ExekeinSM Exelon Generation Company, LLC LaSalle County Station 2601 North 21"Road Marseilles, IL 61341-9757 www.exelonCorp.Com1 Nuclear RA05-48 June 10, 2005 10 CFR 50.55a(g)
United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555 LaSalle County Station, Unit 2 Facility Operating License No. NPF-18 NRC Docket No. 50-374
Subject:
Reference:
Post-Outage 90-Day Inservice Inspection (ISI) Summary Report Milton H. Richter (ComEd) letter to Dr. Thomas E. Murley (NRC), "Structural Margin Evaluation for Reactor Pressure Vessel Head Studs," dated October 3, 1991 Enclosed is the Exelon Generation Company, LLC (EGC) LaSalle County Station Unit 2 Post-Outage 90-Day (ISI) Summary Report, submitted in accordance with 10 CFR 50.55a, "Codes and Standards," and the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code Section Xl, Article IWA-6200, Paragraph IWA-6230.
The enclosed Post-Outage 90-Day ISI Summary Report is for examinations, repair/replacement activities, and Containment Inservice Inspection (CISI) performed between the end of LaSalle County Station Unit 2 ninth refueling outage on February 21, 2003, through the end of the current, tenth refueling outage. This refueling outage started February 7, 2005, and ended March 16, 2005. This refueling outage was the first scheduled for the Third Inspection Period of the Second Inspection Interval, effective from July 5, 2004, through July 4, 2007, for LaSalle County Station Unit 2.
Pressure boundary leakage was detected during examination of the reactor coolant pressure boundary. The leakage was reactor coolant from the weld joint between the body of valve 2B21-F028D and drain line 2MS20AD-2". Issue Report # 311917 was generated to document the leak. Work Order # 789955 was generated and a ASME Section Xl Repair Plan was used to remove the entire defective weld and re-weld the connection. The repaired connection was subjected to System Leakage Test pressure and no leakage was detected. The components' materials of.
construction being joined by the repair weld necessitated Post Weld Heat Treatment (PWHT) of the completed weld. To monitor PWHT, five temporary thermocouples were tack welded to the valve body and one thermocouple was tack welded to the drain line pipe. The PWHT of the completed repair weld was successful and the temporary attachments and their tack welds were removed from the components.
D447
June 10, 2005 U.S. Nuclear Regulatory Commission Page 2 The weld removal areas on the valve body and the drain pipe were not examined by the Magnetic Particle (MT) or Liquid Penetrant (PT) methods as required by Sub Subparagraph NB-4231.2 (g) of the ASME Boiler and Pressure Vessel Code Section III, 1974 Edition. This ASME Code non-compliance was discovered following start-up from the refueling outage. Issue Report # 314183 was generated to document the ASME Code non-compliance. Operability Evaluation # 05-002 was completed and determined that the valve and drain line would remain operable until the weld removal areas could be examined using MT or PT methods. Action Tracking Item # 314183-03 was created to track the completion of the required examinations.
LaSalle County Station Unit 2 is owned and operated by EGC, whose address is:
200 Exelon Way Kennett Square, PA 19348 LaSalle County Station Unit 2 has an authorized power level of 3489 MWt and began Commercial Operation on October 17, 1984.
We certify that, to the best of our knowledge and belief, the statements made in this report are correct, and the examinations and corrective measures, as applicable, conform to the rules of the ASME Boiler and Pressure Vessel Code, Section Xl.
Should you have any questions concerning this letter, please contact Mr. Terrence Simpkin, Regulatory Assurance Manager, at (815) 415-2800.
Respectfully, Susan R. Landhal Site Vice President LaSalle County Station Attachment cc:
NRC Senior Resident Inspector - LaSalle County Station
Attachment Post-Outage 90-Day ISI Summary Report INTRODUCTION The Inservice Inspection (ISI) Summary Report addresses examinations, repair/replacement activities, and Containment Inservice Inspections (CISI) performed between the end of the previous refuel outage, (L2R09) February 21, 2003, through the end of the current refuel outage (L2R1 0). This refuel outage was the tenth for LaSalle County Station Unit 2. It started February 7, 2005 and ended March 16, 2005. This refuel outage was the first scheduled for the Third Inspection Period of the Second Inspection Interval, effective from October 17,1994, through July 4, 2007, for LaSalle County Station Unit 2. Paragraph IWA-2430 (e) of the American Society of Mechanical Engineers (ASME) Code Section Xi allows an Inspection Interval to be extended for a period of time equivalent to the duration of a continuous outage that exceeds six months.
The Second Inservice Inspection Interval is divided into three successive inspection periods as determined by calendar years of plant service within the inspection interval.
Identified below are the period dates for the Second Inservice Inspection Interval as defined by Inspection Program B. In accordance with IWB-2412 (b), the Inspection Periods specified below may be decreased or extended by as much as one year to enable inspections to coincide with.LaSalle County Station's refuel outages.
Unit 2, Period 1 (October 17, 1994 through July 4, 2000**)
Unit 2, Period 2 (July 5, 2000 through July 4, 2004)
Unit 2, Period 3 (July 5, 2004 through July 4, 2007)
- This date reflects a 932-day extension allowed by IWA-2430 (e) for L2R07.
Augmented Inservice Inspection (AISI) examinations, ISI and CISI, and Preservice Inspections (PSI) were completed prior to and during the refuel outage as required by the Code of Federal Regulations, Technical Requirements Manual, ASME Boiler and Pressure Vessel Code, Section Xi, 1989/1998 Edition, and the applicable requirements of the Performance Demonstration Initiative (PDI).
Personnel from General Electric Nuclear Energy (GENE) Inspection Services and Exelon Nondestructive Examination Services group (NDES) performed the Non-Destructive Examinations (NDE), Magnetic Particle (MT), Liquid Dye Penetrant (PT),
and manual and/or automated Ultrasonic (UT) techniques that were used during these inspections. All Intergranular Stress Corrosion Cracking (IGSCC) examinations were completed by personnel qualified for the detection and discrimination of IGSCC Cracking in accordance with the PDI. NDES provided necessary resolution of technical problems, reviewed all ISI personnel qualifications, and all visual, surface, and volumetric examination results.
1
Visual examinations of reactor vessel internals, component supports, and piping pressure tests were performed by GENE personnel, Exelon Generation Company, LLC (EGC) employees of the LaSalle County Station Programs Engineering Group and NDES personnel. These individuals were appropriately certified as ASME Code Section Xl Visual Examiners to EGC's written practice. An underwater camera was used for the visual inspection of the reactor vessel internals. The camera was proven capable of resolving 0.001" and 0.0005" stainless steel wires while underwater and, in the same lighting conditions found during the actual inspection.
The services of an Authorized Nuclear Inservice Concrete Inspector (ANIC) were provided by Hartford Steam Boiler Inspection & Insurance Co. of Connecticut, 2443 Warrenville Road, Suite 500, Lisle, IL 60532.
Mr. Rocky W. White, ANIC, State of Illinois #1927, reviewed written Nondestructive Examination procedures, personnel qualifications, instrument and material certifications, ASME Code Section Xl examination results, Owner's Reports of Repair or Replacement (Form NIS-2), and the Owner's Data Report for Inservice Inspection (Form NIS-1).
II.
SCOPE OF INSPECTIONS The ISI Summary Report is provided with tables that consolidate the extent and results of inspections performed between the end of the previous refuel outage (L2R09),
February 21, 2003, through the end of the current refuel outage (L2R1 0). An explanation of all abbreviations used is in Attachment 3 of the Summary Report.
Table A provides a listing of all completed ASME Code Section XI examinations for this refuel outage with the exception of component support examinations and pressure testing which are addressed separately. Table A is divided by ASME Code Category with a description of the items examined, including the examination types, and the examination results.
Table B provides a listing of all AISI. These are not ASME Code Section Xl requirements, but are additional examination area requirements, increased frequency requirements, or combinations of these, which are requested by the Nuclear Regulatory Commission (NRC). Others have been deemed prudent in view of EGC and industry experience. Table B also gives a description of the items examined as well as the examination types, and examination results. Table B includes the following categories:
BWRVIP These examinations are of austenitic stainless steel piping for the detection of IGSCC.
REACTOR VESSEL INTERNALS AISI - These examinations include inspection of reactor internal components required by the NRC such as core spray spargers and piping. These have been adopted by EGC through its commitment to the Boiling Water Reactor Vessel and Intemals Project (BWRVIP). Other examinations, such as the steam dryer and steam separator, were deemed prudent from industry experience.
MISCELLANEOUS AISI -
Pursuant to LaSalle County Station's commitment to the NRC (reference letter), the AISI examinations included an augmented "End-Shot" UT examination of 100% (76 total) of the reactor pressure vessel closure studs. The "End Shot" UT examination was completed using procedures, calibration standards, and personnel which met all applicable requirements of the 1989 Edition of ASME Code Section Xl, and the PDI.
2
Table C provides a listing of all completed ASME Code Section Xl Class I and 2 component support examinations for this outage. Table C gives the support #(s),
examination type, and examination results. Table C is divided by ASME Code Class.
Table D provides a listing of pressure testing of ASME Code Section Xl Class I & 2 piping and components completed during the period between the L2R09 and L2R10 refuel outages. As applicable, Code Case N-498-4, "Alternative Rules for 10-Year Hydrostatic Testing for Class 1, 2, and 3 Systems Section Xl, Division 1," is utilized during the Third Inspection Period. ASME Code Class 1 components and piping were examined using the VT-2 method during the system leakage test conducted at 1035 psig prior to reactor start-up, within the nominal operating pressure range of the reactor pressure vessel associated with 100% rated reactor power. Pressure testing will be ongoing throughout the remainder of the Third Inspection Period.
Table E is a listing of ASME Code Section Xl Class 1 and 2 repair/replacements completed since the previous refuel outage and those completed during the tenth refuel outage of Unit 2, in accordance with ASME Code Section Xl, Articles IWA-4000 and IWA-7000. This includes the Work Order # which served to implement the applicable activity and a short description. The documentation packages are on file at LaSalle County Station. Each activity has been certified on the Owner's Report of Repair or Replacement, which will serve as documentation of these repair/replacements.
The name of each major component or appurtenance inspected during the tenth refuel outage is listed on Form NIS-1 (Attachment 1) in column #1. This includes the reactor pressure vessel and the Class 1 piping system. A detailed list of components or appurtenances inspected appears in the abstracts listed as items 13, 14, and 15 on Form NIS-1. The descriptions including size, capacity, material, location, and drawings to aid in identification of the components or appurtenances have been previously submitted, including the N-5 ASME Code Data Reports and the Second 10-Year ISI Plan. This information was not included in the ISI Summary Report. These documents are on file at LaSalle County Station. This also applies to the PSI and ISI Summary Reports.
Ill.
SUMMARY
OF RESULTS AND CORRECTIVE ACTIONS The ASME Code Section Xl ISI results obtained during this refuel outage were compared with the Preservice and Inservice results. The following is a summary of the results and corrective actions taken.'
- 1.
ASME Code Section Xl Components Recordable indications were detected in ASME Code Section Xl components and other non-code components, during augmented examinations as discussed below or in the applicable Tables. All indications detected in ASME Code Section Xl components were evaluated against the applicable acceptance standards.
Examinations and tests of the Unit 2 ASME Code Section Xl Class CC post tensioning system were performed. The following conditions have been identified and are being reported as required by 10 CFR 50.55(a):
3
During the examination of tendons, free water was identified in either the grease can or anchorage of the following tendons:
Shop End H39GF 1.5 Ounce Field End H72F 1 Ounce The difference between the amount of sheeting filler grease removed and the amount replaced exceeded 10% of the tendon net duct volume in the following tendons:
V201A 20.29%
V201A 14.88%
V204A 10.82%
V205A 15.45%
V214A 10.77%
V216A 14.04%
V218A 21.06%
V221A 13.09%
V225A 11.50%
V228A 12.20%
V229A 13.93%
V247C 38.67%
Examination of tendons identified degradation in the form of broken wires found on the following:
V219A 1 of 90 wires broken V228A 3 of 90 wires broken. This tendon was replaced.
V229A 9 of 90 wires broken. This tendon was replaced.
V247C 2 of 90 wires broken Five "A" tendons and all thirty "B" tendons are inaccessible for examination during power operations. Degradation of the tendons is due to water-induced corrosion by failure of the water intrusion barriers and, aided by a loss of the corrosion protection medium (grease) in the top region of the accessible "A" tendons. The design of the inaccessible tendons incorporates a welded cover that prevents this type of degradation. To confirm this conclusion, a corrective action has been generated to inspect one inaccessible "A" and "B" tendon at the next scheduled refueling outage. Action Tracking Item #157920, Assignment 33, tracks this inspection.
- 2.
RH40-2877X Welded Attachments During Magnetic Particle testing of the welded attachment lugs associated with component support RH40-2877X, two linear indications were detected. The linear indications were located in the pipe base metal near the lug weldment. The indications were compared to the acceptance standards of ASME Section Xl, WB-3514-4 and did not meet the acceptance standards. Issue Report #300094 was generated to disposition the indications. ASME Section Xl, IWC-3512.1(c), allows flaws exceeding the standards of IWB-3514-4 to be examined by the volumetric method and compared to applicable standards for the volumetric method (i.e., Table IWB-3514-1). Alternatively, controlled mechanical removal may be used to establish each indication's depth. This is supported by ASME Code Interpretation XI-1-95-42, which allows a controlled mechanical removal technique (e.g., grinding) to be used to establish if the surface indication would have been acceptable to the volumetric acceptance standards of IWB-3500 or IWC-3500.
Work Order #781039 was generated and a Section Xl Repair Plan was used to implement controlled mechanical flaw removal using localized grinding. Ultrasonic thickness measurements were performed prior to grinding and after the indications were completely removed. The deepest measurement along each indication was recorded after each of the indications was completely removed. The amount of metal removed representing the initial depth of each indication was used to compare to the acceptance 4
standards of IWB-3514-1. Both indications were acceptable to the volumetric standards and no sample expansion was performed.
- 3.
Pressure Boundary Leakage of Pipe Line 2MS20AD Pressure boundary leakage was detected during examination of the Reactor Coolant Pressure Boundary completed with the System Leakage Test. The leakage was reactor coolant from the weld joint between the body of valve 2B21 -F028D and drain line 2MS20AD-2". Issue Report # 311917 was generated to document the leak. Work Order
- 789955 was generated and a ASME Section Xl Repair Plan was used to remove the entire defective weld and re-weld the connection. The repaired connection was subjected to System Leakage Test pressure and no leakage was detected. The materials of construction of the components being joined by the repair weld necessitated PWHT of the completed weld. To monitor PWHT, five temporary thermocouples were tack welded to the valve body and one thermocouple was tack welded to the drain line pipe. The PWHT of the completed repair weld was successful and the temporary attachments and their tack welds were removed from the components. The weld removal areas on the valve body and the drain pipe were not examined by the MT or PT methods as required by Sub Subparagraph NB-4231.2 (g) of the ASME Boiler and Pressure Vessel Code Section 111, 1974 Edition. This ASME Code non-compliance was discovered after start-up from the refueling outage. Issue Report # 314183 was generated to document the ASME Code non-compliance. Operability Evaluation # 05-002 was completed and determined that the valve and drain line remain operable until the weld removal areas can be examined using MT or PT methods. Action Tracking Item # 314183-03 was created to track the completion of the required examinations.
- 4.
Steam Dryer An augmented visual examination of the steam dryer is completed during each refuel outage. The steam dryer contains numerous indications that were recorded during previous examinations. Areas where historically indications were identified include the lifting eye bracket welds, upper dryer bank vertical welds, uppers support ring, drain channel welds, and dryer bank panels. Specific inspections as recommended by SIL 644 Revision 1 were performed and new indications were identified on tie bars 5 and 28, and on the upper strap associated with the lifting lug at 2150. The indications on the tie bars were evaluated as acceptable as-is with no repair required in accordance with EC
- 353949. Issue Reports #308912 and #309163 (tie bar indications) and #301422 (broken upper strap) were generated to document these conditions. These examination results have been documented on the GENE examination data sheets.
- 5.
Steam Separator An augmented visual examination of the steam separator is completed during each refuel outage. No new indications were observed. The welds and separators around a steam separator tie bar removed in L2R09 were examined as recommended in the removal design change, and no indications were observed. These examination results have been documented on the GENE examination data sheets.
- 6.
Shroud Head Bolts All shroud head bolts were examined, and pin wear was identified on three bolts and window wear was observed on one of these same bolts. Issue Report #309413 was generated to document these indications. The indications were accepted as-is under design analysis EC 354310.
5
- 7.
Jet Pumps One hundred percent (20 total) of the jet pump inlet mixers were replaced with new inlet mixers that had labyrinth seals machined in the slip joint area, with oversized non-stellite main wedges. The changes in the inlet mixer were performed in accordance with EC 348413. The existing 10 Auxiliary Wedges previously installed to eliminate gaps between the jet pumps and the inlet mixers were removed. Visual examinations performed after inlet mixer replacement revealed that no Auxiliary Wedges were required. During the inlet mixer replacements, 17 of the 20 hold down beams were proactively replaced.
Examinations of areas made accessible below the core plate were performed when the inlet mixers were removed. Examinations included accessible portions of bottom head cladding in the vicinity of the jet pumps, surfaces/welds on Control Rod Drive (CRD) stub tubes and guide tubes, shroud to Reactor Pressure Vessel (RPV) weld H9 located below the shroud support plate, and a general overview of the bottom head. No recordable indications were noted. These examination results have been documented on the GENE examination data sheets.
- 8.
Core Spray Piping An augmented ultrasonic examination was completed on accessible core spray piping welds internal to the reactor vessel. An existing relevant indication on weld BP5 was re-sized with no noted growth after two cycles of operation. Issue Report #300599 was generated to document this indication. The indication was accepted as-is for two additional cycles under design analysis L-002704.
- 9.
Core Shroud Four of the core shroud horizontal welds were ultrasonically examined in accordance with BWRVIP-76, UBWR Vessel and Internals Project, BWR Core Shroud Inspection and Flaw Evaluation Guidelines". - No relevant indications were identified. Figure 2-2 of BWRVIP-76 requires that the inspected length for each weld be greater than 50% of the length of the weld or a plant specific evaluation is performed in accordance with Appendix D of BWRVIP-76. The length of weld examined was as follows:
H3: Looking-up:
73.1%
H3: Looking-down:
0%
H5: Looking-up:
40.5%
H5: Looking-down:
71.0%
H6: Looking-up:
0%
H6: Looking-down:
74.5%
H8: Looking-up:
73.7%
H8: Looking-down:
0%
Greater than 50% coverage was not achieved on both sides of any of these welds, and a plant specific evaluation was required per Section 2.2 of BWRVIP-76 and is documented in calculation L-003119. The calculation concluded that the Unit 2 core shroud has been very conservatively evaluated in accordance with BWRVIP-76 to maintain structural integrity for a minimum of 2 years, until the eleventh fuel cycle.
Note: LaSalle County Station weld nomenclature differs from the BWRVIP. The shroud contains two beltline welds (H4 and H5), H6 is BWRVIP weld H5, and H8 is BWRVIP weld H7.
.6
- 10.
ASME Code Section Xl Piping & Component Support Examinations Piping and component supports were inspected (42 total) during this refuel outage. These were distributed between ASME Code Section XI Class 1 and 2/D+ supports as follows:
ASME Code Class 1 - 22 supports.
- ASME Code Class 2/D+ - 20 supports.
One rejectable indication was detected during these examinations.
MS01-2005V had spring can settings outside of design tolerances. Issue Report #
305584 was initiated to disposition the indication. The condition was evaluated under Engineering Change # 354132 and found to be acceptable.
As required by ASME Section XI Code Case N-491-1, "Alternative Rules for Examination of Class 1, 2, 3, and MC Components Supports of Light-Water Cooled Power Plants Section Xl, Division 1," sample expansion examinations were completed for the rejectable indication. No further detrimental indications were detected.
7
LASALLE COUNTY STATION UNIT 2 TENTH REFUEL OUTAGE ASME CODE SECTION XI
SUMMARY
REPORT
TABLE OF CONTENTS
- 1.
INTRODUCTION
- 11.
SCOPE OF INSPECTIONS Table A - ASME Code Section XI Examinations Table B - Augmented Inservice Inspections AISI Table C - ASME Code Section XI Component Support Examinations Table D - ASME Code Section XI Pressure Testing Table E - Class 1 & 2 Repair/Replacements III.
SUMMARY
OF RESULTS, EVALUATIONS, AND CORRECTIVE ACTIONS IV.
ATTACHMENTS
- 1. NIS-1 Form
- 2. NIS-2 Forms
- 3. Abbreviations
TABLE A ASMIE CODE SECTION XI ISI INSPECTIONS ASME CATEGORY B-A ITEM #
1.
2.
3.
4.
5.
6.
7.
ITEM DESCRIPTION LCS-2-AA LCS-2-AD LCS-2-BM GEL-1061-DA GEL-1061 -DE GEL-1061-DF LCS-2-AE EXAM TYPE RESULT UT UT UT UT UT UT UT NRI NRI NRI NRI, 60% COVERAGE, REFERENCE CR-26 NRI, 60% COVERAGE, REFERENCE CR-26 NRI, 60% COVERAGE, REFERENCE CR-26 NRI, 58.1%COVERAGE, REFERENCE CR-26 ASME CATEGORY B-D 1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
I1.
12.
13.
14.
15.
16.
17.
18.
LCS-2-N2B LCS-2-N2C LCS-2-N2F LCS-2-N2G LCS-2-N2H LCS-2-N2J LCS-2-N2K LCS-2-N3A LCS-2-N3B 2-NIR-2B 2-NIR-2C 2-NIR-2F 2-NIR-2G 2-NIR-2H 2-NIR-2J 2-NIR-2K 2-NIR-3A 2-NIR-3B UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT NRI, 70%COVERAGE, REFERENCE CR-26 NRI, 70% COVERAGE, REFERENCE CR-26 NRI, 70% COVERAGE, REFERENCE CR-26 NRI, 70% COVERAGE, REFERENCE CR-26 NRI, 70% COVERAGE, REFERENCE CR-26 NRI, 70% COVERAGE, REFERENCE CR-26 NRI, 70% COVERAGE, REFERENCE CR-26 NRI, 68% COVERAGE, REFERENCE CR-26 NRI, 68% COVERAGE, REFERENCE CR-26 NRI NRI NRI NRI NRI NRI NRI NRI NRI ASME CATEGORY B-G-2 1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
MS-2001B-I I MS-2002B-22 MS-2002B-26 MS-2002B-30 MS-2003B-12 MS-2003B-16 MS-2003B-20 RI-2002B-22 RT-2001B-18A RT-2001B-18B 2B21-F013M 2B21-F028B 2B21-F028D 2B21-F032A 2B33-F067B 2E12-FO50A VT-I VT-I VT-1 VT-I VT-I VT-I VT-l VT-i VT-I VT-I VT-1 VT-I VT-i VT-I VT-I VT-I NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI ASME CATEGORY B-K 1.
2.
3.
4.
5.
RPV-SS-2 VS-I HP02-2812C RH40-2817C RH40-2818C PT/VT MT/UT.
MT MT MT NRI, 52% COVERAGE, REFERENCE CR-25 NRI NRI NRI NRI
TABLE A (CONT'D.)
ASME CODE SECTION XI ISI INSPECTIONS ITEM #
ITEM DESCRIPTION EXAM TYPE RESULT
- 6.
RH53-2840C MT NRI
- 7.
R124-2853X MT NRI
- 8.
R124-2854X MT TWO INDICATIONS, ACCEPTABLE ASME CATEGORY B-M-2
- 1.
2B21-F028B VT-3 NRI
- 2.
2B21-F028D VT-3 NRI
- 3.
2B21-F032A VT-3 NRI
- 4.
2B33-F067B VT-3 NRI
- 5.
2E12-F050A VT-3 NRI ASME CATEGORY B-N-I
- 1.
SURFACES ABOVE THE CORE VT-3 NRI
- 2.
SURFACES BELOW THE CORE VT-3 NRI
- 3.
GENERAL EXAM OF RPV BOTTOM HEAD VT-3 NRI
- 4.
BOTTOM HEAD SURFACES ATJETPUMPS#1-20 VT-3 NRI ASME CATEGORY B-N-2
- 1.
(3) CORE SPRAY PIPING ATT. EVT-I NRI
- 2.
(2) FEEDWATER SPAGER ATT. EVT-I NRI
- 3.
DRYER SUPPORT LUGS EVT-I NRI
- 4.
LOWER SURVEILLANCE LUGS VT-I NRI
- 5.
UPPER SURVEILLANCE LUGS VT-3 NRI
- 6.
ACCESSIBLE CRD STUB
.TUBE WELDS VT-3 NRI
- 7.
ACCESSIBLE CRD STUB TUBE SURFACES VT-3 NRI
- 8.
ACCESSIBLE SHROUD SUPPORT TO RPV WELD BOTTOM SIDE VT-3 NRI
- 9.
SUPPORT PLATE GUSSET TO RPV WELDS EVT-1 NRI
- 10.
SUPPORT PLATE SURFACES VT-3 NRI
- 11.
SUPPORT PLATE TO SHROUD CYLINDER WELD EVT-I NRI
- 12.
ACCESSIBLE SHROUD SUPPORT LEGS TO RPV WELDS VT-3 NRI
- 13.
DRYER HOLD DOWN LUGS VT-3 NRI ASME CATEGORY C-A
- 1.
IRH-HX2B-05 UT NRI
- 2.
IRH-HX2B-06 UT NRI ASME CATEGORY C-B
- 1.
IRH-HX2B-07 NOZ TO SHELL UT NRI
- 2.
IRH-HX2B-07 INNER RADIUS UT NRI ASME CATEGORY C-C
- 1.
RH03-2853V MT NRI
- 2.
RH03-2884S MT NRI
TABLE A (CONT'D.)
ASME CODE SECTION XI ISI INSPECTIONS ITEM #
ITEM DESCRIPTION EXAM TYPE RESULT 3.
4.
5.
6.
RH03-2009V RH14-2807X RH40-2877X RH53-2826X MT MT MT/UT MT NRI NRI TWO INDICATIONS, SEE REPORT PG. 4 NRI ASME CATEGORY C-G 1.
2.
3.
IRH-PU2B-01 IRH-PU2B-02 IRH-PU2B-03 MT MT MT NRI NRI NRI ASME CATEGORY R-A ITEM #
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
ITEM DESCRIPTION FW-2002-18 FW-2002-27 HP-2001-02 LP-2001 -01 LP-2001-23 LP-2001-24 MS-2003-02 MS-2003-03 MS-2004-02 MS-2004-03 MS-2051-17 MS-2051-20 MS-2052-15 RH-2001-01 RH-2077-26 RH-2003-21 RH-2004-02 RH-2004-26 RI-2002-18 RR-2005-20 RR-2005-21 RR-2008-52 RT-2001-03 MS-2046-12 MS-2046-13 MS-2046-13B MS-2046-15 EXAM TYPE RESULT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT UT NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI ROOT GEOMETRY NRI NRI NRI NRI NRIIPSI NRI/PSI ROOT GEOMETRY/PSI NRI/PSI
TABLE B AUGMENTED ISI INSPECTIONS AISI CATEGORY BWVRVIP-75 IGSCC ITEM #
I.
2.
3.
4.
5.
6.
7.
8.
ITEM DESCRIPTION RH-2001-21A RR-2006-07 RR-2006-08 RR-2006-09 RR-2006-13 RR-2006-14 RR-2007-04 RR-2007-09 EXAM TYPE RESULT UT/PT NRI UT NRI UT NRI UT/PT NRI UT/PT NRI UT/PT NRI UT/PT NRI UT/PT NRI AISI CATEGORY VESSEL INTERNALS 1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
STEAM DRYER VT-I STEAM SEPARATOR VT-3 CORE SPRAY PIPING UT/EVT-I CORE SPRAY SPARGERS VT-I CORE SPRAY PIPING & SPARGER BRACKETS EVT-I JET PUMP ASSY. WELDS EVT-I, VT-I & VT-3 FEEDWATER SPARGER BRACKETS EVT-1 LPCI COUPLINGS EVT-I, VT-I & VT-3 ACCESSIBLE JET PUMP ADAPTER WELDS VT-3 SUPPORT PLATE TO SHROUD CYLINDER WELD EVT-I SHROUD HEAD BOLTS VT-3 ACCESS HOLE COVERS VT-I TOP GUIDE C-CLAMP VT-3 SHROUD UT SEE REPORT PAGE 5 NRI, SEE REPORT PAGE 5 SEE REPORT PAGE 6 BWRVIP-18 NRI, BWRVIP-18 NRI, BWRVIP-18 SEE REPORT PAGE 6 BWRVIP-41 NRI, BWRVIP-48 NRI, BWRVIP-42 NRI NRI SEE REPORT PAGE 5 NRI NRI NRI, SEE REPORT PAGE 6 AISI CATEGORY MISC.
ITEM #
ITEM DESCRIPTION EXAM TYPE RESULT
- 1.
