03 I.OOE-03 1.OOE-03 1.00E-03 LOW LIM. I.00E-07 1.00E-07 1.00E-07 I.00E-07 1.00E-07 I.00E-07 1.00E-07 I.00E-07 1.GOE-07 1.00E-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19788. 24643. 30753. 38888. 45248. 55820. 66561. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 49259. 44229. 37799. 29069. 23162. 12193. 444. 0. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 28.66 35.78 44.86 57.22 66.14 82.07 99.34 100.00 100.00 100.00 95th PERCENTILE XIQ VALUES 6.86E-04 6.57E-04 6.17E-04 5.55E-04 4.48E-04 3.19E-04 1.89E.04 1.59E-04 1.39E-04 1.26E-04 95% X/Q for standard averaging intervals 0 to 2 hours 6.86E-04 2 to 8 hours 5.12E-04 8 to 24 hours 2.01E-04 I to 4 days 1.46E-04 4 to 30 days 1.17E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 8.72E-04 6.48E-05 SECTOR-AVERAGE 5.09E-04 3.78E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 227 of 283 RWT2ACI I.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00a.m. NRC Contacts: J.Y. Lee Phone: (301) 415 1080 e-mail: jylI nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J.V. Ramsdell Phone: (509) 372 6316 e-mail:jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results ofsuch use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 9/2/2003 at 08:25:11
*****. ARCON INPUT *********
Number of Meteorological Data Files = 8 Meteor6logical Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 14.7 Building Area (m^2) = 2000.0 Effluent vertical velocity (Trns) = .00 Vent or stack flow (m"3/s) = - .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) - 207 Wind direction sector width (deg) 90 Wind direction window (deg) 162 - 252 Distance to intake (m) _ 72.6 Intake height (m) - 13.9 Terrain elevation difference (m) = .0 Output file names RWT2ACI l.out RWT2ACII jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) - .20
CA 06012 Rev.O Page 228 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data 1084 Hours direction in window = 24907 Hours elevated plume wl dir. in window = 0 Hours of calm wvinds = 863 Hours direction not in window or calm = 43277 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPERLIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 L.OOE-02 1.00E-02 1.OOE-02 1.OOE-02 1.00E-02 1.OOE-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 L.OOE-06 1.OOE-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 25770. 29676. 34490. 40673. 45559. 54141. 65714. 66461. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 43277. 39196. 34062. 27284. 22851. 13872. 1291. 152. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 37.32 43.09 50.31 59.85 66.60 79.60 98.07 99.77 100.00 100.00 95th PERCENTILE X/Q VALUES 1.27E-03 1.26E-03 1.22E-03 1.16E-03 9.54E-04 6.88E-04 4.37E-04 3.79E-04 3.29E-04 3.01E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.27E-03 2 to 8 hours 1.12E-03 8 to 24 hours .4.51E-04 I to 4 days 3.53E-04.
4 to 30 days 2.80E-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 1.54E-03 1.33E-04 SECTOR-AVERAGE 9.00E-04 7.75E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 229 of 283 RWTIAC13.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRCContacts: J. Y.Lee Phone: (301)415 1080 e-mail: jyllnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhsnrc.gov LA Brown Phone:(301)415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail:j_ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 9/2/2003 at 08:25:20
**** ARCON INPUT *******
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991 .MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CCI 998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 14.7 Building Area (nYA2) = 2000.0 Emuent vertical velocity (mis) - .00 Vent or stack flow (m"3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 270 Wind direction sector width (deg) = 90 Wind direction window (deg) - 225 - 315 Distance to intake (m) - 65.2 Intake height (m) = 16.1 Terrain elevation difference (m) = .0 Output file names RWTIAC13.out RWTI ACI 3.jfd Minimum Wind Speed (mrs) - .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 230 of 283 Sector averaging constant - 4.3 Initial value of sigma y - .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window - 18925 Hours elevated plume w/ dir. in window - 0 Hours of calm winds 863 Hours direction not in window or calm - 49259 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-42 1.00E2 1.00EE42 1.00E42 1.00EE42 1.00E402 1.00E-02 1.00E-02 L.OOE-02 1.00E-02 LOW LIM. 1.OOE-06 1.OOE-06 1.0OE406 1.00E-06 1.00E-06 1.00E406 1.00E-06 1.00E406 1.00E-06 1.00E406 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19788. 24643. 30753. 38888. 45248. 55820. 66561. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 49259. 44229. 37799. 29069. 23162. 12193. 444. 0. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 28.66 35.78 44.86 57.22 66.14 82.07 99.34 100.00 100.00 100.00 95th PERCENTILE X/Q VALUES 1.48E-03 1.41E-03 1.32E-03 I.19E-03 9.60E-04 6.82E-04 4.04E-04 3.41E-04 2.96E-04 2.69E.04 95% X/Q for standard averaging intervals 0 to 2 hours 1.48E-03 2 to 8 hours 1.09E-03 8 to 24 hours 4.29E-04 I to4days 3.11E04 4 to 30 days 2.48E.04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 1.90E-03 1.38E-04 SECTOR-AVERAGE L.11E403 8.03E-0S NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 231 of 283 RWT2AC13.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Programn Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl I nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 9/2/2003 at 08:25:25
*+** *ARCON INPUT ********
Numberof Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET
. CC1997.MET CC 1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 14.7 Building Area (mA2) - 2000.0 Effluent vertical velocity (m/s) = .00 Vent or stack flow (mW3/s) - .00 Ventor stack radius (m) - .00 Direction .. intake to source (deg) 180 Wind direction sector width (deg) - 90 Wind direction windowv(deg) - 135 -225 Distance to intake (m) = 65.2 Intake height (m) = 16.1 Terrain elevation difference (m) - .0 Output file names RWT2AC I3.out RWT2AC13.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 232 of 283 Sector averaging constant - 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window 21707 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 863 Hours direction not in window or calm - 46477 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPERLIM. I.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 11.OOE-02 1.OOE-02 LOW LIM. I.OOE-06 L.OOE-06 1.OOE-06 1.OOE-06 1.OOE-06 1.OOE-06 1.OOE-06 1.OOE-06 I.OOE-06 l.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 22570. 26459. 31208. 37328. 42336. 51818. 65637. 66443. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 46477. 42413. 37344. 30629. 26074. 16195. 1368. 170. 0. 0. TOTALXIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 32.69 38.42 45.52 54.93 61.89 76.19 97.96 99.74 100.00 100.00 95th PERCENTILE X/Q VALUES 1.51E-03 1.48E-03 1.43E-03 1.34E-03 1.09E-03 7.91E-04 4.75E.04 4.10E-04 3.56E-04 3.24E-04 95% X/Q for standard averaging intervals O to 2 hours 1.SIE-03 2 to 8 hours 1.28E-03 8 to 24 hours 5.17E-04 I to 4 days 3.69E-04 4 to 30 days 3.OOE-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 1.90E-03 1.62E-04 SECTOR-AVERAGE 1.1 IE-03 9.46E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 233 of 283 RWTISWGI .OUT Program
Title:
ARCON96. Developed For. U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl l enrc.gov J.J. Hayes Phone: (301) 415 3167 e-mail: jjhlnrc.gov LA Brown Phone: (30t) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jjramsdellQpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 9/ 212003 at 08:25:33
***+ ARCON INPUT *****+**
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 14.7 Building Area (mn2) = 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (m^3/s) . .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 231 Wind direction sector width (deg) - 90 Wind direction window (deg) = 186 - 276 Distance to intake (m) 63.1 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names RWTISWGI .out