RPV STUDS (1-76)
UT NRI, SEE REPORT PAGE 2
TABLE C ASME CODE SECTION XI COMPONENT & SUPPORT EXAMINATIONS ASME CLASS I ITEM #
ITEM DESCRIPTION EXAM TYPE RESULT 1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
RPV Skirt FW02-2837C FW02-2847X HP02-2801 C
-MSOO-2039X MSOO-2046V MSOO-2056V MSOI-2005V MSOI-2006V MS06-2810C MS 14-2826X RH03-2891V RH03-2895C RH04-2859X RH04-2892C RH40-2817C RH40-2826X R124-2842X RROO-2038V RROO-2063V RR16-2800C RTOI-2885G VTr-3 '
VT-3 VT VT-3 VT-3 VT-3 VT-3 VT-.3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT VT-3 NRI NRI NRI NRI NRI NRI NRI SETTINGS, ACCEPTED NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI 1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
HGO5-2013X HGO5-2015X HP14-2803V HP14-2806X LP02-2826G LP02-2868X MS38-2808C RHO1-240IX RH02-2833V RH03-2838X RH03-2853V RH03-2898X RH03-2900V RH33-2401G RH40-2869X RH40-2877X RH53-2826X RH53-2835V RH58-2808X 2C RHR PUMP ASME CLASS 2 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 VT-3 NRI NRI
... NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI
TABLE D ASME CODE SECTION XI PRESSURE TESTING ITEM #
ITEM DESCRIPTION EXAM TYPE RESULT
- 1.
2-CM-03 VT-2 NRI
- 2.
2-CM-04 VT-2 NRI
- 3.
2-CM-05 VT-2 NRI
- 4.
2-CM-14 VT-2 NRI
- 5.
2-ES-01 VT-2 NRI
- 6.
2-FC-09 VT-2 NRI
- 7.
2-FC-10 VT-2 NRI
- 8.
2-FW-01 VT-2 NRI
- 9.
2-HG-03 VT-2 NRI
- 10.
2-HG-08 VT-2 NRI
- 11.
2-HG-09 VT-2 NRI
- 12.
2-IN-09 VT-2 NRI
- 13.
2-IN-10 VT-2 NRI
- 14.
2-IN-1 I VT-2 NRI
- 15.
2-IN-12 VT-2 NRI
- 16.
2-IN-13 VT-2 NRI
- 17.
2-IN-14 VT-2 NRI
- 18.
2-IN-15 VT-2 NRI
- 19.
2-MC-01 VT-2 NRI
- 20.
2-MS-01 VT-2 NRI
- 21.
2-NB-01 VT-2 NRI
- 22.
2-RR-01 VT-2 NRI
- 23.
2-RR-02 VT-2 NRI
- 24.
2-RR-04 VT-2 NRI
- 25.
2-RR-05 VT-2 NRI
- 26.
2-RR-06 VT-2 NRI
- 27.
2-RR-08 VT-2 NRI
- 28.
2-SA-01 VT-2 NRI
- 29.
2-VP-01 VT-2 NRI
- 30.
2-VP-02.
VT-2 NRI
- 31.
2-VQ-02 VT-2 NRI
- 32.
2-VQ-03 VT-2 PACKING
- 33.
2-VQ-05 VT-2 PACKING
- 34.
2-WR-01 VT-2 NRI
- 35.
2-RCPB VT-2 THROUGH WALL LEAK, SEE REPORT PAGE 5
TABLE E REPAIR/REPLACEMENT ACTIVITIES CLASS-I WORK PACKAGE #
DESCRIPTION
- 1.
428318 Replace Main Steam SRV with Rebuilt Spare
- 2.
428319 Replace Main Steam SRV with Rebuilt Spare
- 3.
429584 Replace Main Steam SRV with Rebuilt Spare
- 4.
515539 Replace Main Steam Isolation Valve Disc
- 5.
515542 Replace Main Steam Isolation Valve Disc
- 6.
544418 Replace Control Rod Drive & Cap Screws
- 7.
544419 Replace Control Rod Drive & Cap Screws
- 8.
544420 Replace Control Rod Drive & Cap Screws
- 9.
544421 Replace Control Rod Drive & Cap Screws
- 10.
554320 Repair RR Valve
- 11.
554321 Replace Outboard MS Drain Isolation Valve
- 12.
554322 Replace Inboard MS Drain Isolation Valve
- 13.
585833 Replace Main Steam SRV with Rebuilt Spare
- 14.
585834 Replace Main Steam SRV with Rebuilt Spare
- 15.
585835 Replace Main Steam SRV with Rebuilt Spare
- 16.
593839 Replace Main Steam SRV with Rebuilt Spare
- 17.
605993 Replace Explosive Valve
- 18.
- 19.
625682 Repair RH Check Valve
- 20.
628869 Replace Control Rod Drive & Cap Screws
- 21.
628870 Replace Control Rod Drive & Cap Screws
- 22.
628871 Replace Control Rod Drive & Cap Screws
- 23.
628888 Replace Control Rod Drive & Cap Screws
- 24.
628889 Replace Control Rod Drive & Cap Screws
- 25.
628891 Replace Control Rod Drive & Cap Screws
- 26.
628893 Replace Control Rod Drive & Cap Screws
- 27.
628895 Replace Control Rod Drive & Cap Screws
- 28.
628897 Replace Control Rod Drive & Cap Screws
- 29.
628898 Replace Control Rod Drive & Cap Screws
- 30.
632225 Repair RPV Head Cladding
- 31.
696096 Replace Control Rod Drive & Cap Screws
- 32.
696097 Replace Control Rod Drive & Cap Screws
- 33.
696098 Replace Control Rod Drive & Cap Screws
- 34.
696099 Replace Control Rod Drive & Cap Screws
- 35.
696100 Replace Control Rod Drive & Cap Screws
- 36.
781368 Replace HP Pipe fitting
- 37.
782779 Replace Control Rod Drive & Cap Screws
- 38.
789955 Repair Weld on MS Drain Line TABLE E (CONT'D)
REPAIR/REPLACEMENT ACTIVITIES CLASS-2
'WORK PACKAGE #
DESCRIPTION
- 1. 421977 Replace HP Water Leg Pump
- 2.
437834 Replace RI Rupture Disc
- 3.
437835 Replace RI Rupture Disc
- 4. 541468 Replace SC Valve & Piping
- 5.
552479 Replace Extension Tube on MS Strut
- 6.
582162 Repair RH Valve
- 7.
582163 Repair RH Valve
- 8.
668477 Repair Heat Exchanger by Plugging Tubes
- 9.
677752 Replace RI Valve Disc
- 10. 781039 Repair Indications on RH Pipe
- 11. 94060704 Replace Pump Seal Gland Plate
ATTACHMENT 3 ABBREVIATIONS AD ADDENDA ANIC AUTHORIZED NUCLEAR INSERVICE CONCRETE AISI AUGMENTED INSERVICE INSPECTIONS ASSY ASSEMBLY ATT ATTACHMENT ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS AUTO UT AUTOMATED ULTRASONIC TEST BOM BILL OF MATERIAL BWR BOILING WATER REACTOR BWROG BOILING WATER REACTOR OWNER'S GROUP BWRVIP BOILING WATER REACTOR VESSEL AND INTERNALS PROJECT CHRON TRACKING SYSTEM FOR ENGINEERING EVALUATIONS CID CATALOG IDENTIFICATION CM CONTAINMENT MONITERING CISI CONTAINMENT INSERVICE INSPECTION CR COMPONENT RELIEF REQUEST CRD CONTROL ROD DRIVE EC ENGINEERING CHANGE ED EDITION EGC EXELON GENERATION COMPANY ES EXTRACTION STEAM EVT ENHANCED VISUAL TEST FC FUEL POOL COOLING FW FEEDWATER GENE GENERAL ELECTRIC NUCLEAR ENERGY HG CONTAINMENT COMBUSTIBLE GAS CONTROL HP HIGH PRESSURE CORE SPRAY HSB-CT HARTFORD STEAM BOILER INSPECTION & INSURANCE CO. OF CONNECTICUT HT#
HEAT#
ATTACHMENT 3 (CONT'D)
ID/OD INSIDE DIAMETER/OUTSIDE DIAMETER IGSCC INTERGRANULAR STRESS CORROSION CRACKING IL ILLINOIS IN INSTRUMENT NITROGEN IRM INTERMEDIATE RANGE MONITOR ISI INSERVICE INSPECTION L2R07 LASALLE TWO REFUEL OUTAGE SEVEN L2R08 LASALLE TWO REFUEL OUTAGE EIGHT L2R09 LASALLE TWO REFUEL OUTAGE NINE L2RIO LASALLE TWO REFUEL OUTAGE TEN LLC LIMITED LIABILITY COMPANY LPRM LOCAL POWER RANGE MONITOR LP LOW PRESSURE CORE SPRAY MIL MILLIMETER MC CLEAN CONDENSATE STORAGE MS MAIN STEAM MSIV MAIN STEAM ISOLATION VALVE MT MAGNETIC PARTICLE TEST' MWt MEGAWATT THERMAL N/A NOT APPLICABLE NB NUCLEAR BOILER NDE NON-DESTRUCTIVE EVALUATION NDES NONDESTRUCTIVE EXAMINATION SERVICES NIR NOZZLE INNER RADIUS NR NUCLEAR INSTRUMENTATION NRC NUCLEAR REGULATORY COMMISSION NRI NON-RECORDABLE/NON-RELEVANT INDICATION PA PENNSYLVANIA PC PRIMARY CONTAINMENT PCE PART CLASSIFICATION EVALUATION
ATTACHMENT 3 (CONT'D)
PDI PERFORMANCE DEMONSTRATION INITIATIVE PG PAGE PO PURCHASE ORDER PR PRESSURE TESTING RELIEF REQUEST PSI PRESERVICE INSPECTION PSIG POUNDS PER SQUARE INCH GAGE PT LIQUID PENETRANT TEST PTE PART TECHNICAL EVALUATION PWHT POST WELD HEAT TREATMENT QRI QUALITY RECEIPT INSPECTION RC-PB REACTOR COOLANT PRESSURE BOUNDARY RD ROD DRIVE RE REACTOR BUILDING EQUIPMENT DRAINS RF REACTOR BUILDING FLOOR DRAINS RH RESIDUAL HEAT REMOVAL RI REACTOR CORE ISOLATION COOLING RIN RECEIPT INSPECTION #
RPV REACTOR PRESSURE VESSEL RR REACTOR RECIRCULATION RT REACTOR WATER CLEAN UP SA SERVICE AIR SAR SAFETY ANALYSIS REPORT SC STANDBY LIQUID CONTROL SDC SHUTDOWN COOLING SEAG SITE ENGINEERING ADMIN GROUP SIL SERVICES INFORMATION LETTER SRM SOURCE RANGE MONITOR SRV SAFETY RELIEF VALVE STM STEAM UT ULTRASONIC TEST
ATTACHMENT 3 (CONT'D)
VG STANDBY GAS TREATMENT VLV VALVE VP PRIMARY CONTAINMENT CHILLED WATER VQ PRIMARY CONTAINMENT VENT AND PURGE VT VISUAL TEST WO WORK ORDER WR REACTOR BUILDING CLOSED COOLING WATER
ATTACHMENT I NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTION
1'UK?4 A1l-1 UVViAh('b kJKAUJK I UK' 11NbLKV ILI 11NbrhqYJUINb As required by the Provisions of the ASME Code Rules
- 1. Owner Exelon Generation Company (EGC), LLC, 200 Exelon Way, Kennett Square, PA 19348 (Name and Address of Owner)
- 2. Plant LaSalle County Station, 2601 North 21st Road Marseilles, IL 61341-9757 (Name and Address of Owner)
- 3. Plant Unit Two
- 4. Owner Certificate of Authorization (if required)
N/A
- 5. Commercial Service Date 10/17/84
- 6. National Board # for Unit 10
- 7. Components Inspected Component or Manufacturer Manufacturer State or National Appurtenance Or Installer or Installer Province No.
Board No.
Serial No.
Reactor Pressure Chicago Bridge & Iron T-37 B-243 19 0
Vessel Reactor Recirculation General Electric N/A N/A N/A Company Nuclear Boiler & CM B.F. Shaw N/A N/A N/A Systems Residual Heat B.F. Shaw N/A N/A N/A Removal Feedwater, FC & VQ B.F. Shaw N/A N/A N/A Systems High Pressure Core B.F. Shaw N/A N/A N/A Spray Low Pressure Core B.F. Shaw N/A N/A N/A Spray Main Steam, & IN GE/B.F. Shaw N/A N/A N/A RI & RT Systems B.F. Shaw N/A N/A N/A ES, MC, SA & WR B.F. Shaw N/A N/A N/A Systems SC, HG & VP B.F. Shaw N/A N/A N/A Systems Note: Supplemental sheets in torm ot lists, sketches, or drawings may De used, provided (1) size is zSi2 in. x I1i Y in., (2) information n items I through 6 on this report is included on each sheet, and (3) each sheet is #ed and the # of sheets is recorded at the top of thi!
1orm.
FORM NIS-1 (Back)
- 8. Examination Dates:
- 9. Inspection Period Identification:
- 10. Inspection Interval Identification:
- 11. Applicable Edition of Section XI
- 12. Date/Revision of Inspection Plan:
02/21/03 to 03/16/05 3rd Period - From 07/05/04 to 07/04/2007 2nd Interval - From 10/17/94 to 07/04/2007 1989/1998*
Addenda N/A 11/20/2002 Rev.4
- 13. Abstract of Examination and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See Summary Report for item 13.
- 14. Abstract of Results of Examinations and Tests. See Summary Report for item 14.
- 15. Abstract of Corrective Measures. See Summary Report for item 15.
- Via Relief Request CR-32, the 1998 Edition of the ASME Code,Section XI applies to CISI Action Tracking Item # 314183-03 is tracking completion of NDE for Work Order # 789955.
We certify that a) the statement made in this report are correct, b) the examinations and tests meet Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the ASME Code,Section XI.
Certificate of Authorization No. (if applicable)
N/A Expiration Date N/A Date Abuz
/0.
20 05 Signed ExelonGenerationCompany,LLC By i
,~
C.
Owner CERTIFICATE OF INSERVICE INSPECTION 1, the under signed, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois And employed by HSB-CT of Hartford, Connecticut Have inspected the components described in the Owner's Report during the period 02/21/2003 To 03/16/2005
, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
/I Inspector's Signature Commissions IIL. 1927 National Board, State, Province, and Endorsements Date 6_-,
20 05
ATTACHMENT 2 NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi
- 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Date 05/14/05 Address LaSalle County Nuclear Station
- 2.
Plant Name 2601 N. 21" Rd. Marseilles. 1I. 61341 Address Sheet I
of I
Unit 2
W.O. #428318 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed b,v Morhanteal Unlnfanance (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A 4.
5.
Identification of System (MS) Main Steam (a) Applicable Construction Code Sect lii 19 71 Edition S172 Addenda, Code Cases 1567 and 1711 (b)
Applicable Edition of Section Xi Utilized for Repairs or Replacements-19 89, No Ad, Code Cases No Identification of Comnonents Renalred or Reolaced. and Replacement Comoonents 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Safety Relief AG Crosby N63790-00-0073 N/A 2B21-F013E Replaced NIA V alve__
Safety Reiief AG Crosby N63790-00-0004 N/A 2B21-F013E Replacement N/A Valve or N63790 Receipt # 101593 0004 (Modified)_
Nozzle AG Crosby N93184-49-0138 N/A Replaced N/A Nozzle AG Crosby N97498-32-0009 N/A Receipt# 101593 2003 Replacement NIA Disc Insert N93185-46-0170 N/A Replaced N/A Disc Insert AG Crosby N97499-45-0113 N/A Receipt# 101593 2004 Replacement N/A 8.
9.
Description of Work Class I Repair & Replacement. * = Per N-5 Code Data Regort on file at LaSalle CountV Station.
Tests Conducted:
Hydrostatic i I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure. 1035 esl Test Temp. 155 Deg. F Remarks Valve SN# N63790-05-0004 was refurbished at Wvle Labs with documentation provided under Quality (Applicable Manufacturer's Data Report to be Attached )
Recelot #101593 and installed as a replacement for SN# N63790-00-0073 under work order #428318. SRV nozzle
-I--
I -
... t.
..
-I---
emly wab sbU als
~dot:U WVIL11 Ic UV ne UDUV I
smI.
oVeIall Ilu it Was IJIUW 111111111JUl11 LUIUlI doIr e
Ia
- V Serial No. was modified due to the Installation of a new flexi-disc seat design.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and these Replacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Au orization No.s_
Rinned ZZcc NIA
.Expiration Date NIA tRI r~nnrd~natnr Date Hi
/;
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boiler Insp. & Ins. Co. of Connecticut have inspected the components described in this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
C at rltfinn-6h1--Artfif1"fa nnkitb--
- imInna^
nor hie amnnimsxr maile anu t Swrro l
rAo a_____
I 10159 3 Q.C.-434A Sheet 1 of 2 FORM NVR-1 REPORT OF REPAIR MODIFICATION
],
OR REPLACEMENT
- OF NUCLEAR PRESSURE RELIEF DEVICES
- 1. Work performed by ANDERSON GREENWOOD CROSBY 00076601 (name of organization)
(P.O. no., job no., etc.)
43 Kendrick St., Wrentham, MA 02093 (address)
- 2. Work performed for 'EXELON CORPORATION,LASALLE STATION,MARSEILLES,IL.
(name and address)
- 3. Owner EXELON CORPORATION,LASALLE STATION,MARSEILLES,IL.
(name)
(address)
- 4. Name, address and identification of nuclear power plant EXELON CORPORATION,LASALLE STATION, MARSEILLES, IL.
- 5. a.
Repaired pressure relief device MAIN STEAM SAFETY RELIEF VALVE
- b.
Name of manufacturer ANDERSON GREENWOOD CROSBY
- c.
Identifying nos.
HB-65-BP l"' N63790.05.0004 STEAM 6 R 10 1981 (type)
(mfr's serial no.)
(Nat'l Bd. No.)
(service)
(size)
(year built)
- d.
Construction Code ASME III 1971 S1972 1567,1711 I
(narne/section/division)
(edition)
(addenda)
(Code Case(s))
(Code Class)
- 6. ASME Code Section Xl applicable for Inservice inspection 1989 NO
- edition)
(addenda)
(Code Case(s))
7.' ASME Code Section XI used for repairs, modifications," or replacements 1989 NO (edition)
(addenda)
(Code Case(s))
8.. Construction Code used for repairs, modifications, or replacements 1971 S1972 1567,1711 (edition)
(addenda)
(Code Case(s))
- 9. Design responsibilities ANDERSON GREENWOOD CROSBY
- 10. Opening pressure 1175 PSIG Blowdown (if applicable). 3
% Set pressure and blowdown adjustment made at WYLE LABORATORIES,HUNTSVILLE.AL.
using STEAM (location)
(test medium)
- 11. Description of work: (include name and identifying number of replacement parts)
FLEXIDISC MODIFICATION, REPAIR AND TESTING MADE AT WYLE LABORATORIES, HUNTSVILLE,AL. USING STEAM.
- 12. Remarks THE DISC INSERT WAS REPLACED AND VARIOUS PARTS MODIFIED AS PART OF THE FLEXIDISC MODIFICATION.
i
Form NVR-1 (Back) 10 1593 Certificate Holder's Serial Nos. N63790-05-0004 Q.C.-434A Sheet 2 of 2 "
CERTIFICAE1OF COMPLIANCE I,
))A dI
< 3~-z certify that the statements made in this report are correct and the repair, modification ox replacement of the pressure relief device described above conforms to Section XI of the ASME Code and the National Board Inspection Code "VRW and "NR" rules.
.National Board Certificate of Authorization No.
75 to 84 to use the WVR' stamp expires JAN. 14,2007 National Board Certificate of Authorization No.
68 to use the "NR* stamp expires DEC.11,2006 Date 7-14&P
,>o Signed Anderson Greenwood/Crosby Oi
/
QA MGR.
(name of repair organization)
(authorized representative)
(title)
- l
~~~CER TIFICATE OF INSPECTIN l,
,holding a valid commission issued by The Nationial Boardof Boiler and ressuie Vessel Inspectors and Certificate of competency issued by the jurisdiction of MASSACHUSETTS and employed by
-HSB-CT of HARTFORD - CT.
have:
inspected the repair, modification or replacement described in this report on
&6 Oand state that to the best of my knowledge and belief, this repair, modification or replacement has been completed in accordance with Section XI of the ASME Codeand the National Board Inspection Code 'VRW and 'NR' rules.
By signing this certificate, neither the undersigned nor my employer makes any warranty, expressed or implied, concerning the repair, modification or replacement described in this'report.. Furthermore, neither the undersigned nor my employer shall be liable in any manner for any personal injury, property damage or loss of any kind arising from or connected with this Inspection.
Date 5 *.
Signed ____________'
Commissions MA1420 A, N. I (Inspector)
(Nat'l. Bd. (inc. endorsements), and jurisdiction, and no.)
- 2.
Jan. 8. 2005 10:26AM No.1163 P. 4/5 Q.C.-392 Sheet 1 of 2 FORM N-2 CERT[CATE HOLDERS' DATA REPORT FOR IDENTICAL
'-NUCLEAR PARTS AND APpuRTENANCES*
As required by the Provisions of the ASME Code. SectioIf, Drvislon 1 - Not to Exceed One Day's Production
- 1. Manufactured and certified by
- 2. Manufactured for Anderson Greenwood Crosby, 43 Kendrick St., Wrentham, MA 02093
-(Name axnd Address of N Certificate Holder)
EXELON GENER~AT1ON (Name and Address of Purchaser or Owner)
LASALLE COUNTY STATION
- 3. Location of Installation (Name and Address)
- 4. Type DS-C-63790-5 REV.A ASME SA182 GR.F316 70,000 2003 (drawing no.)
(mat'l. spec. no.)
(tensile strength)
(CRN)
(year built)
- 5. ASME Code,Section III, Division 1:
1971 SLJMER 1972 1
(edition)
(addenda date)
(class)
(Code Case No.)
- 6. Fabricated in accordance with Const. Spec. (Div. 2 only)
Revision Date (no.)
- 7. Remarks 2,9 B. Nom. thickns (in.)
Min. desigi thickness (in.)
Dia. ID (ft & in.)
Length overall (ft & in.)
- 9. 'When applicable, Certificate Holders' daa reports are attacedo each item of this report.
Part or Appurtenance Serial Number
,(1)7N97498-32.0009 j (2) N97498-32-0010 (3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
(21)_
(22)
(23)
(24)
(25)
National I Board No.;:
in Numerical Order (26)
- (27)
_(29)
(30)
-_m:^. (3l)
> (32)
-i 1 1(33)
(3 5)~
(37)
(38)
(39)
(40)
(41)
(42)
(43)
(44)
,(45)
_ 146)
(47)
(48)
(49)
_____________(50)_
Part or Appurtenance Serial Number National Board No.
in Numerical Order I
I
- 10. Design press e psi.
Temp.
F Hydro. test pressure 2370 at temp. 70 p F (when applicable) k/ceZl nformation ia tocmn ofrrisk setches, or dnwip rmay be tsedprovidcd (I) sizc b8-112 x21 (2) inbrmrion ia hoxt 2 and 3on tis DAa Rcport is included on euch sheet. (3) each shaec is manbcmd and cie nwuber of sheets rCordeda e itop ofthi forn.
This form (E00040) nay be ohtad from d&C order DepL, ASME, 22 Law Drive. Box 2300, Fairtded, NJ 07007-230Q
.12n.
A. M5 10:26AM No-1163 P. 5/5
.bn R. 700 102A
- o16 P. L 5/5 C)a / 0Q.C.-392 Form N-2 (Back)
Sheet 2 of 2 Certificate Holder's Serial No. N97498-32-0009 J
CERTIFICAT ORDESIGN Design specifications certified by C.T. NIEH P.E. State CA Reg. no. 15581 (when applicable)
Design reporE* certified by P.E. State Reg no.
(when applicable)
CERTIFICATE OF COMPliANCE We certify 2hat the statements made in this report are correct and that this (these)
Nozzles conforms to the rules of construction of the ASMB Code, Section Jr, Dii'iosa 1.
NPT Certificate of Authorization No.
N-1877 Expires Sep. 30, 2004 Anderson Greenwood Crosby Date ZO -f8-O3 Signed Wrentha by mMA (NPT Certificate Holder)
(Authorized Representative)
CERTICAOF SPECON 1, the umdersigned, holding a valid commission issued by the.National Board of Boiler and Pressure Vessel inspectors and tLe State or Province of Massachusetts and employedbby" Factory Muttial Tsuran=c Co.
of Johnston, Rhode Island have inspected these items described in this Data Report on
_a
, 20 _2, 1 and state that to the best of my knowledge and belief, the Certificate Holder has fabricated tse parts or appurtenances in accordaiceifh tlhe AivME Code, Section Em, Division 1. Each part listed has becn authorized for stamping on the date shown above.
^
By signing this certificate, neither the Inspector nor his employer makes arty warranty, expressed or implied, concerning the equipment described in this Data Report. Firthermoire, neither the lospector nor his employer shall be liable in any manner for any personal injury or property damage or loss5of any ktd arising from or connected with this inspection.
Date
- P d 20 O3 Signed Commissions
/7,
/
(Authorized Inspector) aT.Bd. (ioel. endbrsemes) and slate or proy. a&d no.)
.Jan. 8. 2005 10:26AM No.1163 P. 2/5 Q.C.-392 Sheet I of 2 FOJRM N-2 CERtlfICATE HOLDERS' DATA REFORT.FOR IDEIflCAL NUCLEAR PARTS AND.APPURTENANCES;*
As requir-edb the Provisions of the ASME Code. Secton m. Division I - Not to Exceed One Day's Production
- 1. Manufactured and certified by Anderson Greenwood Crosby, 43 Kendrick St., Wrentbani, MA 02093
- (Name and Address of N Certificate Holder)
EXELON GENERATION 2 Manufactured for (Name and Address of Purchaser or Owner)
LASALLE STATION
- 3. Location of Installation (Name and Address)
- 4. Type DS-A-63790-2 REV.-
. ASME SA637 GR 718 185,000 2004 (drawing no.)
(mat'l. spec. no.)
(tensile strength)
(CRN)
(year built)
- 5. ASME Code,Section III, Division 1.
1971 SUMMER 1972 1
(edition)
(addenda date)
(class)
(Code Case No.)
- 6. Fabncated in accordance with Const. Spec. (Div. 2 only)
Revision Date (no.)
- 7. Remarks 8
Nom thiclsaess (in.)
Min. design thickness (in.)
Dia. ID (t & in.)
Length overall (ft & in.)
9 When aprplicable. Certificate Holders' data reports are attached for each item of this report.
Parn or Apputenanice Serial Number (1) N97499-45-0112 (2) zN97499-45-1O 13 J(3) N97499-45-0114 (4) N9g7499-45-0115 (5) N97499-45-0116 (6) N97499-45-0117 (7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19) 20)
(21)
(22)
(2)-
(24)
(25)
National Board No in Numerical Order
.~
I Part or Appurtenance Serial Number (2
(2 (2
(2-(31 (3
(3:
(3:
(36 (3!
(3f (31 (38 (39 (40 (41:
(420 (43; (44)
(45)
(46)
(47)
(48)
(49)
(5O)
.6_
7)_
8)_
9)-
D) 0)
Z)-
National Board No.
in Numerical Order 4)-
1)
)
)
?
I I-II Design pressure psi.
Temp.
F Hydro. test pressure 2370 psig at temp. 70 0 F (when applicable)
~1r tesnuJnformtzdon inathe foru of itrm. skehes. or drawSS nuy be Wed provded (1) se Is 8-Ml x 11. (2) Irormaxion In Items 2 and 3 on this Dat Report Is includcd on eacb shle, (3) ezcA sheet Is numbered and the nr ober ofsheea As recorded ct the top of Ws form.
This brn (E00O40) may be obtained frcm ihc Order Dept.. ASM E. 22 Law Drive. Box 2300. Fairfield. NJ 070t7-2300
.Jan. 8. 2005 10:26AM No.1163 P. 3/5 Q.C.-392 Form N-2 (Back)
Sheet 2 of 2 Certificate Holder's Serial No. N97499-45-0112 thru 0117 CERTIFICATE QF DESIGN Design specifications certified by C T NIEH P.E. State CA Reg. no 15587 (when applicable)
Design report* certified by W.D. GREENLAW P.E. State MA Reg. no. 14784 (when applicable)
CERTIFJCA ZE OF COMPLCk We cerufy that the statements made in this report are correct and that this (these)
Disc Inserts conforms to the rules of construction of the ASME Code, Section m, Division 1.
NPT Certificate of Authonzation No.
N-1877 Expires Sep. 30, 2004 Anderson Greenwood Crosby Dam 5_
FE_
Zc Sgned Wrentham, MA by
____I D
(NPT Certificate Holder)
(Authorized Representative)
CERTIFICATE OF INSPECTION 1, the undersigned, holding a valid commmssion issued by the National Board of Boiler and Pressure Vessel Inspectors and the State eor-Pre4neeof 45AS.#
and employed by ABS Grout Inc.
of Houston Tcxas have inspected these items described in ti5 Data Report on
,gR-,
20o.0 and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASMB Code,Section III, Division 1. Each part listed has been authorized for stamping on the date shown above.