- RWTISWGI jfd Minimum Wind Speed (nris) = .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 234 of 283 Sector averaging constant 4.3 Initial value of sigma y - .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours ofmissing data = 1084 Hours direction in window - 23875 Hours elevated plume w/ dir. in window - 0 Hours of calm winds - 863 Hours direction not in window or calm = 44309 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.OOE-02 1.00E-02 I.OOE.02 1.00E-02 I .OE-02 I.OOE-02 I .OOE-02 I.OOE-02 I .00E.02 I.OOE-02 LOW LIM. 1.00E-06 1.00E-06 I.OOE-06 I.OOE-06 1.00E-06 1.00E-06 I.OOE-06 1.OOE-06 1.OOE-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 24738. 28548. 33540. 40432. 46069. 55251. 66138. 66571. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 44309. 40324. 35012. 27525. 22341. 12762. 867. 42. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 35.83 41.45 48.93 59.50 67.34 81.24 98.71 99.94 100.00 100.00 95th PERCENTILE XIQ VALUES 1.66E-03 1.62E-03 1.56E-03 1.48E-03 1.20E-03 8.55E-04 5.46E-04 4.72E-04 4.07E-04 3.74E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.66E-03 2 to 8 hours 1.42E-03 8 to 24 hours 5.42E-04 I to 4 days 4.44E-04 4 to 30 days 3.47E-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 2.01E-03 1.72E-04 SECTOR-AVERAGE 1.17E-03 1.00E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 235 of 283 RWT2SWGI .OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl 1enrc.gov J.3. Hayes Phone:(301)415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: j_ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 9/2/2003 at 08:25:43
*'* ARCON INPUT *+*+*
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 14.7 Building Area (mA2) 2000.0 Effluent vertical velocity (ms) = .00 Vent or stack flow (m^3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 171 Wind direction sector width (deg) 90 Wind direction window (deg) - 126 - 216 Distance to intake (m) 106.4 Intake height (m) 9.5 Terrain elevation difference (m) = .0 Output file names RWT2SWGI .out RWT2SWGI .jfd Minimum Wind Speed (mls) e .5 Surface roughness length (m) .20
CA06012 Rev.0 Page 236 of 283 Sector averaging constant = 4.3 Initial value of sigma y - .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window = 18583 Hours elevated plume wi dir. in window = 0 Hours of calm winds - 863 Hours direction not in window or calm - 49601 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.OOE-03 1.OOE-03 1.OE-03 1.00E-03 L.GOE-03 1.00E-03 1.00E-03 1.00E-03 l.OOE-03 1.00E-03 LOW LIM. 1.OOE-07 1.00E-07 1.00E-07 l.OOE-07 1.00E-07 1.OOE-07 1.00E.07 1.00E-07 1.OOE-07 1.OOE-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19446. 23350. 28328. 34842. 40144. 50300. 65533. 66441. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 49601. 45522. 40224. 33115. 28266. 17713. 1472. 172. 0. 0. TOTALXIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 28.16 33.90 41.32 51.27 58.68 73.96 97.80 99.74 100.00 100.00 95th PERCENTILE X/Q VALUES 5.88E-04 5.67E-04 5.42E-04 S.OIE-04 4.05E-04 2.86E-04 1.66E-04 1.43E-04 1.23E-04 1.12E-04 95% X/Q for standard averaging intervals 0 to 2 hours 5.88E.04 2 to 8 hours 4.72E.04 8 to 24 hours 1.79E-04 I to 4 days 1.26E-04 4 to 30 days 1.03E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 7.44E-04 6.62E-05 SECTOR-AVERAGE 4.34E-04 3.86E.05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 237 of 283 RWTISWG2.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m: NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhhnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jTamsdellipnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 9/2/2003 at 08:25:37
******* ARCON INPUT-Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height oflower wind instrument (m) = 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 14.7 Building Area (m^2) = 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 279 Wind direction sector width (deg) 90 Wind direction window (deg) - 234 - 324 Distance to intake (m) - 106.4 Intake height (m) 9.5 Terrain elevation difference (m) = .0 Output file names RWTISWG2.out RWTI SWG2.jfd Minimum Wind Speed (mi/s)
Surface roughness length (m) -. 20
CA 06012 Rev.0 Page 238 of 283 Sector averaging constant 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window = 17704 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 863 Hours direction not in window or calm = 50480 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-03 1.OOE-03 1.OOE.03 I.OOE-03 1.OOE-03 I.OOE-03 1.OOE-03 1.00E-03 I.OOE-03 l.OOE-03 LOW LIM. I.OOE.07 I.OOE.07 I.OOE-07 I.OOE-07 1.OOE.07 1.00E.07 1.OOE-07 1.OOE-07 I.OOE-07 I.OOE-07 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 18567. 23096. 28822. 36526. 42695. 53653. 66491. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 50480. 45776. 39730. 31431.. 25715. 14360. 514. 0. 0. 0. TOTALXIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 26.89 33.53 42.04 53.75 62.41 78.89 99.23 100.00 100.00 100.00 95th PERCENTILE X/Q VALUES 5.74E-04 5.46E-04 5.IIE.04 4.62E-04 3.75E.04 2.74E.04 1.57E-04 1.33E-04 1.16E-04 1.06E.04 95% X/Q for standard averaging intervals 0 to 2 hours 5.74E-04 2 to 8 hours 4.25E.04 8 to 24 hours 1.79E-04 I to 4 days .1 8E.04 4 to 30 days 9.78E-05 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 7.44E.04 5.62E.05 SECTOR-AVERAGE 4.34E.04 3.27E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 239 of 283 RWT2SWG2.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone:(301)415 1080 e-mail: jyllenrc.gov J.J.Hayes Phone:(301)4153167 e-mail: jjhenrc.gov L.A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jamsdellpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 9/2/2003 at 08:25:48
**'** ARCON INPUT *********
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CCI992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 14.7 Building Area (mA2) = 2000.0 jffluent vertical velocity (m's) e .00 Vent or stack flow (m"3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) " 219 Wind direction sector width (deg) - 90 Wind direction window (deg) = 174-264 Distance to intake (m) e 63.1 Intake height (m) 9.5 Terrain elevation difference (m) = .0 Output file names RWT2SWG2.out RWvT2SWG2.jfd Minimum Wind Speed (m's) e.5 Surface roughness length (m) _ .20
CA 06012 Rev.0 Page 240 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in window = 24452 Hours elevated plume w/ dir. in window 00 Hours of calm winds = 863 Hours direction not in window or calm = 43732 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.OOE-02 I.OOE-02 .1.00E-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 l.00E.02 LOW LIM. I.OOE-06 I.OOE-06 I.OOE-06 1.OOE-06 I.OOE-06 I.OOE-06 I.OOE-06 I.OOE-06 l.OOE-06 l.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 25315. 29052. 33893. 40454. 45706. 54565. 66062. 66568. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 43732. 39820. 34659. 27503. 22704. 13448. 943. 45. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 36.66 42.18 49.44 59.53 66.81 80.23 98.59 99.93 100.00 100.00 95th PERCENTILE XIQ VALUES 1.66E-03 1.63E.03 1.58E-03 1.50E-03 1.22E-03 8.75E-04 5.58E-04 4.81E-04 4.20E-04 3.85E-04 95% X/Q for standard averaging intervals O to 2 hours 1.66E-03 2 to 8 hours 1.44E-03 8 to 24 hours 5.63E-04 I to 4 days 4.52E-04 4 to 30 days 3.59E-04 HOURLY VALUE RANGE MAXX/Q MIN X/Q CENTERLINE 2.01E-03 1.72E-04 SECTOR-AVERAGE 1.17E-03 L.OOE-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 241 of 283 RWTITB.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25,1997 11:00a.m. NRCContacts: J.Y.Lee Phone:(301)415 1080 e-mail: jyllenrc.gov I. J.Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: j_ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 15:09:39
**** ARCON INPUT ********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (im) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 14.7 Building Area (mA2) - 2000.0 Effluent vertical velocity (mis) - .00 Vent or stack flow (mr3Is) t .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) - 255 Wind direction sector width (deg) = 90 Wind direction window (deg) = 210 - 300 Distance to intake (m) = 92.4 Intake height (m) .9 Terrain elevation difference (m) .0 Output file names RWTITB.out RWTITB.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 242 of 283 Sector averaging constant 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number ofhours of data processed = 70131 Hours of missing data = 1084 Hours direction in window - 21537 Hours elevated plume w/ dir. in window = 0 Hours of calm winds 8663 Hours direction not in window or calm = 46647 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-03 1.00E-03 1.OOE-03 1.OOE-03 1.OOE-03 1.00E-03 1.00E-03 1.00E-03 1.OOE-03 1.O0E-03 LOW LIM. 1.OOE-07 1.OOE-07 1.OOE-07 1.OOE-07 1.00E-07 I.OOE-07 1.00E-07 1.OOE-07 1.OOE-07 1.OOE-07 ABOVERANGE 0. 0. 0. 0. 0. 0. 0. - 0. 0. 0. IN RANGE 22400. 27125. 32942. 40688. 46730. 56257. 66310. 66613. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 46647. 41747. 35610. 27269. 21680. 11756. 695. 0. 0. 0. TOTAL XlQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 32.44 39.38 48.05 59.87 68.31 82.72 98.96 100.00 100.00 100.00 95th PERCENTILE X/Q VALUES 7.72E-04 7.49E-04 7.18E-04 6.56E-04 5.26E-04 3.70E-04 2.33E-04 I.99E-04 1.71E-04 1.57E-04 95% XIQ for standard averaging intervals 0 to 2 hours 7.72E-04 2 to 8 hours 6.18E-04 8 to 24 hours 2.26E-04 I to 4 days. 1.87E-04 4 to 30 days 1.45E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 9.54E-04 7.72E-05 SECTOR-AVERAGE 5.56E-04 4.50E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 243 of 283 RWT2TB.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl l1nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhlnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jnamsdellepnl.gov Code Documentation: NUREGICR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 15:09:44
***+ ARCON INPUT *********
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 14.7 Building Area (m^2) = 2000.0 Effluent vertical velocity (m/s) - .00 Vent or stack flow (m^3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) = 195 Wind direction sector width (deg) = 90 Wind direction window (deg) = 150-240 Distance to intake (m) 92.4 Intake height (m) = .9 Terrain elevation difference (m) = .0 Output file names RWT2TB.out RWT2TB jfd Minimum Wind Speed (mis) Surface roughness length (m) = .20
CA 06012 Rev.0 Page 244 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window - 24862 Hours elevated plume w/ dir. in window = 0 Hours of calm winds -= 863 Hours direction not in window or calm = 43322 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.00E-03 1.OOE-03 l.00E-03 1.OOE-03 I.00E-03 1.00E-03 1.OOE-03 1.OOE-03 1.OOE-03 1.00E-03 LOW LIM. 1.00E-07 L.OOE-07 1.00E-07 1.00E-07 1.00E-07 1.00E-07 1.00E-07 1.00E-07 1.OOE-07 1.OOE-07 ABPVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 25725. 29605. 34105. 39889. 44613. 53474. 65674. 66442. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 1066. 95. 0. 0. ZERO 43322. 39267. 34447. 28068. 23797. 14539. 265. 76. 0. 0. TOTALXtQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 37.26 42.99 49.75 58.70 65.21 78.62 99.60 99.89 100.00 100.00 95th PERCENTILE XIQ VALUES 7.90E-04 7.72E-04 7A9E-04 7.16E-04 5.89E-04 4.30E-04 2.73E-04 2.36E-04 2.07E-04 1.89E-04 95% X/Q for standard averaging intervals 0 to 2 hours 7.90E-04 2 to 8 hours 6.92E-04 8 to 24 hours 2.86E-04 I to 4 days 2.21 E-04 4 to 30 days 1.76E-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 9.54E-04 8.32E-05 SECTOR-AVERAGE 5.56E-04 4.85E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 245 of 283 RWTIWR.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 15:09:27
**'* ARCON INPUT ****+*****
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1 994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 14.7 Building Area (m^2) - 2000.0 Effluent vertical velocity (m/s) = .00 Vent or stack flow (mW3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) e 324 Wind direction sector width (deg) 90 Wind direction window (deg) - 279 - 009 Distance to intake (m) . 46.9 Intake height (m) - 9.1 Terrain elevation difference (m) .0 Output file names RWTIWR.out RWTI WRjfd Minimum Wind Speed (m/s) .5 Surface roughness length (m) . .20
CA 06012 Rev.0 Page 246 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window = 18468 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 863 Hoursdirectionnotinwindoworcalm = 49716 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 LOW LIM. l.OOE.06 1.OOE-06 1.OOE-06 l.OOE-06 1.OOE-06 1.00E-06 l.OOE-06 1.OOE-06 1.OOE-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19331. 23084. 28162. 35057. 40689. 51300. 66253. 66558. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 49716. 45788. 40390. 32900. 27721. 16713. 752. 55. 0. 0. TOTALXIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 28.00 33.52 41.08 51.59 59.48 75.43 98.88 99.92 100.00 100.00 95th PERCENTILE X/Q VALUES 2.57E-03 2.50E.03 2.41E-03 2.24E-03 1.83E-03 .1.31E-03 7.57E-04 6.68E-04 5.73E-04 5.21E-04 95% X/Q for standard averaging intervals 0 to 2 hours 2.57E-03 2 to 8 hours 2.13E-03 8 to 24 hours 8.50E-04 I to 4 days 5.71 E-04 4 to 30 days 4.85E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 3.54E-03 2.54E-04 SECTOR-AVERAGE 2.07E-03 1.48E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 247 of 283 RWT2WROUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl l inrc.gov J.J.Hayes Phone:(301)4153167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jamsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third partys use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 15:09:32
* **** ARCON INPUT ********+*
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 14.7 Building Area (mA2) = 2000.0 Effluent vertical velocity (mls) .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) - 126 Wind direction sector width (deg) 90 Wind direction window (deg) - 081 -171 Distance to intake (m) 46.9 Intake height (m) = 9.1 Terrain elevation difference (m) = .0 Output file names RWT2WR.out RWT2WR.jfd Minimum Wind Speed (mns) Surface roughness length (m) = .20
CA06012 Rev.0 Page 248 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data e 1084 Hours direction in window = 10496 Hours elevated plume w/ dir. in window - 0 Hours of calm winds = 863 Hours direction not in window or calm - 57688 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 l.00E-02 1.00E-02 LOW LIM. I.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.003-06 1.00E-06 1.00E-06 1..OOE6 .00E-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. INRANGE 11359. 14517. 18925. 25739. 31626. 43793. .64380. 66249. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 57688. 54355. 49627. 42218. 36784. 24220. 2625. 364. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%hNONZERO 16.45 21.08 27.61 37.88 46.23 64.39 96.08 99.45 100.00 100.00 95th PERCENTILE X/Q VALUES 2.30E-03 2.10E-03 1.82E-03 1.57E-03 1.24E-03 8.47E-04 4.85E-04 3.99E-04 3.30E-04 2.85E-04 95% X/Q for standard averaging intervals 0 to 2 hours 2.30E-03 2 to 8 hours 1.32E-03 8 to 24 hours 4.87E-04 I to 4 days 3.64E-04 4 to 30 days 2.55E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 3.54E-03 3.78E-04 SECTOR-AVERAGE 2.06E-03 2.20E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.O0 Page 249 of 283 VSIACIl.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00an.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllI nrc.gov J.3J. Hayes Phone: (301) 415 3167 e-mail:bjh~nrc.gov L A Browvn Phone: (301) 415 1232 e-mail: lab2@nrc-gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:j ramidell&pn.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/18/2003 at 09:45:19