By igning tins certificate, neither the Inspector nor his employer makes any warranty, expremsed or implied, concerunwg the equipment described in this Data Report. Furthermore7 neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or loss of any kand arismg from or connected with thas inspection.
Date 5, 20OO Signed_ __
Co ssions Lk ILJ 4
(Authorized Inspector)
(Nat'l. Bd. (ncl. endorseniasts) and state or prov. and no)
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section XI
- 1.
Owner Exelon Generation Company (EGCC LLC (Name) 200 Exelon Way, Kenneth Square, PA., 19348 Address
- 2.
Plant LaSalle County Nuclear Station Name 2601 N. 21" Rd. Marseilles. II. 61341 Address Datp 051AI4/0 Sheet 1
of 1
Unit 2
W.O. #428319 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed by IJ"I{P+AN^
%- +f Mechanical Maintenance (Name)
Mechanical Maintenance (Address)
- lime "1"1 cheat Type Code Symbol Stamp NJA Authorization No.
N/A Expiration Date N/A 4.
5.
IUVIMllCILIUVII WI QYZLem IM4IJI OLUdII (a) Applicable Construction Code Sect III 19 71 Edition S172 Addenda, Code Cases 1567 and 1711 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19 89, No Ad, Code Cases NO Identification of Components Renalred or Replaced, and Reolacement Comnonents 6.
Name of Name of Mfrs. Ser.-
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Safety Relief Valve AG N63790-00-0065 N/A 2B21-F013R1 Replaced NIA Crosby Safety Relief Valve AG N63790-00-0015 N/A 2B21-F013R a
Replacement N/A Crosby or N63790 Receipt # 101593 0015 (Modifled)__
Disc Insert N93185-53-0214 N/A Replaced N/A Disc Insert AG N97499-45-0115 N/A Recelpt# 101593 2004 Replacement N/A Crosby 7.
8.
9.
Description of Work Class 1 Repair & Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure.Q1035 psl Test Temp. 155 Deg. F Remarks Valve SN# N63790-05-0015 was refurbished at Wyle Labs with documentation provided under Quality (Applicable Manufacturer's Data Report to be Attached )
Receipt# 101593 and Installedas a replacementforSN# N63790-00-0065 underwork order#428319. Ail bolting materials were reused. A visual examination VT-1 was performed on all Class 1 Inlet bolting.
- Renlacement SRV Serial No. was modified due to the Installation of a new flexi-disc seat design.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Auth rIzatIon No.
Signed N/A
-Expiratlon Date N/A ISI Coordinator Date
/
=
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois' and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described in this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
i Commissions IL 1927 In ctor's Signature National Board, State, Province, and Endorsements Date 2005
101593-Q.C.-434A Sheet I of 2 FORM NVR-1 REPORT OF REPAIR MODIFICATION [,
OR REPLACEMENT I OF NUCLEAR PRESSURE RELIEF DEVICES
- 1. Work performed by ANDERSON GREENWOOD CROSBY 00076601 (name of organization)
(P.O. no., job no., etc.)
43 Kendrick St., Wrentham, MA 02093 (address)
- 2. Work performed for EXELON CORPORATION,LASALLE STATIONMARSEILLES,IL.
(name and address)
- 3. Owner EXELON CORPORATIONLASALLE STATION,MARSEILLES,IL.
(name)
(address)
- 4. Name, address and identification of nuclear power plant EXELON CORPORATION,LASALLE STATION, MARSEILLES, IL.
- 5. a.
Repaired pressure relief device MAIN STEAM SAFETY RELIEF VALVE
- b.
Name of manufacturer ANDERSON GREENWOOD CROSBY
- c.
Identifying nos.
HB-65-BP N63790-05-0015 STEAM 6 R 10 1981 (type)
(mfr's serial no.)
(Nat'l Bd. No.)
(service)
(size)
(year built)
- d.
Construction Code ASME III 1971 S1972 1567,1711 1
(name/section/division)
(edition)
(addenda)
(Code Case(s))
(Code Class)
- 6. ASME Code Section XI applicable for Inservice inspection.
1989 NO (edition)
(addenda)
(Code Case(s))
- 7. ASME Code Section XI used for repairs, modifications, or replacements 1989 NO (edition)
(addenda)
(Code Case(s))
- 8. Construction Code used for repairs, modifications, or replacements 1971
.S1972 1567,1711 (edition)
(addenda)
(Code Case(s))
- 9. Design responsibilities ANDERSON GREENWOOD CROSBY
- 10. Opening pressure 1205 PSIG Blowdown (if applicable) 3
% Set pressure and blowdown adjustment made at WYLE LABORATORIES,HUNTSVILLE,AL.
using STEAM (location)
(test medium)
I1. Description of work: (include name and identifying number of replacement parts)
-FLEXIDISC MODIFICATION, REPAIR AND TESTING MADE AT WYLE LABORATORIES, HUNTSVILLE,AL. USING STEAM.
\\
- 12. Remarks THE DISC INSERT WAS REPLACED AND VARIOUS PARTS MODIFIED AS PART OF THE FLEXIDISC MODIFICATION.
- A 0 1 5 9 3 Q.C.-434A '
Form NVR-l (Back)
- 01Sheet523ofQ2 Certificate Holder's Serial Nos. N63790-05-0015
.CERTIFICATE OF COMPLIANCE.
I, Ap~t/ f3 -j-.s,
'certify that the statements made in this report are correct and the repair, modification oz replacement of the pressure relief device described above conforms to Section XI of the ASME Code and the National Board Inspection Code 'VR' and "NR' rules.
National Board Certificate of Authorization No.
75 to 84 to use the 'VR' stamp expires JAN. 14,2007 National Board Certificate of Authorization No.
68 to use the NRW' stamp expires DEC.11,2006 Date 7-SA
, !O(Signed Anderson Greenwood/Crosby
.C /
QAMGR.
(name of repair organization)
(authorized representative)
(title)
'CER..,CA.TE F
.N,,E.
T.
i2 j~-~,holinga vlidcomision isse by Th'le Nati onal Board of Boiler 'and Pressure Vessel Insecorand er~ticate of competency issued by the jurisdiction of MASSACHUSETTS ' and employed by.'.
HSB-CT of HARTFORD - CT.
have inspected the repair, modification or replacement described in this report on _ __________oj and state that to th, best of my knowledge and belief, this repair, modificatio or replacement has been completed in accordance of the ASME Codeand the National Board Inspection Code
'VR.
and '-N' rules.
By signing this certificate,:neithr the undersigned nor my employer makes any warranty, expressed 'or implied, concerning'.:'
the repair, modification or replacement described in this report. Furthermore, neither the undersigned nor my employer shall
-be liable in any manner for any personal injury, property damage or loss of any kind arising from or connected with this Inspection.
Date Signed an e
Commissions MA1420 A, N, I (Inspector)
(Nat'l. Bd. (incl. endorsements), and jurisdiction, and no.)
.Jan. 8. 2005 10:26AM No.1163 P. 2/5 Q.C.-392 Sheet I of 2 FOiRM N-2 CERIMFCATE HOLDERS DATA REPORT.FOA LWENICAL NUCL}EAR PARTS ANDAPURTEINANCES*
As reuiired bV the Provisions of tbe ASME Code, Section IlI Division I - Not to Exceed One Day's Production
- 1. Manufactured and ceritified by 2
Manufactured for Anderson Greenwood Crosby, 43 Kendriclk St., Wreniham, MA 02093 (Namc and Address of N Certificate Holder)
EXELON GENERATION (Name and Address of Purchaser or Owner)
LASALLE STATION 3.- Location of InstaUation (Name and Address)
- 4. Type DS-A-63790-2 REV.-
. ASME SA637 GR 718 185,000 2004 (drawing no.)
(mat'l. spec. no.) -
(tensile strength)
(CRN)
(year built)
- 5. ASME Code,Section III. Division 1.
1971 SUMMER 1972 1
(edition)
(addenda date)
(class)
(Code Case No.)
- 6. Fabricated in accordance with Const. Spec. (Div. 2 only)
R Revision Date (no.)
- 7. Remarks 8 Nom thickness (in.)
Mi. design thickness (in.)
Dia. 1I) (ft & in,)
Lengt overall (ft & in.)
9 When applicable, Certificate Holders' data reports amc attached for each item of this report.
Parn or Appurtenance Serial Number (1) N97499-45-0112 (2) Nl97499-45-0113 (3) N97499-45-0114 (4),N97499-45-0115-w (5) N97499-45-0116 (6) N9749945-0117 (8)
(9)
(10)
(11)
(12)
(13)
(14)
(15.)
(16)
(17)
(18)
(19)
(20)
(21)
(22) 523)'
(24)
(25)
National Board No in Numerical Order I
Part or Appurtenance Senal Number National Board No.
in Numerical Order
("I
.(3 (3
(3 (3~
(3~
(3' (43 (4)
(4(
!6)_
17)_
!8)-
M'.9 0G) 31) 2)
3) 4)
5) 6)
7)
I)
[)
(43)
(44)
(45)
(46)
(4'7)
(48)
(49)
(50) 1A Design pressure psi.
Temp.
F Hydro. rest pressure 2370 psig at temp. 70 (when applicable)
"ipterntil mformidon In the form ot Ulsu. Iketchte. or dnmgS nuy be ued provd () Size s S.ISl xl il. (2) hirormrtion In Items 2 and 3 on tbis Pata Report is included on eacb shet, (3) mest sheet is numberd Ai tc nmber of shect is recorded et the top of Ohh fornm.
This orm (EOOd4O) may bc obtsined frem the Order Dept., ASME, 22 Lae Drive. Box 300. Fairfield. N1 07007-2300 Do F
.Jan. 8. 2005 10:26AM No.1163 P. 3/5
_'s o//N7
- e.fCe-ficate Holder's Serial No. N97'499-45-01 12 thru 01 17 Form N-2 (Back)
Q.C.-392 Sheet 2 of 2 CERTIFICATE OF COMPLIACi We certify that the statements made in this report are correct and that this (these)
DIsc Inserts conforms to the rules of construction of the ASfE Code,-Section m, Division 1.
NPT Certificate of Authorization No.
N-1877 Expires Sep. 30, 2004 Anderson Greenwood Crosby Date 5 Fw Zcoq Signed Wrentham, MA by (NPT Certificate Holder)
Authorized Representative)
I CERNFCA QE OFISPECTION i
1, the undersigned, holding a valid commission issued by the National Board of Bogler and Pressure Vessel Inspectors and the State oe-Preyhw&.of A14
-5 and employed by ABS Grcm Inc.
of Houston. Texas have inspected thece items described in this Data Report on o_-_6_, 2003t1 and state that to the best of myi knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance vwith the ASME Code,Section III, Division 1. Each part listed has been authorized for stamping on the date shown above.
By sigaing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of aly kind arising from or connected with his dspection.
Date 2004~.
Signed
[..
Commissions Itl-L-.
AJ (Authorized Inspector)
(Nat'). Bd. (ine. endorsenicats) and state or prov. and no)
I)
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl
- 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way, Kenneth Sauare. PA.. 19348 Address
- 2.
Plant LaSalle County Nuclear Station Name 2601 N. 21' Rd. Marseilles. II. 61341 Address Date 05/14/05 Sheet
.I of 2
Unit 2
W.O. #429584 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed bTV Maechannicl Malntannnra (Name)
Mechanical Maintenance Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A (Address) 4.
5.
Identification of System (MS) Main Steam (a) Applicable Construction Code Sect 1i1 19 71 Edition S/72 Addenda, Code Cases 1567 and 1711 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19p 89, No Ad, Code Cases N-496-1 Identification of Comoonents Renaired or Renlaced. and Reolacement Comnonents 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Safety Relief Valve AG N63790-00-0014 N/A 2B21-FO13L Replaced N/A Crosby Safety Relief Valve AG N63790-00-0013 N/A 2B21-FO13L Replacement N/A Crosby or N63790 Receipt # 101593 0013 (Modified)'
Disc Insert N93185.33-0070 N/A Replaced N/A Disc Insert AG N9749945-0114 N/A Receipt# 101593 2004 Replacement N/A C rosb y 7.
8.
9.
Description of Work Class 1 Repalr & Replacement. * = Per N-5 Code Data Renort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I _ I Normal Operating Pressure I X I Other Visual Pressure 1035 psi Test Temp. 155 Deg. F Remarks Valve SN# N63790-05-0013 was refurbished at Wyle Labs with documentation provided under Quality (Applicable Manufacturer's Data Report to be Attached )
Recelot# 101593 and Installedas a replacementforSN# N63790-00-0014 underworkorder#429584. Forthe remainder of the Repaired. Replaced and ReDlacement Items, see Form NIS-2 Supplemental Sheet on Pages 2 of 2.
- Replacement SRV Serial No. was modified due to the Installation of a new flexl-disc seat design.
CERTIFICATION OF COMPLIANCE We certify that the statements made in the report are correct and these Repalr and Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
Signed C
- 2~Z.
&11A r
r%~-.
n MP_
_____ dLIUI i LdaL N/A ISI Coordinator Date,"%
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, Theundersigned, holding a valid commission Issuedby the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner foranypersonal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 InspecXr's Signature National Board, State, Province, and Endorsements Date __
2005
- 1.
Owner:
- 2.
Plant:
FORM NIS-2 SUPPLEMENTAL SHEET Exelon Generation Company (EGC) LLC Sheet 2
200 Exelon Way, Kenneth Square, Date 05114/05 PA., 19348 Unit LaSalle County Station 2601 N. 21st. Rd.
Marseilles, Illinois 61341 W.O. # 4295 of 2
2 584
- 3.
Work Performed by: Mechanical Maint.
Name Mechanical Maintenance P. 0. No., WR No., etc.
Type Code Symbol Stamp N/A Authorization No.
NIA Expiration Date N/A 4.
5a.
5b.
6.
Address Identification of System MS (Main Steam)
Applicable Construction Code 71 Edition S72 Addenda Applicable Edition of Section Xi utilized 89 Edition None Addenda Identification of Components Repaired or Replaced and Replacement Components.
Name of Name of Manufacturer National Other Year
- Repaired, ASME Component Manufacturer Serial No.
Board Identification Built Replaced Code No.
or Stamped Replacement (Yes or No)
Valve Body AG Crosby N93183 NIA Receipt #
Repaired NIA 0002 101593 (1) Hell-Coil AG Crosby N97823-0051 N/A Receipt #
2002 Repaired NIA Insert 101593 (Outlet)
1059 1.0 1 5 9 3 :Q.C.-434A
-Sheet I of2 FORM NVR-1 REPORT OF REPAIR Fx MODIFICATION F.TOR REPLACEMENT F OF NUCLEAR PRESSURE RELIEF DEVICES
- 1. Work performed by ANDERSON GREENWOOD CROSBY 00076601 (name of organization)
(P.O. no., job no., etc.)
43 Kendrick St., Wrentham, MA 02093-(address)
'2. Work performed for EXELON CORPORATION,LASALLE STATION,MARSEILLES,IL.
(name and address)
- 3. Owner EXELON CORPORATION,LASALLE STATION,MARSEILLES,IL.
(name)
(address)
- 4. Name, address and identification of nuclear power plant EXELON CORPORATIONLASALLE STATION, MARSEILLES, IL.
- 5. a.
Repaired pressure relief device MAIN STEAM SAFETY RELIEF VALVE
- b.
Name of manufacturer ANDERSON GREENWOOD CROSBY
- c.
Identifying nos.
HB-65-BP N63790-05-0013 STEAM 6 R 10 1981 (type)
(mfr's serial no.) -
(Nat'l Bd. No.)
(service)
(size)
(year built)
- d.
Construction Code ASME III 1971 S1972 1567,1711 1
(name/section/division)
(edition)
(addenda)
(Code Case(s))
(Code Class)
- 6. ASME Code Section XI applicable for Inservice inspection 1989 NO (edition)
(addenda)
(Code Case(s))
- 7. ASME Code Section XI used for repairs, modifications, or replacements 1989 NO
.(edition)
(addenda)
(Code Case(s))
- 8. Construction Code used for repairs, modifications, or replacements 1971 S1972 1567,1711 (edition)
(addenda)
(Code Case(s))
- 9. Design responsibilities ANDERSON GREENWOOD CROSBY
- 10. Opening pressure 1195 PSIG Blowdown (if applicable) 3
% Set pressure and blowdown adjustment made at WYLE LABORATORIES,HUNTSVILLE,AL.
using STEAM (location)
(test medium)
- 11. Description of work: (include name and identifying number of replacement parts)
FLEXIDISC MODIFICATION, REPAIR AND TESTING MADE AT WYLE LABORATORIES, HUNTSVILLEAL. USING STEAM.
- 12. Remarks THE DISC INSERT WAS REPLACED AND VARIOUS PARTS MODIFIED AS PART OF THE FLEXIDISC MODIFICATION.
Form NVR-1 (Back)
Certificate Holder s Serial Nos. N63790-05-0013 I 3 -
Q.C.-434A Sheet 2 of 2 CERTIFICATE OF COMPLIANCE 1,
Ad,1L 7-- certify that the statements made in this report are correct and the repair, modification ot replacement of the pressure relief device described above conforms to Section XI of the ASME Code and the National Board Inspection Code "VRW and 'NR" rules.
National Board Certificate of Authorization No.
75 to 84 to use the 'VR' stamp expires JAN. 14,2007 National Board Certificate of Authorization No.
68 to use the 'NR' stamp expires DEC.11,2006 Date 7-SEP
,ZOO4Signed Anderson Greenwood/Crosby I
, r= A OQA MGR.
(name of repair organization)
(authorized representative)
(title)
.. I
'I- ;-.:.
1A I CERTIFICA TE OF INSPECTIN
'I, '~ /C/6a_
2 Hi
,holding a valid commission issued by The National Board of Boiler and Pressure Vessel:-.
Inspectors and certificate of competency issued by the jurisdiction of MASSACHUSETIS and employed by' HSB-CT of HARTFORD-CT.
have.;
inspected the repair, modification or replacement described in this report on etand state that to the best of my knowledge and belief, this repair, modification or replacement has been completed in accordance with Section XI' of the ASME Codeand the National Board Inspection Code 'VR' and 'NRn rules.
By signing this certificate, neither the undersigned nor my employer makes any warranty,"expressed or implied, concerning the repair, modification or replacement described in this report.. Furthermore, neither the undersigned nor my employer shall be liable in any manner for any personal injury, property damage or loss of any kind arising from or connected with this' Inspection.
Date S"v3 P Signed I J PL
.. ep-TM-f -
Commissions MA1420 A, N, I (Nat'l. Bd. (incl. endorsements), and jurisdiction, and no.)
1 '
(Inspector)
.Jan. 8. 2005 10:26AM No.1163 P. 2/5 Q.C.-392 Sheet 1 of 2 FORM N-. CE~RTCATE HOLDERS' DATA RPORT FOR IDENTICAL NUCLEAR PARTS ANDAPPURENANCES*
As reouired bY the Provsion t
he the ASME Code, Secton III. Division 1 - Not to Exceed One Day's Producton
- 1. Manufactured and ceritified by 2
Manrufactured for Anderson Greenwood Crosby, 43 Kendrick St., Wreabam, MA 02093 L(Naru and Address of N Certificate Holder)
EXELON GENJERA77ON (Name and Addres" of Purchaser or Owner)
LASALLE STATION
=
3 Location of Installatjon (Name and Address)
- 4. Type DS-A-63790-2 REV.-
. ASME SA637 GR 718 185,000 D_
2004 (drawing no.)
(mat'l-spec. no.)
(tensile streigth)
(CRN)
(year built)
- 5. ASME Code,Section III, Division 1.
1971 SUMMER 1972 1
(edition)
(addenda date)
(class)
(Code Case No.)
- 6. Fabncated in accordance with Const. Spec. (Div. 2 only)
Revision Date (no.)
- 7. Remarks 8 Nom thiclaxesz (in.)
Min. design thickness (in.)
Dia. ID (ft & in.)
Length overall (ft & in.)
9 When applicable, Certificate Holders' data reports are attached for each item of this report.
Part or Appurtenance Serial Number (1) N97499-45-1I12
/ (2) N97499-45-0113 1(3)'-N97499-45-0114 1k (4) N97499-45-0115 (5) N97499-45-0116 (6) N97499-45-0117 (7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
(21)
(22)
(2)'
(24)
(25)
Dratiual Board IYo sn Numerical Order Part or Appurtenance Serial Number (26)_
(27)_
(28)
(29)-
(30)
C, (I
(I (I
(I 13 1) 32) 33) 34) 35) 36) 37) 38) 39)
'40)-
tO) 41) 42) 43)
National Board No.
in Niumerical Order (44)_
(45)
(46)_
(4'7)_
(48).
(49)
(50)_
VI Design pressure psi.
Temp.
F Hydro. test pressure 2370 psi9 at temp. 70 J
(when applicable) pltmetnn wnformardon in the form ot lsm. aketches. or draw-L5ts sny be Ustd providd (1) slze Is 8-1l2 x It. (2) Irorrnstion In Itewns 2 And 3 on this Data Report 1s included on eadch Aet, (3) each sheet is numbered Wd the numbet of sheets is recorded et the top of tWis form This tobn (EOOAOd) may be obtained from die Ordef Dept.. ASM E 22 Low Drive. Box 2300. Fairfield. N] 070072300 a, F
Jan. 8. 2005 10:26AM No.1163 P. 3/5 IV77Y7 -9 o/
l i
Form N-2 (Back)
K)
Q.C.-392 Sheet 2 of 2
_Certficate Holder's Serial No. N97499-45-0112 thru 0117 CERTIFICATE OF COLCE We certify that the statemnents made in this report are correct and that this (these)
Disc Inserts conforms to the rules of construction of the ASME Code, Section m, Division 1.
NPT Certificate of Authomzation No.
N-1877 Expires Sep.30,2004 Anderson Greenwood Crosby v
Date 5_
Zco Signed Wrentham, MA by _
D (NPT Certificate Holder)
Authorized Representative)
I I
CER TFICWT QE INSPECTION
/
1, the undersigned, holding a valid comml sion issued by the National Board of Boiler and Pressure Vessel Inspectors and the State e r}
of, A1 and employed by ABS Group Inc.
of Houston Texas have inspected these items described in this Data Report on
_-6_,
200o and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code, Section m, Division 1. Each part listed has been authonzed for stamping on the date shown above.
By swgng this certificate, neither the Inspector nor his omployer makes any warranty, expressed or implied, concernn the equipment described in this Data Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kand arisrug from or connected with this inspection.
Date
,, 0O.
Signed l
Commissions AiL
,LAC>_
AJ (Authorized Inspector)
(Nat'l. Bd. (ind.
endorseiants) and state or proa. and no)
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section XI
- 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Address
- 2.
Plant LaSalle County Nuclear Station Name 2601 N. 2111 Rd. Marseilles. II. 61341 Address Date 05/23/05 Sheet 1
of 1
Unit 2
W.O. #515539 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed by_
Mechanical Maintenance Type Code Symbol Stamp N/A Authorization No.
N/A (Name)
Mechanical Maintenance (Address)
Expiration Date_
N/A 4.
5.
Identification of System (MS) Main Steam (a) Applicable Construction Code Sect ill 19 71 Edition W'71 Addenda, Code Cases NO (b)
Appilcable Edition of Section XI Utilized for Repairs or Replacements-19 89, No Ad, Code Cases NO n_ _--- _-
_s _____
-s__
_-t_l___
b.Identification oT Gom )onenms Repairea or Keplacea, ana Kepiacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
MSIV Stem/Stem-Rockwell N/A 2B21-F028D Replaced N/A Disk Assy.
Corp MSIV Stem/Stem-Flowserve 76366-3 N/A Size 26 Figure 2004 Replacement N/A Disk Assy.
Corp 1612JMMNTY Valve W.O. # 659252 7.
8.
Description of Work: Class 1 Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic IlI Normal Operating Pressure I X I Other Visual Pressure 1035 asI Test Temp. _155 Deg. F Remarks: The old Main Steam Isolation Valve (MSIV) main disk assembly removed from MSIV 1B21-F028D (Appilcable Manufacturer's Data Report to be Attached )
was refurbished with a new style Stem/Stem-DIsk Assembly with SN# 76366-3 under work order # 659252. This 9.
niwv refurbished disk assemblv was Installed and tested In MSIV2B21-F028D under Work Order# 515539.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement of the ASME Code,Section XI.
(repair or repla Type Code Symbol Stamp NONE
~conforms to the rules cement)
Criiaeof Au No Segneorizado Signedf N/A
_Expiration Date N/A ISI Coordinator Date
? it
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Ilinols - and employed by The Hartford Steam Boiler Inso. & Ins. Co. of Connecticut have Inspected the components described in this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any -manner for any personal Injury or property damage or a loss of any kind arl rom or connected with this spectlon.
API.0 ommiss ions IL 1927 lnspectorfignature National Board, State, Province, and Endorsements Date_
205
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl
- 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way, Kenneth Sauare. PA., 19348 Date 05123105 Address
- 2.
Plant LaSalle Countv Nuclear Station Sheet 1
of I
Unit 2
W.O. #515542 Repair Organization, P.O. No., Job No., etc.
Name 2601 N. 21" Rd. Marseilles. II. 61341 Address 3.
Work Performed by_
IrI -
+IIPTIA-So C Mechanical Maintenance (Name)
Mechanical Maintenance (Address) s~oe mmURS Susn CA-Type Code Symbol Stamp NIA Authorization No.
5.
IUVIR111IIL0d&UH I UI QYILVI II IffK11 iRi0lil
.~LVdI I (a) Applicable Construction Code Sect 111.19 71 Edition W'71 Addenda, Code Cases NO (b)
Applicable Edition of Section XI Utilized for Repairs or Replacements-19 89, No Ad, Code Cases NO
- 6.
Identification of Com onents Repalred or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
MSIV Stem/Stem-Rockwell N/A 2B21-FO28B Replaced N/A Disk Assy.
Corp MSIV Stem/Stem-Flowserve 76366-5 N/A Size 26 Figure 2004 Replacement N/A Disk Assy.
Corp 1612JMMNTY Valve W.O. # 659253 8.
9.
Description of Work: Class I Replacement. * = Per N-5 Code Data Renort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure l X I Other Visual Pressure 1035 osi Test Temp. _155 Deg. F Remarks: The old Main Steam Isolation Valve WMSIV) main disk assembly removed from MSIV 1 B21.F028C (Applicable Manufacturer's Data Report to be Attached )
was refurbished with a new style Stem/Stem-Disk Assembly with SN# 76366-5 under work order # 659253. This newly refurbished disk assembly was Installed and tested In MSIV 2B21 -F028B under Work Order # 515542.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
N/A
-Expiration Date NIA ISI Coonrdinator Date A f 0le 'Z
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Ilinols and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arl g from or connected with th Inspection.
AO" Commissions IL 1927 InspersSnature National Board, State, Province, and Endorsements Date 0
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA., 19348 Address Plant LaSalle County Nuclear Station Date 04118105 Sheet 1
of I
Unit 2 2.
Name 2601 N. 211" Rd. Marseilles, II. 61341 (Address)
W.O. # 544418 Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp NIA Aiuthnrizatinn N.
NIA 3.
Work Performed blV Uaehannc.l antn.ance-(Name)
Mechanical Maintenance (Address)
Expiration Date_
NIA 4.
S.
Identification of System I(RD) Control Rod Drive (a) Applicable Construction Code.ASME Sect liI 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section XI Utilized for Repairs or Replacements-1989, No Ad, Code Cases None Identlflcation of ComnDonents Renalred or Renlatced. and Renlacement Comnonents 6.
~-*~-*--~-~-
--*-r*---.--*r*--
%r--e---r---.
--- ~----...-
r-*----.-_
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
7565A N/A 18-03 Replaced NIA CRD Assembly G.E.
7467 N/A Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova NIA 18-03 Replaced NIA (8) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 102444 2004 Replacement N/A
_ _ _R 139 1
7.
8.
9.
Description of Work Class I Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osi Test Temp.
155 Deg. F Remarks CRD SN# 7467 was refurbished with documentation provided under Quality Recelit # 105348 and (Appilcable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 7565A under work order #544418.
- = Replacement CRD Code of Construction Is ASME Section 111.1971 Ed. S73 & W75 Ad. Reconciled to the original per PTEs PTE 88-13 & PTE 88-396 on file at LaSalle Statlon. Replacement Canscrew Code of Construction Is ASME Section 1i1. Class 1.1986 Ed. No Ad. Reconciled to the orlalnal Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
N/A Expiration Date NIA Signed g
6 ISI Coordinator Date
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable 1n any manner for any personal Injury or property damage or a loss of any kind arisiW from or connected with this Inspection.
kl24 1
Commissions IL 1927 Inspect Signature National Board, State, Province, and Endorsements Date 2
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
2.
Owner Exelon Generation Comoanv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA., 19348 Address Plant LaSalle County Nuclear Station Date 04118105 QSIWUL
l
%# I I
Sheet I
of 1
Unit 2 W.O. # 544419 Name 2601 N. 21'" Rd. Marseilles. II. 61341 (Address) 3.
Wnl-A 0_rfnnnA I-
&A-1-1-1a L2.1.4 ------
Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp NIA Authorization No.
NIA Expiration Date N/A I..I,' -
CI I1II y
f l
mal*0*,.0a*Ua (Name)
Mechanical Maintenance 4.