****ARCON INPUIT Number of Meteorological Data Files =8 Meteorological Data File Names CC1991.MET CC1 992.MET CCI1993.MET CC1994.MET CC 1995.M ET CCI1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (in) 10.0 Height of upper wind instrument (in) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (in) = 48.3 Building Area (mA2) =2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (in) = .00 Direction .. intake to source (deg) 299 Wind direction sector width (deg) = 90 Wind direction window (deg) =254 - 344 Distance to intake (in) 57.7 Intake height (in) = 13.9 Terrain elevation difference (in) .0 Output file names VS IAC I Lout VS IACl Lijfd Minimum Wind Speed (m/s) = .5 Surface roughness length (in) = .20
CA 06012 Rev.0 Page 250 of 283 Sector averaging constant = 4.3 Initial value of sigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window - 17356 Hours elevated plume wI dir. in window = 0 Hours of calm winds - 1058 Hours direction not in window or calm = 50633 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.OOE-02 I.OOE-02 I.OOE-02 I.OOE-02 I.OOE.02 I.00EE2 I.OOE-02 I.OOE.02 IE.OOE-02 I.OOE-02 LOW LIM. l.OOE-06 L.OOE-06 I.OOE-06 I.OOE-06 I.OOE-06 1.OOE-06 I.OOE-06 l.OOE-06 I.OOE-06 I.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 18414. 21661. 26284. 33018. 38706. 49773. 66208. 66556. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 50633. 47211. 42268. 34939. 29704. 18240. 797. 57. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 26.67 31.45 38.34 48.59 56.58 73.18 98.81 99.91 100.00 100.00 95th PERCENTILE X/Q VALUES 1.42E-03 1.38E-03 1.31E-03 1.20E-03 9.62E-04 6.90E-04 4.OOE-04 3.40E-04 2.90E-04 2.66E-04 95% X/Q for standard averaging intervals 0 to 2 hours I A2E-03 2 to 8 hours 1.12E-03 8 to 24 hours 4.38E-04 I to 4 days 3.03E-04 4 to 30 days 2.45E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.79E-03 8.65E-05 SECTOR-AVERAGE 1.05E-03 5.04E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 251 of 283 VS2ACI LOUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J.J.Hayes. Phone:(301)4153167 e-mail: jjhenrc.gov LA Brown Phone:(301)415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results ofsuch use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/18/2003 at 09:45:29
.**.*.* ARCON INPUT ******
Number of Meteorological Data Files. 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) = 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 48.3 Building Area (mA2) = 2000.0 Effluent vertical velocity (m/s) = .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) = 195 Wind direction sector width (deg) = 90 Wind direction window (deg) 150 - 240 Distance to intake (m) 18.2 Intake height (m) 13.9 Terrain elevation difference (m) = .0 Output file names VS2ACI L.out VS2AC I Ijfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) .20
CA06012 Rev.0 Page 252 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window = 23249 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 1058 Hours direction not in window or calm - 44740 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.OOE-02 1.OOE-02 1.OOE-02 L.OOE-02 I.OOE-02 I.OOE-02 1.00E-02 1.00E-02 L.OOE-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 L.OOE-06 1.OOE-06 1.00E-06 1.00E-06 L.OOE-06 L.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 24307. 27669. 31947. 37537. 42169. 51253. 65398. 66433. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 44740. 41203. 36605. 30420. 26241. 16760. 1607. 180. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 3520 40.17 46.60 55.24 61.64 75.36 97.60 99.73 100.00 100.00 95th PERCENTILE X/Q VALUES 4.34E-03 4.22E-03 4.01E-03 3.72E-03 3.01E-03 2.18E-03 1.37E-03 L.18E-03 1.02E-03 9.40E-04 95% XIQ for standard averaging intervals 0 to 2 hours 4.34E-03 2 to 8 hours 3.51E-03 8 to 24 hours 1.41 E-03 I to 4 days 1.10E-03 4 to 30 days 8.74E-04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 5.17E-03 3.04E-04 SECTOR-AVERAGE 3.01E-03 1.77E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 253 of 283 VSIAC13.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J.Y. Lee Phone: (301) 415 1080 e-mail:jyllenrc.gov J. J. Hayes Phone (301) 415 3167 e-mail: jjhQnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer. J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramnsdellspnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/18/2003 at 09:45:36
***+ ARCON INPUT *******
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 48.3 Building Area (mA2) 2000.0 Effluent vertical velocity (mls) = .00 Vent or stack flow (m13/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 327 Wind direction sector width (deg) 90 Wind direction window (deg) 282 - 012 Distance to intake (m) 32.9 Intake height (m) 16.1 Terrain elevation difference (m) - .0 Output file names VSIAC13.out VSIAC13.jfd Minimum Wind Speed (m/s) e .5 Surface roughness length (m) = .20
CA06012 Rev.0 Page 254 of 283 Sector averaging constant 4.3 Initial value ofsigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window = 20846 Hours elevated plume w/ d ir.in window = 0 Hours of calm winds = 1058 Hours direction not in window or calm - 47143 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 l.00E-02 1.00E-02 1.00E-02 1.OOE-02 LOW LIM. 1.00E-06 1.OOE-06 I.OOE-06 I.GOE-06 1.OOE-06 1.OOE-06 1.OOE-06 1.00E-06 I.OOE-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 21904. 25327. 30086. 36674. 42091. 52257. 66308. 66562. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 47143. 43545. 38466. 31283. 26319. 15756. 697. 51. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 31.72 36.77 43.89 53.97 61.53 76.83 98.96 99.92 100.00 100.00 95th PERCENTILE X/Q VALUES 2.89E-03 2.80E-03 2.66E-03 2.44E-03 1.97E-03 1.42E-03 8.29E-04 7.25E-04 6.30E-04 5.72E-04 95% X/Q for standard averaging intervals 0 to 2 hours 2.89E-03 2 to 8 hours 2.29E-03 8 to 24 hours 9.15E-04 I to4 days 6.32E-04 4 to 30 days 5.33E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 3.72E-03 1.42E-04 SECTOR-AVERAGE 2.17E-03 8.25E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 2S5 of 283 VS2AC13.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301)415 1080 e-mail: jyllInrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhQnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J.V. Ramsdell Phone: (509) 372 6316 e-mail: jjamsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/18/2003 at 09:45:41
' ARCON INPUT * "'
Number of Meteorological Data Files - 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CCI 997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 48.3 Building Area (mA2) - 2000.0 Effluent vertical velocity (m/s) - .00 Vent or stack flow (mW3/s) - .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) e 122 Wind direction sector width (deg) 90 Wind direction window (deg) 077 - 167 Distance to intake (m) 32.9 Intake height (m) = 16.1 Terrain elevation difference (m) - .0 Output file names VS2AC13.out VS2AC13.jfd Minimum Wind Speed (mis) .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 2S6 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data = 1084 Hours direction in window - 11787 Hours elevated plume wI dir. in window = 0 Hours of calm winds - 1058 Hours direction not in window or calm = 56202 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.OE-02 1.OOE-02 1.OOE-02 1.OOE-02 1.OOE-02 L.GOE-02 I .OOE-02 1.OOE-02 1.00E-02 LOW LIM. 1.00E-06 L.OOE-06 L.00E-06 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 12845. 15748. 19911. 26462. 32227. 44143. 64522. 66202. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 56202. 53124. 48641. 41495. 36183. 23870. 2483. 411. 0. 0. TOTAL XIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 18.60 22.87 29.05 38.94 47.11 64.90 96.29 99.38 100.00 100.00 95th PERCENTILE X/Q VALUES 2.62E-03 2.45E-03 2.22E-03 1.94E-03 1.54E-03 1.06E-03 5.79E-04 4.83E-04 3.95E-04 3.51E-04 95% X/Q for standard averaging intervals 0 to 2 hours 2.62E-03 2 to 8 hours 1.72E-03 8 to 24 hours 6.13E-04 I to 4 days 4.20E-04 4 to 30 days 3.16E.04 HOURLY VALUE RANGE MAX X/Q MIN XIQ CENTERLINE 3.72E-03 2.72E-04 SECTOR-AVERAGE 2.17E-03 1.59E-04 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 257 of 283 VS ISWGI.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRCContacts: J.Y.Lee Phone: (301)415 1080 e-mail:jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2Gnrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:j_ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/18/2003 at 09:45:51
**'+ ARCON INPUT **********
Number of Meteorological Data Files e 8 Meteorological Data File Names CC1991.MET CCI992.MET-CCI993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CCI 998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 48.3 Building Area (mn2) - 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mW3ls) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 187 Wind direction sector width (deg) = 90 Wind direction window (deg) = 142-232 Distance to intake (m) 12.3 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names VSISWGI.out VSISWGI .jfd Minimum Wind Speed (mis) = .5 Surface roughness length (m) .20
CA 06012 Rev.0 Page 258 of 283 Sector averaging constant 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data - 1084 Hours direction in window = 22730 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 1058 Hours direction not in window or calm - 45259 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 I.OOE-02 1.002-2 1.OE-02 I.OOE-02 I .00E-02 1.OOE-02 1.00E-02 1.002-02 1.OOE-02 LOW LIM. 1.00E-06 1.00E-06 l.OOE-06 1.00E-06 1.00E-06 1.OOE-06 I.OOE-06 I.OOE-06 l.OOE-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. INRANGE 23788. 27001. 31162. 36682. 41302. 50501. 65362. 66433. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 45259. 41871. 37390. 31275. 27108. 17512. 1643. 180. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 34.45 39.20 45.46 53.98 60.37 74.25 97.55 99.73 100.00 100.00 95th PERCENTILE X/Q VALUES 3.94E-03 3.84E-03 3.65E-03 3.40E-03 2.75E-03 I.99E-03 1.23E-03 1.06E-03 9.08E-04 8.43E-04 95% X/Q for standard averaging intervals 0 to 2 hours 3.94E-03 2 to 8 hours 3.21 E-03 8 to 24 hours 1.28E-03 I to 4 days 9.74E-04 4 to 30 days 7.84E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 4.73E-03 2.80E-04 SECTOR-AVERAGE 2.76E-03 1.63E-04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 259 of 283 VS2SWGI.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRCContacts: J.Y.Lee Phone: (301)415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellspnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/18/2003 at 09:51:04
***+ ARCON INPUT *****'***
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CCI992.MET CC1993.MET CC1994.MET CC1995.MET CCI996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) - 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) , 48.3 Building Area (mA2) - 2000.0 Effluent vertical velocity (mis) .00 Vent or stack flow (mA3/s) e .00 Vent or stack radius (m) - .00 Direction .. intake to source (deg) = 142 Wind direction sector width (deg) = 90 Wind direction window (deg) 097 - 187 Distance to intake (m) = 72.4 Intake height (m) ' 9.5 Terrain elevation difference (m) - .0 Output file names VS2SWGI.out VS2SWGI .jfd Minimum Wind Speed (m/s) Surface roughness length (m) = .20
CA 06012 Rev.0 Page 260 of 283 Sector averaging constant - 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window - 13655 Hours elevated plume wI dir. in window - 0 Hours of calm winds - 1058 Hours direction not in window or calm = 54334 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.001E-02 I.OOE-02 I.OOE-02 l.OOE-02 l.OOE-02 I.OOE-02 I.OOE-02 I.00E-02 .OOE-02 l.OOE-02 LOW LIM. 1.OOE-06 L.GOE-06 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 l.OOE-06 1.00E-06 1.OOE-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 14713. 17558. 21769. 28278. 33968. 45258. 64766. 66282. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 54334. 51314. 46783. 39679. 34442. 22755. 2239. 331. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 21.31 25.49 31.76 41.61 49.65 66.54 96.66 99.50 100.00 100.00 95th PERCENTILE X/Q VALUES 9.33E-04 8.97E-04 8.33E-04 7.42E-04 5.85E-04 3.95E-04 2.23E-04 1.88E-04 1.57E-04 1.40E-04 95% X/Q for standard averaging intervals 0 to 2 hours 9.33E-04 2 to 8 hours 6.78 E-04 8 to 24 hours 2.21 E-04 I to 4 days 1.65E-04 4 to 30 days 1.27E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.22E-03 9.96E-05 SECTOR-AVERAGE 7.1 IE-04 5.8 1E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 261 of 283 VSISWG2.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhsnrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:j_ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/18/2003 at 09:46:08
******* ARCON INPUT *******
Number of Meteorological Data Files 8 Meteorological Data File Names
- CC1991.MET CC1992.MET CC1993.MET CC1994.MET CCI995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 48.3 Building Area (mW2) 2000.0 Effuent vertical velocity (mrs) = .00 Vent or stack flow (mA3/s) . .00 Vent or stack radius (m) .00 Direction ;. intake to source (deg) 307 Wind direction sector width (deg) = 90 Wind direction window (deg) 262 - 352 Distance to intake (m) = 72.4 Intake height (m) 9.5 Terrain elevation difference (m) = .0 Output file names VS ISWG2.out VSISWG2jfd Minimum Wind Speed (mis) .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 262 of 283 Sector averaging constant = 4.3 Initial value of sigma y .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours ofdata processed - 70131 Hours of missing data 1084 Hours direction in window - 18098 Hours elevated plume w/ dir. in window = 0 Hours ofcalm winds - 1058 Hours direction not in window or calm - 49891 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 I.OOE-02 I.OOE-02 1.OOE-02 1.00E-02 .OOE-02 .OOE-02 1.00E-02 .OOE02 1.OOE-02 LOW LIM. 1.00E-06 L.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 I.OOE-06 1.00E-06 I.OOE-06 L.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19156. 22391. 27040. 33804. 39471. .50434. 66260. 66545. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 49891. 46481. 41512. 34153. 28939. 17579. 745. 68. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 27.74 32.51 39.44 49.74 57.70 74.15 98.89 99.90 100.00 100.00 95th PERCENTILE X/Q VALUES 9.65E.04 9.43E-04 8.97E-04 8.24E-04 6.66E-04 4.79E-04 2.75E-04 2.35E.04 2.03E-04 1.84E-04 95% XIQ for standard averaging intervals 0 to 2 hours 9.65E.04 2 to 8 hours 7.78E-04' 8 to 24 hours 3.06E-04 I to 4 days 2.07E-04 4 to 30 days I.70E.04 HOURLY VALUE RANGE MAX XIQ MIN X/Q CENTERLINE 1.22E-03 5.94E-05 SECTOR-AVERAGE 7.11 E-04 3.47E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 263 of 283 VS2SWG2.OUT ProgramrTitle: ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyllenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhhnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdelllpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/18/2003 at 09:51:09
****+** ARCON INPUT
- Number of Meteorological Data Files 8.
Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) - 48.3 Building Area (m^t2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (m^3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) = 262 Wind direction sector width (deg) 90 Wind direction window (deg) 217 -307 Distance to intake (m) 12.3 Intake height (m) 9.5 Terrain elevation difference (m) - .0 Output file names VS2SWG2.out VS2SWG2.jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 264 of 283 Sector averaging constant 4.3 Initial value of sigma y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 701.31 Hours of missingdata - 1084 Hours direction in window = 17841 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 1058 Hours direction not in window or calm - 50148 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E.02 1.00E-02 1.00E-02 L.OOE-02 LOW LIM. 1.OOE-06 1.OOE-06 1.OOE-06 1.OOE-06 l.OOE-06 1.OOE-06 1.00E-06 1.OOE-06 1.00E306 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 18899. 23007. 28560. 36324. 42440. 53400. 65893. 66514. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. .0. 0. 0. ZERO 50148. 45865. 39992. 31633. 25970. 14613. 1112. 99. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NONZERO 27.37 33.41 41.66 53.45 62.04 78.51 98.34 99.85 100.00 100.00 95th PERCENTILE X/Q VALUES 3.82E-03 3.63E-03 3.36E-03 3.00E-03 2.40E-03 1.68E-03 9.91E-04 8.32E-04 7.10E-04 6.48E-04 95% X/Q for standard averaging intervals 0 to 2 hours 3.82E-03 2 to 8 hours 2.72E-03 8 to 24 hours 1.02E-03.
I to4 days 7.61E-04 4 to 30 days 5.95E-04 HOURLY VALUE RANGE MAX X/Q MIN XIQ CENTERLINE 4.73E-03 2.56E-04 SECTOR-AVERAGE 2.76E-03 1.49E.04 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 265 of 283 VS ITB.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jyl I 3nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail:jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2Gnrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jpnrasdell3pnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/ 11/2003 at 15:36:18
- ARCON INPUT *******.