5.
A (Address)
Identification of System (RD) Control Rod Drive (a) Applicable Construction Code._ASME Sect III 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989, No Ad, Code Cases None Identiflcrtlnn of Comnonnntq Renalred or Rpnlaepd-and Reniacemennt Comnonnentts Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
7906 N/A 50-47 Replaced N/A CRD Assembly G.E.
6726 N/A Receipt # 105348 2005 Replacement N/A (8) CRD Capscrews Nova N/A 50-47 Replaced N/A (8) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 102444 2004 Replacement N/A
_ _ _ _ _ _ _ _R I 3 9 8.
9.
Description of Work Class I Replacement * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure _1035 psi Test Temp.
155 Deg. F Remarks CRD SN# 6726 was refurbished with documentation provided under Quality Recelit # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a reolacement for SN# 7906 under work order # 544419.
= Replacement CRD Code of Construction Is ASME Section 111.1971 Ed. S73 & W75 Ad. Reconciled to the original per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section 1I1. Class 1. 1986 Ed. No Ad. Reconciled to the orlainal Code of Construction ner PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authori ation No.
N/A Expiration Date NIA Signed 6
ISI Coordinator Date
- 2005 Owner or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to I
L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In -accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 Insp or's Signature National Board, State, Province, and Endorsements Date
- 'AZ 2005 KJ
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of. ASME Code Section XI 1.
2.
Owner Exelon Generation Companv(EGC) LLC (Name) 200 Exelon Way, Kenneth Square. PA.. 19348 Address Plant LaSalle County Nuclear Station Name 2601 N. 21" Rd. Marseilles. II. 61341 (Address)
Dafe n4ijRin8/
B.9
. rev_
Sheet I
of I
Unit 2 W.0Q
- 54œ420 3.
4.
5.
Work Performed tTV Mechanical Mnlnfoannnr Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
NIA Expiration Date NIA (Name)
Mechanical Maintenance (Address)
Identification of System (RD) Control Rod Drive (a) Applicable Construction Code.ASME Sect ill 19 71 Edition No Addenda, Code Cases 1361-1. & 1361.2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989, No Ad, Code Cases None IdAntifcation of Comnonents Renalred or Renlaced. and Renlacement Comnonents 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.-
Replacement (Yes or No)
CRD Assembly G.E.
8147 NIA 54-43 Replaced NIA CRD Assembly G.E.
7538 NIA Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova N/A 54-43 Replaced NIA (8) CRD Capscrews Nova Ht. Trace Code NIA Receipt # 102444 2004 Replacement NIA
_RI139 I
I 7.
8.
9.
Description of Work Class I Replacement, * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I
Pneumatic II Normal Operating Pressure I X I Other Visual Pressure 1035 psi TestTemp.
155 Deg.F Remarks CRD SN# 7538 was refurbished with documentation provided under Quality Recelpt # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 8147 underwork order# 544420. ** = Reolacement CRD Code of Construction Is ASME Section 111.1971 Ed. S73 & W75 Ad. Reconciled to the orialnal per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section lii. Class 1. 1986 Ed. No Ad. Reconciled to the orialnal Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE(
r Certificate of Authorization No.
NIA Expiration Date NIA Signed 6
a ISI Coordinator Date 74.-oe'L2 0?_
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 andstate thattothe best of my knowledge and belief, theOwner hasperformed examinationsand taken corrective measures described Inthis Owner'sReport In accordance with the requirements ofthe ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner forany personal Injury or property damage or a loss of any kind arisin from or connected with this Inspection.
//
2 %
Commissions IL 1927 Inspect VI Signature 5-R-2005 National Board, State, Province, and Endorsements Date_
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
2.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA., 19348 Address Plant LaSalle County Nuclear Station Name 2601 N. 21" Rd. Marseilles. II. 61341 (Address)
Date Sheet 1
of 1
Unit 2 W.O. # 544421 Repair Organization, P.O. No., Job No., etc.
05105/05 3.
Work Performed by_
Mechanical Maintenance (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp NIA Authorization No.
5.
Identification of System (RD) Control Rod Drive (a) Applicable Construction Code ASME Sect M 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Sectlon XI Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None Identification of Components Repaired or Renlaced. and Replacement Comronents 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
9246 N/A 30-19 Replaced N/A CRD Assembly G.E.
A936 N/A Receipt # 105348 2005 Replacement N/A (8) CRD Capscrews Nova N/A 30-19 Replaced N/A (8) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 102444 2004 Replacement N/A
_ _ _ _ _ _R I 39 7.
8.
9.
Description of Work Class I Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure -1035 osl Test Temp.
155 Deg. F Remarks CRD SN# A936 was refurbished with documentation provided under Quality Recelpt # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 9246 under work order # 544421. ** = Replacement CRD Code of Construction Is ASME Section 111.1971 Ed. S73 & W75 Ad. Reconciled to the orlainal per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section iII. Class 1. 1986 Ed. No Ad. Reconciled to the orialnal Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of AuthorliNon No.
NIA Expiration Date NIA Slaned C..d[
ISI Coordinator Date At
/o
. 2005 Owner or Owner's Designee, Title
.01 -
CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have inspected the components described in this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report in accordance with the requirements ofthe ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner foranypersonal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 Inspe r's Signature National Board, State, Province, and Endorsements Date
_ Pi
/-
2005
FORM NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI 1.
Owner Exelon Generation Company (EGC) LLC Drlte fml2nri
.x:
v.71uvlwv (Name) 200 Exelon Way. Kennett Square. PA.. 19348 Sheet 1
of I
(Address)
Plant LaSalle County Station 2.
Unit 2 554320 (Name) 2601 N. 2 1", Rd. Marseilles. II. 61341 Repair Organization, P.O. No., Job No., etc.
3.
(Address)
Work Performed by Mechanical Maintenance (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A 4.
5.
Identification of System
' (RR) Reactor Recirculation (a) Applicable Construction Code Sect ill 1971 Edition No. Addenda, Code Cases None (b) Applicable Edition of Section XI Utilized for Repairs or Replacements-1989, No Ad, Code Cases N-416-2
- 6.
Identification of Com onents Repaired or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l CRN Other Year Repaired ASME Code Component Mfr.
No.
Bd.
No.
Identi-Built
- Replaced, Stamped No.
Fication Replacement (Yes or No)
Gate Valve Body Atwood NIA N/A 2B333F067B1 Repaired NIA Morill
- 7.
Description of Work Class 1 Repair. Repaired valve body by machining and welding.
- 8.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 psi Test Temp. 155 Deg. F
- 9.
Remarks * = Per Orialnal N-5 Code Data Report on file at LaSalle County Station.
(Applicable Manufacturer's Data Report to be Attached)
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Repair conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
N/A Expiration Date NIA Signed 6
ISI Coordinator Date May 13.
20 05 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boller Inso. & Ins. Co. Of Hartford, CT. have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, Neither the Inspector nor his employer shall be liable In any manner foranypersonal Injury or property damage or a loss of any kind ar connected with this Inspection.
Z XZ iX'7.fSt 4 1h = Commissions IL 1927 In tor's Signature 4-/?-20 05 National Board, State, Province, and Endorsements Date_
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi
,1.
Owner Exelon Generation Company (EGCI LLC (Name) 200 Exelon Way. Kenneth Square. PA., 19348 Address
- 2.
Plant LaSalle County Nuclear Station Name 2601 N. 21" Rd. Marseilles. II. 61341 Address Date 02124/05 Sheet 1
of I
Unit 2
W.n #5A41
- 3.
Work Performed by.
Mechanical Maintenance Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp NIA Authorization No.
NIA Expiration Date NIA (Name)
Mechanical Maintenance (Address) 4.
5.
Identification of System (MS) Main Steam (a) I Applicable Construction Code Sect Ill 19 71 Edition W72 Addenda, Code Cases 1516-1 & 1567 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19 89, No Ad. Code Cases N-416-2 IdentIfication of Comnonpnts Renalred or Renlaced-and Ranlacnment Comnonpnth 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No) 3" Flex Wedge Anchor NIA 2B21-F019 Replaced N/A Gate Valve Dariing 3" Double Disc Velan 052004-2 N/A 2B21-F019 2005 Replacement N/A Gate Valve 7.
8.
Description of Work Class 1 Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 asl Test Temp. 155 Deg. F Remarks Replaced Inboard Main Steam Flex Wedge Gate valve with a Double Disc Gate valve.
(Applicable Manufacturer's Data Report to be Attached )
9.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement of the ASME Code, Section Xl.
(repair or repla Type Code Symbol Stamp NONE cement) conforms to the rules Certificate of Au rization No.
S lan eell BO1A Rvnrktxn 6t MP%
Apli OUL01 I watu N/A cr-ISI Coordinator Date May 13 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois -and employed by The Hartford Steam Boller lnsp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
/
Co~mmissions IL 1927 InV ctor's Signture National Board, State, Province, and Endorsements Date
/6/
2005
I-i IPAGE 3-
- 052004 FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES
- As Required by the Provisions of the ASM E Code,Section III, Division 1 Pg. 1 of 2
/
- 1. Manufactured and certified by VELAN INC. 550 McArthurSt.. Montreal Quebec CANADA H4T1iX8 (nane and address of N Certificatc Holder)
Zl eaIIII
- 2. Manufactured for zxELcO cNRATIG Co.LLC.
4459 N7. Ohrmwt Gitemeh D flET -L" 6101b U1 (name and address of purchaser)
- 3.
Location of installation Commonmsath *dison La Salle COUntY STNH-Uidts XHarafillsX1.61341-9757 USA (name and address)
- 4. ModelNo.,SerlesNo.,orType: B10-7054P-O4PSDraving P012-421440-NOI Rev 8l CRN NIA
- 5. ASME Code,Section III, Division 1: 1971 WINTER-1972 1
1516-1 L 1567 (edhion)
(addenda date)
(class)
(Code Cas no.)
- 6. Pump or valve: mmssug S8AL 900o caLTz VLV Nominal inlet size 3"
Outlet size 3"
(in.)
(in.)
- 7. Hat"1.: Body SA-182 F5 Bonnet SA-182 F5 Wedge SA-182 F6A CL2 GASXET 1RET. SA-182 FOA CL2 I
i '
I (a)
Cert.
Holder's SerialNo.
- 052004-1
- 052004-2 Cb)
Nat'l Board No.
N/A N/A HEAT / TESr LOT:
CASRMT AZ?.8/N
_HEAT/Test Lot (c)
Body Serial No.
644 646 52070 / lOT 7162 Cd)
Bonnet Serial No.
16753 16765 G9253 / 68829 (e)
Wedge Serial No.
6837 6838 L82431 68833
- 2FML-1 S 2 L8243 / 68833 SEATS S/H:
SEATS S/N:-
SEAT MATO'L.:-
HAT/Test Lot:
_G9253 7 50125 1
SN: 052004-2) 81399-S1397 (VLV SN: 052004-1)
Z j.%
I PM=I
- Suppk~emental in~cmtion In form oflKstssketches ordrswings maybe wed provided (1) size isS 12x l.(2) information in items I through4 onthisDtaRepott is included on each sheet, (3) each sheet Is numbered and the number of sheets Is recorded at the top of this form.
(12a3a) lb'is fionn (E00037) may 'ee obtained fiom thie Order Dept. ASME, 22 LAW DRIV< BOX 2300 Feirfleld, NJ 07007 2300.
B A l/Ad A N
- B AVANVUAN11
105 749 FORM NPV-1 (Back -
Pg. 2 of 2 )PAGE-4 Certificate Holder's Serial No.# 052 0 0 4 esign conditions 1250 psi 75
- F or valve pressure class 900#
(1)
- - -.(pressure)
.(temperature) old working pressure 210-'s_________
hydrostatic test Shell:
3250 -
sig.. Disc differential test pressure..
NMA psi bemarks:* MATERIAL SPEC. StIPPLED IS TO ASME SEC.II PART-A CODE EDITION 1995 ADDENDA: 1996.::
CERTIFICATE OF DESIGN ign Specification certified by William B.Hilton P.E State Illinois, USA Reg.no.
062-043892 ign'report certified by S. ISBITSKY RE State QUECANADA Reg. no.
- 22115 CERTIFICATE OF COMPLIANCE i certify that the statements made In this report are correct and that this pump or valve conforms to the rules for ristruction of the ASME Code,Section III, Division 1.
Certificate of Authorization No.
N2797-2 IN)
Expires APRIL 20, 20'07 te 3 February 2005 Name VELAN INC.
Signed (N Certificate Holder).
Authorized representative)
CERTIFICATE OF INSPECTION he undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors I the State or Province of QUEBEC and employed hy-REGIE DU BATWMENT of QUEBEC ye inspected the pump, or valve, described in this Data Report on 6re2 p,
/r c
I i state that to the best of my know ledge and belief, the Certificate Holder ha&contructed this pump, or valve, in
- ordance with the ASME Code, Section ill, Division 1.
signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, ncerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall liable in any manner for a injury or property damage or a loss of any kind arising from or connected th this inspe ion.
J.P.FACHINETl QC# 13813 ite O
'ig Commissions
(-
(Aut or/zed Inspector)
(Nat'l. Bd. (=cl. EndorsementsJi MseorP'k.and no.)
For manually operated values only.
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Sauare, PA.. 19348 Date 02/24l/0 Own,.
w_. __.
vz Address
- 2.
Plant LaSalle County Nuclear Station Name 2601 N. 2 1" Rd. Marseilles, II. 61341 Address Sheet I
of 1
Unit 2
Wfl N 554322
'2 AW _L, DA-ba L...t
- i...
- ,t----
Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A
.J.f Tvul,renorm IUIII1duy IenWI.nIcd1d WIlm (Name)
Mechanical Maintenance (Address) 4.
5.
6.
Identification of System (MS) Main Steam (a) I Appiicable Construction Code Sect III 19 71 Edition W72 Addenda, Code Cases 1516-1 & 1567 (b)
Appilcable Edition of Section Xi Utilized for Repairs or Replacements-19 89, No Ad. Code Cases N-416-2 Identification of Comoonents Reoalred or Reolaced. and Replacement Comnonents Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No) 3" Flex Wedge Anchor N/A 2B21-F016 Replaced N/A Gate Valve Darling 3" Double Disc Velan 052004-1 N/A 2821-F016 2005 Replacement N/A Gate Valve 3" Sch. 80 Pipe B.F. Shaw N/A 2MS14A-3" Replaced N/A 3" Sch. 80 Pipe Consolidated Ht. # 14239 N/A 2MS14A-3" 2005 Replacement N/A Power Supply 7.
8.
Description of Work Class I Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osl Test Temp. 155 Deg. F Remarks Replaced Inboard Main Steam Flex Wedge Gate valve with a Double Disc Gate valve and Pipe PuP niece.
9.
(Applicable Manufacturer's Data Report to be Attached )
Anntlirahlp Cotnor4lnn CodeMr fnr nnn Is AqMF Sect. III 17A PEd Un Arddendaa CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Reolacement of the ASME Code,Section XI.
(repair or repla Type Code Symbol Stamp NONE conforms to the rules cement)
Certificate of Au orization No.
N/A Expiration Date Sinned l C
eZ:
/C IAI C
o ordinator D
ate N/A Mav13 2005 Owner or Owner's Designee, Title An._ _
CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boiler Insp. & Ins. Co. of Connecticut have inspected the components described In this Owner's Report during the period L2R09 to L2R1O10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arlsn from or connected with this Ins ection.
/o
&.1Commisslons IL 1927 Inspecies Signature National Board, State, Province, and Endorsements Date 5//
2005:
III
- EI PGE3-- #052004 FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUM PS OR VALVES
- As Required by the Provisions of the ASME Code,Section III, Division I Pg. 1 of 2
- 1. Manufactured and certified by VELAN INC. 550McArthurSt.. Montreal Quebec CANADA 14T I1X8 (name and address of N Certificate Holder)
) o?l/O5
- 2. Manufactured for zxO CGE:RATm Co.'LLC. 4450 N-.Cerzwi Chch n
DYTtZU i Gl U3 (name and address ofpiurhaser)
- 3. Location of installation Comuonwealth rdison La Salle CountX STN-Units MArasallos,Xl.61341-9757 USA (name and address)
- 4. ModelNo., Ser1es No.,orType: BIO-7054P-04PS Drawing P012-421440-NOI Rev B -cEN N/A
- 5.
AS)E Code,Section III, Division 1: 1971 WINTER-1972 1
1516-1 & 1567 (editon)
(addenda dae)
(class)
(Code Cas no.)
- 6. Pump or valve:
rmssmtz 8EAL 900# Can: VLV Nominal inlet size 3" Outlet size 3"
fln.)
(an)
- 7. Hat' I.:
Body SA4182 F5 Bonnet SA-182 FS Wedge SA-182 F6A CL2 GASKET RET. SA-182 F6A CL2 (a)
Cert.
Holder' a SerialNo.
(b)
Nat'l Board No.
(c)
Body Serial No.
(d)
Bonnet Serial No.
Ce)
Wedge Serial No.
KI 1
- 052004-1
- 052004-2 N/A N/A HEATr/ TEST Lo 644 646 52075 / lor 7162 16753 16765 G9253 / 68829 6837 6838 L8243/ 68833 CASKET RZT.8/N HEAT/Test Lot 2F1L-1 S 2 L8243 / 68833 SEATS S/N:
SEATS S/N:
SEAT MAT'L.:-
HEAT/Test Lot:,
.It-81399-81397 CVLV SN: 052004-1)
I1398-81400 CVLV SN: 052004-2)
SA-182 F5
_G9253 / 50125
- Supplementallnfonnation infbm oftsts~sketchordrwit mybe wed provided (I) site is S 1,(2) infoaion Intms I thDg onthiDftRcpod is included on each sheet, (3) each sheet Is numbered and the number of sheets s recorded at the top of this form.
(12183)
This form (E00037) may be obtained from the Order Dept, ASME, 22 LAW DRIVE< BOX 2300 Fairfield, NJ 07007-2300.
i-f~
BAvAvNd VN
-S tB AVANVUAN11
- 1 105 749 -- =
FORM NPV-1 (Back Pg. 2 of 2 )PAGE-4 CeFtificate Holder's Serial No.
- 0 52 0 04
- esign conditions 1250
'psi 5i5
- F or valve pressure class 900#
(1)
(pressure):
(temperature) old workingpressure 2160 psiatl100F.
)ydrostatic test Shell:
3250 psig;. Disc differential test pressure..
CERTIFICATE OF DESIGN ign Specification certified by William B.Hilton P.E State Illinois, USA Reg.no.
062-043892 ign report certified by S. ISBITSKY P.E State QUECANADA Reg. no.
- 22115 CERTIFICATE OF COMPLIANCE certify that the statements made in this report are correct and that this pump or valve conforms to the rules for instruction of the ASME Code,Section III, Division 1.
Certificate of Authorization No.
N2797-2 (N)
Expires APRIL 20, 2007 ie 3 Februarv 2005 Name VELAN INC.
Signed
(-t (N Certificate Holder) authorized representative)
CERTIFICATE OF INSPECTION he undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors I the State or Province of QUEBEC and employed b EGIE DU BATMENT of QUEBEC ve inspected the pump, or valve, described in this Data Report on 6
l 4
&&2-s I
i state that to the best of my knowledge and belief, the Certificate Holder hascon tructed this pump, or valve, in
,ordance with the ASME Code, Section 1II, Division 1.
signing this certificate, neither the inspector.nor his employer makes any warranty, expressed or implied, ncerning the component described In this Data Report. Furthermore, neither the inspector nor his employer shall liable in any manner for a injury or property damage or a loss of any kind arising from or connected th this inspecion.
/J.P.FACHINETTI QC# 13813 Ite O 4
/
0isig Commissions
(
oen
- r.
- i. sm An sl a ear
.a
)
/
d(Authnorized Inspector)
(Nat' l. lBd. (Incl. &-doiiie-mel ;
sane or p7Ko~and no.)
For manually operated vales only.
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi
- 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Wa.. Kenneth Suare. PA.. 19348 Date 05/06105 Address LaSalle County Nuclear Station
- 2.
Plant Sheet 1
of 2
Unit 2
W.O. #585833 Repair Organization, P.O. No., Job No., etc.
Name 2601 N. 213" Rd. Marseilles. II. 61341 Address 3.
Work Performed h-Mn,.bnleal Mbnlnt.,n,.n (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp NIA Authorization No.
N/A Expiration Date NIA 4.
5.
Identification of System (MS) Main Steam (a) Applicable Construction Code Sect iII 19 71 Edition S172 Addenda, Code Cases 1567 and 1711 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19 89, No Ad, Code Cases N496-1 Idelnfificatinn nf Cnmnnnent Ranatrpe4 nr Renlanped and RPn1a.cement Eonmnnnsnfc Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Safety Relief Valve AG N63790-00-0005 NIA 21B21-F013C Replaced NIA Crosby Safety Relief Valve AG N63790-0.0106 NIA 2B21-F013C Replacement NIA Crosby or N63790 Receipt #101593 0106 (Modlfied)**__
Disc Insert N93185-46-0171 N/A Replaced NIA Disc insert AG N97499-45-0117 NIA Receipt# 101593 2004 Replacement N/A Crosby 7.
8.
Description of Work Class I Repair & Renlacement. * = Per N-5 Code Data Reoort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osI Test Temp. 155 Deg. F Remarks Valve SN# N63790-05-0106 was refurbished at Wvle Labs with documentation provided under Quality (Applicable Manufacturer's Data Report to be Attached)
Recelot # 101593 and installed as a reolacement for SN# N63790-00-0005 under work order # 585833. For the 9.
remainder of the Renalred. Renlaced and Reolacement Items. see Form NIS-2 Sunolemental Sheet on Paaes 2 of 2.
- Replacement SRV Serial No. was modified due to the Installation of a new flexi-disc seat design.
CERTIFICATION OF COMPLIANCE We certify that the statements made in the report are correct and these Revalr and Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate f Io No Signed NIA
-Expiration Date NIA ISI Coordinator Date
/% Ha
/E)
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Ililnois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period 12R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind from or connected with this Inspection.
Commissions IL 1927 Inspelor's Signature NationalBoard, State, Province, and Endorsements Date 2005
FORM NIS-2 SUPPLEMENTAL SHEET
- 1.
Owner:
Exelon Generation Company (EGC) LLC Sheet.
200 Exelon Way, Kenneth Square, Date PA., 19348 Unit
- 2.
Plant:
LaSalle County Station 2601 N. 21st. Rd.
Marseilles, Illinois 61341
- 3.
Work Performed by: Mechanical Maint.
Type C Name Autho Mechanical Maintenance Fynira 2
of 2
05/06105 2
W.O. # 585833 P. O. No., WR No., etc.
Code Symbol Stamp N/A rization No.
NIA ition Date N/A
-or..
4.
5a.
5b.
6.
Address Identification of System MS (Main Steam)
Applicable Construction Code 71 Edition S72 Addenda Applicable Edition of Section Xl utilized 89 Edition None Addenda Identification of Components Repaired or Replaced and Replacement Components.
Name of Name of Manufacturer National Other Year
- Repaired, ASME Component Manufacturer Serial No.
Board Identification Built Replaced Code No.
or Stamped Replacement (Yes or No)
Valve Body AG Crosby N93183 NIA Receipt Repaired NIA 0030 101593 (1) Heli-Coil AG Crosby N97823-0050 N/A Receipt #
2002 Repaired NIA Insert 101593 (Outlet)
(2) Inlet NOVA NIA Replaced NIA Tension Nuts (2) Inlet NOVA Ht. Code NIA Receipt #
2002 Replacement NIA Tension D170 78197 Nuts
1 0 1 5 9 3 Q.C.434A Sheet I of 2 FORM NVR-1 REPORT OF REPAIR 53X ODIFICATION F, OR REPLACEMENT F -
OF NUCLEAR PRESSURE RELIEF DEVICES
- 1. Work performed by ANDERSON GREENWOOD CROSBY 00076601 (name of organization)
(P.O. no., job no., etc.)
43 Kendrick St., Wrentham, MA 02093 (address)
- 2. Work performed for EXELON CORPORATION,LASALLE STATIONMARSEILLES,IL.
(name and address)
- 3. Owner EXELON CORPORATION,LASALLE STATION,MARSEILLES,IL.
(name)
(address)
- 4. Name, address and identification of nuclear power plant EXELON CORPORATIONLASALLE STATION, MARSEILLES, IL.
- 5. a.
Repaired pressure relief device MAIN STEAM SAFETY RELIEF VALVE'
- b.
Name of manufacturer ANDERSON GREENWOOD CROSBY
- c.
Identifying nos.
HB-65-BP N63790-05-0106 STEAM 6 R 10 1980 (type)
(mfr's serial no.)
.(Nat'l Bd. No.)
(service)
(size)
(year built)
- d.
Construction Code ASME III 1971 S1972 1567,1711 1
(name/section/division)
(edition)
(addenda)
(Code Case(s))
(Code Class)
- 6. ASME Code Section XI applicable for Inservice inspection 1989 NO (edition)
(addenda)
(Code Case(s))
- 7. ASME Code Section XI used for repairs, modifications, or replacements 1989 NO (edition)
(addenda)
(Code Case(s))
- 8. Construction Code used for repairs, modifications, or replacements. 1971 S1972 1567,1711 (edition)
(addenda)
(Code Case(s))
- 9. Design responsibilities ANDERSON GREENWOOD CROSBY
- 10. Opening pressure 1175 PSIG Blowdown (if applicable) -3
% Set pressure and blowdown adjustment made at WYLE LABORATORIES,HUNTSVILLE,AL.
.using STEAM (location)
(test medium)
- 11. Description of work: (include name and identifying number of replacement parts)
FLEXIDISC MODIFICATION, REPAIR AND TESTING MADE AT WYLE LABORATORIES, HUNTSVILLEAL. USING STEAM.
- 12. Remarks THE DISC INSERT WAS REPLACED AND VARIOUS PARTS MODIFIED AS PART OF THE FLEXIDISC MODIFICATION.
10:
- Certificate Holder's Serial Nos. N63790-05-0106 1593
. Q.C.434A.
Sheet 2 of 2 Form NVR-1 (Back)
-CERTIFICATE OF COMPLANLE 1, -- 6 ib B r-n certify that the statements made in this report are correct and the repair, modification Ox replacement of the pressure relief device described above conforms to Section XI of the ASME Code and the National Board Inspection Code 'VRW and "NR' rules.
National Board Certificate of Authorization No.
75 to 84 to use the 'VR' stamp expires JAN. 14,2007 National Board Certificate of Authorization No.
68 to use the 'NR' stamp expires DEC.11 2006 Date 7_.___
,lSigned Anderson Greenwood/Crosby
- 7.
i=
/A QA MGR.
(name of repair organization)
(authorized representative)
(title)
I
..1.
l-..CERTIFICATE OF INSPECTIOI K
I, LgLS i
2 holding a valid commission issued by The National Board of Boiler and Pressure Vessel Inspect competency issued by the jurisdiction of MASSACHUSETTS and employed by HSB-CT of' HARTFORD - CT.
have inspected the repair, modification or replacement described in this report on
-.-4,c;z7/and state that to the
-best of my knowledge and belief, this repair, modification or replacement has been completed in accordance with Section XI of the ASME Codeand the National Board Inspection Code 'VRi"and 'NR' rules.
By signing this certificate, neither the undersigned nor my employer makes any warranty, expressed or implied, concerning
.the repair, modification or replacement described in this report. Furthermore, neither the undersigned nor my employer shall be liable in any manner for any personal injury, property damage or loss of any kind arising from or connected with this Inspection.
Date dt¢L Signed Commissions
- MA1420 A, N, I (Inspector)
(Nat'l. Bd. (incl. endorsements), and jurisdiction, and nO.)
.Jan. 8. 2005 10:26AM No.1163 P. 2/5 Q.C.-392 Sheet 1 of 2 FO1RM N-2 CERIMCATE HOLDERS' DATA REFORTFOA IDESMCAL NUJCLEAR PAP.TS ANDAPPURTEANACES*
As renuired by the Provisions of the ASME Code, Section I1I, Division 1 - Not to Exceed One Day's Production 1
- 1. Manufactured and ceitified by 2 Manufactured for Anderson Greenwood Crosby, 43 Kendrick St., Wrentham, MA 02093 (Name and Address of N Certificate Holder)
EXELON GENERATION (Name and Addres$ of Purchaser or Owner)
LASALLE STATION 3
Location of Installation (Name and Address)
- 4. Type DS-A-63790-2 REV.-
. ASME SA637 GR 718 185,000 24_
004 (drawing no.)
(mat'l. spec. no.)
(tensile strength)
(CRN)
(year built)
- 5. ASME Code,Section III, Division 1.
1971 SUMMER 1972 1
(edition)
(addenda date)
(class)
(Code Case No.)
- 6. Fabncated in accordance with Const. Spec. (Div. 2 only)
Revision Date (no.)
- 7. Remarks 8 Nom thickness (in.)
Min. design thickness (in.)
Dia. ID (ft & in.)
Length overall (ft & in.)