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.M ET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) e 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 48.3 Building Area (mA2) = 2000.0 Effluent vertical velocity (m/s) .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) . .00 Direction .. intake to source (deg) = 275 Wind direction sector width (deg) 90 Wind direction window (deg) e 230 - 320 Distance to intake (m) = 42.0 Intake height (m) .9 Terrain elevation difference (m) - .0 Output file names VSITB.out VS ITB.jfd Minimum Wind Speed (in's) .5 Surface roughness length (m) e .20
CA 06012 Rev.0 Page 266 of 283 Sector averaging constant - 4.3 Initial value ofrsigma y .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed- 70131 Hours of missing data - 1084 Hours direction in window - 17022 Hours elevated plume w/ dir. in window 0 Hours of calm winds - 1058 Hours direction not in window or calm - 50967 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 l.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E-02 I.OOE-02 LOW LIM. l.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 l.00E-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 18080. 21865. 27068. 34396. 40312. 51444. 65866. 66522. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 50967. 47007. 41484. 33561. 28098. 16569. 1139. 91. 0. 0. TOTALX1Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 26.19 31.75 39.49 50.61 58.93 75.64 98.30 99.86 100.00 100.00 95th PERCENTILE X/Q VALUES 1.63E-03 1.55E-03 *1.44E-03 1.30E-03 1.04E-03 7.40E-04 4.26E-04 3.58E-04 3.11E-04 2.83E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.63E-03 2 to 8 hours 1.19E-03 8 to 24 hours . 4.61 E-04 I to 4 days 3.22E-04 .4 to 30 days 2.61E-04 HOURLY VALUE RANGE MAX X/Q MINX/Q CENTERLINE 2.01 E-03 9.67E-05 SECTOR-AVERAGE 1.17E-03 5.64E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 267 of 283 VS2TB.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997. 11:00 a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail: jylIenrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov LA Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdelllpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/112003 at 15:36:24
**** ARCON INPUT "
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CCI994.MET CCI995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 48.3 Building Area (mA2) = 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mA3/s) . .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 175 Wind direction sector width (deg) 90 Wind direction window (deg) - 130 - 220 Distance to intake (m) = 42.0 Intake height (m) .9 Terrain elevation difference (m) = .0 Output file names VS2TB.out VS2TB jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 268 of 283 Sector averaging constant 4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number ofhours of data processed = 70131 Hours of missing data = 1084 Hours direction in window = 20642 Hours elevated plume wi dir. in window = 0 Hours of calm winds e 1058 Hours direction not in window or calm = 47347 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.OOE-02 1.OOE-02 I.OOE-02 I.OOE-02 1.OOE-02 l.OOE-02 1.00E-02 1.00E-02 1.00E-02 LOW LIM. I .OOE.06 I.DOE-06 I .OOE-06 I .OOE-06 I.OOE-06 1.LOE-0 1.005-066 1.00-06 I .OOE-06 1.005-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 21700. 24968. 29218. 34985. 39778. 49232. 65164. 66430. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0.- 0. 0. 0. ZERO 47347. 43904. 39334. 32972. 28632. 18781. 1841. 183. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 31.43 36.25 42.62 51.48 58.15 72.39 97.25 99.73 100.00 100.00 95th PERCENTILE X/Q VALUES 1.68E-03 1.62E-03 l.55E-03 1.42E-03 1.15E-03 8.17E-04 4.92E-04 4.24E-04 3.59E-04 3.36E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.68E-03 2 to 8 hours 1.34E-03 8 to 24 hours 5.14E-04 I to i days 3.84E-04 4 to 30 days 3.12E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 2.01E-03 1.32E-04 SECTOR-AVERAGE 1.17E-03 7.72E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 269 of 283 VS IWR.OUT. Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m. NRCContacts: J.Y.Lee Phone:(301)415 1080 e-mail: jyll enrc.gov J.J. Hayes Phone: (301)415 3167 e-mail: jjhhnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemrient Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal' liability or responsibilities for any third party's use, or the results ofsuch use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. ProgramRun 8/11/2003 at 15:36:03
**** ARCON INPUT *****..
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) = 10.0 Height of upper wind instrument (m) - 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 48.3 Building Area (mA2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mA3/s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) = 017 Wind direction sector width (deg) = 90 Wind direction window (deg) - 332 - 062 Distance to intake (m) 68.5 Intake height (m) = 9.1 Terrain elevation difference (m) = .0 Output file names VSI WRout VSIWR.jfd Minimum Wind Speed (mls) .5 Surface roughness length (in) = .20
CA 06012 Rev.0 Page 270 of 283 Sector averaging constant = 4.3 Initial value of sigrna y = .00 Initial value of sigma z .00 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data - 1084 Hours direction in window - 18810 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 1058 Hoursdirectionnotinwindoworcalm - 49179 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 I.OOE-02 1.OOE-02 1.OOE-02 1.00E-02 1.OOE-02 I.00E-02 I.OOE-02 LOW LIM. 1.00E-06 1.00E-06 I.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 .00E-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 19868, 22924. 27123. 33172. 38489. 48612. 65635. 66449. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 49179. 45948. 41429. 34785. 29921. 19401. 1370. 164. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 28.77 33.28 39.57 48.81 56.26 71.47 97.96 99.75 100.00 100.00 95th PERCENTILE X/Q VALUES 9.54E-04 8.97E-04 8.35E-04 7.53E-04 6.16E-04 4A8E-04 2.72E404 2.36E-04 1.96E-04 1.71E-04 95% X/Q for standard averaging intervals 0 to 2 hours 9.54E-04 2 to 8 hours 6.86E.04 8 to 24 hours 2.95E-04 I to 4 days 2.13E-04 4 to 30 days 1.56E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.32E403 4.35E-05 SECTOR-AVERAGE 7.68E-04 2.54E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 271 of 283 VS2WR.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyllenrc.gov I. J. Hayes Phone: (301) 415 3167 e-mail: jjhhnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J.V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/11/2003 at 15:36:10
.****+* ARCON INPUT *****'***
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) = 10.0 Height of upper wind instrument (m) = 60.0 Wind speeds entered as rneters/second Ground-level release Release height (m) 48.3 Building Area (mA2) = 2000.0 Effluent vertical velocity (m/s) = .00 Vent or stack flow (mA3/s) - .00 Vent or stack radius (m) . .00 Direction ;. intake to source (deg) 073 Wind direction sector width (deg) = 90 Wind direction window (deg) 028 - 118 Distance to intake (m) = 68.5 Intake height (m) - 9.1 Terrain elevation difference (m) = .0 Output file names VS2WR.out VS2NVR.jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) .20
CA06012 Rev.0 Page 272 of 283 Sector averaging constant .4.3 Initial value of sigma y = .00 Initial value of sigma z = .00 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window = 10690 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 1058 Hours direction not in window or calm = 57299 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. I 2 4 8 12. 24 96 168 360 720 UPPER LIM. 1.00E-02 1.00E-02 1.00E-02 1.00E-02 1.00E.02 1.00E-02 1.00E.02 1.OOE-02 1.OOE-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.OOE-06 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 11748. 14634. 18827. 25136. 30478. 41380. 63374. 65816. 67243. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 4. 0. ZERO 57299. 54238. 49725. 42821. 37932. 26633. 3631. 797. 0. 0. TOTAL XIQs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 17.01 21.25 27.46 36.99 44.55 60.84 94.58 98.80 100.00 100.00 95th PERCENTILE X/Q VALUES 8.73E-04 8.30E.04 7.37E-04 6.53E-04 5.19E.04 .3.59E-04 2.02E-04 1.69E-04 1.36E-04 1.16E-04 95% X/Q for standard averaging intervals 0 to 2 bours 8.73E-04 2 to 8 hours 5.79E-04 8 to 24 hours 2.12E-04 I to 4 days 1.49E-04 4 to 30 days 1.03E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.32E-03 4.35E-05 SECTOR-AVERAGE 7.67E-04 2.54E-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 273 of 283 CTMTI WRA.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June 25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mnail: jyl I@nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhnrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J. V. Ramsdell Phone: (509) 372 6316 e-mail:j ramsdell1pnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third partys use: or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/1412003 at 13:19:38
*""* ARCON INPUT ********
Number of Meteorological Data Files 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1 995.MET CC1996.MET CC1997.MET CC1998.MET. Height of lower wind instrument (m) e 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) 29.7 Building Area (mA2) 1.0 Efuent vertical velocity (mis) - .00 Vent or stack fldw (mr3/s) . .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) = 358 Wind direction sector width (deg) = 90 Wind direction window (deg) = 313 - 043 Distance to intake (m) - 33.4 Intake height (m) 9.1 Terrain elevation difference (m) - .0 Output file names CTMTI WRA.out CTMTI WRA.jfd Minimum Wind Speed (mis) = .5 Surface roughness length (in) = .20
CA06012 Rev.0 Page 274 of 283 Sector averaging constant 4.3 Initial value of sigma y = 6.99 Initial valueofsigmaz 5.18 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data . - 1084 Hours direction in window = 19377 Hours elevated plume w/ dir. in window - 0 Hours of calm winds - 863 Hours direction not in window or calm - 48807 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.001E-02 I.OO0E-02 1.00E-02 1.002-02 1.002-02 1.002-02 1.001-02 1.00E-2 1. -02 E.00-02 LOW LIM. 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 20240. 24125. 29070. 35744. 41353. 51447. 66031. 66557. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 48807. 44747. 39482. 32213. 27057. 16566. 974. 56. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
%NON ZERO 29.31 35.03 42.41 52.60 60.45 75.64 98.55 99.92 100.00 100.00 95th PERCENTILE X/Q VALUES 1.22E-03 I.IIE-03 1.00E-03 9.04E-04 7.39E-04 5.36E-04 3.30E-04 2.96E-04 2.56E-04 2.34E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.22E-03 2 to 8 hours 7.98E-04 8 to 24 hours 3.52E-04 I to4 days 2.61E-04 4 to 30 days 2.19E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.61 E-03 1.68E-04 SECTOR-AVERAGE 9.39E-04 9.77E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 275 of 283 CTMTI WRB.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 .11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyll nrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer: J.V. Ramsdell Phone: (509) 372 6316 e-mail:j_ramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/14/2003 at 13:19:46
.*.*.*. ARCON INPUT *******
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) e 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 29.7 Building Area (m2) = 10000.0 Effluent vertical velocity (mis) .00 Vent or stack flow (m^3/s) .00 Vent or stack radius (m) = .00 Direction .. intake to source (deg) 358 Wind direction sector width (deg) = 90 Wind direction window (deg) e 313 -043 Distance to intake (m) - 33.4 Intake height (m) 9.1 Terrain elevation difference (m) = .0 Output file names CTMTI WRB.out CTMTIWRB jfd Minimum Wind Speed (mls) = .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 276 of 283 Sector averaging constant 4.3 Initial value of sigma y = 6.99 Initialvalueofsigmaz - 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in window - 19377 Hours elevated plume w/ dir. in window = 0 Hours of calm winds - 863 Hours direction not in window or calm - 48807 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. 1.OOE-02 1.00E-02 1.OOE-02 1.00E-02 1.OOE-02 1.00E-02 I.OOE-02 I.00E-02 1.OOE-02 1.OOE-02 LOW LIM. 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.OOE-06 1.OOE-06 1.00E406 1.00E-06 1.OOE-06 1.OOE-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 20240. 24125. 29070. 35744. 41353. 51447. 66031. 66557. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 48807. 44747. 39482. 32213. 27057. 16566. 974. 56. 0. 0. TOTALX/Qs 69047. 68872. 68552. 67957. .68410. 68013. 67005. 66613. 67247. 67747.