9 When applicable, Certificate Holders' data reports are attached for each item of this report.
Natona Part or Appurtenance Serial Numbes (1) N97499-45-0112 (2) N 97~499-45-~0113 (3) N97499-459-014 (4) N917499-45-0115 (4) N97499-45-0116 (6)3N97499-45^0117 1 (7)
(9)
(10)
(11)
(12)
(13)
(14)
(1)
(16)
(17)
(18)
(19)
(2 0
(21)
(22)
(23)
(24)
(25)
National Board INo in Numerical Order
.I -
Part or Appurtenance Serial Number (2
(2 (2
(Z (35 (3
t39 (40 (13 (432 (3e (34 (4C (41 (42 (43 I(44 (46' (471 (48)
(49)
(50)
.6) 8)
9),
1)
Z) 3)
4) 7)
1)
National Board No.
in Numerical Order
)
I.
" Design pressure psi.
Temp.
F Hydro. test pressure 2370 psig at temp. 70 o
(when applicable)
A ttn 1 inforinidon to the tm oara. ikeiches. c drwu' mn e Wed provzded (1) slzc 1S s-ln2 x ii. (2) Iflto.lrtiofL tn Itcxs 2 ar 3 on his DatrkReport t3 included on e*cb st:
(3) each sheet Is ncmbered Wd the nubet of shteu Is recordod *t e tog of this form This ormi (EQOOS4) may be obun)ed frou the Ordec Dept.. A..SME, 22 Low Drive. Box 2300. FAirrield. NJ 07007-2300
.Jan. 8. 2005 10:26AM No.1163 P. 3/5
/V 7 7 y 7 9 40' (, "
Form N-2 (Back)
Q.C.-392 Sheet 2 of 2
-Certificate Iolder's Serial No. N97499-45-0112 thru 0117 CERZIFLTE OF COMPLEANCi We certify that the statements made in this report are correct and that this (these)
Disc inserts conforms to the rules of construction of the ASME Code, Section m, Division 1.
NPT Certificate of Authonzation No.
N-1877 Expires Sep. 30, 2004 Anderson Greenwood Crosby Date 5
zB
[CO'f Signed Wrentham, MA by (NPT Certificate Holder)
(Authorized Representativ CERTIFICATE QE INSPECTION JI I, the undersigned, holding a valid commrrsslon issued by the National 13oard of Boller and Pressure Vessel inspectors and the State erefsovkoof
,A1-i#
and employed by ABS Group Inc.
of Houstoin Texas have insected thesc items described in this Data Report on
_ 6
_ 200oj and state that to the best of m knowledge and beief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code,Section III, DivisIon 1. Each part listed has been authorized for stamping on the date shown above.
By igning this certificate, neither the InsPector nor his employer malkes any warranty, expresed or implied, concerning the equipment described in this Data Report. Furthermore, neither the Inspector nor his employer shall be liable mu any manner for any personal injury or property damage or loss of any kind arlsmig from or connected -Aith this spection.
Date Sigaec
_ ~
6!,
20 r
d l-6 v 10 Gt (Authorized Inspector)
Commissions A,4
/I,&cb-d (Nat'l. Bd. (mc1. endorsemaets) and state or proy. and no )
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi
- 1.
Owner Exelon Generation Comoanv(EGC) LLC (Name) 200 Exelon Way, Kenneth Square. PA.. 19348 Address
- 2.
Plant LaSalle CountV Nuclear Station Name 2601 N. 21' Rd. Marseilles. II. 61341 Address Date 05106105 Sheet 1
of I
Unit 2
W.O. #585834 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed by-Mechanical Maintenance (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp NIA Authorization No.
5.
Identification of System (MS) Main Steam (a) Applicable Construction Code Sect il 19 71 Edition S172 Addenda, Code Cases 1567 and 1711 (b)
Appilcable Edition of Section Xl Utilized for Repairs or Replacements-19_89_,
No Ad, Code Cases NO Identification of Comnonents Ranalrad or Replaced-and Renlacement Cnmpinnnts 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Bulit Replaced, or Stamped No.
Replacement (Yes or No)
Safety Relief Valve AG N63790-00-0001 NIA 2B21-F013U Replaced NIA C rosby Safety Relief Valve AG N63790-00-0002 NIA 2B21-FO13U Replacement NIA Crosby or N63790 Receipt# 101593 0002 (Modifled)_
Disc Insert N93185-32-0002 N/A Replaced NIA Disc Insert AG N97499-45-0112 N/A Receipt# 101593 2004 Replacement N/A C rosby 7.
8.
Description of Work Class i ReoaIr & Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I _ I Normal Operating Pressure I X I Other Visual Pressure 1035 osi Test Temp.-155 Deg. F Remarks Valve SN# N63790-05-0002 was refurbished at Wvle Labs with documentation erovided under Quality (Applicable Manufacturers Data Report to be Attached )
Receipt # 101593 and Installed as a replacement for SN# N63790-00-0001 under work order # 585834. All bolting 9.
4 A
%rr-.f nA n
-^A 11 r-IOt pa
-A 1,,,MI.a.c Were,cueaI.
. visua, CaoIIuI n V I was P on au tasn
,,,ic
,JtItnu.
- ReIlacement SRV Serial No. was modified due to the installatlon of a new fiexl-disc seat des In.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Mhorization No.
Slaned 0
N/A
_Expiration Date NIA IS[ Coordinator Date At
/O,
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, Theundersigned, holding a valid commission Issuedby the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R1 O and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner forany personal Injury or property damage or a loss of any kind arising from or connected with this Inspection..
o
'1A. 4L0Commissions IL 1927 rnsp
's Signature National Board, State, Province, and Endorsements Date An._
101593 Q.C.-434A Sheet I of 2 FORM NVR-1 REPORT OF REPAIR X
MODIFICATION [,OR REPLACEMENT F OF NUCLEAR PRESSURE RELIEF DEVICES
- 1. Work performed by ANDERSON GREENWOOD CROSBY 00076601 (name of organization)
(P.O. no., job no., etc.)
43 Kendrick St., Wrentham, MA 02093 (address)
- 2. Work performed for EXELON CORPORATIONLASALLE STATION,MARSEILLESIL.
(name and address)
- 3. Owner EXELON CORPORATION,LASALLE STATION.MARSEILLES,IL.
(name)
(address)
- 4. Name, address and identification of nuclear power plant EXELON CORPORATION,LASALLE STATION, MARSEILLES, IL.
- 5. a.
Repaired pressure relief device MAIN STEAM SAFETY RELIEF VALVE
- b.
Name of manufacturer ANDERSON GREENWOOD CROSBY
- c.
Identifying nos.
HB-65-BP N63790-05-0002 STEAM 6 R 10 1981 (type)
(mfr's serial no.)
(Nat'l Bd. No.)
(service)
(size)
(year built)
- d.
Construction Code ASMEInI 1971 S1972
.1567,1711 1
(name/section/division)
(edition)
(addenda)
(Code Case(s))
(Code Class)
- 6. ASME Code Section XI applicable for Inservice inspection -- 1989 NO (edition)
(addenda)
(Code Case(s))
- 7. ASME Code Section XI used for repairs, modifications, or replacements 1989 NO (edition)
(addenda)
(Code Case(s))
- 8. Construction Code used for repairs, modifications, orreplacenients 1971
- S1972 1567,1711 (edition)
(addenda)
(Code Case(s))
- 9. Design responsibilities ANDERSON GREENWOOD CROSBY
- 10. Opening pressure 1150 PSIG Blowdown (if applicable) 3
% Set pressure and blowdown adjustment made at WYLE LABORATORIESHUNTSVILLEAL.
using STEAM (location)
(test medium)
- 11. Description of work: (include name and identifying number of replacement parts)
FLEXIDISC MODIFICATION, REPAIR AND TESTING MADE AT WYLE LABORATORIES. HUNTSVILLE,AL. USING STEAM.
- 12. Remarks THE DISC INSERT WAS REPLACED AND VARIOUS PARTS MODIFIED AS PART OF THE FLEXIDISC MODIFICATION.
Form NVR-1 (Back)
Certificate Holder's Serial Nos. N63790-05-0002 5
-93 Q.C.-434A Sheet 2 of 2 CERTIFICAE OF COMPLIAMNCE 1, CARS Go 1Drit certify that the statements made in this report are correct and the repair, modification ox replacement of the pressure relief device described above conforms to Section XI of the ASME Code and the National Board Inspection Code 'VR' and 'NR' rules.
National Board Certificate of Authorization No.
75 to 84 to use the 'VR' stamp expires JAN. 14,2007 National Board Certificate of Authorization No.
68 to use the 'NR' stamp expires DEC.11.2006 Date 7-S6f9
,2L04 Signed Anderson Greenwood/Crosby
- / p (name of repair organization)
(authorized representative)
QA MGR.
(title)
- g.
o.'.
I1 CERTIFICATE OFINSPECT:.
Inspectos aholding a valid commission issued by The National Board of Boiler and Pressure Vessel of competency issued by the jurisdiction of MASSACHUSETTS.
and employed by HSB-CT.
of HARTFORD - CT.
have inspected the repair, modification or replacement described in this report on.
&-6
- caf
_ and state that to the best of my knowledge and belief, this repair, modification or replacement has been completed in accordance with Section XI of the ASME Codeand the National Board Inspection Code 'VR' and 'NR' rules..
By signing this certificate, neither the undersigned nor my employer makes any warranty, expressed or implied, concerning.
the repair, modification or replacement described in this report.. Furthermore, neither the undersigned nor my employer shall be liable in any manner for any personal injury, property damage or loss of any kind arising from or connected with this.
Inspection.
Date t,
- .*..D<_.*
Signed I1JJ#-
Commissions MA 1420 A, N, I 7
(Inspector)
(Nat'l. Bd. (mcl. endorsements), and jurisdiction, and no.)
I i
.Jan. 8. 2005 10:26AM No.1163 P. 2/5 Q.C.-392 Sheet 1 of 2 FORM N-2 CERMFICATE HOLDERS' DATA REPORT FOR IEDENCAL NUCLEAR PARTS AND.APPURTENMACES*
As requtredjbf te Provisions of the ASME Code, Section llL Division 1 - Not to Exceed One Day's Production I
Manufactured and ceftifled by Anderson Greenwood Crosby, 43 Kendrick St., Wrentham, MA 02093
. (Name and Address of N Certificate Holder)
EXELON GENERATION 2
Manufacmred for (Name and Address of Purchaser or Owner)
LASALLE STATION 3-Locauon of Inwtallation (Name and Address)
- 4. Type DS-A-63790-2 REV.-
ASME SA637 GR 718 185,000 2_ 004 (drawing no.)
(mat'l-spec. no.)
(tensile stredgth)
(CRN)
(year built)
- 5. ASME Code,Section III, Division 1.
1971 SUMMER 1972 I
(edition)
(addenda date)
(class)
(Code Case No.)
- 6. Fabncated in accordance with Const. Spec. (Div. 2 only)
Revision Date (no.)
- 7. Remarks 8 Nom thickness (in.)
Mi. designthickness (iii.)
Dia. ID (ft &in.)
Lengthoverall (ft &in) 9 When applicable, Certificate Holders' data reports are attached for each item of this report.
Part or Appurtenance Serial Number (1) N97499-45-0112" Z (2) N97499-45-113 (3) N97499-45-0114 (4) N97499-45-0115 (5) N97499-45-0116 (6) N97499-45-0117 (7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
National Board No in Numerical Order Part or Appurtenae Serial Number National Board No.
in Numerical Order (26)
(27)
(28)
(29)
(30)
(31)
(32)
(33)
(34)
-(35)
(36)
(37)
(38)
(39)
(40)
(41)
(42)
(43)
(44)
(45)
(46)
(47)
(18)
(19)
(20)
(21)
(22)
(23)
(24)
(48)'
(49)
(50)
In Design pressure psi.
Temp.
F Hydro. test pressure 2370 pSig at temp. 70 0 F (when applicable)
Supple,,ntal mnfonadon in the fora of lists. skethcs. or dnwigs may be Wed provided (t) stze 15 5-1/2 s 11. (2) Inromwion to Items 2 -nd 3 on this Da2t Report la included on eclb sh::t, (3) eej sheet Is numbered und the au-ber otshcets Is recorded at die top of dW fonn This form (EO0040) may be obtined froni dte Order Dept.. ASME. 22 Low Prive. Box 2300. Fairrield. NJ D7007-2300
.Jan. 8. 2005 10:26AM No.1163 P. 3/5 IV(77Y79 4-"o/
Formn N-2 (Back)
Q.C.-392 Sheet 2 of 2
_Certitcate lolder's Serial No. N97499-45-0112 thru 0117 CERTIFJCATE OF COMPLACE We certify that the statements made in this report are correct and that this (these)
Disc Inserts conforms to the rules of construction of the ASME Code, Section m, Division 1.
NPT Certificate of Authorization No.
N-1877 Expires Sep. 30, 2004 Anderson Greenwood Crosby Date 5 F ZCOOf Signed Wrenham, MA by A
A (NPT Certificate Holder)
RAuthorized Representative)
J CERTIFICATE INSPECTiON I, the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the State eorf zke. of /4!;
and employed by BAS Group Tnc.
of Houston-Texas have inspected Arc items described in this Data Report on W__
, 200 and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code, Section m, Division 1. Each part listed has been authorized for stamping on the date shown above.
By igmnng this certificate, neither the Inspector nor his employer makes any warranty, expresed or implied, concernung the equipment described in this Data Report. Furthermore, neither the Inspector nor his employer shall be Uable in any manner for any personal injury or property damage or loss of any kind arising from or connected with tbis inspection.
Date i,2O Signed
- /_'.,
Coinsions 4L I
(Nat'l. Bd. (inc. endorsedcats) and state or proy. and no )
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi
- 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Square, PA., 19348 Address
- 2.
Plant LaSalle County Nuclear Station Name 2601 N. 21*' Rd. Marseilles, II. 61341 Address Date 05114/05 Sheet 1
of 2
Unit 2
W.O. #585835 Repair Organization, P.O. No., Job No., etc.
3.
W-oLr Paf nrl iM-&-nl-nl &auN tvnn-- r (Name)
Mechanical Maintenance Type Code Symbol Stamp NIA Authorization No.
N/A Expiration Date N/A 4.
5.
(Address)
Identification of System (MS) Main Steam (a) Applicable Construction Code Sect II 19 71 Edition Sf72 Addenda, Code Cases 1567 and 1711 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19 89, No Ad, Code Cases N496-1 Identification of Components Repalred or Replaced, and Replacement Components 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Safety Relief Valve AG N63790-00-0069 N/A 2B21-FO13H Replaced NIA Crosby _
Safety Relief Valve AG N63790-00-0079 N/A 2B21-FO13H Replacement N/A Crosby or N63790 Receipt # 101593 0079 (Modified)**
Disc Insert N93185-543-0221 N/A Replaced NIA Disc Insert AG N97499-45-0116 NIA Receipt # 101593 2004 Replacement N/A Crosby 7.
8.
9.
Description of Work Class I Repair & Replacement. * = Per N-5 Code Data Renort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osi Test Temp. 155 Deg. F Remarks Valve SN# N63790-05-0079 was refurbished at Wyle Labs with documentation provided under Quality (Applicable Manufacturer's Data Report to be Attached)
Recelot #101593 and installed as a replacement for SN# N63790-00-0069 under work order #585835. For the remainder of the Reoaired. Renlaced and Renlacement Items. see Form NIS-2 SunnIemrental Sheet on Paaes 2 of 2.
- Replacement SRV Serial No. was modified due to the Installation of a new flexi-disc seat design.
CERTIFICATION OF COMPLIANCE We certify that the statements made in the report are correct and these Repair and Replacement conforms to the rules of the ASME Code, Section Xi.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
Signedn Z
IIA fl1J*S CS*%If%
N/A H----------
-- LIL 1.
'e7 ISI Coordinator Date A
Z
- 4.
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner forany personal Injury or property damage or a loss of any kind rising from or connected with this inspection.
0 4 39 X
ii Commissions IL 1927 Ins or's Signature National Board, State, Province, and Endorsements Date 2005
FORM NIS-2 SUPPLEMENTAL SHEET
- 1.
Owner:
Exelon Generation Company (EGC) LLC Sheet.
200 Exelon Way, Kenneth Square, Date PA., 19348 Unit
- 2.
Plant:
LaSalle County Station 2601 N. 21 "' Rd.
Marseilles, Illinois 61341
- 3.
Work Performed by: Mechanical Maint.
Type C Name Autho Mechanical Maintenance Eynir-2 of 2
05/14/05 2
W.O. # 585835 P. 0. No., WR No., etc.
'ode Symbol Stamp N/A rization No.
N/A ition Date N/A
-_r I -
4.
5a.
5b.
6.
Address Identification of System MS (Main Steam)
Applicable Construction Code 71 Edition S72 Addenda Applicable Edition of Section XI utilized 89 Edition None Addenda Identification of Components Repaired or Replaced and Replacement Components.
Name of Name of Manufacturer National Other Year
- Repaired, ASME Component Manufacturer Serial No.
Board Identification Built Replaced Code No.
or Stamped Replacement (Yes or No)
Valve Body AG Crosby N93183 N/A Receipt #
Repaired N/A 0044 101593 (1) Heli-Coil AG Crosby N97823-0052 N/A Receipt #
2002 Repaired N/A Insert 101593 (Outlet)
(1) Heli-Coil AG Crosby N97823-0053 N/A Receipt #
2002 Repaired N/A Insert 101593 (Outlet)
- :=
101593 Q.C.-434A Sheet I of 2 MODIFICATION
~
[I OR REPLACEMENT FORM NVR-1 REPORT OF REPAIR FX ON O
OF NUCLEAR PRESSURE RELIEF DEVICES
- 1. Work performed by ANDERSON GREENWOOD CROSBY 00076601 (name of organization)
(P.O. no., job no., etc.)
43 Kendrick St., Wrentham, MA 02093 (address)
- 2. Work performed for EXELON CORPORATION,LASALLE STATION,MARSEILLESIL.
(name and address)
- 3. Owner EXELON CORPORATION,LASALLE STATIONMARSEILLES,IL.
(name)
(address)
- 4. Name, address and identification of nuclear power plant EXELON CORPORATION,LASALLE STATION, MARSEILLES, IL.
.5. a.
Repaired pressure relief device
..MAIN STEAM SAFETY RELIEF VALVE
- b.
Name of manufacturer ANDERSON GREENWOOD CROSBY
- c.
Identifying nos.
HB-65-BP N63790-05-0079 STEAM 6 R 10 1979 (type)
(mfr's serial no.)
(Nat'l Bd. No.)
(service)
(size)
(year built)
- d.
Construction Code ASME HI 1971 S1972 1567,1711 I
(name/section/division)
(edition)
(addenda)
(Code Case(s))
(Code Class)
- 6. ASME Code Section XI applicable for Inservice inspection 1989 NO
_E-(edition)
(addenda)
(Code Case(s))
- 7. ASME Code Section XI used for repairs, modifications, or replacements 1989 NO (edition)
(addenda)
(Code Case(s))
- 8. Construction Code used for repairs, modifications, or replacements 1971 S1972 1567,1711 (edition)
(addenda)
(Code Case(s))
- 9. Design responsibilities ANDERSON GREENWOOD CROSBY
- 10. Opening pressure 1195 PSIG Blowdown (if applicable) 3
% Set pressure and blowdown adjustment made at WYLE LABORATORIESHUNTSVILLE,AL.
using STEAM (location)
(test medium)
- 11. Description of work: (include name and identifying number of replacement parts)
FLEXIDISC MODIFICATION, REPAIR AND TESTING MADE AT WYLE LABORATORIES, HUNTSVILLEAL. USING STEAM.
- 12. Remarks THE DISC INSERT WAS REPLACED AND VARIOUS PARTS MODIFIED AS PART OF THE FLEXIDISC MODIFICATION.
Form NVR-1 (Back) 101593
- Q.C-434A t
H r s SSheet 2 of 2 Certificate Holder's Serial Nos. N63790-05-0079-:
CERTECA TE OF COMPLIANCE I, -DAV f/ > 'I%),7z-t5 certify that the statements made in this report are correct and the repair, modification oi
-replacement of the pressure relief device described above conforms to Section XI of the ASME Code and the National Board Inspection Code 'VRt and 'NR' rules.
- National Board Certificate of Authorization No.
75 to 84
-to use the "VR" stamp expires' JAN. 14,2007 National Board Certificate of Authorization No.
68 to use the "NRW stamp expires DEC.11,2006 Date 7-S,
,#Z~t~J igned Anderson Greenwood/Crosby t
/
QA MGR.
(name of repair organization)
(authorized representative)
(title) i I
TE OF INSPECT I,
_ holding a valid commission issued by The National Board of Boiler and Pressure Vessel sand rtificate ofcompetency issued by the jurisdiction of MASSACHUSETTS and employed by.
HSB-CT of:
HARTFORD - CT.
have' inspected the repair, modification or replacement described in this report on o
f and state that to the' best of my knowledge and belief, this repair, modification or replacement has been completed in accordance with Section XI:
of the ASME Codeand the National Board Inspection Code 'VR' and 'NR rules.'
-By signing this certificate, neither the undersigned nor my employer makes any warranty, expressed or implied, concerning the repair, modification or replacement described in this report. Furthermore, neither the undersigned nor my employer shall be liable in any manner for any personal injury, property damage or loss of any kind arising from or connected with this Inspection.
Date 8
S
§ t.
Signed.
I Commissions MA1420 A, N, I I (Nat'l. Bd. (incl. endorsements), and jurisdiction, and no.)
V (Inspector)
.Jan. 8. 2005 10:26AM No.1163 P. 2/5 Q.C.-392 Sheet I of 2 FORM N-2 ciEmICATE HOLDERS' DATA RPORT.FOR XDETICAL NUCIE:AR PARTS ANDAPPURTXAN CES*
As required the Provisions of the ASME Code Section III, Division 1 - Not to Exceed One Day's Production
- 1. Manufactured and ceified by Anderson Greenwood Crosby, 43 Kendrick St., Wrentham, MA 02093 (Name and Address of N Certificate Holder)
EXELON GENERATION 2 Manufactured for (Name and Address of Purchaser or Owner)
LASALLE STATION
.AT enctjon of Installation (Name and Address)
- 4. Type DS-A-63790-2 REV.-
ASME SA637 GR 718 185,000 2004 (drawing no.)
(mat'l. spec. no.)
(tensile strength)
(CRN)
(year built)
- 5. ASME Code,Section III, Division I.
1971 SUMMER 1972 1
(edition)
(addeda date)
(class)
(Code Case No.)
- 6. Fabncated in accordance with Const. Spec. (Div. 2 only)
Revision Date (no.)
- 7. Remarks 8 Nom thickness (in.)
Min. design thickness (mi.)
Dia. ED (ft & in.)
Length overall (ft & in.)
9 When applicable, Certficate Holders' data reports are atached for each item of this report.
I-Part or Appuzteiiaxce Serial Number (1) N97499-45-0112 (2) 97499-45-O113 (3) N9749945-114 (4) N97499-45-0115 (5) -N9749945-0116 (6) N97499-45-0117 (1)
(8)
(9)
(10)
(11)
(12)
(13)
(14)_
(15)
(17)
(18)
(19)
(20)
(21)
(22)
(23)
(24)
(25)
National '
Board No in Numerical Order Part or Appurtenance Serial Number National Board No.
in Numerical Order (25)
(27)
Cm8)
(79)=
(30)_
(3!)
(32)
(33) t34)_
(35)
(36)
(37)_
(38)
(39).
(40)_
(41)
(42)
(43)
(44)
(45)
(46)_
(47)
(48)
(49)
(50) 17 D~esign pressure ________psi.
Ternp.
F Ilydro. test pressure 2370
_pSig_ at tezap. '70 (when appllcable)
~,~pzemcntal infrmiaon to the form of uama.
akechdeS. oT dawm$S any be Used MAWtde (1) stzo is 3-1/fl x II. C'2) ivoromitio~n in Items 2 VA4 3 on t~his Dat2 Re~rt la sncludd on ne.b sh=, (3) tasci Sheet is atizbered MA Uhe ownbat at shtetc is recorded at the top of this fOra Thij forn (E0O0040) ma'y be pbtained from the Ordet Dept.. ASNIE. 22 Low LI-ivt. Box 2300, Fairrield. N~J 0O7007-2Q00
) F
.Jan. 8. 2005 10:26AM No.'1163 P. 3/5
/V 777t/9
Ž -
011
.-cer~tiflcate Holder's Serial No. N97499-45-01 12 thru 01 17 Form N-2 (Back)
Q.C.-392 Sheet 2 of 2 CERTIFICATE OF COMPLIANCL We certify that the statements made in this report are correct and that this (these)
Disc Inserts conforms to the rules of construction of the ASME Code, Section m, Division 1.
NPT Certificate of Authorization No.
N-1877 Expires Sep. 30, 2004 A* derson Greenwood Crosby Date 5_
__O'_
Signed Wrentham, MA by ___
D (NPT Certificate Holder)
(Authorized Representative)
CERTIFICATE OEF INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the State e Orefineof A.Sg Iand employed by ABS Grou Jcu.
of Houston Texas have inspected these items described in this Data Report on
_-6_,
200J._
and state that to the best of mi knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code, Section m, Division 1. Each part listed has been authorized for stamping on the date shown above.
By sogning this certficate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any lknd arising fromn or connected with this inspection.
-4k5, -200 Date
_(-
'Signed Commissions "W-14.b-AJI (Nat'l. Bd. (Act. endorserments) and state or prov. and no )
1/ (Authorized Inspector)
'I1
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl
- 1.
Owner Exelon Generation Companv(EGC) LLC Date 09/15/03 (Name) 200 Exelon Wav. Kenneth Sauare. PA.. 19348 Address
- 2.
Plant LaSalle County Nuclear Station Sheet I
of I
Unit 2
W.O. #00593839 Repair Organization, P.O. No., Job No., etc.
Name 2601 N. 2. t Rd. Marseilles.
61341 Address 3.
Work Performed h-MRnAk-u1-1 MAnAnann.n
_y (Name)
Mecthanicl-Mnln$Anannc Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A
..,v9...,,,.9>,..,a,,,.v..a..9v 4.
5.
6.
(Address)
Identification of System (MS) Main Steam (a) Applicable Construction Code Sect III 19 71 Edition Sf72 Addenda, Code Cases 1567 and 1711 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19 89, No Ad,Code Cases None Identification of Components Repaired or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Safety Relief Valve AG N63790-00-0006 N/A 2B21-F013C Replaced N/A (SRV)
Crosby Safety Relief Valve AG N63790-00-0005 N/A 2B21-F013C Replacement N/A (SRV)
Crosby or N63790 0005(Modfled)**
Disc Insert N93185-46-0168 N/A Replaced N/A Disc Insert AG N97499-43-0099 N/A Receipt #91436 2003 Replacement N/A Crosby (1) Nut, Tension N/A Replaced N/A (1) Nut, Tension NOVA Ht. Code C491 N/A Receipt # 69812 2001 Replacement N/A 7.
8.
9.
Description of Work Class 1 Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1004 psi Test Temp. 534.9 Deg. F
- Remarks Valve SN# N63790-05-0005 was refurbished at Wyle Labs with documentation provided under Quality (Applicable Manufacturer's Data Report to be Attached )
Receipt # 91436 and Installed as a reolacement for SN# N63790-00-0006 under work order # 00593839.
- Replacement SRV Serial No. was modified due to the Installation of a new flexi-disc seat design. "*Pressure test of the new SRV replacement was performed below 10% reactor power.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No SlaneS c
MIA Frlttl 6
nt r.-cpidll 1.
N/A ISI Coordinator Date 9zzt6
, 2003 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 I
and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arlsi g from or connected with this Inspection.
gr 1
Commissions IL 1927 Inspntor's Signature National Board, State, Province, and Endorsements Date C
2003
91436 Q.C.434A Sheet I of 2 FOM NVR-1 REPORT OF REPAIR [],
MODIFICATION [3, OR =PMACUr*ENT [
OF NUCLEAR PRESSURE RELIEF DEVICES
- 1. Work perfozmedby ANDERSON GREBNWOOD CROSBY 00061440 (name of organdzation)
(P.O. no., job no., etc.)
43 Kendrick St., Wrentham, MA 02093 (address)
- 2. Workperformed for EXELON CORPORATION,LASALLB STATION,MARSEILLES,IL.
(name and address)
- 3. Owner FXELON CORPORATIONLASALLE STATION,MARSEILLES,IL.
(name)
(address)
- 4. Name, address and identification of nuclear power plant EXELON CORPORATION,LASALLE STATION, MARSEILLES, IL.
- 5. a. Repaired pressure relief device MAIN STEAM SAFETY RELIEF VALVE
- b. Name of manufacturer ANDERSON GREENWOOD CROSBY
- c.
Identifying nos.
HB-65-BP N63790-50005 STEM 6 R 10 1981 (type)
(mfr's serial no.)
(Nat'1 Bd. No.)
(service)
(size)
(year built)
- d.
Constuction Code ASME III 1971 S1972 1567,1711 1
(name/section/division)
(edition)
(addenda)
(Code Case(s))
(Code Class)
- 6. ASME Code Section XI applicable forInservice inspection 1989 NO (edition)
(addenda)
'.(Code Case(s))
ASME Code Section XI used for repairs, modifica ons, or replacements 1989 NO (edition).
(addenda)
(Code Case(s))
- 8. Construction Code used for repairs, modifications, or replacem~nts 1971 S1972 1567,1711 (edition)
(addenda)
(Code Casets))
- 9. Design responsibilities ANDERSON GREENWOOD CROSBY 10.0peningpressure 1175PSIG 1lowdow a
(if applicable) 2-11
% Set pressure blowdonsadjustment made at WYLE LABORATORIES,HUNTSVILLE,AL.
using STEAM (ocation)
(test medium)
- 11. Description of worki (indude name and identifygg number of replacement pafls)
FLEXIDISC MODIFICATION, REPAIR AND TESTING MADE AT WYLE LABORATORIES, HUNTSVILLE,AL. USING STEAM.
- 12. Remarks TIE DISC INSERT WAS REPLACED AND VARIOUS PARTS MODIFIED AS PART OF THE F
PLEXIDISC MODIFICATION.
. s
Form NVR-1 (Back)
Q.C.-434A Sheet 2 of 2 Certificate Holder's Serial Nos. N63790-05-ooo5 CERTIMCATE OF COQM~tPL ANJ I,
K'A a) j13. &
?
certify that the statements made in this report are correct and the repair, modification oi replacement of the pressure relief device described above conforms to Section Xl of the ASME Code and the National Board Inspection Code "VR' and KNRE rules.
National Board Certificate of Authorization No.
75 to 84 to use the UVR' stamp expires JAN.14,2004 National Board Certificate of Authorization No.
68 to use the NR' stamp expires DEC.11,2003 Dare _
ci
, z-,_ Signed AndersonGreenwood/Crosby 4,R D,
QA MGR.
(name of repair organization)
(authorized representative)
(title) 1 CERTIICA TE OF hWSPECTION I. PA It hC1,r
. holding a valid commission issued by The National Board of Boiler and Pressure Vessel Inspectors and eertificaie of competency issued by the jurisdiction of MASSACHUSETTS and employed by ABS GROUP INC.
_:_of have inspected the repair, modification or replacement described in this report on 7-I
_and stare that torthe best of my knowledge and belief, this repair, modification or replacement has been completed in accorane with Section XI of the ASMB Codeand the National Board Inspection Code WVR and 'NR' roles.
By signing this certificate, neither the undersigned nor my employer makes any warranty, expressed or implied, concerning the repair, modification or replacement described in this report. Furthermore, neither the undersigned nor my employer shall be liable in any manner for any personal injury, property damage or loss of any kind arising from or connected with this Inspection.
Date L2 - /D r27t Z3.
Signed a
° i
c t
(Inspector)
Commissions UfT 1 f 4 I
(Nat'l. Bd. (m:1. endorsemnts), and jurisdiction, and no.)
- N.
R d
Iln/R I AfN Pidt7:0 PnnV end inn
_...
j a71 9 14I3 6 Q.C.-39g Sheet I of 2 FOP17 N.2 CMRTIFICATE HOLDERS'.DATA REPORT FOR DENTICAL MJCIE;AR PARTS AND APPRUMANCES*
As required by the Provisions of the ASME Code. Section llT, Division I - Nor to Exceed One Dav's Producrion
- 1. Manufactured and certified by Anderson Greeawood Crosby, 43 Kcedrick Sr., Wrenifiam, MA 093 (Name and Address of N Certificate Hlolder)
- 2. Manufactured for EXELON GENERATION (Naxne and Address of Parchaser or Owner)
- 3. Location of Itallaion LASALUE COUNTY STATION1 (Name and Address)
- 4. Type DS-C-63790-5 REV.A ASME SA637 GR.718 185,000 2003 (drawing no.)
(maTl spec. no.)
(tensile strength)
(CRN) 6iear built)
- 5. ASME Code,Section III, Division 1:
I971 SUMMER 1972 I I (edition)
(addenda dafe)
(class)
(Code Case No.)
6 Vabricated in accordance with Consr. Spec. CDiv 2 only) evision Date (no.)
- 7. Remarks
- 8. NoD. Ucknes (in.)
Mi.
design thickness (in.)
Dia. ED (ft & in.)
Length overaII (ft &
4.
- 9. When amlicable, Cerrificare Holders' data porrs aro 2trached for each erem of this repor.
Pat or Appurtenance National Par= or Appnwenance National Serial Number Board No.
Serial Number Board No in Numerical Order.
in NUmerical Ordr (1) N97499-38-0060 (26)
(2) N97499-38-0061 (27)
(3) N97499-43-0098
- 28)
(4) NY97499.43.0099 (f~.
t29)
__._l orE s~ns~ii-2Slnl.
53-. I
() : N97499-43-0102 C)
N797499-43.0103 (8)
(9)
(10)-
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
(21)
(23)
(24)
I I
I
.I F.
(I (I
(4 I.
(4 r
(4 (5
(31)
(32)
(33)_
(34)
(35)
(36)
(37)=
(38) t39)
(40) 41)_
42) 43) 14)
- .5)=
48)-
16) 9)
0)
.1
- 10. Diilga' preissuric psi.
Temp.
P flydro. resr pressure 2370 att temp. 70 a0 (whenx applIcAble)
-.'Tpplcmenmi aifon~uIan lae tfo t otuuz, skmches, or drawInts myba used pwoided (I Shte ft 14142 x 11. (2 IUformCWA InizonW2 and on~
Wbs 0=9t~.port
-iuam d
=-c~
beet.
) t Mm zhme numribe~d nd the mshfler orscezs Is reordrdsp he wp of zJut form.
This fbrm (E004) may be abrmned (tOm abe Ord.-r Dept.. ASMdE. 22 Ltw Witt, Rox 2300, Fa~xrdctd. NJ 07007-2300
Form N-2 (Back)
Q.C.-392 Sheet 2 of 2 Certificate Holder's Serial No. N97499-38-0060 CER TIFIATE OF COMPLIE We certify that the statements made in this report are correct and that this (these)
Disc Inserts conforms to the rules of construction of the ASME Code,Section III, Division 1.
NPT CertificAte of Authorization No.
N-1877 Expires Sep. 30, 2004 Anderson Greenwood Crosby Date 1O-A 3-9O3 Signed Wrentha M. MA fb (NPT Certificate Holder)
(Authorized eprcsentative)
CERT1FICATE. OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of MAS and empIoyed1by Factory Mutual Insurance Co.
of Johnston. ghode sland have inspected these items described in this Data Report on hoh*
th 20 3 and state that to EC best of my knowledge and belief, the Certificate Holder has fabricated thesa parts or appurtenances in accordance wiih lhe ASME Code,Section III, Division 1. Each part listed has been authorized for stamping on the date shown above Bly signing this cerdficate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss. of any kind arising from or connected with this inspection.
Commissions A7,-4-i y (Nat'l. Dd. (Ind. endorsements) and state or prov. and no.)
7 a n Iio n o wAI7.:C fnnlz nl Inn
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
2.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Square, PA.. 19348 Address Plant LaSalle County Nuclear Station Date 03109105 Sheet 1
of I
Unit 2 Name 2601 N. 218t Rd. Marseilles. ii. 61341 (Address) 3.
Work Performed by_
Mechanical Maintenance W.O. # 605993 Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A (Name)
Mechanical Maintenance (Address) 4.
5.
identification of System 1C41) Standby Liguld Control (a) Applicable Construction Code ASME Sect. III 19 77 Edition S77 Addenda, Code Cases None (b)
Applicable Edition of Section Xi Utilized for Repairs or Replacements-1989 No Ad. Code Cases None Idantifle-ation of Comnonents Ranalred or Ronlaced-and Ranlacemant Comnonnnts 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Inlet Fitting IST-Conax N/A 2C41.FO04A
- Replaced, NIA Nuclear Inlet Fitting IST-Conax 7123 N/A Receipt # 98991 2004 Replacement N/A Nuclear Trigger Body IST-Conax N/A 2C41.FO04A Replaced N/A Assembly Nuclear Trigger Body IST-Conax 7125 N/A Recelpt # 98991 2004 Replacement N/A Assembly Nuclear 7.
8.
Description of Work: Class I Replacement * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I _I Normal Operating Pressure IX I Other Visual Pressure 1220/1055 psl Test Temp. Ambient Deg. F Remarks: Reolacement components were constructed to ASME Sect ill. Class 1 1977 Ed S77 Addenda.
(Applicable Manufacturer's Data Report to be Attached )
Replacement reconciled Per PTE 88-161 on file at LaSalle Station.
9.
- CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate ofAuthpdzation No.
N/A Expiration Date N/A Signed I
151 Coordinator Date -
2005 t(/OwN&r or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boiler Insy. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period _
L2R09 to L2-10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
-tCommissions IL 1927 Inslector's Signature NationalBoard, State, Province, and Endorsements Date 3-9' 2005
FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES' As Required by the Provisions of the ASME Code,Section III Not to Exceed One Day's Production P
.Pg. 1 of 2
- 1. Manufactured and certified by
- 2. Manufactured for.
IST Conax Nuclear, Inc. 402 Sonwil Drive. Cheektowaga, NY 14225 fname and address of NPT Certificate Holder)
Exelon Business Services Co.. P.O. Box 805388. Chicago. If 60680
- 3. Location of Installation (name and address of Purchaser)
LaSalle Nuclear Power Plant (name and address)
- 4. Tvne:
N38017 Rev. F SA479=304SST 75 KSI N/A N/A 2004
/
(drawing no.)
(mat') Ipec. no.]
(CRM (year bult?
- 5. ASME Code, Section 1I1, Division 1:
77 Summer 77 I
N/A Xedifton)
(addenda date)
(class)
(Cod Case no.)
- 6. Fabricated In accordance with Const. Spec. (Div. 2 only)
N/A Revision Date (no.)
- 7. Remarks:
Inlet Fitting for explosive actuated valve replacement kit for Standby Uquld Control System Pressure Test at 2800 psi for 10 minutes
- 8. Nom. thickness (in.)
.040-Min. design thickness (in.)
.031 Di. ID (ft & In.)
.815 Length overall (ft & In.)
2.245-
- 9. When applicable, Certificate Holders' Data Reports are attached for each item of this report:
National Part or Appurtenance arNo Serial Number Board No.
In Numerical Order
- 11) 7123 7123 (2) 7124 7124 (3)
(4)
(5)
(6)
(7)
(8)
(9)
(1 0 )_
(1
- 1)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
(21)
(22)
(23)
(24) -
(25)
Part or Appurtenance Serial Number National Board No.
In Numerical Order (26)
(27)
(28)
(29)
(30)
(31)
(32)
(33)
(34)
(35)
(36)
(37) 138)
(39)
(40)
(41)
(42).
(43)
(44)
(45),
(46)
(47)
(48)
(49)
(50)
"I 4
4 4
a.
4.
.9
.9
.9 I,
so. Design pressure 1500 Dsi. Temp.
150 OF.
Hydro. test pressure
- See Remarks at temp. *F (when appncable)
- Supplemental Information In the form of lists, sketches, or drawings may be used provided (1) size is 8% x 11, (2) Information In items 2 and 3 on this Data Report Is Included on each sheet, (31 each sheet Is numbered and the number of sheets Is recorded at the top of this form.
004
.0I
..,2.1ack.,
Pg..? of 2 )
.. Ceifcat Fiolder'sSerial Ns.
7123 through 7124 j:
)
-CERTIFICATiOa OF.DESIGN
.1 O
FD SG Design specifications certified by.
George I. Skoda P.E. State CA Reg. no.
15847 a J4 ppeipb4e 4,I..
Frn i J. DS.
Francis J. Domino P.E. State NY fleg, no.
36832 Design report' certified by IwtwVt~
iPP0-b MIO L' -.
e t
LIANCE CERTIFICATE OF COMP We certify that the statements made In this report are corroet and that this (these)
Td conforms to the rules of construction of the ASME Code, Section lI;Division i.
dgger Body Subassembly NPT Certificate of Authorization No.
Date; 3 1,;2 2 9/
Narne,_
I N-1850 Exoires September 2. 2004 q -,
lgT.Ccnix Nud4ai Signed I
11 (NpTr Cetfict e Hoider)
./
fazthodzd reprmsnta et)4 CERTiFICATE OF INSPECTION i;tne derslgned, hoidiriga vild commisslon ;ssued by the'National 9 erd of Bfier and Pressure Vessel pectorxithe State or Provhef NewYork and employed by
2
.2,Z 2.004
- and state that to the best of my knowledge and belief, the Certificate Holder has fabricated.these parts of appurtenances In acccfrdance with the ASME Code, Section 111, Division 1. Each part listed has been authorized for stamping on the date shown above.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment dlescribed In this Data Report. Furthermore, neither the Inspector not his employer shall be giable In any-manner for any personal Injury or roperty damage or loss of any kind arising from or connected with this inspection.
Dateedpaj,
.Sig Commissions NB 10964AN NY 5057 V.M aC I~ a i
- d. Ific.
fi or w n nt ) waj 1d ta t, or p wo. e nd o.I
FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES" As RequIred by the Pr6visions of the ASME Code, Section UI Not to Exceed One Day's Production 005 Pa. I of 2
- 1. Manufactured ad certified by
- 2. Manufactured for 19T Concs Nuclear, Inc. 402 SonwI Drt. Cheetowaga, NY 14225 nIfitn -a WM= of NPT COMMcx WM.du t
Exeltin Buoiness Servic-es Co.. P.O. Box 805388. Chkcago, 1 60680 W4 ofdriii of Roe9~w~
- 3. Location of installation LaSeR. Nucear Power Plan ed sddolo")
bWlW
- 6. ASME Code, Sectin IN, Division 1:
77 Summer 77 I
MIA OdftN addend datul
- e. Fabricated In uccordenc whh Const. Spec. (Div. 2 only)
MIA Revision r t cm u
j Date
- 7. Remarks:
Triwar Boyd Subassembly for oxploWv ctte valve rep tut a for Standby Uqutd Control Syst8m Par NB*2121 lb) Is eppalable to ram. Prss 1etal on.S28 a.4375 dianmter. Overal subassoby fength Is 2.8.
Pres" Tmt at 2800 psi for 10 mnites.
- 8. Non. thicknesl ran.) Se roma Min. design thickness fin.)
See nxior Di&. I0 ift & in.) ae u"w!akq Lanah ovew (ft & hI.)
iserts S. When applicale, Certificte Holders' Data Reports are attached for each hem of thb report:
National Part or AppurtenanceBor o
Serial Number InNmrca re 7125 '2 (2) 7126 7128
( 3 )
14
)
( 7 )
(1 0 1 1 1 3 )
(1 4 )
(1 5 )
(18).
(20)___________
( 2 4 )
( 2 5 )
Part or Appurtenance Sei Number National
. Board No.
in Ntnericat Order.
(281 (271 (283 1291 (301 131) 1321 (33J (341 (36)
(38)
(37)
(38) 139)
(40) 1411 (42)
(431 (44)
(45)
(461 (47)
(48)
(49)
(60 I.
I.
6*
.9 a
- 10. Design pressue 1500 Dl.
Temp.
150
'F.
Hydro. teat pressure Ilee S
ears atteamp. *F 0*taN aaplicablool
- SuppfanentalW hIormsaton hI i forfm of Ists, sketchs, or drowings may be used provided II) size i a8K x 11. 2) information In hunr. 2 and 3 on t Data Aleport Is inckded on eacn sheet. (3) each st Is numbered sid the rnuber of Sheets is recorded at the top of ts form
006 F R (B a c k P, 2 $.....
.~
C p iftc te.H ider
..7 t12 6 thr Iio u gh 7 2 ThlFlCA,1lONOb9t
.N Design specifications certified by.
Ooore 1. Skods P.E. State CA A". no.
15847 Dlslgn report certified by Frasnda J. Domlno P.E. State NY Rog. no.
36832
.1vo"flspmvuww C
T
. F
.CO M L I A ; ; E I
I "I'..
.I I "I
I I
.... 1
...I..
1...
CERTFCTE OF COMPLIANCE We certify.ihat the statements made In this report are correct pnd that this (these)
- I
.ontB t _
_h l
S e.
l cofrsto Ih rueilonufno he ASME Coda, Soelo WI1, D6;ivbiot.
'r.-
T&
wA.
..kw ¶ NPT Certiffce of Authorization No.
N-1Ep0 E
ires Septmber 2, 2004 iS T-ona N uc earS ig n ed D 7 L 7 / p a 4 v < t -e p, I P T ' ' c p CERTIFCATEOFItNSPECT1ON 1.u (jnd ~ gned. h i r
- s v g s b u ed by th e aiotn al B ~ &
d ~ a ijr es ielr IidP c or o ao sid &htSuia j o r Prov kiN bt New York employed by HSUCt ' :
ol Hirtford, CT haw inspected these his described in this Data Report on
,I o nd st that to best of my knowledge and beRet, the Certifcate Holder has f thes pub or a I
c e
wW th ASME Codto Section lIl, Division 1. Each part listed has been authorizod for stmping on the data shown abov.
By signing this certificate, nefther the inspector nor his *mpIoyer makes an warranty. expressed or ipledi, concerning the equipment desdribed In this Data Rpo rthermorm. neither the inspector nor Nis employer shal b O" hi an nmawr for any personal inry or property dmg or loss of any kind arsng from or connected with this inspection.
Daet!
Zko
~
_SWO UR 10OBIAM MY fifM7
-2 M A JI--
~~ ~
w glW§- ~ ~ ~ ~ ~
~
~
~
~
~
t W M
n. l-et I ) n t n e p u. a d n I
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Address Plant LaSalle County Nuclear Station Date 02/26105 Sheet I
of I
Unit 2 2.
Name 2601 N. 21"t Rd. Marseilles: Ii. 61341 (Address)
W.O. # 620332 Repair Organization, P.O. No., Job No., etc.
3.
4.
5.
Work Performed b'V Mechanicl2 Ma2ntfancnn (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp NIA Authorization No.
NIA Expiration Date N/A Identification of System (RT) Reactor Water Clean Up (a) Applicable Construction Code ANSI B31.7 19 69 Edition No Addenda, Code Cases None (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-I989 No Ad, Code Cases None Identification of Comoonents Reoalred or Replaced. and Replacement Components 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped
._I_ _ No.
Replacement (Yes or No)
Mechanical Pacific 8553 NIA RTOI-2873S Replaced N/A Snubber Scientific Mechanical Pacific 9953 NIA RT01-2873S 1979 Replacement NIA Snubber Scientific 7.
8.
9.
Description of Work: Class I Renlacement of Mechanical Snubber Assembly.
Tests Conducted:
Hydrostatic I - I Pneumatic II Normal Operating Pressure I I
Other Visual Pressure psl Test Temp._Deg. F Rpmarks! * = Per Orininal Deslan Sneclfication J-2530-
......... 1-(Applicable Manufacturer's Data Report to be Attached )
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this_
of the ASME Code, Section Xl.
Type Code Symbol Stamp NONE Replacement_
- conforms to the rules (repair or replacement)
MIA Certificate of Autorization No.
Signed Ewnlv,*?nn fln:E NIA 1.
ISI Coordinator Dat e M2v 12 2005l vs
.,.o,..
. vvv_
Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L12R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
i s4 A ---74,Ay'-'
Commissions IL 1927 Insp or's Signature National Board, State, Province, and Endorsements Date
-_____2005
FORM NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI 1.
Owner Exelon Generation Companv (EGC) LLC Date 03110105 (Name) 200 Exelon Way. Kennett Square.
PA., 19348 Sheet I
of 1
2.
(Address)
Plant LaSalle County Station (Name) 2601 N. 2 1"t Rd. Marseilles. II. 61341 Unit 2 Repair Organization, P.O. No., Job No., etc.
3.
(Address)
Work Performed by Mechanical Maintenance (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp NIA Authorization No.
5.
Identification of System (RH) Residual Heat Removal (a) Applicable Construction Code Sect liI 1974 Edition Winter 1974, Addenda, Code Cases 1567. 1622 & 1682 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989, No Ad, Code Cases N-416-2
- 6.
Identification of Com onents Kepalrea or Replaced, anl Ieplacement Components Name of Name of Mfrs. Ser.
Nat'l CRN Other Year Repaired ASME Code Component Mfr.
No.
Bd.
No.
Identi-Built
- Replaced, Stamped No.
Fication Replacement (Yes or No)
Check Valve Body Anchor-N/A N/A 2E12-F050A Repaired N/A Darling
- 7.
Description of Work Class 1 Repair. Repaired valve body by machining and welding.
- 8.
Tests Conducted:
Hydrostatic I -
I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osl Test Temp. 155 Deg. F
- 9.
Remarks' = Per Orlainal N-5 Code Data Report on file at LaSalle County Station.
(Applicable Manufacturer's Data Report to be Attached)
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Repair conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
N/A Expiration Date NIA Signed
(-
ISICoordinator Date May12.
20 05 Owner or Owner's Designee, Title r.__
CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boller lns. & Ins. Co. Of Hartford, CT. have Inspected the components described In this Owner's Report during the period L2R09 to L2R1O10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, Neither the Inspector nor his employer shall be liable In any manner foranypersonal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
le
!ZX9ff Commissions IL 1927 Inspect Signature Date
-'/T-20 05 National Board, State, Province,-,and Endorsements
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
2.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way, Kenneth Square, PA., 19348 Address Plant LaSalle Countv Nuclear Station Name 2601 N. 21' Rd. Marseilles. II. 61341 (Address)
Sheet 1
of 1
Unit 2 W.O. N A28869 Date 04114105 Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
NIA 3.
Work Performed hTV Moehanical Mtalnftannnr (Name)
Mechanical Maintenance (Address)
Expiration Date.
NIA 4.
5.
Identification of System (RD) Control Rod Drive (a) Applicable Construction CodeqASME Sect III 19 71 Edition No Addenda, Code Cases 1361-1. & 1361.2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None Identification of Comnonents Renalred or Renlaced. and Renlacement Comnonents 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped
_No.
IReplacement (Yes or No)
CRD Assembly G.E.
9352 N/A 26-55 Replaced N/A CRD Assembly G.E.
7742 N/A Receipt# 105348 2005 Replacement NIA (8) CRD Capscrews Nova N/A 26-55 Replaced NIA (5) CRD Capscrews Nova Ht. Trace Code N/A Receipt# 102444 2004 Replacement N/A
_R139 (3) CRD Capscrews Nova Ht. Trace Code N/A Receipt #94495 2003 Replacement NIA I__
H 490 I_
I_ _
7.
8.
Description of Work Class I Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osi Test Temp.
155 Deg. F Remarks CRD SN# 7742 was refurbished with documentation provided under Quality Receipt # 105348 and 9.
(Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 9352 under work order # 628869.
= Replacement CRD Code of Construction Is ASME Section Ilil. 1971 Ed. S73 & W75 Ad. Reconciled to the original per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section ill. Class 1. 1986 Ed. No Ad. Reconciled to the orialnal Code of Construction ner PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
NIA Expiration Date NIA Slo ned i4
)
ISI Coordinator Date 74°wle 6
. 2005 U
Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2RIO and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any ki d ing from or connected with this Inspection.
IZf./
2LA.7$
Commissions IL 1927 Int ctor's Signature National Board, State, Province, and Endorsements Date 4-/
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi
- 1.
Owner Exelon Generation Comoanv (EGC1 LLC Date 04M14105 (Name) 200 Exelon Way. Kenneth Square, PA.. 19348 Sheet I
of I
Address
- 2.
Plant LaSalle County Nuclear Station Unit 2 Name 2601 N. 21st Rd. Marseilles. ii. 61341 W.O. # 628870 (Address)
Repair Organization, P.O. No., Job No., etc.
- 3.
Work Performed by Mechanical Maintenance Type Code Symbol Stamp N/A (Name)
Authorization No.
N/A Mechanical Maintenance Expiration Date NIA (Address)
- 4.
Identification of System (RD) Control Rod Drive
- 5.
(a) Applicable Construction CodeASME Sect ill 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None
- 6.
Identification of Components Repalred or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
9190 NIA 22-11 Replaced NIA CRD Assembly G.E.
6628 N/A Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova N/A 22-11 Replaced N/A (8) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 94495 2003 Replacement N/A
- 7.
Description of Work Class I Reolacement.
= Per N-5 Code Data Report on file at LaSalle County Station.
- 8.
Tests Conducted:
Hydrostatic L IJPneumatic I I Normal Operating Pressure l X I Other Visual Pressure 1035 psl Test Temp.
155 Deg. F
- 9.
Remarks CRD SN# 6628 was refurbished with documentation provided under Quality Recelot # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed asa reolacementforSN# 9190 underworkorder# 628870.
- Replacement CRD Code of Construction Is ASME Section lil.1971 Ed. S73 & W75 Ad. Reconciled to the orialnal per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section Ill. Class 1. 1986 Ed. No Ad. Reconciled to the original Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Renlacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Auth zation No.
NIA Expiration Date NIA Signed
/
ISI Coordinator Date 74 'e'Z
/*
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller lnsp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
IOU/ S A
Commissions IL 1927 Insntor's Signature National Board, State, Province, and Endorsements Date 2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section XI
- 1.
Owner Exelon Generation Company (EGC) LLC Date 03130/05 (Name) 200 Exelon Way. Kenneth Square. PA., 19348 Sheet I
of I
Address
- 2.
Plant LaSalle County Nuclear Station Unit 2 Name 2601 N. 21" Rd. Marseilles. 11i.61341 W.O. # 628871 (Address)
Repair Organization, P.O. No., Job No., etc.
- 3.
Work Performed by Mechanical Maintenance Type Code Symbol Stamp N/A (Name)
Authorization No.
NIA Mechanical Maintenance Expiration Date NIA (Address)
- 4.
Identification of System (RD) Control Rod Drive
- 5.
(a) Applicable Construction CodeLASME Sect IiI 19 71 Editlon No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None
- 6.
Identification of Coiponents Repalred or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
9580 N/A 54-47 Replaced N/A CRD Assembly G.E.
9234 NIA Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova NIA 54-47 Replaced NIA (8) CRD Capscrews Nova Ht Trace Code NIA Receipt # 94495 2003 Replacement NIA
_ _ _ _ _ _ _H 4 9 0
- 7.
Description of Work Class I Replacement.
- Per N-5 Code Data Reoort on file at LaSalle County Station.
- 8.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 psI Test Temp.
155 Deg. F
- 9.
Remarks CRD SN# 9234 was refurbished with documentation provided under Quality Recelit # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 9580 under work order # 628871. 'a = Replacement CRD Code of Construction Is ASME Section 111.1971 Ed. S73 & W75 Ad. Reconciled to the original per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section lil. Class 1.1986 Ed. No Ad.
Reconciled to the orlalnal Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Auth gzatlon No.
N/A
-Expiration Date NIA Sig nede ISI Coordinator Date /X
-,e f_ 3/
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to
_L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
--Commissions IL 1927 Ins btor's Signature National Board, State, Province, and Endorsements Date__________
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the -Provisions of ASME Code Section Xl 1.
2.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Sauare. PA., 19348 Address Plant LaSalle County Nuclear Station Date 04/18/05 Sheet 1
of 1
Unit 2 Name 2601 N. 21" Rd. Marseilles. II. 61341 (Address)
W.O. # 628888 Repair Organization, P.O. No., Job No., etc.
3.
4.
5.
6.
Work Performed by
,l o
Cre.-a Mechanical Maintenance (Name)
Mechanical Maintenance (Address)I.r no% rn ft-rad new Type Code Symbol Stamp N/A Authorznation Nao N/A Expiration Date N/A IuW,,LI,..aLju,, 'WI
-Y*tU,.,
alnlJ 'VMrI, n
UJIIVC (a) Applicable Construction Code ASME Sect iII 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section XI Utilized for Repairs or Replacements-1989, No Ad, Code Cases None Identification of Components Repalred or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
9437 N/A 46-35 Replaced N/A CRD Assembly G.E.
9420 N/A Receipt # 105348 2005 Replacement N/A (8) CRD Capscrews Nova N/A 46-35 Replaced N/A (8) CRD Capscrews Nova Ht. Trace Code NIA Receipt # 94495 2003 Replacement N/A 7.
8.
9.
Description of Work Class 1 Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic II Normal Operating Pressure I X I Other Visual Pressure 1035 osi Test Temp.
155 Deg. F Remarks CRD SN# 9420 was refurbished with documentation provided under Quality Recelit # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 9437 under work order # 628888. '* = Replacement CRD Code of Construction Is ASME Section lil. 1971 Ed. S73 & W75 Ad. Reconciled to the orlignal per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Caoscrew Code of Construction Is ASME Section Ill. Class 1. 1986 Ed. No Ad. Reconciled to the original Code of Construction per PTE M91-007-0320w01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
N/A Expiration Date N/A qInned J
A<
i IS ordnnrinator D
ate Z o 2 0.
2 00 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boiler lnsp. & Ins. Co. of Connecticut have inspected the components described in this Owner's Report during the period 12R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 Inspsor's Signature National Board, State, Province, and Endorsements Date
('- 2 2005 K>
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
Owner Exelon Generation Comrlanv(EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Address Plant LaSalle County Nuclear Station Date 04/118JIS Sheet I
of 1
Unit 2 2.
Name 2601 N. 21" Rd. Marseilles. II. 61341 (Address)
W.O. # 628889 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed h..
aMrhn-1-2 UM-ln - -
I-. y
,.,c,,a,,,da rfla,,,Uanfl (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A 4.
5.
6.