% NONZERO 29.31 35.03 42.41 52.60 60.45 75.64 98.55 99.92 100.00 100.00 95th PERCENTILE XIQ VALUES 1.20E-03 1.09E-03 9.80E-04 8.82E-04 7.19E-04 5.19E-04 3.19E-04 2.84E-04 2.47E-04 2.26E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.20E-03 2 to 8 hours 7.77E-04 8 to 24 hours 3.38E-04 I to 4 days 2.53E-04 .4 to 30 days 2. 1 E-04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.60E-03 1.50E-04 SECTOR-AVERAGE 9.34E-04 8.76E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 277 of 283 CTMTIWRC.OUT Program
Title:
ARCON96. Developed For U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25, 1997 11:00a.m. NRC Contacts: J. Y. Lee Phone: (301) 415 1080 e-mail:jyl lnrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjhenrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J. V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellepnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/14/2003 at 13:27:35
*"'*' ARCON INPUT e*""""
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CCI994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) e 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 29.7 BuildingArea (mA2) = 100.0 Effluent vertical velocity (rrs) - .00 Vent or stack flow (mW31s) = .00 Vent or stack radius (m) .00 Direction .. intake to source (deg) 358 Wind direction sector width (deg) 90 Wind direction window (deg) = 313 - 043 Distance to intake (m) 33.4 Intake height (m) 9.1 Terrain elevation difference (m) = .0 Output file names CTMTI WRC.out CTMTIWRCjfd Minimum Wind Speed (mrs) Surface roughness length (m) = .20
CA 06012 Rev.0 Page 278 of 283 Sector averaging constant 4.3 Initial value of sigma y 6.99 Initial value of sigma z 5.18 Expanded output for code testing not selected Total number of hours of data processed - 70131 Hours of missing data = 1084 Hours direction in %window = 19377 Hours elevated plume w/ dir. in window = 0 Hours of calm winds = 863 Hours direction not in window or calm = 48807 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 96 168 360 720 UPPER LIM. I.00E-02 1.00E-02 1.OOE-02 1.OOE-02 1.00E-02 l.00E-02 I.OOE-02 1.00E-02 1.00E-02 1.00E-02 LOW LIM. 1.00E-06 1.00E-06 1.OOE-06 1.00E-06 1.00E-06 1.00E-06 1.00E.06 1.00E-06 1.OOE-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0.. 0. 0. IN RANGE 20240. 24125. 29070. 35744. 41353. 51447. 66031. 66557. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 48807. 44747. 39482. 32213. 27057. 16566. 974. 56. 0. 0. . TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 29.31 35.03 42.41 52.60 60.45 75.64 98.55 99.92 100.00 100.00 95th PERCENTILE X/Q VALUES 1.20E-03 L.10E-03 .9.84E-04 8.87E-04 7.24E-04 5.23E-04 3.22E-04 2.87E-04 2.49E-04 2.27E-04 95% X/Q for standard averaging intervals 0 to 2 hours 1.20E.03 2 to 8 hours 7.83E-04 8 to 24 hours 3.40E-04 I to 4 days 2.55E-04 4 to 30 days 2.13E-04 HOURLY VALUE RANGE MAX X1Q MIN X/Q CENTERLINE 1.60E-03 1.54E-04 SECTOR-AVERAGE 9.35E-04 8.97E-05 NORMAL PROGRAM COMPLETION
CA06012 Rev.0 Page 279 of 283 CTMTIWRTS.OUT Program
Title:
ARCON96. Developed For: U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Reactor Program Management Date: June25,1997 11:00a.m. NRC Contacts: J.Y. Lee Phone: (301) 415 1080 e-mail:jyllInrc.gov J. J. Hayes Phone: (301) 415 3167 e-mail: jjh3nrc.gov L A Brown Phone: (301) 415 1232 e-mail: lab2@nrc.gov Code Developer J.V. Ramsdell Phone: (509) 372 6316 e-mail: jramsdellpnl.gov Code Documentation: NUREG/CR-6331 Rev. I The program was prepared for an agency of the United States Govemment. Neither the United States Govemment nor any agency thereof, nor any of their employees, makes any warranty, expressed or implied, or assumes any legal liability or responsibilities for any third party's use, or the results of such use, of any portion of this program or represents that its use by such third party would not infringe privately owned rights. Program Run 8/29/2003 at 10:46:38
**~*** ARCON INPUT ********.*
Number of Meteorological Data Files = 8 Meteorological Data File Names CC1991.MET CC1992.MET CC1993.MET CC1994.MET CC1995.MET CC1996.MET CC1997.MET CC1998.MET Height of lower wind instrument (m) 10.0 Height of upper wind instrument (m) 60.0 Wind speeds entered as meters/second Ground-level release Release height (m) = 29.7 Building Area (mA2) 2000.0 Effluent vertical velocity (mis) = .00 Vent or stack flow (mA3/s) - .00 Vent or stack rad ius (m) .00 Direction .. intake to source (deg) 358 Wind direction sector width (deg) 90 Wind direction window (deg) 313 - 043 Distance to intake (m) - 36.6 Intake height (m) 9.1 Terrain elevation difference (m) - .0 Output file names CTMTI WRTS.out CTMTIWRTS.jfd Minimum Wind Speed (m/s) = .5 Surface roughness length (m) = .20
CA 06012 Rev.0 Page 280 of 283 Sector averaging constant - 4.3 Initial value of sigma y = 6.99 Initial value of sigma z 5.18 Expanded output for code testing not selected Total number of hours of data processed = 70131 Hours of missing data 1084 Hours direction in window - 19377 Hours elevated plume w/ dir. in window = 0. Hours of calm winds = 863 Hours direction not in window or calm - 48807 DISTRIBUTION
SUMMARY
DATA BY AVERAGING INTERVAL AVER. PER. 1 2 4 8 12 24 .96 168 360 720 UPPER LIM. l.00E-02 1.OOE-02 1.OOE-02 1.00E-02 1.00E-02 1.OOE-02 1.OOE-02 l.OOE-02 I.OOE-02 l.OOE-02 LOW LIM. l.00E-6 I.OOE-06 l.00E006 1.OOE-06 l.OOEE06 1.00E-06 l.O0066 l.OOE-06 1.00E-06 1.00E-06 ABOVE RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. IN RANGE 20240. 24125. 29070. 35744. 41353. 51447. 66031. 66557. 67247. 67747. BELOW RANGE 0. 0. 0. 0. 0. 0. 0. 0. 0. 0. ZERO 48807. 44747. 39482. 32213. 27057. 16566. 974. 56. 0. 0. TOTAL X/Qs 69047. 68872. 68552. 67957. 68410. 68013. 67005. 66613. 67247. 67747.