Identification of System IRD) Control Rod Drive (a) Applicable Construction CodeASME Sect liI 19 71 Edition No Addenda, Code Cases 1361-1. & 1361.2 (b)
Applicable Edition of Section Xi Utilized for Repairs or Replacements-1989, No Ad, Code Cases None Identification of Components Repalred or Replaced. and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
A937 N/A 46-27 Replaced N/A CRD Assembly G.E.
7593A N/A Receipt # 105348 2005 Replacement N/A
. - I.
(8) CRD Capscrews Nova N/A 46-27 Replaced N/A (7) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 90242 2003 Replacement N/A C192 (1) CRD Capscrew Nova Ht. Trace Code NIA Receipt # 94495 2003 Replacement NIA H490 I
_I 7.
8.
9.
Description of Work Class 1 Replacement. * = Per N-5 Code Data Revort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure. 1035 osi Test Temp.
155 Deg. F Remarks CRD SN# 7593A was refurbished with documentation provided under Quality Recelpt # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# A937 under work order # 628889. " = Replacement CRD Code of Construction Is ASME Section Ill. 1971 Ed. S73 & W75 Ad. Reconciled to the orlalnal per PTEs PTE 88.013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section III. Class 1. 1986 Ed. No Ad. Reconciled to the original Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of AuthNzaton No.
-N/A Expiration Date N/A Slgnedr/
ISI Coordinator Date "g4Ze 0
dO
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of IllinoIs and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 inspe Signature National Board, State, Province, and Endorsements Date _
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way, Kenneth Square. PA.. 19348 Address Plant LaSalle County Nuclear Station no$n nrinA ct W.4.
.41v4lv
Sheet I
of I
Unit 2 2.
Name 2601 N. 2 1't Rd. Marseilles. II. 61341 (Address)
W.O. # 628891 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed he.
RA.1rnlr: - - - - - -r (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A 4.
5.
6.
Identification of System (RD) Control Rod Drive (a) Applicable Construction CodeASME Sect liI 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.No Ad, Code Cases None Identification of Comoonents Renalred or Reolaced. and Reolacement Comnonents Name of Name of Mfrs. Ser.
Nat'il Other Year Repaired ASME Code Component Mfr.
No.
Sd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
A8469 N/A 42-.39 Replaced N/A CRD Assembly G.E.
7904 N/A Receipt # 105348 2005 Replacement N/A I
I I
(8) CRD Capscrews Nova I
N/A 42-39 Replaced N/A (8) CRD Capscrews Nova Ht. Trace Code NIA Receipt # 102444 2004 Replacement N/A R 139 7.
8.
9.
Description of Work Class I Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I
Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 DsI Test Temp.
155 Deg. F Remarks CRD SN# 7904 was refurbished with documentation provided under Quality Recelit # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# A8469 under work order # 628891. ** = Replacement CRD Code of Construction Is ASME Section 111. 1971 Ed. S73 & W75 Ad. Reconciled to the original ver PTEs PTE 88.013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section lil. Class 1. 1986 Ed. No Ad. Reconciled to the original Code of Construction Der PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorl lon No.
N/A Expiration Date N/A Rmnned II oordinatfr Date ago 9'n
/°.0 Owner or Owner's Designee, Title
, - - 7_
CERTIFICATE OF INSERVICE INSPECTION I, Theundersigned, holding a valid commission issuedby the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 andstate thattothe best of my knowledgeand belief, theOwner has performed examinationsand taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
A 7 PI 7A I
<Commissions IL 1927 Ins 4qftor's Signature Date
/
2005 National Board, State, Province, and Endorsements
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square, PA.. 19348 Address Plant LaSalle County Nuclear Station nn#.
nW1n2Inc 2.
Name 2601 N. 21" Rd. Marseilles. II. 61341 (Address)
Sheet 1
of I
Unit 2 W.O. # 628893 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed by Id~tilr+l^^n^^-vto Mechanical Maintenance (Name)
Mechanical Maintenance (Address) lor% cotO-rv^l nov Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date NIA 4.
5.
6.
5tJ* luv dl%
l US...I-*
-.11 tla
.jI I ve (a) Applicable Construction Code._ASME Sect liI 19 71 EditIon No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None Identification of Components Repalred or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
8711 NIA 38-51 Replaced NIA CRD Assembly G.E.
A1056 NIA Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova NIA 38-51 Replaced NIA (8) CRD Capscrews Nova Ht. Trace Code NIA Receipt # 102444 2004 Replacement N/A R139 7.
8.
9.
Description of Work Class 1 Replacement. I = Per N-5 Code Data Recort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 psi TestTemp.
155 Deg.F Remarks CRD SN# Al 056 was refurbished with documentation provided under Quality Recelnt # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 8711 under work order # 628893. *- = Replacement CRD Code of Construction Is ASME Section fit. 1971 Ed. S73 & W75 Ad. Reconciled to the orialnal per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section 1II. Class 1. 1986 Ed. No Ad.
Reconciled to the orlainal Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authoation No.
NIA Expiration Date NIA Slnnund.
ISI Coordinatnr Date Aw'.4'ew
-?/
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
s 4 4w J ACommissions IL 1927 ector's Signature NationalBoard, State, Province, and Endorsements D a t.7 I JI 2 0 0 Date I'll -/
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section XI 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Sauare. PA.. 19348 Address Plant LaSalle County Nuclear Station Dato n3ninrn B
vol.7vlua Sheet I
of I
Unit 2 2.
Name 2601 N. 21" Rd. Marseliles. II. 61341 (Address)
W.O. # 628895 Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A 3.
Work Performed h..
MfiA-hnn -ln-n-a-ay,
,.U...,,a, ma,,,,U.,a,,at:
(Name)
Mechanical Maintenance (Address) 4.
5.
6.
Identification of System (RD) Control Rod Drive (a) Applicable Construction Code ASME Sect III 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None IdentificatIon of Components Repalred or Replaced. and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repalred ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
7076 N/A 30-03 Replaced N/A CRD Assembly G.E.
9538 N/A Receipt # 105348 2005 Replacement N/A (8) CRD Capscrews Nova N/A 30-03 Replaced N/A (8) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 102444 2004 Replacement N/A R139 I
8.
9.
Description of Work Class I Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic l__Ij Pneumatic II Normal Operating Pressure I X I Other Visual Pressure 1035 nsl TestTemp.
155 Deg.F Remarks CRD SN# 9538 was refurbished with documentation provided under Quality Receipt # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 7076 under work order #628895.
- = Replacement CRD Code of Construction Is ASME Section 111.1971 Ed. S73 & W75 Ad. Reconciled to the orllnal per PTEs PTE 88013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section lii. Class 1. 1986
_Ed. No Ad. Reconciled to the orialnal Code of Construction Per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Auth~lzatlon No.
NxA Expiration Date N/A nnol A'
a ISI Coordinator Date
/9D O.Z
, 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, Theundersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boiler Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R1O and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Am ICommissions IL 1927 Inspec s Signature National Board, State, Province, and Endorsements Date
/V y
<-2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the-Provisions of ASME Code Section Xi
- 1.
Owner Exelon Generation Comoinv (EGC) LLC Date 04118105 (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Sheet I
of 1
Address
- 2.
Plant LaSalle County Nuclear Station Unit 2 Name 2601 N. 21't Rd. Marseilles. II. 61341 W.O. # 628897 (Address)
Repair Organization, P.O. No., Job No., etc.
- 3.
Work Performed by Mechanical Maintenance Type Code Symbol Stamp N/A (Name)
Authorization No.
NIA Mechanical Maintenance Expiration Date N/A (Address)
- 4.
Identification of System r
-RD)
Control Rod Drive
- 5.
(a) Appilcable Construction CodeASME Sect Uil 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None
- 6.
Identification of Components Repalred or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Repiacement (Yes or No)
CRD Assembly G.E.
9411
-N/A 14-23 Replaced NIA CRD Assembly G.E.
9330 NIA Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova NIA 14-23 Replaced NIA (8) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 94495 2003 Replacement NIA H490
- 7.
Description of Work Class 1 Replacement.
= Per N-5 Code Data Regort on file at LaSalle County Station.
- 8.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osl Test Temp.
155 Deg. F
- 9.
Remarks CRD SN# 9330 was refurbished with documentation provided under Quality Recelit # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 9411 under work order # 628897.
= Replacement CRD Code of Construction Is ASME Section 1I1, 1971 Ed. S73 & W75 Ad. Reconciled to the original per PTEs PTE 88-13 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section lii. Class 1. 1986 Ed. No Ad. Reconciled to the orlalnal Code of Construction ver PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
NIA Expiration Date NIA Signed 6-2 IS!i Coordinator Date-7°A,4 e
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements ofthe ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner foranypersonal Injury or property damage or a loss of any kind arIsing from or connected with this Inspection.
/1r..dctifv 241X 024thZ~L Commissions IL 1927 Insp or's Signature National Board, State, Province, and Endorsements Date 2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Address Plant LaSalle County Nuclear Station Date 04/A8105 Sheet 1
of I
Unit 2 2.
Name 2601 N. 21" Rd. Marseilles. ii. 61341 (Address)
W.O. # 628898 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed h..
am-I-&lr~ -l
-nanr My IIv
- anI1a, IaIenac (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorlzatlon No.
NIA Expiration Date.
NIA 4.
5.
6.
rtanVl{Son+I^n of t
%w_+^
irnn% r ft-l
>^
A l
IUt:IILiIIdL;4IUII Vt QYbLCIII MfUI
%.UIILUVI 5VU IJIIVr (a) Applicable Construction Code._ASME Sect !II 19 71 Edition No Addenda, Code Cases 1361-1. & 1361.2 (b)
Applicable Edition of Sectlon Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None Identification of Components Renalred or Replaced, and Reolacement Comnonents Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
9436 N/A 10-31 Replaced N/A CRD Assembly G.E.
6696 N/A Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova N/A 10-31 Replaced N/A (8) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 102444 2004 Replacement NIA R1 39 7.
8.
9.
Description of Work Class I Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I
Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 psi TestTemp.
155 Deg.F Remarks CRD SN# 6696 was refurbished with documentation provided under Quality Recelpt # 105348 and (Applicable Manufacturer's Data Report to be Attached)
Installed as a reolacement for SN# 9436 underwork order #628898.
= Replacement CRD Code of Construction Is ASME Section 111.1971 Ed. S73 & W75 Ad. Reconciled to the orlainal per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section III. Class 1. 1986 Ed. No Ad. Reconciled to the original Code of Construction oer PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certfcof Auth rization No.
-Expiration Date N/A I n n a d e
" Os IRI ronrdninatnr Date
- I' e7C V 2nn0 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insy. & Ins. Co. of Connecticut have inspected the components described In this Owner's Report during the period 12R09 to L2R1110 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described Inthis Owner's Report in accordance withthe requirements ofthe ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described Inthis Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner foranypersonal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
.> - 014Commissions IL 1927 I
tor's Signature National Board, State, Province, and Endorsements Date_
2005
FORM NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI 1.
Owner Exelon Generation Companv (EGC) LLC Date.
"1519fl5
^w^wbvz (Name) 200 Exelon Way. Kennett Scuare. PA., 19348 2.
(Address)
Plant LaSalle County Station (Name) 2601 N. 21" Rd. Marseilles., I. 61341 Unit 2 Sheet 1
of 1
632225 Repair Organization, P.O. No., Job No., etc.
3.
(Address)
Work Performed by Mechanical Maintenance (Name)
Mechanical Maintenance (Address)-
Type Code Symbol Stamp NIA Authorization No.
N/A Expiration Date NIA 4.
5.
Identification of System (NBI Nuclear Boller (a) Applicable Construction Code Sect IiI 1968 Edition Winter 1970. Addenda, Code Cases 140146.1332-5.1420 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements-198, No Ad, Code Cases None
- 6.
Identilcatlon of Com )onents Repalred or Repl ced, anld Replacement omponents Name of Name of Mfrs. Ser.
Nat'l CRN Other Year Repaired ASME Code Component Mfr.
No.
Bd.
No.
Identi-Built
- Replaced, Stamped No.
Fication Replacement (Yes or No)
Reactor Pressure Chicago T-37 10 NIA 2B13-D003 1975 Repaired NlA Vessel Head Bridge &
Cladding Iron
- 7.
Description of Work Class 1 Reoalr by welding. Repaired cladding on Reactor Pressure too closure head.
- 8.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osI Test Temp. 155 Deg.F
- 9.
Remarks Repalred RPV head claddina damaged during Installation of O-Ring retainer clip design change.
(Applicable Manufacturer's Data Report to be Attached)
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Repair conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
NIA Expiration Date NIA Signed 66 ISI Coordinator Date May 12.
20 05 Owner or Owner's Designee, Title
- r.
_......a CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by Hartford Steam Boller Insp. & Ins. Co. Of Hartford. CT. have Inspected the components described In this Owner's Report during the period L2R09 to L2R1110 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, Neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this In ection.
_Commissions IL 1927 lnspect SiSgnyure, Date
//2"20 0S National Board, State, Province, and Endorsements
.'.;-'M'$
3 t'
>\\;...........
a @-..
@4};;.
- X t'72204 I'
- -i,.,-.FOllU 5N¢1A MANW(A Ml-FrPS' DATA nEPOnT FOR NUC EX VESSEi 1
- .,# t.- >4.;,>,So. -............-. J...,AltemsteFors for Siagle Cbumbher C'omtpletely Shop E rettnSeli O:K;xF t
-f-,
>12As required hs h
' i oWn h tSWk Iler Ituirt
- r~~~~~~~~~~~~~~~IN;
- .t.*.
- .*'-.8***!*4.-
~.-
' o-f 0-
-t
,- 'M-1.
Vert vh, l,e,,".
6 T-7 I,
NA Nd."--.*. -1 yeerobil-., '197-
--,-t
- i.
- l 1 :BL uft H.
Ys >X~l. C mplte Irie*¢ loo*allN f
ai
,i
- ;;D.>"O WDB ut
-N r
,-.x;i'*
,...-^
Sp X
illP s
iP AJ-1PJ datl e
'5 5
1 5:j~~~~coe outst*Dt;*
tt
" Shal: U prar_~
s
-1*
at.'^.-!
l.-'ic' scerao Psu'Veit gg1
'_8t..
F-0j'¢'.tt
-S33
- .,rR^t C8-B COMPit
- t^
LM 7¢9
~a-$0J;
_l**_~s-Ciaogin rnCsrsn tcet eod etr
- $b 9....
- t;¢t4
- -.
',............,-zbVf~~tstrtSs on tddsEbtso
.,est;.
trap....................................Ca"A.)@*..160" i
E> ;§,7;".>iX
_f*,*,{lW 9attanttkhttia -
a.Ys hi
.d 0
3 5
C.
-Topf'
!S r~;
X
- Ift (Itidat"li-e D*
W la-P
- 22 1
- 1/
0 V§e te a tt Z
f E8,-i*,s,._..,
jt b)BtHatford Mrada Aolar P 7-1/8,- Hartor-Z I
Conncive !1t S
JIMAs^^b t'*
.__.t",
~
S S',
^ E~~~~~~~~~s~~i !ti.
re ' 'ssovale hall.i-'WS'-"'"-@':" -:<-'">s'o 8%A: *2i t i*
r.,.
ti..
4 *t
~~~~~~~~o the- _l __ _t r losWe _. _*_1
._et ;_ '
B¢:-4*!..)
Z;
-i.
._Z._,
.".:_,",,,W.b
,,".__b.
,"t
~witt S
A, F;rS-t**
t li-.-*et@<^"
-~e A
t7~~~~
S,,
-2 Or,;>
2;@*..*-';t j
i1 nuijfctureA by CBS 20 Tulz pnSnheennessee; S{.,,
'-'l' r-2**manufactured fat General Ci ctricv~omllny for.Cosmslet ds; g- '"
- 3... ype Vertical. ;Vessel1T7.jWBo,,10 a.t19755
- w
's.1eX*
SS° y
)Tl;, hk.
,;-leRaLnf I
^
Xircula tion-
,2,"<w 11 z*l t - N r)
{
s 04 n.*.;.
s<',S .
o: - <',
aa:'w O
u s"
tla (N o'!
1 X
~
X '
v attL;,
- ac.(S$}.*s*-
.,2.0
- Wg 7
^ %<..... v ;. :.:Y ast Sr stC ",,-., -;r,,................-3; isid
!r W).
_y t
.R/
C
);
3 127.
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA. 19348 Address Plant LaSalle County Nuclear Station Name 2601 N. 215t Rd. Marseilles. II. 61341 (Address)
Date 03/31 nr a.w, vies wFvv 2.
Sheet I
of I
Unit 2 W.O. # 696096 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed I.W U-eh..ea nl Malnten&&e (Name)
Mechanical Maintenance Type Code Symbol Stamp N/A Authorization No.
NIA Expiration Date N/A 4.
S.
(Address)
Identification of System (RD) Control Rod Drive (a) Applicable Construction Code ASME Sect II 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None Identification of Comoonents Renalred or Renlaced. and Renlacement Comnonents 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
A8569 NIA 26-27 Replaced N/A CRD Assembly G.E.
9576 N/A Receipt # 105348 2005 Replacement N/A (8) CRD Capscrews Nova N/A 26-27 Replaced N/A (5) CRD Capscrews Nova Ht. Trace Code N/A Receipt #102444 2004 Replacement NIA
_F512 (3) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 72558 2001 Replacement N/A
_PK J
'I 8.
9.
Description of Work Class 1 Replacement * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I _ I Normal Operating Pressure I X I Other Visual Pressure 1035 usi Test Temp.
155 Deg. F Remarks CRD SN# 9576 was refurbished with documentation provided under Quality Receipt # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# A8569 under work order # 696096. * = Reniacement CRD Code of Construction Is ASME Section Ill. 1971 Ed. S73 & W75 Ad. Reconciled to the original eer PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Reolacement Capscrew Code of Construction Is ASME Section lil. Class 1.1986 Ed. No Ad. Reconciled to the orlalnal Code of Construction ner PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Reolacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
N/A Expiration Date NIA Signed _
ISI Coordinator Date
,'-W" e'5
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 Inspeor's Signature
-National Board, State, Province, and Endorsements Date J
2 2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section XI 1.
2.
3.
4.
S.
Owner Exelon Generation Companv (EGC) LLC (Name)-
200 Exelon Way. Kenneth Sauare. PA., 19348 Address Plant LaSalle County Nuclear Station Name 2601 N. 21s" Rd. Marseilles. II. 61341 (Address)
F Work Performed by Mechanical Maintenance I
Date 03131105 Sheet 1
of I
Unit 2 N.O. # 696097 Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorlzation No.
N/A Expiration Date N/A (Name)
Mechanical Maintenance E
(Address)
Identification of System
- (RD) Control Rod Drive (a) Applicable Construction CodeASME Sect liI 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None Identification of Comoonents Repalred or Replaced, and Replacement Components 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
8374 N/A 30-39 Replaced N/A CRD Assembly G.E.
9178 NIA Receipt # 105348 2005 Replacement N/A (8) CRD Capscrews Nova N/A 30-39 Replaced N/A (6) CRD Capscrews Nova Ht. Trace Code NIA Receipt # 90559 2003 Replacement N/A F512_
(2) CRD Capscrews Nova Ht. Trace Code NIA Receipt # 102444 2004 Replacement N/A SJH
- 7.
Description of Work Class I Replacement.
= Per N-5 Code Data Report on file at LaSalle County Station.
- 8.
Tests Conducted:
Hydrostatic I_
I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 5s1 Test Temp.
155 Deg. F
- 9.
Remarks CRD SN# 9178 was refurbished with documentation provided under Quality Receipt # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 8374 under work order # 696097.
= Replacement CRD Code of
- Construction Is ASME Section Ill. 1971 Ed. S73 & W75 Ad. Reconciled to the-orlilnal Per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section ill. Class 1.1986 Ed. No Ad. Reconciled to the orlainal Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
{repair or replacement)
Type Code Symbol Stamp NONE(
Certificate of Autho ation N).
N/A Expiration Date N/A Signed (...4
'ISI Coordinator Date
.4W'd 0%
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In'accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 Insi~r r's Signature National Board, State, Province, and Endorsements Date_
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
2.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Address Plant LaSalle County Nuclear Station Name 2601 N. 21" Rd. Marseilles. II. 61341 (Address)
Date 03131/05 Sheet 1
of 1
Unit 2 3.
Work Performed by_
Mechanical Maintenance Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
NIA Expiration Date NIA (Name)
Mechanical Maintenance (Address) 4.
5.
Identification of System (RD) Control Rod Drive (a) Applicable Construction Code._ASME Sect iII 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989 No Ad, Code Cases None Identifination of Comnonents Renalred or Renlaced. and Renlacement Comnonents Name of Name of Mfrs. Ser.
Nat'l Other Year Repalred ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
A8636 NIA 34-27 Replaced NIA CRD Assembly G.E.
7829 NIA Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova NIA 34-27 Replaced NIA (8) CRD Capscrews Nova Ht. Trace Code NIA Receipt # 102444 2004 Replacement NIA
_ _ _ _ _ _R I3 9_
8.
9.
Description of Work Class I Replacement. * = Per N-5 Code Data Revort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osi Test Temp.
155 Deg. F Remarks CRD SN# 7829 was refurbished with documentation orovided under Quality Recelit # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# A8636 under work order # 696098. ** = Replacement CRD Code of Construction Is ASME Section ill. 1971 Ed. S73 & W75 Ad. Reconciled to the orialnal per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Reolacement Capscrew Code of Construction Is ASME Section lii. Class 1. 1986 Ed. No Ad. Reconciledtotheorlainal Code of-Construction oerPTE M91-007-0320-01 on file attaSalleStatlon.-.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorltlon No.
NIA Expiration Date NIA Slaned /i-47
/
ISI Coordinator Date 7f7f'ele 02
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owners Report during the period
_L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable Inany manner foranypersonal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
u
'z Commissions IL 1927 l&
ctor's Signature National Board, State, Province, and Endorsements Date _
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Address Plant LaSalle County Nuclear Station Name 2601 N. 21" Rd. Marseilles: II. 61341 (Address)
Date 04/14/05 2.
Sheet 1
of I
Unit 2 WA
- #6qr60qq Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A 3.
Work Performed ITV Mechanical Mlntnfannna (Name) -
Mechanical Maintenance (Address)
Expiration Date N/A 4.
5.
Identification of System (RD) Control Rod Drive (a) Applicable Construction Code.ASME Sect III 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases None Identific-ation of Comnonents Renaired or Rerlaced-and Reniacement Comnanents 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Bulit Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
8525 NIA 14-27 Replaced N/A CRD Assembly G.E.
9384 N/A Receipt # 105348 2005 Replacement N/A (8) CRD Capscrews Nova N/A 14-27 Replaced N/A (8) CRD Capscrews Nova Ht.Trace NIA Receipt # 102444 2004 Replacement N/A R13*
7.
8.
9.
Description of Work Class 1 Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I - I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 psi TestTemp.
155 Deg.F Remarks CRD SN# 9384 was refurbished with documentation provided under Quality Recelit # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 8525 under work order # 696099. *- = Replacement CRD Code of Construction Is ASME Section 111.1971 Ed. S73 & W75 Ad. Reconciled to the original per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section lii. Class 1. 1986 Ed. No Ad. Reconciled to the original Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Auth Sation No.
N/A Expiration Date NIA Signed g
ISI Coordinator Date
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2RIO and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner foranypersonal injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 Insp gnature National Board, State, Province, and Endorsements Date 2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Company 1EGC) LIC Date 04114105 (Name) 200 Exelon Wav. Kenneth Sauare. PA.. 19348 Address Plant LaSalle County Nuclear Station Sheet 1
of I
Unit 2 2.
Name 2601 N. 2 1"t Rd. Marseilles. 1i. 61341 W.O. # 696100 (Address)
Repair Organization, P.O. No., Job No., etc.
3.
Work Performed h-M22h-lr - - - - -nt My
,,,C,,*O e,,
S.O, *
.... cra....c ~
(Name)
Mechanical Maintenance Type Code Symbol Stamp NIA Authorization No.
5.
6.
(Address)
Identification of System IRD) Control Rod Drive (a) Applicable Construction Code ASME Sect !II 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989 No Ad, Code Cases None Identification of Components Repalred or Replaced. and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
CRD Assembly G.E.
A920 NIA 50-19 Replaced N/A CRD Assembly G.E.
9546 NIA Receipt # 105348 2005 Replacement NIA (8) CRD Capscrews Nova NIA 50-19 Replaced NIA (8) CRD Capscrews Nova Ht. Trace Code NIA Receipt # 102444 2004 Replacement NIA R I 39 7.
8.
9.
Description of Work Class I Replacement. * = Per N-5 Code Data Renort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 1035 osl Test Temp. _155 Deg. F Remarks CRD SN# 9546 was refurbished with documentation provided under Quality Receipt # 105348 and (Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# A920 under work order # 696100.
= Replacement CRD Code of Construction Is ASME Section liI. 1971 Ed. S73 & W75 Ad. Reconciled to the original per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section liI. Class 1. 1986 Ed. No Ad. Reconciled to the original Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
NIA Expiration Date NIA SIgned Z
/
ISI CnnrdInator Damte
-7&oei
/5
- 2n00 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described in this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In 'accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 Infector's Signature National Board, State, Province, and Endorsements Date
/
/D 2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi
- 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Address
- 2.
Plant LaSalle County Nuclear Station Name 2601 N. 21' Rd. Marseilles. II. 61341 Address Date 05/23105 Sheet I
of I
Unit 2
W.O. #78136R Repair Organization, P.O. No., Job No., etc.
3.
4.
5.
6.
Work Performed by Idantificafinn of Avsefm Mechanical Maintenance (Name)
Mechanical Maintenance Type Code Symbol Stamp N/A Authorization No.
N/A Exniratlon Date NIA (Address)
(HP) Hich Pressure Core Sorav
,W,,,,,,9s,.w..
V-
-cog"'_
(a) Applicable Construction Code Sect lii 19 74 Edition No Addenda, Code Cases NO (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19 89. No Ad, Code Cases N416-2 Identification of Comoonents Renalred or Replaced. and Renlacement Comoonents Name of Name of Mfrs.
Nat'l Other Year Repaired ASME Code Component Mfr.
Ser.
Bd.
Identification Built Replaced, or Stamped No.
No.
Replacement (Yes or No)
(1)-1.5" Inlet x 0.75" N/A 2E22-F3471F348 Replaced N/A outlet dia. C.S. Double Block Valve -
(1)-1.5" x 0.75" dia.
Consolidated Ht. Code N/A Receipt # 105931 2005 1 Replacement N/A C.S. Reducing Insert Power AZZ I
I 8.
9.
Description of Work: Class I Replacement. * = Per N-5 Code Data Revort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I X I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure 105411035 psI Test Temp.
751155 Deg.7F Remarks: ^^ Reolaced existing 1.5" X 0.75" dia. carbon steel double block valves with two (2) single 0.75" dia.
(Applicable Manufacturer's Data Report to be Attached )
carbon steel lobe valves. A new 1.5" x 0.75" dia. reducing Insert was Installed In order to reduce down the line for the new 0.75" dia. globe valves and associated plping. Reolacement is per engineering chanae EC #353832.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Autorization No.
N/A Expiration Date N/A Signed
,.Z ISI Coordinator Date
. 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have inspected the components described in this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
- t.
Commissions IL 1927 Inspotor's Signature National Board, State, Province, and Endorsements Date
<CA'/A 2005 K..>
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Company (EGC) LLC (Name) 200 Exelon Way. Kenneth Square, PA.. 19348 Address Plant LaSalle County Nuclear Station Date 05/05105 Sheet I
of 1
Unit 2 2.
Name 2601 N. 21*t Rd. Marseilles, II. 61341 (Address)
W.O. # 782779 3.
Work Performed I...
MaAha1-6u
- - -l -n-n-Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date NIA (Name)
Mechanical Maintenance (Address) 4.
5.
6.
Irlnt~a1^nofCvan
- r0n cnr2-4no nrli (a) Appiicable Construction Code._ASME Sect iII 19 71 Edition No Addenda, Code Cases 1361-1. & 1361-2 (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989, No Ad, Code Cases None Identification of Comnonents Repalred or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
I
_IReplacement (Yes or No)
CRD Assembly G.E.
9282 NIA 22-59 Replaced N/A CRD Assembly G.E.
7472 N/A Receipt # 105348 2005 Replacement N/A (8) CRD Capscrews Nova NIA 22-59 Replaced NIA (4) CRD Capscrews Nova Ht. Trace Code N/A Receipt # 90242 2003 Replacement NIA
_ _ _C 4 7 5 (3) CRD Capscrews Nova Ht. Trace Cod N/A Receipt # 69749 2001 Replacement NIA (1)_
C 4 7 5 2c (1) CR0 Capscrews Nova Ht. Trace Code N/A Receipt # 94495 2004 Replacement NIA I__
I__
H 490 I*
7.
S.
Description of Work Class 1 Replacement. * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic II Normal Operating Pressure I X I Other Visual Pressure 1035 esl TestTemp.
155 Deg.F Remarks CRD SN# 7472 was refurbished with documentation provided under Quality Receipt # 105348 and 9.
(Applicable Manufacturer's Data Report to be Attached )
Installed as a replacement for SN# 9282 under work order # 782779.