% NON ZERO 29.31 35.03 42.41 52.60 60.45 75.64 98.55 99.92 100.00 100.00 95th PERCENTILE X/Q VALUES I.IIE-03 1.03E-03 9.18E-04 8.25E-04 6.74E-04 4.88E-04 2.99E-04 2.68E-04 2.32E-04 2.IIE-04 95% XIQ for standard averaging intervals 0 to 2 hours 1.1I E-03 2 to 8 hours 7.29E-04 8 to 24 hours 3.19E-04 I to 4 days 2.36E-04 4 to 30 days 1.98E.04 HOURLY VALUE RANGE MAX X/Q MIN X/Q CENTERLINE 1.48E-03 1.39E-04 SECTOR-AVERAGE 8.65E-04 8.1 IE-05 NORMAL PROGRAM COMPLETION
CA 06012 Rev.0 Page 281 of 283 ATTACHMENT F ANALYSIS OF JOINT FREQUENCY DATA BY YEAR AND VELOCITY Joint Frequency Data vs Year and Peak Velocity (mis) at 60m 0.2 0.5 0.7 1.0 1.5 2.0 3.0 5.0 7.0 10.0 13.0 18.0 1991 31 46 34 104 236 348 994 2762 2655 1120 143 8 8481 1992 14 25 33 78 220 361 1120 3132 2498 1023 195 23 8722 1993 6 22 40 91 212 373 1134 3018 2414 1120 219 22 8671 1994 8 26 24 69 214 327 1018 2728 2699 1310 161 17 8601 1995 7 28 28 80 228 354 1099 3028 2573 1128 127 3 8683 1996 8 35 32 91 246 393 1019 3005 2380 1118 205 36 8568 1997 2 26 31 80 220 353 1046 2921 2605 1208 191 .6 8689 1998 1 14 27 74 226 384 1162 3108 2366 938 176 37 8513 Average 9.6 27.8 31.1 83.4 225.3 361.6 1074.0 2962.8 2523.8 1120.6 177.1 19.0 StdDev 9.5 9.4 4.9 11.3 11.4 21.2 62.6 149.3 128.3 111.1 31.6 13.0 Joint Frequency Data vs Year and Peak Velocity (mis) at 1Om 0.2 0.5 0.7 1.0 1.5 2.0 3.0 5.0 7.0 10.0 13.0 18.0 1991 41 150 173 318 821 1043 2345 2887 855 75 0 0 8708 1992 61 124 143 315 856 1137 2456 2740 738 150 10 0 8730 1993 58 140 166 336 858 1178 2329 2553 872 178 5 *0 8673 1994 39 111 132 346 775 977 2323 2826 900 113 6 2 8550 1995 22 96 135 323 779 1108 2454 2860 791 94 1 0 8663 1996 34 118 151 293 868 1134 2311 -.2387 807 213. 4 0 8320 1997 41 97 126 302 830 1228 2481 2662 818 124 4 0 8713 1998 31 114 128 321 983 .* 1320 2553 2477 589 124 12 0 8652 Average 40.9 118.8 144.3 319.3 846.3 1140.6 2406.5 2674.0 796.3 133.9 5.3 0.3 StdDev 13.1 19.0 17.6 17.0 65.4 106.0 90.7 186.5 97.8 45.0 4.1 0.7
CA 06012 Rev.0 Page 282 of 283 Joint Frequency Data (%) vs Year and Peak Velocity (mis) at 60m 0.2 0.5 0.7 1.0 1.5 2.0 3.0 5.0 7.0 10.0 13.0 18.0 1991 0.37 0.54 0.40 1.23 2.78 4.10 11.72 32.57 31.31 13.21 1.69 0.09 100 1992 0.16 0.29 0.38 0.89 2.52 4.14 12.84 35.91 28.64 11.73 2.24 0.26 100 1993 0.07 0.25 0.46 1.05 2.44 4.30 13.08 34.81 27.84 12.92 2.53 0.25 100 1994 0.09 0.30 0.28 0.80 2.49 3.80 11.84 31.72 31.38 15.23 1.87 0.20 100 1995 0.08 0.32 0.32 0.92 2.63 4.08 12.66 34.87 29.63 12.99 1.46 0.03 100 1996 0.09 0.41 0.37 1.06 2.87 4.59 11.89 35.07 27.78 13.05 2.39 0.42 100 1997 0.02 0.30 0.36 0.92 2.53 4.06 12.04 33.62 29.98 13.90 2.20 0.07 100 1998 0.01 0.16 0.32 0.87 2.65 4.51 13.65 36.51 27.79 11.02 2.07 0.43 100 Average 0.11 0.32 0.36 0.97 2.62 4.20 12.46 34.38 29.29 13.01 2.06 0.22 StdDev 0.11 0.11 0.06 0.14 0.15 0.26 0.70 1.64 1.52 1.28 0.36 0.15 Joint Frequency Data (%) vs Year and Peak Velocity (m/s) at 1Om 0.2 0.5 0.7 1.0 1.5 2.0 3.0 5.0 7.0 10.0 13.0 18.0 1991 0.47 1.72 1.99 3.65 9.43 11.98 26.93 33.15 9.82 0.86 0.00 0.00 100 1992 0.70 1.42 1.64 3.61 9.81 13.02 28.13 31.39 8.45 1.72 0.11 0.00 100 1993 0.67 1.61 1.91 3.87 9.89 13.58 26.85 29.44 10.05 2.05 0.06 0.00 100 1994 0.46 1.30 1.54 4.05 9.06 11.43 27.17 33.05 10.53 1.32 0.07 0.02 100 1995 0.25 1.11 1.56 3.73 8.99 .12.79 28.33 33.01 9.13 1.09 0.01 0.00 100 1996 0.41 1.42 1.81 3.52 10.43 13.63 27.78 28.69 9.70 2.56 0.05 0.00 100 1997 0.47 1.11 1.45 3.47 9.53 14.09 28.47 30.55 9.39 1.42 0.05 0.00 100 1998 0.36 1.32 1.48 3.71 11.36 15.26 29.51 28.63 6.81 1.43 0.14 0.00 100 Average 0.47 1.38 1.67 3.70 9.81 13.22 27.90 30.99 9.23 1.56 0.06 0.00 StdDev 0.15 0.22 0.21 0.19 0.78 1.21 0.91 1.95 1.16 0.54 0.05 0.01
CA06012 Rev.0 Page 283 of 283 ATTACHMENT G ANALYSIS OF JOINT FREQUENCY DATA BY YEAR AND STABILITY CLASS Joint Frequency Data vs Year and Stability Class at 1Om and 60m A B *C D E F G 1991 1029 528 568 2705 2166 984 545 8525 1992 442 302 383 3364 2903 814 540 8748 1993 577 332 369 3096 2761 877 652 8664 1994 689 449 459 3083 2547 859 649 8735 1995 625 432 471 3376 2377 875 552 8708 1996 541 371 469 3285 2564 848 547 8625 1997 1329 409 . 435 2780 2202 857 681 8693 1998 886 335 385 2663 2634 1156 621 8680 Average 764.75 394.75 442.38 3044.00 2519.25 908.75 598.38 StdDev 297.05 74.61 65.29 293.92 258.38 111.33 58.34 Joint Frequency Data (%) vs Year and Stability Class at 1Om and 60m A B C D E F G 1991 .12.07 6.19 6.66 31.73 25.41 11.54 *6.39 100 1992 5.05 3.45 4.38 38.45 33.18 9.30 6.17 100 1993 6.66 3.83 4.26 35.73 31.87 10.12 7.53 100 1994 7.89 5.14 5.25 35.29 29.16 9.83 7.43 100 1995 7.18 4.96 5.41 38.77 27.30 10.05 6.34 100 1996 6.27 4.30 5.44 38.09 29.73 9.83 6.34
- 100 1997 15.29 4.70 5.00 31.98 25.33 9.86 7.83 100 1998 10.21 3.86 4.44- 30.68 30.35 13.32 7.15 100 Average 8.83 4.56 5.11 35.09 29.04 10.48 6.90 StdDev 3.45 0.89 0.79 3.27 2.86 1.31 0.66}}