= Replacement CRD Code of Construction is ASME Section Ill. 1971 Ed. S3 & W75 Ad. Reconciled to the original per PTEs PTE 88-013 & PTE 88-396 on file at LaSalle Station. Replacement Capscrew Code of Construction Is ASME Section III. Class 1. 1986 Ed. No Ad. Reconciled to the original Code of Construction per PTE M91-007-0320-01 on file at LaSalle Station.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xi.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate oh.utpation Nod N/A Expiration Date N/A Sinned F
IRIt rnrdinatnr Date A.d-.
- 200fs5 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boiler lnsp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period 12R09 to
- L2R1O10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind a Ing from or connected with this Inspection.
i Z.
Commissions IL 1927 Insp516r's Signature National Board, State, Province, and Endorsements Date
.* 5-
//
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section XI 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Date 05119105 Address Plant LaSalle County Nuclear Station Sheet I
of 1
Unit 2 2.
Name 2601 N. 21' Rd. Marseilles. II. 61341 (Address) 3.
Work Performed by_
Mechanical Maintenance W.O. # 789955 Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
NIA Expiration Date N/A (Name)
Mechanical Maintenance (Address) 4.
S.
Identification of System (MS) Main Steam (a) Applicable Construction Code ASME Sect ilI 19 74 Edition No Addenda, Code Cases None (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989.
No Ad, Code Cases N-416-2 Identification of Components Repaired or Replaced, and Replacement Components 7.
B.
9.
Description of Work Class I Repair
= Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I_ I Normal Operating Pressure I X I Other Visual Pressure 1047.5 osi Test Temp.
166 Deg. F Remarks: Aweld between Main Steam Isolation Valve 2B21-F028D and its drain line 2MS20AD-2" was reoaired (Applicable Manufacturer's Data Report to be Attached) under work order # 789955 Per Enalneerina Chanae # 354418. The repair was conducted due to a pinhole leak observed on the weld during the conduct of ASME Class 1 Reactor Coolant Pressure Boundary System Leakage test. A non-destructive examination (NDE) was not performed on the Post Weld Heat Treatment (PWHT) thermocouple removal areas. as required by code. Action Trackina Item # 314183-03 Is tracking comnletlon of this NDE for Work Order # 789955. The repaired weld successfully passed the required pressure testing.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Renair of the ASME Code,Section XI.
(repair or re Type pda.Symbof Stamp If NONE placement)
- conforms to the rules Date N/A Date 57.0
. 2005 111 rJlr¢Stul CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R1O10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kin isin from or onneed wlt his spection.
mCommissions IL 1927 in9 ctor's S[ature National Board, State, Province, and Endorsements Date 7 a
/d a/
2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
Owner Exelon Generation Companv (EGC) LLC nla#.
nlgzy') mA v.
F<L1 UIO.-
(Name) 200 Exelon Wav. Kenneth Sauare. PA.. 19348 Address Plant LaSalle County Nuclear Station Sheet 1
of I
Unit 2 2.
Name 2601 N. 211 Rd. Marseilles. II. 61341 (Address)
W.O. # 421977 Repair Organization, P.O. No., Job No., etc.
3.
IAI-A, 13arf-4ar h
MRrhnlrl
- -ln -n - -r-vv ore rt7 GC l Ilt' Uy Il'~dlUll 7
IN l.a M
I IC 1t' (Name)
Mechanical Maintenance Type Code Symbol Stamp N/A Authorization No.
NIA Expiration Date N/A 4.
5.
6.
(Address)
Identification of System (E21) Low Pressure Core Spray (a) Applicable Construction CodeASME Sect. III 19 71 Edition S73 Addenda, Code Cases None (b)
Applicable Edition of Section Xi Utilized for Repairs or Replacements-1989, No Ad. Code Cases None Identification of Components Repalred or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Water Leg Crane Deming NDC000997 N/A 2E21-C002 Replaced N/A Pump Crane
___NM_1 R
a n
Water Leg Crane Deming NDC002130 N/A 2E21-CO02 1974 Replacement N/A P um p I
_I__
_I I__
_I__
I
_I___I 7.
8.
Description of Work: Class 2 Replacement * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic II Normal Operating Pressure I X I Other I I Pressure 67 isi Test Temp. Ambient Deg. F Remarks: Replaced Water Lea Pump with refurbuished spare pump.
(Applicable Manufacturer's Data Report to be Attached )
9.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE CertIficateof Oorization No.
N/A Expiration Date Signed 5
ISI Coordinator Date May 19
_conforms to the rules N/A
.2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner forany personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Commissions IL 1927 4Igator's Signature National Board, State, Province, and Endorsements Date V
'2/7 2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xl 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Sguare. PA., 19348 Address Plant LaSalle County Nuclear Station Date 02127/04 Sheet 1
of I
Unit 2 2.
Name 2601 N. 21" Rd. Marseliles. II. 61341 (Address) 3.
Work Performed by_
Mechanical Maintenance W.O. # 437834 /437835 Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A (Name)
Mechanical Maintenance 4.
5.
A (Address)
Identification of System (RI) Reactor Core isolation Coolant (a) Applicable Constructlon Code._ASME Sect. 1111974 Edition No Addenda, Code Cases None (b)
Applicable Edition of Section Xl Utilized for Repalrs or Replacements-1989, No Ad. Cde Cases None IdAntifiaftinn of onmnnnante Rpialred or Rpnlaepd-and Rrielarment Comnonantn Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
(2). 6 "- Std.-V-N/A 2E51-D001 and Replaced N/A R (ILI) Rupture 2E51 -0002 Disc (2)- 6 "- Std.-V-Continental 8018239A N/A Receipt # 90296 2003 Replacement N/A R (LL) Rupture Disc Corp.
D isc I__
I__
7.
8.
Description of Work: Class 2 Replacement * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I-.
Pneumatic I _I Normal Operating Pressure L X I Other Visual Pressure 10 psl Test Temp. AMbient Deg. F Remarks: Replaced rupture discs every five years with new. Reolacement oer Desian Soeclflcation J-2530 and T-3763. Code Reconciliation ner Eval. L-1996-76-2. on file at LaSalle County Nuclear Station.
(Applicable Manufacturer's Data Report to be Attached )
9.
CERTIFICATION OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificats-f Authorization No.
N/A Expiration Date N/A SUe Ko CoA Dt Signed 1SI Coordinator Date 2,6'.
.27
. 20 111/
e
(/tYiwner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Insy. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
&7 Z
&2.!
-<14 h Commissions IL 1927 Inspecto Y Signature National Board, State, Province, and Endorsements Date eZ-2.
2004
90296 FORM NR-I MANUFACTURERS' DATA REPORT OF RUPTURE DISCS As roquid by the pomof the ASME Code Rulks
<, w.
e
- 1. Ma.ficturod by 4
.s Cagneal Disc CoM2M - L&M Mo 64063 Name and addo of Manuhacare
-)ENTJ1CATION OF RLYTURE DISC
- 2. Manufiwas Type ar Sqle No.
STIV)R (U)
Scrial No.
MFG 3013239
- 3. Disc Diensial Ch
- acrisic:
Inlet Size 6-stla Size 6
Relief Area
- 2.
SO. IN.
- 4. MaIerial Speoficatsm ONCE DI SC, INE VACUUM "PORT.
NICKEL RMNG
- 5. MNanufacnws Drawing No.
SC12454 AUTHORZATUON TEST RESULTS
- 6. BhsI'Presswer 143 147 Min.
(i)
(psi)
A
- 7. Coinident Disc Tea~cr e S.
ld Uxsed in Tess._
- 9. CQdac Test Rmsts (if rqWaW 400 F Air None CER1KTI
- 10. Place-of Test.
Continentl DicCerpAan.
.Ie cmseiTe Man9 2003 We ceriify the above data to b ca. ad ofibc m
c ASME Col rules hm been mmt.
Sig& C entl DscCc C
Ma 14.2003 Daror o(Qwds% Asrance 0l2m)
T(is~O_
bu cm 2be.iW S
Opgr DqII. ASeE. 3s U 475 S. Nca Ys9 N.Y. 10017
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section XI
- 1.
Owner Exelon Generation Companv (EGC) LLC Daito n12M-11ns (Name) 200 Exelon Wav. Kenneth Sauare. PA.. 19348 Address
- 2.
Plant LaSalle County Nuclear Station Name 2601 N. 21" Rd. Marseilles, II. 61341 Address Sheet 1
of.
1 Unit 2
W.O. #541468
-2 Wnl-A Porfnrrn.
h-ILA-h-nl-RA.M1.
Repair Organization, P.O. No., Job No., etc.
Type Code Symbol Stamp NIA Authorization No.
- o.
arsr Pro r (Name)
Mechanical Maintenance (Address) 4.
5.
Identification of System (C41) Standby Liquld Control (a)
Applicable Construction Code Sect III 19 74 Edition No Addenda, Code Cases None (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19_89, No Ad. Code Cases N.416-2 Identification of Components Repaired or Replaced, and Replacement Components I
7.
8.
9.
Description of Work Class 2 Replacement. * = Per N-5 Code Data Renort on file at LaSalle County Station.
Tests Conducted:
Hydrostatic II Pneumatic I _ I Normal Operating Pressure I X I Other Visual Pressure 1222 J
sl Test Temp. Ambient Deg.F Remarks Replaced existing valve and plenga spool. Reolacement valve Is ASME Section lii. Class 2.1971 Ed..
(Applicable Manufacturer's Data Report to be Attached )
W1971 Addenda reconciled per Evaluation 36437 and the manufacturer.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement of the ASME Code,Section XI.
(repair or repla Type Code Symbol Stamp NONE conforms to the rules cement)
Certificate of Authorization No.
Signed
<z,'
1II A Frnraln at nr iirtu N/A ISI Coordinator Date Mav 20 2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the Stae or Province of Illinois -and employed by The Hartford Steam Boller Insp. 8 Ins. Co. of Connecticut have inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arlsin from or connected with this ins ection.
,Commisslons IL 1927 InspecQ Signature National Board, State, Province, and Endorsements Date J.' _
2005
FORM NPV-1 N CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*.
As Required by the Provisions of the ASME Code, Section IiI, Div. I Pg.Iof 2-
- 1.
Manufactured by Flowserve Corporation.
1900 S. Saunders St.,
Raleizh, NC 27603 (Name aM Adobes of N Ceificate Holder)
Manufactured for Exelon Company PO Box 805388 Chicaeo. IL 60680-5388 (Nam wn Address of Purclaser or Ower)
- 3.
Location of Installation LaSalle 2601 N. 21" Rd. Marseilles. IL 61341-9757
- 4.
Pump or Valve (a) Model No.
Series No.
or Type Valve (b) N Certificate Holder's SIrisl Nn
_Name and Add Nominal Inlet Size (c) Canadian Registration (e
No.
1-1i2" OWN Outlet Size 1-1n2" (uiCh) d) Drawing No.
(i) Natrl.
Bd. No.
(g) Year Built (e) Class (1) 1500N(1878Series) 44BBJ N/A 04-32037-01 Rev. A 2
N/A 2005 (2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(1 0)
- A SS6
- Q to I..
.0-I
- 5.
1-1/2"-1500# (1878 Series) Y-Globe Valve 6
7 8
(Bnie desCrits of sedvice for which equipMern was designed) reconciled to ASME Section III 1974 Editon No Addenda 32037 Design Conditions 2511 psi 680
°F or Valve Pressure Class 1500 (1)
(Pressure)
(Terperstrte)
Cold Working Pressure 3600 psi at 100 OF.
Pressure Retaining Pieces Mark No.
Material Spec. No.
Manufacturer Remarks (a) Castings N1543 SA351-CF8M Flowserve Body 21560 A747-CB7-CU1-H1100 Flowserve Disc (b) Forgings__
(1) For manually operated valves only Supplemental sheets in form of lists, sketches or drawings may be used provided (1) size is 8-1/2' x 11', (2) information in items 1. 2 and 5 on this Data Report is included on each sheet, and (3) each sheet Is numbered and number of sheets Is recorded at top of this form.
- Rn,l;ved By ze
,S-0
. P,
- ppr
~
Pt I A N I 14MN II
t-UKM NI"V-1 toacK) ru.su
^ u.
Valve SIN 44BBJ through *'*^
Mark No.
Material Spec. No.
Manufacturer Remarks
'(c) Bolting J%
~,.
(d) Other Parts
- 9.
Hydrostatic test 5400 psi.
Disk Differential test pressure 3960 psi.
CERTIFICATE OF COMPLIANCE We certify that the statements made In this report are correct and that this pump, or valve, to the rules of construction
'onforms 1971 t the ASME Code for Nuclear Power Plant Components.
Section III, Div. 1.,
Edition Addenda Winter 1971**
.Code Case No.
N/A Date 2-I{^OS Signed Flowserve by (N Cerifica3e Holder)
Our ASME Certificate of Authorization No.
N-1562 to use the N
symbol expires 11-26-06 IN)
(Date)
CERTIFICATION OF DESIGN Design Information on file at Flowserve Corporation Raleigh, NC Stress analysis report (Class I only) on file at Design specifications certified by (1)
D.C. Haan PE State IL Reg. No.
62-32917 Stress analysis certified by (1)
PE State Reg. No.
(1) Signature not required. List name only.
CERTIFICATE OF SHOP INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of North Carolina and employed by HSB CT of Hartford Connecticut have Inspected the pump, or valve, described In this Data Report on.
1 1 6 5 and state that, to the best of my knowledge and belief, the N Certificate Holder has constructed this pump, or valve, In accordance with ASME Code, Section IlIl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described In this s Data Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
Date Jl.L.I as He sq.
IQ v°OJ
? jned Commissions
.Ct/aP.N/
(Narl Ud.. State. Prov. and No.)
(W~podo&)
I
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi
- 1.
Owner Exelon Generation Comnanv (EGC) LIC (Name) 200 Exelon Way, Kenneth Square. PA., 19348 Address
- 2.
Plant LaSalle County Nuclear Station Date 05/26105 Sheet I
of I
Unit 2
W.O. # 552479 Name 2601 N. 21t Rd. Marseilles. II. 61341 Address Repair Organization, P.O. No., Job No., etc.
3.
Work Performed h-MU1n-n1e-MRnAnfnna..
(Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A 4.
5.
Identification of System (MS) Main Steam (a) Applicable Construction Code B31.1 19 73 Editlon S/74 Addenda, Code Cases NO (b)
Applicable Edition of Section Xl Utilized for Repairs or Replacements-19 89, No Ad, Code Cases None Identifli-atlnn nf onmnnnnents Renalred or Renlaced-and Renlacement Cnmnonentn Name of Name of Mfrs.
Nat'l Other Year Repaired ASME Code Component Mfr.
Ser.
Bd.
Identification Built Replaced, or Stamped No.
No.
Replacement (Yes or No)
%' dia. Ext. Pipe N/A N/A N/A 2MS28-2804X NIA Replaced No
%' dia. Ext. Pipe N/A N/A N/A CID 34672 2005 Replacement No (2) ea. Adapter Assy.
NIA N/A N/A 2MS28-2804X N/A Replaced No (2) ea. Adapter Assy.
N/A N/A N/A CID 46874 2005 Replacement No (1) ea. Pipe Clamp N/A N/A 2MS28-2804X N/A Replaced No (1) ea. 4"dia. Pipe Clamp N/A N/A CID 251801 2005 Replacement No 7.
8.
9.
Description of Work: Class D+ (Cl. 2) Replacement (Non-Safety Related)
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I I Other I Visual I Pressure N/A osi Test Temp.
N/A Deg.F Remarks: - Replaced parts of an existing strut 2MS28-2084X per W.O. # 552479. A VT-3 visual examination was (Applicable Manufacturer's Data Report to be Attached )
performed after the replacement. Strut had no defect. Strut extension pipe was removed and replaced with a lonaer one durina valve 2B21-F072 replacement. Also. during the replacement, the strut adapter assemblies and
- vloe clamp were replaced.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this F
of the ASME Code, Section Xl.
(rer Type Code Symbol Stamp NONE Certificate of Auth zation No.
N/A Expiration Date _
Sinned g
Date
_ine
/
.S Coriao Date __._
Reolacement conforms iair or replacement) to the rules N/A 3
2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller lnsy. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R1O10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty,expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind gfrom or connected with th s in pection.
fCommissions IL 1927 Insp y5r's Signature National Board, State, Province, and Endorsements Date v
16
-2005
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
2.
Owner Exelon Generation ComDanv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square, PA., 19348 Address Plant LaSalle County Nuclear Station Name 2601 N. 21" Rd. Marseilles. II. 61341 (Address)
Dfa u.9 v_^w_^v_
Sheet 1
of 1
Unit 2 W.On N 5R2162 039nain0 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed I:bv Merhanical MalntAn2naea (Name).
Mechanical Maintenance Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A (Address) 4.
5.
Identification of System (RH) Residual Heat Removal (a) Applicable Construction CodeASME Sect. III 19 71 Edition W72. Addenda, Code Cases None (b)
Applicable Editlon of Section Xl Utlized for Repairs or Replacements-1989.
No Ad. Code Cases None Identification of Comnonents Renaired or Renlaced. and Renlacement Comoonents 6.
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped l
No.
Replacement (Yes or No) 8" Check Valve Anchor Darling N/A 2E12+F046A Repaired N/A Bonnet l
1 I
I=
7.
B.
Description of Work: Class 2 Repair Repaired valve bonnet by welding.
Tests Conducted:
Hydrostatic IIJ Pneumatic IlI Normal Operating Pressure II Other Visual Pressure psi Test Temp.
Deg. F Remarks: ^ = Per N-5 Code Data Report on file at LaSalle County Station.
(Applicable Manufacturer's Data Report to be Attached )
9.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Repair of the ASME Code, Section Xl.
(repair or repl Type Code Symbol Stamp NONE Certificate of Au horization No.
N/A Expiration Date ned l
ISI Coordinator Date conforms to the rules acement)
N/A 0e40O
. 2005 Sima 6W ;%rner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Ililnois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R1O0 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
t us iCommissions IL 1927 1 6ector's Signature National Board, State, Province, and Endorsements vary A,
,V-i
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section Xi 1.
Owner Exelon Generation Company (EGC) LIC (Name) 200 Exelon Way. Kenneth Square, PA., 19348 Address Plant - LaSalle County Nuclear Station Name 2601 N. 2l' Rd. Marseilles. II. 61341 (Address)
Data 03109105 w.9 v</vvlvv 2.
Sheet 1
of 1
Unit 2 W.O. # 582163 Repair Organization, P.O. No., Job No., etc.
3.
%Ai..l flt....J L...
222-n
-a -r^ -~rnrro Wv L0u5 Ire n
jui ii,uu Ly fIV.cU11id,..
Md1i ma.. iul (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorization No.
5.
6.
Identification of System 1RH) Residual Heat Removal (a) Applicable Construction CodeASME Sect. III 19 71 Edition W72. Addenda, Code Cases None (b)
Appilcable Editon of Section Xl Utilized for Repairs or Replacements-1989 No Ad. Code Cases None IdentIfication of Components Reoalred or Replaced, and Reolacement Components Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement f(Yes or No) 8" Check Valve Anchor Daring l NIA 2E12-F046B1 Repaired NIA Bonnet I~
I=
7.
8.
Description of Work: Class 2 Repair Renaired valve bonnet by welding.
Tests Conducted:
Hydrostatic I j Pneumatic I I Normal Operating Pressure II Other Visual Pressure Dsl Test Temp.
Deg. F Remarks: * = Per N-5 Code Data Renort on file at LaSalle County Station.
(Applicable Manufacturer's Data Report to be Attached) 9.
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Repair of the ASME Code, Section Xl.
(repair or repl Type Code Symbol Stamp NONE Certificate of Authorizatlon No.
NIA Expiration Date Signed Sii g
C Coordinator Date Zwder or Owner's Designee, Title conforms to the rules lacement)
NIA a5 2d 7. 2005 CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the NatIonal Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller lnsp. & Ins. Co. of Connecticut have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
lb,, /1 / -7wl
-: Commissions IL 1927 Inspepo1's Signature National Board, State, Province, and Endorsements Date,9-2005
FORM NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xl 1.
2.
3.
Ownar FYvlnn Ganaratinn tCnmnanv IEG)
I I (L Date 2/23/05 (Name) 200 Exelon Way, Kennett Square. PA.. 19348 Sheet I
of I
(Address)
Plant LaSalle County Station Unit 2 00668477 (Name) 2601 N. 21" Rd. Marseilles. II. 61341 (Address)
Work Performed by Mechanical Maintenance (Name)
Mechanical Maintenance (Address)
Repair Organization, P.O.No., Job No., etc.
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A 4.
5.
Identification of System (RH) Residual Heat Removal (a) Applicable Construction Code Sect IIl 1968 Edition June 70. Addenda, Code Cases 1332-5 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements-1989 o Ad, Code Cases None
- 6.
Identification of Com onents Kepalreo or Keplaced, ana Replacement Components Name of Name of Mfrs. Ser.
Nat'l CRN Other Year Repaired ASME Code Component Mfr.
No.
Bd.
No.
Identi-Built
- Replaced, Stamped No.
Fication Replacement (Yes or No)
RH Heat Struthers N/A N/A 2E12-B001A Repaired N/A Exchanger Wells Corp.
(8) Tube Plugs Ecker-Ht # 233868 N/A N/A Receipt
- 2002 Repaired N/A Erhardt 92748
- 7.
Description of Work Class 2 Renalr.
Repaired Heat Exchanaer bv Tube Pluanina.
- 8.
Tests Conducted:
Hydrostatic II Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure _psi Test Temp. _
Deg. F
- 9.
Remarks * = Per N-5 Code Data Report on file at LaSalle County Station. Plugged four U-Tubes by Welding.
(Applicable Manufacturers Data Report to be Attached)
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Repair conforms to the rules of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authoriz on No.
N/A Expiration Date N/A S1gne ISI Coordinator Date March 10.
20 05 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Ilinois and employed by Hartford Steam Boller Insp. & Ins. Co. Of Hartford. CT. have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this owners Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, Neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
i7 /4 HJ 7-Commissions IL 1927 Iector's Signature
_q -
/-7 20 05 National Board, State, Province, and Endorsements Date K2
FORM NIS-2 OWNER'S REPORT OF REPAIRS OR REPLACEMENTS As Required by the Provisions of ASME Code Section XI 1.
Owner Exelon Generation Companv (EGC) LLC (Name) 200 Exelon Way. Kenneth Square. PA.. 19348 Address Plant LaSalle County Nuclear Station Date 0A4/18i/0 Sheet I
of I
Unit 2 2.
Name 2601 N. 21.
Rd. Marseilles. _..61341 (Address)
W.O. # 677752 Repair Organization, P.O. No., Job No., etc.
3.
Work Performed by Ir~nt^^alx of-C8+
Ill allc.dll l
MO ILVe (Name)
Mechanical Maintenance Type Code Symbol Stamp NIA Authorization No.
N/A Expiration Date N/A (Address)
ME51 4.
5.
6.
(a) Applicable Construction CodeASME Sect. III 19 71 Edition S73 Addenda, Code Cases None (b)
Applicable Edition of Section Xl Utilized for Repairs orReplacements-1989 No Ad, Code Cases None Identification of Comoonents Reoalred or Replaced, and Replacement Comoonents Name of Name of Mfrs. Ser..
Nat'l Other Year Repaired ASME Code Component Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
(1) 1.25" dia.
Rockwell N/A 2E51-F028 Replaced N/A Disc International (1) 1.25" dia.
Edward Vogt 139362-N/A Receipt # 103019 2000 Replacement N/A Disc Valve Co.
1897-2 1
1 1
1 1
7.
8.
Description of Work: Class 2 Replacement * = Per N-5 Code Data Report on file at LaSalle County Station.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I I
Other LLRT Pressure per TS-I00-38 psi Test Temp. Ambient Deg. F Remarks: Replaced valve disc like for like.
9.
(Applicable Manufacturer's Data Report to be Attached )
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Replacement of the ASME Code, Section Xl.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Auth tion No.
N/A Expiration Date Sinned A
ISI Coordinator Date conforms to the rules NIA of
.2005 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinois and employed by The Hartford Steam Boller Inso. & Ins. Co. of Connecticut have Inspected the components described in this Owner's Report during the period L2R09 to L2R1O10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
%?PA/
ZI/ t' Commissions IL 1927 Inspftor's Signature National Board, State, Province, and Endorsements Date 4
2005
FORM NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xl 1.
Nwn~
g olaz Nnn-slxnr^^u
{oe-d I I ^
n.t-Owner_
vxelonllUeNeratll
%nvigmdanv aruL-ua
%UZMU t51UDv (Name) 200 Exelon WaV. Kennett Square.
PA., 19348 2.
(Address)
Plant LaSalle County Station (Name) 2601 N. 2 1 "t Rd. Marseilles. II. 61341 Sheet 1
of I
781039 Unit 2 Repair Organization, P.O. No., Job No., etc.
3.
(Address)
Work Performed by Mechanical Maintenance (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorization No.
NIA Expiration Date N/A 4.
5.
Identification of System (RH) Residual Heat Removal (a) Applicable Construction Code Sect liI 1974 Edition No_,
Addenda, Code Cases None (b) Appilcable Edition of Section XI Utilized for Repairs or Replacements-1989 No Ad, Code Cases None
- 6.
Identification of Corn onents Repaired or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l CRN Other Year
- Repaired ASME Code Component Mfr.
No.
Bd.
No.
Identi-Built
- Replaced, Stamped No.
Fication Replacement (Yes or No) 16" RH Pipe B.F. Shaw NIA N/A 2RH4OCB.
Repaired N/A Spool 16"
- 7.
Description of Work Class 2 Renalr. Renalred magnetic oarticle Indications by grinding.
- 8.
Tests Conducted:
Hydrostatic I I Pneumatic I I Normal Operating Pressure I X I Other MT/UT Pressure _psl Test Temp.
Deg. F
- 9.
Remarks * = Per Original N-5 Code Data Reoort on file at LaSalle County Station.
(Applicable Manufacturer's Data Report to be Attached)
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Reoair conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
N/A Expiration Date NIA Signed c*
ISI Coordinator Date May 13 20 05 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, The undersigned, holding a valid commission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Illinols and employed by Hartford Steam Boller Ins3. & Ins. Co. Of Hartford CT. have Inspected the components described In this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this owner's Report In accordance with the requirements of the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, Neither the Inspector nor his employer shall be liable In any manner forany personal Injury or property damage or a loss of any kindsing from or connected wit
,i! _
- Commissions IL 1927 InDt0tor's Snature
/i~
20 05 National Board, State, Province, and Endorsements Date
FORM NIS-2 OWNER'S REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xl 1.
none,~~~~~~~~
eIr enlnrm~n e~
or14e i2A OwnerICI WcLuV
- eneraLIu I,ua.
{cede LLl&
ae LI* 1UJ (Name) 200 Exelon Way. Kennett Sauare. PA., 19348 2.
(Address)
Plant LaSalle County Station (Name) 2601 N. 21"' Rd. Marseilles. II. 61341 Sheet I
of 1
94060704 Unit 2 Repair Organization, P.O. No., Job No., etc.
3.
(Address)
Work Performed by Mechanical Maintenance (Name)
Mechanical Maintenance (Address)
Type Code Symbol Stamp N/A Authorization No.
N/A Expiration Date N/A 4.
5.
Identification of System (RH) Residual Heat Removal (a) Applicable Construction Code Sect III 1968 Edition March 1970. Addenda, Code Cases None (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements-1989, No Ad, Code Cases None U.
Identification of Com onents Kepaired or Replaced, and Replacement Components Name of Name of Mfrs. Ser.
Nat'l CRN Other Year Repaired ASME Code Component Mfr.
No.
Bd.
No.
Identi-Built
- Replaced, Stamped No.
Fication Replacement (Yes or No)
Pump Mechanical John Crane UTC #
N/A N/A 2E12-C002A 1995 Replaced NIA Seal 2016883 l
Gland Plate Ingersoll N/A N/A 2E12-C002A
=
Replacement N/A X
Rand
=
- 7.
Description of Work Class 2 Replacement. Installed original -land dlate on new renlacement seal.
- 8.
Tests Conducted:
Hydrostatic I-I Pneumatic I I Normal Operating Pressure I X I Other Visual Pressure _psi Test Temp. _
Deg. F
- 9.
Remarks * = Per Origlnal Desian Specification on file at LaSalle County Station.
(Applicable Manufacturer's Data Report to be Attached)
CERTIFICATION OF COMPLIANCE We certify that the statements made In the report are correct and this Renlacement conforms to the rules of the ASME Code,Section XI.
(repair or replacement)
Type Code Symbol Stamp NONE Certificate of Authorization No.
NIA Expiration Date NIA Signed _
K ISI Coordinator Date May 12.
20 05 Owner or Owner's Designee, Title ULKIINlUAIt Ul-IN KVI16r INCWMAIIUN I, The undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Ilinois and employed by Hartford Steam Boiler Insp. & Ins. Co. Of Hartford. CT. have Inspected the components described in this Owner's Report during the period L2R09 to L2R10 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this owner's Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, Neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Inspection.
/S? A!I I 2....
I I
Commissions IL 1927 Inspect4g Signature Date
_5I/3 20 05 National Board, State, Province, and Endorsements